ELECTRICAL DRAWING SET.pdf

PDF 20 MB Posted

Attached to
Z2AA - Renovate Historic Building 4 Federal contract opportunity
Solicitation number
36C24624R0030
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

This document is a Solicitation for the renovation of Historic Building 4 for administrative space and offices at a Department of Veterans Affairs facility. The project involves a complete renovation of the existing historic building, including upgrades to the mechanical, plumbing, electrical, and fire protection systems, as well as the addition of an elevator and code-compliant stairwells. Exterior renovations will be performed in compliance with National and State Historic Preservation Office (SHPO) requirements. The project is designated as Mission Critical and must meet VA Physical Security and Resiliency Design Manual (PSRDM) requirements. The solicitation requires the use of Revit and Building Information Modeling (BIM) at a minimum Level of Detail (LOD) 300, and the contractor shall provide a mobilization plan and other required plans prior to being allowed on site. Asbestos and lead abatement is also required, and the contractor shall relocate any existing underground utilities and installations. The solicitation number is 36C24624R0030, and the project is being managed by the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 6.

View the file

Other files for this federal contract opportunity

Other files attached to Z2AA - Renovate Historic Building 4, newest first.
File Type Posted
36C24625C0027_1 Award Notice.docx DOCX document
230923 Direct-Digital Control System Connect to Existing N4.pdf PDF
36C24624R0030 0006.pdf PDF
1_b H - Renovate Building 4 IFC pages 12-14.pdf PDF
1_a G - Renovate Building 4 IFC page 1.pdf PDF
Specification Section 00 01 15 - LIST OF DRAWING SHEETS 01 21 25.pdf PDF
2_C - L and S - Renovate Building 4 IFC pages 15-35.pdf PDF
4_FP and P - Renovate Building 4 IFC pages 86-109.pdf PDF
36C24624R0030 0005.docx DOCX document
INSTRUCTIONS CONDITIONS AND OTHER STATEMENTS TO BIDDERS-OFFERORS .docx DOCX document
Proposal Item I Cost Breakdown.xlsx XLSX spreadsheet
Fayetteville - Temp Fence.pdf PDF
230541 - NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.pdf PDF
230512 - GENERAL MOTOR REQUIREMENTS FOR HAVAC AND STEAM GENERATION EQUIPMENT.pdf PDF
014529 - TESTING LABORATORY SERVICES.pdf PDF
234000 - HVAC AIR CLEANING DEVICES.pdf PDF
232300 - REFRIGERANT PIPING.pdf PDF
Statement of Proposal Items - 0003.docx DOCX document
Building 4 and 16 LBP Results.pdf PDF
Asbestos Reinspection Report - August 2019.pdf PDF
230711 - HVAC AND BOILER PLANT INSULATION.pdf PDF
230511 - COMMON WORK RESULTS FOR HVAC.pdf PDF
233100 - HVAC DUCTS AND CASINGS.pdf PDF
237200 - AIR TO AIR ENERGY RECOVERY EQUIPMENT.pdf PDF
233700 - AIR OUTLETS AND INLETS.pdf PDF
Proposal Item V Cost Breakdown.xlsx XLSX spreadsheet
Asbestos - Lead Paint Survey 12-31-2020.pdf PDF
Geotech Report_Fayetteville Bldg 4 Renovation.pdf PDF
230593 - TESTING ADJUSTING AND BALANCING FOR HVAC.pdf PDF
238129 - VARIABLE REFRIGERANT FLOW HVAC SYSTEMS.pdf PDF
230923 - DIRECT DIGITAL CONTROL SYSTEMS FOR HVAC.pdf PDF
238143 - AIR SOURCE UNITARY HEAT PUMPS.pdf PDF
230800 - COMMISSIONING OF HVAC SYSTEMS.pdf PDF
36C24624R0030 0003.docx DOCX document
Proposal Item II Cost Breakdown.xlsx XLSX spreadsheet
Proposal Item III Cost Breakdown.xlsx XLSX spreadsheet
36C24624R0030 0002.docx DOCX document
11-19-2024 Site Visit Attendance.pdf PDF
36C24624R0030 0001.docx DOCX document
Statement of Work - Renovate Historic Building 4.pdf PDF
STRUCTRAL DRAWING SET.pdf PDF
ARCHITECTURAL DRAWING SET.pdf PDF
36C24624R0030_1.docx DOCX document
Specifications - Renovate Building 4 Issued For Construction.pdf PDF
Wage Determination.pdf PDF
PLUMBING DRAWING SET.pdf PDF
MECHANICAL DRAWING SET.pdf PDF
LANDSCAPE DRAWING SET.pdf PDF
FIRE PROTECTION DRAWING SET.pdf PDF
CIVIL DRAWING SET.pdf PDF
Show all 50

Z2AA - Renovate Historic Building 4 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C

E

FLEXIBLE CONDUIT CONNECTION

SUBSCRIPT: WP - WEATHERPROOF, GF - GROUND FAULT CIRCUIT

INTERRUPTER

FLUSH FLOOR MOUNTED NEMA 5-20 DUPLEX RECEPTACLE

UNLESS NOTED OTHERWISE

BASED ON MANUFACTURERS RECOMMENDATIONS

NEMA 5-20 DUPLEX RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE.

JUNCTION BOX

NON-FUSED DISCONNECT SWITCH. SIZE AS SHOWN

FUSED DISCONNECT SWITCH. SIZE FUSES FOR EQUIPMENT

SURFACE MOUNTED PANELBOARD OR AUTOMATIC TRANSFER

SWITCH AS INDICATED.

MOTOR

J

WP/GF

POWER

CONCEALED OR OPEN

UNDERGROUND

WIRINGLIGHTING

EXTERIOR SITE

FLUSH FLOOR MOUNTED NEMA 5-20 QUAD RECEPTACLE

UNLESS NOTED OTHERWISE

RECESSED MOUNTED PANELBOARD

RECEPTACLE, (NEMA CONFIGURATION AS NOTED)

GROUNDING

A AMPERE

AC ABOVE COUNTER, 42"AFF UNLESS OTHERWISE INDICATED

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR - TO BOTTOM

AL ALUMINUM

1/C ONE CONDUCTOR

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CU COPPER

EF EXHAUST FAN

EMT ELECTRICAL METALLIC TUBING

EWC ELECTRIC WATER COOLER

FACP FIRE ALARM CONTROL PANEL

FM FREQUENCY MODULATION

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

HACR HEATING AIR CONDITIONING REFRIGERATION

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HT HEIGHT

HZ HERTZ

IDS INTRUSION DETECTION SYSTEM

J JUNCTION BOX

KWH KILOWATT HOUR

LED LIGHT EMITTING DIODE

MCB MAIN CIRCUIT BREAKER

MH MOUNTING HEIGHT - TO CENTER

MLO MAIN LUGS ONLY

MTD MOUNTED

NEC NATIONAL ELECTRICAL CODE

NF NON FUSED

NO. NUMBER

OS OCCUPANCY SENSOR

PH PHASE

PIR PASSIVE INFRARED

RGS RIGID GALVANIZED STEEL

SM SINGLE MODE

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

SPD SURGE PROTECTIVE DEVICE

UNO UNLESS NOTED OTHERWISE

V VOLT

VA VOLTAMPERE

VVD VARIABLE VOLUME DAMPER

W WATTS

WP WEATHERPROOF

XFMR TRANSFORMER

ABBREVIATIONS

NEW PAD MOUNTED TRANSFORMER

EXISTING COMMUNICATIONS MANHOLE

NEW COMMUNICATIONS MANHOLE

EXISTING ITEMS TO BE REMOVED

EXISTING POLE MOUNTED LIGHTING FIXTURE

NEW POLE MOUNTED LIGHTING FIXTURE

EXISTING UNDERGROUND ELECTRICAL LINE.

EXISTING OVERHEAD ELECTRICAL LINE.

EXISTING UNDERGROUND COMMUNICATION LINE

EXISTING OVERHEAD COMMUNICATION LINE

EX

NEW ELECTRICAL HANDHOLE

NEW BOLLARD LIGHT FIXTURE.

E

EP

UP

EUC

EC

GRID COUNTERPOISE CONDUCTOR

LIGHTNING PROTECTION ROOF CONDUCTOR

CONNECTION TO GROUND

LIGHTNING PROTECTION DOWN CONDUCTOR

RC

DC

G

AIR TERMINAL

GROUNDING ROD

STATIC GROUNDING RECEPTACLE

UP

US

UC

NEW UNDERGROUND PRIMARY

NEW UNDERGROUND SECONDARY

NEW UNDERGROUND COMMUNICATIONS

EXISTING SECTIONALIZER CABINETS

T

H

M

M

FIRE ALARM

DATA/TELEPHONE

DATA/TELEPHONE OUTLET. PROVIDE (2) CAT 6a CABLES WITHIN

CONDUIT FROM OUTLET TO NEAREST IT CLOSET OR CABLE TRAY.

SUBSCRIPT INDICATES # OF DATA CABLES.

CARD READER

PANIC BUTTON

HANDICAP DOOR MOTOR

HANDICAP DOOR OPERATOR

ELECTRIC LATCH

SECURITY CAMERA CCTV - DOME

DURESS/PANIC ALARM

SECURITY / ACCESS CONTROL

PILOT LIGHT / CHIME

PUSHBUTTON

S SMOKE DETECTOR

F FIRE ALARM SPEAKER/STROBE

FIRE ALARM STROBE

F FIRE ALARM SENDING STATION

S R

FIRE ALARM CONTROL RELAY. C- CONTROL I-INPUT.

