2025-04-11_Volusia-County-EOC_FireScan.pdf
PDF 1 MB Posted
- Solicitation number
- 26-B-18LL
- Issued by
- Volusia County, Florida
About this file
This is a Fire Alarm System Inspection Certificate for the Volusia County Emergency Operations Center (EOC) located at 3825 Tiger Bay Road, Daytona Beach, Florida, inspected on April 11, 2025, by United Fire Protection - Orlando. The inspection was conducted in accordance with NFPA 72 standards on a Notifier NFS2-3030 fire alarm control panel originally installed on January 27, 2014. The facility's fire alarm system comprises 87 total items across multiple categories: 40 control devices, 2 indicating devices, 37 initiating devices, and 8 supervisory devices. Of these items, 85 were serviced during the annual inspection, with 83 passing and 2 failing. The two failed items were batteries located in the Middle Can For Amplifiers in Room 133 Building Systems that did not meet load test requirements per NFPA 72 Table 10.4.2.2.5. The inspection included testing of annunciators, batteries, communicators, duct detectors, pull stations, smoke detectors, special controls, voice evacuation systems, waterflow switches, and supervisory valves distributed throughout the building's mechanical systems and occupied spaces. The proposed solution called for replacement of the two failed PS-12180 NB sealed lead acid batteries on a time and materials basis. Sound testing could not be completed due to building occupancy.
The inspection report documents that 13 of the 15 total batteries in the system passed testing, with rated capacities ranging from 7 to 55 amp-hours and manufacture dates spanning from June 2022 through February 2023. The facility operates a multi-zone fire alarm system with 27 addressable zones covering various locations including dispatch areas, corridors, mechanical rooms, break rooms, bunks, and exterior generator yards. Equipment inventory indicates that most components have been in service for 10 to 15 years, with some batteries replaced within the last one to two years. The system includes pre-action and wet-pipe sprinkler supervision, clean agent fire suppression components, and integrated voice evacuation capability. This inspection is part of the broader Volusia County Life Safety Systems contract opportunity (Solicitation No. 26-B-18LL), which requires ongoing annual fire alarm inspections per NFPA 72 standards, semi-annual clean agent system inspections per NFPA 2001, and 24/7 emergency repair services across five county facilities, with mandatory pre-bid site visits scheduled for December 4-5, 2025, and bids due by January 8, 2026.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Volusia County EOC 3825 Tiger Bay Road Daytona Beach, FL 32124 386-547-2703
Building Contact: Phil Fielder Title: Facilities
Company: United Fire Protection - Orlando Contact: Ryan Lynch Title: Inspector
Inspection Date: Apr 11, 2025 Tested to NFPA 72 Standards
Fire Alarm Systems
INSPECTION
CERTIFICATE
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 24 Executive Summary
United Fire Protection - Orlando Download Date: 12/29/2025
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information Volusia County EOC 3825 Tiger Bay Road Daytona Beach, FL 32124 United States of America
Contact: Phil Fielder
Phone: 386-547-2703
Fax:
Mobile:
Email: pfielder@volusia.org
Inspection Performed By United Fire Protection - Orlando 4602 35th Street Suite 100 Orlando, Florida 32811 United States of America
Inspector: Ryan Lynch
Phone: 407-830-7000
Fax:
Mobile:
Email: rlynch@united-fire.com
System Control Unit Manufacturer: Notifier Inspection Date: 04/11/2025 IDC Style: B
Model Number: NFS2-3030 Install Date: 01/27/2014 SLC Style: 4
Software Version: 18.0 Version Date: 01/27/2014 NAC Style: Y
Location: Room 133 Building Systems Disconnect Location: Disconnect Type:
Current Protection: Breaker
Central Station Signal Verification Type: Digital Communicator Mfg: Silent Knight Model #: 5104
Test Time/Date: 4/11/25 10:06:50 AM Restore Time: Note:
Page of 3 24 Executive Summary
United Fire Protection - Orlando Download Date: 12/29/2025
Building: Volusia County EOC Contact: Phil Fielder
Company: United Fire Protection - Orlando Inspector: Ryan Lynch
Signed: Apr 11, 2025
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Control 40 45.98% 40 100.00% 38 95.00% 2 5.00%
Indicating 2 2.30% 0 0.00% 0 0.00% 0 0.00%
Initiating 37 42.53% 37 100.00% 37 100.00% 0 0.00%
Supervisory 8 9.20% 8 100.00% 8 100.00% 0 0.00%
Totals 87 100% 85 97.70% 83 97.65% 2 2.35%
Certification
Page of 4 24 Discrepancy Report
United Fire Protection - Orlando Download Date: 12/29/2025
Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC
DISCREPANCY REPORT
Deficiency, Impairment, and Observation
Generated by: BuildingReports.com
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Building: Volusia County EOC
Items listed for Recall or Replacement/Upgrade Device Type Manufacturer Model Number Date Qty
No recalled items found during this inspection.
