26 32 13 - ENGINE GENERATORS Addendum 3.doc
DOC document 60 KB Posted
- Attached to
- Repair/Addition Facility 610 Federal contract opportunity
- Solicitation number
- FA4897-12-B-0006
About this file
Revised Specification Section 26 32 13 Engine Generators
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract.pdf | ||
| Amendment 0005.pdf | ||
| Amendment 4 with addendum 3.pdf | ||
| 28 31 00 - FIRE ALARM AND MASS NOTIFICATION - BLDG 610 Addendum 3.doc | DOC document | |
| 27 13 13 - COMMUNICATIONS CABLING SYSTEMS Addendum 3.doc | DOC document | |
| 270536 Cable Spec.pdf | ||
| Amendment 0003 with Attachments.pdf | ||
| Amendment 0002.doc | DOC document | |
| 610 Addendum 2 Binder.pdf | ||
| Site Visit Attendance.pdf | ||
| Amendment 0001.doc | DOC document | |
| Solicitation.doc | DOC document | |
| MHAFB 610 Technical Specifications Book 1.pdf | ||
| Notification of Complaince with Insurance.doc | DOC document | |
| Addendum 1.pdf | ||
| MHAFB 610 Technical Specifications Book 2.pdf | ||
| General Decision Number.docx | DOCX document | |
| DETERMINATION OF RESPONSIBILITY RFP.doc | DOC document | |
| Solicitation Draft.doc | DOC document | |
| Bldg_610_signed_100 Submittal.pdf |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Amendment 0004/FA4897-12-B-0006
SECTION 26 32 13 - ENGINE GENERATORS
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes packaged engine-generator sets for emergency power supply with the following features:
1. Diesel engine capable of operating on both JP-5 and JP-8 fuel.
2. Unit mounted cooling system.
3. Unit mounted control and monitoring.
4. Outdoor enclosure.
B. See Section 263600 "Transfer Switches" for transfer switches including sensors and relays to initiate automatic-starting and -stopping signals for engine-generator sets.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of packaged engine generator and accessory indicated.
B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
1.3 INFORMATIONAL SUBMITTALS
A. Manufacturer Seismic Qualification Certification: Submit certification that engine-generator set, batteries, battery racks, accessories, and components will withstand seismic forces specified.
1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the unit will be fully operational after the seismic event."
2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.
3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.
1.4 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for installation of units required for this Project.
B. Manufacturer Qualifications: A qualified manufacturer. Maintain, within 100 miles of Project site, a service center capable of providing training, parts, and emergency maintenance repairs.
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
D. Comply with ASME B15.1.
E. Comply with NFPA 37.
F. Comply with NFPA 70.
G. Comply with NFPA 110 requirements for Level 1 emergency power supply system.
H. Comply with UL 2200.
I. Engine Exhaust Emissions: Comply with applicable state and local government requirements.
1.6 PROJECT CONDITIONS
A. Environmental Conditions: Engine-generator system shall withstand the following environmental conditions without mechanical or electrical damage or degradation of performance capability:
1. Ambient Temperature: Minus 15 to plus 40 deg C.
2. Relative Humidity: 0 to 95 percent.
3. Altitude: 3300
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
C. Basis-of-Design Product: Subject to compliance with requirements, provide or a comparable product by one of the following:
1. Caterpillar; Engine Div.
2.2 ENGINE-GENERATOR SET
A. Factory-assembled and -tested, engine-generator set.
B. Mounting Frame: Maintain alignment of mounted components without depending on concrete foundation; and have lifting attachments.
C. Capacities and Characteristics
1. Power Output Ratings: Nominal ratings as indicated. 300kW at .8pf
2. Output Connections: Three-phase, four-wire.
3. Nameplates: For each major system component to identify manufacturer's name and address, and model and serial number of component.
D. Generator-Set Performance
1. Steady-State Voltage Operational Bandwidth: 3 percent of rated output voltage from no load to full load.
2. Transient Voltage Performance: Not more than 20 percent variation for 50 percent step-load increase or decrease. Voltage shall recover and remain within the steady-state operating band within three seconds.
3. Steady-State Frequency Operational Bandwidth: 0.5 percent of rated frequency from no load to full load.
4. Steady-State Frequency Stability: When system is operating at any constant load within the rated load, there shall be no random speed variations outside the steady-state operational band and no hunting or surging of speed.
5. Transient Frequency Performance: Less than 5 percent variation for 50 percent step-load increase or decrease. Frequency shall recover and remain within the steady-state operating band within five seconds.