DUCT DETECTOR. "R" INDICATES RETURN DUCT. "S"

INDICATES SUPPLY DUCT.

AM

C a

OS

1' x 4' FIXTURE. UPPERCASE INDICATES TYPE PER THE FIXTURE SCHEDULE.

LOWER CASE LETTER "a" INDICATES SWITCH ZONE. "#" INDICATES CIRCUIT

NUMBER.

OS

LC#

2' x 4' FIXTURE.

WALL MOUNTED FIXTURE.

INDUSTRIAL FIXTURE.

WALL MOUNTED FIXTURE.

EXIT SIGN WITH DIRECTIONAL ARROWS AS INDICATED

RECESSED FIXTURE, DOWNLIGHT

3-WAY, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 42" AFF.

4-WAY, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 42" AFF.

WALL MOUNTED OCCUPANCY SENSOR WITH OVERRIDE SWITCH

CEILING MOUNTED OCCUPANCY SENSOR

20 AMP, 125 VOLT SINGLE-POLE TOGGLE SWITCH MOUNTED 42"

AFF.

a - CONTROLS LIGHTS WITH "a" DESIGNATION

LIGHTING CONTROLLER

D 20A, 125V DIMMER SWITCH MOUNTED 42" AFF

2' x 2' FIXTURE.

A1 a

EMERGENCY LIGHT

2' x 4' FIXTURE. SOLID FILL FIXTURE OR LABEL "em" INDICATES FIXTURE ON EMERGENCY CIRCUIT

E EXISTING

MD MOTION DETECTOR

CC

CR

EL

AP

X

PB

K

HD

HA

PP

WIRELESS ACCESS POINT

KEY PAD

COMBINATION STARTER

NEMA 5-20 DUPLEX RECEPTACLE MOUNTED 44" AFF

UNLESS NOTED OTHERWISE.

NEMA 5-20 DOUBLE DUPLEX RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE.

POWER CONNECTION

KC KEY PAD / CARD READER

6-30R

NEMA 5-20 DUPLEX RECEPTACLE WITH USB CHARGER MOUNTED 18" AFF

UNLESS NOTED OTHERWISE.

NEMA 5-20 DUPLEX SPLIT RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE.

NEMA 5-20 SIMPLEX RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE.

FACP

FIRE ALARM CONTROL PANEL

FAA

FIRE ALARM ANNUNCIATOR PANEL

F FIRE ALARM CHIME/STROBE

FIRE ALARM SPEAKER/STROBE CEILDING MOUNTEDS

F COMBINATION HORN/STROBE WITH SENDING STATIONF

H HEAT DETECTOR

R DUCT REMOTE TEST STATION

K KNOX BOX

D DOOR HOLDER

DS CEILING MOUNTED DAYLIGHT SENSOR

PC PHOTOCELL

ABA AMERICAN BARRIERS ACT

D

EM EMERGENCY

SP SUMP PUMP

RF REFRIGERATOR

CO COPIER

ECB ENCLOSED CIRCUIT BREAKER

# 6" POKE THRU DEVICE WITH (2) DUPLEX 5-20 RECEPTACLES AND 4 DATA

NEMA 5-20 DUPLEX RECEPTACLE FOR TELEVISION MOUNTED 60" AFF

UNLESS NOTED OTHERWISE.TV

AUDIO/VISUAL OUTLET. AV

em

LADDER CABLE TRAY.

PB PULL BOX

V SUPERVISORY VALVE SWITCH

FS WATER FLOW SWITCH

2' x 4' FIXTURE. FIXTURE HAS EMERGENCY BATTERY PACK.

M NEW ELECTRICAL MANHOLE

EX REQUEST TO EXIT

DC DOOR CONTACT

A. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT

HOMERUN SHALL HAVE A SPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.

B. MULTI-GANG BOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH CIRCUIT

WIREING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

C. ALL CONDUCTORS SHALL BE COPPER.

D. ALL WORK WILL BE DONE IN ACCORDANCE WITH THE CURRENT VERSION OF THE NEC – NFPA-70 FOR A

COMPLETE AND OPERATIONAL INSTALLATION.

E. PROVIDE A SEPARATE NEUTRAL CONDUCTOR WITH EACH 20A-120V POWER CIRCUIT - GROUND TOTAL SYSTEM

PER NEC 250.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:4

P

M

E001

LEGEND

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

GENERAL NOTES

No. Revisions: Date:

REV 0 07/24/2023

OS

OS

OS

OS

ATS ATS

G F

S

F

F

F

75F

T

T

C1

A22

SOUTH CORRIDOR

H.C.

X1

A22

X1

C1 C1 C1 C1 C1 C1 C1

C1 C1 C1 C1 C1 C1 C1

C1

C1

C1

4-EM1 - 1 4-EM1 - 1 4-EM1 - 1

4-EM1 - 1 4-EM1 - 1 4-EM1 - 1 4-EM1 - 1

4-EM1 - 1

4-EM1 - 1

DEDUCT ALTERNATE

4-MDP-OS

H.C.

FACP

4-MDP

4-BB - 10

DEDUCT ALTERNATE

4-BA - 4

4-BA - 4 4-BA - 4

4-BA - 44-BA - 4

4-BA - 5

4-BA - 5

4-BA - 5

4-BA - 5

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:5

P

M

EN100

BASEMENT - ALTERNATE PLAN

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N

1/4" = 1'-0"

BASEMENT - LIGHTING PLAN - ALTERNATE

N

1/4" = 1'-0"

BASEMENT - POWER AND SYSTEMS PLAN - ALTERNATE

F

D

F

F

WP/GF

2 D

DATA FMS RACK

PACS

CCTV

TMGB

4" SLEEVES DOWN

TELEPHONE WALL FIELD

4" SLEEVES

PACS DOOR CONTROLLERS

TR

4-1B - 9,11,13

4-1A - 15,17,19

DATA PACS

CCTV

"x

"x

12"x1"

12"x1"

LADDER

4"ø

"ø

NOTES:

1. 48 PORT LIGHT INTERFACE UNIT.

2. 48 PORT RJ-45 CAT 6A JACKS.

3. HORZONTAL CABLE MANAGER.

4. 48 PORT POE DATA SWITCH (VA)

5. 5kW UPS.

6. VERTICAL CABLE MANAGER.

DATA

TELEPHONE/

FUTURE DATA

DATA SWITCHES

TELEPHONE - 110 CROSS CONNECT

FUTURE DATA SWITCHES

PACS

CCTV

NOTES

1. DATA - BLUE

2. PHONE - YELLOW

3. BLANK

4. BLANK

1 2

3 4

LABEL

LABEL

BUILDING 21 BUILDING 4

CIRCUIT PROTECTOR

100 PR, CAT 3 CU

110 PUNCH

BLOCKS

WALL FIELD

66 PUNCH BLOCKS

LIGHT INTERFACE UNIT

24 STRAND MULTI-MODE 50/125 MICRON OM4 FIBER OPTIC CABLE

24 STRAND SINGLE-MODE OS2 FIBER OPTIC CABLE

LIGHT INTERFACE UNIT LIGHT INTERFACE UNIT

LIGHT INTERFACE UNIT

CIRCUIT PROTECTOR 110 PUNCH

BLOCKS - RJ45 IN

DATA RACK

TELEPHONE RJ45 TO

WORK AREA OUTLET

CROSS CONNECT

L21-30RL21-30R

PDU-A PDU-B

UPS

5kW 208V, 3PH UPS

REAR

UPS

PDU-A PDU-B

5kW 208V, 3PH UPS

ZONE PDU

NOTES:

1. NEMA L21-30R RECEPTACLE - MOUNTED ON SIDE OF CABLE TRAY.

2. CHATSWORTH ECONNECT PDU. VERTICAL; MONITORED; L21-20 CORD CAP.

INPUT-208Y/120V, 2A. OUTPUT- (30) C13, (6) C19 RECEPTACLES. (3) 2 POLE 20A

HYDROULIC MAGNETIC BREAKERS; LCD;ETHERNET, USB,AND ENVIRONMENTAL

SENSOR PORTS;IP AND SERIAL MONITORING;IP COLIDATION (PDU LINKING);TOOL-LESS

MOUNTING.

3. ZONE PDU. 30A 3PH. INPUT (2) 30A 208V 3PH 4W CIRCUITS.OUTPUT- (4) L21-20R & (6) 5-20

RECEPTACLES. (2) 10' POWER CORDS. L21-30P CAPS.

4. 5 kW UPS. 208V, 3PH 30A.

5. 30A CABLES.

2 2

2 2

4 4

OIT ROOMELECTRIC ROOM

TMGB

MAIN SWITCHBOARD

GROUND BAR

GROUNDING SYSTEM

NEC ARTICLE 250

CABLE TRAY

CABLE TRAY

RBB

TYPICAL DATA RACK

DATA EQUIPMENT

BOND TO TRAY

BOND TO TRAY

#6 AWG

#4 AWG

#4 AWG

3/0 AWG

TMGB - TELECOMMUNICATIONS MAIN GROUNDING BAR

TMG- TELECOMMUNICATIONS GROUNDING BAR

RBB - RACK BONDING BAR

NOTES

A. TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR SHALL BE BARE OR BRAIDED

COPPER.