Discrepancies ScanID Location Problem Address Reference
CONTROL
Battery
28706562 Room 133 Building Systems Middle Can For Amplifiers
Failed Test 1 NFPA 72 Table 10.4.2.2.5(a-e)
28706563 Room 133 Building Systems Middle Can For Amplifiers
Failed Test 1 NFPA 72 Table 10.4.2.2.5(a-e)
Code References NFPA 72 Table 10.4.2.2.5(a-e)
(a) Batteries shall be inspected for corrosion or leakage. Tightness of connections shall be checked and ensured. If necessary, battery terminals or connections shall be cleaned and coated. Electrolyte level in lead-acid batteries shall be visibly inspected. (b) Batteries shall be replaced in accordance with the recommendations of the alarm equipment manufacturer or when the recharged battery voltage or current falls below the manufacturer's recommendations. (c) Operation of battery charger shall be checked in accordance with charger test for the specific type of battery. (d) Discharge Test: With the battery charger disconnected, the batteries shall be load tested following the manufacturer's recommendations. The voltage level shall not fall below the levels specified. Exception: An artificial load equal to the full fire alarm load connected to the battery shall be permitted to be used in conducting this test. (e) With the battery charger disconnected, the terminal voltage shall be measured while supplying the maximum load required by its application.The voltage
Page of 5 24 Discrepancy Report
United Fire Protection - Orlando Download Date: 12/29/2025 level shall not fall below the levels specified for the specific type of battery. If the voltage falls below the level specified, corrective action shall be taken and the batteries shall be retested.
Exception: An artificial load equal to the full fire alarm load connected to the battery shall be permitted to be used in conducting this test.
Page of 6 24 Proposed Solutions Report
United Fire Protection - Orlando Download Date: 12/29/2025
Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC
PROPOSED SOLUTIONS REPORT
Generated by: BuildingReports.com
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
CONTROL
Battery
28706562 Room 133 Building Systems Middle Can For Amplifiers
Replace Battery PS-12180 NB T/M ☐
28706563 Room 133 Building Systems Middle Can For Amplifiers
Replace Battery PS-12180 NB T/M ☐
Customer WO/PO #:
(none)
Internal WO/PO #:
(none)
Total: T/M
Page of 7 24 Notes & Recommendations
United Fire Protection - Orlando Download Date: 12/29/2025
Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note
(2) batteries failed and should be replaced. Sound test could not be performed due to occupancy. RL 4/11/25.
Note Device Type Location Comment ScanID
CONTROL
1 Battery Room 133 Building Systems Middle Can For Amplifiers
Failed Test 28706563
Other battery in sequence failed. RL 4/11/25.
