Bldg_610_signed_100 Submittal.pdf
PDF 23 MB Posted
- Attached to
- Repair/Addition Facility 610 Federal contract opportunity
- Solicitation number
- FA4897-12-B-0006
About this file
Attachment 3--Construction Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract.pdf | ||
| Amendment 0005.pdf | ||
| 27 13 13 - COMMUNICATIONS CABLING SYSTEMS Addendum 3.doc | DOC document | |
| 270536 Cable Spec.pdf | ||
| 26 32 13 - ENGINE GENERATORS Addendum 3.doc | DOC document | |
| Amendment 4 with addendum 3.pdf | ||
| 28 31 00 - FIRE ALARM AND MASS NOTIFICATION - BLDG 610 Addendum 3.doc | DOC document | |
| Amendment 0003 with Attachments.pdf | ||
| 610 Addendum 2 Binder.pdf | ||
| Amendment 0002.doc | DOC document | |
| Site Visit Attendance.pdf | ||
| Amendment 0001.doc | DOC document | |
| Solicitation.doc | DOC document | |
| Notification of Complaince with Insurance.doc | DOC document | |
| Addendum 1.pdf | ||
| MHAFB 610 Technical Specifications Book 2.pdf | ||
| General Decision Number.docx | DOCX document | |
| DETERMINATION OF RESPONSIBILITY RFP.doc | DOC document | |
| Solicitation Draft.doc | DOC document | |
| MHAFB 610 Technical Specifications Book 1.pdf |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING
COURTYARD
EXISTING
RADIO
TOWEREXISTING
TELEPHONE
SWITCH ROOM
EXISTING
SERVER ROOM
EXISTING
MECHANICAL
ROOM
SEE GENERAL NOTES FOR WALL FINISH
REMOVAL TO EXISTING SUBSTRATE AS A
REQUIREMENT TO ALLOW ELECTRICAL
AND PLUMBING INSTALLATIONS.
TYP. - ALL INTERIOR WALLS
a: 2785 North Bogus Basin Road Boise, Idaho 83702 p: (208)343.7523 f: (208)343.0940 a: 2785 North Bogus Basin Road Boise, Idaho 83702
EXISTING
COURTYARD
EXISTING
RADIO
TOWEREXISTING
TELEPHONE
SWITCH ROOM
EXISTING
SERVER ROOM
O.T.S. EXISTING
MECHANICAL
ROOM
a: 2785 North Bogus Basin Road Boise, Idaho 83702 p: (208)343.7523 f: (208)343.0940 a: 2785 North Bogus Basin Road Boise, Idaho 83702
440 East Corporate Dr., Ste. 103 Meridian ID 83642 ph 208-288-2181 fax 208-288-2182 projectproject JOB #11MCM07
TOILET PAPER
MOUNTING AREA
60" MIN
" M
IN
W
AL
L H
UN
G
TO
ILE
T
" M
IN
F
LO
OR
M
OU
NT
T
OI
LE
T
1'-6" 3'-6"MIN
CLEAR
FLOOR
SPACE
" M
IN
1'-0"
MAX
3'-6"
MIN
39" - 41"
4'-6"MIN
7" - 9"
1'- 2"
MI
N
1 1 /2"
MI
N
16" - 18"
3'-0"
MIN
3'- 6"
1'- 0"
2'-0"
URINAL SCREEN
WHERE OCCURS
MA
X
2'-0"
MIN
1'-0"
MIN
A B C D E GF
FINISH FLOOR
SOAP
DISPENSER
TOILET PAPER
DISPENSER
GRAB BARS MIRROR TILT MIRROR
(18 x 30)
(UNOBSTRUCTED)
CUSTODIAN
UTILITY SHELF
PAPER TOWEL DISPENSER
& WASTE RECEPTACLE
11" MIN
LEG CLEARANCE
8" MIN
9" M
IN
TO
E
CL
EA
RA
NC
E
" M
IN
17" MINADA STYLE
LEVER FAUCET
2'-6"
MIN
MI
N
MA
X
4'- 0"
MI
N
" M
IN
CLEAR
FLOOR
SPACE
1'-3"
MIN
WALL MOUNTED
SIGNAGE TO BE
LOCATED ON LATCH SIDE
OF DOOR & CLEAR OF
DOOR SWING, MOUNT AT
48" MIN, 60" MAX TO
CENTERLINE OF SIGN
FROM FINISH FLOOR
HEIGHT OF
LETTERING,
5/8" TO 2" MAX,
WITH UPPER
CASE
CHARACTERS
CORRESPONDING
GRADE 2 BRAILLE
INSTALL AT LATCH
SIDE OF DOOR UNO
OR ON RIGHT SIDE
OF DOUBLE DOORS
SEE 5/GA-1 FOR SIZE OF SIGN
3 5/8" STEEL STUDS @ 16" O.C.