B. ALL WIRE TAPS SHALL BE MADE WITH IRREVERSIBLE CRIMP CONNECTORS OR EXOTHERMIC

WELDING.

C. LUGS SHALL BE 2-HOLE TYPE AND COMPRESSION TYPE. PROVIDED AT EACH BAR AND

TERMINATION POINT.

BOND TO RACK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:4

P

M

E501

TECHNOLOGY DETAILS

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/2" = 1'-0"

ENLARGED OIT CLOSET

N 1/2" = 1'-0"

ENLARGED OIT CLOSET - CABLE TRAY

N 1 1/2" = 1'-0"

DATA RACKS - FRONT VIEW

N 12" = 1'-0"

FACE PLATE DETAIL

NTS

TECHNOLOGY SINGLE-LINE DIAGRAM

N 1 1/2" = 1'-0"

DATA RACKS - REAR VIEW

N 1/2" = 1'-0"

TECHNOLOGY GROUNDING AND BONDING DIAGRAM

TOP VIEW

SECTION "A-A"

POWER

SECTION "B-B"

S L O

P E

S

LO

P E

SLOPE

305x305mm (12"x12") SUMP

FINISHED

GRADE

GROUND ROD

PER SECTION

26 05 26.

A

A

B B

PULLING

IRON

CONC.

ENVELOPE

GROUND

ROD

SLEEVE

PULLING

IRON

CABLE STANCHION PER

SECTION 26 05 41.

305mm (12") SUMP

SUMP FRAME &

COVER

GRADE RINGS AS REQ'D TO MATCH

CIVIL FINISHED GRADE ELEVATION.

CABLE STANCHION

0.764 CUBIC METERS

(1 CUBIC YARD) 19mm

(3/4") GRAVEL SUMP

GENERAL NOTE:

1. INCLUDE ALUMINUM LADDER

(NOT SHOWN FOR CLARITY)

V A

R

IE

S

(5'-0")

1930mm

(6'-4")

(8")

1524mm 203mm

(8 m m

(6 m m m m

(1

M

IN

m m

(8

1524mm

(5'-0") m m

(8 ")2 m m

(7

965mm965mm

(3'-2")

1930mm

(6'-4")

(3'-2")

(5

(3

(9 m m m m m m

(3")

76mm

(8

(8 m m (9

(8 m m m m m m

(3 m m915mm

(3'-0")

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:5

P

M

E502

ELECTRICAL DETAILS & MOTOR

SCHEDULE

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

NTS

POWER MANHOLE DETAILS

No. Revisions: Date:

REV 0 07/24/2023

NOTES:

1. INDOOR CASSETTE UNITS. REFER TO MECHANICAL SCHEDULE FOR QUANTITY AND

EXACT LOAD. LARGES MCA FOR CASSETTE UNIT 0.86 A.

MOTOR & EQUIPMENT SCHEDULE

MOTOR ID Description

MOTOR STARTER DISCONNECT CONTROLS FEEDER

S E

E N

O T

E

CHARACTERISTICS TYPE LOCATION

F U

R N

IS

H

E D

B Y

D

IV

TYPE

N E

M A

T Y

P E

D

IS

C S

IZ

E

F U

S E

S

IZ

E

LOCATION

F U

R N

IS

H

E D

B Y

D

IV

M A

N U

A L

A T

S T

A R

T E

R

IN

T

E G

R A

L W

IT

H

E Q

U

IP

M E

N T

D D

C

F U

R N

IS

H

E D

B Y

D

IV

S E

E N

O T

E

N U

M B

E R

O F

C O

N D

U C

T O

R S

W

IR

E S

IZ

E

G R

O U

N D

S

IZ

E

C O

N D

U

IT

S

IZ

E

V O

LT

A

G E

P O

LE

L O

A D kV

A

N E

M A

S

IZ

E

M A

N U

A L

M A

G N

E T

IC

C O

M B

IN

A

T

IO

N S

T A

R T

E R

V F

D D

R

IV

E

E C

M O

T O

R

S E

E N

O T

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

R O

O M

N U

M B

E R

S E

E N

O T

E

D

IS

C S

W

IT

C H

M A

N U

A L

S T

A R

T E

R

R E

C E

P T

A C

LE

S W

IT

C

H

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

P A

N E

LB

O

A R

D

S E

E N

O T

E

AD-1 AUTOMATIC

DOOR

120 V 1 0.12 2 12 12 3/4

DOAS ERC-1 208 V 3 3.71 ● ● 23 ● ● 26 23 3 12 12 0.75"

DOAS-1 208 V 3 3.71 ● ● 23 ● ● 26 23 3 12 12 0.75"

EF-2 EXHAUST FAN 120 V 1 0.18 ● ● ● ● 2 12 12 3/4

IDU INDOOR

COOLING UNIT

208 V 2 0.06 ● 23 ● ● 26 23 2 12 12 0.75" 1

MDC-1-1 REFRIGERANT

HEAT RECOVERY

CONTROLLER

208 V 2 0.32 ● 23 ● ● 26 23 2 12 12 0.75" 1

MDC-2-1 REFRIGERANT

HEAT RECOVERY

CONTROLLER

208 V 2 0.22 ● 23 ● ● 26 23 2 12 12 0.75" 1

ODU-1 AIR COOLED

CONDENSING

UNIT

208 V 3 29.9 ● ● 23 ● ● 26 23 3 1 6 1.5"

ODU-2 AIR COOLED

CONDENSING

UNIT

208 V 3 25.58 ● ● 23 ● ● 26 23 3 4 6 1.5"

ODU-3 AIR COOLED

CONDENSING

UNIT

208 V 3 9.01 ● 23 ● ● 26 23 3 8 10 0.75"

SDC-1-1 REFRIGERANT

HEAT RECOVERY

CONTROLLER

208 V 2 0.21 ● 23 ● ● 26 23 2 12 12 0.75" 1

SDC-1-2 REFRIGERANT

HEAT RECOVERY

CONTROLLER

208 V 2 0.21 ● 23 ● ● 26 23 2 12 12 0.75" 1

SDC-2-1 REFRIGERANT

HEAT RECOVERY

CONTROLLER

208 V 2 0.21 ● 23 ● ● 26 23 2 12 12 0.75" 1

SDC-2-2 REFRIGERANT

HEAT RECOVERY

CONTROLLER

208 V 2 0.21 ● 23 ● ● 26 23 2 12 12 0.75" 1

400A 120/208V 3PH-4W

4-1A 4-BA 4-2A

4-MDP

PAD MOUNT TRANSFORMER

T-4 150kVA

EXISTING PMH SWITCH - 5

400A

225A 225A 225A 60A 40A 60A 60A 60A 40A

4-BB

300A 60A 60A

SPARE

TO

RANGE

NORTH

COMPRESSOR

NORTH AHU

TO ATTIC HEAT

STRIPS

WATER

HEATER SOUTH

COMPRESSOR

SOUTH AHU

800A 120/208V 3PH-4W

4-BA 4-1A

4-MDP-OS

800A

225A 225A 225A 150A 110 A

4-2A

ELEVATOR

TRANSFORMER

T-4 225kVA 12,470V 208Y/120V

4.5%Z IMPEDANCE

(LTG &

RECP 42

CIRC.)

(LTG &

RECP 42

CIRC.)

(LTG &

RECP 42

CIRC.)

N E

4-EM1

G

NEW BLDG 4

GENERATOR

200 KW

120/208V

ATS-2

100A

4 POLE

BYPASS ATS

800 A

PAD MOUNT TRANSFORMER

EXISTING T-5

500kVA 12470V

120/208V

TO CLC MV PRIMARY SWITCH

FUSE 25A

N EATS-1

800A

4 POLE

BYPASS ATS

4-1B4-BB 4-2B

ODU-1

80 A

ODU-2

WIREWAY

800A

ECB-2

100A

ECB-1

800A 120/208V 3PH-4W

4-MDP

800A

800A 100A

3-#2 15 KV MV CABLE, #2 600V GRD., IN 4" C.

(3 SETS) 3-300 KCMIL, IN 2-1/2" C.

(2 SETS) 4-500 KCMIL, #1/0 GRD., 3-1/2" C.) 4-#1, #8 GRD., IN 1.5" C.

4-#4/0 AWG, #4 GRD., IN 2-1/2" C.

60A

GARAGE/MAINTENANCE

BLDG

4-#6, #10 GRD., IN 1.5" C.

4-#1, #8 GRD., 1-1/2" C.

N G

#2/0

GEC

(3 SETS) 4-300 KCMIL, IN 2.5" C.

#2/0

GEC

4-#1, #8 GRD., 1-1/2" C.

(2 SETS) 4-500 KCMIL, #1/0 GRD., 3-1/2" C.

3-#2/0 15KV MVCABLE, #6 600V GRD., IN 4" C.

100A

4-3A

30A

TVSS

TVSS

30A

TVSS

NEW

MH #4

NEW MANHOLE

(2 SETS) 4-500 KCMIL, #1/0 GRD., IN 3.5" C.

3-#1/0, #6 GRD., 2" C.

3-#1, #6 GRD., 1-1/2" C.

3-#3, #8 GRD., 1-1/4" C.

