Attachment 3 Specifications Dated 2/21/2012 26 05 73.00 40 OVERCURRENT PROTECTIVE DEVICES

View the file

Other files

File Type Posted
Questions and Answers of FBO.pdf PDF
amendment 3.pdf PDF
amendment 2.pdf PDF
Sign in sheet.pdf PDF
C101.pdf PDF
QUESTION FORM.doc DOC document
Amendment 1.doc DOC document
32 16 13 CONCRETE SIDEWALKS AND CURBS AND GUTTERS.doc DOC document
05 05 23 WELDING STRUCTURAL.doc DOC document
32 92 23 SODDING.doc DOC document
08 81 00 GLAZING.doc DOC document
A-10.pdf PDF
23 23 00 REFRIGERANT PIPING.doc DOC document
01 35 29 SAFETY AND OCCUPATIONAL HEALTH REQUIREMENTS.doc DOC document
C102.pdf PDF
26 41 01.00 10 LIGHTNING PROTECTION SYSTEM.doc DOC document
Solicitation.doc DOC document
08 11 13 STEEL DOORS AND FRAMES .doc DOC document
07 11 13 BITUMINOUS DAMPPROOFING.doc DOC document
26 24 16.00 40 PANELBOARDS.doc DOC document
E5.pdf PDF
23 00 00 AIR SUPPLY DISTRIBUTION VENTILATION AND EXHAUST.doc DOC document
33 30 00 SANITARY SEWERS.doc DOC document
10 26 13 WALL AND CORNER GUARDS.doc DOC document
Demo Plan2-Layout2.pdf PDF
m2.pdf PDF
02 41 00 DEMOLITION AND RECONSTRUCTION.doc DOC document
A-1.pdf PDF
31 60 00 FOUNDATION PREPARATION.doc DOC document
08 51 23 STEEL WINDOWS.doc DOC document
28 05 26.00 40 GROUNDING AND BONDING FOR ELECTRONIC SAFETY A.doc DOC document
E4 —
03 15 13 00 10 EXPANSION JOINTS CONTRACTION JOINTS AND WAT.doc DOC document
08 71 00 DOOR HARDWARE.doc DOC document
03 20 01.00 10 CONCRETE REINFORCEMENT.doc DOC document
Attach 1 Building Wage Determination.docx DOCX document
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM.doc DOC document
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS.doc DOC document
FP02.pdf PDF
A-9.pdf PDF
A-4.pdf PDF
sow.pdf PDF
E9.pdf PDF
A-5.pdf PDF
27 05 28.36 40 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS.doc DOC document
27 21 10.00 10 FIBER OPTIC DATA TRANSMISSION SYSTEM.doc DOC document
E6 —
26 51 00 INTERIOR LIGHTING.doc DOC document
X-1.pdf PDF
A-3.pdf PDF
Show 40 more

Latest 50 of 146 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Copies of the design calculat***************************************************************************

USACE / NAVFAC / AFCESA / NASA UFGS-26 05 73.00 40 (July 2007) Preparing Activity: NASA Superseding UFGS-26 05 73.00 40 (July 2006)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated October 2007

SECTION 26 05 73.00 40

OVERCURRENT PROTECTIVE DEVICES

NOTE: This specification covers the requirements for circuit breakers, fuses, motor controls, and control devices. This section supports Section 26 27 26.00 40 WIRING DEVICES,Section 26 24 16.00 40 PANELBOARDS, Section 26 24 19.00 40 MOTOR-CONTROL CENTERS, and Section 33 75 00.00 40 HIGH-VOLTAGE SWITCHGEAR AND PROTECTION DEVICES; accordingly, it should be included to the extent applicable to project requirements. Drawings should show frame and trip ratings, interrupting ratings, and NEMA types and sizes, as well as single-line and schematic diagrams, elevations, and details.

Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.

Remove information and requirements not required in respective project, whether or not brackets are present.

Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of the specification. A listing of technical proponents, including their organization designation and telephone number, is on the Internet.

Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).

PART 1 GENERAL

1.1 REFERENCES

NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.

Use the Reference Wizard's Check Reference feature when you add a RID outside of the Section's Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizard's Check Reference feature to update the issue dates.

