2025-04-11_Volusia-County-EOC_FireScan.pdf

PDF 1 MB Posted

Attached to
Volusia County Life Safety Systems Inspection, Testing and Repairs
Solicitation number
26-B-18LL
Issued by
Volusia County, Florida

About this file

This is a Fire Alarm System Inspection Certificate for the Volusia County Emergency Operations Center (EOC) located at 3825 Tiger Bay Road, Daytona Beach, Florida, inspected on April 11, 2025, by United Fire Protection - Orlando. The inspection was conducted in accordance with NFPA 72 standards on a Notifier NFS2-3030 fire alarm control panel originally installed on January 27, 2014. The facility's fire alarm system comprises 87 total items across multiple categories: 40 control devices, 2 indicating devices, 37 initiating devices, and 8 supervisory devices. Of these items, 85 were serviced during the annual inspection, with 83 passing and 2 failing. The two failed items were batteries located in the Middle Can For Amplifiers in Room 133 Building Systems that did not meet load test requirements per NFPA 72 Table 10.4.2.2.5. The inspection included testing of annunciators, batteries, communicators, duct detectors, pull stations, smoke detectors, special controls, voice evacuation systems, waterflow switches, and supervisory valves distributed throughout the building's mechanical systems and occupied spaces. The proposed solution called for replacement of the two failed PS-12180 NB sealed lead acid batteries on a time and materials basis. Sound testing could not be completed due to building occupancy.

The inspection report documents that 13 of the 15 total batteries in the system passed testing, with rated capacities ranging from 7 to 55 amp-hours and manufacture dates spanning from June 2022 through February 2023. The facility operates a multi-zone fire alarm system with 27 addressable zones covering various locations including dispatch areas, corridors, mechanical rooms, break rooms, bunks, and exterior generator yards. Equipment inventory indicates that most components have been in service for 10 to 15 years, with some batteries replaced within the last one to two years. The system includes pre-action and wet-pipe sprinkler supervision, clean agent fire suppression components, and integrated voice evacuation capability. This inspection is part of the broader Volusia County Life Safety Systems contract opportunity (Solicitation No. 26-B-18LL), which requires ongoing annual fire alarm inspections per NFPA 72 standards, semi-annual clean agent system inspections per NFPA 2001, and 24/7 emergency repair services across five county facilities, with mandatory pre-bid site visits scheduled for December 4-5, 2025, and bids due by January 8, 2026.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Volusia County EOC 3825 Tiger Bay Road Daytona Beach, FL 32124 386-547-2703

Building Contact: Phil Fielder Title: Facilities

Company: United Fire Protection - Orlando Contact: Ryan Lynch Title: Inspector

Inspection Date: Apr 11, 2025 Tested to NFPA 72 Standards

Fire Alarm Systems

INSPECTION

CERTIFICATE

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Page of 2 24 Executive Summary

United Fire Protection - Orlando Download Date: 12/29/2025

EXECUTIVE SUMMARY

Generated by: BuildingReports.com

Building Information Volusia County EOC 3825 Tiger Bay Road Daytona Beach, FL 32124 United States of America

Contact: Phil Fielder

Phone: 386-547-2703

Fax:

Mobile:

Email: pfielder@volusia.org

Inspection Performed By United Fire Protection - Orlando 4602 35th Street Suite 100 Orlando, Florida 32811 United States of America

Inspector: Ryan Lynch

Phone: 407-830-7000

Fax:

Mobile:

Email: rlynch@united-fire.com

System Control Unit Manufacturer: Notifier Inspection Date: 04/11/2025 IDC Style: B

Model Number: NFS2-3030 Install Date: 01/27/2014 SLC Style: 4

Software Version: 18.0 Version Date: 01/27/2014 NAC Style: Y

Location: Room 133 Building Systems Disconnect Location: Disconnect Type:

Current Protection: Breaker

Central Station Signal Verification Type: Digital Communicator Mfg: Silent Knight Model #: 5104

