FIRE_ALARM_CONTROL_PANEL_MANUAL.pdf

PDF 3 MB Posted

Attached to
Volusia County Life Safety Systems Inspection, Testing and Repairs
Solicitation number
26-B-18LL
Issued by
Volusia County, Florida

About this file

Fire Alarm Control Panel Manual and Volusia County Life Safety Systems Solicitation Summary

This document is a comprehensive technical manual for the NFW-100X Series Fire Alarm Control Panel manufactured by Honeywell, combined with a state procurement solicitation from Volusia County, Florida. The manual provides detailed installation, programming, and operating instructions for an addressable fire alarm system with integrated communications capabilities, including POTS (Plain Old Telephone Service) and IP-based central station reporting. The NFW-100X features a single SLC loop supporting up to 198 addressable devices (99 detectors and 99 control/relay/monitor modules), four notification appliance circuits (NACs) capable of 2.5 amps per circuit, and optional expansion modules including cellular GSM communicators, wireless gateways, and annunciator modules. The solicitation requires contractors to perform comprehensive life safety systems services—including annual fire alarm system testing and inspection per NFPA 72 standards, semi-annual and annual clean agent fire suppression system inspections per NFPA 2001 requirements, and 24/7 emergency repair services—across five Volusia County facilities in Daytona Beach and DeLand, Florida. Mandatory pre-bid site visits are scheduled for December 4-5, 2025, with written questions due by December 19, 2025, and bids due electronically by January 8, 2026, at 3:00 p.m.

The contract is structured as a three-year initial term with two optional one-year renewals, with pricing to be evaluated based on total cost, delivery capability, past performance, and technical compliance. All technicians must hold NICET certification, and supervisory personnel must have a minimum of five years' experience in fire protection systems. The solicitation offers a local preference of up to five percent for qualified local businesses with documented permanent locations in specified counties for at least six months prior to the closing date. Contractors must provide three references from similar government contracts and maintain comprehensive insurance coverage, including workers' compensation, commercial general liability, motor vehicle liability, and pollution liability with Volusia County named as an additional insured. No specific incumbent vendor is identified, and while an explicit contract award value is not stated, the detailed price sheet structure indicates substantial annual inspection and maintenance services with pricing for labor, parts, materials, and emergency response capabilities across the five specified facilities.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Document LS10131-001NF-E Rev: C

7/25/2018 ECN: 18-323

Addressable Fire Alarm Control Panel

NFW-100X

Manual

2 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018

Fire Alarm & Emergency Communication System Limitations While a life safety system may lower insurance rates, it is not a substitute for life and property insurance!

An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel (FACP) with remote notifica-tion capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.

An emergency communication system—typically made up of an automatic fire alarm system (as described above) and a life safety communication system that may include an autonomous control unit (ACU), local operating console (LOC), voice communication, and other various interoperable communication methods—can broadcast a mass notification message. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire or life safety event.

The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premises following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. This document can be found at http:// www.systemsensor.com/appguides/. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:

Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.

Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:

• Barriers such as closed or partially closed doors, walls, chim-neys, even wet or humid areas may inhibit particle or smoke flow.

• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.

• Smoke particles may be blown away from detectors by air out-lets, such as air conditioning vents.

• Smoke particles may be drawn into air returns before reaching the detector.

The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a devel-oping fire at the location of detectors, the detectors will not go into alarm.

Smoke detectors, even when working properly, have sensing limita-tions. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires.

Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.

IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signal-ing, and/or power. If detectors are not so located, a developing fire may damage the alarm system, compromising its ability to report a fire.

Audible warning devices such as bells, horns, strobes, speak-ers and displays may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert peo-ple with a disability or those who have recently consumed drugs, alcohol, or medication. Please note that:

• An emergency communication system may take priority over a fire alarm system in the event of a life safety emergency.

• Voice messaging systems must be designed to meet intelligibility requirements as defined by NFPA, local codes, and Authorities Having Jurisdiction (AHJ).

• Language and instructional requirements must be clearly dis-seminated on any local displays.

• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.

• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond to or comprehend the meaning of the signal. Audible devices, such as horns and bells, can have different tonal patterns and frequencies. It is the property owner's responsibility to conduct fire drills and other training exercises to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.

• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.

A life safety system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.

Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.

Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.

The most common cause of life safety system malfunction is inad-equate maintenance. To keep the entire life safety system in excel-lent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Envi-ronments with large amounts of dust, dirt, or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Mainte-nance should be scheduled as required by National and/or local fire codes and should be performed by authorized professional life safety system installers only. Adequate written records of all inspec-tions should be kept.

Limit-D2-2016 http://www.systemsensor.com/appguides/

NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 3

Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING - Several different sources of power can be con-nected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.

CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming opera-tion or change in site-specific software. Re-acceptance testing is required after any change, addition or deletion of system compo-nents, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadver-tently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.

This system meets NFPA requirements for operation at 0-49º C/ 32-120º F and at a relative humidity . However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity.

Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.

Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R.

drop from the specified device voltage.

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from light-ning transients and interference, proper grounding will reduce sus-ceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Con-sult with the Technical Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs. Over-tighten-ing may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any cir-cuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and pro-gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.

Precau-D1-9-2005

FCC Warning WARNING: This equipment generates, uses, and can radi-ate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interfer-ence to radio communications. It has been tested and found to comply with the limits for class A computing devices pur-suant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his or her own expense.

Canadian Requirements

This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Depart-ment of Communications.

Le present appareil numerique n'emet pas de bruits radio-electriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.

HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus™, eVance®, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®, Honeywell®, Intelligent FAAST®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.

Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.

©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

4 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018

Software Downloads In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system.

Contact Technical Support with any questions about software and the appropriate version for a specific application.

Documentation Feedback Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.

Please include the following information:

• Product name and version number (if applicable)

• Printed manual or online Help

• Topic Title (for online Help)

• Page number (for printed manual)

• Brief description of content you think should be improved or corrected

• Your suggestion for how to correct/improve documentation

Send email messages to:

FireSystems.TechPubs@honeywell.com

Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 5

Table of Contents

Section 1: Product Description 1.1: Features and Options 1.2: Specifications 1.3: Controls and Indicators 1.4: Components

1.4.1: Intelligent Addressable Detectors 1.4.2: Intelligent Addressable Modules 1.4.3: Addressable Device Accessories

End-of-Line Resistor Assembly Power Supervision Relay EOL-C(R/W) Mounting Plate

1.5: Optional Modules 1.6: Accessories

1.6.1: FS-Tools Programming Utility 1.6.2: Dress Panel 1.6.3: Trim Ring 1.6.4: Battery Box

BB-26

NFS-LBB

1.6.5: Battery Charger CHG-75 Battery Charger CHG-120 Battery Charger

1.6.6: NFC-50/100

1.6.7: NFC-FFT

1.6.8: FWSG Wireless Gateway 1.6.9: ANN-BUS Annunciators/Modules

Guidelines N-ANN-80/N-ANN-100 Remote Fire Annunciators N-ANN-S/PG Serial/Parallel Interface Module N-ANN-I/O LED Driver Module N-ANN-LED Annunciator Module N-ANN-RLY Annunciator Module

1.7: Getting Started 1.8: Telephone Requirements and Warnings

1.8.1: Telephone Circuitry 1.8.2: Telephone Company Rights and Warnings

Section 2: Installation 2.1: Mounting the Backbox 2.2: Power

2.2.1: AC Power and Earth Ground Connection 2.2.2: Battery Power 2.2.3: Special Application DC Power Output Connection

2.3: Relays 2.4: Notification Appliance Circuits

2.4.1: Class B NAC Wiring 2.4.2: Class A NAC Wiring

2.5: Remote Synchronization Output 2.6: UL Power-limited Wiring Requirements 2.7: IPOTS-COM Communicator

Wiring Dip Switches

2.8: Optional Module Installation

2.8.1: CELL-CAB-N/CELL-MOD

Installation Wiring

2.8.2: PWRMOD24 NAC Expander Installation and Wiring

2.8.3: 4XTM Transmitter Module Installation 2.8.4: ANN-BUS Annunciators/Modules

ANN-BUS Wiring

6 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018

ANN-BUS Device Addressing N-ANN-80 Remote Fire Annunciator N-ANN-100 Remote Fire Annunciator N-ANN-S/PG Serial/Parallel Interface Module N-ANN-I/O LED Driver Module N-ANN-LED Annunciator Module N-ANN-RLY Annunciator Module

2.8.5: Printer Printer Configuration

2.8.6: NFC-FFT Firefighter Telephone 2.8.7: FWSG Wireless Gateway

2.9: Automatic Audio Panel Control

Section 3: Programming 3.1: Programming Data Entry 3.2: User Programming 3.3: Initial Power-up 3.4: Programming Screens Description 3.5: Programming and Passwords 3.6: Master Programming Level

3.6.1: Autoprogram 3.6.2: Point Program

Detector Programming Module Programming

3.6.3: Zone Setup Enable Disable Special Purpose Zone Zones Installed Zones Enabled Zones Disabled Zone Type Zones Available Zone Message

3.6.4: Loop Setup Class Loop Protocol Device Addressing

3.6.5: System Setup Function Keys Banner Time-Date Timers NAC (Notification Appliance Circuit) Relays Canadian Option Waterflow Silenceable MNS Override Auxiliary Power Trouble Reminder Language Charger Enable 4XTM Supervision Remote Sync Enable

3.6.6: History View Events Erase History

3.6.7: Communicator Communicator Installed POTS Settings IP Settings Primary and Secondary Communication Paths

NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 7

Trouble Report Limit (Dialer Runaway Prevention) Report Style Event Codes

3.6.8: Annunciators ANN-BUS Setup ANN-BUS Options

3.6.9: Password Change Invalid Password

3.6.10: Clear Program 3.6.11: Program Check

3.7: Maintenance Programming Level 3.7.1: Disable Point 3.7.2: History 3.7.3: Program Check 3.7.4: Walktest 3.7.5: System 3.7.6: Zone Setup