ST

X

AVAILABLE FAULT I

15,128A

X14,605A

X13,822A

X11,655A X11,364A X10,829A X7,615A X2,584AX5,532A X7,801A X6,939A

X10,176A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:5

P

M

E600

SINGLE LINE DIAGRAM

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

1. DISCONNECT AND REMOVE EXISTING BUILDING 4 PAD MOUNT TRANSFORMER, DISTRIBUTION PANEL, BRANCH PANELBOARDS AND EQUIPMENT DISCONNECTS. REMOVE ALL CIRCUITRY AND CONDUIT BACK

TO SOURCE.

2. REFER TO SITE PLAN FOR NEW SERVICE ROUTE INTO BUILDING.

3. REMOVE BUILDING 4 ELECTRICAL SERVICE FEEDER BACK TO PMH SWITCH 5.

KEY NOTES

A. EXISTING DISTRIBUTION PANELBOARDS, BRANCH PANELBOARDS, FEEDERS AND CONDUIT TO BE

REMOVED.

GENERAL NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:5

P

M

E601

PANEL SCHEDULES

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

Notes:

Lighting 6072 VA 100.00% 6072 VA

Power 7670 VA 100.00% 7670 VA Total Est. Demand: 395 A

Receptacle 77400 VA 56.46% 43700 VA Total Conn.: 468 A

Other 0 VA 0.00% 0 VA Total Est. Demand: 142202 VA

Motor 77004 VA 109.71% 84480 VA Total Conn. Load: 168427 VA

Heating 350 VA 100.00% 350 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 468 A

Total Conn. Load: 168427 VA

16 Space 1 -- -- --

15 Space 1 -- -- --

14 Space 1 -- -- --

13 Space 1 -- -- --

12 Space 1 -- -- --

11 Space 1 -- -- --

10 Space 1 -- -- --

9 Space 1 -- -- --

8 GARAGE/MAINTENANCE BLDG 3 100 A 60 A 0 VA

7 ODU-2 3 100 A 95 A 25579 VA

6 ODU-1 3 100 A 100 A 29902 VA

5 ELEVATOR 3 150 A 150 A 0 VA

4 4-3A 3 100 A 100 A 38291 VA

3 4-2A/4-2B 3 225 A 225 A 19379 VA

2 4-1A/4-1B 3 225 A 225 A 23156 VA

1 4-BA/4-BB 3 225 A 225 A 32120 VA

CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks

Notes:

Enclosure: NEMA 1 MCB Rating: 800 A

Mounting: Surface Wires: 4 Mains Rating: 800 A

Supply From: 4-MDP Phases: 3 Mains Type: MCB

Location: ELEC/UTILITY 004 Volts: 120/208 Wye A.I.C. Rating: 25,000A

Switchboard: 4-MDP-OS

Notes:

Lighting 7902 VA 100.00% 7902 VA

Power 7670 VA 100.00% 7670 VA Total Est. Demand: 401 A

Receptacle 78260 VA 56.39% 44130 VA Total Conn.: 475 A

Other 0 VA 0.00% 0 VA Total Est. Demand: 144461 VA

Motor 77004 VA 109.71% 84480 VA Total Conn. Load: 171116 VA

Heating 350 VA 100.00% 350 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 475 A

Total Conn. Load: 171116 VA

8 Space 1 -- -- --

7 Space 1 -- -- --

6 Space 1 -- -- --

5 Space 1 -- -- --

4 Space 1 -- -- --

3 TVSS 1 30 A 30 A 0 VA

2 4-EM1 3 100 A 100 A 2689 VA

1 4-MDP-OS 3 800 A 800 A 168427 VA

CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks

Notes:

Enclosure: NEMA 1 MCB Rating: 800 A

Mounting: Surface Wires: 4 Mains Rating: 800 A

Supply From: Phases: 3 Mains Type: MCB

Location: ELEC/UTILITY 004 Volts: 120/208 Wye A.I.C. Rating: 25,000A

Switchboard: 4-MDP

Notes:

Lighting 1953 VA 100.00% 1953 VA

Power 2000 VA 100.00% 2000 VA Total Est. Demand: 67 A

Receptacle 7980 VA 100.00% 7980 VA Total Conn.: 60 A

Other 0 VA 0.00% 0 VA Total Est. Demand: 24012 VA

Motor 9547 VA 123.59% 11798 VA Total Conn. Load: 21760 VA

Heating 350 VA 100.00% 350 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 60 A 65 A 57 A

Total Load: 7190 VA 7758 VA 6813 VA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30

27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28

25 FACP-ELEC/UTILITY 004 20 A 1 0 VA 0 VA 1 20 A Spare 26

23 -- -- -- 3002... 0 VA 1 20 A Spare 24

21 -- -- -- 3002... 150 VA -- -- -- 22

19 ODU-3 45 A 3 3002... 150 VA 2 20 A BDR-5 20

17 Power PIV STAFF 024 20 A 1 500 VA 500 VA 1 20 A Power PIV STAFF 024 18

15 -- -- -- 270 VA 1000... 1 20 A Power 16

13 IDU 20 A 2 270 VA 308 VA -- -- -- 14

11 Receptacle 20 A 1 900 VA 308 VA 2 20 A BDR-4 12

9 Receptacle 20 A 1 1080... 900 VA 1 20 A Receptacle 10

7 Receptacle 20 A 1 900 VA 900 VA 1 20 A Receptacle 8

5 Receptacle 20 A 1 1080... 540 VA 1 20 A Receptacle 6

3 Lighting Room 000, 001, 009, 016, 017 20 A 1 276 VA 1080... 1 20 A Receptacle 4

1 Lighting Room 029, 028, 031, 026, 024, 022, 025... 20 A 1 948 VA 729 VA 1 20 A Lighting Room 002, 006, 007, 005, 003, 006B,... 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: 4-MDP-OS Phases: 3 Mains Type: MLO

Location: ELEC/UTILITY 004 Volts: 120/208 Wye A.I.C. Rating: 22,000A

Branch Panel: 4-BA

Notes:

Total Est. Demand: 29 A

Total Conn.: 29 A

Total Est. Demand: 10413 VA

Receptacle 9040 VA 100.00% 9040 VA Total Conn. Load: 10360 VA

Motor 1320 VA 103.98% 1373 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 27 A 37 A 23 A

Total Load: 3225 VA 4385 VA 2750 VA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- 0 VA 1 20 A Spare 36

33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34

31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32

29 -- -- -- 500 VA 450 VA -- -- -- 30

27 BDR-6 20 A 2 500 VA 450 VA 2 20 A BDR-3 28

25 HOT WATER RECIRC PUMP 20 A 1 300 VA 180 VA 1 20 A EF-2 26

23 TRAP PRIMER 20 A 1 0 VA 0 VA 1 20 A WATER HEATER 24

21 AUTO DOOR OPERATOR 20 A 1 120 VA 30 VA -- -- -- 22

19 -- -- -- 105 VA 30 VA 2 20 A IDU 20

17 SDC-1-1 20 A 2 105 VA 105 VA -- -- -- 18

15 -- -- -- 120 VA 105 VA 2 20 A SDC-2-1 16

13 IDU 20 A 2 120 VA 150 VA -- -- -- 14

11 Receptacle 20 A 1 180 VA 150 VA 2 20 A IDU 12

9 Receptacle 20 A 1 180 VA 900 VA 1 20 A Receptacle 10

7 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 8

5 Receptacle 20 A 1 900 VA 360 VA 1 20 A Receptacle 6

3 Receptacle 20 A 1 1080... 900 VA 1 20 A Receptacle 4

1 Receptacle 20 A 1 900 VA 1080... 1 20 A Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: 4-MDP-OS Phases: 3 Mains Type: MLO

Location: ELEC/UTILITY 004 Volts: 120/208 Wye A.I.C. Rating: 22,000A

Branch Panel: 4-BB

Notes:

Total Est. Demand: 23 A

Lighting 1908 VA 100.00% 1908 VA Total Conn.: 23 A

Power 2000 VA 100.00% 2000 VA Total Est. Demand: 8363 VA

Receptacle 3960 VA 100.00% 3960 VA Total Conn. Load: 8348 VA

Motor 480 VA 103.13% 495 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 35 A 15 A 22 A

Total Load: 4063 VA 1784 VA 2500 VA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34

31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32

29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30

27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28

25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26

23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24

21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22

19 -- -- -- 60 VA 0 VA 1 20 A Spare 20

17 -- -- -- 60 VA 0 VA 1 20 A Spare 18

15 DATA RACK - TR 104 30 A 3 60 VA 240 VA -- -- -- 16

13 Receptacle 20 A 1 900 VA 240 VA 2 20 A IDU 14

11 Power 20 A 1 500 VA 500 VA 1 20 A Power 12

9 Power 20 A 1 500 VA 500 VA 1 20 A Power 10

7 Receptacle 20 A 1 540 VA 900 VA 1 20 A Receptacle 8

5 Receptacle 20 A 1 900 VA 540 VA 1 20 A Receptacle 6

3 Lighting Room 100, 112, 101, S100B, 114, 115 20 A 1 420 VA 65 VA 1 20 A Lighting Room 122, 102 4

1 Lighting Room 121, 120, 119, 116, 117 20 A 1 701 VA 722 VA 1 20 A Lighting Room 105, 107, 108, 112, 109, 110, 106... 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: 4-MDP-OS Phases: 3 Mains Type: MLO

Location: ELEC 103 Volts: 120/208 Wye A.I.C. Rating: 22,000A

Branch Panel: 4-1A

Notes:

