C o n t r a c t D r a w i n g s F o r
31 JULY 2020
MODERNIZE HVAC AND
ELECTRICAL REDUNDANCY,
B848
CANNON AIR FORCE BASE
Curry County, New Mexico
Project No.: 1081400
Issued for Bid
B848
I N D E X O F D R A W I N G S
GENERAL
G001 COVER SHEET/INDEX OF DRAWINGS
G002 CONTRACTOR HAUL ROUTE AND STAGING AREA
G003 ABBREVIATIONS
G004 GENERAL LEGEND
G005 PHASING PLAN
ARCHITECTURAL
A101 ARCHITECTURAL PLAN 1ST FLOOR AREA "C"
A501 ARCHITECTURAL DETAILS AND SCHEDULES
A502 WALL TYPES AND DETAILS
STRUCTURAL
S001 GENERAL STRUCTURAL NOTES & TYPICAL DETAILS
MECHANICAL
M001 MECHANICAL LEGEND
XM101 MECHANICAL DEMO PLAN 1ST FLOOR AREA "C"
XM102 MECHANICAL PIPING DEMO PLAN 1ST FLOOR AREA "D"
M101 MECHANICAL PLAN 1ST FLOOR AREA "B"
M102 MECHANICAL PLAN 2ND FLOOR AREA "B"
M103 MECHANICAL PIPING PLAN 1ST FLOOR AREA "C"
M104 MECHANICAL PIPING PLAN 1ST FLOOR AREA "D"
M401 ENLARGED MECHANICAL PLAN 1ST FLOOR AREA "C"
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
M602 MECHANICAL CONTROLS
ELECTRICAL
E001 ELECTRICAL LEGEND
E002 ELECTRICAL LEGEND
E101 ELECTRICAL SITE PLAN
E102 ELECTRICAL PLAN 1ST FLOOR AREA "B"
E103 ELECTRICAL PLAN 1ST FLOOR AREA "C"
E104 ELECTRICAL PLAN 1ST FLOOR AREA "D"
E105 ELECTRICAL PLAN 2ND FLOOR AREA "B"
E401 ENLARGED ELECTRICAL PLAN 1ST FLOOR AREA "C"
E501 ELECTRICAL DETAILS
E601 EXISTING ONE LINE DIAGRAM
E602 EXISTING ONE LINE DIAGRAM
E603 EXISTING ONE LINE DIAGRAM
E611 PROPOSED ONE LINE DIAGRAM
E612 PROPOSED ONE LINE DIAGRAM
E613 PROPOSED ONE LINE DIAGRAM
E614 PROPOSED ONE LINE DIAGRAM
E615 PROPOSED ONE LINE DIAGRAM
E616 PROPOSED ONE LINE DIAGRAM
E617 ELECTRICAL SCHEDULE AND ELEVATIONS
E621 DATA CENTER - RACK CIRCUITING SCHEDULES
FIRE AND LIFE SAFETY
FA101 FIRE ALARM PLAN 1ST FLOOR AREA "B"
FA102 FIRE ALARM PLAN 1ST FLOOR AREA "C"
FA401 ENLARGED FIRE ALARM PLAN 1ST FLOOR AREA "C"
FP101 FIRE PROTECTION PLAN 1ST FLOOR AREA "B"
FP102 FIRE PROTECTION PLAN 1ST FLOOR AREA "C"
FP401 ENLARGED FIRE PROTECTION PLAN 1ST FLOOR AREA "C"
OP
27 SOW
SP
27th
IAL
EC
W
IN
G
ERATION
OF
SP
EC
IAL
O
PE
RA
TIO
NS
Mo de rni ze
H
VA
C an d E lec tric al
Re du nd an cy , B
JU
LY
G001
CO
VE
R
SH
EE
T
PROJECT LOCATION MAP
Property of the United States Government;
Copying, Dissemination, or Distribution of these drawings or specifications to any unathorized person is prohibited.
UNCLASSIFIED/FOR OFFICIAL USE ONLY
CONTRACTOR
ACCESS GATE
PROJECT
SITE
HAUL
ROUTE
BASE CIVIL
ENGINEERING
OP
27 SOW
SP
27th
IAL
EC W
IN
G
ERATION
OF
SP
EC
IAL
O
PE
RA
TIO
NS
Mo de rni ze
H
VA
C an d E lec tric al
Re du nd an cy , B
JU
LY
G002
CO
NT
RA
CT
OR
HA
UL
RO
UT
E A
ND
ST
AG
ING
AR
EA
BASE MAP
B848
CONTRACTOR
STAGING
AREA
HAUL
ROUTE
GENERAL NOTES:
1. CONTRACTOR STAGING AREA MUST BE FULLY ENCLOSED WITH
A MINIMUM 9 GAUGE CHAIN LINK FENCE 6 FEET HIGH.
2. STORAGE AREA HAS:
- WATER TIE-IN
- 480V 3 PH TRANSFORMER W/ DISCONNECT AND PAD.
CHILLER
STAGING
Property of the United States Government;
Copying, Dissemination, or Distribution of these drawings or specifications to any
1. THESE ABBREVIATIONS APPLY TO THE ENTIRE SET
OF CONTRACT DRAWINGS.
2. LISTING OF ABBREVIATIONS DOES NOT IMPLY THAT
ALL ABBREVIATIONS ARE USED IN THE CONTRACT
DRAWINGS.
3. ABBREVIATIONS SHOWN ON THIS SHEET INCLUDE
VARIATIONS OF A WORD. FOR EXAMPLE, "MOD"
MAY MEAN MODIFY OR MODIFICATION; "INC" MAY
MEAN INCLUDED OR INCLUDING AND "REINF" MAY
MEAN EITHER REINFORCE OR REINFORCING.
4. SEE MECHANICAL AND ELECTRICAL LEGEND SHEETS FOR
PROJECT-SPECIFIC EQUIPMENT SYMBOLS,
EQUIPMENT ABBREVIATIONS, AND PIPING SYSTEM
ABBREVIATIONS.
FLG
FLOR
FLR
FLS
FN
FO
FOB
FOC
FOF
FOM
FOS
FOT
FPT
FR
FRP
FRTM
FS
FT
FTG
FUR
FURN
FUT
FV
FW
FWD
FWE
FXTR
G
GA
GAL
GALV
GB
GC
GD
GEN
GFCI
GFMU
GG
GJ
GL
GLB
GND
GP
GR
GRTG
GSB
GT
GVL
GW
GWB
GYP
H
HB
HBD
HC
HD
HDR
HDW
HEX
HGR
HH
HID
HM
HORIZ
HP
HPC
HPS
HPT
HR
HS
HSS
HT
HTG
HV
HVAC
HWD
HWL
HYD
HZ
ID
IE
IF
IH
IMP
IN
INC
INF
INSTR
INSUL
INT
INTR
INV
IPS
IPT
IR
IRR
ISO
IW
JB
JCT
JF
JST
JT
K
KB
KCMIL
KD
KO
KSI
KW
L
LAD
LAM
LATL
LB
FLANGE
FLUORESCENT
FLOOR
FLASHING, FLUSH
FENCE
FINISHED OPENING, FIBER OPTIC
FLAT ON BOTTOM
FACE OF CONCRETE, FACE OF CURB
FACE OF FINISH
FACE OF MASONRY
FACE OF STUDS
FLAT ON TOP
FEMALE PIPE THREAD
FRAME
FIBERGLASS REINFORCED PLASTIC
FIRE RETARDANT TREATED MATERIAL
FLOOR SINK, FAR SIDE
FEET, FOOT
FOOTING, FITTING
FURRED, FURRING
FURNITURE, FURNISH
FUTURE
FACE VELOCITY
FIELD WELD, FIRE WALL
FORWARD
FURNISHED WITH EQUIPMENT
FIXTURE
GRILLE, GROUND
GAGE (METAL THICKNESS)
GALLON
GALVANIZED
GRAB BAR, GRADE BREAK
GROOVED COUPLING
GUARD
GENERAL
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FACE MASONRY UNIT
GUTTER GRADE
GROOVED JOINT
GLASS
GLASS BLOCK, GLULAM BEAM
GROUND
GUY POLE
GRADE
GRATING
GYPSUM SHEATHING BOARD
GREASE TRAP
GRAVEL
GUY WIRE
GYPSUM WALLBOARD
GYPSUM HARDBOARD
HIGH
HOSE BIBB
HARDBOARD
HANDICAPPED, HOLLOW CORE, HORIZONTAL
CURVE, HORIZONTAL CENTERLINE
HEAD, HOT DIP
HEADER
HARDWARE
HEXAGONAL
HANGER
HANDHOLE
HIGH-INTENSITY DISCHARGE
HOLLOW METAL
HORIZONTAL
HIGH POINT, HORSEPOWER
HORIZONTAL POINT OF CURVATURE
HIGH-PRESSURE SODIUM
HORIZONTAL POINT OF TANGENCY
HOSE REEL, HOUR
HEADED STUD, HIGH STRENGTH
HOLLOW STRUCTURAL SHAPE
HEIGHT
HEATING
HIGH VOLTAGE
HEATING, VENTILATING AND
AIR CONDITIONING
HARDWOOD
HIGH WATER LEVEL
HYDRAULIC
HERTZ, CYCLES PER SECOND
INSIDE DIAMETER, INTERIOR DIMENSION
INVERT ELEVATION, FOR EXAMPLE
INSIDE FACE
INTAKE HOOD
IMPACT
INCH
INCLUDE, INCANDESCENT
INFLUENT
INSTRUMENTATION
INSULATION
INTERIOR, INTERSECTION
INTERMEDIATE, INTERIOR
INVERT
IRON PIPE SIZE
INTERNAL PIPE THREAD
INSIDE RADIUS, IRON ROD
IRRIGATION
ISOMETRIC
INDUSTRIAL WASTE WATER
JUNCTION BOX
JUNCTION
JOINT FILLER
JOIST
JOINT
KIP
KNEE BRACE
THOUSAND CIRCULAR MILS
KNOCK DOWN
KNOCK OUT
KIPS PER SQUARE INCH
KILOWATT
ANGLE, LENGTH, LAVATORY, LINTEL
LADDER
LAMINATE
LATERAL
LAG BOLT, POUND
CONC
CONN
CONST
CONT
COOR
CORR
CP
CPLG
CRL
CSC
CSK
CSS
CT
CTJ
CTR
CTRL
CVT
CU
CW
CY
d
D
DB
DBA
DBL
DC
DEG
DEG F
DEMO
DEP
DEPT
DET
DGCO
DI
DIA
DIAG
DIFF
DIM
DISCH
DIST
DIV
DL
DMJ
DMPF
DN
DO
DP
DPDT
DPST
DS
DT
DUP
DWG
DWL
DWR
E
EA
EC
ECC
ED
EDB
EE
EF
EFF
EHH
EIFS
EJ
EL
ELEC
EMBD
EMER
EMH
ENCL
ENGR
ENTR
EOP
EQ
EQUIP
EQUIV
ES
ESEW
EST
EW
EWC
EWEF
EWTB
EXC
EXH
EXP
EXST
EXT
F TO F
F&B
FAB
FB
FBD
FBG
FBM
FBO
FC
FCA
FD
FDC
FDR
FDTN
FE
FEC
FES
FEXT
FF
FG
FH
FIG
FIN
FJT
FL
FLEX
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATE
CORROSIVE, CORRUGATED
CHECKER PLATE, CONTROL POINT
COUPLING
CORROSION-RESISTANT LINING
