54"Ø SPIRAL DUCT
MECHANICAL CONTRACTOR SHALL
FURNISH AND INSTALL 5'-0x5'-0x9" DEEP
PLENUM OVER 48" SQUARE OPENING. SEAL
AIR TIGHT AND CONNECT NEW 54"Ø
SPIRAL DUCT AS SHOWN. (TYPICAL 6 PLACES)
EF-4
6'-0"X6'-0"
EXHAUST LOUVER
30,000 CFM
FLEX. CONN.
(TYPICAL)
EXIST. ROOF
RETRO ROOF
BUILDING 932 ADDITION - SECTION
1/8" = 1'-0"
INFRARED HEATER TUBE INFRARED HEATER TUBE
M1 M2 A
FIRE DAMPER
INTERLOCK
DD - DIRECT DRIVE
BD - BELT DRIVE
DESCRIPTION
EXT. S.P.
APPROX.
INCH WATER
UNIT
NO.
AIR
CFM
TOTAL
AT 5'
SONES
FREE AIR
FAN
SPEED
R.P.M.
MAX.
CONTROL
PHASEMOTOR
H.P.
MAX.
VOLTS HZ. REMARKS
FAN SCHEDULE
EF-1
EF-2
DD - CENTRIFUGAL
ROOF EXHAUSTER225 0.375 5.4 1,150 60120 1
CONTRACTOR
ELECTRICAL
W/LIGHT
SWITCH
BIRDSCREEN, ROOF CURB FOR SLOPED ROOF AND UL LISTING.
FAN SPEED CONTROL FIELD MOUNTED TO FAN CABINET, DISCONNECT SWITCH,
EQUAL TO GREENHECK MODEL G-095-D COMPLETE WITH BACKDRAFT DAMPER,
BD - PROPELLER
WALL EXHAUSTER40,000 0.75 56.0 620 60480 3
SWITCH
START-
STOP 10
AND UL LISTING. SEE NOTE.
DAMPER, WALL COLLAR, OSHA APPROVED FAN SAFETY GUARD, DISCONNECT SWITCH
EQUAL TO GREENHECK MODEL SBE-3H60-100 COMPLETE WITH BACKDRAFT
N.T.S.
SMALL BRANCH SPLITTER
DAMPER DETAIL
M.V.D.
MAIN TRUNK DUCT
L = 1/4 W (4" MIN.)
"W" TAKE OFF
BRANCH DUCT
"L"
SQUARE DUCT ELBOW WITH
TURNING VANES
MAIN BRANCH SPLITTER
(SEE DETAIL)
OR
MECHANICAL LEGEND
SPIN-IN FITTING
DIRECTION OF THROW
EXHAUST REGISTER
CEILING RETURN OR
SPLITTER (SEE DETAIL)
SMALL BRANCH DUCT
CEILING DIFFUSER
FLEXIBLE ROUND DUCT
DIRECTION (UP OR DOWN)
INDICATES CHANGE IN
RIGID ROUND PIPE
W/ DAMPER
HP-1
O.S.A.
R.A.
T
EF-1
S.A.
THERMOSTAT
HEAT PUMP UNIT NO.
OUTSIDE AIR
RETURN AIR
EXHAUST FAN NO.
SUPPLY AIR
MOTORIZED DAMPER
MANUAL BALANCING DAMPER
DETAIL - WALL MOUNTED EXHAUST FAN
N.T.S.
GRAVITY SHUTTER
FASTEN FAN HOUSING SECURELY
STEEL WALL SLEEVE
16 GAGE GALVANIZED
EXHAUST FAN
TO WALL SLEEVE
4"MIN.
8"
WALL LOUVER
SEE PLANS
SPLIT SYSTEM HEAT PUMP SCHEDULE
MINIMUM
CIRCUIT
AMPS
OUTDOOR SECTION OF HEAT PUMP
NO.
COMPR
OF
AMPS
RLA
COMPRESSOR
AMPS
FLA
FANS
NO.
OF
O.D. FANS
VOLT
POWER SUPPLY
MAXIMUM
AMPS
FUSE PHASE HZ
REMARKS
TEMP.
ENT.
ELECTRIC HEATER DATA
TEMP.
ENT.
REVERSE CYCLE HEATING
HEATING
B.T.U.H.
F F
TEMP.
AMB.
C.O.P.
MIN.
MINIMUM
HEATING
B.T.U.H.
CAPACITY F
INDOOR SECTION POWER SUPPLY
NUMBER
F
TEMP.
LVG.
STAGES
OF
MINIMUM
CIRCUIT
208V
K.W.
TOTAL
AMPS
PHASE
MAXIMUM
AMPS
FUSE VOLT HZ
UNIT
NO.
MIN.
TOTAL
AIR
CFM
AIR
CFM
OUT.
ENT AIR F
D.B.
MOTOR
TYPE
MAX.
TYPE
UNITAIR
CFM
OUT.