Total Est. Demand: 37 A

Total Conn.: 41 A

Power 670 VA 100.00% 670 VA Total Est. Demand: 13449 VA

Receptacle 12880 VA 88.82% 11440 VA Total Conn. Load: 14809 VA

Motor 1259 VA 106.36% 1339 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 53 A 41 A 31 A

Total Load: 6240 VA 4789 VA 3779 VA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38

35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36

33 -- -- -- 30 VA 500 VA -- -- -- 34

31 IDU TR 104 20 A 2 30 VA 500 VA 2 20 A BDR-7 32

29 Receptacle 20 A 1 360 VA 269 VA -- -- -- 30

27 Receptacle 20 A 1 540 VA 269 VA 2 20 A MDC 28

25 TOWEL DISPENSER 20 A 1 550 VA 540 VA 1 20 A Receptacle 26

23 DRINKING FOUNTAIN 20 A 1 120 VA 180 VA -- -- -- 24

21 -- -- -- 150 VA 180 VA 2 20 A IDU 22

19 IDU 20 A 2 150 VA 450 VA -- -- -- 20

17 Receptacle 20 A 1 900 VA 450 VA 2 20 A BDR-2 18

15 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 16

13 -- -- -- 60 VA 180 VA 1 20 A Receptacle 14

11 -- -- -- 60 VA 180 VA 1 20 A Receptacle 12

9 DATA RACK - TR 104 30 A 3 60 VA 900 VA 1 20 A Receptacle 10

7 Receptacle 20 A 1 900 VA 900 VA 1 20 A Receptacle IT/LAN 104 8

5 Receptacle Room 108 20 A 1 720 VA 540 VA 1 20 A Receptacle 6

3 Receptacle 20 A 1 900 VA 900 VA 1 20 A Receptacle 4

1 Receptacle 20 A 1 900 VA 1080... 1 20 A Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: 4-MDP-OS Phases: 3 Mains Type: MLO

Location: ELEC 103 Volts: 120/208 Wye A.I.C. Rating: 22,000A

Branch Panel: 4-1B

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:0

P

M

E602

PANEL SCHEDULES

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

Notes:

Total Est. Demand: 29 A

Lighting 1983 VA 100.00% 1983 VA Total Conn.: 29 A

Power 1500 VA 100.00% 1500 VA Total Est. Demand: 10518 VA

Receptacle 6480 VA 100.00% 6480 VA Total Conn. Load: 10503 VA

Motor 540 VA 102.78% 555 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 37 A 36 A 18 A

Total Load: 4209 VA 4084 VA 2210 VA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Space -- 1 -- -- 1 -- Space 34

31 Space -- 1 -- -- 1 -- Space 32

29 Space -- 1 -- -- 1 -- Space 30

27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28

25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26

23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24

21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22

19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20

17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18

15 Power 20 A 1 500 VA 540 VA 1 20 A Receptacle 16

13 -- -- -- 270 VA 500 VA 1 20 A Power EAST CORRIDOR 215 14

11 IDU 20 A 2 270 VA 500 VA 1 20 A Power HSS 220 12

9 Receptacle 20 A 1 720 VA 900 VA 1 20 A Receptacle 10

7 Receptacle 20 A 1 900 VA 900 VA 1 20 A Receptacle 8

5 Receptacle 20 A 1 1080... 360 VA 1 20 A Receptacle 6

3 Lighting Room 200, 216-2, 216-5, 215 20 A 1 344 VA 1080... 1 20 A Receptacle 4

1 Lighting Room 227, 226, 222, 224, 218, 220,... 20 A 1 872 VA 767 VA 1 20 A Lighting Room 205, 207, 204, 202, 216-2, 212,... 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: 4-MDP-OS Phases: 3 Mains Type: MLO

Location: ELEC 203 Volts: 120/208 Wye A.I.C. Rating: 22,000A

Branch Panel: 4-2A

Notes:

Total Est. Demand: 25 A

Total Conn.: 25 A

Power 1500 VA 100.00% 1500 VA Total Est. Demand: 8928 VA

Receptacle 6420 VA 100.00% 6420 VA Total Conn. Load: 8876 VA

Motor 956 VA 105.44% 1008 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 28 A 25 A 22 A

Total Load: 3358 VA 2928 VA 2590 VA

41 Space -- 1 -- -- 1 -- Space 42

39 Space -- 1 -- -- 1 -- Space 40

37 Space -- 1 -- -- 1 -- Space 38

35 Space -- 1 -- -- 1 -- Space 36

33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34

31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32

29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30

27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28

25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26

23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24

21 -- -- -- 104 VA 104 VA -- -- -- 22

19 SDC 20 A 2 104 VA 104 VA 2 20 A SDC 20

17 TOWELL DISPENSER 20 A 1 1000... 360 VA 1 20 A Receptacle 18

15 DRINKING FOUNTAIN 20 A 1 500 VA 270 VA -- -- -- 16

13 270 VA 2 20 A IDU 14

11 150 VA -- -- -- 12

9 Receptacle 20 A 1 180 VA 150 VA 2 20 A ERP-1 10

7 Receptacle 20 A 1 180 VA 180 VA 1 20 A Receptacle 8

5 Receptacle 20 A 1 900 VA 180 VA 1 20 A Receptacle 6

3 Receptacle 20 A 1 720 VA 900 VA 1 20 A Receptacle 4

1 Receptacle 20 A 1 1440... 1080... 1 20 A Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: 4-MDP-OS Phases: 3 Mains Type: MLO

Location: ELEC 203 Volts: 120/208 Wye A.I.C. Rating: 22,000A

Branch Panel: 4-2B

Notes:

Total Est. Demand: 7 A

Total Conn.: 7 A

Total Est. Demand: 2689 VA

Lighting 1829 VA 100.00% 1829 VA Total Conn. Load: 2689 VA

Receptacle 860 VA 100.00% 860 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 8 A 5 A 10 A

Total Load: 870 VA 602 VA 1217 VA

29 Space -- 1 -- -- 1 -- Space 30

27 Space -- 1 -- -- 1 -- Space 28

25 Space -- 1 -- -- 1 -- Space 26

23 Space -- 1 -- -- 1 -- Space 24

21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22

19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20

17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18

15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16

13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14

11 Receptacle 20 A 1 180 VA 500 VA 1 20 A Elevator Cab Lighting 12

9 Lighting STAIR B S300B 20 A 1 153 VA 180 VA 1 20 A Receptacle 10

7 Lighting Room 122, 102 20 A 1 110 VA 454 VA 1 20 A Lighting Room 216-2, 200, 216-5, 215 8

5 Lighting Room S201B, S100B, S000B 20 A 1 125 VA 412 VA 1 20 A Lighting Room S100B, 100, 101, 121, 118, 112,... 6

3 Lighting ELEVATOR E000 20 A 1 144 VA 125 VA 1 20 A Lighting Room S100A, S000A, S200B 4

1 Lighting Room 001, 016, 000, 017, 009 20 A 1 255 VA 51 VA 1 20 A Lighting 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: 4-MDP Phases: 3 Mains Type: MLO

Location: ELEC 103 Volts: 120/208 Wye A.I.C. Rating: 22,000A

Branch Panel: 4-EM1

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:0

P

M

E603

LIGHTING SCHEDULE

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

LIGHTING FIXTURE SCHEDULE

Image TYPE DESCRIPTION

LOAD

(VA) LAMP(S) LUMINOUS FLUX COLOR TEMP. CRI

MOUNTING

S-SURFACE

R-RECESSED

CH-CHAIN HUNG

P-PENDANT

A1 LOW PROFILE LED LINEAR FIXTURE.BEZEL TRIM. 120-277V. POWDER COAT

FINISH. FIELD REPLACEABLE LED BOARDS.

0 LED 1 lm 3500 K 90 R

A2 LOW PROFILE LED LINEAR FIXTURE. PLASTER TRIM. 120-277V. POWDER

COAT FINISH. FIELD REPLACEABLE LED BOARDS.

0 LED 1 lm 3500 K 90 R

A3 LOW PROFILE LED LINEAR FIXTURE.BEZEL TRIM. 120-277V. POWDER COAT

FINISH. FIELD REPLACEABLE LED BOARDS.

0 LED 1 lm 3500 K 90 R

A4 3.5"x8' LED RECESSED LINEAR FIXTURE. 60% RECYCLED ALUMINUM

EXTRUDED HOUSING. HIGH EFFICACY EXTRUDED DIFFUSE ACRYLIC LENS.

120-277V. 0-10V DIMMING.

36 LED 3264 lm 3500 K 90 R

A5 3.5"x6' LED RECESSED LINEAR FIXTURE. 60% RECYCLED ALUMINUM

EXTRUDED HOUSING. HIGH EFFICACY EXTRUDED DIFFUSE ACRYLIC LENS.

120-277V. 0-10V DIMMING.

27 LED 2448 lm 3500 K 90 R

A22 2X2 RECESSED LED LOW PROFILE ARCHITECTURAL TROFFER. 26 LED 3300 lm 3500 K 90 R

A24 3.5"x8' LED RECESSED LINEAR FIXTURE. 60% RECYCLED ALUMINUM

EXTRUDED HOUSING. HIGH EFFICACY EXTRUDED DIFFUSE ACRYLIC LENS.

120-277V. 0-10V DIMMING.