6. Output Waveform: At no load, harmonic content measured line to line or line to neutral shall not exceed 5 percent total and 3 percent for single harmonics. Telephone influence factor, determined according to NEMA MG 1, shall not exceed 50 percent.
7. Sustained Short-Circuit Current: For a 3-phase, bolted short circuit at system output terminals, system shall supply a minimum of 250 percent of rated full-load current for not less than 10 seconds and then clear the fault automatically, without damage to generator system components.
8. Start Time: Comply with NFPA 110, Emergency Power System requirements.
2.3 ENGINE
A. Fuel: Diesel, JP-5, JP-8 B. Rated Engine Speed: 1800 rpm.
C. Lubrication System: The following items are mounted on engine or skid:
1. Filter and Strainer: Rated to remove 90 percent of particles 5 micrometers and smaller while passing full flow.
2. Thermostatic Control Valve: Control flow in system to maintain optimum oil temperature. Unit shall be capable of full flow and is designed to be fail-safe.
3. Crankcase Drain: Arranged for complete gravity drainage to an easily removable container with no disassembly and without use of pumps, siphons, special tools, or appliances.
D. Engine Fuel System
1. Main Fuel Pump: Mounted on engine. Pump ensures adequate primary fuel flow under starting and load conditions.
2. Relief-Bypass Valve: Automatically regulates pressure in fuel line and returns excess fuel to source.
E. Coolant Jacket Heater: Electric-immersion type, factory installed in coolant jacket system. Comply with NFPA 110 requirements for Level 1 equipment for heater capacity.
F. Governor: Adjustable isochronous, with speed sensing.
G. Cooling System: Closed loop, liquid cooled, with radiator factory mounted on engine-generator-set mounting frame and integral engine-driven coolant pump.
1. Coolant: Solution of 50 percent ethylene-glycol-based antifreeze and 50 percent water, with anticorrosion additives as recommended by engine manufacturer.
2. Temperature Control: Self-contained, thermostatic-control valve modulates coolant flow automatically to maintain optimum constant coolant temperature as recommended by engine manufacturer.
H. Air-Intake Filter: Heavy-duty, engine-mounted air cleaner with replaceable dry-filter element and "blocked filter" indicator.
I. Starting System: 24V electric, with negative ground.
1. Components: Sized so they will not be damaged during a full engine-cranking cycle with ambient temperature at maximum specified in Part 1 "Project Conditions" Article.
2. Cranking Motor: Heavy-duty unit that automatically engages and releases from engine flywheel without binding.
3. Cranking Cycle: As required by NFPA 110 for system level specified
4. Battery: Adequate capacity within ambient temperature range specified in Part 1 "Project Conditions" Article to provide specified cranking cycle at least twice without recharging.
5. Battery-Charging Alternator: Factory mounted on engine with solid-state voltage regulation and 35-A minimum continuous rating.
a. Battery Charger: Current-limiting, automatic-equalizing and float-charging type. Unit shall comply with UL 1236.
2.4 FUEL OIL STORAGE
A. Comply with NFPA 30.
B. Base-Mounted Fuel Oil Tank: Factory installed and piped, complying with UL 142 fuel oil tank. Features include the following:
1. Tank level indicator.
2. Capacity: 700 gallons
3. Vandal-resistant fill cap.
4. Containment Provisions: Comply with requirements of authorities having jurisdiction.
5. Width not to exceed: 84”
6. Length no to exceed: 192”
7. Height not to exceed: 48”
2.5 CONTROL AND MONITORING
A. Automatic Starting System Sequence of Operation: When mode-selector switch on the control and monitoring panel is in the automatic position, remote-control contacts in one or more separate automatic transfer switches initiate starting and stopping of generator set. When mode-selector switch is switched to the on position, generator set starts. The off position of same switch initiates generator-set shutdown. When generator set is running, specified system or equipment failures or derangements automatically shut down generator set and initiate alarms.
B. Configuration: Operating and safety indications, protective devices, basic system controls, and engine gages shall be grouped in a common control and monitoring panel mounted on the generator set. Mounting method shall isolate the control panel from generator-set vibration.
C. Indicating and Protective Devices and Controls: As required by NFPA 110 system, and the following:
1. AC voltmeter.
2. AC ammeter.
3. AC frequency meter.
4. DC voltmeter (alternator battery charging).
5. Engine-coolant temperature gage.
6. Engine lubricating-oil pressure gage.
7. Running-time meter.
8. Ammeter-voltmeter, phase-selector switch(es).
9. Generator-voltage adjusting rheostat.
10. Generator overload.
D. Supporting Items: Include sensors, transducers, terminals, relays, and other devices and include wiring required to support specified items. Locate sensors and other supporting items on engine or generator, unless otherwise indicated.