COMPRESSION SLEEVE COUPLING
COUNTERSINK
CLINIC SERVICE SINK
CERAMIC TILE
CONTRACTION JOINT
CENTER
CONTROL
CULVERT
COPPER, CUBIC
CLOCKWISE
CUBIC YARD
PENNY (NAIL MEASURE)
DEEP, DIFFUSER, DRAIN
DUCT BANK, DECIBEL, DRY BULB
DEFORMED BAR ANCHOR
DOUBLE
DIRECT CURRENT
DEGREE
DEGREE FAHRENHEIT
DEMOLITION
DEPRESSED
DEPARTMENT
DETAIL
DOUBLE GRADE CLEAN OUT
DROP INLET, DUCTILE IRON, DIGITAL INPUT
DIAMETER
DIAGONAL, DIAGRAM
DIFFERENTIAL, DIFFERENCE
DIMENSION
DISCHARGE
DISTANCE, DISTRIBUTION
DIVISION
DEAD LOAD
DOUBLE MECHANICAL JOINT
DAMP PROOFING
DOWN
DISSOLVED OXYGEN, DIGITAL OUTPUT, DITTO
DEPTH
DOUBLE POLE, DOUBLE THROW
DOUBLE POLE, SINGLE THROW
DOWN SPOUT
DOUBLE TEE, DRIP TRAP ASSEMBLY
DUPLICATE
DRAWING
DOWEL
DRAWER
EAST
EACH, EXHAUST AIR
ELECTRICAL CONTRACTOR
ECCENTRIC
EQUIPMENT DRAIN
ELECTRICAL DUCT BANK
EACH END
EACH FACE
EFFLUENT, EFFICIENCY
ELECTRICAL HANDHOLE
EXTERIOR INSULATION &
FINISH SYSTEM
EXPANSION JOINT
ELBOW, ELEVATION
ELECTRICAL
EMBEDDED
EMERGENCY
ELECTRICAL MANHOLE
ENCLOSURE
ENGINEER
ENTRANCE
EDGE OF PAVEMENT
EQUAL
EQUIPMENT
EQUIVALENT
EACH SIDE, EQUAL SPACE,
EMERGENCY SHOWER
EMERGENCY SHOWER AND EYE WASH
ESTIMATE
EACH WAY, EMERGENCY
EYE/FACE WASH
ELECTRIC WATER COOLER
EACH WAY, EACH FACE
EACH WAY, TOP AND BOTTOM
EXCAVATION
EXHAUST
EXPANSION, EXPOSED
EXISTING
EXTERIOR, EXTERNAL, EXTENSION
FACE TO FACE
FACE AND BYPASS
FABRICATE
FLOOR BEAM
FIBERBOARD
FIBERGLASS
BOARD FOOT MEASURE
FURNISHED BY OWNER
FLUSHING CONNECTION
FLANGED COUPLING ADAPTER
FLOOR DRAIN
FLEXIBLE DUCT CONNECTION
FEEDER
FOUNDATION
FLANGED END
FIRE EXTINGUISHER CABINET
FLARED END SECTION
FIRE EXTINGUISHER
FAR FACE, FACTORY FINISH, FLAT FACE
FINISHED GRADE
FIRE HYDRANT
FIGURE
FINISH
FLUSH JOINT
FLOW, FLOW LINE
FLEXIBLE
A/C
A/E
A
AB
ABAN
ABC
ABT
AC
ACK
ACP
ACST
AD
ADDL
ADH
ADJ
AF
AFF
AFG
AGGR
AI
AIC
ALIG
ALT
ALUM
AM
AMB
ANC
AO
AP
APRX
APVD
ARCH
ASSY
AT
ATC
ATM
AUTO
AUX
AVE
AVG
AWG
AWT
B TO B
BAL
BBD
BC
BD
BE
BF
BITUM
BKG
BL
BLDG
BLK
BLKG
BM
BOC
BOD
BOG
BOL
BOP
BOR
BOT
BOU
BP
BRG
BRGP
BRKT
BS
BTU
BTW
BTWLD
BU
BUR
BW
BYP
C TO C
C&G
C
CAB
CAP
CAT
CAV
CB
CCB
CCW
CDF
CE
CER
CF
CFL
CHBD
CHD
CHFR
CHH
CI
CIP
CIPB
CIRC
CJ
CKT
CL
CLG
CLKG
CLR
CMH
CMP
CMU
CO
COL
COM
COMB
COMM
COMP
CON
AIR CONDITIONING
ARCHITECT/ENGINEER
AMPERE
ANCHOR BOLT
ABANDON
AGGREGATE BASE COURSE
ABOUT
ALTERNATING CURRENT
ACKNOWLEDGE
ACOUSTIC CEILING PANEL,
ASPHALTIC CONCRETE PAVEMENT
ACOUSTIC
ADDENDUM, AREA DRAIN
ADDITIONAL
ADHESIVE
ADJUSTABLE, ADJACENT
AMP FRAME, AMP FUSE
ABOVE FINISH FLOOR
ABOVE FINISH GRADE
AGGREGATE
AREA INLET, ANALOG INPUT
AMPS INTERRUPTING CAPACITY
ALIGNMENT
ALTERNATE, ALTITUDE
ALUMINUM
ACOUSTICAL MATERIAL
AMBIENT
ANCHOR
ANALOG OUTPUT
ACCESS PANEL
APPROXIMATE
APPROVED
ARCHITECTURAL
ASSEMBLY
ACOUSTICAL TILE, AMP TRIP
ACOUSTICAL TILE CEILING
ATMOSPHERE
AUTOMATIC
AUXILIARY
AVENUE
AVERAGE
AMERICAN WIRE GAGE
ACOUSTICAL WALL TILE
BACK TO BACK
BALANCE
BULLETIN BOARD
BASE CABINET, BOTTOM CHORD,
BOLT CENTER, BOLT CIRCLE
BOARD
BOTH ENDS, BELL END
BOTH FACES, BOTTOM FACE,
BLIND FLANGE, BOARD FEET
BITUMINOUS
BACKING
BASE LINE
BUILDING
BLOCK
BLOCKING
BENCHMARK, BEAM
BACK OF CURB
BOTTOM OF DUCT
BOTTOM OF GRILLE
BOTTOM OF LOUVER, BOLLARD
BOTTOM OF PIPE
BOTTOM OF REGISTER
BOTTOM
BOTTOM OF UNIT
BASE PLATE
BEARING
BEARING PLATE
BRACKET
BOTH SIDES
BRITISH THERMAL UNIT
BETWEEN
BUTT WELD
BELL UP, BUILT-UP
BUILT-UP ROOFING
BOTH WAYS
BYPASS
CENTER TO CENTER
CURB AND GUTTER
CHANNEL SHAPE, CENTIGRADE,
CONDUIT
CABINET
CAPACITY
CATALOG, CATALOGIORY
CAVITY
CATCH BASIN
CONCRETE BLOCK
COUNTER CLOCKWISE
CONTROLLED-DENSITY FILL
CONCRETE EDGE
CERAMIC
CUBIC FEET (FOOT)
COUNTER FLASHING
CHALKBOARD
CHORD
CHAMFER
COMMUNICATION HANDHOLE
CURB INLET
CAST-IN-PLACE
CONCRETE INTERLOCKING PAVER
BALLAST
CIRCULATION, CIRCULAR
CONSTRUCTION JOINT
CIRCUIT
CENTERLINE, CLASS, CLOSE
CEILING
CAULKING
CLEAR
COMMUNICATION MANHOLE
CORRUGATED METAL PIPE
CONCRETE MASONRY UNIT
CLEANOUT, CONCRETE OPENING
COLUMN
COMMON
COMBINATION
COMMUNICATION
COMPOSITION, COMPRESSIBLE,
COMPOSITE
CONCENTRIC
GENERAL NOTES:
LCTB
LDG
LDR
LE
LF
LG
LH
LIN
LIQ
LLH
LLV
LMLU
LNG
LOC
LP
LPS
LR
LT
LTD
LTG
LTL
LTNG
LV
LVL
LVR
LW
LWC
LWL
MA
MACH
MAINT
MAN
MATL
MAX
MB
MBR
MC
MCB
MCJ
MDMJ
MECH
MED
MFR
MH
MIN
MIR
MISC
MJ
ML
MLO
MMB
MO
MOD
MON
MPT
MRGWB
MS
MSL
MT
MU
MULL
MV
MW
N
NA
NAT
NC
NEG
NF
NIC
NMED
NO
NOM
NPS
NPT
NPW
NS
NTS
NWL
O TO O
OA
OC
OCPD
OD
OED
OF
OFCI
OFOI
OG
OH
OPNG
OPP
OPT
OR
ORD
ORIG
OSE
OVFL
OVHG
OZ
P
PA
PAR
PB
PBD
PC
PCC
PCF
PCT
PE
PED
PEN
PERF
PERM
PERP
LIQUID CHALK AND TACK BOARD
LANDING
LEADER
LIFTING EYE
LINEAR FOOT
LONG
LEFT HAND
LINEAR
LIQUID
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LIQUID MARKER LECTURE UNIT
LONGITUDINAL
LOCATION
LOW POINT
LOW-PRESSURE SODIUM
LONG RADIUS
LEFT
LIMITED
LIGHTING
LINTEL
LIGHTNING
LOW VOLTAGE
LAMINATED VENEER LUMBER
LOUVER
LIGHTWEIGHT
LIGHTWEIGHT CONCRETE
LOW WATER LEVEL
MIXED AIR
MACHINED
MAINTENANCE
MANUAL
MATERIAL
MAXIMUM
MACHINE BOLT
MEMBER
MECHANICAL CONTRACTOR,
MECHANICAL COUPLING,
MOMENT CONNECTION
METAL CORNER BEAD
MASONRY CONTROL JOINT
MODIFIED DOUBLE MECHANICAL JOINT
MECHANICAL
MEDIUM
MANUFACTURER
MANHOLE, METAL HALIDE
MINIMUM
MIRROR
MISCELLANEOUS
MECHANICAL JOINT
MASONRY LINTEL
MAIN LUGS ONLY
MEMBRANE
MASONRY OPENING
MODULAR, MODIFY
MONUMENT
MALE PIPE THREAD
MOISTURE-RESISTANT
GYPSUM WALLBOARD
MOP SINK
MEAN SEA LEVEL
MOUNT
MASONRY UNIT
MULLION
MEDIUM VOLTAGE
MONITORING WELL
NORTH, NEUTRAL
NOT APPLICABLE
NATURAL, NATIONAL
NORMALLY CLOSED
NEGATIVE
NEAR FACE, NON-FUSED
NOT IN CONTRACT
NEW MEXICO ENVIRONMENT DEPARTMENT
NORMALLY OPEN, NUMBER
NOMINAL
NOMINAL PIPE SIZE
NATIONAL PIPE THREAD
NON-POTABLE WATER
NEAR SIDE
NOT TO SCALE
NORMAL WATER LEVEL
OUT TO OUT
OUTSIDE AIR, OVERALL
ON CENTER
OVER CURRENT PROTECTION DEVICE
OUTSIDE DIAMETER
OPEN END DUCT
OUTSIDE FACE, OFFICE FURNISHING
OWNER FURNISHED CONTRACTOR
INSTALLED
OWNER FURNISHED OWNER INSTALLED
ORIGINAL GROUND
OVERHEAD
OPENING
OPPOSITE
OPTIONAL
OUTSIDE RADIUS
OVERFLOW ROOF DRAIN
ORIGINAL
OFFICE OF THE STATE ENGINEER
OVERFLOW
OVERHANG
OUNCE
PAINT
PUBLIC ADDRESS
PARALLEL, PARAPET
PANIC BAR, PULL BOX
PARTICLE BOARD
POINT OF CURVE, PIECE, PRECAST
POINT OF COMPOUND CURVATURE
POUNDS PER CUBIC FOOT
PERCENT
PLAIN END
PEDESTAL
PENETRATION
PERFORATED
PERMANENT
PERPENDICULAR
POWER FACTOR
PREFACED MASONRY UNIT
PHASE
POINT OF INTERSECTION
PACKAGE
PLATE, PROPERTY LINE,
PRECAST LINTEL
PLASTER
PLATFORM
PLUMBING
POUNDS PER LINEAR FOOT
PNEUMATIC
POLISH
POSITIVE, POSITION