Page of 8 24 Inspection & Testing
United Fire Protection - Orlando Download Date: 12/29/2025
Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Annunciator Distpatch 137 Annual 10:53:02 AM 04/11/2025
Annunciator Main Entrance Annual 10:25:03 AM 04/11/2025
Battery Room 133 Building Systems Communicator Annual 10:07:18 AM 04/11/2025
Battery Room 133 Building Systems FACP Annual 10:03:44 AM 04/11/2025
Battery Room 133 Building Systems FACP Annual 10:03:53 AM 04/11/2025
Battery Room 133 Building Systems Far Right Can For Amplifiers
Annual 9:32:12 AM 04/11/2025
Battery Room 133 Building Systems Far Right Can For Amplifiers
Annual 9:36:42 AM 04/11/2025
Battery Room 133 Building Systems Far Right Can For Power Supply 1
Annual 9:50:40 AM 04/11/2025
Battery Room 133 Building Systems Far Right Can For Power Supply 1
Annual 9:52:32 AM 04/11/2025
Battery Room 133 Building Systems Far Right Can For Power Supply 2
Annual 9:46:42 AM 04/11/2025
Battery Room 133 Building Systems Far Right Can For Power Supply 2
Annual 9:48:45 AM 04/11/2025
Battery Room 133 Building Systems Far Right Can For Power Supply 3
Annual 9:40:31 AM 04/11/2025
Battery Room 133 Building Systems Far Right Can For Power Supply 3
Annual 9:44:09 AM 04/11/2025
Battery Room 133 Building Systems Middle Can For Amplifiers
Annual 9:19:39 AM 04/11/2025
Page of 9 24
United Fire Protection - Orlando Download Date: 12/29/2025
Device Type Location Service Time Date
PASSED (continued)
Control (continued)
Battery Room 133 Building Systems Middle Can For Amplifiers
Annual 9:25:15 AM 04/11/2025
Communicator Room 133 Building Systems Annual 10:06:50 AM 04/11/2025
Control Panel Room 133 Building Systems Annual 9:02:33 AM 04/11/2025
Power Supply Room 133 Building Systems Far Right Can Annual 9:06:04 AM 04/11/2025
Power Supply Room 133 Building Systems Far Right Can Annual 9:06:21 AM 04/11/2025
Power Supply Room 133 Building Systems Far Right Can Annual 9:06:38 AM 04/11/2025
Special Control Distpatch 137 Remote Mic Annual 10:53:06 AM 04/11/2025
Special Control Main Entrance Remote Mic Annual 10:25:07 AM 04/11/2025
Special Control Room 128 Mechanical AHU-2 For Duct Detector 23
Annual 10:44:45 AM 04/11/2025
Special Control Room 128 Mechanical AHU-2 For Duct Detector 24
Annual 10:44:44 AM 04/11/2025
Special Control Room 128 Mechanical AHU-3 For Duct Detector 15
Annual 10:48:01 AM 04/11/2025
Special Control Room 128 Mechanical AHU-3 For Duct Detector 16
Annual 10:48:02 AM 04/11/2025
Special Control Room 128 Mechanical AHU-4 For Duct Detector 25
Annual 10:40:59 AM 04/11/2025
Special Control Room 128 Mechanical AHU-4 For Duct Detector 26
Annual 10:41:03 AM 04/11/2025
Special Control Room 128 Mechanical Across AHU-1 For Duct Detector 17
Annual 10:44:20 AM 04/11/2025
Special Control Room 128 Mechanical Across AHU-1 For Duct Detector 18
Annual 10:44:19 AM 04/11/2025
Special Control Room 128 Mechanical Across AHU-5A For Duct Detector 19
Annual 10:45:57 AM 04/11/2025
Special Control Room 128 Mechanical Across AHU-5A For Duct Detector 20
Annual 10:45:56 AM 04/11/2025
Special Control Room 128 Mechanical Across AHU-5B For Duct Detector 21
Annual 10:45:46 AM 04/11/2025
Page of 10 24
United Fire Protection - Orlando Download Date: 12/29/2025
Device Type Location Service Time Date
PASSED (continued)
Control (continued)
Special Control Room 128 Mechanical Across AHU-5B For Duct Detector 22
Annual 10:45:45 AM 04/11/2025
Voice Evacuation Building Systems 133 Annual 9:02:45 AM 04/11/2025
Voice Evacuation Room 133 Building Systems Middle Can Annual 9:04:07 AM 04/11/2025
Voice Evacuation Room 133 Building Systems Middle Can Annual 9:04:23 AM 04/11/2025