E. Common Remote Audible Alarm: Comply with NFPA 110 requirements for Level 1 systems. Include necessary contacts and terminals in control and monitoring panel.
1. Overcrank shutdown.
2. Coolant low-temperature alarm.
3. Control switch not in auto position.
4. Battery-charger malfunction alarm.
5. Battery low-voltage alarm.
F. Remote Alarm Annunciator: Comply with NFPA 99. An LED labeled with proper alarm conditions shall identify each alarm event and a common audible signal shall sound for each alarm condition. Silencing switch in face of panel shall silence signal without altering visual indication. Connect so that after an alarm is silenced, clearing of initiating condition will reactivate alarm until silencing switch is reset. Cabinet and faceplate are surface- or flush-mounting type to suit mounting conditions indicated.
G. Integral load bank for generator full load testing.
2.6 GENERATOR OVERCURRENT AND FAULT PROTECTION
A. Generator Circuit Breaker: Molded-case, thermal-magnetic type; 100 percent rated; complying with NEMA AB 1 and UL 489.
1. Tripping Characteristic: Designed specifically for generator protection.
2. Trip Rating: Matched to generator rating.
3. Shunt Trip: Connected to trip breaker when generator set is shut down by other protective devices.
4. Mounting: Adjacent to or integrated with control and monitoring panel.
B. Ground-Fault Indication: Comply with NFPA 70, "Emergency System" signals for ground-fault. Integrate ground-fault alarm indication with other generator-set alarm indications.
2.7 GENERATOR, EXCITER, AND VOLTAGE REGULATOR
A. Comply with NEMA MG 1.
B. Drive: Generator shaft shall be directly connected to engine shaft. Exciter shall be rotated integrally with generator rotor.
C. Electrical Insulation: Class H or Class F.
D. Stator-Winding Leads: Brought out to terminal box to permit future reconnection for other voltages if required.
E. Construction shall prevent mechanical, electrical, and thermal damage due to vibration, overspeed up to 125 percent of rating, and heat during operation at 110 percent of rated capacity.
F. Enclosure: Dripproof.
G. Instrument Transformers: Mounted within generator enclosure.
H. Voltage Regulator: Solid-state type, separate from exciter, providing performance as specified.
1. Adjusting rheostat on control and monitoring panel shall provide plus or minus 5 percent adjustment of output-voltage operating band.
I. Strip Heater: Thermostatically controlled unit arranged to maintain stator windings above dew point.
J. Windings: Two-thirds pitch stator winding and fully linked amortisseur winding.
2.8 OUTDOOR GENERATOR-SET ENCLOSURE
A. Engine Cooling Airflow through Enclosure: Maintain temperature rise of system components within required limits when unit operates at 110 percent of rated load for 2 hours with ambient temperature at top of range specified in system service conditions.
1. Louvers: Fixed-engine, cooling-air inlet and discharge. Storm-proof and drainable louvers prevent entry of rain and snow.
2. Automatic Dampers: At engine cooling-air inlet and discharge. Dampers shall be closed to reduce enclosure heat loss in cold weather when unit is not operating.
B. Interior Lights with Switch: Factory-wired, vaporproof-type fixtures within housing; arranged to illuminate controls and accessible interior. Arrange for external electrical connection.
1. AC lighting system and connection point for operation when remote source is available.
2.9 INTEGRAL LOAD BANK
A. All 250 kW generators or larger shall have an integral load bank sized to a minimum of at 50% of the generator nameplate kW rating.
B. Load Banks shall be used to augment the facility load to achieve a load up to 75% of the generator nameplate kW rating for generator periodic testing.
C. The Load Bank shall be such that different load steps can be incrementally applied so that the generator can be exercised between 30% and 75% of the generator nameplate kW rating.
D. The load step resolution shall have the capacity to be set in 5 kW increments from 5kW to the generator nameplate kW rating for generators ranging from 200 kW to 400kW.
2.10 FINISHES
A. Indoor and Outdoor Enclosures and Components: Manufacturer's standard finish over corrosion-resistant pretreatment and compatible primer.
2.11 SOURCE QUALITY CONTROL
A. Prototype Testing: Factory test engine-generator set using same engine model, constructed of identical or equivalent components and equipped with identical or equivalent accessories.