FAN
UNIT FAN
APPROX.
EXT S.P.
INCHES
2H 0 H.P.
FAN MIN. CAPACITY
B.T.U.H.
TOTAL
COOLING DATA
MAX COIL
FACE VEL
F.P.M. B.T.U.H.
SENSIBLE
W.B. S.E.E.R.
MIN.
INDOOR SECTION OF HEAT PUMP
MINIMUM
CAPACITY NO.
UNIT
7.5 208 6016053.8125,598 52.9 79.7 SINGLE POINT CONNECTION AND VIBRATION ISOLATORS.
WITH HEAT PUMP COIL, ELECTRIC HEAT ACCESSORY WITH
INDOOR SECTION CARRIER MODEL FV4BNF003 COMPLETE
OUTDOOR SECTION EQUAL TO CARRIER MODEL 25HNB530.
HP-1HP-1 250 VERT. F.C.D. T. 0.50 1/2 500875 250 1208 601 18.514.1 EACH
0.9
30115.5 70.0 47.0 3.8681.1 69.329,340 19,000 28,630
CD CEILING DIFFUSER
CRR CEILING RETURN REGISTER
EF-3
EF-4
DD - PROPELLER
INLINE EXHAUSTER30,000 1.0 84 dba 1,170 60480 3
SWITCH
START-
STOP 15
CONNECTIONS, CEILING SUSPENSION KIT, VIBRATION ISOLATORS AND UL LISTING.
OUTLET COMPANION FLANGES, DISCONNECT SWITCH, INLET AND OUTLET FLEX DUCT
EQUAL TO GREENHECK MODEL AX-103-275-0633-B15 COMPLETE WITH INLET AND
EF-9
THRU
INFRARED HEATER SCHEDULE
TAG LOCATION DESCRIPTION
MAX.
INPUT
(MBH)
TUBE
LENGTH TUBE MATERIAL FUEL
ELECTRICAL DATA MANUFACTURER AND MODEL
NUMBER (AS STANDARD) REMARKS
V PH HZ FLA
IR-1 BLDG. 932 INFRARED HEATER 100 45' 4" Ø BLACK COATED
ALUMINIZED STEEL
NAT
GAS 120 1 60 0.7 DETROIT RADIANT HLV-100 SEE NOTES
IR-2 BLDG. 932 INFRARED HEATER 100 60' 4" Ø BLACK COATED
ALUMINIZED STEEL 120 1 60 0.7 DETROIT RADIANT HLV-100 SEE NOTES
IR-3 BLDG. 932 INFRARED HEATER 100 60' 4" Ø BLACK COATED
ALUMINIZED STEEL
120 1 60 0.7 DETROIT RADIANT HLV-100 SEE NOTES
IR-4 BLDG. 932 INFRARED HEATER 100 45' 4" Ø BLACK COATED
ALUMINIZED STEEL
120 1 60 0.7 DETROIT RADIANT HLV-100 SEE NOTES
IR-5 BLDG. 932 INFRARED HEATER 100 50' 4" Ø BLACK COATED
ALUMINIZED STEEL
120 1 60 0.7 DETROIT RADIANT HLV-100 SEE NOTES
NOTES:
VACUUM PUMP SCHEDULE (INFRARED HEAT)
TAG LOCATION DESCRIPTION HP RPM v PH HZ FLA
MANUFACTURER AND MODEL
NUMBER (AS STANDARD) REMARKS
VP-1 thru 3 BLDG. 932 VACUUM PUMP .50 3450 120 1 60 7.4 DETROIT RADIANT HLV-PB8 SEE NOTES
NOTES:
NAT
GAS
NAT
GAS
NAT
GAS
NAT
GAS
1. REFER TO SPECIFICATIONS, DETAILS, AND CONTROL DRAWINGS FOR ADDITIONAL INFORMATION.
2. VERIFY TUBE LENGTH IN FIELD PRIOR TO ORDERING.
3. MIN. 11 IN. WCg.
4. FURNISH COMPLETE WITH ALUMINUM REFLECTORS, STAINLESS STEEL BURNER, MOUNTING CHAINS, FLEXIBLE GAS CONNECTOR AND GAS SHUT-OFF.
5. MOUNT AS HIGH AS POSSIBLE PER MANUFACTURER'S RECOMMENDATION.
1. REFER TO SPECIFICATIONS, DETAILS, AND CONTROL DRAWINGS FOR ADDITIONAL INFORMATION.
2. FURNISH COMPLETE WITH PRIMARY DAMPER, ISOLATION BOOTS, VIBRATION ISOLATORS AND CONTROL PANEL.
1/8
NOTE: INTERLOCK EF-2 AND EF-3 WITH RESPECTIVE MOTORIZED INTAKE DAMPER. MOTERIZED DAMPERS SHALL OPEN PRIOR TO EXHAUST FAN OPERATION.
CAPE