References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.

1.1.1 The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only. Unless other wise noted, the latest published version and/or revision shall be used.

1.1.1.1 AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

a. ANSI C63.2 Standard for Electromagnetic Noise and Field Strength Instrumentation, 10 KHz to 40 GHz – Specifications

b. ANSI C63.4 Methods of Measurement of Radio - Noise Emissions from Low-Voltage Electrical and Electronic Equipment in the Range of 9 KHz to 40 GHz

1.1.2 ASTM INTERNATIONAL (ASTM)

a. ASTM A 167-99 Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip

b. ASTM A 48 Standard Specification for Gray Iron Castings

c. ASTM D 3487 Standard Specification for Mineral Insulating Oil Used in Electrical Apparatus

d. ASTM D 877 Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes

1.1.3 ELECTRONIC INDUSTRIES ALLIANCE (EIA)

a. EIA 443 Standard for Solid-State Relay Service, EIA/NARM

1.1.4 INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

a. IEEE C37.09 IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis

b. IEEE C37.121 American National Standard for Switchgear Unit Substations Requirements

c. IEEE C37.13 Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures

d. IEEE C37.16 Recommendations for Low-Voltage Power Circuit Breakers and AC Power Circuit Protectors, - Preferred Ratings, Related Requirements, and Application

e. IEEE C37.17 Standard for Trip Devices for AC and General-Purpose DC Low-Voltage Power Circuit Breakers

f. IEEE C37.90 Standard for Relays and Relay Systems Associated With Electric Power Apparatus

g. IEEE C57.13 Standard Requirements for Instrument Transformers

1.1.5 IPI - ASSOCIATION CONNECTING ELECTRONICS INDUSTRIES (IPC)

a. IPC D330 Switches

1.1.6 NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

a. NEMA 107 Methods of Measurement of Radio Influence Voltage (RIV) of High-Voltage Apparatus

b. NEMA 250 Enclosures for Electrical Equipment (1000 Volts Maximum)

c. NEMA AB 1 Molded-Case Circuit Breakers, Molded Case Switches, and Circuit-Breaker Enclosures

d. NEMA AB 3 Molded Case Circuit Breakers and Their Application

e. NEMA C12.1 Electric Meters; Code for Electricity Metering

f. NEMA C78.23 Standard for Incandescent Lamps - Miscellaneous Types

g. NEMA FU 1 Low Voltage Cartridge Fuses

h. NEMA ICS 1 Standard for Industrial Control and Systems General Requirements

i. NEMA ICS 2 Standard for Industrial Control and Systems: Controllers, Contractors, and Overload Relays Rated Not More than 2000 Volts AC or 750 Volts DC: Part 8 - Disconnect Devices for Use in Industrial Control Equipment

j. NEMA ICS 3 Standard for Industrial Control and Systems: Medium Voltage Controllers Rated 2001 to 7200 Volts AC

k. NEMA ICS 6 Standard for Industrial Controls and Systems Enclosures

l. NEMA SG 2 Standard for High-Voltage Fuses

1.1.7 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

a. NFPA 70 National Electrical Code

1.1.8 UNDERWRITERS LABORATORIES (UL)

a. UL 20 Standard for General-Use Snap Switches

b. UL 489 Standard for Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures

c. UL 50 Standard for Enclosures for Electrical Equipment

d. UL 508 (1999; Rev thru Jul 2005) Standard for Industrial Control Equipment

1.2 SUBMITTALS

NOTE: Review Submittal Description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the project. Submittals should be kept to the minimum required for adequate quality control.

A “G” following a submittal item indicates that the submittal requires Government approval. Some submittals are already marked with a “G”. Only delete an existing “G” if the submittal item is not complex and can be reviewed through the Contractor’s Quality Control system. Only add a “G” if the submittal is sufficiently important or complex in context of the project.

For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the "G" designation to indicate the approving authority. Codes for Army projects using the Resident Management System (RMS) are: "AE" for Architect-Engineer; "DO" for District Office (Engineering Division or other organization in the District Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project Office. Codes following the "G" typically are not used for Navy, Air Force, and NASA projects.

Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects.