POLYPROPYLENE, POWER POLE
POINT OF REVERSE CURVATURE
PREFINISHED
PREFABRICATED
PRELIMINARY
PREPARE
PRESSURE
PRIMARY
PROPERTY, PROPOSED
PROTECTION
PIPE SUPPORT
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH ABSOLUTE
POUNDS PER SQUARE INCH GAGE
PRESTRESSED
POINT, POINT OF TANGENCY
PARTITION
POLYVINYL CHLORIDE, POINT OF
VERTICAL CURVE
PAVEMENT
PLYWOOD
PLYWOOD WEB JOIST
PIEZOMETER
RATE OF FLOW
QUARRY TILE
QUARTER
QUANTITY
QUALITY
REMOVE AND REPLACE
REMOVE AND SALVAGE
RADIUS, REGISTER, RISER
RETURN AIR
RESILIENT BASE, ROCK BERM
RECEPTACLE
ROOF DRAIN
RECESS
RECEIVED
RECTANGULAR
REDUCER
REFERENCE
REINFORCING
REMOVE
REQUIRED
RESILIENT
RETAINING, RETURN
REVISION, REVERSE
RESILIENT FLOORING
ROOFING
REFLECTED, REFLECTOR
ROUGH
RIGID GALVANIZED STEEL
PVC COATED RGS
RELIEF HOOD, RIGHT HAND,
RELATIVE HUMIDITY
REQUIRED LAP
RELIEF AIR
ROUND
RUNNING
ROUGH OPENING
RIGHT-OF-WAY
REVOLUTIONS PER MINUTE
RAILROAD
ROCK SLOPE PROTECTION
RIGHT
RESILIENT VINYL TILE
READY
SOUTH, SINK
SUPPLY AIR
SOUND-ABSORBING MASONRY UNIT
SANITARY
SPLASH BLOCK
SOLID CORE
SCHEDULE
SCHEMATIC
SCREEN
STEEL/ALUMINUM EDGE
SECONDARY, SECONDS
SECTION
SEPARATE
SQUARE FOOT, SILT FENCE
SHEET GLASS, SEALANT GROOVE
SHOWER
SHEET
SHEATHING
SILENCE
SIMILAR
SLAB JOINT
SLOPE, STEEL LINTEL
SLOTTED
SLEEVE
SEAMLESS
SLAB ON GRADE
SOUNDPROOF, STANDPIPE
SPACING
SPECIFICATION
SUPPLY
SINGLE POLE SINGLE THROW
SET POINT
SQUARE
SHORT RADIUS
SERVICE SINK
STAINLESS STEEL
STREET
STATION
STANDARD
STIFFENER
PF
PFMU
PH
PI
PKG
PL
PLAS
PLAT
PLBG
PLF
PNEU
POL
POS
PP
PRC
PREF
PREFAB
PRELIM
PREP
PRES
PRI
PROP
PROT
PS
PSF
PSI
PSIA
PSIG
PST
PT
PTN
PVC
PVMT
PWD
PWJ
PZ
Q
QT
QTR
QTY
QUAL
R&R
R&S
R
RA
RB
RCPT
RD
REC
RECD
RECT
RED
REF
REINF
REM
REQD
RESIL
RET
REV
RF
RFG
RFL
RGH
RGS
RGS-PVC
RH
RL
RLFA
RND
RNG
RO
ROW
RPM
RR
RSP
RT
RVT
RY
S
SA
SAMU
SAN
SB
SC
SCH
SCHEM
SCN
SE
SEC
SECT
SEP
SF
SG
SH
SHT
SHTG
SIL
SIM
SJ
SL
SLTD
SLV
SMLS
SOG
SP
SPA
SPEC
SPLY
SPST
SPT
SQ
SR
SS
SST
ST
STA
STD
STIF
STIRRUP
STEEL
STORAGE
STRUCTURAL, STRAIGHT
SUBSTITUTE
SUCTION
SUSPENDED
SQUARE YARD
SYMBOL
SYMMETRICAL
SYNTHETIC
SYSTEM
TOP AND BOTTOM
TONGUE AND GROOVE
TILE, TREAD
TOILET ACCESSORY, TEMPERED AIR
TANGENT
TEMPORARY BENCHMARK
TEMPORARY CONSTRUCTION EASEMENT
TROWELED EPOXY FLOORING
TEMPORARY, TEMPERATURE
THREAD
THICK
THRESHOLD
TACK BOARD
TOP OF BOLT, TOP OF BANK,
TOP OF BEAM, TOP OF BERM
TOP OF CURB, TOP OF CONCRETE
TOP OF DUCT
TOP OF FOOTING
TOP OF GRATING
TOLERANCE, TOP OF LEDGER
TOP OF MASONRY
TOP OF PLATE
TOPOGRAPHY
TOP OF SLAB, TOP OF STEEL,
TOE OF SLOPE
TOP OF WALL
TOILET PARTITION, TELEPHONE POLE,
TOE PLATE, TRAP PRIMER
TOILET PAPER DISPENSER
TOPPING, THROUGH PLATE GIRDER
TRANSOM
TRANSITION
TRENCH DRAIN
TYPICAL
URINAL
UNDERGROUND
ULTIMATE
UNFINISHED
UNLESS NOTED OTHERWISE
UTILITY
VENT, VELOCITY, VOLT
VOLT AMPERE
VACUUM
VARNISH, VARIABLE,
VOLT AMPERES REACTIVE
VAPOR BARRIER, VINYL BASE,
VALVE BOX
VERTICAL CURVE
VITRIFIED CLAY PIPE
VINYL COMPOSITION TILE,
VERTICAL CENTERLINE
VELOCITY
VENTILATION
VERTICAL
VERTICAL REINFORCING
VERTICAL GRAIN
VERIFY IN FIELD
VINYL
VOLUME
VERTICAL POINT OF CURVATURE
VERTICAL POINT OF INTERSECTION
VERTICAL POINT OF TANGENCY
VERSUS, VAPOR SEAL
VENT THROUGH ROOF
VINYL WALL COVERING
WITH
WITHOUT
WATT, WEST, WIDE, WINDOW, WIRE,
WIDE FLANGE BEAM
WOOD BASE
WATER CLOSET, WATER COLUMN
WOOD, WIDTH
WIDE FLANGE, WASH FOUNTAIN
WIRE GLASS, WATER GAGE
WALL HYDRANT, WEEP HOLE
WROUGHT IRON
WATER LEVEL
WELDED
WIRE MESH
WEATHERPROOF
WATERSTOP, WATER SURFACE
WAINSCOT
WEIGHT, WATER TIGHT
WATERPROOF, WORKING POINT
WELDED WIRE FABRIC
EXPLOSION-PROOF
EXTRA STRONG
CROSS SECTION
DOUBLE EXTRA STRONG
YARD HYDRANT
YIELD STRENGTH
STIR
STL
STOR
STR
SUB
SUC
SUSP
SY
SYM
SYMM
SYN
SYS
T&B
T&G
T
TA
TAN
TBM
TCE
TEF
TEMP
THD
THK
THRESH
TKBD
TOB
TOC
TOD
TOF
TOG
TOL
TOM
TOP
TOPO
TOS
TOW
TP
TPD
TPG
TR
TRANS
TRD
TYP
U
UG
ULT
UNFN
UNO
UTIL
V
VA
VAC
VAR
VB
VC
VCP
VCT
VEL
VENT
VERT
VERTS
VG
VIF
VIN
VOL
VPC
VPI
VPT
VS
VTR
VWC
W/
W/O
W
WB
WC
WD
WF
WG
WH
WI
WL
WLD
WM
WP
WS
WSCT
WT
WTHP
WWF
XP
XS
XSECT
XXS
YH
YS
OP
27 SOW
SP
27th
IAL
EC
W
IN
G
ERATION
OF
SP
EC
IAL
O
PE
RA
TIO
NS
Mo de rni ze
H
VA
C an d E lec tric al
Re du nd an cy , B
JU
LY
G003
AB
BR
EV
IAT
IO
NS
Property of the United States Government; Copying, Dissemination, or Distribution of these drawings or specifications to any unathorized person is prohibited. UNCLASSIFIED/
FOR OFFICIAL USE ONLY
OP
27 SOW
SP
27th
IAL
EC W
IN
G
ERATION
OF
SP
EC
IAL
O
PE
RA
TIO
NS
Mo de rni ze
H
VA
C an d E lec tric al
Re du nd an cy , B
JU
LY
G004
GE
NE
RA
L L
EG
EN
D
EQUIPMENT
NUMBER
1. THIS IS A STANDARD SHEET SHOWING COMMON
SYMBOLOGY. ALL SYMBOLS ARE NOT NECESSARILY
USED ON THIS PROJECT.
2. SCREENING OR SHADING OF WORK IS USED TO
INDICATE EXISTING COMPONENTS OR TO
DE-EMPHASIZE PROPOSED IMPROVEMENTS TO
HIGHLIGHT SELECTED TRADE WORK. REFER TO
CONTEXT OF EACH SHEET FOR USAGE.
EQUIPMENT IDENTIFICATION
PUMP 23
INDICATES PUMP
EXAMPLEFIGURE
TARGET ELEVATION
ARCHITECTURAL
PIPING
KEY NOTE NUMBER
KEY NOTE DESIGNATION
LOUVER
WINDOW TYPE
WALL TYPE
COLUMN GRID LINE
ROOM NUMBER
DOOR NUMBER
36"LINE SIZE
PLANT EFFLUENTSERVICE
EXAMPLE
36"-PLE
FIGURE
GENERAL NOTES:
NPWP-23
XXX
X
X
X
X
X
ACCESSORY, FURNITURE,
AND MISCELLANEOUS
EQUIPMENT IDENTIFIER
PLAN TITLE
GENERAL LINE SYMBOLOGY
COLUMN GRID LINE/CENTERLINE
INDICATES
NON-POTABLE WATER
SERVICE
ABBREVIATION
EQUIPMENT
ABBREVIATION
IDENTIFICATION SYMBOLOGYGENERAL SYMBOLOGY SHEET NAMING CONVENTION
ARCHITECTURAL SECTION, SHEET 01
SHEET TYPE DESIGNATOR
SHEET NUMBER
DISCIPLINE DESIGNATOR
DRAWING TYPE DESIGNATOR
GENERAL (SYMBOLS, LEGENDS)
PLANS
ELEVATIONS
SECTIONS
LARGE SCALE VIEWS
DETAILS
SCHEDULES AND DIAGRAMS
PROFILES
3D REPRESENTATIONS
GENERAL
SURVEYING/MAPPING
DEMOLITION
CIVIL
MULTI-DISCIPLINE
STRUCTURAL
ARCHITECTURAL
MECHANICAL (HVAC)
PLUMBING
ELECTRICAL
FIRE ALARM
FIRE PROTECTION
DISCIPLINE DESIGNATOR & DISCIPLINE ORDER
G
V
X
C
U
S
A
M
P
E
FA
FP
EXAMPLE
0 1
A
SHEET WHERE DETAIL
IS LOCATED *
DETAIL NUMBER
SHEET WHERE SECTION
VIEW IS FIRST CUT *
SECTION LETTER
SHEET WHERE SECTION
IS LOCATED
SECTION LETTER
FLAG INDICATES DIRECTION
OF SECTION CUT
ELEVATION NUMBER
ARROW INDICATES
POINT OF VIEW
SECTION CUT MARKER
DETAIL MARKER
SHEET WHERE ELEVATION
IS LOCATED *
ARROW INDICATES POINT OF
VIEW ELEVATION
ELEVATION NUMBER
SINGLE ELEVATION OR PHOTO MARKER
MULTIPLE ELEVATION OR PHOTO MARKER
INDICATES SHEET WHERE
ELEVATION IS LOCATED
FOR REFERENCING DETAILS BOUND IN
SPECIFICATIONS OR SEPARATE VOLUME.