ALL NEW WALLS RECEIVE FULL THICK
INSULATION PER SPECIFICATION SECTION
072100
FIRE TEST
HEIGHT
FIRE RATING
TO DECK ABOVE
NONE
NONE TYPE
TYPE
TYPE
TYPE
TYPE
5/8" TYPE "X" GYPSUM BOARD EACH SIDE.
SEE FINISH SCHEDULE FOR MATERIAL FINISH
(USE TILE BACKING BOARD AT WALLS TO
RECEIVE TILE,TYP.)
±4 7/8"
2 1/2" FURRING CHANNELS @ 16" O.C.
C.M.U. WALL PER FLOOR PLAN
FIRE TEST
HEIGHT
FIRE RATING
6" ABOVE CEILING
NONE
NONE
5/8" TYPE "X" GYPSUM BOARD.
SEE FINISH SCHEDULE FOR MATERIAL FINISH
±3 1/8" FIRE TEST
HEIGHT
FIRE RATING
TO DECK ABOVE
UL U419 (NON-BEARING)
1 - HOUR
±7 1/4"
6" STEEL STUDS @ 16" O.C.
ALL NEW WALLS RECEIVE FULL THICK
INSULATION PER SPECIFICATION SECTION
072100
5/8" TYPE "X" GYPSUM BOARD EACH SIDE.
SEE FINISH SCHEDULE FOR MATERIAL FINISH
TYPE
6" FURRING CHANNELS @ 16" O.C.
C.M.U. WALL PER FLOOR PLAN
FIRE TEST
HEIGHT
FIRE RATING
TO DECK ABOVE
NONE
NONE
5/8" TYPE "X" GYPSUM BOARD.
SEE FINISH SCHEDULE FOR MATERIAL FINISH
±6 5/8"
TYPE
6" FURRING CHANNELS @ 16" O.C.
FIRE TEST
HEIGHT
FIRE RATING
TO DECK ABOVE
NONE
NONE
5/8" TYPE "X" GYPSUM BOARD.
SEE FINISH SCHEDULE FOR MATERIAL FINISH
±7 7/8"
(2) LAYERS 5/8" TYPE "X" GYPSUM BOARD.
SEE FINISH SCHEDULE FOR MATERIAL FINISH
SHOWER
SIDE
BREAK ROOM
SIDE
1 1/2" FURRING CHANNELS @ 16" O.C.
WITH TOP AND BOTTOM TRACKS
C.M.U. WALL PER FLOOR PLAN
FIRE TEST
HEIGHT
FIRE RATING
TO DECK ABOVE
NONE
NONE
5/8" TYPE "X" GYPSUM BOARD.
SEE FINISH SCHEDULE FOR MATERIAL FINISH
±4 1/8"
2" RIGID INSULATION
2 1/2" FURRING CHANNELS @ 16" O.C.
WITH TOP AND BOTTOM TRACKS
C.M.U. WALL PER FLOOR PLAN
FIRE TEST
HEIGHT
FIRE RATING
TO DECK ABOVE
NONE
NONE
5/8" TYPE "X" GYPSUM BOARD.
SEE FINISH SCHEDULE FOR MATERIAL FINISH
±5 1/8"
2" RIGID INSULATION
TYPE
1 1/2" FURRING CHANNELS @ 16" O.C.
C.M.U. WALL PER FLOOR PLAN
FIRE TEST
HEIGHT
FIRE RATING
6" ABOVE CEILING
NONE
NONE
5/8" TYPE "X" GYPSUM BOARD.
SEE FINISH SCHEDULE FOR MATERIAL FINISH
±2 1/8"
WALL SIGNAGE
PER UFC-3-120-01
SEE 4/GA-1 FOR MOUNTING @ DOOR LOCATIONS
a: 2785 North Bogus Basin Road Boise, Idaho 83702
DOOR SCHEDULE
REMARKS
ABBREVIATIONS
DOOR TYPES STEEL (HOLLOW METAL) FRAME TYPES
ALLUMINUM FRAME TYPES
a: 2785 North Bogus Basin Road Boise, Idaho 83702 p: (208)343.7523 f: (208)343.0940
ROOM FINISH SCHEDULE
REMARKS
ABBREVIATIONS
12'-0" TYPICAL
12'-0" TYPICAL
4'-0" MAX
O
A-15
3 FIRST LINE OF BRACING, 4'-0"
OR LESS FROM WALL BOUNDARY.
METAL SUSPENSION SYSTEM.