36 LED 3264 lm 3500 K 90 R

B1 3" LED RECESSED SQUARE DOWNLIGHT. DIE-CAST ALUMINUM PERCISION

FIT HOUSING. MICRO-PRISMATIC LENS. 120-277V. 0-10V DIMMING.

12 LED 1405 lm 3500 K 92 R

C1 LINEAR 4' HIGH-OUTPUT LED INDUSTRIAL CHAIN HUNG FIXTURE.

CODE-GUAGE COLD-ROLLED STEEL HOUSING. 120-277V. WITH ACRYLIC

LENS.

26 LED 4000 lm 3500 K 90 CH

D1 24" WIDE DECORATIVE LED PENDANT. POWERDER COAT FINISH, 0-10V 1%

DIMMING UL-94 HB FLAME CLASS RATED ACRYLIC LENS.

15 LED 1695 lm 3500 K 80 P (7'-0" AFF)

366 LUM/FT

366 LUM/FT

366 LUM/FT

6.4 W/FT

6.4 W/FT

6.4 W/FT

LIGHTING FIXTURE SCHEDULE

Image TYPE DESCRIPTION

LOAD

(VA) LAMP(S) LUMINOUS FLUX COLOR TEMP. CRI

MOUNTING

S-SURFACE

R-RECESSED

CH-CHAIN HUNG

P-PENDANT

F1 DECORATIVE LED WET LOCATION LISTED EXTERIOR PENDANT LIGHT.

120-277V. STEM MOUNTED. POWER COAT FINISH, BRONZE.

10 LED 1250 lm 3500 K 90 P (7'-6" AFF)

H1 LED ILLUMINATED HANDRAIL. INTEGRAL POWER SUPPLY IN HANDRAIL

POST.

0 LED 1 lm 3500 K 90 R

K1 WALL MOUNTED DIRECT/INDERECT FIXTURE WITH ALLUMINUM HOUSING.

SQUARE BODY PAINTED BRONZE. 90 DOWNLIGHT, 10 UPLIGHT.

17 LED 1500 lm 3500 K 80 S (7'-6" AFF)

M1 MULLION MOUNTED LED LINEAR FIXTURE. EXTRUDED DIFFUSE ACRYLIC

LENS. 0-10V DIMMING. 120V

14 LED 1716 lm 3500 K 80 S

W1 SURFACE MOUNTED LED LINEAR GASKETED FIXTURE. WATER RESISTANT

FIBERGLASS HOUSING. INJECTION MOLDED ACRYLIC LENS. 120-277V

18 LED 3000 lm 3500 K 80 S

W4 4' DIRECT/INDIRECT WALL MOUNTED STAIRWELL FIXTURE. EXTRUDED

ALUMINUM HOUSING. INJECTION MOLDED PRIMARY OPTIC LENS. 0-10V

DRIVER. INTEGRAL OCCUPANCY SENSOR.

25 LED 1800 lm 3500 K 80 S (7'-6" AFF)

X1 SINGLE FACE EDGE-LIT EXIT SIGN WITH RED LETTERS, MIRROR

BACKGROUND. 120-277V

2 LED 0 lm 0 K S

X2 DOUBLE FACE EDGE-LIT EXIT SIGN WITH RED LETTERS, MIRROR

BACKGROUND

2 LED 0 lm 0 K S

800 LM/FT - DIRECT

500 LUM/FT - UPLIGHT

J

T

9°

EXISTING PMH

SWITCH #5

REMOVE EXISTING

PAD MOUNT

TRANSFORMER

EX.

MH #4

BLDG 21

EXISTING COMMUNICATIONS

MANHOLE

1 2

3 3

EX.

PB

EXISTING COMMUNICATIONS MANHOLE

EXISTING

COMMUNICATIONS

MANHOLE

EXISTING PAD MOUNT

TRANSFORMER

EXISTING

COMMUNICATIONS

MANHOLE AND

CABLE TV BOX

GARAGE/MAINTENANCE BLDG

M c

M c

M c

M c

BUILDING 4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:5

:2

P

M

ES100

SITE PLAN - DEMOLITION

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1" = 30'-0"

ELECTRICAL SITE PLAN - DEMOLITION

1. REMOVE EXISTING BUILDING 4 ELECTRICAL FEEDER BACK TO PRIMARY SWITCH PMH #5. EXISTING

ELECTRIC MANHOLE #4 IS TO REMAIN.

2. REMOVE EXISTING FIBER OPTIC AND COPPER PAIRS BACK TO BULDING 21.

3. REFER TO BASEMENT DEMOLITION PLAN FOR CONTINUATION.

4. FIRE ALARM CIRCUIT EXTENDS TO BUILDINGS 45, 46, 47, AND 48. NEW FIRE ALARM CIRCUIT SHALL

EXTEND TO EXISTING BUILDINGS FOR A COMPLETE AND FUNCTIONAL SYSTEM.

5. REMOVE CLC BLDG 71/72 FEEDER BACK TO PMH #5.

6. EXISTING LIGHT POLE TO BE RELOCATED. REMOVE FIXTURE AND STORE FOR RELOCATION. REFER TO

NEW WORK PLANS.

7. DISCONNECT AND REMOVE EXISTING GARAGE/MAINTENANCE BUILDING PANEL. REMOVE CIRCUITRY

BACK TO BUILDING 4.

8. DISCONNECT AND REMOVE EXISTING STREET LIGHT POLE. MAINTAIN EXISTING CIRCUIT FOR NEW

PEDESTRIAN POLE LIGHT.

KEY NOTES

F F F

D

D D

D D

D D

D

D

D D

D

D D

D

D

D D

D

D

D

DD

OS

S

R

S

R

S R

S R

S

M H

F

D

S

R

S R

S

R

S R

FACP

FIBER, TELEPHONE AND FIRE

ALARM CABLING TO MANHOLE.

REFER TO SITE PLAN.

AP

X

AP

X

CRAWL SPACE

003A

MECHANICAL

OFFICE

ASSOCIATE CHIEF, CPS

PHARMACY RESIDENTS

FEMALE TOILET

MALE TOILET

AFGE STORAGE OFFICE

MECHANICAL

TRAINING ROOM

AFGE LIASISON OFFICE

STORAGE

STORAGE

007A

MECHANICAL ROOM

007B

STORAGE

STAIRS

4-MDP

4BB

4-BA

REMOVE EXISTING FEEDER

BACK TO PAD MOUNT

TRANSFORMER

AP

X

CR

CR

22 1 1

GENERAL DEMOLITION NOTES

A. ALL LIGHTING FIXTURES, ELECTRICAL, DATA, SECURITY, AND FIRE ALARM DEVICES WITHIN THE BUILDING 4

AREA OF DEMOLITION SHALL BE REMOVED UNLESS OTHERWISE NOTED.

B. REMOVE WIRING AND CONDUIT BACK TO SOURCE OR LAST POINT OF CONNECTION TO REMAIN.

C. EXISTING EQUIPMENT OUTSIDE OF SCOPE OF WORK BOUNDARIES SHALL BE MAINTAINED. RECONNECT

ANY CIRCUITS CUT PASSING THROUGH DEMOLITION AREAS IN BUILDING OR ON BUILDING SITE.

D. REMOVE, CAP AND RELOCATE EQUIPMENT, OUTLETS, CONDUIT WIRE, ETC. AS SHOWN AND SPECIFIED ON

DRAWINGS, AND AS MAY BECOME NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. VISIBLY

EXAMINE ALL EXISTING WALLS DESIGNATED FOR REMOVAL TO DETERMINE THE CONDUIT AND THE WIRING

THAT WILL REQUIRE CAPPING AND REMOVAL, WHETHER OR NOT SUCH CONDITIONS ARE INDICATED ON

DRAWINGS.

E. FAILURE TO VISIT THE SITE TO TAKE ALL EXISTING CONDITIONS INTO ACCOUNT WILL NOT ALLOW FOR

CHANGES TO THE SCOPE OF WORK. REMOVE ALL CONDUITS AND CONDUCTORS BACK TO THEIR SOURCE.

F. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING FIXTURES, OUTLETS, EQUIPMENT ETC. TO REMAIN IN USE

WHETHER NOTED ON PLANS OR NOT. FIELD VERIFY EXISTING ITEMS TO REMAIN IN USE. RECONNECT

RACEWAYS AND WIRING FOR EXISTING CIRCUITS WHICH MUST BE RE-ROUTED OR WHICH ARE PARTIALLY

ABANDONED TO POWER THE REMAINING OUTLETS ON THE CIRCUIT.

G. REMOVE ALL UNUSED WIRING AND CABLES BACK TO THEIR SOURCE. REMOVE ALL UNUSED CONDUIT THAT

IS EXPOSED OR ABOVE ACCESSIBLE CEILING WHICH IS AFFECTED BY OR IS IN THE AREA OF DEMOLITION

WORK .

H. THE INTENTION OF THE ELECTRICAL DEMOLITION DRAWINGS IS TO DISCONNECT AND REMOVE ALL

ELECTRICAL WORK MADE VOID BY THE SCOPE OF THE CONSTRUCTION AND ALTERATION. FIELD VERIFY

EXACT MATERIAL QUANTITIES REQUIRED TO BE REMOVED.

I. TAKE ALL REMOVED MATERIALS FROM THE PROJECT SITE, EXCEPT FOR THOSE TO BE RELOCATED

STORED OR TURNED OVER TO THE GOVERNMENT.

