Attachment_9_CAFB_DDC_Requirements_Guide_-_Sep_2014.pdf

PDF 3 MB Posted

Attached to
Fire Suppression HVAC Building 2110 Federal contract opportunity
Solicitation number
FA4855-16-R-0023
Issued by
Department of the Air Force Special Operations Command

About this file

Attachment 9 CAFB DDC Requirements Guide

View the file

Other files for this federal contract opportunity

Other files attached to Fire Suppression HVAC Building 2110, newest first.
File Type Posted
Asbestos__Report_B2110.pdf PDF
FA4855-16-R-0023_Questions_and_Answeres_Site_Visit.pdf PDF
Asbestos_Inventory_Report_B2110.pdf PDF
Attachment_6_CAFB_Architec_Compat_Guide-2013.pdf PDF
Attachment_17_-_As-Built_Submittal_Guidelines.pdf PDF
Attachment_12_-_Appendix_A_Quality_Checklist.pdf PDF
Attachment_13_-_Appendix_B_Model_File_Layers.pdf PDF
Attachment_14_-_Appendix_C_Sheet_File_Layers.pdf PDF
Attachment_16_-_Appendix_F_Homeland_Security.pdf PDF
FA4855-16-R-0023_Amendment_0002.pdf PDF
Attachment_15_-_Appendix_D_Title_Blocks.pdf PDF
Attachment_11_-_AEC_CAD_Standard_TR-12-X_R-5.pdf PDF
FA4855-16-R-0023_Section_L_-_Amendment_0001.pdf PDF
FA4855-16-R-0023_SF_30_-_Solicitation_Amendment_0001.pdf PDF
FA4855-16-R-0023.pdf PDF
Attachment_3_WD_NM20150023.pdf PDF
Attachment_1_SOO_-_CZQZ98-0130_Install_Fire_Suppression_and_HVAC _B2110.pdf PDF
Attachment_6_CAFB_Architectural_Compatibility_Guide-2012.pdf PDF
Attachment_7_CANNONAFBI32_201_Fire_Protection_Operations_N_Fire_Prevention_Program.pdf PDF
Attachment_10_CAFB_Labeling_Standards__2009_Rev1.pptx PPTX presentation
Attachment_4_CAFB_Electrical_Standards-2016.pdf PDF
Attachment_5_Contractor_Base_Briefing_Pamphlet_(March_2016).pdf PDF
Attachment_8_CAFB_Hardware_Specifications_Guideline-_2011.pdf PDF
Attachment_2_SOMS_-_CZQZ98-0130_Install_Fire_Suppression_and_HVAC _B2110.pdf PDF
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2 7 S O C E S / C E N

DDC General Requirements Guide

For Cannon Air Force Base Scott Hindt - Mechanical Engineer Dave Proctor - EMCS Technician

Barry King - EMCS Technician

U.S Air Force

Page 1 Cannon Air Force Base September 2014

(BLANK PAGE)

September 2014 Cannon Air Force Base Page 2

TABLE OF CONTENTS

I. DIRECT DIGITAL CONTROL SYSTEM

1. GENERAL REQUIREMENTS

2. TECHNICIAN WORKSTATION

3. PROGRAMMING

4. EMCS PANEL

II. DIRECT DIGITAL CONTROL POINTS

1. MINIMUM POINTS LIST

2. GENERAL REQUIREMENTS

3. EXHAUST/SUPPLY FANS

4. AIR HANDLING UNITS – VAV BOX SYSTEM

5. AIR HANDLING UNITS – SINGLE ZONE

6. AIR HANDLING UNITS - THREE DECK MULTIZONE

7. AIR HANDLING UNITS - TWO DECK MULTIZONE

8. PACKAGE A/C UNITS – GAS HEATER

9. DEDICATED OUTDOOR AIR UNITS

10. TERMINAL UNITS – FAN COIL

11. TERMINAL UNITS – FAN POWERED VARIABLE AIR VOLUME

12. TERMINAL UNITS – VARIABLE AIR VOLUME

13. BOILER

14. CHILLER

15. DOMESTIC HW SYSTEM AND RECIRCULATING PUMP UNIT (MONITOR ONLY)

16. DOMESTIC WATER BOOSTER PUMP UNIT (MONITOR ONLY)

17. UTILITY METERS

III. DIRECT DIGITAL CONTROL GRAPHIC SCREENS

1. GENERAL REQUIREMENTS

2. TOP DISPLAY

3. OVERVIEW

4. FLOOR PLAN

5. AIR HANDLING UNITS – VAV BOX SYSTEM

6. AIR HANDLING UNITS – SINGLE ZONE

7. AIR HANDLING UNITS - THREE DECK MULTIZONE

8. ZONES - THREE DECK MULTIZONE

9. AIR HANDLING UNITS - TWO DECK MULTIZONE

10. ZONES - TWO DECK MULTIZONE

11. PACKAGED A/C UNITS - GAS HEATER

12. DEDICATED OUTDOOR AIR UNITS

13. TERMINAL UNITS – FAN COIL (WATER COIL HEATING/COOLING)

14. TERMINAL UNITS – FAN COIL (WATER COIL HEATING, DX COOLING, ECONOMIZER)

15. TERMINAL UNITS – FAN POWERED VARIABLE AIR VOLUME

16. TERMINAL UNITS – VARIABLE AIR VOLUME

17. BOILER

18. CHILLER

APPENDIX A

Page 3 Cannon Air Force Base September 2014

(BLANK PAGE)

September 2014 Cannon Air Force Base Page 4

I. Direct Digital Control System

1. General Requirements

1.1. A DDC system is required for any building that

has 10 tons of cooling or more whether in a single system or multiple systems combined.

1.2. Cannon AFB has received Air Force Special

Operations Command (AFSOC) authority to operate (ATO) Alerton hardware and Envision 2.0 software on existing base VLAN. These are the only systems that are currently authorized to connect to the base VLAN. All other proposed equipment and software shall receive ATO approval through AFSOC prior to installation.

1.3. The Installing Contractor shall complete and

submit an IP Address Request Form to Mr. Howard Blake 27 SOCES prior to installation of DDC system unless other arrangements are made with the Cannon AFB EMCS Technicians. The form shall be submitted utilizing an AF Form 3000.

1.4. All equipment (to include dampers) in the ceiling

space shall be labeled on the T-bars of the drop ceiling.

1.5. All T-stats shall be labeled with the equipment tag

of the unit it controls.

1.6. All navigation buttons shall be security level 5.

1.7. All data entry buttons and tickers shall be security

level 10.

2. Technician Workstation

2.1. Located in building 371.

2.2. The existing Base EMCS system front end software

and tools shall be able to fully customize device programming and be capable of sending changes to existing device programming and/or new programming for added devices to the DDC controllers located in the project building.

Microsoft Visio is currently used to create and send programs to building controllers. The proposed system shall utilize the graphical block programming offered by Visio to create and send new programs.

2.3. Communication with the Technician Workstation

and server (B355) shall be through existing Base VLAN using BACnet protocols in accordance with ASHRAE 135 BACnet Communication without the use of gateways or additional software.