Section 4: Operating Instructions 4.1: Panel Control Buttons

4.1.1: Acknowledge 4.1.2: Alarm Silence 4.1.3: Drill/Hold 2 Sec 4.1.4: Reset 4.1.5: Function Keys F1-F4

4.2: LED Indicators 4.3: Normal Operation 4.4: Trouble Operation 4.5: Alarm Operation 4.6: CO Alarm Operation 4.7: Supervisory Operation 4.8: Process Monitor Operation 4.9: Hazard/Tornado Condition Operation 4.10: Medical Alert Condition Operation 4.11: Mass Notification Operation 4.12: NAC Operation 4.13: Programmed Zone Operation 4.14: Disable/Enable Operation 4.15: Waterflow Circuits Operation 4.16: Detector Functions 4.17: Time Functions: Real-Time Clock 4.18: Synchronized NAC Operation 4.19: Coded Operation 4.20: Presignal 4.21: Positive Alarm Sequence 4.22: Special System Timers

4.22.1: Silence Inhibit Timer 4.22.2: Autosilence Timer 4.22.3: Trouble Reminder 4.22.4: Waterflow Retard Timer 4.22.5: Alarm Verification (None or One Minute) 4.22.6: Control Module Delay Timer

4.23: Walktest 4.24: Read Status

4.24.1: System Point 4.24.2: Zones 4.24.3: Trouble Reminder 4.24.4: Timers 4.24.5: NACs 4.24.6: Relays 4.24.7: Program Check 4.24.8: History

8 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018

4.24.9: Annunciators 4.24.10: Communicator 4.24.11: Print

Chamber Value Drift Compensation Maintenance Alert

4.24.12: Time-Date 4.24.13: Battery Charger 4.24.14: 4XTM Supervision 4.24.15: Remote Sync

Section 5: Central Station Communications - POTS Transmission 5.1: Transmittal Priorities

Section 6: FS-Tools Upload/Download 6.1: FS-Tools Upload/Download 6.2: Transferring a Program

6.2.1: Security Features Secret Code Verification Time-out at Control Panel Error Checking Central Station Data Protection

Section 7: USB Upload/Download 7.1: USB Upload/Download

Section 8: Firmware Upgrade 8.1: Firmware Upgrade

Section 9: Power Supply Calculations 9.1: Overview 9.2: Calculating the AC Branch Circuit 9.3: Calculating the System Current Load

9.3.1: Overview 9.3.2: How to Calculate System Current Load

9.4: Calculating the Battery Size 9.4.1: NFPA Battery Requirements 9.4.2: Selecting and Locating Batteries

Appendix A: Software Zones A.1: Correlations

Appendix B: Default Programming

Appendix C: NFPA Standard-Specific Requirements C.1: MBT-1 Municipal Box Trip - Silenceable

Appendix D: Wire Requirements D.1: NAC Wiring

Appendix E: HVAC Control E.1: Control Module Operation

E.1.1: HVAC SHUTDOWN

E.2: Monitor Module Operation

E.2.1: HVAC RESTART

E.2.2: HVAC OVRRIDE

Appendix F: Ademco Contact ID Format Event Code Descriptions F.1: Transmission Format Between DACT and Receiver F.2: Ademco Contact ID Typical Printout

Appendix G: Central Station Points

Appendix H: NFPA Requirements

Appendix I: Open/Short/Ground Trip Values

Index

NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 9

Slide-in Labels

NFW-100X Series Fire Alarm Control Panel Operating Instructions

It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the stan-dards set forth by the following regulatory agencies:

• Underwriters Laboratories

• National Fire Protection Association

NFPA Standards

NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code NFPA 720 Carbon Monoxide Detection and Warning Equipment

Underwriters Laboratories Documents:

UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and Systems UL 2075 Standard for Gas and Vapor Detector and Sensors UL 2572 Communication and Control Units for Mass Notification Systems

Other:

EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)

NOTIFIER Documents:

NOTIFIER Device Compatibility Document #15378 FireWarden SLC Wiring Manual Document #52304 ONYX Series SLC Wiring Manual Document #51253 NFC-50/100 Manual Document #LS10001-001NF-E NFC-FFT Manual Document #LS10031-001NF-E Notifier Wireless Gateway Manual Document #LS10036-000NF-E CHG-120 Battery Charger Document #50641 CHG-75 Battery Charger Document #51315 IPOTS-COM POTS/IP Communicator Document #LS10184-000GE-E PWRMOD24 NAC Power Module Document #LS10185-000GE-E CELL-CAB-N GSM Communicator Document #LS10186-001NF-E N-ANN-80 Product Installation Document Document #52986 N-ANN-100 Product Installation Document Document #LS10205-001NF-E N-ANN-(R)LED Product Installation Doc. Document #53317 N-ANN-I/O Product Installation Document Document #151243 N-ANN-RLY Product Installation Document Document #53318 N-ANN-S/PG Product Installation Document Document #151424

This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Sys-tems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such oper-ation requires the approval of the local Authority Having Jurisdiction (AHJ).