CROSS RUNNER2" MIN MAIN RUNNER
45 deg. MAX 45 deg. MAX
2" MIN
1 5/8' STUD FOR COMPRESSION
VERTICAL HANGER WIRES, 4'-0" O.C.
SPLAY HANGER WIRE @ 12'-0" O.C.
EACH PLANE, EACH RUNNER
a: 2785 North Bogus Basin Road Boise, Idaho 83702
ID DESCRIPTION ACCEPTABLE MANUFACTURERS LAMPS WATTAGE VOLTAGE COLOR MOUNTING NOTES
EE1 DIE CAST ARCHITECTURAL LITHONIA AFN SERIES (2)6W 35 277 DARK ABOVE DOOR
OUTDOOR EMERGENCY LIGHT SURELITE AEL SERIES XENON BRONZE
WET LOCATION ISOLITE EYE SERIES INCLUDED
EX1 THERMOPLASTIC EXIT LITHONIA LQM SERIES LED 0.7 277 WHITE, ABOVE DOOR
NICKEL CADMIUM BATTERY SURELITE LPX SERIES INCLUDED RED
COMPASS CSX SERIES LETTERING
GF1 2X4 ACRYLIC GRID TROFFER LITHONIA GT8 SERIES (3)F32 T8 88 277 RECESSED 1
COMMERCIAL GRADE COOPER GR8 SERIES 3500
3-LAMP, LOW PROFILE COLUMBIA JT8 SERIES
GF2 2X2 ACRYLIC GRID TROFFER LITHONIA GT8 SERIES (3)F17 T8 51 277 RECESSED 1
COMMERCIAL GRADE COOPER GR8 SERIES 3500
3-LAMP, LOW PROFILE COLUMBIA JT8 SERIES
P1 1 HEAD SHOEBOX POLE FIXTURE WITH LITHONIA KAD SERIES (1)400W 465 277 DARK POLE 2
25' SQUARE STRAIGHT STEEL POLE LUMARK HR SERIES METAL BRONZE MOUNTED
TYPE 3 DISTRIBUTION SPAULDING RCS SERIES HALIDE
P2 1 HEAD SHOEBOX POLE FIXTURE WITH LITHONIA KAD SERIES (1)400W 465 277 DARK POLE 2
25' SQUARE STRAIGHT STEEL POLE LUMARK HR SERIES METAL BRONZE MOUNTED
TYPE 4 DISTRIBUTION SPAULDING RCS SERIES HALIDE
P3 CYLINDRICAL SHAPED POST TOP LITHONIA KVR SERIES (1)100W 130 277 DARK POLE 2
WITH SYMMETRICAL DISTRIBUTION McGRAW EDISON CIRRUS SERIES METAL BRONZE MOUNTED
15' ROUND STEEL POLE SPAULDING DL SERIES HALIDE
RR1 6" DOWNLIGHT, HORIZONTAL LAMP LITHONIA LF6N SERIES (1)CF32 TRT 36 277 RECESSED
WITH CLEAR DIFFUSER PORTFOLIO C6142 SERIES 3500
PRESCOLITE CFT SERIES
SF1 4' STEEL CHANNEL STRIPLIGHT LITHONIA C SERIES (2)F32 T8 59 277 CHAIN HUNG 3
COOPER SS SERIES +8'-6" AFF
COLUMBIA CS SERIES
WF1 4' STEEL WALL BRACKET WITH LITHONIA WC SERIES (2)F32 T8 59 277 WALL
ACRYLIC DIFFUSER COOPER BS SERIES ABOVE
COLUMBIA W SERIES MIRROR
WP1 BI-LEVEL WALL PACK EVERLAST EOF-ED-100W-BL-120-40-X (1)100W 130 277 BRONZE +12'-0" AFF
(AS DIRECTED BY THE GOVERNMENT METAL
NO EQUALS ALLOWED) HALIDE
GENERAL NOTES:
1. LUMINAIRE SUBSTITUTIONS ARE ALLOWED AND MUST MEET FUNCTIONALITY, AESTETICS, AND PERFORMANCE RATING OF FIXTURES, TO BE APPROVED BY GOVERNMENT UNO.