2.4. MS/TP network settings shall be configured and/or

modified utilizing the existing software and tools installed to include device instances, network numbers, mac addresses and baud rate.

2.5. Automatic weekly updates shall be saved to the

existing server (B355).

2.6. Installing Contractor shall identify a Site Manager

for Cannon AFB. The Site Manager shall be the only one who has permission to upload new programs and graphics with supervision by the Cannon AFB EMCS Technicians.

2.7. All modifications to the existing Base EMCS system

software and hardware shall be done by technicians who are currently certified and trained.

The Contractor shall upload the current program and graphics being used prior to any work being done on existing building programs.

2.8. New programs shall be proofed by the Base EMCS

Technicians before being uploaded.

2.9. New programs shall be uploaded at least one week

prior to the final inspection of the project.

2.10. The Installing contractor shall meet with Cannon

AFB EMCS technicians prior to the building final to verify that there is connectivity to the Technician Workstation.

3. Programming

3.1. All systems shall be programmed with an

occupancy schedule. The installing contractor shall work with the user to determine and test an actual occupancy schedule before the final inspection.

3.2. The MS/TP Network # shall be the same as the

building number.

3.3. Each equipment item shall be described in the

device manager in the following format: Building #_Device #_Room #.

4. EMCS Panel

4.1. All demoed DDC controller of any manufacturer

shall be turned over the base EMCS Technicians.

4.2. All controllers shall be located in the mechanical

room of the building in a dedicated enclosure. The Building Control Module (BCM) shall be installed in a lockable panel that is keyed to match the current EMCS panel key used by the Base EMCS Technicians.

Page 5 Cannon Air Force Base September 2014

4.3. Each main piece of equipment shall have its own

dedicated controller(s) (AHU, Boiler, Chiller, etc.).

Each controller shall have 25% of inputs/outputs open (IN, AO, BO).

4.4. Ensure wire raceways are used inside the

enclosure and covers are in place to provide a neat and tidy organization of wires.

4.5. Install a standard electrical outlet if one does not

exist.

4.6. Provide controller termination diagram to depict

the controller and connected peripherals for easy trouble shooting. One copy shall be submitted with the O&M manuals and a second copy shall be mounted on the interior door of the panel.

4.7. Utilize wire labels to physically identify the wire

used for each peripheral.

4.8. CAT-6 cable shall be pulled from the patch panel

located in the communications room of the project building to the BCM in the mechanical room mounted in a dedicated enclosure.

September 2014 Cannon Air Force Base Page 6

II. Direct Digital Control Points

1. Minimum Points List

FANS

EXHAUST/SUPPLY AI BI AO BO ALARM

ON/OFF X

FAN STATUS - CURRENT (< 5HP) X

FAN STATUS - CURRENT SWITCH (≥ 5HP) X

FAN SPEED (≥ 5HP) X

AIR HANDLING UNITS

VAV BOX SYSTEM AI BI AO BO ALARM

SUPPLY FAN ON/OFF X

SUPPLY FAN STATUS - CURRENT (< 5HP) X

SUPPLY FAN STATUS - CURRENT SWITCH (≥ 5HP) X

SUPPLY FAN SPEED (≥ 5HP) X

SUPPLY AIR TEMPERATURE X

SUPPLY AIR STATIC PRESSURE X

SUPPLY AIR HIGH LIMIT STATIC PRESSURE X X

SUPPLY AIR FLOW X

SUPPLY AIR DUCT SMOKE (> 2000 CFM) X X

SUPPLY AIR RELATIVE HUMIDITY (IF REQUIRED) X

HUMIDIFIER SIGNAL (IF REQUIRED) X

RETURN FAN ON/OFF X

RETURN FAN STATUS - CURRENT (NO VFD) X

RETURN FAN STATUS - CURRENT SWITCH (VFD) X

RETURN FAN SPEED (SUPPLY FAN ≥ 5HP) X

RETURN AIR TEMPERATURE X

RETURN AIR DUCT SMOKE (IF NO AREA DETECTION SYSTEM) X X

RETURN AIR DAMPER POSITION X

RETURN AIR FLOW X

RETURN AIR CO2 X

RETURN AIR RELATIVE HUMIDITY (IF REQUIRED)

OUTSIDE AIR TEMPERATURE (ONE PER FACILITY) X

OUTSIDE AIR DAMPER POSITION X

OUTSIDE AIR FLOW X

OUTSIDE AIR CO2 X

RELIEF AIR DAMPER POSITION X

BUILDING PRESSURE X

MIXED AIR TEMPERATURE X

FILTER PRESSURE DIFFERENTIAL X X

COOLING VALVE POSITION X

HEATING VALVE POSITION X

LOW LIMIT TEMPERATURE (FREEZE STAT) X X

Page 7 Cannon Air Force Base September 2014

SINGLE ZONE AI BI AO BO ALARM

SPACE TEMPERATURE X

SUPPLY FAN ON/OFF X

SUPPLY FAN STATUS - CURRENT (< 5HP) X

SUPPLY FAN STATUS - CURRENT SWITCH (≥ 5HP) X

SUPPLY FAN SPEED (≥ 5HP) X

SUPPLY AIR TEMPERATURE X

SUPPLY AIR STATIC PRESSURE X

SUPPLY AIR HIGH LIMIT STATIC PRESSURE X X

SUPPLY AIR FLOW X

SUPPLY AIR DUCT SMOKE (> 2000 CFM) X X

RETURN FAN ON/OFF X

RETURN FAN STATUS - CURRENT (NO VFD) X

RETURN FAN STATUS - CURRENT SWITCH (VFD) X

RETURN FAN SPEED (SUPPLY FAN ≥ 5HP) X

RETURN AIR TEMPERATURE X

RETURN AIR DUCT SMOKE (IF NO AREA DETECTION

SYSTEM)