Before proceeding, the installer should be familiar with the following documents.

10 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018

R T

N

O U

T

250V

C O

M M

U N

IC

A

T O

R

D

IS

P L

A Y

P W

R

V

2ANPM

R T

N

O U

T

B A

T T

E R

Y N

/L

E A

R T

H H

/L

U S

B -A

C N

O N

C C

N O

N C

C N

C N

O

S U

P V

T R

B L

A L

R M

A N

N -L

C

ES200-PCA REV

ES50-PCA REV

S L

C

P W

R

R M

T S

Y N

C A

N N

-B U

S P

R I

A N

N -B

U S

S E

C

N A

C

N A

C

N A

C

N A

C

S L

C L o o p su pe rv is e d

S ec o n d ar y A

N N

-B U

S to

A nn un ci a to rs

(p o w er

-li m ite d su pe rv is ed

P ri m a ry A

N N

-B U

S to

A n n un ci at rs

(p w er -li m ite d

R e m o te S y n ch ro n iz at io n O u tp u t

S up er vi se d, P o w er

L im ite d c irc ui ts

V

D C f ilt er ed

0.

a m p m a xi m u m

R eq ui re s a

.7

K oh m E n d-o f-

L in e R e si st o r

S up er vi so ry

A la rm

T ro ub le

P ro g ra m m ab le R el ay s

F ix ed T ro u b le

R el ay N on -s u pe rv is e d re la y co n ta ct s

C on ta ct r a tin g

.0 a m p s

V D

C re si st iv e)

.5 a m p s

V A

C re si st iv e

C on ta ct s sh o w n b el ow in n rm a l c on di tio n

A C p o w er ith n o al ar m

, t ro u bl e , o r su pe rv is or y ac tiv ity

A C

F a il S af e

T ro u bl e re la y sw itc he s to th e N

O p os iti o n d u rin g tr o ub le c o nd iti o ns a nd u de r lo ss o f a ll p ow er

F ac to ry d e fa ul t re la y p ro gr am m in g)

N A

C

N

A C

N A

C

N

A C

N o ti fi ca ti o n

A p p li an ce

C ir c u it s

N A

C

1, #3

C la ss B o r

C la ss A

(S p er vi se d

, P o w e r- L im ite

d) (S p e ci al a p pl ic at io n)

.5 m p s m ax pe r ci rc u it E

LR

s, .7 K

, 1 /2

W (f or C la ss

A iri n g)

A u xi lia ry ro ub le

In p ut

C A

U T

IO

N

H

IG

H

V O

LT

A

G E

A C

P o w er

(S u pe rv is e d, N o np ow er

-L im ite d o r

V

A C

/6

H z, .2 a m ps

B a tt e ry

V D

C , s u pe rv is e d no n po w er

-li m ite d

A H m ax im um

U S

B P o rt

J fo r fir m w re pd a te s, lo ca l p ro gr am m g si n p er so al co m p ut e r nd

F S

-T oo ls til ity o th um b dr iv e

T o d is a b le g ro u n d fa u lt d et e ct io n , s lid e

S W to t he le ft.

Im p o rt an t!

D is a b lin g

G ro u nd

F au lt D e te ct io n v o id s U

L/ N

F P

A C la ss id e n tif ic at io n s fo r ci rc u its

D is ab le

G ro u n d F a u lt o n ly w ith th e a p p ro va l o f th e A

H J

(A u th o rit y

H a vi n g Ju ri sd ic tio n)

S p ec ia l A p p lic at io n D

C P o w er O u tp u ts

V D

C

N o n su p er vi se d , P o w er -L im ite d c irc u its N on re se tt ab le

P o w er s u ita bl e fo r p ow e rin nu nc ia to rs

; R e se tt a bl e P o w e r su ita bl e fo r po w e rin g sm ok e de te ct or s.

A u x P o w e r

1:

R es e tt ab le o r N o nr es e tta bl e P ow er

V D

C fi lte re d, p o w er -l im ite d (1

.0 am p m ax im um

C la ss A o r

C la ss B w ir in g p os si b le . S up e rv is io n re qu ir ed fo r

C la ss B w iri n g.