2. PROVIDE ALL ACCESSORIES AS REQUIRED FOR A COMPLETE INSTALLATION.
NOTES:
1. SEE LAY-IN MOUNTING DETAIL ON SHEET E-8.
2. SEE POLE BASE DETAIL ON SHEET E-1.
3. COORDINATE MOUNTING HEIGHTS AND FIXTURE PLACEMENT WITH MECHANICAL DUCTWORK.
LUMINAIRE SCHEDULE
COMcheck Software Version 3.8.1
Interior Lighting Compliance Certificate
2009 IECC
Section 1: Project Information Project Type: New Construction Project Title : REPAIR/ADDITION TO FACILITY 610
Construction Site: Owner/Agent: Designer/Contractor:
Marc Pride DC Engineering 440 E Corporate Drive Meridian, ID 83642 208-288-2181 mpride@dcengineering.net
Section 2: Interior Lighting and Power Calculation A
Area Category B
Floor Area (ft2)
C Allowed
Watts / ft2
D Allowed Watts
(B x C) Workshop 8051 1.4 11271
Total Allowed Watts = 11271
Section 3: Interior Lighting Fixture Schedule A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B
Lamps/ Fixture
C # of Fixtures
D Fixture Watt.
E (C X D)
Workshop (8051 sq.ft.)
Linear Fluorescent 1: GF1: 2X4 LAYIN / 48” T8 32W / Electronic 3 56 88 4928 Linear Fluorescent 4: GF2: 2X2 LAYIN / 24” T8 17W / Electronic 3 3 51 153 Compact Fluorescent 1: RR1: DOWNLIGHT / Triple 4-pin 32W / Electronic 1 5 36 180 Linear Fluorescent 2: SF1: 4’ STRIP / 48” T8 32W / Electronic 2 28 59 1652 Linear Fluorescent 3: WF1: WALL BRACKET / 48” T8 32W / Electronic 2 3 59 177 Linear Fluorescent 5: (E): EXISTING 2X4 / 48” T8 32W / Electronic 3 24 88 2112 Linear Fluorescent 6: (R): RELOCATED 2X4 / 48” T8 32W / Electronic 3 4 88 352
Total Proposed Watts = 9554
Section 4: Requirements Checklist
Lighting Wattage:
1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Watts
Proposed Watts
Complies
11271 9554 YES
Controls, Switching, and Wiring:
2. Daylight zones under skylights more than 15 feet from the perimeter have lighting controls separate from daylight zones adjacent to vertical fenestration.
3. Daylight zones have individual lighting controls independent from that of the general area lighting.
Exceptions:
Contiguous daylight zones spanning no more than two orientations are allowed to be controlled by a single controlling device.
Daylight spaces enclosed by walls or ceiling height partitions and containing two or fewer light fixtures are not required to have a separate switch for general area lighting.
4. Independent controls for each space (switch/occupancy sensor).
Exceptions:
Areas designated as security or emergency areas that must be continuously illuminated.
Lighting in stairways or corridors that are elements of the means of egress.
5. Master switch at entry to hotel/motel guest room.
6. Individual dwelling units separately metered.
7. Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control of the nonexempt lighting.
8. Each space required to have a manual control also allows for reducing the connected lighting load by at least 50 percent by either controlling all luminaires, dual switching of alternate rows of luminaires, alternate luminaires, or alternate lamps, switching the middle lamp luminaires independently of other lamps, or switching each luminaire or each lamp.
Exceptions:
Only one luminaire in space.
An occupant-sensing device controls the area.
The area is a corridor, storeroom, restroom, public lobby or sleeping unit.
Areas that use less than 0.6 Watts/sq.ft.
9. Automatic lighting shutoff control in buildings larger than 5,000 sq.ft.
Exceptions:
Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security.
10. Photocell/astronomical time switch on exterior lights.
Exceptions:
Lighting intended for 24 hour use.
11. Tandem wired one-lamp and three-lamp ballasted luminaires (No single-lamp ballasts).
Exceptions:
Electronic high-frequency ballasts; Luminaires on emergency circuits or with no available pair.
Interior Lighting PASSES: Design 15% better than code.
Section 5: Compliance Statement Compliance Statement: The proposed lighting design represented in this document is consistent with the building plans, specifications and other calculations submitted with this permit application. The proposed lighting system has been designed to meet the 2009 IECC requirements in COMcheck Version 3.8.1 and to comply with the mandatory requirements in the Requirements Checklist.