Voice Evacuation Room 133 Building Systems Middle Can Annual 9:04:37 AM 04/11/2025
Initiating
Duct Detector Room 128 Mechanical AHU-1 Return DNR
HOUSING
Annual 10:42:32 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-1 Supply DNR
HOUSING
Annual 10:46:45 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-2 Return DNR
HOUSING
Annual 10:46:59 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-2 Supply DNR
HOUSING
Annual 10:42:10 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-3 Return DNR
HOUSING
Annual 10:46:48 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-3 Supply DNR
HOUSING
Annual 10:42:37 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-4 Return DNR
HOUSING
Annual 10:46:56 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-4 Supply DNR
HOUSING
Annual 10:46:51 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-5A Return DNR
HOUSING
Annual 10:46:25 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-5A Supply DNR
HOUSING
Annual 10:46:20 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-5B Return DNR
HOUSING
Annual 10:46:16 AM 04/11/2025
Duct Detector Room 128 Mechanical AHU-5B Supply DNR
HOUSING
Annual 10:46:13 AM 04/11/2025
Page of 11 24
United Fire Protection - Orlando Download Date: 12/29/2025
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Duct Detector UPS 27 Annual 10:56:17 AM 04/11/2025
Pull Station Cafeteria 110 Exit Annual 10:29:20 AM 04/11/2025
Pull Station Corridor 11 Exit By Operations 122 Annual 10:22:34 AM 04/11/2025
Pull Station Corridor 13 Exit By Dispatch 137 Annual 10:14:24 AM 04/11/2025
Pull Station Corridor Exit By COMM CDR 167 Annual 10:18:34 AM 04/11/2025
Pull Station Corridor Exit By Dispatch Breakroom 147 Annual 10:17:03 AM 04/11/2025
Pull Station Corridor Exit By VCEM Manager 117 Annual 10:19:45 AM 04/11/2025
Pull Station Distpatch Back Exit 137 Annual 10:54:20 AM 04/11/2025
Pull Station Kitchen Exit Annual 10:38:17 AM 04/11/2025
Pull Station Main Entrance Annual 10:25:35 AM 04/11/2025
Pull Station Media Broadcasting 108 Exit Annual 10:30:25 AM 04/11/2025
Pull Station Outside In Generator Yard Annual 10:49:57 AM 04/11/2025
Pull Station Outside In Generator Yard Annual 10:50:43 AM 04/11/2025
Pull Station Room 128 Mechanical Annual 10:40:30 AM 04/11/2025
Pull Station Room 129 Switch Gear Annual 10:51:53 AM 04/11/2025
Smoke Detector Corridor 11 Annual 10:23:09 AM 04/11/2025
Smoke Detector Door Entrance To Corridor 11 Annual 10:21:31 AM 04/11/2025
Smoke Detector Room 133 Building Systems Annual 10:11:23 AM 04/11/2025
Smoke Detector Training & Mens Bunk 157 Annual 11:01:23 AM 04/11/2025
Smoke Detector Training & Mens Bunk 157 Annual 11:01:27 AM 04/11/2025
Smoke Detector Training & Womens Bunk 155 Annual 11:01:30 AM 04/11/2025
Smoke Detector Training & Womens Bunk 155 Annual 11:01:34 AM 04/11/2025
Smoke Detector 1st Door Entrance To Operations 122 Annual 10:20:20 AM 04/11/2025
Waterflow Switch Mechanical room 128 Pre-Action Pressure Switch
Annual 10:48:44 AM 04/11/2025
Page of 12 24
United Fire Protection - Orlando Download Date: 12/29/2025
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Waterflow Switch Mechanical room 128 Wet System Vane type Annual 10:48:41 AM 04/11/2025
Supervisory
Air Pressure Switch Mechanical room 128 Pre-Action Annual 10:48:42 AM 04/11/2025
Supervisory Valve Mechanical room 128 Backflow Inlet Annual 10:48:57 AM 04/11/2025
Supervisory Valve Mechanical room 128 Backflow Outlet Annual 10:48:54 AM 04/11/2025
Supervisory Valve Mechanical room 128 Pre-Action Annual 10:48:49 AM 04/11/2025
Supervisory Valve Mechanical room 128 Pre-Action Annual 10:48:50 AM 04/11/2025
Supervisory Valve Mechanical room 128 Wet System Annual 10:48:46 AM 04/11/2025