S up er vi se w ith a p ow e r su p er vi si on r e la y

E O

LR

-1

A u x P o w e r

2:

N o nr es e tta bl e o r R es e tta b le P ow er

V

D C fi lte re d

, p ow e r-lim ite d (1

.0 am p m a xi m u m

S up er vi si o n re qu ire d

B as ic S ys te m C on ne ct io ns

K ey p ad

C on n ec to r

N P

M C o n n ec to r

C on n ec tio n to th e P

W R

M O

D

N A

C p o w er e xp a n de r m o du le

C on ne ct io n t o th e

IP

O

T S

C

O M c o m m un ic at o r ca rd fo

P O

T S a n d

IP

r ep o rt in g

J

J

3:

X

M co nn ec tio n

S W

X

S up er vi so ry R el a y:

S lid e sw itc h to t he d ow n p os iti o to en bl e th e r el a y w he n th e

X

T is st al le d

NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 11

Peripheral Devices and Their Documents:

SW2

SW3

S W

LED1

L ED2

LED3

L E

D

L E

D

L E

D

L E

D

L E

D

J3 J5J4

ETHLINE2LINE1

Addressable Devices and SLC Wiring Doc. #52304 and #51253 Wireless Gateway Doc. #LS10036-001NF-E

CHG-120 Charger Doc. #50641

ANN-BUS - TB9/TB10

SLC Loop - TB12

Battery Connector - J15 n fw

0x a nn pe ri.

w m f

N-ANN-80

LCD Text Annunciator

Doc. #52986

N-ANN-I/O

LED Driver

Doc. #151243

N-ANN-S/PG

Printer Driver Doc. #151424

CHG-75 Charger Doc. # 51315

N-ANN-(R)LED

LED Display Doc. #53317

N-ANN-RLY

Relay Card

Doc. #53318

4XTM

Reverse Polarity Module

J12 & J13

ANN Audio Control for NFC-50/100 Doc. #LS10001-001NF-E

IPOTS-COM

POTS and IP Communicator Doc. #LS10184-000GE-E

J6

CELL-CAB-N

GSM Communicator Doc. #LS10186-001NF-E

PWRMOD24 NAC Power Expander Doc. #LS10085-000GE-E

J16

J15

N-ANN-100

LCD Text Annunciator

Doc. #LS10205-001NF-E

TB2

12 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018

Section 1: Product Description The NOTIFIER NFW-100X is an addressable FACP (Fire Alarm Control Panel) with a pre-installed communicator card that is compact, cost effective, intelligent, and has an extensive list of powerful features which offers the latest in fire protection technology. The power supply and all electronics are housed in a metal cabinet, providing a complete fire control system for most applications. Optional mod-ules, which plug into the main circuit board, are available for special functions. Available accessories include multi-technology central station communicators, LED, graphic, and LCD annunciators, reverse polarity/city box transmitter, local and remote upload/download software, and remote power expansion.

Inventory

When NFW-100X shipment is received, check that all parts have been included in shipment. The NFW-100X shipment consists of one of each of the following:

main circuit board with display backbox with door plastic bag containing screws, cables, ELRs, terminal blocks, etc.

1.1 Features and Options

• Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Telephone Service) Central Station Communicator

• Optional CELL-MOD or CELL-CAB-N GSM Central Station Communicator over AlarmNet

• Automated activation of the NFC-50/100 First Command Center

• NFC-FFT Firefighter Telephone option

• Compatible with SWIFT® wireless devices

• FlashScan® polling protocol for faster SLC response time

• SLC operates up to 10,000 ft. (3,000 m) in FlashScan mode with twisted, unshielded wire (refer to “Wire Requirements” on page 142)

• Single addressable SLC loop which meets NFPA Class A, Class B, and/or Class X requirements

• 198 addressable device capacity (99 detectors and 99 control/relay/monitor modules)

• 99 software zones

• Four (4) Class B or four (4) Class A NAC (Notification Appliance Circuits) circuits - special application power

• 3.0 amps total 24 VDC output circuit current in alarm condition

• NAC power expandable by 3.0 amps with optional PWRMOD24 module

• Four programmable function keys for ease of maintenance

• Two programmable relay outputs and one fixed trouble relay

• Synchronization output for remote power supply applications (special application)

• Built-in Programmer

• 80-character LCD display (backlit)

• Real-time clock/calendar with daylight savings time control

• History file with 1,000 event capacity

• Addressable sounder base compatibility

• Advanced fire technology features:

Automatic drift compensation Maintenance alert Detector sensitivity test capability (NFPA 72 compliant) Automatic device type-code verification Point trouble identification

• Waterflow selection per module point

• Alarm verification selection per detector point

• Walktest, silent or audible

• PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)

• Silence inhibit timer option per NAC

• Autosilence timer option per NAC

• Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability

• Selectable strobe synchronization per NAC

• Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or N-ANN-80/N-ANN-100 Remote annunciator

• Auto-program (learn mode) reduces installation time. Reports two devices set to the same address

• Password and key-protected nonvolatile memory

• User programmable password

• Fully programmable from local keypad

• Optional FS-Tools programming utility for local or remote Upload/Download of programming and data (available for download from www.notifier.com)

• Compatible with FireWarden’s and NOTIFIER’s addressable devices (refer to the FireWarden/ONYX SLC Wiring Manuals for a list of compatible addressable devices)

• Optional 4XTM module (conventional reverse polarity/city box transmitter)

• ANN-BUS for connection to following optional modules:

N-ANN-80 Remote Annunciator (UL applications only) NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 13

Product Description Specifications N-ANN-100 (FM only) N-ANN-I/O LED Driver N-ANN-S/PG Printer Module N-ANN-RLY Form-C Relay Module N-ANN-LED Annunciator Module annunciates alarm, trouble and supervisory (required for emergency signaling) N-ANN-RLED Annunciator Module annunciates alarms only

• Automated activation of the legacy NFV-25/50(ZS/T) FireVoice audio panel

1.2 Specifications

Refer to Illustration on page 10 for terminal locations and connections.