Name - Title Signature Date
440 East Corporate Dr., Ste. 103 Meridian ID 83642
440 East Corporate Dr., Ste. 103 Meridian ID 83642 ph 208-288-2181 fax 208-288-2182 projectproject JOB #11MCM07
DSB (208V)AMPS
Panel B 62
UPS1(U1) 88
Panel A 33
HVAC1 160
TTP1 100
Total 443
PanelGPB(48V0) AMPS
Ppanel DSB 192.0
MS1 31
MS2 78
CRAC4 21
Panel H1 63
Total 385.0
Panel MPB(480V)AMPS
Panel DSB 385.0 site light 32 Panel D 23 Panel E 68
Total 508.0
PANELBOARD SCHEDULE
CONNECTED LOADS: Amps VA NOTES:
PHASE A: 49 5869
PHASE B: 35 4162
PHASE C: 32 3892
TOTAL: 13923
LOAD NOTES AMPS/ CKT CKT AMPS/ NOTE LOAD
(VA) LOAD SERVED POLES NO PHASE NO POLES LOAD SERVED (VA)
696 N 20 1 1 A 2 20 1 E 1232 R 20 1 3 B 4 20 1 E 1232 R 20 1 5 C 6 20 1 E
E 20 1 7 A 8 20 1 E E 20 1 9 B 10 20 1 E E 40 1 11 C 12 20 1 E
1408 R 20 1 13 A 14 20 1 E E 20 1 15 B 16 50 2 E E 20 1 17 C 18 - - E
E 20 1 19 A 20 20 1 R 885 500 N 20 1 21 B 22 20 1 E 500 N 20 1 23 C 24 20 1 E
2880 N 60 3 25 A 26 20 1 E 2430 N - - 27 B 28 20 1 E 2160 N - - 29 C 30 30 1 E
E 20 3 31 A 32 20 1 E E - - 33 B 34 20 1 E E - - 35 C 36 20 1 E
PANEL: (E)A PROJECT: MHAFB BLDG 610
VOLTAGE: 120/208V PHASE: 3 WIRE: 4 AMPERE RATING: 100A SC RATING: MAIN: 100A MCB
ENTRY: BOTTOM MOUNTING: SURFACE
E - EXISTING CIRCUIT BREAKER TO REMAIN
R - REUSE EXISTING CIRCUIT BREAKER
N - NEW CIRCUIT BREAKER REQUIRED
FC-1 SPARE
LTG - RM 125 SPARE
LTG - RM 125 SPARE
(E)VAULT LTS & REC (E)REC - RM 104, 106
(E)VAULT SUMP SPARE
(E)MICROWAVE TANK SPARE
LTG - RM 103 (E)INTERCOM, BUZZER, DOOR LOCKS
(E)TELE EQUIPMENT SPARE
(E)DATA RACKS ---
(E)LTS - NORTHERN TELE & SWITCH ROOM LTG - RM 104
VESDA PANEL POWER SUPPLY SPARE
VESDA BEACON POWER SUPPLY SPARE
PANEL AA SPARE
--- SPARE
--- SPARE
--- SPARE
(E)TELECOM EQUIP SPARE
--- SPARE
PANELBOARD SCHEDULE
CONNECTED LOADS: Amps VA LOAD TYPES: 1 = LIGHTING NOTES:
PHASE A: 24 2880 2 = RECEPTACLES
PHASE B: 20 2430 3 = MISC
PHASE C: 18 2160 4 = MOTOR
TOTAL: 7470 5 = KITCHEN
LOAD LOAD AMPS/ CKT CKT AMPS/ LOAD LOAD
(VA) LOAD SERVED TYPE POLES NO PHASE NO POLES TYPE LOAD SERVED (VA)
1080 2 20 1 1 A 2 20 1 2 1080 1080 2 20 1 3 B 4 20 1 2 1080 1080 2 20 1 5 C 6 20 1 2 1080
720 2 20 1 7 A 8 20 1 270 3 20 1 9 B 10 20 1
20 1 11 C 12 20 1
20 1 13 A 14 20 1 20 1 15 B 16 20 1 20 1 17 C 18 20 1
20 1 19 A 20 20 1 20 1 21 B 22 20 1 20 1 23 C 24 20 1
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
REC - INFRASTRUCTURE SPARE
EF-6 SPARE
SPARE SPARE
REC - INFRASTRUCTURE REC - INFRASTRUCTURE
REC - INFRASTRUCTURE REC - INFRASTRUCTURE
REC - INFRASTRUCTURE REC - INFRASTRUCTURE
ENTRY: BOTTOM MOUNTING: SURFACE
PANEL: (N)AA PROJECT: MHAFB BLDG 610
VOLTAGE: 120/208V PHASE: 3 WIRE: 4 AMPERE RATING: 100A SC RATING: 10kA MAIN: MLO
PANELBOARD SCHEDULE
CONNECTED LOADS: Amps VA NOTES:
PHASE A: 28 3374
PHASE B: 31 3770
PHASE C: 33 3948
TOTAL: 11092
LOAD NOTE AMPS/ CKT CKT AMPS/ LOAD LOAD
(VA) LOAD SERVED POLES NO PHASE NO POLES TYPE LOAD SERVED (VA)
134 R 20 1 1 A 2 20 1 134 R 20 1 3 B 4 20 1 D 720 R 20 1 5 C 6 20 1 D
720 R 20 1 7 A 8 20 1 E 1056 N 20 2 9 B 10 20 1 1056 N - - 11 C 12 20 1 R 1068
1056 R 20 1 13 A 14 20 2 N 1056 1044 R 20 1 15 B 16 - - N 1056 696 N 20 1 17 C 18
408 R 20 3 19 A 20 20 3 E 480 R - - 21 B 22 - - E
PANEL: (E)D PROJECT: MHAFB BLDG 610
VOLTAGE: 120/208V PHASE: 3 WIRE: 4 AMPERE RATING: 100A SC RATING: MAIN: MLO
ENTRY: BOTTOM MOUNTING: SURFACE
E - EXISTING CIRCUIT BREAKER TO REMAIN
R - REUSE EXISTING CIRCUIT BREAKER
N - NEW CIRCUIT BREAKER REQUIRED
D - DEMO
WH-1 SPARE
1 - PROVIDE RED CIRCUIT BREAKER
WH-2 (D)EMCS PANEL
B-1 (D)TEMP CNTL PANEL & FIRE ALARM
B-2 (E)SPRINKLER CONTROL
P-1 SPARE
--- EF-4, EF-5
FC-4, FC-5, FC-6 P-1
FC-2, FC-3 ---
FC-7, FC-8 SPACE
DOAS SPARE
PANELBOARD SCHEDULE
CONNECTED LOADS: Amps VA LOAD TYPES: 1 = LIGHTING NOTES:
PHASE A: 53 6350 2 = RECEPTACLES
PHASE B: 51 6108 3 = MISC
PHASE C: 58 6953 4 = MOTOR
TOTAL: 19411 5 = KITCHEN
LOAD LOAD AMPS/ CKT CKT AMPS/ LOAD LOAD
(VA) LOAD SERVED TYPE POLES NO PHASE NO POLES TYPE LOAD SERVED (VA)