1.2.1 Government approval may be required on any of the following items. Items requiring submittals will be listed on the AF Form 66. Provide copies of all submittals per the requirements in Section 01 33 00, Submittal Procedures, or as listed on the AF Form 66.

1.2.1.1 SD-01 Preconstruction Submittals

a. No change in continuous-current rating, interrupting rating, and clearing or melting time of fuses shall be made unless written permission has first been secured from the Contracting Officer.

1.2.1.2 SD-02 Shop Drawings

a. Connection Diagrams and Fabrication Drawings shall be submitted for the following items in accordance with paragraph entitled, "General Requirements," of this section.

b. Installation drawings shall also be submitted for the following items in accordance with the paragraph entitled, "Installation," of this section.

(1) Control Devices

(2) Protective Devices

1.2.1.3 SD-03 Product Data

a. Equipment and performance data shall be submitted for the following items including use life, system functional flows, safety features, and mechanical automated details.

b. Manufacturer's catalog data shall also be submitted for the following items:

(1) Motor Control

(2) Instrument Transformers

(3) Enclosures

(4) Circuit Breakers

(5) Fuses

(6) Control Devices

(7) Time Switches

(8) Protective Relays

(9) Indicating Instruments

(10) Indicating Lights

1.2.1.4 SD-06 Test Reports

a. Factory Test Reports shall be submitted for Power, High Voltage, and Oil Circuit Breakers in accordance with IEEE C37.09.

(1) Dielectric Tests

(2) Timing Test

(3) Insulation Power Factor Test

1.2.1.5 SD-07 Certificates

a. Certificates shall be submitted for Circuit Tests on similar motor-control or motor-circuit protector (MCP) units under actual conditions may be submitted in lieu of factory tests on the actual units provided.

1.2.1.6 SD-08 Manufacturer's Instructions

a. Manufacturer's Instructions shall be submitted for the following items, including special provisions required to install equipment components and system packages. Special notices shall detail, resistance impedances, hazards and safety precautions.

(1) Control Devices

(2) Protective Devices

1.2.1.7 SD-10 Operation and Maintenance Data

a. Operation and Maintenance Manuals shall be submitted for the following equipment:

(1) Manual Motor Controllers

(2) Magnetic Motor Controllers

(3) Combination Motor Controllers

(4) High Voltage Motor Controllers

(5) Circuit Breakers

(6) Time Switches

(7) Protective Relays

(8) Indicating Instruments

1.3 GENERAL REQUIREMENTS

NOTE: If Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS is not included in the project specification, applicable requirements therefrom should be inserted and the following paragraph deleted.

1.3.1 Section 26 00 00.00 20 Basic Electrical Materials and Methods applies to work specified in this section.

1.3.2 Connection Diagrams shall be submitted showing the relations and connections of control devices and protective devices by showing the general physical layout of all controls, the interconnection of one system (or portion of system) with another, and internal tubing, wiring, and other devices.

1.3.3 Fabrication Drawings shall be submitted for control devices and protective devices consisting of fabrication and assembly details to be performed in the factory.

PART 2 PRODUCTS

2.1 MOTOR CONTROL

2.1.1 Motor controllers shall conform to NEMA ICS 1, NEMA ICS 2, and UL 508. Controllers shall have thermal overload protection in each phase.

2.1.2 Manual Motor Controllers

2.1.2.1 Manual motor controllers for the control and protection of single-phase 60-hertz ac small wattage rating (fractional-horsepower) squirrel-cage induction motors shall be full-voltage, manually operated devices.

2.1.2.2 Controllers shall be single-throw, single- or double-pole, three-position devices rated not more than 750 watt rated( 1 horsepower) at 115- and 230-volts single phase. Controller shall include a supporting base or body of electrical insulating material with enclosed switching mechanism, yoke, thermal overload relay, and terminal connectors. Controllers shall clearly indicate operating condition: on, off, or tripped.

2.1.2.3 Manual motor controllers shall be the toggle- or key-operated type as indicated and shall be arranged so that they may be locked with a padlock in the "OFF" position.