1. Report factory test results within 10 days of completion of test.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Comply with packaged engine-generator manufacturers' written installation and alignment instructions and with NFPA 110.
B. Install packaged engine generator to provide access, without removing connections or accessories, for periodic maintenance.
C. Install packaged engine generator with elastomeric isolator pads having a minimum deflection of 1 inch (25 mm) on a minimum of 4-inch- (100-mm-) high concrete base. Secure sets to anchor bolts installed in concrete bases. Bond generator frame and tank with 2 AWG Cooper wire to a minimum of (2) 10’ long 5/8” diameter cooper clad ground rods at diagonal corners of the pad. Bond the steel of the pad to these ground rods as well as the enclosure. Refer to the grounding plan on Sheet E-10 for other bonding connections.
D. Install Schedule 40, black steel piping with welded joints and connect to engine muffler. Install thimble at wall. Piping shall be same diameter as muffler outlet. Flexible connectors and steel piping materials and installation requirements are specified in Section 232113 "Hydronic Piping."
1. Install condensate drain piping to muffler drain outlet full size of drain connection with a shutoff valve, stainless-steel flexible connector, and Schedule 40, black steel pipe with welded joints. Flexible connectors and piping materials and installation requirements are specified in Section 232113 "Hydronic Piping."
E. Electrical Wiring: Install electrical devices furnished by equipment manufacturers but not specified to be factory mounted. Install load bank so that it can be connected to the total load during any generator testing.
F. Piping installation requirements are specified in other Sections. Drawings indicate general arrangement of piping and specialties.
G. Connect fuel, cooling-system, and exhaust-system piping adjacent to packaged engine generator to allow service and maintenance.
H. Connect engine exhaust pipe to engine with flexible connector.
I. Connect fuel piping to engines with a gate valve and union and flexible connector.
3.2 FIELD QUALITY CONTROL
A. Perform tests and inspections and prepare test reports.
1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.
B. Tests and Inspections:
1. Perform tests recommended by manufacturer and each electrical test and visual and mechanical inspection. Certify compliance with test parameters.
2. NFPA 110 Acceptance Tests: Perform tests required by NFPA 110 that are additional to those specified here including, but not limited to, single-step full-load pickup test.
3. Battery Tests: Equalize charging of battery cells according to manufacturer's written instructions. Record individual cell voltages.
a. Measure charging voltage and voltages between available battery terminals for full-charging and float-charging conditions. Check electrolyte level and specific gravity under both conditions.
b. Test for contact integrity of all connectors. Perform an integrity load test and a capacity load test for the battery.
c. Verify acceptance of charge for each element of the battery after discharge.
d. Verify that measurements are within manufacturer's specifications.
4. Battery-Charger Tests: Verify specified rates of charge for both equalizing and float-charging conditions.
5. System Integrity Tests: Methodically verify proper installation, connection, and integrity of each element of engine-generator system before and during system operation. Check for air, exhaust, and fluid leaks.
C. Coordinate tests with tests for transfer switches and run them concurrently.
D. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.
E. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation.
F. Load Bank Test: After generator has passed mechanical test connect the load bank and use it to test the generator at 30%, 50%, and 75% or the generator nameplate kW rating.
G. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.
H. Retest: Correct deficiencies identified by tests and observations and retest until specified requirements are met.
I. Report results of tests and inspections in writing. Record adjustable relay settings and measured insulation resistances, time delays, and other values and observations. Attach a label or tag to each tested component indicating satisfactory completion of tests.
J. ETL 11-21 Change 2 Test 1: Test the generator to section 8.1.2 Method 2 for Monthly RPIE Generator Test using load banks only. Use AFCESA Form 487 to record this test. This is a one (1) hour on load test.
K. ETL 11-21 Change 2 Test 2: With approval of the 366 CES and 366 CS, preform 8.1.3 Semiannual RIPE Generator Test. Insure that all ATS and MTS are in the proper standard operating positions, remove utility power, and test generator under actual building load. Use AFCESA Form 487 to record this test. This is a two (2) hour on load test.
3.3 DEMONSTRATION
A. Engage a factory-authorized service representative to train USAF maintenance personnel to adjust, operate, and maintain packaged engine generators. Refer to Section 017900 "Demonstration and Training."
- END OF SECTION -
REPAIR / ADDITION TO FACILITY 610
ENGINE GENERATORS
QYZH 10 - 0076 A/B
PAGE 26 32 13 - 10
File details come from the government source that posted it. Updated .