DETAIL MARKER
ELEVATION IDENTIFICATION
NUMBER
SHEET WHERE POINT OF VIEW
MARKER CAN BE FOUND *
SECTION TITLE
* EXCEPTIONS WHERE THE SHEET NUMBER IS REPLACED BY A DASH (-).
1) FOR COMMON DETAILS, SECTIONS, ELEVATIONS OR DETAILS THAT
ARE CUT OR CALLED OUT ON MULTIPLE SHEETS.
2) SECTIONS, ELEVATIONS OR DETAILS THAT ARE LOCATED ON THE
SAME SHEET THEY ARE CUT OR CALLED OUT ON.
ELEVATION TITLE
FOR REFERENCING DETAILS INCLUDED IN DRAWING SET.
DETAIL TITLE
X
XX
X
PLAN
1/4" = 1'-0"
X
XXX
X
XXX
SECTION
3/8" = 1'-0"
XXX
XXXXXX
X
XXX
DETAIL
1/4" = 1'-0"
SHEET WHERE DETAIL
IS LOCATED *
DETAIL NUMBER
X
XXX
X
XXX
X
XXX
ELEVATION
3" = 1'-0"
X
XXX
INTERIOR EXTERIOR
ROOM
NAME
XX-XX
A
SHEET WHERE
SECTION IS LOCATED
SECTION LETTER
FULL BUILDING SECTION CUT MARKER
X
XXX
X
XXX
ARROW INDICATES
DIRECTION OF SECTION
CUT
ARCHITECTURAL
DISCIPLINE
SECTION SHEET TYPE
SHEET NUMBER 01
SAMPLE SHEET NUMBER
0 1 A 3
ARROW INDICATES
DIRECTION OF
PLAN NORTH
NORTH ARROW
MATCHLINE
Property of the United States Government;
Copying, Dissemination, or Distribution of these drawings or specifications to any
C O
P
PHASE 2
PHASE 4
P H
A S
E
PHASE 1
SECURE SPACE
BOUDARY
PHASE 3
P H
A S
E
OP
27 SOW
SP
27th
IAL
EC W
IN
G
ERATION
OF
SP
EC
IAL
O
PE
RA
TIO
NS
Mo de rni ze
H
VA
C an d E lec tric al
Re du nd an cy , B
JU
LY
A
B
C
D
KEY PLAN
PHASING PLAN 1ST FLOOR
1/16" = 1'-0"
PHASING NOTES:
1. THIS PLAN SHOWS THE PROPOSED PROJECT PHASING PLAN. THE
PROJECT PHASING SHALL MEET ALL THE FOLLOWING
REQUIREMENTS
2. SEE SPECIFICATION SECTION 01 11 00 FOR ADDITIONAL
REQUIREMENTS AND NOTIONAL PROJECT SCHEDULE.
3. WORK INSIDE THE SECURE SPACE WILL REQUIRE A GOVERNMENT
ESCORT AT ALL TIMES.
4. NO MORE THAN 3 FIXED FACILITY ROOMS (GCS BAYS) CAN BE
REMOVED FROM SERVICE AT ANY ONE TIME.
5. THE FIXED FACILITY ROOMS WITHIN EACH PHASE MUST BE FULLY
COMMISSIONED AND PLACED INTO OPERATION PRIOR TO WORK
BEING INITIATED IN THE FOLLOWING PHASE.
6. WORK IN CORRIDORS TO BE GENERALLY COORDINATED WITH
ADJACENT PHASING. IF WORK IN ANOTHER CORRIDOR IS REQUIRED
IT SHALL BE COORDINATED WITH THE GOVERNMENT CONTRACTING
OFFICER.
7. PHASING SHALL LIMIT THE NUMBER OF MECHANICAL AND
ELECTRICAL OUTAGES TO THE MINIMAL AMOUNT POSSIBLE. ALL
OUTAGES SHALL BE COORDINATED WITH THE CONTRACTING
OFFICER.
8. CONTRACTOR TO PROVIDE PHASING SIMILAR TO WHAT IS SHOWN.
SEE SPECIFICATIONS FOR NOTIONAL CONSTRUCTION SCHEDULE
AND MINIMAL REQUIREMENTS FOR OPERATIONS.
9. PHASE 1 ELECTRICAL WORK SHALL BE COMPLETE BEFORE START OF
PHASE 2 WORK.
A. THE USE OF GENERATORS TO MAINTAIN FACILITY OPERATION IS
ACCEPTABLE FOR SHORT DURATIONS AFTER APPROVAL BY
CONTRACTING OFFICER. FUEL WILL BE PROVIDED BY THE
GOVERNMENT.
B. PLACING UPS IN MAINTENANCE OR UTILITY BYPASS IS
ACCEPTABLE FOR SHORT DURATIONS AFTER APPROVAL BY
CONTRACTING OFFICER.
C. CRITICAL LOADS SHALL BE POWERED THROUGH A MINIMUM OF
ONE UPS THROUGHOUT THE DURATION OF THE CONSTRUCTION
PERIOD, EXCEPT AS APPROVED BY THE CONTRACTING OFFICER
FOR WORK ON UPS EQUIPMENT.
D. FUNCTIONAL TESTING REQUIREMENTS PER SECTION 26 08 00 TO
BE SCHEDULED AT THE END OF ALL PHASED WORK.
KEY NOTES:
1. WORK IN THE SERVER ROOM 130 CAN OCCUR OUTSIDE OF THE
PROPOSED PHASING PLAN. WORK IN THIS AREA COULD
SIGNIFICANTLY DISRUPT FACILITY OPERATIONS, WORK TO BE
COORDINATED WITH THE CONTRACTING OFFICER TO MINIMIZE
FACILITY DISRUPTIONS.
2. WORK IN THIS AREA CAN OCCUR OUTSIDE OF THE PROPOSED
PHASING PLAN. WORK TO BE COORDINATED WITH THE CONTRACTING
OFFICER.
G005
PH
AS
IN
G
PL
AN
Property of the United States Government;
Copying, Dissemination, or Distribution of these drawings or specifications to any
B
M O
44 44
44 44
A
M
I N
3'-4"
3A
3 2F443
3J3J3J3J3J
44 32F 3
3J3J3J 3J 3J 3J
3A
3A
3B
3B
3B
3A
3E
3E
3E
3B
A101
AR
CH
ITE
CT
UR
AL
PL
AN
1S T F
LO
OR
AR
EA
"C
OP
27 SOW
SP
27th
IAL
EC W
IN
G
ERATION
OF
SP
EC
IAL
O
PE
RA
TIO
NS
Mo de rni ze
H
VA
C an d E lec tric al
Re du nd an cy , B
JU
LY
A
B
C
D
KEY PLAN
KEY NOTES:
1. REMOVE EXISTING EXTERIOR WALL AS REQUIRED FOR NEW DOOR AND
FRAME. REFER TO DETAILS ON SHEET A501. PAINT EXTERIOR WALL TO
MATCH EXISTING EXTERIOR FINISHES.
2. REMOVE EXISTING 12" HIGH RAISED FLOOR SYSTEM WITH CARPET TILE IN
ITS ENTIRETY AND TURN OVER TO THE GOVERNMENT PER DIRECTION OF
THE CONTRACTING OFFICER. REMOVE ALL WALL BASE IN ROOM 132 IN ITS
ENTIRETY AND DISCARD. REPAIR ANY DAMAGE OF WALL TO MATCH
EXISTING WALL SURFACES. PROVIDE A COMPLETE NEW RAISED FLOOR
SYSTEM IN ROOM.AND NEW VINYL WALL BASE.
3. REMOVE EXISTING SLIDING DOOR IN ITS ENTIRETY, TURN OVER TO
GOVERNMENT, AND PROVIDE A NEW WALL INFILL WITH CONSTRUCTION TO
MATCH THE EXISTING ADJACENT WALL CONSTRUCTION. SEE ROOM FINISH
SCHEDULE FOR EXTENTS OF PAINTING OF WALL.
4. REMOVE PORTIONS OF EXISTING ACOUSTICAL GRID CEILINGS AND 12"
HIGH RAISED FLOOR SYSTEM AS REQUIRED FOR DEMOLITION AND
COORDINATION OF NEW WORK.. SALVAGE EXISTING AND RE-INSTALL.
5. REMOVE PORTIONS OF EXISTING ACOUSTICAL GRID CEILINGS AND 4" HIGH
RAISED FLOOR SYSTEM WITH CARPET TILE IN CORRIDORS AS REQUIRED
FOR DEMOLITION AND COORDINATION OF NEW WORK. SALVAGE EXISTING
AND RE-INSTALL.
X
GENERAL NOTES:
1. REFER TO SHEET A501 FOR ROOM FINISH AND DOOR
SCHEDULES.
2. REFER TO SHEET A502 FOR WALL TYPES.
3. CONTRACTOR SHALL DEVELOP A DEMOLITION AND
CONSTRUCTION PHASING PLAN TO BE APPROVED BY THE
CONTRACTING OFFICER PRIOR TO ANY WORK SCHEDULED.
REFER TO SHEET G005.
6. CONTRACTOR SHALL INSTALL A SECURE, TEMPORARY ENCLOSURE
DURING DEMOLITION OF THE SECURE EXTERIOR WALL AND INSTALLATION
OF THE NEW DOOR AND FRAME. REFER TO WALL TYPE-T ON SHEET A502
FOR WALL CONSTRUCTION.
7. PROVIDE A NEW DOOR FRAME ONLY IN EXISTING WALL. PATCH AND
REPAIR WALL TO MATCH EXISTING SURFACES.
8. REMOVE EXISTING CEILING IN ITS ENTIRETY. REPAIR WALL THAT HAS BEEN
DAMAGED DURING DEMOLITION TO MATCH EXISTING SURFACES. PAINT
ALL WALLS IN THIS ROOM FROM FINISH FLOOR TO STRUCTURE. AVERAGE
HEIGHT OF THE NORTH AND SOUTH WALLS ARE 19'-0" AFF.
9. ADD 1-LAYER OF 5/8" TYPE-X GWB TO THIS ENTIRE WALL TO MAKE THIS
WALL PART OF THE SECURE SPACE BOUNDARY. WALL IS ALSO MODIFIED
TO BE 1-HOUR RATED. FIRE RATE ANY PENETRATIONS IN THESE WALLS.
FINISH ENTIRE WALL FROM TRUE FLOOR TO ROOF DECK.
10. REPAIR OPENINGS IN WALL TO MATCH ADJACENT SURFACES AND PAINT
ENTIRE WALL FROM FINISH FLOOR TO STRUCTURE..
11. REMOVE PORTION OF EXISTING GYPSUM BOARD CEILING FOR
COORDINATION WITH NEW MECHANICAL WORK. PATCH AND RE-PAINT
CEILING AND WALLS AS REQUIRED.