2.1.2.4 Recessed manual motor controllers for single-speed, small wattage rating( fractional-horsepower) squirrel-cage induction motors shall include a single controller and indicating light in a (4-inch) square wall outlet box for flush-wiring devices with matching corrosion-resistant steel flush cover plate. Surface-mounted manual motor controllers for single-speed, small wattage rating (fractional-horsepower) squirrel cage induction motors shall include a single controller and indicating light in a NEMA enclosure suitable for the environment.

2.1.2.5 Recessed and surface-mounted manual motor controllers for two-speed, small wattage rating( fractional-horsepower) squirrel-cage induction motors shall include two controllers, two indicating lights, and a selector switch in a multiple-gang wall outlet box for flush-wiring devices with matching corrosion-resistant steel flush-cover plate. Surface-mounted manual motor controllers for two-speed small wattage rating (fractional-horsepower) squirrel-cage induction motors shall include two controllers, two indicating lights, and a selector switch in a NEMA enclosure suitable for the environment.

2.1.3 Magnetic Motor Controllers

2.1.3.1 Full-Voltage Controllers

a. Magnetic motor controllers for the control and protection of single- and three-phase, 60-hertz, squirrel-cage induction motors shall be full-voltage, full magnetic devices in accordance with NEMA ICS 1, NEMA ICS 2, and UL 508.

b. Operating coil assembly shall operate satisfactorily between 85 and 110 percent of rated coil voltage.

c. Controller shall be provided with two normally open and two normally closed auxiliary contacts rated per NEMA ICS 1 and NEMA ICS 2 in addition to the sealing-in contact for control circuits.

d. Solderless pressure wire terminal connectors shall be provided for line-and load-connections to controllers.

e. Overcurrent protection shall include three manual reset thermal overload devices, one in each pole of the controller. Thermal overload relays shall be bimetallic nonadjustable type with continuous current ratings and service-limit current ratings and shall have a plus or minus 15 percent adjustment to compensate for ambient operating conditions.

f. An externally operable manual-reset button shall be provided to re-establish control power to the holding coil of the electromagnet. After the controller has tripped from overload, resetting the motor-overload device shall not restart the motor.

g. Enclosure shall be in accordance with NEMA suitable for the environment.

2.1.3.2 Reduced-Voltage Starters

a. Reduced-voltage starters shall conform to the requirements for full-voltage controllers, except for voltage, and to the following additional requirements.

b. Overload devices, one in each motor leg, shall fully protect the motor during all phases of motor starting. Starter contacts shall be rated to withstand the switching surges during selector to full voltage. Starter shall contain the necessary sensing and timing devices to monitor motor operation and select the correct time for selector to full voltage.

c. Resistors and autotransformers used for starting shall be adequately ventilated. Solid-state starters shall be ventilated for starting cycles as well as any follow-on restart-run cycles. External control circuits or solid-state starters shall operate at 120 volts ac, maximum.

d. For solid-state starters, starting torque shall be adjustable from 0 to 50 percent of applied voltage, minimum. Autotransformer starters shall have a minimum of three taps above 50 percent reduced voltage.

2.1.3.3 Combination Motor Controllers

a. Following requirements are in addition to the requirements specified for magnetic motor controller:

(1) Combination motor controllers for the control and protection of single-and three-phase 60-hertz alternating-current squirrel-cage induction motors with branch-circuit disconnecting and protective devices shall be in accordance with NEMA ICS 1, NEMA ICS 2, and NEMA ICS 6.

(2) Combination motor controllers shall include magnetic motor controllers and molded-case circuit breakers or MCP in metal enclosures in accordance with NEMA 250 or motor-control center draw-out assemblies with control-power transformers, selector switches, pushbuttons, and indicating lights as follows:

(a) Magnetic motor controllers and enclosures shall be full-voltage, full-magnetic devices as specified in this section under paragraph entitled, "Remote-Control Station Enclosures."

(b) Molded-case circuit breakers shall be thermal-magnetic breakers as specified in paragraph entitled, "Manual Motor Controllers." Manufacturer's standard MCP may be used in lieu of molded-case circuit breakers.

(c) Control-power transformers (120-volt ac maximum selector switches), pushbuttons, and pilot lights shall be as required.

(d) Combination motor controllers shall be identified with identification plates affixed to front cover of the controller.