Test Time/Date: 4/11/25 10:06:50 AM Restore Time: Note:

Page of 3 24 Executive Summary

United Fire Protection - Orlando Download Date: 12/29/2025

Building: Volusia County EOC Contact: Phil Fielder

Company: United Fire Protection - Orlando Inspector: Ryan Lynch

Signed: Apr 11, 2025

Inspection Summary

Category

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Control 40 45.98% 40 100.00% 38 95.00% 2 5.00%

Indicating 2 2.30% 0 0.00% 0 0.00% 0 0.00%

Initiating 37 42.53% 37 100.00% 37 100.00% 0 0.00%

Supervisory 8 9.20% 8 100.00% 8 100.00% 0 0.00%

Totals 87 100% 85 97.70% 83 97.65% 2 2.35%

Certification

Page of 4 24 Discrepancy Report

United Fire Protection - Orlando Download Date: 12/29/2025

Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC

DISCREPANCY REPORT

Deficiency, Impairment, and Observation

Generated by: BuildingReports.com

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Building: Volusia County EOC

Items listed for Recall or Replacement/Upgrade Device Type Manufacturer Model Number Date Qty

No recalled items found during this inspection.

Discrepancies ScanID Location Problem Address Reference

CONTROL

Battery

28706562 Room 133 Building Systems Middle Can For Amplifiers

Failed Test 1 NFPA 72 Table 10.4.2.2.5(a-e)

28706563 Room 133 Building Systems Middle Can For Amplifiers

Failed Test 1 NFPA 72 Table 10.4.2.2.5(a-e)

Code References NFPA 72 Table 10.4.2.2.5(a-e)

(a) Batteries shall be inspected for corrosion or leakage. Tightness of connections shall be checked and ensured. If necessary, battery terminals or connections shall be cleaned and coated. Electrolyte level in lead-acid batteries shall be visibly inspected. (b) Batteries shall be replaced in accordance with the recommendations of the alarm equipment manufacturer or when the recharged battery voltage or current falls below the manufacturer's recommendations. (c) Operation of battery charger shall be checked in accordance with charger test for the specific type of battery. (d) Discharge Test: With the battery charger disconnected, the batteries shall be load tested following the manufacturer's recommendations. The voltage level shall not fall below the levels specified. Exception: An artificial load equal to the full fire alarm load connected to the battery shall be permitted to be used in conducting this test. (e) With the battery charger disconnected, the terminal voltage shall be measured while supplying the maximum load required by its application.The voltage

Page of 5 24 Discrepancy Report

United Fire Protection - Orlando Download Date: 12/29/2025 level shall not fall below the levels specified for the specific type of battery. If the voltage falls below the level specified, corrective action shall be taken and the batteries shall be retested.

Exception: An artificial load equal to the full fire alarm load connected to the battery shall be permitted to be used in conducting this test.

Page of 6 24 Proposed Solutions Report

United Fire Protection - Orlando Download Date: 12/29/2025

Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC

PROPOSED SOLUTIONS REPORT

Generated by: BuildingReports.com

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

CONTROL

Battery

28706562 Room 133 Building Systems Middle Can For Amplifiers

Replace Battery PS-12180 NB T/M ☐

28706563 Room 133 Building Systems Middle Can For Amplifiers

Replace Battery PS-12180 NB T/M ☐

Customer WO/PO #:

(none)

Internal WO/PO #:

(none)

Total: T/M

Page of 7 24 Notes & Recommendations

United Fire Protection - Orlando Download Date: 12/29/2025

Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC

NOTES & RECOMMENDATIONS

Generated by: BuildingReports.com

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

General Note

(2) batteries failed and should be replaced. Sound test could not be performed due to occupancy. RL 4/11/25.

Note Device Type Location Comment ScanID

CONTROL

1 Battery Room 133 Building Systems Middle Can For Amplifiers

Failed Test 28706563

Other battery in sequence failed. RL 4/11/25.