Property of the United States Government;
Copying, Dissemination, or Distribution of these drawings or specifications to any
EXTERIOR HM DOOR JAMB
@ STUCCO WALL DETAIL
1 1/2"=1'-0"
GROUT SOLID FROM
FLOOR TO LINTEL
BEARING
S E
E
P L
A N
S
HM DOOR FRAME AND
DOOR
BACKER ROD AND
SEALANT EACH SIDE
NEW CONCRETE
MASONRY JAMB
5/8" GWB ON AIR
BARRIER
00A501
3-COAT STUCCO ON 2"
RIGID BD INSULATION
(MATCH EXIST COLOR
AND FINISH)
EXTERIOR HM DOOR JAMB
@ CMU WALL DETAIL
1 1/2"=1'-0"
GROUT SOLID FROM
FLOOR TO LINTEL
BEARING
S E
E
P L
A N
S
HM DOOR FRAME AND
DOOR
BACKER ROD AND
SEALANT EACH SIDE
NEW CONCRETE
MASONRY JAMB
AS REQUIRED
5/8" GWB ON AIR
BARRIER
2" METAL STUD FRAMING
W/ HIGH DENSITY SPRAY
FOAM INSULATION
2" RIGID BD INSULATION
SPLIT-FACE CMU
VENEER WAINSCOT
2" METAL STUD FRAMING
W/ HIGH DENSITY SPRAY
FOAM INSULATION
00A501
SEE
PLANS
EXIST CONCRETE
MASONRY WALL
NEW CONCRETE MASONRY
SOAPS; SEE STRUCT
BACKER ROD AND
SEALANT EACH SIDE
HM DOOR FRAME AND
DOOR
EXTERIOR HM DOOR HEAD
(4") @ STUCCO WALL DETAIL
1 1/2"=1'-0"
5/8" GWB ON AIR
BARRIER
NEW STEEL LINTEL;
SEE STRUCT
00A501
3-COAT STUCCO ON 2" RIGID BD
INSULATION (MATCH EXIST
COLOR AND FINISH)
2" METAL STUD FRAMING
W/ HIGH DENSITY SPRAY
FOAM INSULATION
EPOXY FLOOR FINISH
@ DOOR OPENING
EXTERIOR HM DOOR SILL
DETAIL
1 1/2"=1'-0"
NEW RAISED FLOOR
SYSTEM
00A501
EXISTING CONCRETE
FLOOR AND FOUNDATION
NEW HM DOOR AND
FRAME
THRESHOLD SET IN
FULL BED OF SEALANT
MASONRY VENEER
RETURN BEYOND
NEW CONCRETE STOOP;
SEE STRUCT
1/2" COMPRESSIBLE
FILLER WITH SEALANT
SLOPE 1/2"
4"
THRU-WALL FLASHING
WITH DRIP EDGE
00A301
HM DOOR HEAD IN STUD WALL
3" = 1' - 0"
GYPSUM BOARD OR TILE
BACKER BOARD EACH SIDERUNNER CHANNEL
ON TOP OF
DOUBLE STUD
LINTEL
HM DOOR
FRAME
METAL STUD HEADER FRAMING
3 5/8 " METAL STUDS @ 16" OC
WITH SOUND BATT INSULATION
00A301
HM DOOR JAMB IN STUD WALL
3" = 1' - 0"
GYPSUM BOARD OR TILE
BACKER BOARD EACH SIDE
METAL STUDS
"DRYWALL" TYPE
HM DOOR FRAME
3 5/8" METAL STUDS @ 16 OC
00A301
HM DOOR HEAD IN CAVITY STUD WALL (JAMB SIM)
3" = 1' - 0"
RUNNER CHANNEL
ON TOP OF
DOUBLE STUD
LINTEL
HM DOOR AND
FRAME
EXIST GYPSUM EACH SIDE
NEW METAL STUD HEADER
FRAMING
EXIST METAL STUDS @ 16" OC
WITH SOUND BATT INSULATION
J TRIM AND SEALANT
AT PERIMETER
00A301
HM DOOR SILL IN CAVITY STUD WALL
3" = 1' - 0"
RUNNER CHANNEL
ON TOP OF
DOUBLE STUD
LINTEL
HM DOOR AND
FRAME
5/8" TYPE-X GYPSUM EACH SIDE
NEW METAL STUD HEADER
FRAMING (BOTH SIDES)
METAL STUDS @ 16" OC
WITH SOUND BATT INSULATION
(BOTH SIDES)
3/4" FIRE RATED PLYWOOD
FIRE CAULKING EACH SIDE
MATCH EXISTING
F
R A
M I N
G
H
E I G
H T
VCT FLOORING
EXISTING RAISED
FLOORING
NEW RAISED FLOOR
NOTE:
SILL DETAIL IS SIMILAR TO 7/00501. FRAMING HEIGHT IS 12" AFF.
NOTE:
SILL DETAIL IS SIMILAR TO 7/00501. FRAMING HEIGHT IS 12" AFF.
REFER TO WALL TYPE 3A, SECOND LAYER
GWB ADDED OVER EXISTING WALL
CORNER BEAD AND SEALANT
WHERE OCCURS
A501
AR
CH
ITE
CT
UR
AL
D
ET
AIL
S A
ND
SC
HE
DU
LE
S
OP
27 SOW
SP
27th
IAL
EC W
IN
G
ERATION
OF
SP
EC
IAL
O
PE
RA
TIO
NS
Mo de rni ze
H
VA
C an d E lec tric al
Re du nd an cy , B
JU
LY
20Property of the United States Government;
Copying, Dissemination, or Distribution of these drawings or specifications to any
1'-0" (VERIFY)
WALL TYPE
SCALE: NTS
WALL TYPE
SCALE: NTS
FIRE RATING: VARIES, SEE BELOW
TEST: UL U419
FIRE RATING: NOT RATED
DECK
FIRE STOPPING AND
FIRE RATED SEALANT
METAL STUD TO
BOTTOM OF
STRUCTURE
LINE OF CEILING
5/8" TYPE-X GWB
6" METAL STUDS
LINE OF FLOOR
FIRE RATED SEALANT
SOUND BATT INSULATION
DECK
ACOUSTICAL SEALANT
EACH SIDE
METAL STUD TO
BOTTOM OF
STRUCTURE
LINE OF CEILING
5/8" GWB
4" METAL STUDS
STAGGERED
LINE OF FLOOR
ACOUSTICAL SEALANT
EACH SIDE
SOUND BATT INSULATION
3B
EXISTING: 1 HR RATED STC-45,
GYP BD WALL (U419) - 6" STUDS
3J
EXISTING: STC-45, 5/8" GYP BD
WALL (NOT RATED) - 8" STUDS
EXISTING: STC-45, 5/8" TYPE-X GYP
BD WALL (NOT RATED) - 6" STUDS
3E
EXISTING: 1 HR RATED, STC-45, GYP BD
WALL WITH CERAMIC TILE ON ONE SIDE
(U419) - 6" STUDS
WALL TYPE
SCALE: NTS
FIRE RATING: MAXIMUM 1 HR
TEST: UL U419
DECK
FIRE STOPPING AND
FIRE RATED SEALANT
METAL STUD TO
BOTTOM OF
STRUCTURE
LINE OF CEILING
5/8" TYPE-X GWB
4" METAL STUDS
LINE OF FLOOR
FIRE RATED SEALANT
SOUND BATT INSULATION
2F
EXISTING: STC-50, 5/8 " TYPE-X
GWB BOTH SIDES - 4" STUDS
GENERAL NOTES:
1. UL NUMBERS FOR PARTITION TYPES ARE BASED ON THE
AS BUILT DRAWINGS PROVIDED BY THE GOVERNMENT.
2. SEE ROOM FINISH SCHEDULE FOR FINISHES
3. SEE PLANS FOR WALL TPES
4. PROVIDE ACOUSTICAL SEALANT AT WALL TYPES
INDICATED TO RECEIVE SOUND INSULATION.
5. PROVIDE FIRE STOPPING AND FIRE RATED SEALANT AS
REQUIRED FOR ASSEMBLY INDICATED AT FIRE RATED
WALLS.
6. SEE PLANS FOR WALL THICKNESS NOT SHOWN ON THIS
DRAWING.
7. MAINTAIN STC SOUND RATING LISTED FOR WALLS BEING
PENETRATED.
8. ADD 1-LAYER 5/8 " TYPE-X GWB TO WEST AND SOUTH
WALLS OF ROOM 132 TO MAKE THESE WALLS 1 HOUR
RATED.
9. ALL WALLS AROUND COMM ROOM-233 ARE WALL TYPE-3F.
10. TEMPORARY WALL TYPE-T SHALL HAVE IDS. SEE
ELECTRICAL.
00A502
WALL TYPES
NTS
CHASE WALL
T
WALL TYPE
SCALE: NTS
FIRE RATING: MAXIMUM 1 HR
TEST: UL U419
DECK
FIRE STOPPING AND
FIRE RATED SEALANT
METAL STUD TO BOTTOM
OF STRUCTURE
LINE OF CEILING
2 LAYERS OF 5/8"
TYPE-X GWB
4" METAL STUDS (16 GA)
LINE OF
STRUCTURAL FLOOR
FIRE RATED SEALANT
BOTH SIDES
3 1/2 " SOUND BATT
INSULATION (MIN)
FASTENED TO PREVENT
SLIDING DOWN AND
LEAVING A VOID AT TOP
NEW: TEMPORARY WALL TYPE-T SHALL
CONFORM TO UFC 4-010-05 SCIF
PLANNING AND DESIGN AND SCIF TECH
SPECS V1.4, 28 SEPT 2017, CHAPTER 3,
FIGURE 1 (WALL A) ON PAGE 17.
5/8" TYPE-X GWB
CONTROLLED SIDE UNCONTROLLED SIDE
16 GA CONT TRACK TOP
AND BOTTOM W/
ANCHORS AT 32" MAX
SET ON CONT BED OF
ACOUSTICAL SEALANT
NOTE: ENTIRE WALL ASSEMBLY SHALL
BE PAINTED FROM TRUE FLOOR TO
TRUE CEILING STRUCTURE.
EXISTING: 5/8" GYP BD WALL - 6"
STUDS
3A
NEW: ADD ONE LAYER OF 5/8" TYPE-X
GYP BD TO THE SECURE SIDE OF
EXISTING WALL TYPE 3. INTENT IS THIS
WALL BECOMES THE NEW SECURE
BOUNDARY, CONFORMS TO ICD 705
WALL A, AND 1 HR RATED (U419).
A502
WA
LL
TY
PE
S A
ND
D
ET
AIL
S
OP
27 SOW
SP
27th
IAL
EC
W
IN
G
ERATION
OF
SP
EC
IAL
O
PE
RA
TIO
NS
Mo de rni ze
H
VA
C an d E lec tric al
Re du nd an cy , B
JU
LY
Property of the United States Government;
Copying, Dissemination, or Distribution of these drawings or specifications to any
GROUT CORES FULL
W LINTEL SEE
DETAIL 7/S001
STIFF PL
1/4 EA SIDE
SEE
NOTE 3
3/16
3/16
NOTES:
1. SHORE EXISTING MASONRY WALL AS REQUIRED AND REMOVE
EXISTING LINTEL.
2. REMOVE 12" CMU AS REQUIRED TO INSTALL W-LINTEL W/ BOTTOM
PLATE.
3. CONTRACTOR TO VERIFY CMU COURSING TO ENSURE LINTEL IS
BEARING AT THE FIRST FULL CMU CELL. SAW TOOTH IN SOLID BLOCK
AT EXISTING PARTIAL BLOCK.
STEEL LINTEL
BEARING @ EXISTING CMU
1"=1'-0"
BEARING PL 1/2x7x0'-11"
W/2-1/2" DIAx4 LONG
HEADED STUDS
8" MIN
BEARING
C5. PROVIDE 3/4" CHAMFERS AT ALL EXPOSED EDGES. NOT ALL CHAMFERS MAY BE SHOWN ON
DRAWINGS.
C6. FIELD ADJUST REINFORCING AT OPENINGS AND EMBEDDED ITEMS AS INDICATED.
C7. ANCHOR BOLTS NOT SPECIFIED BY ENGINEER SHALL BE DESIGNED AND CERTIFIED BY A
REGISTERED PROFESSIONAL ENGINEER, RETAINED BY THE CONTRACTOR, IN ACCORDANCE WITH
APPLICABLE PROJECT AND CODE REQUIREMENTS. SUBMIT AS A SHOP DRAWING FOR REVIEW AND
APPROVAL BY THE ENGINEER. COORDINATE LOCATION, SIZE AND EMBEDMENT PRIOR TO CASTING
CONCRETE.
C8. ABSOLUTELY NO WELDING OF REINFORCING BARS OR TORCHING TO BEND REINFORCING BARS
SHALL BE ALLOWED WITHOUT SPECIFIC APPROVAL FROM THE STRUCTURAL ENGINEER.
C9. CONTRACTOR SHALL SUBMIT A CONCRETE PLACEMENT PLAN PER SPECIFICATION 03 30 00
IDENTIFYING JOINT TYPES, JOINT LOCATIONS AND CONCRETE PLACEMENT SEQUENCE.
