FAIDIQ_DRAWINGS.pdf

PDF 4 MB Posted

Attached to
Radio Fire Alarm IDIQ - Hanscom AFB
Solicitation number
FA283524DXXXX
Issued by

About this file

This document is a set of drawings related to a federal contract opportunity for a Radio Fire Alarm IDIQ (Indefinite Delivery, Indefinite Quantity) contract at Hanscom Air Force Base.

The drawings provide details on the scope of work for fire-resistance rating improvements to the receiving station, including potential server locations, door replacements, and partition upgrades. The drawings also include a typical penetration detail and installation diagram for the new radio fire alarm system.

The related federal contract opportunity is solicitation FA283524DXXXX for the Radio Fire Alarm IDIQ contract, which is a 100% Small Business Set Aside. The work is under NAICS code 238210 with a size standard of $19M and a construction value between $5-10M. Bids are due by 1:50 PM EST on 12 August 2024, and the contract will have a minimum order guarantee of $2,500 with no individual task order exceeding $5,000,000.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

rwassmer Rectangle rwassmer Polygon rwassmer Cloud+ rwassmer Cloud+

EXTENT OF RECEIVING STATION FIRE-RESISTANCE RATING IMPROVEMENTS

rwassmer Callout

ALARM ROOM AND RECEIVING STATION EQUIPMENT

rwassmer Callout POTENTIAL SERVER LOCATION, ADJACENT TO EXISTING ALARM, COMMUNICATION AND REPORTING EQUIPMENT rwassmer Rectangle rwassmer Text Box

RADIO FIRE ALARM IDIQ

A-100

B1721 HISTORY AND SCOPE

11X17 - NTS

rwassmer Snapshot rwassmer Text Box

1999 ADDITION

rwassmer Text Box

1988 ADDITION

rwassmer Text Box

1955 ORIGINAL BUILDING

rwassmer Rectangle rwassmer Text Box

1991 ADDITION

Snapshot rwassmer Rectangle rwassmer Rectangle rwassmer Text Box

RADIO FIRE ALARM IDIQ

A-101

B1721 FRR SCOPING PLAN

11X17 - NTS

rwassmer Text Box

- REFER TO UNDERLINED NOTATIONS ONLY.

- UNDERLINED TEXT REPRESENTS ANTICIPATED PROJECT SCOPE.

- ADDITIONAL DRAWING NOTATIONS REPRESENT DATED CONTENT; UNVERIFIED AND TO BE CONSIDERED GENERAL INFORMATION ONLY.

- DRAWING FOR BIDDING PURPOSES ONLY, CONTRACTOR TO FIELD VERIFY EXTENTS OF SCOPE AND REQUIRED UPGRADES TO OBTAIN CODE COMPLIANCE rwassmer Snapshot rwassmer Cloud+ rwassmer Cloud+

EXTENT OF RECEIVING STATION FIRE-RESISTANCE RATING IMPROVEMENTS

rwassmer Callout

ALARM ROOM AND RECEIVING STATION EQUIPMENT

rwassmer Callout POTENTIAL SERVER LOCATION, ADJACENT TO EXISTING ALARM, COMMUNICATION AND REPORTING EQUIPMENT rwassmer Callout

REPLACE DOOR TO MEET FRR

rwassmer Callout APPROXIMATE QUANTITIES OF PARTITION UPGRADES - CONTRACTOR TO FIELD VERIFY EXTENTS OF SCOPE rwassmer Callout

REPLACE DOOR TO MEET FRR

rwassmer Cloud+ rwassmer Cloud+ FIELD CONDITIONS ALIGN WITH PARTITION CONSTRUCTION, VOIDS AND HEAD CONDITION NOT SEALED AS REQUIRED TO MEET 1 HOUR FIRE-RESISTANCE RATING (FRR) rwassmer Polylength Measurement 14'-9" rwassmer Polylength Measurement 18'-6" rwassmer Polylength Measurement 71'-6"

Snapshot rwassmer Callout

EXISTING AIR AND/OR VAPOR BARRIER

rwassmer Text Box

DETAIL NOTES

EXISTING ASSEMBLY COMPONENTS WILL VARY IN TYPE AND LOCATION OF WALL CONSTRUCTION.