AC Power - TB13

Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 amps, auto-sensing. No switch or jumper required.

Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation

Battery (Sealed Lead Acid Only) - J15

Maximum Charging Circuit: Normal Flat Charge – 27.6 VDC @ 1.5 amps Maximum Battery Charger Capacity: 18 Amp Hour (FACP cabinet holds maximum of two 18 Amp Hour batteries. The BB-26 Battery Box holds two 26 Amp Hour batteries and the CHG-75. For greater than 26 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120 Battery Charger and NFS-LBB Battery Box).

Minimum Battery Size: 7 Amp Hour Note: Refer to the programming section to disable the FACP battery charger when using an external battery charger.

Communication Loop - TB12

24 VDC nominal, 27.6 VDC maximum Maximum length - refer to “Wire Requirements” on page 142) Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited circuit Refer to SLC Wiring manuals for wiring information

Notification Appliance Circuits - TB4, TB5, TB6, & TB7

Four (4) Class B NAC circuits or four (4) Class A circuits Special Application, filtered power Power-limited circuitry NAC wiring requirements refer to “NAC Wiring” on page 143 Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 2.5 amps special application, 250 mA regulated (see Figure 1.1 on page 15) End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) required for each circuit; system capable of 1.9 kΩ - 22 kΩ ELR range.

Refer to the Device Compatibility Document for listed compatible devices

Two Programmable Relays and One Fixed Trouble Relay - TB1, TB2, & TB3

Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays Refer to Figure 2.6 on page 26 for information on power-limited relay circuit wiring

Nonresettable or Resettable Special Application Power (24 VDC Nominal) - TB11, Terminals 1 (+), 2 (-), 3(+), & 4(-) (programmable)

Factory-set as nonresettable, suitable for powering annunciators Programmable Class A or Class B wiring Maximum ripple voltage: 20mVRMS Total DC current available is up to 1.0 amp (see Figure 1.1 on page 15) Power-limited circuit Note: Refer to the programming section to configure power as resettable/non-resettable and for Class A or Class B wiring.

Resettable or Nonresettable Special Application Power (24 VDC Nominal) - TB11, Terminals 5 (+) & 6 (-)

Factory-set as resettable, suitable for powering four-wire smoke detectors Class B wiring only Maximum ripple voltage: 20 mVRMS Total DC current available is up to 1.0 amp (see Figure 1.1) Power-limited circuit Refer to the Device Compatibility Document for listed compatible devices Note: Refer to the programming section to configure power as resettable/non-resettable.

14 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018

Specifications Product Description Remote Sync Output - TB8

Remote power supply synchronization output 24 VDC nominal special application power Maximum current is 350 mA End-of-Line Resistor: 4.7KΩ Output linked to NAC 1 control Supervised and power-limited circuit Programmable Class A or Class B wiring

Secondary ANN-BUS - TB10

ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B) Annunciators require non-resettable power

Primary ANN-BUS - TB9

Class A or Class B wiring ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B) Class A wiring uses Terminal 3 (+/A Return) and Terminal 4 (-/B Return) Annunciators require non-resettable power

The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP.

TB5

TB6

TB7

TB8

Figure 1.1 Current Availability without PWRMOD24 Option

Refer to the battery calculations section for additional information.

Standby

2.0 amps max per panel

Special Application Nonresettable or Resettable Power

Special Application Resettable or Nonresettable Power

NAC #1

NAC #2

NAC #3

NAC #4

1.0 amp max per circuit

2.5 amps max per circuit

Alarm

3.0 amps max* per panel

Remote Synchronization

Output

*Note: When the option module PWRMOD24 is installed, an additional 3.0 amps of alarm power is available across NAC #1 through NAC #4 and the remote synchronization output expanding max power to 6.0 amps

1.0 amp max per circuit

2.5 amps max per circuit

2.5 amps max per circuit

2.5 amps max per circuit

0.35 amp max per circuit NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 15

Product Description Controls and Indicators

1.3 Controls and Indicators

LCD Display

The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.

Key Panel

Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed below. The key panel, which is visible with the cabinet door closed, has 30 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.

LED Indicators

LED indicators are provided to annunciate the following conditions:

• Fire Alarm (red)

• CO Alarm (red)

• AC Power (green)

• Supervisory (yellow)

• Trouble (yellow)

• Ground fault (yellow)

• Battery fault (yellow)

• Disabled (yellow)

• Maintenance (yellow)

• Communication (yellow)

• Alarm Silenced (yellow)

• F1-F4 Function Keys (yellow)

Function keys:

• Acknowledge

• Alarm Silence

• Drill

• Reset (lamp test)

• four (4) programmable function keys

Service/program keys:

• Keys labeled 1 to 9

• * key

• # key

• 0 (recall) key

• First Event and scroll keys

• Last Event and scroll keys

• Clear key

• Escape key

• Two cursor keys (left and right)

• Menu/Enter key

Local Piezo Sounder

A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.