C10. ALL CAST IN PLACE AND POST-INSTALLED ANCHORS INDICATED IN THE STRUCTURAL DOCUMENTS
SHALL COMPLY WITH CHAPTER 17 OF ACI 318 AND CHAPTER 19 OF THE IBC. ALL EXPANSION AND
ADHESIVE ANCHORS SHALL HAVE THE ICC REPORT SHOWING EQUIVALENT LOAD CAPACITY.
SUBMIT AND INSTALL PER THE ICC EVALUATION REPORT.
MASONRY
M1. DESIGN STRENGTHS:
F'm= 1500 PSI
Fy = 60,000 PSI
M2. GROUT FOR FILLING MASONRY CAVITIES TO BE COARSE GROUT UNO, MAXIMUM COARSE
AGGREGATE SIZE IS 3/8 INCH.
M3. GROUT POURS SHALL NOT EXCEED 4 FEET IN HEIGHT UNLESS CLEANOUTS ARE PROVIDED IN THE
BOTTOM COURSE OF THE CELL(S) TO BE GROUTED AND WRITTEN PERMISSION IS OBTAINED FOR
HIGH LIFT GROUTING.
M4. RESTRICTED BAR ANCHORAGE:
IN CASES WHERE REINFORCING BARS CANNOT BE EXTENDED AS FAR AS REQUIRED, THE BARS
SHALL EXTEND AS FAR AS POSSIBLE AND END IN STANDARD HOOK. SHOW ON SHOP DRAWINGS
AND HIGHLIGHT WITH A BOX TO BRING TO ENGINEER'S ATTENTION.
M5. ANCHOR BOLTS:
ALL EXPANSION AND ADHESIVE ANCHORS SHALL HAVE THE ICC REPORT SHOWING EQUIVALENT
LOAD CAPACITY. SUBMIT AND INSTALL PER THE ICC EVALUATION REPORT.
M6. LINTEL BLOCKS SHALL NOT BE USED AS BOND BEAM BLOCKS EXCEPT AT OPENINGS WHERE BOND
BEAMS AND LINTELS COINCIDE.
STEEL
S1. DESIGN STRENGTHS:
WIDE FLANGE, TEES, AND HSS SECTIONS: Fy=50 KSI
PIPES: Fy=35KSI
STAINLESS STEEL Fy=33 KSI
ALL OTHER PLATES AND SHAPES: Fy=36 KSI
S2. DIMENSIONS:
TO CENTERLINES OF COLUMNS AND BEAMS, TOP SURFACES OF BEAMS AND TUBES AND BACKS OF
CHANNELS AND ANGLES UNO.
S3. ELEVATIONS:
TOP OF STEEL REFERS TO TOP SURFACE OF MEMBER OR FLANGE UNO.
S4. WHEN FILLET WELD SIZE IS NOT INDICATED, PROVIDE MAXIMUM WELD SIZE BASED ON MATERIAL
THICKNESS IN ACCORDANCE WITH AISC SPECIFICATIONS.
S5. ALL BOLTED STRUCTURAL CONNECTIONS ARE BEARING TYPE CONNECTIONS UNLESS OTHERWISE
SPECIFIED TO BE SLIP-CRITICAL. PROVIDE LOAD INDICATING WASHERS AT SLIP-CRITICAL
CONNECTIONS.
ALUMINUM
A1. STRUCTURAL ALUMINUM YIELD STRENGTHS
STRUCTURAL ALUMINUM: Fy=35 KSI
STRUCTURAL ALUMINUM IS ALLOY 6061-T6 UNO
A2. DIMENSIONS:
TO CENTERLINES OF COLUMNS AND BEAMS, TOP SURFACES OF BEAMS AND TUBES AND BACKS OF
CHANNELS AND ANGLES UNO.
A3. ELEVATIONS:
TOP OF ALUMINUM REFERS TO TOP SURFACE OR FLANGE OF MEMBER UNO.
A4. WHEN FILLET WELD SIZE IS NOT INDICATED, PROVIDE MAXIMUM WELD SIZE FOR THE MATERIAL
THICKNESS IN ACCORDANCE WITH THE LATEST EDITION OF THE "ALUMINUM DESIGN MANUAL" BY
THE ALUMINUM ASSOCIATION.
A5. ALUMINUM IN CONTACT WITH DISSIMILAR MATERIALS OR CONCRETE:
CONTACT SURFACES SHALL BE PROVIDED WITH GALVANIC SEPERATION PER SPECIFICATIONS.
GENERAL STRUCTURAL NOTES (GSN)
GENERAL
G1. SCOPE
THE NOTES ON THIS SHEET AND THE STANDARD STRUCTURAL DETAILS ARE GENERAL AND APPLY
TO THE ENTIRE PROJECT WHETHER SPECIFICALLY CALLED OUT OR NOT, EXCEPT WHERE THERE
ARE SPECIFIC INDICATIONS TO THE CONTRARY ON STRUCTURAL SHEETS. IF THERE ARE
QUESTIONS, THEY SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER AND ANSWERED IN
WRITING PRIOR TO CONSTRUCTION.
G2. APPLICABLE SPECIFICATIONS AND CODES
A. INTERNATIONAL BUILDING CODE, IBC 2018 WITH APPLICABLE EDITIONS OF THE CODE
REFERENCED STANDARDS.
B. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE ACI 318-14.
C. MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES ASCE 7-16.
D. AMERICAN INSTITUE OF STEEL CONSTRUCTIONS AISC.
E. AMERICAN WELDING SOCIETY (AWS) D1.1, D1.3, D1.4.
F. ASTM MATERIAL STANDARDS AS NOTED.
G. BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY.
H. UFC 1-200-01 DOD BUILDING CODE.
I. UFC 3-301-01 STRUCTURAL ENGINEERING (OCTOBER 2019)
G3. DESIGN CRITERIA
1. APPLIES TO ALL STRUCTURES (UNO)
A. DEAD LOAD:
1. ACTUAL TRIBUTARY STRUCTURE WEIGHT
B. LIVE LOAD:
1. WALKWAYS, STAIRS, GRATING: 100 PSF
2. SLAB ON GRADE: 250 PSF
C. ROOF LIVE LOADS: 20 PSF
D. WIND LOADS:
1. BASIC WIND SPEED: 106 MPH ASCE 7-16
E. SEISMIC:UFC-301-01
1. IMPORTANCE FACTOR, IE: 1.00
2. MAPPED SPECTRAL RESPONSE ACCELERATIONS:
S
S
: 0.086
S
: 0.033
3. SITE CLASSIFICATION: D
4. SPECTRAL RESPONSE COEFFICIENTS:
S
DS
: 0.091
S
D1
: 0.053
5. SEISMIC DESIGN CATEGORY: A
a. BASIC SEISMIC FORCE RESISTING SYSTEM: DUAL SYSTEM
ORDINARY REINFORCED MASONDRY SHEAR WALLS AND ORDINARY
STEEL MOMENT FRAMES.
G4. GEOTECHNICAL ASSUMPTIONS WERE BASED ON EXISTING SOILS INFORMATION PROVIDED FROM
AS-BUILT DRAWING S-001.
G5. SAFETY
SAFETY AND STRUCTURE STABILITY DURING CONSTRUCTION ARE THE SOLE RESPONSIBILITY OF
THE CONTRACTOR. STRUCTURES HAVE BEEN DESIGNED TO RESIST THE DESIGN LIVE LOADS ONLY
AS A COMPLETED STRUCTURE.
G6. OPENINGS
OPENINGS FOR PIPES, DUCTS, CONDUITS, ETC. ARE NOT ALL SHOWN ON THE STRUCTURAL
DRAWINGS. COORDINATE AND PROVIDE OPENINGS AS REQUIRED TO ACCOMMODATE ALL WORK
SHOWN OR SPECIFIED IN THE CONTRACT DOCUMENTS AND OTHERWISE REQUIRED FOR THE
FURNISHING OF A FUNCTIONALLY COMPLETE PROJECT. REINFORCE AROUND OPENINGS PER
STANDARD STRUCTURAL DETAILS UNLESS OTHERWISE SHOWN.
G7. SPECIAL INSPECTIONS
SPECIAL INSPECTIONS ARE REQUIRED IN ACCORDANCE WITH CHAPTER 1 AND CHAPTER 17 OF THE
IBC. PAYMENT FOR THESE INSPECTIONS IS NOT THE RESPONSIBILITY OF THE CONTRACTOR. THE
CONTRACTOR SHALL PROVIDE FOR FULL ACCESS TO THE WORK BY THE SPECIAL INSPECTOR AND
SHALL PROVIDE FOR THESE INSPECTIONS IN HIS CONSTRUCTION SCHEDULE IN ACCORDANCE
WITH THE SPECIFICATIONS.
G8. STANDARD DETAILS
THE STANDARD DETAILS DEPICT TYPICAL DETAILING TO BE USED ON THIS PROJECT. IF
CONDITIONS ARE NOT EXPLICITLY SHOWN ON THE DRAWINGS THEY SHALL BE MADE SIMILAR TO
THE STANDARD DETAILS. OBTAIN APPROVAL OF ENGINEER IN WRITING FOR SIMILAR CONDITIONS
PRIOR TO CONSTRUCTION.
G9. THE CONTACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS OF EXISTING
CONSTRUCTION AS REQUIRED TO COORDINATE NEW CONSTRUCTION. SUBMIT REQUIRED
CHANGES FOR APPROVAL.
G10. CONTRACTOR TO SUBMIT FOR REVIEW ALL EQUIPMENT SIZES, OPERATING WEIGHTS, VIBRATION
FORCES, SUPPORT LOCATIONS, ALONG WITH ANY FLOOR OPENINGS, NOTCHES, AND RECESSES
REQUIRED BY SUCH EQUIPMENT. CONCRETE SUPPORT PADS AND/OR FRAMING REQUIRED TO
SUPPORT SAID EQUIPMENT SHALL NOT BE FABRICATED AND PLACED UNTIL THE CONCRETE
SUPPORT PADS AND/OR FRAMING IS APPROVED TO SUPPORT THE EQUIPMENT.
CONCRETE
C1. DESIGN STRENGTHS:
F'c = 4000 PSI
Fy = 60,000 PSI
C2. CONCRETE COVER
UNLESS OTHERWISE NOTED, PROVIDE CONCRETE COVER FOR REINFORCING AS FOLLOWS:
CONCRETE DEPOSITED AGAINST EARTH: 3"
ALL OTHER: 2"
SEE DRAWINGS FOR EXCEPTIONS
C3. SEE SPECIFICATIONS FOR REINFORCING PLACEMENT REQUIREMENTS.
C4. REFER TO OTHER DISCIPLINE DRAWINGS PRIOR TO CONSTRUCTION FOR EMBEDDED ITEMS AND
PENETRATIONS NOT SHOWN ON STRUCTURAL DRAWINGS. AS REQUIRED TO ACCOMMODATE ALL
WORK SHOWN OR SPECIFIED IN THE CONTRACT DOCUMENTS AND OTHERWISE REQUIRED FOR THE
FURNISHING OF A FUNCTIONALLY COMPLETE PROJECT. REINFORCE AROUND OPENINGS PER
STANDARD STRUCTURAL DETAILS UNLESS OTHERWISE SHOWN.
CONCRETE (CONTINUED)
NOTE:
1. BAR SIZES NOTED ON DRAWINGS ARE GIVEN IN
"INCH-POUND" BAR SIZES. EQUIVALENT "METRIC
BARS" HAVING THE SAME PHYSICAL SIZE AND
MINIMUM YIELD STRENGTH MAY BE SUBSTITUTED
PER THE TABLE ABOVE.