X X

RETURN AIR DAMPER POSITION X

RETURN AIR FLOW X

RETURN AIR CO2 X

OUTSIDE AIR TEMPERATURE (ONE PER FACILITY) X

OUTSIDE AIR DAMPER POSITION X

OUTSIDE AIR FLOW X

OUTSIDE AIR CO2 X

RELIEF AIR DAMPER POSITION X

BUILDING PRESSURE X

MIXED AIR TEMPERATURE X

FILTER PRESSURE DIFFERENTIAL X X

COOLING VALVE POSITION X

September 2014 Cannon Air Force Base Page 8

THREE DECK MULTIZONE AI BI AO BO ALARM

SPACE TEMPERATURE X

SUPPLY FAN ON/OFF X

SUPPLY FAN STATUS - CURRENT (< 5HP) X

SUPPLY FAN STATUS - CURRENT SWITCH (≥ 5HP) X

SUPPLY FAN SPEED (≥ 5HP) X

SUPPLY AIR TEMPERATURE (EACH ZONE) X

COLD DECK AIR TEMPERATURE X

HOT DECK AIR TEMPERATURE X

BYPASS DECK AIR TEMPERATURE X

SUPPLY AIR STATIC PRESSURE X

SUPPLY AIR HIGH LIMIT STATIC PRESSURE X X

SUPPLY AIR FLOW X

SUPPLY AIR DUCT SMOKE (> 2000 CFM) X X

RETURN FAN ON/OFF X

RETURN FAN STATUS - CURRENT (NO VFD) X

RETURN FAN STATUS - CURRENT SWITCH (VFD) X

X X

RETURN AIR DAMPER POSITION X

RETURN AIR FLOW X

RETURN AIR CO2 X

OUTSIDE AIR TEMPERATURE (ONE PER FACILITY) X

OUTSIDE AIR DAMPER POSITION X

OUTSIDE AIR FLOW X

OUTSIDE AIR CO2 X

RELIEF AIR DAMPER POSITION X

BUILDING PRESSURE X

MIXED AIR TEMPERATURE X

FILTER PRESSURE DIFFERENTIAL X X

BYPASS DAMPER POSITION X

MULTIZONE DAMPER POSITION (EACH ZONE) X

COOLING VALVE POSITION X

Page 9 Cannon Air Force Base September 2014

TWO DECK MULTIZONE AI BI AO BO ALARM

SPACE TEMPERATURE X

SUPPLY FAN ON/OFF X

SUPPLY FAN STATUS - CURRENT (< 5HP) X

SUPPLY FAN STATUS - CURRENT SWITCH (≥ 5HP) X

SUPPLY FAN SPEED (≥ 5HP) X

SUPPLY AIR TEMPERATURE (EACH ZONE) X

COLD DECK AIR TEMPERATURE X

HOT DECK AIR TEMPERATURE X

SUPPLY AIR STATIC PRESSURE X

SUPPLY AIR HIGH LIMIT STATIC PRESSURE X X

SUPPLY AIR FLOW X

SUPPLY AIR DUCT SMOKE (> 2000 CFM) X X

RETURN FAN ON/OFF X

RETURN FAN STATUS - CURRENT (NO VFD) X

RETURN FAN STATUS - CURRENT SWITCH (VFD) X

X X

RETURN AIR DAMPER POSITION X

RETURN AIR FLOW X

RETURN AIR CO2 X

OUTSIDE AIR TEMPERATURE (ONE PER FACILITY) X

OUTSIDE AIR DAMPER POSITION X

OUTSIDE AIR FLOW X

OUTSIDE AIR CO2 X

RELIEF AIR DAMPER POSITION X

BUILDING PRESSURE X

MIXED AIR TEMPERATURE X

FILTER PRESSURE DIFFERENTIAL X X

MULTIZONE DAMPER POSITION (EACH ZONE) X

COOLING VALVE POSITION X

September 2014 Cannon Air Force Base Page 10

PACKAGED A/C - GAS FURNACE AI BI AO BO ALARM

SPACE TEMPERATURE X

SUPPLY FAN ON/OFF X

SUPPLY FAN STATUS - CURRENT (< 5HP) X

SUPPLY FAN STATUS - CURRENT SWITCH (≥ 5HP) X

SUPPLY FAN SPEED (≥ 5HP) X

SUPPLY AIR TEMPERATURE X

SUPPLY AIR STATIC PRESSURE X

SUPPLY AIR HIGH LIMIT STATIC PRESSURE X X

SUPPLY AIR FLOW X

SUPPLY AIR DUCT SMOKE (> 2000 CFM) X X

RETURN FAN ON/OFF X

RETURN FAN STATUS - CURRENT (NO VFD) X

RETURN FAN STATUS - CURRENT SWITCH (VFD) X

X X

RETURN AIR DAMPER POSITION X

RETURN AIR FLOW X

RETURN AIR CO2 X

OUTSIDE AIR TEMPERATURE (ONE PER FACILITY) X

OUTSIDE AIR DAMPER POSITION X

OUTSIDE AIR FLOW X

OUTSIDE AIR CO2 X

RELIEF AIR DAMPER POSITION X

BUILDING PRESSURE X

MIXED AIR TEMPERATURE X

FILTER PRESSURE DIFFERENTIAL X X

CONDENSER ON/OFF X

COMPRESSOR STATUS - CURRENT (EACH COMPRESSOR) X

HEATER ON/OFF X

Page 11 Cannon Air Force Base September 2014

DEDICATED OUTDOOR AIR UNIT AI BI AO BO ALARM

SPACE TEMPERATURE X

SUPPLY FAN ON/OFF X

SUPPLY FAN STATUS - CURRENT (< 5HP) X

SUPPLY FAN STATUS - CURRENT SWITCH (≥ 5HP) X

SUPPLY FAN SPEED (≥ 5HP) X

SUPPLY AIR TEMPERATURE X

SUPPLY AIR STATIC PRESSURE X

SUPPLY AIR HIGH LIMIT STATIC PRESSURE X X

SUPPLY AIR FLOW X

SUPPLY AIR DUCT SMOKE (> 2000 CFM) X X

OUTSIDE AIR TEMPERATURE (ONE PER FACILITY) X

OUTSIDE AIR DAMPER POSITION X

OUTSIDE AIR FLOW X

RELIEF AIR DAMPER POSITION X

BUILDING PRESSURE X

FILTER PRESSURE DIFFERENTIAL X X

COOLING VALVE POSITION X

HUMIDITY CONTROL - ADD AI BI AO BO ALARM

SPACE RELATIVE HUMIDITY X

SUPPLY AIR RELATIVE HUMIDITY X

HUMIDIFIER SIGNAL X

TERMINAL UNITS - FAN COILS

FAN COIL AI BI AO BO ALARM

SPACE TEMPERATURE X

SUPPLY FAN ON/OFF X

SUPPLY FAN STATUS - CURRENT X

SUPPLY AIR TEMPERATURE X

SUPPLY AIR DUCT SMOKE (> 2000 CFM) X X

X X

OUTSIDE AIR TEMPERATURE (ONE PER FACILITY) X

FILTER PRESSURE TRANSMITTER X

WATER COOLING - ADD AI BI AO BO ALARM

COOLING VALVE POSITION X

DX COOLING - ADD AI BI AO BO ALARM

CONDENSER ON/OFF X

COMPRESSOR STATUS - CURRENT (EACH COMPRESSOR) X

September 2014 Cannon Air Force Base Page 12

WATER HEATING - ADD AI BI AO BO ALARM

HEATING VALVE POSITION X

GAS HEATING - ADD AI BI AO BO ALARM

FURNACE ON/OFF X

ECONOMIZER - ADD AI BI AO BO ALARM

SUPPLY AIR FLOW X

RETURN AIR TEMPERATURE X

RETURN AIR DAMPER POSITION X

RETURN AIR CO2 X

OUTSIDE AIR DAMPER POSITION X

OUTSIDE AIR FLOW X

OUTSIDE AIR CO2 X

RELIEF AIR DAMPER POSITION X

BUILDING PRESSURE X

MIXED AIR TEMPERATURE X

HUMIDITY CONTROL - ADD AI BI AO BO ALARM

SPACE RELATIVE HUMIDITY X

SUPPLY AIR RELATIVE HUMIDITY X

HUMIDIFIER SIGNAL X

TERMINAL UNITS VAV BOXES

FAN POWERED AI BI AO BO ALARM

SPACE TEMPERATURE X

DISCHARGE AIR TEMPERATURE X

DISCHARGE AIR FLOW X

DAMPER POSITION X

REHEAT VALVE POSITION X

FAN ON/OFF X

FAN CURRENT SENSOR X

STANDARD AI BI AO BO ALARM

SPACE TEMPERATURE X

DISCHARGE AIR TEMPERATURE X

DISCHARGE AIR FLOW X

DAMPER POSITION X

REHEAT VALVE POSITION X

Page 13 Cannon Air Force Base September 2014

BOILER

BOILER AND HW PUMP AI BI AO BO ALARM

BOILER ON/OFF X X

OUTSIDE AIR TEMPERATURE (ONE PER FACILITY) X

SUPPLY WATER TEMPERATURE X

DIFFERENTIAL PRESSURE ACROSS PUMP X

RETURN WATER TEMPERATURE X

WATER MIXING VALVE POSITION X

PUMP ON/OFF (EACH PUMP) X

PUMP STATUS - CURRENT (< 5HP) X

PUMP STATUS - CURRENT SWITCH (≥ 5HP) X

PUMP SPEED X

WATER FLOW X

BOILER INLET TEMPERATURE X

BOILER DISHARGE TEMPERATURE X

CHILLER

CHILLER AND CHW PUMP AI BI AO BO ALARM

CHILLER ON/OFF X X

OUTSIDE AIR TEMPERATURE (ONE PER FACILITY) X