Tamper Switch Main Backflow Annual 12:02:00 PM 04/11/2025
Tamper Switch Main Backflow Annual 12:02:04 PM 04/11/2025
FAILED/OTHER
Control
Battery Room 133 Building Systems Middle Can For Amplifiers
Annual 9:29:40 AM 04/11/2025
Battery Room 133 Building Systems Middle Can For Amplifiers
Annual 1:12:33 PM 04/11/2025
Page of 13 24 Service Summary
United Fire Protection - Orlando Download Date: 12/29/2025
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Volusia County EOC
Device Type Service Quantity
PASSED
Air Pressure Switch Annual 1
Annunciator Annual 2
Battery Annual 13
Communicator Annual 1
Control Panel Annual 1
Duct Detector Annual 13
Power Supply Annual 3
Pull Station Annual 14
Smoke Detector Annual 8
Special Control Annual 14
Supervisory Valve Annual 5
Tamper Switch Annual 2
Voice Evacuation Annual 4
Waterflow Switch Annual 2
Total 83
FAILED/OTHER
Battery Annual 2
Total 2
Grand Total 85
Page of 14 24 Auxiliary Functions Testing
United Fire Protection - Orlando Download Date: 12/29/2025
Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC
AUXILIARY FUNCTIONS TESTING
Generated by: BuildingReports.com
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
PASSED
Duct Detector
Air Duct Room 128 Mechanical AHU-1 Return DNR
HOUSING
Passed 28706585
Air Duct Room 128 Mechanical AHU-1 Supply DNR
HOUSING
Passed 28706584
Air Duct Room 128 Mechanical AHU-2 Return DNR
HOUSING
Passed 28706597
Air Duct Room 128 Mechanical AHU-2 Supply DNR
HOUSING
Passed 28706596
Air Duct Room 128 Mechanical AHU-3 Return DNR
HOUSING
Passed 28706589
Air Duct Room 128 Mechanical AHU-3 Supply DNR
HOUSING
Passed 28706588
Air Duct Room 128 Mechanical AHU-4 Return DNR
HOUSING
Passed 28706593
Air Duct Room 128 Mechanical AHU-4 Supply DNR
HOUSING
Passed 28706592
Air Duct Room 128 Mechanical AHU-5B Supply DNR
HOUSING
Passed 28706576
AHU Shutdown UPS 27 Passed 41763588
Page of 15 24 Sound and Visual Testing
United Fire Protection - Orlando Download Date: 12/29/2025
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Volusia County EOC
Location Comment Ambient Alarm Voice
Intelligibility STI Sound Test
UNTESTED
Entire Building ☐ 0001
Outside Chiller/Mechanical Yard ☐ 0002
Page of 16 24 Battery & Power Supply Testing
United Fire Protection - Orlando Download Date: 12/29/2025
Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location Rated
Ah Rated Volts
Pre Test
Post Test
Min Ah
Teste d Ah
MFG
Date
PASSED
Sealed Lead Acid Room 133 Building Systems Communicator
7 12 12.75 12.60 4.55 6.0 02/03 /2023
Sealed Lead Acid Room 133 Building Systems FACP 55 12 13.54 13.41 35.75 57.0 01/14 /2023
Sealed Lead Acid Room 133 Building Systems FACP 55 12 13.53 13.38 35.75 65.0 01/14 /2023
Sealed Lead Acid Room 133 Building Systems Far Right Can For Amplifiers
18 12 13.37 13.07 11.70 12.0 09/16 /2022
Sealed Lead Acid Room 133 Building Systems Far Right Can For Amplifiers
18 12 13.47 13.16 11.70 12.0 09/16 /2022
Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 1
7 12 12.82 12.62 4.55 6.80 01/22 /2023
Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 1
7 12 12.71 12.51 4.55 6.80 01/22 /2023
Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 2
7 12 12.93 12.75 4.55 7.60 12/18 /2023
Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 2
7 12 12.63 12.50 4.55 7.20 01/22 /2023
Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 3
7 12 12.85 12.72 4.55 7.40 12/18 /2023
Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 3
7 12 12.60 12.43 4.55 6.0 06/10 /2022
Page of 17 24 Battery & Power Supply Testing
United Fire Protection - Orlando Download Date: 12/29/2025
Type Location Rated
Ah Rated Volts
Pre Test
Post Test
Min Ah
Teste d Ah
MFG
Date
PASSED (continued)