902 1 20 1 1 A 2 20 1 1408 1 20 1 3 B 4 20 1 1276 1 20 1 5 C 6 20 1
792 1 20 1 7 A 8 20 1 500 3 20 1 9 B 10 20 1
20 1 11 C 12 20 1
20 1 13 A 14 20 1 20 1 15 B 16 20 1 2 1080
897 1 20 1 17 C 18 20 1 2 1080
720 2 20 1 19 A 20 20 1 2 1080 540 2 20 1 21 B 22 20 1 2 500 720 2 20 1 23 C 24 20 1 2 720
360 20 1 25 A 26 20 1 2 720 20 1 27 B 28 20 1 2 1000 20 1 29 C 30 20 1 2 1000
696 3 20 1 31 A 32 20 1 2 1080 20 1 33 B 34 20 1 2 1080
900 2 20 1 35 C 36 20 1 2 360
20 1 37 A 38 20 1 20 1 39 B 40 20 1 20 1 41 C 42 20 1
SPARE SPARE
SPARE SPARE
REC - CORRIDORS REC - MULL CHARGER
SPARE SPARE
FC-1 REC - RM 107, 108
SPARE REC - RM 104
REC - COURTYARD REC - RM 111
SPARE REC - RM 112 COUNTER
SPARE REC - RM 112 REFER
REC - RM 109 DRINKING FOUNTAIN
REC- RM 120 REC - RM 112, 113, 114, 122
LTG- WALL PKS, RECESSED CANS REC - RM 116
REC - RM 109 REC - RM 116, 117
SPARE SPARE
SPARE REC - RM 115
LTG - RM 103, 120 SPARE
LIGHTING CONTROL PANEL SPARE
SPARE SPARE
LTG - RM 115, 116, 117 SPARE
LTG - RM 101, 102, 105, 106, 111, 119 SPARE
LTG - RM 112, 113, 114, 118, 123. 107, 108 SPARE
ENTRY: BOTTOM MOUNTING: SURFACE
1. PROVIDE RED BREAKER.
PANEL: (N)E PROJECT: MHAFB BLDG 610
VOLTAGE: 120/208V PHASE: 3 WIRE: 4 AMPERE RATING: 125A SC RATING: 10kA MAIN: 125A MCB
PANELBOARD SCHEDULE
CONNECTED LOADS: Amps VA LOAD TYPES: 1 = LIGHTING NOTES:
PHASE A: 67 8000 2 = RECEPTACLES
PHASE B: 58 7000 3 = MISC
PHASE C: 58 7000 4 = MOTOR
TOTAL: 22000 5 = KITCHEN
LOAD LOAD AMPS/ CKT CKT AMPS/ LOAD LOAD
(VA) LOAD SERVED TYPE POLES NO PHASE NO POLES TYPE LOAD SERVED (VA)
1000 2 20 2 1 A 2 20 1 2 1000 1000 2 - - 3 B 4 20 1 2 1000 1000 2 20 1 5 C 6 20 1 2 1000
1000 2 20 1 7 A 8 20 1 2 1000 1000 2 20 1 9 B 10 20 1 2 1000 1000 2 20 1 11 C 12 20 1 2 1000
20 1 13 A 14 20 1 2 1000 20 1 15 B 16 20 1 2 1000 20 1 17 C 18 20 1 2 1000
20 1 19 A 20 20 1 2 1000 20 1 21 B 22 20 1 2 1000 20 1 23 C 24 20 1 2 1000
20 1 25 A 26 20 1 2 1000 20 1 27 B 28 20 1 2 1000 20 1 29 C 30 20 1 2 1000
20 1 31 A 32 20 1 2 1000 20 1 33 B 34 20 1 20 1 35 C 36 20 1
20 1 37 A 38 20 1 20 1 39 B 40 20 1 20 1 41 C 42 20 1
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE SPARE
SPARE REC - SERVER ROOM RACK
SPARE SPARE
SPARE REC - SERVER ROOM RACK
SPARE REC - SERVER ROOM RACK