COMPRESSOR STATUS - CURRENT (EACH COMPRESSOR) X

ISOLATION VALVE POSITION (IF MORE THAN ONE CHILLER) X

SUPPLY WATER TEMPERATURE X

DIFFERENTIAL PRESSURE ACROSS PUMP X

RETURN WATER TEMPERATURE SENSOR X

WATER MIXING VALVE POSITION X

PUMP ON/OFF (EACH PUMP) X

PUMP STATUS - CURRENT (< 5HP) X

PUMP STATUS - CURRENT SWITCH (≥ 5HP) X

PUMP SPEED X

WATER FLOW X

CHILLER INLET TEMPERATURE X

CHILLER DISCHARGE TEMPERATURE X

CONDENSING UNIT AI BI AO BO ALARM

COMPRESSOR ON/OFF X X

COMPRESSOR STATUS - CURRENT (EACH COMPRESSOR) X

September 2014 Cannon Air Force Base Page 14

2. General Requirements

2.1. As a minimum, the following systems shall be

provided with the indicated control points for monitoring and control of the HVAC systems installed.

2.2. Outside Air Temperature - Display air

temperature in °F. Sensor shall be mounted to the north facing exterior wall of the building at least 4” away from the wall surface and include shielding from direct sunlight.

2.3. Building pressure - Display building pressure in

iwc. Building pressure shall be used to control the relief damper.

2.4. A VFD is required for any motor greater than or

equal to 5 hp. If supply fan motor is large enough to have a VFD, the return fan (if equipped) shall also have a VFD regardless of size.

2.5. All penetrations through the exterior of the

building shall include a motorized actuator to close the opening in the event of an emergency shutdown.

2.6. The system shall be programed to default to heat

mode in the event of a power outage.

2.7. ATFP - Each facility shall have at least one

centrally located emergency HVAC shutdown button within 200 feet from any point in the building. When pressed, all fans in the building will disable and all exterior penetrations shall close. The EMCS front end software must also be capable of activating this feature remotely.

3. Exhaust/Supply Fans

3.1. On/Off - Fan shall be on or off as shown in design.

3.2. Fan Status (< 5HP) - Measure current through the

motor in amps.

3.3. Fan Status (≥ 5HP) - Detect current through the

motor with a switch.

3.4. Fan Speed (≥ 5HP) - Fan speed signal sent to the

VFD.

4. Air Handling Units – VAV Box System

4.1. Supply fan on/off: Fan shall be on unless disabled

due to alarm status of occupancy schedule.

4.2. Supply fan status (< 5HP) - Measure current

through the motor in amps.

4.3. Supply fan status (≥ 5HP) - Detect current

through the motor with a current switch.

4.4. Supply fan speed (≥ 5HP) - Fan speed shall

modulate to maintain the specified duct static pressure. A minimum supply power shall be set according to motor’s manufacturer suggested requirements.

4.5. Supply air temperature - A reset schedule shall be

programmed to provide 55°F (Adj) air when the highest cooling signal is 100% and provide 65°F (Adj) air when the highest cooling signal is below 100%.

4.6. Supply air static pressure - Measure duct pressure

in iwc. The VFD (if equipped) shall maintain the specified set-point (Adj).

4.7. Supply air high limit static pressure - When duct

pressure exceeds 4 iwc (Adj), disable the AHU utilizing the freeze stat sequence.

4.8. Supply air flow - Measure flow rate in units of

CFM.

4.9. Supply air duct smoke (> 2000cfm) - When

smoke is detected, disable the AHU utilizing the freeze stat sequence.

4.10. Return fan on/off (if equipped with return fan) -

Fan shall be interlocked with the supply fan and be on unless disabled due to alarm status of occupancy schedule.

4.11. Return fan status (No VFD) - Measure current

through the motor in amps.

4.12. Return fan status (VFD) - Detect current through

the motor with a current switch.

4.13. Return fan speed (Supply fan > 5HP) - Fan speed

shall modulate to track the supply air fan speed at 50% (Adj). A minimum supply power shall be set according to motor’s manufacturer suggested requirements.

4.14. Return air temperature - Measure air

temperature in °F.

4.15. Return air duct smoke - When smoke is detected, disable the AHU utilizing the freeze stat sequence.

4.16. Return air damper position - Shall modulate

opposite of the outside air damper through linkage or additional actuator.

4.17. Return air flow - Measure flow rate in units of

CFM.

4.18. Return air CO2 - Measure the CO2 level in ppm.

4.19. Outside air damper position - Link damper

control with return air damper to open/close opposite of each other. Outside air and return air damper positions shall modulate to maintain the supply air set-point in cooling mode only.

Two modes shall be available as described below.

Page 15 Cannon Air Force Base September 2014

4.19.1. Auto mode: 100% outside air shall be

enabled when the outside air temperature is less than the return air temperature. During unfavorable outside air conditions the outside air shall modulate to maintain a set CO2 differential (Adj) between the return and outside air.

4.19.2. Manual mode: 100% outside air shall be

enabled when the outside air temperature is less than OAT Manual High SP (Adj). During unfavorable outside air conditions the outside air damper shall open to the set minimum position (Adj).

4.20. Outside air flow - Measure flow rate in units of

CFM.

4.21. Outside air CO2 - Measure the CO2 level in ppm.

4.22. Relief air damper position - Damper shall

modulate to maintain the specified building pressure set-point (Adj).

4.23. Mixed air temperature - Measure air temperature

in °F.

4.24. Filter pressure differential (analog input) -

Measure pressure drop through the filter in iwc.

4.25. Cooling/Heating valve position - Valve shall

modulate to maintain supply air temperature.

4.26. Low limit temperature (freeze stat) - When the

heating coil discharge air temperature is below 35°F (Adj), disable the fans, close the outside and relief air dampers, open return air dampers and open heating valve.