Sealed Lead Acid Room 133 Building Systems Middle Can For Amplifiers
18 12 13.35 12.96 11.70 12.0 09/16 /2022
Sealed Lead Acid Room 133 Building Systems Middle Can For Amplifiers
18 12 13.44 13.10 11.70 12.0 09/16 /2022
FAILED/OTHER
Sealed Lead Acid Room 133 Building Systems Middle Can For Amplifiers
18 12 07/23 /2022
Sealed Lead Acid Room 133 Building Systems Middle Can For Amplifiers
18 12 13.37 13.12 11.70 7.90 07/23 /2022
Page of 18 24 Inventory & Warranty Report
United Fire Protection - Orlando Download Date: 12/29/2025
Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Building: Volusia County EOC
Device or Type Category % of Inventory Quantity
Air Pressure Switch Supervisory 1.15% 1
Annunciator Control 2.30% 2
Battery Control 17.24% 15
Communicator Control 1.15% 1
Control Panel Control 1.15% 1
Duct Detector Initiating 14.94% 13
Power Supply Control 3.45% 3
Pull Station Initiating 16.09% 14
Smoke Detector Initiating 9.20% 8
Sound Test Indicating 2.30% 2
Special Control Control 16.09% 14
Supervisory Valve Supervisory 5.75% 5
Tamper Switch Supervisory 2.30% 2
Voice Evacuation Control 4.60% 4
Waterflow Switch Initiating 2.30% 2
Type Qty Model # Description Install Date
IN SERVICE - 1 YEAR TO 2 YEARS
Duracell
Page of 19 24
United Fire Protection - Orlando Download Date: 12/29/2025
Type Qty Model # Description Install Date
IN SERVICE - 1 YEAR TO 2 YEARS (continued)
Duracell (continued)
Battery 2 DURDC12-55 Sealed Lead Acid 03/25/2024
Power Sonic
Battery 4 PS-12180 NB Sealed Lead Acid 03/25/2024
Battery 7 PS-1270 F2 Sealed Lead Acid 03/25/2024
IN SERVICE - 5 YEARS TO 10 YEARS
Notifier
Duct Detector 1 Photoelectric 02/23/2018
Power Sonic
Battery 2 PS-12180 NB Sealed Lead Acid 03/05/2019
IN SERVICE - 10 YEARS TO 15 YEARS
Notifier
Annunciator 2 LCD80-2 LCD 01/27/2014
Control Panel 1 NFS2-3030 01/27/2014
Duct Detector 12 FSP-851 Photoelectric 01/31/2013
Power Supply 3 HPFF8CM 01/31/2013
Pull Station 2 NBG-12LO Dual Action 01/27/2014
Pull Station 12 NBG-12LX Dual Action 01/27/2014
Smoke Detector 8 FSP-851 Photoelectric 01/31/2013
Special Control 2 RM-1 Remote Mic 01/27/2014
Voice Evacuation 3 DAA2-5025 01/31/2013
Voice Evacuation 1 DVC 01/27/2014
Silent Knight
Communicator 1 5104 Digital Communicator 01/27/2014
System Sensor
Air Pressure Switch 1 EPS40-2 Low 01/27/2014
Special Control 1 Photoelectric 01/27/2014
Page of 20 24
United Fire Protection - Orlando Download Date: 12/29/2025
Type Qty Model # Description Install Date
IN SERVICE - 10 YEARS TO 15 YEARS (continued)
System Sensor (continued)
Special Control 11 Remote Test/Reset 01/27/2014
Tamper Switch 2 OSY2 01/27/2014
Waterflow Switch 1 EPS10-2 01/27/2014
Waterflow Switch 1 WFD40 01/27/2014
Victaulic
Supervisory Valve 2 702 01/27/2014
Supervisory Valve 3 705 01/27/2014
Page of 21 24 Zone Address Report
United Fire Protection - Orlando Download Date: 12/29/2025
Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC
ZONE ADDRESS REPORT
Generated by: BuildingReports.com
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
ZONE/CIRCUIT:
01 Special Control Distpatch 137 Remote Mic Remote Mic 28706621
01 Annunciator Main Entrance LCD 28706612
01 Pull Station Main Entrance Dual Action 28706611
01 Special Control Main Entrance Remote Mic Remote Mic 28706613
01 Smoke Detector Room 133 Building Systems Photoelectric 28706575
02 Smoke Detector Corridor 11 Photoelectric 28706602
02 Pull Station Corridor Exit By COMM CDR 167 Dual Action 28706614
03 Pull Station Corridor Exit By Dispatch Breakroom 147 Dual Action 28706604
03 Smoke Detector Door Entrance To Corridor 11 Photoelectric 28706605
04 Pull Station Distpatch Back Exit 137 Dual Action 28706619