Page of 8 24 Inspection & Testing

United Fire Protection - Orlando Download Date: 12/29/2025

Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC

INSPECTION & TESTING

Generated by: BuildingReports.com

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .

Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

PASSED

Control

Annunciator Distpatch 137 Annual 10:53:02 AM 04/11/2025

Annunciator Main Entrance Annual 10:25:03 AM 04/11/2025

Battery Room 133 Building Systems Communicator Annual 10:07:18 AM 04/11/2025

Battery Room 133 Building Systems FACP Annual 10:03:44 AM 04/11/2025

Battery Room 133 Building Systems FACP Annual 10:03:53 AM 04/11/2025

Battery Room 133 Building Systems Far Right Can For Amplifiers

Annual 9:32:12 AM 04/11/2025

Battery Room 133 Building Systems Far Right Can For Amplifiers

Annual 9:36:42 AM 04/11/2025

Battery Room 133 Building Systems Far Right Can For Power Supply 1

Annual 9:50:40 AM 04/11/2025

Battery Room 133 Building Systems Far Right Can For Power Supply 1

Annual 9:52:32 AM 04/11/2025

Battery Room 133 Building Systems Far Right Can For Power Supply 2

Annual 9:46:42 AM 04/11/2025

Battery Room 133 Building Systems Far Right Can For Power Supply 2

Annual 9:48:45 AM 04/11/2025

Battery Room 133 Building Systems Far Right Can For Power Supply 3

Annual 9:40:31 AM 04/11/2025

Battery Room 133 Building Systems Far Right Can For Power Supply 3

Annual 9:44:09 AM 04/11/2025

Battery Room 133 Building Systems Middle Can For Amplifiers

Annual 9:19:39 AM 04/11/2025

Page of 9 24

United Fire Protection - Orlando Download Date: 12/29/2025

Device Type Location Service Time Date

PASSED (continued)

Control (continued)

Battery Room 133 Building Systems Middle Can For Amplifiers

Annual 9:25:15 AM 04/11/2025

Communicator Room 133 Building Systems Annual 10:06:50 AM 04/11/2025

Control Panel Room 133 Building Systems Annual 9:02:33 AM 04/11/2025

Power Supply Room 133 Building Systems Far Right Can Annual 9:06:04 AM 04/11/2025

Power Supply Room 133 Building Systems Far Right Can Annual 9:06:21 AM 04/11/2025

Power Supply Room 133 Building Systems Far Right Can Annual 9:06:38 AM 04/11/2025

Special Control Distpatch 137 Remote Mic Annual 10:53:06 AM 04/11/2025

Special Control Main Entrance Remote Mic Annual 10:25:07 AM 04/11/2025

Special Control Room 128 Mechanical AHU-2 For Duct Detector 23

Annual 10:44:45 AM 04/11/2025

Special Control Room 128 Mechanical AHU-2 For Duct Detector 24

Annual 10:44:44 AM 04/11/2025

Special Control Room 128 Mechanical AHU-3 For Duct Detector 15

Annual 10:48:01 AM 04/11/2025

Special Control Room 128 Mechanical AHU-3 For Duct Detector 16

Annual 10:48:02 AM 04/11/2025

Special Control Room 128 Mechanical AHU-4 For Duct Detector 25

Annual 10:40:59 AM 04/11/2025

Special Control Room 128 Mechanical AHU-4 For Duct Detector 26

Annual 10:41:03 AM 04/11/2025

Special Control Room 128 Mechanical Across AHU-1 For Duct Detector 17

Annual 10:44:20 AM 04/11/2025

Special Control Room 128 Mechanical Across AHU-1 For Duct Detector 18

Annual 10:44:19 AM 04/11/2025

Special Control Room 128 Mechanical Across AHU-5A For Duct Detector 19

Annual 10:45:57 AM 04/11/2025

Special Control Room 128 Mechanical Across AHU-5A For Duct Detector 20

Annual 10:45:56 AM 04/11/2025

Special Control Room 128 Mechanical Across AHU-5B For Duct Detector 21

Annual 10:45:46 AM 04/11/2025

Page of 10 24

United Fire Protection - Orlando Download Date: 12/29/2025

Device Type Location Service Time Date

PASSED (continued)