5. Air Handling Units – Single Zone

5.1. Space temperature - Thermostat shall be installed

on an interior wall in the most central location. If a central location is not available, install thermostat near the return air diffuser for the space. Temperature set-points shall follow a facility specific occupancy schedule. Temperature set-points for occupied and unoccupied modes shall follow the most recent AFSOC Energy Policy.

5.2. Supply fan on/off - Fan shall operate three

different ways depending on the fan mode chosen on the front end software. (1) Fan shall run continuously. (2) Fan shall cycle with a call for heating. (3) Fan shall cycle with a call for heating or cooling.

5.3. Supply fan status (< 5HP) - Measure current

through the motor in amps.

5.4. Supply fan status (≥ 5HP) - Detect current

through the motor with a current switch.

5.5. Supply fan speed (≥ 5HP) - In “Continuous” mode

the fan shall reduce speed proportionally as the call for heating/cooling decreases. When the zone temperature is satisfied, the fan speed shall be at the motor manufacturer’s recommended minimum speed. In “Cycle Heating Only” mode the AHU shall shut down when the zone temperature is satisfied during heating only.

During cooling, the fan shall modulate speed as described in “Continuous” mode. In “Cycle Heating and Cooling” mode, the AHU shall shut down when the zone temperature is satisfied during heating and cooling.

5.6. Supply air temperature - Measure air temperature

in °F. A cooling reset schedule shall be programmed to provide 55°F (Adj) air when the cooling signal is 100% and provide 65°F (Adj) air when the cooling signal is below 100%. A heating reset schedule shall be programmed to provide 90°F (Adj) air when the heating signal is 100% and provide 80°F (Adj) air when the heating signal is below 100%.

5.7. Supply air static pressure - Measure duct pressure

in iwc. The VFD (if equipped) shall maintain the specified set-point (Adj).

5.8. Supply air high limit static pressure - When duct

pressure exceeds 4 iwc (Adj), disable the AHU utilizing the freeze stat sequence.

5.9. Supply air flow - Measure flow rate in units of

CFM.

5.10. Supply air duct smoke (> 2000cfm) - When

smoke is detected, disable the AHU utilizing the freeze stat sequence.

5.11. Return fan on/off (if equipped with return fan) -

Fan shall be interlocked with the supply fan and cycle in the same way as the supply fan.

5.12. Return fan status (No VFD) - Measure current

through the motor in amps.

5.13. Return fan status (VFD) - Detect current through

the motor with a current switch.

5.14. Return fan speed (Supply fan > 5HP) - Fan speed

shall modulate to track the supply air fan speed at 50% (Adj). A minimum supply power shall be set according to motor’s manufacturer suggested requirements.

5.15. Return air temperature - Measure air

temperature in °F.

September 2014 Cannon Air Force Base Page 16

5.16. Return air duct smoke - When smoke is detected, disable the AHU utilizing the freeze stat sequence.

5.17. Return air damper position - Shall modulate

opposite of the outside air damper through linkage or additional actuator.

5.18. Return air flow - Measure flow rate in units of

CFM.

5.19. Return air CO2 - Measure the CO2 level in ppm.

5.20. Outside air damper position - Link damper

control with return air damper to open/close opposite of each other. Outside air and return air damper positions shall modulate to maintain the supply air set-point in cooling mode only.

Two modes shall be available as described below.

5.20.1. Auto mode: 100% outside air shall be

enabled when the outside air temperature is less than the return air temperature. During unfavorable outside air conditions the outside air shall modulate to maintain a set CO2 differential (Adj) between the return and outside air.

5.20.2. Manual mode: 100% outside air shall be

enabled when the outside air temperature is less than OAT Manual High SP (Adj). During unfavorable outside air conditions the outside air damper shall open to the set minimum position (Adj).

5.21. Outside air flow - Measure flow rate in units of

CFM.

5.22. Outside air CO2 - Measure the CO2 level in ppm.

5.23. Relief air damper position - Damper shall

modulate to maintain the specified building pressure set-point (Adj).

5.24. Mixed air temperature - Measure air temperature

in °F.

5.25. Filter pressure differential (analog input) -

Measure pressure drop through the filter in iwc.

5.26. Cooling/Heating valve control - Valve shall

modulate to maintain supply air temperature.

5.27. Low limit temperature (freeze stat) - When the

heating coil discharge air temperature is below 35°F (Adj), disable the fans, close the outside and relief air dampers, open return air dampers and open heating valve.

6. Air Handling Units - Three Deck Multizone

6.1. Space temperature - Thermostat shall be installed

on an interior wall in the most central location in each zone. If a central location is not available, install thermostat near the return air diffuser for the space. Temperature set-points shall follow a facility specific occupancy schedule. Temperature set-points for occupied and unoccupied modes shall follow the most recent AFSOC Energy Policy.

6.2. Supply fan on/off - Fan shall be on unless disable

due to alarm status of occupancy schedule.

6.3. Supply fan status (< 5HP) - Measure current

through the motor in amps.

6.4. Supply fan status (≥ 5HP) - Detect current

through the motor with a current switch.

6.5. Supply fan speed (≥ 5HP) - Fan speed shall

modulate to maintain the specified fan box pressure. A minimum supply power shall be set according to motor’s manufacturer suggested requirements.

6.6. Supply air temperature - Measure air temperature

in °F for each zone. A cooling reset schedule shall be programmed to provide 55°F air when the highest cooling signal is 100% and provide 65°F air when the highest cooling signal is below 100%. A heating reset schedule shall be programmed to provide 90°F air when the highest heating signal is 100% and provide 80°F air when the highest heating signal is below 100%.

6.7. Cold deck air temperature - Measure air

temperature leaving the cooling coil in °F.

6.8. Hot deck air temperature - Measure air

temperature leaving the heating coil in °F.

6.9. Bypass deck air temperature - Measure air

temperature in °F.

6.10. Supply air static pressure - Measure static

pressure inside the fan box in iwc.

6.11. Supply air high limit static pressure - When duct

pressure exceeds 4 iwc (Adj), disable the AHU utilizing the freeze stat sequence.

6.12. Supply air flow - Measure flow rate in CFM for

each zone.

6.13. Supply air duct smoke - When smoke is detected, disable the AHU utilizing the freeze stat sequence.

6.14. Return fan on/off (if equipped with return fan) -

Fan shall be interlocked with the supply fan and cycle in the same way as the supply fan.

Page 17 Cannon Air Force Base September 2014

6.15. Return fan status (No VFD) - Measure current

through the motor in amps.

6.16. Return fan status (VFD) - Detect current through

the motor with a current switch.

6.17. Return fan speed (Supply fan > 5HP) - Fan speed

shall modulate to track the supply air fan speed at 50% (Adj). A minimum supply power shall be set according to motor’s manufacturer suggested requirements.

6.18. Return air temperature - Measure air

temperature in °F.

6.19. Return air duct smoke - When smoke is detected, disable the AHU utilizing the freeze stat sequence.

6.20. Return air damper position - Shall modulate

opposite of the outside air damper through linkage or additional actuator.

6.21. Return air flow - Measure flow rate in units of

CFM.

6.22. Return air CO2 - Measure the CO2 level in ppm.

6.23. Outside air damper position - Link damper

control with return air damper to open/close opposite of each other. Outside air and return air damper positions shall modulate to maintain the supply air set-point in cooling mode only.