2.1.3.4 Nonreversing Combination Motor Controllers

NOTE: Nonreversing, reversing, and two-speed combination motor controllers should be selected from the following paragraphs to suit the project requirements.

a. Following requirements are in addition to the requirements for magnetic motor controllers:

b. Nonreversing combination motor controllers for the control and protection of single-speed squirrel-cage induction motors shall include a magnetic controller with molded-case circuit breaker or MCP with selector switch or start/stop pushbutton and indicating light in the cover of the enclosure.

c. Rating of single and three-phase single-speed full-voltage magnetic controllers for non-plugging and non-jogging duty shall be in accordance with NEMA ICS 1 and NEMA ICS 2.

d. Wiring and connections for full-voltage single-speed magnetic controllers shall be in accordance with NEMA ICS 1 and NEMA ICS 2.

2.1.3.5 Reversing Combination Motor Controllers

a. Following requirements are in addition to the requirements for magnetic motor controllers:

(1) Reversing combination motor controllers for the control and protection of single-speed squirrel-cage induction motors shall include two interlocked magnetic controllers with molded-case circuit breaker or MCP, with selector switch or forward/reverse/stop pushbutton and two indicating lights in the cover of the enclosure. Indicating lights shall indicate the forward and reverse running connection of the motor controller.

(2) Rating of single and three-phase single-speed full-voltage magnetic controllers for plug-stop, plug-reverse, or jogging duty shall be in accordance with NEMA ICS 1 and NEMA ICS 2.

(3) Wiring and connections for full-voltage single-speed magnetic controllers shall be in accordance with NEMA ICS 1 and NEMA ICS 2.

2.1.3.6 Two-Speed Combination Motor Controllers

a. Following requirements are in addition to the requirements for magnetic motor controllers:

(1) Two-speed combination motor controllers for the control and protection of single- and two-winding, two-speed, three-phase, squirrel-cage induction motors shall include two magnetic controllers with molded-case circuit breaker or MCP, with selector switch or fast/slow/stop pushbutton and two indicating lights in the cover of the enclosure. Indicating lights shall indicate the high- and low-speed running connection of the motor controller.

(2) Rating of three-phase, two-speed, full-voltage, magnetic controllers for non-plugging and non-jogging duty for constant- and variable-torque motors shall be in accordance with NEMA ICS 1 and NEMA ICS 2.

(3) Rating of three-phase, two-speed, full-voltage, magnetic controllers for non-plugging and nonjogging duty for constant-motors (horsepower) motors shall be in accordance with NEMA ICS 1 and NEMA ICS 2.

(4) Rating of three-phase, two-speed, full-voltage, magnetic controllers for plug-stop, plug-reverse, or jogging duty for constant-torque, variable-torque, and constant wattage (horsepower) motors shall be in accordance with NEMA ICS 1 and NEMA ICS 2.

2.1.4 High-Voltage Motor Controllers

2.1.4.1 High-voltage motor controllers for the control and protection of squirrel-cage induction motors, wound-rotor induction motors, and synchronous machines rated 2.4 through 7.2 kilovolts, three-phase, shall be NEMA ICS 2, Class E2, type as required.

2.1.4.2 Unless enclosed within a switchgear or unit-substation cubicle, high-voltage motor controllers shall be housed in floor-mounted structures of the NEMA type indicated, approximately (90 inches) high, (30 inches) wide, and (30 inches) deep, with suitable draw-out compartments. Structure shall include provisions for padlocking the doors.

2.1.4.3 Structure shall be subdivided into low-voltage control compartment with separate door, high-voltage control compartment with separate door, ac bus compartment, and cable-entrance compartment.

2.1.4.4 Controller shall be isolated by externally operated draw-out stabs with shutter mechanism. Isolating device shall also open the secondary of the control-power transformer. Interlocks shall be provided to prevent inadvertent operation of the isolating mechanism under load, opening the medium-voltage compartment door without isolating the starter, and closing the line contactor with door open. An isolating switch assembly shall be included.

2.1.4.5 For overload protection, ambient-compensated thermal overload relays, hand reset, shall be included in all three phases. Solid-state multifunction overload protection may be utilized when approved.