Control (continued)

Special Control Room 128 Mechanical Across AHU-5B For Duct Detector 22

Annual 10:45:45 AM 04/11/2025

Voice Evacuation Building Systems 133 Annual 9:02:45 AM 04/11/2025

Voice Evacuation Room 133 Building Systems Middle Can Annual 9:04:07 AM 04/11/2025

Voice Evacuation Room 133 Building Systems Middle Can Annual 9:04:23 AM 04/11/2025

Voice Evacuation Room 133 Building Systems Middle Can Annual 9:04:37 AM 04/11/2025

Initiating

Duct Detector Room 128 Mechanical AHU-1 Return DNR

HOUSING

Annual 10:42:32 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-1 Supply DNR

HOUSING

Annual 10:46:45 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-2 Return DNR

HOUSING

Annual 10:46:59 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-2 Supply DNR

HOUSING

Annual 10:42:10 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-3 Return DNR

HOUSING

Annual 10:46:48 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-3 Supply DNR

HOUSING

Annual 10:42:37 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-4 Return DNR

HOUSING

Annual 10:46:56 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-4 Supply DNR

HOUSING

Annual 10:46:51 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-5A Return DNR

HOUSING

Annual 10:46:25 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-5A Supply DNR

HOUSING

Annual 10:46:20 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-5B Return DNR

HOUSING

Annual 10:46:16 AM 04/11/2025

Duct Detector Room 128 Mechanical AHU-5B Supply DNR

HOUSING

Annual 10:46:13 AM 04/11/2025

Page of 11 24

United Fire Protection - Orlando Download Date: 12/29/2025

Device Type Location Service Time Date

PASSED (continued)

Initiating (continued)

Duct Detector UPS 27 Annual 10:56:17 AM 04/11/2025

Pull Station Cafeteria 110 Exit Annual 10:29:20 AM 04/11/2025

Pull Station Corridor 11 Exit By Operations 122 Annual 10:22:34 AM 04/11/2025

Pull Station Corridor 13 Exit By Dispatch 137 Annual 10:14:24 AM 04/11/2025

Pull Station Corridor Exit By COMM CDR 167 Annual 10:18:34 AM 04/11/2025

Pull Station Corridor Exit By Dispatch Breakroom 147 Annual 10:17:03 AM 04/11/2025

Pull Station Corridor Exit By VCEM Manager 117 Annual 10:19:45 AM 04/11/2025

Pull Station Distpatch Back Exit 137 Annual 10:54:20 AM 04/11/2025

Pull Station Kitchen Exit Annual 10:38:17 AM 04/11/2025

Pull Station Main Entrance Annual 10:25:35 AM 04/11/2025

Pull Station Media Broadcasting 108 Exit Annual 10:30:25 AM 04/11/2025

Pull Station Outside In Generator Yard Annual 10:49:57 AM 04/11/2025

Pull Station Outside In Generator Yard Annual 10:50:43 AM 04/11/2025

Pull Station Room 128 Mechanical Annual 10:40:30 AM 04/11/2025

Pull Station Room 129 Switch Gear Annual 10:51:53 AM 04/11/2025

Smoke Detector Corridor 11 Annual 10:23:09 AM 04/11/2025

Smoke Detector Door Entrance To Corridor 11 Annual 10:21:31 AM 04/11/2025

Smoke Detector Room 133 Building Systems Annual 10:11:23 AM 04/11/2025

Smoke Detector Training & Mens Bunk 157 Annual 11:01:23 AM 04/11/2025

Smoke Detector Training & Mens Bunk 157 Annual 11:01:27 AM 04/11/2025

Smoke Detector Training & Womens Bunk 155 Annual 11:01:30 AM 04/11/2025

Smoke Detector Training & Womens Bunk 155 Annual 11:01:34 AM 04/11/2025

Smoke Detector 1st Door Entrance To Operations 122 Annual 10:20:20 AM 04/11/2025

Waterflow Switch Mechanical room 128 Pre-Action Pressure Switch

Annual 10:48:44 AM 04/11/2025

Page of 12 24

United Fire Protection - Orlando Download Date: 12/29/2025

Device Type Location Service Time Date

PASSED (continued)