Two modes shall be available as described below.

6.23.1. Auto mode: 100% outside air shall be

enabled when the outside air temperature is less than the return air temperature. During unfavorable outside air conditions the outside air shall modulate to maintain a set CO2 differential (Adj) between the return and outside air.

6.23.2. Manual mode: 100% outside air shall be

enabled when the outside air temperature is less than OAT Manual High SP (Adj). During unfavorable outside air conditions the outside air damper shall open to the set minimum position (Adj).

6.24. Outside air flow - Measure flow rate in units of

CFM.

6.25. Outside air CO2 - Measure the CO2 level in ppm.

6.26. Relief air damper position - Damper shall

modulate to maintain the specified building pressure set-point (Adj).

6.27. Mixed air temperature - Measure air temperature

in °F.

6.28. Filter pressure differential (analog input) -

Measure pressure drop through the filter in iwc.

6.29. Bypass damper position (if equipped) - Damper

shall modulate with the outside air damper.

6.30. Multizone damper position - shall modulate per

zone to ensure the cold deck damper is 0% open when a call for heating is present and the hot deck damper is 0% open when a call for cooling is present.

6.31. Cooling/Heating valve control - Valve shall

modulate to maintain cold/hot deck air temperature setpoint.

6.32. Low limit temperature (freeze stat) - When the

heating coil discharge air temperature is below 35°F (Adj), disable the fans, close the outside and relief air dampers, open return air dampers and open heating valve.

7. Air Handling Units - Two Deck Multizone

7.1. Space temperature - Thermostat shall be installed

on an interior wall in the most central location in each zone. If a central location is not available, install thermostat near the return air diffuser for the space. Temperature set-points shall follow a facility specific occupancy schedule. Temperature set-points for occupied and unoccupied modes shall follow the most recent AFSOC Energy Policy.

7.2. Supply fan on/off - Fan shall be on unless disable

due to alarm status of occupancy schedule.

7.3. Supply fan status (< 5HP) - Measure current

through the motor in amps.

7.4. Supply fan status (≥ 5HP) - Detect current

through the motor with a current switch.

7.5. Supply fan speed (≥ 5HP) - Fan speed shall

modulate to maintain the specified fan box pressure. A minimum supply power shall be set according to motor’s manufacturer suggested requirements.

7.6. Supply air temperature - Measure air temperature

in °F for each zone. A cooling reset schedule shall be programmed to provide 55°F air when the highest cooling signal is 100% and provide 65°F air when the highest cooling signal is below 100%. A heating reset schedule shall be programmed to provide 90°F air when the highest heating signal is 100% and provide 80°F air when the highest heating signal is below 100%.

September 2014 Cannon Air Force Base Page 18

7.7. Cold deck air temperature - Measure air

temperature leaving the cooling coil in °F.

7.1. Hot deck air temperature - Measure air

temperature leaving the heating coil in °F.

7.2. Supply air static pressure - Measure static

pressure inside the fan box in iwc.

7.3. Supply air high limit static pressure - When duct

pressure exceeds 4 iwc (Adj), disable the AHU utilizing the freeze stat sequence.

7.4. Supply air flow - Measure flow rate in CFM for

each zone.

7.5. Supply air duct smoke - When smoke is detected, disable the AHU utilizing the freeze stat sequence.

7.6. Return fan on/off (if equipped with return fan) -

Fan shall be interlocked with the supply fan and cycle in the same way as the supply fan.

7.7. Return fan status (No VFD) - Measure current

through the motor in amps.

7.8. Return fan status (VFD) - Detect current through

the motor with a current switch.

7.9. Return fan speed (Supply fan > 5HP) - Fan speed

shall modulate to track the supply air fan speed at 50% (Adj). A minimum supply power shall be set according to motor’s manufacturer suggested requirements.

7.10. Return air temperature - Measure air

temperature in °F.

7.11. Return air duct smoke - When smoke is detected, disable the AHU utilizing the freeze stat sequence.

7.12. Return air damper position - Shall modulate

opposite of the outside air damper through linkage or additional actuator.

7.13. Return air flow - Measure measured air flow

through return air duct in unit of CFM.

7.14. Return air CO2 - Measure the CO2 level in ppm.

7.15. Outside air damper position - Link damper

control with return air damper to open/close opposite of each other. Outside air and return air damper positions shall modulate to maintain the supply air set-point in cooling mode only.

Two modes shall be available as described below.

7.15.1. Auto mode: 100% outside air shall be

enabled when the outside air temperature is less than the return air temperature. During unfavorable outside air conditions the outside air shall modulate to maintain a set CO2 differential (Adj) between the return and outside air.

7.15.2. Manual mode: 100% outside air shall be

enabled when the outside air temperature is less than OAT Manual High SP (Adj). During unfavorable outside air conditions the outside air damper shall open to the set minimum position (Adj).

7.16. Outside air damper status - Measure damper

position percent provided by the feedback signal.

7.17. Outside air flow rate - Measure measured air flow

through outside air duct in units of CFM.

7.18. Outside air CO2 - Measure the CO2 level in ppm.

7.19. Relief air damper position - Damper shall

modulate to maintain the specified building pressure set-point (Adj).

7.20. Mixed air temperature - Measure air temperature

in °F.

7.21. Filter pressure differential (analog input) -

Measure pressure drop through the filter in iwc.

7.22. Multizone damper position - shall modulate

cold/hot deck dampers per zone to maintain zone supply air temperature.

7.23. Cooling/Heating valve control - Valve shall

modulate to maintain cold/hot deck air temperature setpoint.

7.24. Low limit temperature (freeze stat) - When the

heating coil discharge air temperature is below 35°F (Adj), disable the fans, close the outside and relief air dampers, open return air dampers and open heating valve.

8. Package A/C Units – Gas Heater

8.1. Space temperature - Thermostat shall be installed

on an interior wall in the most central location. If a central location is not available, install thermostat near the return air diffuser for the space. Temperature set-points shall follow a facility specific occupancy schedule. Temperature set-points for occupied and unoccupied modes shall follow the most recent AFSOC Energy Policy.

8.2. Supply fan on/off - Fan shall operate three

different ways depending on the fan mode chosen on the front end software. (1) Fan shall run continuously. (2) Fan shall cycle with a call for heating. (3) Fan shall cycle with a call for heating or cooling.

8.3. Supply fan status (< 5HP) - Measure current

through the motor in amps.

Page 19 Cannon Air Force Base September 2014

8.4. Supply fan status (≥ 5HP) - Detect current

through the motor with a current switch.

8.5. Supply fan speed (≥ 5HP) - In “Continuous” mode

the fan shall reduce speed proportionally as the call for heating/cooling decreases. When the zone temperature is satisfied, the fan speed shall be at the motor manufacturer’s recommended minimum speed. In “Cycle Heating Only” mode the AHU shall shut down when the zone temperature is satisfied during heating only.

During cooling, the fan shall modulate speed as described in “Continuous” mode. In “Cycle Heating and Cooling” mode, the AHU shall shut down when the zone temperature is satisfied during heating and cooling.