J. COORDINATE ALL DEMOLITION WORK WITH ALL OTHER TRADES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:1

P

M

ED100

BASEMENT - DEMOLITION PLAN

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

BASEMENT - DEMOLITION PLAN

D R A W I N G N O T E S :

1 HEAT PUMP TO BE REMOVED. DISCONNECT AND REMOVE CIRCUITRY AND CONDUIT BACK TO SOURCE. REMOVE

ASSOCIATED DISCONNECT SWITCH.

2 CONDENSING UNITS ON GRADE TO BE REMOVED. DISCONNECT AND REMOVE CIRCUITRY AND CONDUIT BACK TO

SOURCE. REMOVE ASSOCIATED DISCONNECT SWITCHES.

3 HVAC EQUIPMENT IN THIS ROOM TO BE REMOVED. DISCONNECT AND REMOVE ALL ASSOCIATED CIRCUITRY, CONDUIT, DISCONNECT SWITCHES AND FIRE ALARM DEVICES.

4 REMOVE DISCONNECT SWITCH AND ASSOCIATED WIRING BACK TO SOURCE.

GF

D

DD

D

D

D

D

D

D

D

GF

F

F

F

F

D

D

D

D

D

FF

S

D

84" MH

S

D

S

DD

D

D

D

D

S

D

D D

F

PNL 4-1AAP

X

AP

X

OFFICE

STORAGE

RESTROOM

OFFICE

STAIRS

OFFICE

RESTROOM

HOUSEKEEPING

OFFICE

CLOSET

109A

CLOSET

108A

CLOSET

107A

OFFICE

OFFICE

OFFICE

CLOSET

105A

BREAK

OFFICE

107B

OFFICE

CLOSET

104A

OFFICE

OFFICE

OFFICE

WAITING/ENTRY

OFFICE

CLASSROOM

CLASSROOM

OFFICE

150 KVA

PAD MOUNT

TRANSFORMER

CC

AP

X

CRCR

CC

AP

X

AP

X

AP

X

CR EL

46" MH

CR EL

46" MH

EXISTING RAMP

ED101

GENERAL DEMOLITION NOTES

A. ALL LIGHTING FIXTURES, ELECTRICAL, DATA, SECURITY, AND FIRE ALARM DEVICES WITHIN THE BUILDING 4

AREA OF DEMOLITION SHALL BE REMOVED UNLESS OTHERWISE NOTED.

B. REMOVE WIRING AND CONDUIT BACK TO SOURCE OR LAST POINT OF CONNECTION TO REMAIN.

C. EXISTING EQUIPMENT OUTSIDE OF SCOPE OF WORK BOUNDARIES SHALL BE MAINTAINED. RECONNECT

ANY CIRCUITS CUT PASSING THROUGH DEMOLITION AREAS IN BUILDING OR ON BUILDING SITE.

D. REMOVE, CAP AND RELOCATE EQUIPMENT, OUTLETS, CONDUIT WIRE, ETC. AS SHOWN AND SPECIFIED ON

DRAWINGS, AND AS MAY BECOME NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. VISIBLY

EXAMINE ALL EXISTING WALLS DESIGNATED FOR REMOVAL TO DETERMINE THE CONDUIT AND THE WIRING

THAT WILL REQUIRE CAPPING AND REMOVAL, WHETHER OR NOT SUCH CONDITIONS ARE INDICATED ON

DRAWINGS.

E. FAILURE TO VISIT THE SITE TO TAKE ALL EXISTING CONDITIONS INTO ACCOUNT WILL NOT ALLOW FOR

CHANGES TO THE SCOPE OF WORK. REMOVE ALL CONDUITS AND CONDUCTORS BACK TO THEIR SOURCE.

F. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING FIXTURES, OUTLETS, EQUIPMENT ETC. TO REMAIN IN USE

WHETHER NOTED ON PLANS OR NOT. FIELD VERIFY EXISTING ITEMS TO REMAIN IN USE. RECONNECT

RACEWAYS AND WIRING FOR EXISTING CIRCUITS WHICH MUST BE RE-ROUTED OR WHICH ARE PARTIALLY

ABANDONED TO POWER THE REMAINING OUTLETS ON THE CIRCUIT.

G. REMOVE ALL UNUSED WIRING AND CABLES BACK TO THEIR SOURCE. REMOVE ALL UNUSED CONDUIT THAT

IS EXPOSED OR ABOVE ACCESSIBLE CEILING WHICH IS AFFECTED BY OR IS IN THE AREA OF DEMOLITION

WORK .

H. THE INTENTION OF THE ELECTRICAL DEMOLITION DRAWINGS IS TO DISCONNECT AND REMOVE ALL

ELECTRICAL WORK MADE VOID BY THE SCOPE OF THE CONSTRUCTION AND ALTERATION. FIELD VERIFY

EXACT MATERIAL QUANTITIES REQUIRED TO BE REMOVED.

I. TAKE ALL REMOVED MATERIALS FROM THE PROJECT SITE, EXCEPT FOR THOSE TO BE RELOCATED

STORED OR TURNED OVER TO THE GOVERNMENT.

J. COORDINATE ALL DEMOLITION WORK WITH ALL OTHER TRADES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:1

P

M

ED101

FIRST FLOOR - DEMOLITION PLAN

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

FIRST FLOOR - DEMOLITION PLAN

D R A W I N G N O T E S :

1 DISCONNECT AND REMOVE SECURITY CAMERAS. STORE CAMERAS FOR NEW WORK. REFER TO NEW WORK PLANS FOR

LOCATIONS OF CAMERAS.

2 REMOVE AND SALVAGE HISTORICAL LIGHT. LIGHT TO BE STORED, RE-FURBISHED AND RETROFITTED WITH LED FOR

NEW WORK.

N 1 1/2" = 1'-0"

EXTERIOR PENDANT

G

D

G F

D

G F

GF

GF

G F

GF

G F

G

FGF

D D

S

D

G F

S

S

GF

F FF FF

D

S

OS

D

S

D

M H

D

D

D

D

D

S

S

D D

S

D

S

S

S

GF

GF

D

AP

X

AP

X

CC

CC

OFFICE

CLOSET

216A

OFFICE

CLOSET

215A

RESTROOM

215B

OFFICE

RESTROOM

213B

CLOSET

213A

KITCHEN

STAIRS

MEN

WOMEN

HOUSEKEEPING

OFFICE

CLOSET

208A

OFFICE

CLOSET

207A

CLOSET

206A

OFFICE

OFFICE

CLOSET

205A

RESTROOM

205B

RESTROOM

203B

OFFICE

CLOSET

203A

OFFICE

CLOSET

202A

RESTROOM

202B

OFFICE

OFFICE

CLOSET

219A

RESTROOM

219B

CLOSET

201A

RESTROOM

218B

CLOSET

218A

OFFICE

OFFICE

CLOSET

217A

AP

X

EXISTING

HEAT

PUMP

GENERAL DEMOLITION NOTES

A. ALL LIGHTING FIXTURES, ELECTRICAL, DATA, SECURITY, AND FIRE ALARM DEVICES WITHIN THE BUILDING 4

AREA OF DEMOLITION SHALL BE REMOVED UNLESS OTHERWISE NOTED.

B. REMOVE WIRING AND CONDUIT BACK TO SOURCE OR LAST POINT OF CONNECTION TO REMAIN.

C. EXISTING EQUIPMENT OUTSIDE OF SCOPE OF WORK BOUNDARIES SHALL BE MAINTAINED. RECONNECT

ANY CIRCUITS CUT PASSING THROUGH DEMOLITION AREAS IN BUILDING OR ON BUILDING SITE.

D. REMOVE, CAP AND RELOCATE EQUIPMENT, OUTLETS, CONDUIT WIRE, ETC. AS SHOWN AND SPECIFIED ON

DRAWINGS, AND AS MAY BECOME NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. VISIBLY

EXAMINE ALL EXISTING WALLS DESIGNATED FOR REMOVAL TO DETERMINE THE CONDUIT AND THE WIRING

THAT WILL REQUIRE CAPPING AND REMOVAL, WHETHER OR NOT SUCH CONDITIONS ARE INDICATED ON

DRAWINGS.

E. FAILURE TO VISIT THE SITE TO TAKE ALL EXISTING CONDITIONS INTO ACCOUNT WILL NOT ALLOW FOR

CHANGES TO THE SCOPE OF WORK. REMOVE ALL CONDUITS AND CONDUCTORS BACK TO THEIR SOURCE.

F. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING FIXTURES, OUTLETS, EQUIPMENT ETC. TO REMAIN IN USE

WHETHER NOTED ON PLANS OR NOT. FIELD VERIFY EXISTING ITEMS TO REMAIN IN USE. RECONNECT

RACEWAYS AND WIRING FOR EXISTING CIRCUITS WHICH MUST BE RE-ROUTED OR WHICH ARE PARTIALLY

ABANDONED TO POWER THE REMAINING OUTLETS ON THE CIRCUIT.

G. REMOVE ALL UNUSED WIRING AND CABLES BACK TO THEIR SOURCE. REMOVE ALL UNUSED CONDUIT THAT

IS EXPOSED OR ABOVE ACCESSIBLE CEILING WHICH IS AFFECTED BY OR IS IN THE AREA OF DEMOLITION

WORK .