SPARE REC - SERVER ROOM RACK
SPARE REC - SERVER ROOM RACK
SPARE REC - SERVER ROOM RACK
SPARE REC - SERVER ROOM RACK
SPARE REC - SERVER ROOM RACK
SPARE REC - SERVER ROOM RACK
SPARE REC - SERVER ROOM RACK
REC - SERVER ROOM RACK REC - SERVER ROOM RACK
REC - SERVER ROOM RACK REC - SERVER ROOM RACK
REC - SERVER ROOM RACK REC - SERVER ROOM RACK
--- REC - SERVER ROOM RACK
REC - SERVER ROOM RACK REC - SERVER ROOM RACK
REC - SERVER ROOM RACK REC - SERVER ROOM RACK
ENTRY: BOTTOM MOUNTING: SURFACE
PANEL: (N)U1 PROJECT: MHAFB BLDG 610
VOLTAGE: 120/208V PHASE: 3 WIRE: 4 AMPERE RATING: 100A SC RATING: 10kA MAIN: 100A MCB
PANELBOARD SCHEDULE
CONNECTED LOADS: Amps VA LOAD TYPES: 1 = LIGHTING NOTES:
PHASE A: 67 8000 2 = RECEPTACLES
PHASE B: 58 7000 3 = MISC
PHASE C: 58 7000 4 = MOTOR
TOTAL: 22000 5 = KITCHEN
LOAD LOAD AMPS/ CKT CKT AMPS/ LOAD LOAD
(VA) LOAD SERVED TYPE POLES NO PHASE NO POLES TYPE LOAD SERVED (VA)
1000 2 20 2 1 A 2 20 1 2 1000 1000 2 - - 3 B 4 20 1 2 1000 1000 2 20 1 5 C 6 20 1 2 1000
1000 2 20 1 7 A 8 20 1 2 1000 1000 2 20 1 9 B 10 20 1 2 1000 1000 2 20 1 11 C 12 20 1 2 1000
20 1 13 A 14 20 1 2 1000 20 1 15 B 16 20 1 2 1000 20 1 17 C 18 20 1 2 1000
20 1 19 A 20 20 1 2 1000 20 1 21 B 22 20 1 2 1000 20 1 23 C 24 20 1 2 1000
20 1 25 A 26 20 1 2 1000 20 1 27 B 28 20 1 2 1000 20 1 29 C 30 20 1 2 1000
20 1 31 A 32 20 1 2 1000 20 1 33 B 34 20 1 20 1 35 C 36 20 1
20 1 37 A 38 20 1 20 1 39 B 40 20 1 20 1 41 C 42 20 1
REC - SERVER ROOM RACK
ENTRY: BOTTOM MOUNTING: SURFACE
SPARE
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
SPARE
SPARE
REC - SERVER ROOM RACK
SPARE
SPARE
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
REC - SERVER ROOM RACK
SC RATING: 10kA MAIN: 100A MCB
REC - SERVER ROOM RACK
PROJECT: MHAFB BLDG 610PANEL: (N)U2
VOLTAGE: 120/208V PHASE: 3 WIRE: 4 AMPERE RATING: 100A
PANELBOARD SCHEDULE
CONNECTED LOADS: Amps VA LOAD TYPES: 1 = LIGHTING NOTES:
PHASE A: 42 11634 2 = RECEPTACLES
PHASE B: 42 11634 3 = MISC
PHASE C: 42 11634 4 = MOTOR
TOTAL: 34902 5 = KITCHEN
LOAD LOAD AMPS/ CKT CKT AMPS/ LOAD LOAD
(VA) LOAD SERVED TYPE POLES NO PHASE NO POLES TYPE LOAD SERVED (VA)
120 3 1 A 2 30 3 4 5817
- - 3 B 4 - - 4 5817
- - 5 C 6 - - 4 5817
7 A 8 30 3 4 5817 9 B 10 - - 4 5817 11 C 12 - - 4 5817