8.6. Supply air temperature - Measure air temperature

in °F.

8.7. Supply air static pressure - Measure duct pressure

in iwc. The VFD (if equipped) shall maintain the specified set-point (Adj).

8.8. Supply air flow - Measure flow rate in units of

CFM.

8.9. Supply air duct smoke (> 2000cfm) - When

smoke is detected, disable the AHU utilizing the freeze stat sequence.

8.10. Supply air high limit static pressure - When duct

pressure exceeds 4 iwc (Adj), disable the AHU utilizing the freeze stat sequence.

8.11. Return fan on/off (if equipped with return fan) -

Fan shall be interlocked with the supply fan and cycle in the same way as the supply fan.

8.12. Return fan status (No VFD) - Measure current

through the motor in amps.

8.13. Return fan status (VFD) - Detect current through

the motor with a current switch.

8.14. Return fan speed (Supply fan > 5HP) - Fan speed

shall modulate to track the supply air fan speed at 50% (Adj). A minimum supply power shall be set according to motor’s manufacturer suggested requirements.

8.15. Return air temperature - Measure air

temperature in °F.

8.16. Return air duct smoke - When smoke is detected, disable the AHU utilizing the freeze stat sequence.

8.17. Return air damper postion - Shall modulate

opposite of the outside air damper through linkage or additional actuator.

8.18. Return air flow - Measure flow rate in units of

CFM.

8.19. Return air CO2 - Measure the CO2 level in ppm.

8.20. Outside air damper position - Link damper

control with return air damper to open/close opposite of each other. Outside air and return air damper positions shall modulate to maintain the supply air set-point in cooling mode only.

Two modes shall be available as described below.

8.20.1. Auto mode: 100% outside air shall be

enabled when the outside air temperature is less than the return air temperature. During unfavorable outside air conditions the outside air shall modulate to maintain a set CO2 differential (Adj) between the return and outside air.

8.20.2. Manual mode: 100% outside air shall be

enabled when the outside air temperature is less than OAT Manual High SP (Adj). During unfavorable outside air conditions the outside air damper shall open to the set minimum position (Adj).

8.21. Outside air flow - Measure flow rate in units of

CFM.

8.22. Outside air CO2 - Measure the CO2 level in ppm.

8.23. Relief air damper position - Damper shall

modulate to maintain the specified building pressure set-point (Adj).

8.24. Mixed air temperature - Measure air temperature

in °F.

8.25. Filter pressure differential (analog input) -

Measure pressure drop through the filter in iwc.

8.26. Condenser on/off - Monitor on/off condition.

8.27. Compressor status - Measure current through

each compressor in amps.

8.28. Heater on/off - Monitor on/off condition.

8.29. Low limit temperature (freeze stat) - When the

heating coil discharge air temperature is below 35°F (Adj), disable the fans, close the outside and relief air dampers, open return air dampers and open heating valve.

September 2014 Cannon Air Force Base Page 20

9. Dedicated Outdoor Air Units

9.1. Space temperature - Thermostat shall be installed

on an interior wall in the most central location. If a central location is not available, install thermostat near the return air diffuser for the space. Temperature set-points shall follow a facility specific occupancy schedule. Temperature set-points for occupied and unoccupied modes shall follow the most recent AFSOC Energy Policy.

9.2. Supply fan on/off - Fan shall operate three

different ways depending on the fan mode chosen on the front end software. (1) Fan shall run continuously. (2) Fan shall cycle with a call for heating. (3) Fan shall cycle with a call for heating or cooling.

9.3. Supply fan status (< 5HP) - Measure current

through the motor in amps.

9.4. Supply fan status (≥ 5HP) - Detect current

through the motor with a current switch.

9.5. Supply fan speed (≥ 5HP) - In “Continuous” mode

the fan shall reduce speed proportionally as the call for heating/cooling decreases. When the zone temperature is satisfied, the fan speed shall be at the motor manufacturer’s recommended minimum speed. In “Cycle Heating” mode the AHU shall shut down when the zone temperature is satisfied during heating only. During cooling, the fan shall modulate speed as described in “Continuous” mode. In “Cycle Heating and Cooling” mode, the AHU shall shut down when the zone temperature is satisfied during heating and cooling.

9.6. Supply air temperature - Measure air temperature

in °F. A cooling reset schedule shall be programmed to provide 55°F (Adj) air when the cooling signal is 100% and provide 65°F (Adj) air when the cooling signal is below 100%. A heating reset schedule shall be programmed to provide 90°F (Adj) air when the heating signal is 100% and provide 80°F (Adj) air when the heating signal is below 100%.

9.7. Supply air static pressure - Measure duct pressure

in iwc. The VFD (if equipped) shall maintain the specified set-point (Adj).

9.8. Supply air high limit static pressure - When duct

pressure exceeds 4 iwc (Adj), disable the AHU utilizing the freeze stat sequence.

9.9. Supply air flow - Measure flow rate in units of

CFM.

9.10. Supply air duct smoke (> 2000cfm) - When

smoke is detected, disable the AHU utilizing the freeze stat sequence.

9.11. Outside air damper position - Outside air shall

modulate with supply fan speed.

9.12. Outside air flow - Measure flow rate in units of

CFM.

9.13. Relief air damper position - Damper shall

modulate to maintain the specified building pressure set-point (Adj).

9.14. Filter pressure differential (analog input) -

Measure pressure drop through the filter in iwc.

9.15. Cooling/Heating valve position - Valve shall

modulate to maintain supply air temperature.

9.16. Low limit temperature (freeze stat) - When the

heating coil discharge air temperature is below 35°F (Adj), disable the fans, close the outside and relief air dampers, open return air dampers and open heating valve.

10. Terminal Units – Fan Coil

10.1. Space temperature - Thermostat shall be installed

on an interior wall in the most central location. If a central location is not available, install thermostat near the return air diffuser for the space. Temperature set-points shall follow a facility specific occupancy schedule. Temperature set-points for occupied and unoccupied modes shall follow the most recent AFSOC Energy Policy.

10.2. Supply fan on/off - Fan shall operate three

different ways depending on the fan mode chosen on the front end software. (1) Fan shall run continuously. (2) Fan shall cycle with a call for heating. (3) Fan shall cycle with a call for heating or cooling.

10.3. Supply fan status - Measure current through the

motor in amps.

10.4. Supply air temperature - Measure air temperature

in °F. A cooling reset schedule shall be programmed to provide 55°F (Adj) air when the cooling signal is 100% and provide 65°F (Adj) air when the cooling signal is below 100%. A heating reset schedule shall be programmed to provide 90°F (Adj) air when the heating signal is 100% and provide 80°F (Adj) air when the heating signal is below 100%.

Page 21 Cannon Air Force Base September 2014

10.5. Supply air duct smoke (> 2000cfm) - When

smoke is detected, disable the AHU utilizing the freeze stat sequence.

10.6. Return air duct smoke - When smoke is detected, disable the AHU utilizing the freeze stat sequence.

10.7. Filter pressure differential (analog input) -

Measure pressure drop through the filter in iwc.

10.8. Water cooling (add)

10.8.1. Cooling valve position - Valve shall

modulate to maintain supply air temperature.