H. THE INTENTION OF THE ELECTRICAL DEMOLITION DRAWINGS IS TO DISCONNECT AND REMOVE ALL

ELECTRICAL WORK MADE VOID BY THE SCOPE OF THE CONSTRUCTION AND ALTERATION. FIELD VERIFY

EXACT MATERIAL QUANTITIES REQUIRED TO BE REMOVED.

I. TAKE ALL REMOVED MATERIALS FROM THE PROJECT SITE, EXCEPT FOR THOSE TO BE RELOCATED

STORED OR TURNED OVER TO THE GOVERNMENT.

J. COORDINATE ALL DEMOLITION WORK WITH ALL OTHER TRADES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:2

P

M

ED102

SECOND FLOOR - DEMOLITION

PLAN

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION 4

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N 1/4" = 1'-0"

SECOND FLOOR - DEMOLITION PLAN

D R A W I N G N O T E S :

1 DISCONNECT AND REMOVE SECURITY CAMERAS. STORE CAMERAS FOR NEW WORK. REFER TO NEW WORK PLANS FOR

LOCATIONS OF CAMERAS.

2 EXISTING HEAT PUMP TO BE REMOVED BY OTHERS. DISCONNECT AND REMOVE CIRCUITRY BACK TO SOURCE. REMOVE

ASSOCIATED DISCONNECT SWITCH.

3 REMOVE CONDUIT ON OUT OF BUILDING FEEDING SPOT LIGHTS.

D OS

OS

OS

OS OS

OS OS

OS

OS

OS

OS

OS

OS

OS

OS

OS OS

OS

OS

D D

D

OS

OS

D D

OS O

S

OS O

S

OS OS

DD

D

OS

O S

OS

OS

OS

OS

C1 C1 C1

C1

C1

C1C1

W1

W1

W1 W1

X2

A2A3

A1

A2

A1

A2

B1

B1

B1

B1

B1

A22 A22

B1

A3

A2

A2A3A2

X2

X1

C1 C1 emA3 em

STAIR A

S000A

ELEC RM

E001

ELEVATOR

E000

STORAGE

DETECTIVE

GROUND DEFENSE TRAINING

PIV VISITOR

PIV STAFF

PIV PICTURE RM

DEPUTY CHIEF

CHIEF

ARMORY

SECURE CAGE

ADMIN/PIV/CHECK IN

MAJOR OFFICE

MEN

TOILET

006B

SHOWER

006A

ELEC/UTILITY

SOUTH CORRIDOR

STAIR B

S000B

H.C.SUPP.

H.C.

WOMEN

SHOWER

007A

TOILET

007B

BREAK/WORK RM

SUPPLY

EMERGENCY MANAGER

EAST CORRIDOR

SOUTH CORRIDOR

em em

TRAINING SARGENT

COMM DEVICE STO.

EVIDENCE STO.

PIV STORAGE

ELEC/UTILITY

X1

1 1

1 1 1

A24

A24 A24

A24

A22

A22

A22

A22 A22

A22 A22A22

A22 A22

A22

A22A22

A22

A22

A24

A22A24

A22

A22 A24

A24A22

A24

A22 A22

A22 A22

1 1

B1 B1

B1B1

W4

W4

UNLESS OTHERWISE NOTED LIGHTING ON THIS FLOOR IS CIRCUITED FROM THE

FOLLOWING PANELBOARDS:

A. EMERGENCY - 4-EM1

B. NORMAL - 4-BA

1 1

1 1 1

A22 A22

A22

A22

A22

A22

A22

A22

A22 A22

A22 A22

A22

A22

A22

A22

A22

A22

A22

A24

A24

1 1

2 2

2 2

2 2

2 2

2 2 2

3 3 3

3 3

2 2

4-EM1-4

4-EM1-5

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:2

P

M

EL100

BASEMENT - LIGHTING PLAN

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

N

1/4" = 1'-0"

BASEMENT - LIGHTING PLAN

OS

OS

OS

OSOS

OS

OS

OS

D

D

D D D

D

D D

D

OS

OS

X1

X1

X1

X1

X2

A1

A1

A1A1

A2A3A2

A3

B1B1B1B1

B1B1B1B1

B1

C1

C1

C1

B1 B1 B1 B1

A1

B1

B1

B1

A1 A1 A1

B1

B1

B1

B1

B1

B1 B1 B1

A3

A2A3A2

B1

F1

F1 em em em

B1

A1 em em em em em

D1

ELEV LOBBY

SECURITY SCREEN AREA

ELEVATOR

E100

LEAF COORD STAFF

QUALITY SAFETY STAFF

SYSTEM REDESIGN STAFF

QUALITY SAFETY SUP

WEST CORRIDOR

EAST CORRIDOR

SOUTH CORRIDOR

CHIEF, SYSTEM REDESIGN

BREAK/WORK RM

SUPPLY

WOMEN

MEN

STAIR B

S100B

ELEC

TR

VOLUNTARY SERVICE

CONFERENCE/INCIDENT

COMMAND

QUALITY MANAGER

X1

F1

F1

LEAF COORD OFFICE

STAIR A

S100A

DS

PC

A22 A22

A22 A22

A22 A22

A22 A22

A22

A22

A22 A22

A22 A22

A22 A22

A22 A22

A22

A24

A24

A22

A22

A22

A24

A24 A24

A24

A24

A24

A22 A22

A22 A22

A22

A24

A24

B1 B1

B1B1

B1 B1

B1B1

W4 W4

W4

W4 emem em em em em

K1

4-EM1-4

4-EM1-4

4-EM1-5

4-EM1-5

6 6 6

6 6 6 6

A22

1 1 1 1 1

11111

1 1 1

UNLESS OTHERWISE NOTED LIGHTING ON THIS FLOOR IS CIRCUITED FROM THE

FOLLOWING PANELBOARDS:

A. EMERGENCY - 4-EM1

B. NORMAL - 4-1A

2 2 2 2 2

2 2 2 2 2

2 2 2 2 2

3 3 3 em

H1 H1 H1 H1

H1 em em em em em

7 7 7

M1

X1

X1

N

1/4" = 1'-0"

FIRST FLOOR - LIGHTING PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:3

P

M

EL101

FIRST FLOOR - LIGHTING PLAN

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

ISSUED FOR

CONSTRUCTION

FAYETTEVILLE

VA MEDICAL

CENTER Approved: FAYETTEVILLE VA MEDICAL CENTER

D R A W I N G N O T E S :

1 INSTALL SALVAGED HISTORICAL LIGHT FIXTURE. MOUNT AT 7'-6" AFF.

2 PROVIDE PHOTOCELL ON PORCH ROOF AND CONNECT TO EXTERIOR LIGHTING.

OS

OS OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

D

D D/3 D DD D

O S

OS D

D D

D

D

D/3

W1 W1

W1 W1

A1

A1

A1

A1

A2A3A2

A3

A1

A1

C1

A2A3A2

A3

B1 B1 B1 B1

B1

B1

B1B1

B1

B1

X2 em emem

X1

STAIR A

S200B

ELEV LOBBY

200 ELEVATOR

E200

EAST CORRIDOR

VISITOR

NORTH CORRIDOR

SECRETARY

ASSISTANT DIRECTOR

SECRETARY

SECRETARY

NORTH CORRIDOR-3

216-3

CHIEF OF STAFF

NURSE EXECUTIVE

HSS

HSS

HSS

HSS

NORTH CORRIDOR-1

216-1

NORTH CORRIDOR-2

216-2

PUBLIC AFFAIRS

COMPLIANT OFFICER

ASSOCIATE DIRECTOR

SECRETARY

SECRETARY

SOUTH CORRIDOR-1

216-1

SUPPLY

PRIVATE TOILET

DIRECTOR

SHAFT

ELEC

STAIR B

S201B

MEN

WOMEN

BREAK/WORK RM

RECEP/WAITING

SUPPLY

NORTH CORRIDOR

SOUTH CORRIDOR

A3 A3 A3 A3

X1

DS

X1

B1

A22 A22

A22 A22

A22A22

A22 A22

A22A22

A22 A22

A22A22

A22

A22

A22

A22A22

A22A22

A22A22

A22

A24

A24A22A22

A22 A22A22

A22 A22

A22A22

A22

A22 A22

A22

A22

A24

A24

A22

A22

A22

A22 A22

A22 A22

A22

A22

W4 W4

W4

W4 a b em em

UNLESS OTHERWISE NOTED LIGHTING ON THIS FLOOR IS CIRCUITED FROM THE

FOLLOWING PANELBOARDS:

A. EMERGENCY - 4-EM1

B. NORMAL - 4-2A

1 1

1 1

1 1 1

1 1 1

1 1

1 1

1 1

1 1

11 1 1

1 1

2 2

2 2 2

2 2

2 2

2 2

2 2 2

2 2 2 2

4-EM1-5

4-EM1-5

3 3 3

3 3

4-EM1-4 4-EM1-4

8 8

4-EM1-8

8 8

A4 A5

A4

A4em em em em

8 8 8

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /F a y e tt e v ill e N

C V

A

B ld g

R e n o v a ti o n

/F F

E

F a y e tt e v ill e

R e n o v a te B

M E

P rv t

/2

/2

:4

:4

P

M

EL102

SECOND FLOOR - LIGHTING PLAN

07/24/2023 JB CLG

RENOVATE HISTORIC BUILDING 4 565-20-101

2300 RAMSEY STREET, FAYETTEVILLE, NC 28301

IS…