Initiating (continued)

Waterflow Switch Mechanical room 128 Wet System Vane type Annual 10:48:41 AM 04/11/2025

Supervisory

Air Pressure Switch Mechanical room 128 Pre-Action Annual 10:48:42 AM 04/11/2025

Supervisory Valve Mechanical room 128 Backflow Inlet Annual 10:48:57 AM 04/11/2025

Supervisory Valve Mechanical room 128 Backflow Outlet Annual 10:48:54 AM 04/11/2025

Supervisory Valve Mechanical room 128 Pre-Action Annual 10:48:49 AM 04/11/2025

Supervisory Valve Mechanical room 128 Pre-Action Annual 10:48:50 AM 04/11/2025

Supervisory Valve Mechanical room 128 Wet System Annual 10:48:46 AM 04/11/2025

Tamper Switch Main Backflow Annual 12:02:00 PM 04/11/2025

Tamper Switch Main Backflow Annual 12:02:04 PM 04/11/2025

FAILED/OTHER

Control

Battery Room 133 Building Systems Middle Can For Amplifiers

Annual 9:29:40 AM 04/11/2025

Battery Room 133 Building Systems Middle Can For Amplifiers

Annual 1:12:33 PM 04/11/2025

Page of 13 24 Service Summary

United Fire Protection - Orlando Download Date: 12/29/2025

SERVICE SUMMARY

Generated by: BuildingReports.com

The Service Summary section provides an overview of the services performed in this report.

Building: Volusia County EOC

Device Type Service Quantity

PASSED

Air Pressure Switch Annual 1

Annunciator Annual 2

Battery Annual 13

Communicator Annual 1

Control Panel Annual 1

Duct Detector Annual 13

Power Supply Annual 3

Pull Station Annual 14

Smoke Detector Annual 8

Special Control Annual 14

Supervisory Valve Annual 5

Tamper Switch Annual 2

Voice Evacuation Annual 4

Waterflow Switch Annual 2

Total 83

FAILED/OTHER

Battery Annual 2

Total 2

Grand Total 85

Page of 14 24 Auxiliary Functions Testing

United Fire Protection - Orlando Download Date: 12/29/2025

Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC

AUXILIARY FUNCTIONS TESTING

Generated by: BuildingReports.com

The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

PASSED

Duct Detector

Air Duct Room 128 Mechanical AHU-1 Return DNR

HOUSING

Passed 28706585

Air Duct Room 128 Mechanical AHU-1 Supply DNR

HOUSING

Passed 28706584

Air Duct Room 128 Mechanical AHU-2 Return DNR

HOUSING

Passed 28706597

Air Duct Room 128 Mechanical AHU-2 Supply DNR

HOUSING

Passed 28706596

Air Duct Room 128 Mechanical AHU-3 Return DNR

HOUSING

Passed 28706589

Air Duct Room 128 Mechanical AHU-3 Supply DNR

HOUSING

Passed 28706588

Air Duct Room 128 Mechanical AHU-4 Return DNR

HOUSING

Passed 28706593

Air Duct Room 128 Mechanical AHU-4 Supply DNR

HOUSING

Passed 28706592

Air Duct Room 128 Mechanical AHU-5B Supply DNR

HOUSING

Passed 28706576

AHU Shutdown UPS 27 Passed 41763588

Page of 15 24 Sound and Visual Testing

United Fire Protection - Orlando Download Date: 12/29/2025

SOUND AND VISUAL TESTING

Generated by: BuildingReports.com

The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.

Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility requirements. The STI or Sound Transmission Index is shown if recorded.

Building: Volusia County EOC

Location Comment Ambient Alarm Voice

Intelligibility STI Sound Test

UNTESTED

Entire Building ☐ 0001

Outside Chiller/Mechanical Yard ☐ 0002

Page of 16 24 Battery & Power Supply Testing

United Fire Protection - Orlando Download Date: 12/29/2025

Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC

BATTERY & POWER SUPPLY TESTING

Generated by: BuildingReports.com

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Battery

Type Location Rated

Ah Rated Volts

Pre Test

Post Test

Min Ah

Teste d Ah

MFG

Date

PASSED

Sealed Lead Acid Room 133 Building Systems Communicator

7 12 12.75 12.60 4.55 6.0 02/03 /2023

Sealed Lead Acid Room 133 Building Systems FACP 55 12 13.54 13.41 35.75 57.0 01/14 /2023

Sealed Lead Acid Room 133 Building Systems FACP 55 12 13.53 13.38 35.75 65.0 01/14 /2023

Sealed Lead Acid Room 133 Building Systems Far Right Can For Amplifiers

18 12 13.37 13.07 11.70 12.0 09/16 /2022

Sealed Lead Acid Room 133 Building Systems Far Right Can For Amplifiers

18 12 13.47 13.16 11.70 12.0 09/16 /2022

Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 1

7 12 12.82 12.62 4.55 6.80 01/22 /2023

Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 1

7 12 12.71 12.51 4.55 6.80 01/22 /2023

Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 2

7 12 12.93 12.75 4.55 7.60 12/18 /2023

Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 2

7 12 12.63 12.50 4.55 7.20 01/22 /2023

Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 3

7 12 12.85 12.72 4.55 7.40 12/18 /2023

Sealed Lead Acid Room 133 Building Systems Far Right Can For Power Supply 3

7 12 12.60 12.43 4.55 6.0 06/10 /2022

Page of 17 24 Battery & Power Supply Testing

United Fire Protection - Orlando Download Date: 12/29/2025

Type Location Rated

Ah Rated Volts

Pre Test

Post Test

Min Ah

Teste d Ah

MFG

Date

PASSED (continued)

Sealed Lead Acid Room 133 Building Systems Middle Can For Amplifiers

18 12 13.35 12.96 11.70 12.0 09/16 /2022

Sealed Lead Acid Room 133 Building Systems Middle Can For Amplifiers

18 12 13.44 13.10 11.70 12.0 09/16 /2022

FAILED/OTHER

Sealed Lead Acid Room 133 Building Systems Middle Can For Amplifiers

18 12 07/23 /2022

Sealed Lead Acid Room 133 Building Systems Middle Can For Amplifiers

18 12 13.37 13.12 11.70 7.90 07/23 /2022

Page of 18 24 Inventory & Warranty Report

United Fire Protection - Orlando Download Date: 12/29/2025

Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC

INVENTORY & WARRANTY REPORT

Generated by: BuildingReports.com

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Building: Volusia County EOC

Device or Type Category % of Inventory Quantity

Air Pressure Switch Supervisory 1.15% 1

Annunciator Control 2.30% 2

Battery Control 17.24% 15

Communicator Control 1.15% 1

Control Panel Control 1.15% 1

Duct Detector Initiating 14.94% 13

Power Supply Control 3.45% 3

Pull Station Initiating 16.09% 14

Smoke Detector Initiating 9.20% 8

Sound Test Indicating 2.30% 2

Special Control Control 16.09% 14

Supervisory Valve Supervisory 5.75% 5

Tamper Switch Supervisory 2.30% 2

Voice Evacuation Control 4.60% 4

Waterflow Switch Initiating 2.30% 2

Type Qty Model # Description Install Date

IN SERVICE - 1 YEAR TO 2 YEARS

Duracell

Page of 19 24

United Fire Protection - Orlando Download Date: 12/29/2025

Type Qty Model # Description Install Date

IN SERVICE - 1 YEAR TO 2 YEARS (continued)