10.9. DX cooling (add)

10.9.1. Condenser on/off - Monitor on/off

condition.

10.9.2. Compressor status - Measure current

through each compressor in amps.

10.10. Water heating (add)

10.10.1. Heating valve position - Valve shall

modulate to maintain supply air temperature.

10.11. Gas heating (add)

10.11.1. Furnace on/off - furnace shall cycle to

maintain supply air temperature.

10.12. Economizer (add)

10.12.1. Supply air flow - Measure flow rate in

units of CFM.

10.12.2. Return air temperature - Measure air

temperature in °F.

10.12.3. Return air damper control - Shall

modulate opposite of the outside air damper through linkage or additional actuator.

10.12.4. Return air CO2 - Measure the CO2 level

in ppm.

10.12.5. Outside air damper position - Link

damper control with return air damper to open/close opposite of each other. Outside air and return air damper positions shall modulate to maintain the supply air set-point in cooling mode only. Two modes shall be available as described below.

10.12.5.1. Auto mode: 100% outside air

shall be enabled when the outside air temperature is less than the return air temperature. During unfavorable outside air conditions the outside air shall modulate to maintain a set CO2 differential (Adj) between the return and outside air.

10.12.5.2. Manual mode: 100% outside air

shall be enabled when the outside air temperature is less than OAT Manual High SP (Adj). During unfavorable outside air conditions the outside air damper shall open to the set minimum position (Adj).

10.12.6. Outside air flow - Measure flow rate in

units of CFM.

10.12.7. Outside air CO2 - Measure the CO2 level

in ppm.

10.12.8. Relief air damper position - Damper shall

modulate to maintain the specified building pressure set-point (Adj).

10.12.9. Mixed air temperature - Measure air

temperature in °F.

10.13. Humidity control (add)

10.13.1. Space relative humidity - Measure space

humidity percentage.

10.13.2. Supply air relative humidity - Measure

supply air humidity percentage.

10.13.3. Humidifier signal - Humidifier shall

modulate to maintain space humidity setpoint (Adj).

11. Terminal Units – Fan Powered Variable Air Volume

11.1. Space temperature - Thermostat shall be installed

on an interior wall in the most central location. If a central location is not available, install thermostat near the return air diffuser for the space. Temperature set-points shall follow a facility specific occupancy schedule. Temperature set-points for occupied and unoccupied modes shall follow the most recent AFSOC Energy Policy.

11.2. Discharge air temperature - Measure air

temperature in °F.

11.3. Discharge air flow - Measure air flow in CFM.

11.4. Damper position- Modulate between the

minimum set-point and 100% open to maintain space temperature. During heat mode, damper shall be 100% closed.

11.5. Reheat valve position - Valve shall open upon a

call for heating.

11.6. Fan on/off - Fan shall be enabled with a call for

heating.

11.7. Fan status - Detect current through the motor

with a current switch.

September 2014 Cannon Air Force Base Page 22

12. Terminal Units – Variable Air Volume

12.1. Space temperature - Thermostat shall be installed

on an interior wall in the most central location. If a central location is not available, install thermostat near the return air diffuser for the space. Temperature set-points shall follow a facility specific occupancy schedule. Temperature set-points for occupied and unoccupied modes shall follow the most recent AFSOC Energy Policy.

12.2. Discharge air temperature - Measure air

temperature in °F.

12.3. Discharge air flow - Measure air flow in CFM.

12.4. Damper position - Modulate between the

minimum set-point and 100% open to maintain space temperature.

12.5. Reheat valve position - Valve shall open upon a

call for heating.

13. Boiler

13.1. Boiler on/off - The boiler shall be enabled at 60°F

(Adj) and below.

13.2. Supply water temperature - Measure water

temperature supplying the heating coils in °F. A hot water reset schedule shall be programmed to provide 180°F (Adj) water when outside air temperatures are 32°F (Adj) and below. When outside air temperatures are between 32°F (Adj) and 60°F (Adj) the hot water supply temperature shall be reset to 90°F (Adj).

13.3. Differential pressure across pump - Measure the

differential pressure between supply and return.

13.4. Return water temperature - Measure water

temperature in °F going into the pump.

13.5. Water mixing valve position - Valve shall

modulate to maintain the supply water temperature as required by the reset schedule.

13.6. Pump on/off - Pump shall enable when boiler is

operating to circulate hot water through either the heating coils or the bypass.

13.7. Pump status (< 5HP) - Measure current through

the motor in amps.

13.8. Pump status - (≥ 5HP) - Detect current through

the motor with a current switch.

13.9. Pump speed (≥ 5HP) - Modulate pump speed to

maintain the design pressure differential between the supply side and return side of the pump. If a VFD is used, no balancing valve is required.

13.10. Water flow - Measure water flow rate in GPM.

13.11. Boiler inlet temperature - Measure water

temperature in °F going into the boiler.

13.12. Boiler discharge temperature - Measure water

temperature in °F going out the boiler.

13.13. Boiler water level - Measure water level of the

boiler if equipped with a water holding chamber.

13.14. Flame indicator - Detect presence of a flame.

14. Chiller

14.1. Chiller on/off - The chiller shall be enabled when

the outside air temperature is above 60°F (Adj).

14.2. Compressor status - Measure current through

each compressor.

14.3. Isolation valve position - If multiple chillers are

used, open/close isolation valve for the active/inactive chiller.

14.4. Supply water temperature - Measure water

temperature supplying the cooling coils in °F.

14.5. Differential pressure across pump - Measure the

differential pressure between supply and return.

14.6. Return water temperature - Display water

temperature in °F.

14.7. Water mixing valve position - Valve shall

modulate to maintain the supply water temperature as required by the reset schedule.

14.8. Pump on/off - Pump shall enable when chiller is

operating to circulate chilled water through either the cooling coils or the bypass. The system shall monitor the temperature sensors for the chiller discharge, chiller return, CHWS (in mechanical room), and CHWR (in mechanical room) and if any one temperature sensor reads 33°F or below, the system shall cycle the chilled water pumps.

14.9. Pump status (< 5HP) - Measure current through

the motor in amps.

14.10. Pump status - (≥ 5HP) - Detect current through

the motor with a current switch.

14.11. Pump speed (≥ 5HP) - Modulate pump speed to

maintain the design pressure differential between the supply side and return side of the pump. If a VFD is used, no balancing valve is required.

14.12. Water flow - Measure water flow rate in GPM.

14.13. Chiller inlet temperature - Measure water

temperature in °F going into the chiller.

14.14. Chiller discharge temperature - Measure water

temperature in °F going out the chiller.

14.15. Chiller interface - Display available information

gathered from the onboard controller.

Page 23 Cannon Air Force Base September 2014

15. Condensing Unit

15.1. Compressor on/off - Monitor on/off condition of

each compressor.

15.2. Compressor status - Measure current through

each compressor in amps.

16. Domestic HW System and Recirculating Pump Unit (monitor only)

16.1. Pump on/off - Display bright green/red button if

pump motor is on/off.

16.2. Pump status - Display bright green/red button if

the current sensor does/does not detect current running through the pump motor.

16.3. Return water temperature - Display measured

water…