1.4 Components

Main Circuit Board

The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The 4XTM option module plugs in and is mounted to the main circuit board.

IPOTS-COM Communicator Card

The pre-installed IP/POTS communicator card transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the FS-Tools Upload/Down-load utility and a hard-wired Ethernet IP connection. Any personal computer with Windows® 7 or greater, 32 or 64 bit, and FS-Tools software may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages. Refer to Section 6 on page 123 for more information.

The IPOTS-COM digital communicator provides the following POTS functions:

• Line Seizure: takes control of the phone lines disconnecting any premises phones

• Off/On Hook: performs on and off-hook status to the phone lines

• Listen for dial tone: 440 Hz tone typical in most networks

SYSTEM NORMAL

10:00A 010118

Figure 1.2 Membrane/Display Panel es ky pd .w m f

16 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018

Optional Modules Product Description

• Dialing the Central Station(s) number: default is Touch-Tone®, programmable to rotary

• For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.

• Communicate in the following formats:

Ademco Contact ID

SIA DCS 8

SIA DCS 20

Cabinet

The NFW-100X backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel (DP-ES-R or DP-ES-B), which mounts to the inside of the cabinet.

Batteries

The NFW-100X cabinet provides space for two batteries (up to 18 Amp Hour). Batteries larger than 18 Amp Hour require an external charger such as the CHG-75 or CHG-120 and a UL listed battery box such as the BB-26 or NFS-LBB. Batteries must be ordered separately.

1.4.1 Intelligent Addressable Detectors

Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the FireWar-den/ONYX SLC Wiring Manuals for detailed information on device installation, wiring and operation). This allows the control panel to continually process the information to determine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. The maximum address cannot exceed address 99. Note that a blinking LED on an intelligent detector indicates communication between the detector and the control panel.

These devices can operate in CLIP mode (Classic Loop Interface Protocol) or FlashScan mode to provide a quicker response. Refer to the FireWarden/ONYX SLC Wiring Manuals for a list of compatible addressable detectors.

1.4.2 Intelligent Addressable Modules

Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches. The maximum address cannot exceed address 99.

Note that a blinking LED on an addressable module indicates communication between the module and the control panel.

These devices can operate in CLIP mode (Classic Loop Interface Protocol) or FlashScan mode to provide a quicker response. Refer to the FireWarden/ONYX SLC Wiring Manuals for a list of compatible addressable modules. Refer to the Device Compatibility Document for a list of approved conventional notification and initiating devices.

1.4.3 Addressable Device Accessories

End-of-Line Resistor Assembly The End-of-Line resistors are included with each module. Refer to the specific module documentation for specific information.

Power Supervision Relay The UL listed End-of-Line power supervision relay is used to supervise the power to 4-wire smoke detectors and notification appliances.

EOL-C(R/W) Mounting Plate The EOL-CR (red) and EOL-CW (white) are single End-of-Line resistor plates. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the EOL-C(R/W) plate. Resistors mounted to the plate can be used for the supervision of a monitor and control module circuit.

1.5 Optional Modules

The NFW-100X main circuit board includes option module connectors for the following modules:

CELL-MOD/CELL-CAB-N

Optional GSM communicator card for central station reporting. It mounts in its own plastic or metal enclosure. Use of the CELL- MOD/CELL-CAB-N requires the IPOTS-COM communicator. Connections are made from the CELL-MOD/CELL-CAB to the IPOTS-

COM.

PWRMOD24 Power Expander Module

Optional power module. Increases NAC power output by 3 amps.

4XTM Transmitter Module

The 4XTM provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a dis-able switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J5 and J6 which are located near the right edge the main circuit board. When the 4XTM module is installed, Jumper JP3, on the main circuit board, must be cut to allow supervi-sion of the module.

Battery Cable P/N 75287 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018 17

Product Description Accessories

1.6 Accessories

1.6.1 FS-Tools Programming Utility

The FS-Tools Programming Utility can be used to locally or remotely program the FACP from most Windows® compatible computers (PC), running Windows 7 or newer, 32 or 64 bit. The FACP program files can also be created and stored on the PC for future download to the control panel. FS-Tools can be downloaded from www.notifier.com. A standard USB cable with male-A to male-A connectors, which must be purchased separately, is required for local connection of the PC to the USB port J20 on the FACP main circuit board.

Remote programming requires that the PC have a GSM or Ethernet connection.

FS-Tools also provides the ability to create panel program files on a USB flash drive. The drive can then be plugged into USB port J20 on the FACP main circuit board.

Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to “FS-Tools Upload/Download” on page 123). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option.