EQUIVALENT BAR SIZES
1"=1'-0"
METRICINCH-POUND
EQUIVALENT BAR SIZES
#3
#5
#4
#7
#9
#8
#10
#11
#6
#10
#13
#16
#19
#22
#25
#29
#32
#36
#14
#15
GRADE 60
#43
#57
GRADE 420
INSTALLATION OF PIPES/CONDUITS
1"=1'-0"
1'-0"FOOTING WIDTH1'-0"
AREA OK FOR SLEEVES
FOR PIPES ON THIS AREA
LOWER ENTIRE FOOTING TO
ALLOW PIPE TO EXTEND
THROUGH FOOTING
FOR PIPES ON THIS AREA
LOWER BOTTOM OF
FOOTING TO ALLOW PIPE
TO EXTEND THROUGH
FOOTING
F O
O T
I N
G
D
E P
T H
M A
X
PIPE OF CONDUIT
PERPENDICULAR
TO FOOTING
PROVIDE SLEEVE 2"
(NOMINAL) LARGER
THAN PIPE O.D.
PROVIDE SLEEVE 2" (NOMINAL)
LARGER THAN PIPE O.D.
FOUNDATION WALL
WALL
WIDTH
PIPE OF CONDUIT
PERPENDICULAR TO FOOTING
PROVIDE SLEEVE 2" (NOMINAL)
LARGER THAN PIPE O.D.
NOTES:
1. FOR PIPES 3'-0" OR LESS BELOW FOOTING, PROVIDE SLEEVES AS
SHOWN.
2. FOR PIPES AND CONDUITS MORE THAN 3'-0" BELOW FOOTING, PIPE
SLEEVE MAY BE ELIMINATED.
3. COORDINATE WITH MECH, ELECT AND OTHER AFFECTED TRADES.
180 DEG STD HOOK90 DEG STD HOOK
HL=
HOOK LENGTH
CONCRETE JOINT
M I N
C O
V E
R
HW=
HOOK WIDTH
T L
T A
I L
L
E N
G T
H
TL
3"
5"
4 1/2"
HW
4"
5"
3"
7"
8"
1'-1"
11 3/4"
8"
7"
1'-2 3/4"
1'-1 1/4" 11 1/2"
10 1/2"
6"6"
HL
8"
6"
10"
BAR SIZE
#3
#5
#4
1'-2"
1'-7"
1'-4"
1'-10"
2'-0"
#7
#9
#8
#10
#11
#6 1'-0"
GRADE 60
D
2 1/4"
3 3/4"
3"
5 1/4"
6"
12"
10 3/4"
9 1/2"
4 1/2"
D
T
Y
P
REINFORCING HOOK SCHEDULE
1"=1'-0"
GRID GRID
5'-0"
8"
#4@12
3-#4 CONT
SLOPE 1/4" / F
T
4" CONC SLAB
W/#4@12 EW
3/8" COMP FILLER JT EXISTING EDGE
EXISTING SLAB ON GRADE
SECTION
1"=1'-0"
2'-0"
2'-0"
#4@12
ADHESIVE
DOWEL
1'-0"
1'-0"
3/8" COMP FILLER JT
EXISTING CMU
COMPACTED
STRUCTURAL FILL
EXISTING FOUNDATION,
FIELD VERIFY
2" CLR.
4" MIN.
EXIST 12" CMU
NON-SHRINK GROUT
BETWEEN W8 AND
EXIST CMU
2-123/16
TOP & BOT PL 1/4 x 12" x CONT
STOP 1/2" SHORT AT EACH
END OF OPENING
NOTES:
1. SHORE EXISTING MASONRY WALL AS REQUIRED AND
REMOVE EXISTING LINTEL.
2. REMOVE 12" CMU AS REQUIRED TO INSTALL NEW
W-LINTEL W/ BOTTOM PLATE.
3. FOR ADDITIONAL INFORMATION, SEE DETAIL 8/S001.
4. SEE ARCHITECTURAL DRAWINGS FOR MASONRY
LINTEL LOCATIONS.
STEEL LINTEL
@ EXISTING CMU
1"=1'-0"
W8X24 STEEL
LINTEL
T
S E
E
P L
A N
TYPICAL ISOLATION JOINT (IJ)
1"=1'-0"
NOTE:
1. AT SLAB-ON-GRADE.
FACE OF WALL OR COLUMN
1/2" EXP JOINT MATERIAL
1/2" WIDE X 1/2" DEEP GROOVE
W/SEALANT @ EXPOSED FLOOR
SLAB ON GRADE
EQUIPMENT PAD EXTENSION
1"=1'-0"
EXISTING PAD
SEE MECH
#4@16 T&B ADHESIVE
ANCHOR EMBED 12"
#4@12 T&B
EXISTING MECH
YARD SLAB
PAD EXTENSION
IJ
OP
27 SOW
SP
27th
IAL
EC W
IN
G
ERATION
OF
SP
EC
IAL
O
PE
RA
TIO
NS
Mo de rni ze
H
VA
C an d E lec tric al
Re du nd an cy , B
JU
LY
S001
GE
NE
RA
L S
TR
UC
TU
RA
L N
OT
ES
TY
PIC
AL
D
ET
AIL
S
Property of the United States Government; Copying, Dissemination, or Distribution of these drawings or specifications to any unathorized person is prohibited.
M001
ME
CH
AN
ICA
L L
EG
EN
D
OP
27 SOW
SP
27th
IAL
EC W
IN
G
ERATION
OF
SP
EC
IAL
O
PE
RA
TIO
NS
Mo de rni ze
H
VA
C an d E lec tric al
Re du nd an cy , B
JU
LY
GPM GALLONS PER MINUTE
I/O INPUT/OUTPUT
I/P CURRENT TO PNEUMATIC
IAQ INDOOR AIR QUALITY
IPLV INTEGRATED PART LOAD VALUE
LAT LEAVING AIR TEMPERATURE
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MAU MAKE-UP AIR UNIT
MBH THOUSAND BTUH
MCC MOTOR CONTROL CENTER
NC NOISE CRITERIA
NO NUMBER
NRC NOISE REDUCTION COEFFICIENT
OS&Y OUTSIDE SCREW AND YOKE
PD PRESSURE DROP
PPH POUNDS PER HOUR
RH RELATIVE HUMIDITY
RTU ROOFTOP UNIT
S SIGNAL PORT
SCFM STANDARD CUBIC FEET PER MINUTE
SEER SEASONAL ENERGY EFFICIENCY RATIO
SP STATIC PRESSURE
TC TECHNOLOGY CONTRACTOR
TCC TEMPERATURE CONTROL CONTRACTOR
TCP TEMPERATURE CONTROL PANEL
TD TEMPERATURE DIFFERENTIAL
TES THERMAL ENERGY STORAGE
TSP TOTAL STATIC PRESSURE
UH UNIT HEATER
V&C VALVE AND CAP
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
VTR VENT THROUGH ROOF
WB WET BULB
WC WATER COLUMN
WPD WATER PRESSURE DROP
AD ACCESS DOOR
AFR ABOVE FINISHED ROOF
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP
ARF ABOVE RAISED FLOOR
AV ABOVE RAISED FLOOR
BAS BUILDING AUTOMATION SYSTEM
BDD BACK DRAFT DAMPER
BHP BRAKE HORSE POWER
BOE BOTTOM OF EQUIPMENT
BTUH BRITISH THERMAL UNITS PER HOUR
CAV CONSTANT AIR VOLUME
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
COP COEFFICIENT OF PERFORMANCE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CRAC COMPUTER ROOM AIR CONDITIONER
CU CONDENSING UNIT
DB DRY BULB
DDC DIRECT DIGITAL CONTROL
DH DEHUMIDIFIER
DX DIRECT EXPANSION
EAT ENTERING AIR TEMPERATURE
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EMCS ENERGY MANAGEMENT CONTROL
SYSTEM
ERU ENERGY RECOVERY UNIT
ESP EXTERNAL STATIC PRESSURE
ESS EMERGENCY SHUTOFF SWITCH
EWT ENTERING WATER TEMPERATURE
F FUTURE
FA FREE AREA
FCP FAN CONTROL PANEL
FCU FAN COIL UNIT
FDBK FEEDBACK
FLA FULL LOAD AMPS
FLT FILTER
FPB FAN POWERED BOX
FPM FEET PER MINUTE
GC GENERAL CONTRACTOR
GE GRAVITY EXHAUST
GI GRAVITY INTAKE
GPH GALLONS PER HOUR
GENERAL HVAC NOTESGENERAL MECHANICAL DEMOLITION NOTES GENERAL MECHANICAL NOTES
HVAC SYMBOLOGY
24x18
18x24
SUPPLY AIR OR OUTSIDE AIR
DUCT UP (SECTION CUT,
FIRST DIMENSION DUCT WIDTH)
RETURN AIR DUCT UP
(SECTION CUT)
SUPPLY AIR OR OUTSIDE AIR
DUCT DOWN (NO SECTION CUT)
RETURN AIR DUCT DOWN (NO
SECTION CUT)
TRANSITION -
RECTANGULAR TO ROUND DUCT
STANDARD BRANCH
RECTANGULAR DUCT OR OPENING SIZE
FIRST NUMBER INDICATES SIZE OF
SIDE SHOWN
RECTANGULAR DUCT INCLINE - RISE OR
DROP IN RESPECT TO THE AIR FLOW
ROUND DUCT SIZE
ROUND DUCT INCLINE - RISE OR DROP
IN RESPECT TO THE AIR FLOW
VOLUME DAMPER
ELBOW - (RECTANGULAR),
SMOOTH RADIUS
ELBOW - W/TURNING VANE
(RECTANGULAR)
EXHAUST AIR DUCT UP (NO
SECTION CUT)
EXHAUST AIR DUCT DOWN
(NO SECTION CUT)
ROUND ELBOW UP
ROUND ELBOW DOWN
FIRE DAMPER
SMOKE DAMPER
SMOKE AND FIRE DAMPER
MOTOR OPERATED DAMPER
M
DUCT/PIPE ELEVATION TAG ABOVE
FINISH FLOOR
18x10
HIDDEN DUCT
18x24
T 9'-10"
B 9'-0"
FLEXIBLE CONNECTION
FLEXIBLE DUCT - TWO LINE
UC
TAG-SIZE
CFM
UNDERCUT DOOR
SUPPLY AIR REGISTER
EXHAUST AIR OR
RETURN AIR GRILLE
EXHAUST AIR OR
RETURN AIR GRILLE
SUPPLY AIR ASSEMBLY
SQUARE DIFFUSER
SUPPLY AIR ASSEMBLY
ROUND DIFFUSER
ACOUSTICAL LINING - DUCT
DIMENSIONS FOR NET FREE AREA
FLEXIBLE DUCT - ONE LINE
UNION
CONCENTRIC REDUCER
ECCENTRIC REDUCER,
FLAT ON BOTTOM
ELBOW, 90° TURN DOWN
ELBOW, 90° TURN UP
TEE, OUTLET UP
TEE, OUTLET DOWN
TEE, OUTLET UP
W/ 90° TURN
TEE, OUTLET DOWN
W/ 90° TURN
PIPE BREAK
PIPE CAP
BLIND FLANGE
FLOW ARROW
GLOBE VALVE
DRAIN VALVE
CHECK VALVE
CALIBRATED MANUAL
BALANCING VALVE
AUTOMATIC CONTROL
VALVE, 2-WAY
AUTOMATIC CONTROL
VALVE, 3-WAY
AUTOMATIC FLOW
CONTROL VALVE
BACKFLOW PREVENTER
PT
T
A
PIPING SYMBOLOGY
PIPE ANCHOR
PIPE GUIDE
EXPANSION JOINT
PRESSURE/
TEMPERATURE PORT
THERMOMETER
PRESSURE GAUGE
TEMPERATURE
GAUGE
FLEXIBLE PIPING
CONNECTION
WYE STRAINER
MANUAL AIR VENT
THERMOWELL
AUTOMATIC AIR VENT
SHUTOFF VALVE
(NORMALLY OPEN)
METER (WATER,
GAS, OTHER)
FLOOR CLEANOUT
DOUBLE GRADE