Duracell (continued)

Battery 2 DURDC12-55 Sealed Lead Acid 03/25/2024

Power Sonic

Battery 4 PS-12180 NB Sealed Lead Acid 03/25/2024

Battery 7 PS-1270 F2 Sealed Lead Acid 03/25/2024

IN SERVICE - 5 YEARS TO 10 YEARS

Notifier

Duct Detector 1 Photoelectric 02/23/2018

Power Sonic

Battery 2 PS-12180 NB Sealed Lead Acid 03/05/2019

IN SERVICE - 10 YEARS TO 15 YEARS

Notifier

Annunciator 2 LCD80-2 LCD 01/27/2014

Control Panel 1 NFS2-3030 01/27/2014

Duct Detector 12 FSP-851 Photoelectric 01/31/2013

Power Supply 3 HPFF8CM 01/31/2013

Pull Station 2 NBG-12LO Dual Action 01/27/2014

Pull Station 12 NBG-12LX Dual Action 01/27/2014

Smoke Detector 8 FSP-851 Photoelectric 01/31/2013

Special Control 2 RM-1 Remote Mic 01/27/2014

Voice Evacuation 3 DAA2-5025 01/31/2013

Voice Evacuation 1 DVC 01/27/2014

Silent Knight

Communicator 1 5104 Digital Communicator 01/27/2014

System Sensor

Air Pressure Switch 1 EPS40-2 Low 01/27/2014

Special Control 1 Photoelectric 01/27/2014

Page of 20 24

United Fire Protection - Orlando Download Date: 12/29/2025

Type Qty Model # Description Install Date

IN SERVICE - 10 YEARS TO 15 YEARS (continued)

System Sensor (continued)

Special Control 11 Remote Test/Reset 01/27/2014

Tamper Switch 2 OSY2 01/27/2014

Waterflow Switch 1 EPS10-2 01/27/2014

Waterflow Switch 1 WFD40 01/27/2014

Victaulic

Supervisory Valve 2 702 01/27/2014

Supervisory Valve 3 705 01/27/2014

Page of 21 24 Zone Address Report

United Fire Protection - Orlando Download Date: 12/29/2025

Control Panel: 1 - Notifier NFS2-3030Building: Volusia County EOC

ZONE ADDRESS REPORT

Generated by: BuildingReports.com

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

ZONE/CIRCUIT:

01 Special Control Distpatch 137 Remote Mic Remote Mic 28706621

01 Annunciator Main Entrance LCD 28706612

01 Pull Station Main Entrance Dual Action 28706611

01 Special Control Main Entrance Remote Mic Remote Mic 28706613

01 Smoke Detector Room 133 Building Systems Photoelectric 28706575

02 Smoke Detector Corridor 11 Photoelectric 28706602

02 Pull Station Corridor Exit By COMM CDR 167 Dual Action 28706614

03 Pull Station Corridor Exit By Dispatch Breakroom 147 Dual Action 28706604

03 Smoke Detector Door Entrance To Corridor 11 Photoelectric 28706605

04 Pull Station Distpatch Back Exit 137 Dual Action 28706619

04 Smoke Detector 1st Door Entrance To Operations 122 Photoelectric 28706606

05 Pull Station Corridor 13 Exit By Dispatch 137 Dual Action 28706603

06 Pull Station Room 128 Mechanical Dual Action 28706600

06 Smoke Detector Training & Womens Bunk 155 Photoelectric 28706617

07 Pull Station Room 129 Switch Gear Dual Action 51131768

07 Smoke Detector Training & Womens Bunk 155 Photoelectric 28706618

08 Pull Station Corridor 11 Exit By Operations 122 Dual Action 28706601

08 Smoke Detector Training & Mens Bunk 157 Photoelectric 28706615

09 Pull Station Corridor Exit By VCEM Manager 117 Dual Action 28706607

Page of 22 24

United Fire Protection - Orlando Download Date: 12/29/2025

Address Device Type Location Type ScanID

ZONE/CIRCUIT: (continued)