7 A 8 30 3 4 5817 9 B 10 - - 4 5817 11 C 12 - - 4 5817
CRAC-3
SPACE ---
SPACE ---
SPACE CRAC-2
SPACE ---
SPACE ---
SPACE
MAIN CRAC-1
ENTRY: BOTTOM MOUNTING: SURFACE
MAIN BREAKER SHUNT TRIP TYPE
PANEL: (N)H1 PROJECT: MHAFB BLDG 610
VOLTAGE: 277/480V PHASE: 3 WIRE: 4 AMPERE RATING: 100 SC RATING: 65kA MAIN: MLO
PANELBOARD SCHEDULE
CONNECTED LOADS: Amps VA LOAD TYPES: 1 = LIGHTING NOTES:
PHASE A: 66 7967 2 = RECEPTACLES
PHASE B: 66 7978 3 = MISC
PHASE C: 39 4683 4 = MOTOR
TOTAL: 20628 5 = KITCHEN
LOAD LOAD AMPS/ CKT CKT AMPS/ LOAD LOAD
(VA) LOAD SERVED TYPE POLES NO PHASE NO POLES TYPE LOAD SERVED (VA)
250 3 30 2 1 A 2 30 2 3 250 250 3 - - 3 B 4 - - 3 250 250 3 30 2 5 C 6 30 2 3 250
250 3 - - 7 A 8 - - 3 250 250 3 30 2 9 B 10 30 2 3 250 250 3 - - 11 C 12 - - 3 250
1000 2 20 1 13 A 14 30 1 2 3000 1920 2 20 1 15 B 16 20 1 2 638 3000 2 30 1 17 C 18 20 1 2 683
467 1 20 1 19 A 20 20 1 3 500 1920 2 20 1 21 B 22 20 1 3 500
3 20 1 23 C 24 20 1
1000 3 50 3 25 A 26 50 3 3 1000 1000 3 - - 27 B 28 - - 3 1000 1000 3 - - 29 C 30 - - 3 1000
20 1 31 A 32 20 1 20 1 33 B 34 20 1 20 1 35 C 36 20 1
TOWER 1 TOWER 2
SPARE SPARE
GIANT VOICE EMCS
SPARE SPARE
NETWORK RACK RACK 5
LTG - RM 121, EF-7 FIRE ALARM PANELS (NOTE 1)
LAN RACK NETWORK RACK
LMR RACK RACK 6
RECTIFIER RECTIFIER
RECTIFIER RECTIFIER
RECTIFIER RECTIFIER
ENTRY: BOTTOM MOUNTING: SURFACE
PANEL: (N)B PROJECT: MHAFB BLDG 610
VOLTAGE: 120/208V PHASE: 3 WIRE: 4 AMPERE RATING: 100A SC RATING: 18kA MAIN: MLO
SPARE
SPARE
SPARE
SPARE
440 East Corporate Dr., Ste. 103 Meridian ID 83642
A
B
C
D
S
P
440 East Corporate Dr., Ste. 103 Meridian ID 83642
L
Meridian ID 83642
| Bldg 610 Signed 100%Submittal.pdf |
| 11MCM07_GE-1 |
| Layout1 |
| 11MCM07_GE-2 |
| Layout1 |
| 11MCM07_D-7 |
| Layout1 |
| 11MCM07_D-8 |
| Layout1 |
| 11MCM07_D-9 |
| Layout1 |
| 11MCM07_D-10 |
| Layout1 |
| 11MCM07_D-11 |
| Layout1 |
| 11MCM07_E-1 |
| Layout1 |
| 11MCM07_E-2 |
| Layout1 |
| 11MCM07_E-3 |
| Layout1 |
| 11MCM07_E-4 |
| Layout1 |
| 11MCM07_E-5 |
| Layout1 |
| 11MCM07_E-6 |
| Layout1 |
| 11MCM07_E-7 |
| Layout1 |
| 11MCM07_E-8 |
| Layout1 |
| 11MCM07_E-9 |
| Layout1 |
| 11MCM07_E-10 |
| Layout1 |
File details come from the government source that posted it. Updated .