DETAIL INTENT IS TO MAINTAIN AIR AND WATER PROOFING SYSTEMS IN BUILDING ENCLOSURE TO PREVENT LEAKAGE AS CAUSED BY THE INSTALL OF THE NEW PENETRATION. POTENTIAL AGE OF BUILDINGS MAY NOT PROVIDE BARRIERS SEEN IN CONVENTIONAL CONSTRUCTION. PROVIDE A COMPLETE PENETRATION ASSEMBLY REGARDLESS OF SUBSTRATE MEMBRANE LOCATION.

DETAIL COMPONENTS WILL VARY BASED ON SITE CONDITIONS, DESIGNER-OF-RECORD TO DETERMINE APPLICABILITY AND SUBMIT APPROPRIATE DETAIL BASED ON TASK ORDER BUILDING CONDITIONS.

EXISTING WALL CONSTRUCTION INCLUDES A VARIETY OF CONSTRUCTIONS, INCLUDING:

FINISH:

MASONRY - BRICK AND/OR CMU

CAST-IN-PLACE CONCRETE

EIFS

VINYL & METAL SIDING

METAL PANEL

STRUCTURE/SUBSTRATE:

COLD FORMED METAL FRAMING

WOOD STRUCTURE

CMU

CAST-IN-PLACE CONCRETE

PRECAST CONCRETE

rwassmer Callout

EXISTING WALL SUBSTRATE AND STRUCTURE

rwassmer Callout

EXISTING WALL FINISH

rwassmer Callout REMOVE AND REINSTALL EXTERIOR FINISH AS REQUIRED TO COMPLETE THE WATERPROOFING WORK rwassmer Callout

LAP AIR AND VAPOR BARRIER OVER FLANGE

rwassmer Callout SET FLANGE IN BED OF SEALANT ABOVE EXISTING AIR AND/OR VAPOR BARRIER (WHEN APPLICABLE) rwassmer Callout

CONDUIT

rwassmer Callout

FINISH ESCUTCHEON TO COMPLIMENT BUILDING MATERIALITY

rwassmer Callout

SEALANT, TYP.

rwassmer Callout

SEALANT AND BACKER ROD, TYP.

rwassmer Callout

STAINLESS STEEL PIPE SLEEVE

rwassmer Rectangle rwassmer Text Box

RADIO FIRE ALARM IDIQ

A-400

TYPICAL PENETRATION DETAIL

11X17 - NTS

rwassmer Snapshot rwassmer Dimension

VARIES

rwassmer Dimension

VARIES

Rectangle rwassmer Text Box

RADIO FIRE ALARM IDIQ

E-100

TYPICAL INSTALLATION DIAGRAM

11X17 - NTS

rwassmer Snapshot rwassmer Callout NEW 120v BRANCH CIRCUIT rwassmer Callout

REFER TO WALL PENETRATION TYPICAL DETAIL

rwassmer Callout

WALL-MOUNTED EXTERIOR ANTENNA

PROVIDE FASTENING SYSTEM APPROPRIATE TO BUILDING STRUCTURE AND LOADING REQUIREMENTS rwassmer Rectangle rwassmer Rectangle rwassmer Rectangle rwassmer Rectangle rwassmer Line rwassmer Line rwassmer Rectangle rwassmer PolyLine rwassmer PolyLine rwassmer PolyLine rwassmer Line rwassmer PolyLine rwassmer PolyLine rwassmer PolyLine rwassmer Line rwassmer Line rwassmer Line rwassmer Callout

NEW RADIO FIRE ALARM(RFA) TRANSCEIVER

rwassmer Callout

EXISTING FACP

rwassmer Callout

EXISTING POWER DISTRIBUTION

MATCH POWER SUPPLY (EMERGENCY/NORMAL) OF FACP

rwassmer Callout

ANTENNA CONNECTION IN CONDUIT

QUANTITY AND LOCATION WILL VARY BASED ON AS-BUILT CONDITIONS

PENETRATE EXISTING ASSEMBLIES AS REQUIRED, PATCH AND REPAIR ALL DAMAGE AND OPENINGS rwassmer Callout

EXISTING BUILDING FIRE ALARM SYSTEM

rwassmer Arc rwassmer Callout

BUILDING GROUND SYSTEM

rwassmer Callout

LIGHTNING ARRESTOR

rwassmer Text Box

ROOF LINE

rwassmer Callout

CONNECTION TO EXISTING BUILDING GROUNDING

OR

NEW GROUNDING CONNECTION AS REQ'D

rwassmer Line rwassmer Line rwassmer Callout

FACP TO RFA TRANSCEIVER CONNECTION IN CONDUIT

PolyLine

Installation Diagram