09 Smoke Detector Training & Mens Bunk 157 Photoelectric 28706616

10 Pull Station Kitchen Exit Dual Action 28706608

11 Pull Station Cafeteria 110 Exit Dual Action 28706609

12 Pull Station Media Broadcasting 108 Exit Dual Action 28706610

13 Pull Station Outside In Generator Yard Dual Action 51131769

14 Pull Station Outside In Generator Yard Dual Action 28706622

15 Duct Detector Room 128 Mechanical AHU-3 Return DNR

HOUSING

Photoelectric 28706589

16 Duct Detector Room 128 Mechanical AHU-3 Supply DNR

HOUSING

Photoelectric 28706588

17 Duct Detector Room 128 Mechanical AHU-1 Return DNR

HOUSING

Photoelectric 28706585

18 Duct Detector Room 128 Mechanical AHU-1 Supply DNR

HOUSING

Photoelectric 28706584

19 Duct Detector Room 128 Mechanical AHU-5A Supply

DNR HOUSING

Photoelectric 28706580

20 Duct Detector Room 128 Mechanical AHU-5A Return

DNR HOUSING

Photoelectric 28706581

21 Duct Detector Room 128 Mechanical AHU-5B Supply

DNR HOUSING

Photoelectric 28706576

22 Duct Detector Room 128 Mechanical AHU-5B Return

DNR HOUSING

Photoelectric 28706577

23 Waterflow Switch Mechanical room 128 Pre-Action Pressure Switch

21179737

23 Duct Detector Room 128 Mechanical AHU-2 Supply DNR

HOUSING

Photoelectric 28706596

24 Duct Detector Room 128 Mechanical AHU-2 Return DNR

HOUSING

Photoelectric 28706597

25 Duct Detector Room 128 Mechanical AHU-4 Return DNR

HOUSING

Photoelectric 28706593

26 Duct Detector Room 128 Mechanical AHU-4 Supply DNR

HOUSING

Photoelectric 28706592

Page of 23 24

United Fire Protection - Orlando Download Date: 12/29/2025

Address Device Type Location Type ScanID

ZONE/CIRCUIT: (continued)

61 Waterflow Switch Mechanical room 128 Wet System Vane type

21179729

62 Supervisory Valve Mechanical room 128 Backflow Inlet 21179741

63 Supervisory Valve Mechanical room 128 Backflow Outlet 21179742

64 Supervisory Valve Mechanical room 128 Pre-Action 21179730

65 Tamper Switch Main Backflow 28706623

65 Tamper Switch Main Backflow 28706624

65 Supervisory Valve Mechanical room 128 Wet System 21179726

66 Air Pressure Switch Mechanical room 128 Pre-Action Low 21179735

70 Supervisory Valve Mechanical room 128 Pre-Action 41763589

Page of 24 24 Device Photos

United Fire Protection - Orlando Download Date: 12/29/2025

Device Type: Battery ScanID: 28706562 Location: Room 133 Building Systems Middle Can For Ampl...

Service: Annual Comment: Failed Test Solution: Replace Battery

Device Type: Battery ScanID: 28706563 Location: Room 133 Building Systems Middle Can For Ampl...

Service: Annual Comment: Failed Test Solution: Replace Battery

DEVICE PHOTOS

Generated by: BuildingReports.com

Failed/Other

Cover Page
Executive Summary
Discrepancy Report
Proposed Solutions Report
Notes & Recommendations
Inspection & Testing
Service Summary
Auxiliary Functions Testing
Sound and Visual Testing
Battery & Power Supply Testing
Inventory & Warranty Report
Zone Address Report
Device Photos

File details come from the government source that posted it. Updated .