CLEANOUT
M
FCO
GCO
PIPING SYSTEMS
COLD WATER,
POTABLE (CW)
HOT WATER,
POTABLE (HW)
HOT WATER
RECIRCULATING,
POTABLE (HWC)
NON POTABLE COLD
WATER
SANITARY SEWER
BELOW GRADE
SANITARY SEWER
ABOVE GRADE
SANITARY VENT
STORM DRAIN
ABOVE GRADE
STORM DRAIN
BELOW GRADE
STORM DRAIN
OVERFLOW
PRESSURE DRAINAGE
COMPRESSED AIR
NATURAL GAS
CHILLED WATER
SUPPLY
CHILLED WATER
RETURN
HEATING HOT
WATER SUPPLY
HEATING HOT
WATER RETURN
CONDENSER
WATER SUPPLY
CONDENSER
WATER RETURN
CONDENSATE DRAIN
STEAM SUPPLY - PSI
CONDENSATE PUMP
DISCHARGE
BOILER BLOW DOWN
BOILER FEED
STEAM VENT
HOT WATER -
TEMPERATURE, POTABLE
ACID WASTE
ACID VENT
COMBINATION WASTE
AND VENT
LIQUEFIED PROPANE
GLYCOL HEATING HOT
WATER RETURN
GLYCOL HEATING HOT
WATER SUPPLY
REFRIGERANT
LIQUID
REFRIGERANT
SUCTION
MAKE-UP WATER
VACUUM BREAKER
VB
WATER HAMMER
ARRESTOR
EARTHQUAKE VALVEE
TAG-SIZE
CFM
TAG
CFM
TAG
CFM
TAG
CFM
HWS
HWR
GHWS
GHWR
CHWS
CHWR
CWS
CWR
RL
RS
CD
STM -15
CPD
BBD
BF
SV
MU
CA
LP
NG
OD
SD
SD
PD
CWV
AV
AW
V
SAN
SAN
CLEANOUT
WALL CLEANOUT
BFP
GATE VALVE
TEPID WATER,
POTABLE
TEPID WATER RETURN,
POTABLE
TWR
TW
CO
WCO
ECCENTRIC REDUCER,
FLAT ON TOP
NEW TO EXISTING CONNECTION
REMOVE EXISTING UP TO
THIS POINT
HVAC EMERGENCY
SHUTDOWN SWITCH
NPW
PLUMBING FIXTURE
XX-1
S
S
GLYCOL CHILLED
WATER RETURN
GLYCOL CHILLED
WATER SUPPLY
GCWS
GCWR
TEMPERATURE CONTROL DIAGRAM SYMBOLOGY ABBREVIATIONS
T
M
X
X
XX
XX
COIL IDENTIFIERS
CC CHILLED WATER COOLING COIL
DG DIRECT FIRED GAS BURNER
DX DIRECT EXPANSION COOLING COIL
EH ELECTRIC HEATING COIL
ER DIRECT EVAPORATIVE COIL
FC FACE AND BYPASS COOLING COIL
FH FACE AND BYPASS HEATING COIL
HC HEATING HOT WATER HEATING COIL
IG INDIRECT FIRED GAS BURNER
ST STEAM HEATING COIL
FILTER
BACKDRAFT
DAMPER
FAN
MOTOR OPERATED
DAMPER
DUCT MOUNTED
SMOKE
DETECTOR
TEMPERATURE
AVERAGING
SENSOR
INTAKE/
EXHAUST
LOUVER
PUMP
M
MOTOR OPERATED
SINGLE BLADE
DAMPER
HUMIDIFIER
AFS
AIRFLOW
MEASURING
STATION
PUMP WITH EC MOTOR
EC
M
CONTROL DEVICE IDENTIFIER
AFS AIRFLOW MEASURING STATION
AM AIRFLOW MEASURING SENSOR
CO CARBON MONOXIDE SENSOR
CO2 CARBON DIOXIDE SENSOR
F FLOW SWITCH
FRZ FREEZE STAT
H HUMIDITY SENSOR
HS HIGH STATIC SWITCH
LS LOW STATIC SWITCH
NO2 NITROGEN DIOXIDE SENSOR
P PRESSURE SENSOR
S SPACE TEMPERATURE SENSOR
SD SMOKE DETECTOR
T TEMPERATURE SENSOR
TS TEMPERATURE SWITCH
ΔP DIFFERENTIAL PRESSURE SENSOR
CONTROL ABBREVIATIONS
BTU BTU METER
COMM COMMUNICATION
CT CURRENT TRANSMITTER
EC ELECTRONICALLY COMMUTATED
EF EXHAUST FAN
FM FLOW METER
M MOTOR ACTUATOR
MA MIXED AIR
NC NORMALLY CLOSED
NO NORMALLY OPEN
OA OUTDOOR AIR
RA RETURN AIR
RL RELIEF FAN
RF RETURN FAN
SA SUPPLY AIR
SF SUPPLY FAN
TCC TEMPERATURE CONTROL CONTRACTOR
VFC VARIABLE FREQUENCY CONTROLLER
XX
FAN WITH EC MOTOREC
FRZ
FREEZE STAT
MISCELLANEOUS DEVICE IDENTIFIER
CO SPACE CARBON MONOXIDE SENSOR
CO2 SPACE CARBON DIOXIDE SENSOR
H SPACE HUMIDITY SENSOR
NO2 SPACE NITROGEN DIOXIDE SENSOR
S SPACE TEMPERATURE SENSOR
T THERMOSTAT
X
X
SEE CONTROL
ABBREVIATIONS (TYP)
CONTROL INPUT/OUTPUT IDENTIFIER
AI ANALOG INPUT
AO ANALOG OUTPUT
DI DIGITAL INPUT
DO DIGITAL OUTPUT
XX
S
GENERAL NOTES
SHUTOFF VALVE
(NORMALLY CLOSED)
R OR D
R OR D
1. THE CONTRACTOR SHALL COMPLETELY REMOVE ALL PIPING, DUCTWORK,
COILS, EQUIPMENT, TERMINAL UNITS, ASSOCIATED CONTROLS, WIRING, AND
OTHER ITEMS SHOWN BOLD AND/OR BOLD DASHED LINES UNLESS
SPECIFICALLY NOTED OTHERWISE. THE ITEMS INDICATED ON THE DRAWINGS
TO BE REMOVED ARE ONLY TO INDICATE IN GENERAL THE AMOUNT OF
DEMOLITION WORK INVOLVED. A SITE INVESTIGATION BY THE CONTRACTOR
MUST BE PERFORMED TO AID IN DETERMINING THE COMPLETE EXTENT OF
WORK INVOLVED.
2. PIPING AND DUCTWORK EMBEDDED IN FLOORS, WALLS, AND CEILINGS MAY
REMAIN IF SUCH MATERIALS DO NOT INTERFERE WITH NEW INSTALLATIONS.
REMOVE MATERIALS ABOVE ACCESSIBLE CEILINGS. REMAINING PIPING SHALL
BE DRAINED AND CAPPED WITHOUT CREATING DEAD LEGS IN THE SYSTEM.
REMAINING DUCTWORK SHALL BE CAPPED.
3. LOCATE, IDENTIFY, AND PROTECT MECHANICAL SERVICES PASSING THROUGH
DEMOLITION AREA AND SERVING OTHER AREAS OUTSIDE THE DEMOLITION
LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE DEMOLITION LIMITS. WHEN
SERVICES MUST BE INTERRUPTED, NOTIFY OWNER AND INSTALL TEMPORARY
SERVICES FOR AFFECTED AREAS.
4. EXISTING EQUIPMENT BEING REMOVED AND CONSIDERED SALVAGEABLE BY
THE OWNER SHALL BE TURNED OVER TO THE OWNER. OTHERWISE DISPOSE OF
DEMOLISHED EQUIPMENT AND MATERIALS IN ACCORDANCE WITH
SPECIFICATION SECTION 01 74 19.
5. CONTRACTORS SHALL COORDINATE AND SCHEDULE ALL NECESSARY UTILITY
SHUT-OFFS WITH OWNER PRIOR TO PROCEEDING WITH SUCH WORK.
6. COORDINATE SAW-CUTTING OF THE FLOOR OR WALL WITH OTHER TRADES.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING, PAINTING,
REPAIRING OR REPLACEMENT OF ALL WALLS, FLOORS, CEILINGS, OR OTHER
BUILDING ELEMENTS THAT ARE DISTURBED AS PART OF THE DEMOLITION OR
INSTALLATION OF MECHANICAL WORK. SUCH WORK SHALL MATCH THE
EXISTING CONSTRUCTION, FINISH, AND RATING. FIRE SEAL WALL OPENINGS AS
REQUIRED.
8. REPLACE/REPAIR DAMAGED PIPING AND/OR DUCTWORK INSULATION TO MATCH
EXISTING.
9. CONTRACTOR SHALL PROVIDE WORK IN PHASES AS REQUIRED BY THE
CONTRACT DOCUMENTS WHILE MINIMIZING POTENTIAL WORK DELAYS AND
UTILITY SHUT-DOWNS. COORDINATE ALL WORK WITH PROJECT PHASING PLAN
AND WORK SHOWN ON DEMOLITION AND NEW PLANS. ALL EXISTING AREAS OF
THE BUILDING NOT A PART OF A CURRENT PHASE OF WORK SHALL REMAIN
OPERATIONAL WHILE WORK IN EACH INDIVIDUAL PHASE IS COMPLETED.
10. SEE SPECIFICATION SECTION 01 35 26 FOR HOT WORK REQUIREMENTS.
11. SEE SHEET G005 FOR PHASING PLAN OF WORK.
1. DUCTWORK DIMENSIONS: FIRST NUMBER INDICATES SIDE OF DUCTWORK
SHOWN. ALL DIMENSIONS ARE IN INCHES AND ARE INSIDE CLEAR
DIMENSIONS.
2. VOLUME DAMPERS ABOVE PLASTER OR GYPBOARD CEILINGS SHALL HAVE
EXTENSION RODS AND CHROME-PLATED ESCUTCHEON PLATES.
3. COORDINATE ALL GRILLE, REGISTER AND DIFFUSER LOCATIONS WITH
REFLECTED CEILING PLAN, LIGHTING, AND ALL OTHER CEILING MOUNTED
DEVICES.
4. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK AND PIPING
SYSTEMS CONNECTED TO FANS, PUMPS AND OTHER EQUIPMENT WHICH
REQUIRE VIBRATION ISOLATION.
5. PROVIDE ACCESSIBLE VOLUME DAMPERS OR OTHER MEANS OF AIRFLOW
ADJUSTMENT AT ALL DUCT RUN-OUTS TO DIFFUSERS AND GRILLES.
6. PROVIDE DUCT ACCESS DOORS AT OUTSIDE AIR INTAKE PLENUMS.
7. ALL DUCT RUN-OUTS TO DIFFUSERS AND GRILLES SHALL BE THE SAME AS
THE DIFFUSER OR GRILLE NECK SIZE UNLESS NOTED OTHERWISE.
8. ALL PIPING RUNOUTS SHALL BE 3/4" UNLESS NOTED OTHERWISE.
1. THESE NOTES ARE NOT ALL INCLUSIVE. REFER TO DRAWINGS AND SPECIFICATION FOR
ADDITIONAL REQUIREMENTS.
2. THIS IS A STANDARD MECHANICAL (HVAC AND PLUMBING) SYMBOLOGY AND
ABBREVIATIONS SHEET. LISTING OF SYMBOLS AND ABBREVIATIONS DOES NOT IMPLY ALL
SYMBOLS AND ABBREVIATIONS HAVE BEEN USED ON THIS PROJECT.
3. VALVE SYMBOLS SHOWN HERE ARE APPLICABLE ONLY TO MECHANICAL SHEETS.
4. PROVIDE ALL MATERIALS,…