1.6.2 Dress Panel

An optional dress panel DP-ES-R or DP-ES-B is available for the NFW-100X. The dress panel restricts access to the system wiring while allowing access to the key panel. A ground strap must be connected between the stud on the inside of the dress panel and the ground stud in the backbox.The dress panel mounts to the backbox with two (2) #6-32 screws.

1.6.3 Trim Ring

Optional Trim Rings (P/N TR-CE-B black, TR-CE red) are available for the FACP backbox. The Trim Rings add 1.5” of wall coverage around the backbox, concealing hardware and providing a finished appearance for a semi-flush mounted panel.

1.6.4 Battery Box

BB-26

The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger.

NFS-LBB

The NFS-LBB battery box may be used to house two 26 AH batteries, two 60 AH batteries or one 100 AH battery. When the CHG-120 is mounted in the NFS-LBB, two 26 AH or one 60 AH battery may also be housed in the battery box.

1.6.5 Battery Charger

CHG-75 Battery Charger The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the NFW-100X FACP. The FACP battery charger must be dis-abled, by removing jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box.

Larger batteries and the charger can be housed in the NFS-LBB battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information.

CHG-120 Battery Charger The CHG-120 is capable of charging up to 120 AH lead-acid batteries with the NFW-100X FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-120. The batteries and charger can be housed in the NFS-LBB battery box which can be mounted up to 20 feet away from the control panel. Note that when using the NFS-LBB for housing the charger and batter-ies greater than 26AH, multiple NFS-LBBs are required. Refer to the CHG-120 Manual for additional information.

18 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018

Accessories Product Description

1.6.6 NFC-50/100

The NFC-50/100 is a single channel, 50 watt, 25 VRMS, emergency voice evacuation panel that may be used for fire applications, mass notification applications, or both. Automatic activation of the NFC-50/100 is possible via eight Command Input Circuits (CMD) or via the ANN BUS serial communications link from the NFW-100X FACP.

1.6.7 NFC-FFT

An NFC-FFT Fire Fighter Telephone provides supervision, annunciation, and control for local and remote telephone handsets. The NFC- FFT’s keypad provides indications of phone activation and corresponding trouble conditions. .

1.6.8 FWSG Wireless Gateway

The FWSG Wireless Gateway acts as a bridge between a group of wireless fire devices and a FlashScan SLC loop on the NFW-100X. It is powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply evaluated for life safety. Available wireless devices include a photo detector, a Acclimate detector, a fixed-temperature heat detector, a rate-of-rise heat detector, a monitor module, and a relay module. A maximum of 100 wireless devices can be used in the system. For details about wireless devices, system setup, and operation, see the SWIFT® Smart Wireless Integrated Fire Technology Instruction Manual #LS10036-000NF-E.

1.6.9 ANN-BUS Annunciators/Modules

Guidelines

• A variety of optional annunciation devices can be connected to an ANN-BUS communication circuit. ANN Series devices can be connected to the primary communication circuit (EIA-485) terminals on TB9. A secondary communication circuit for these devices is available at TB8. Each ANN-BUS communication circuit supports up to eight (8) annunciators. Compatible devices include the following:

– N-ANN-80 LCD Annunciator (UL applications only)

– N-ANN-100 LCD Annunciator (FM applications only)

– N-ANN-S/PG Serial/Parallel Printer Interface Module

– N-ANN-I/O LED Driver Module

– N-ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs)

– N-ANN-RLED Annunciator Module (red alarm LEDs only)

– N-ANN-RLY Relay Module (can be mounted in the supplied FACP chassis)

• When operating two ANN-BUS circuits, only one N-ANN-S/PG Printer module can be used in the system.

• The panel is capable of operating a primary ANN-BUS (TB9) and a secondary ANN-BUS (TB10) simultaneously.

• Only one audio system (NFC-50/100 or NFV-25/50) may be connected to the ANN-BUS.

N-ANN-80/N-ANN-100 Remote Fire Annunciators The N-ANN-80 and N-ANN-100 Annunciators are 80 character, backlit LCD remote fire annunciators. They mimic the display on the control panel and will annunciate device type, point alarm, trouble or supervisory conditions, zone assignments plus any custom alpha labels programmed into the FACP. The annunciators also provide system status LEDs to display AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. Additionally, the annunciators are capable of remotely performing critical system functions such as Acknowledge, Silence, Reset and Drill. Communication between the annunciators and the FACP is accomplished over a two wire RS- 485 serial interface employing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the host FACP or remote UL-listed, filtered, regulated, power supply.

The function buttons and piezo sounder may be individually enabled and disabled through the FACP software. Refer to “ANN-80/100 Options” on page 98 for a description of this feature and programming information.

N-ANN-S/PG Serial/Parallel Interface Module The N-ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel printer to the FACP for a real-time log of system events, detector status reports and event history. The module is provided with a plastic enclosure for surface mount-ing.

N-ANN-I/O LED Driver Module…

This is the start of the file's text. The full file is on GovTribe.