04 Smoke Detector 1st Door Entrance To Operations 122 Photoelectric 28706606
05 Pull Station Corridor 13 Exit By Dispatch 137 Dual Action 28706603
06 Pull Station Room 128 Mechanical Dual Action 28706600
06 Smoke Detector Training & Womens Bunk 155 Photoelectric 28706617
07 Pull Station Room 129 Switch Gear Dual Action 51131768
07 Smoke Detector Training & Womens Bunk 155 Photoelectric 28706618
08 Pull Station Corridor 11 Exit By Operations 122 Dual Action 28706601
08 Smoke Detector Training & Mens Bunk 157 Photoelectric 28706615
09 Pull Station Corridor Exit By VCEM Manager 117 Dual Action 28706607
Page of 22 24
United Fire Protection - Orlando Download Date: 12/29/2025
Address Device Type Location Type ScanID
ZONE/CIRCUIT: (continued)
09 Smoke Detector Training & Mens Bunk 157 Photoelectric 28706616
10 Pull Station Kitchen Exit Dual Action 28706608
11 Pull Station Cafeteria 110 Exit Dual Action 28706609
12 Pull Station Media Broadcasting 108 Exit Dual Action 28706610
13 Pull Station Outside In Generator Yard Dual Action 51131769
14 Pull Station Outside In Generator Yard Dual Action 28706622
15 Duct Detector Room 128 Mechanical AHU-3 Return DNR
HOUSING
Photoelectric 28706589
16 Duct Detector Room 128 Mechanical AHU-3 Supply DNR
HOUSING
Photoelectric 28706588
17 Duct Detector Room 128 Mechanical AHU-1 Return DNR
HOUSING
Photoelectric 28706585
18 Duct Detector Room 128 Mechanical AHU-1 Supply DNR
HOUSING
Photoelectric 28706584
19 Duct Detector Room 128 Mechanical AHU-5A Supply
DNR HOUSING
Photoelectric 28706580
20 Duct Detector Room 128 Mechanical AHU-5A Return
DNR HOUSING
Photoelectric 28706581
21 Duct Detector Room 128 Mechanical AHU-5B Supply
DNR HOUSING
Photoelectric 28706576
22 Duct Detector Room 128 Mechanical AHU-5B Return
DNR HOUSING
Photoelectric 28706577
23 Waterflow Switch Mechanical room 128 Pre-Action Pressure Switch
21179737
23 Duct Detector Room 128 Mechanical AHU-2 Supply DNR
HOUSING
Photoelectric 28706596
24 Duct Detector Room 128 Mechanical AHU-2 Return DNR
HOUSING
Photoelectric 28706597
25 Duct Detector Room 128 Mechanical AHU-4 Return DNR
HOUSING
Photoelectric 28706593
26 Duct Detector Room 128 Mechanical AHU-4 Supply DNR
HOUSING
Photoelectric 28706592
Page of 23 24
United Fire Protection - Orlando Download Date: 12/29/2025
Address Device Type Location Type ScanID
ZONE/CIRCUIT: (continued)
61 Waterflow Switch Mechanical room 128 Wet System Vane type
21179729
62 Supervisory Valve Mechanical room 128 Backflow Inlet 21179741
63 Supervisory Valve Mechanical room 128 Backflow Outlet 21179742
64 Supervisory Valve Mechanical room 128 Pre-Action 21179730
65 Tamper Switch Main Backflow 28706623
65 Tamper Switch Main Backflow 28706624
65 Supervisory Valve Mechanical room 128 Wet System 21179726
66 Air Pressure Switch Mechanical room 128 Pre-Action Low 21179735
70 Supervisory Valve Mechanical room 128 Pre-Action 41763589
Page of 24 24 Device Photos
United Fire Protection - Orlando Download Date: 12/29/2025
Device Type: Battery ScanID: 28706562 Location: Room 133 Building Systems Middle Can For Ampl...
Service: Annual Comment: Failed Test Solution: Replace Battery
Device Type: Battery ScanID: 28706563 Location: Room 133 Building Systems Middle Can For Ampl...
Service: Annual Comment: Failed Test Solution: Replace Battery
DEVICE PHOTOS
Generated by: BuildingReports.com
Failed/Other
| Cover Page |
| Executive Summary |
| Discrepancy Report |
| Proposed Solutions Report |
| Notes & Recommendations |
| Inspection & Testing |
| Service Summary |
| Auxiliary Functions Testing |
| Sound and Visual Testing |
| Battery & Power Supply Testing |
| Inventory & Warranty Report |
| Zone Address Report |
| Device Photos |