2.1.4.6 Controllers shall be the fused type employing current-limiting power fuses of the interrupting rating indicated. Single-phase antitrip protection shall be provided. Starters shall employ magnetic air-break line contactors rated not less than 5 kilovolts. Control circuit shall have provisions for external testing of 120-volt control circuit and a minimum of one set of normally open and normally closed auxiliary contacts.

2.2 INSTRUMENT TRANSFORMERS

2.2.1 Instrument transformers shall comply with the interference requirements listed below, measured in accordance with ANSI C63.2, ANSI C63.4, and NEMA 107.

Preferred Radio Influence

Basic Nominal Test Voltage Test Voltage Voltage Level, Insulation Insulation System for Potential for Current Microvolts Class, Level, Voltage, Transformers, Transformers, Dry Oil kV kV kV kV kV Type Filled

0.6 10 0.76

1.2 30

0.208 0.132 0.76

0.416 0.264

0.832 0.528

1.04 0.66

2.5 45

2.40 1.52 1.67 250 250

5.0 60

4.16 2.64 3.34 250 250

4.80 3.04

8.7 75 7.20 4.57 5.77 250 250

8.32 5.28

15L or 15H 95-110

12.00 7.62 9.41

12.47 7.92

14.40 9.14

25 150

23.00 14.60 15.70

34.5 200

34.50 21.90 23.0

46 250

46.00 29.20 29.30

69 350

69.00 43.80 44.00

92 450

92.00 58.40 58.40

115 550

115.00 73.40 73.40 138.00 88.00 88.00

2.2.2 Current Transformers

2.2.2.1 Current transformers shall conform to IEEE C57.13 for installation in metal-clad switchgear.

2.2.2.2 Transformers shall be wound, bushing, bar or window type, as appropriate.

2.2.2.3 Transformers shall have single or double secondary winding as appropriate.

2.2.2.4 Transformers shall be complete with secondary short-circuiting device.

2.2.2.5 Window-type current transformers shall be indoor dry type construction with secondary current ratings as indicated. Burden, frequency, and accuracy shall be as specified.

2.2.3 Potential Transformers

2.2.3.1 Potential transformers shall conform to IEEE C57.13 for installation in metal-clad switchgear.

2.2.3.2 Transformers shall have single secondary.

2.2.3.3 Burden, frequency, and accuracy shall be as required.

2.2.3.4 Disconnecting potential transformers with integral fuse mountings and current-limiting fuses shall be indoor dry type two-winding construction with primary and secondary voltage ratings as required.

2.3 ENCLOSURES

2.3.1 Equipment Enclosures

2.3.1.1 Enclosures for equipment shall be in accordance with NEMA 250.

2.3.1.2 Equipment installed inside, clean, dry locations shall be contained in NEMA Type 1, general-purpose sheet-steel enclosures.

2.3.1.3 Equipment installed in wet locations shall be contained in NEMA Type 4 watertight, corrosion-resistant sheet-steel enclosures, constructed to prevent entrance of water when tested in accordance with NEMA ICS 6 for Type 4 enclosures.

2.3.1.4 Equipment installed in industrial locations shall be contained in NEMA Type 12 industrial use, sheet-steel enclosures constructed to prevent the entrance of dust, lint, fibers, filings, oil, and coolant seepage.

2.3.1.5 Equipment installed in Class I, Division I, Group A, B, C, and D, hazardous locations shall be contained in NEMA Type 7 enclosures approved for the specific flammable gas or vapor which is or may be present under normal operating conditions.

2.3.1.6 Equipment installed in Class II, Division I, Group E, F and G, hazardous locations shall be contained in NEMA Type 9 enclosures approved for use where combustible dust is or may be present under normal operating conditions.

2.3.1.7 Sheet-steel enclosures shall be fabricated from uncoated carbon-steel sheets of commercial quality, with box dimensions and thickness of sheet steel in accordance with UL 50.

2.3.1.8 Steel enclosures shall be fabricated from corrosion-resistant, chromium-nickel steel sheet conforming to ASTM A 167 Type 300 series with ASM No. 4 general-purpose polished finish. Box dimensions and thickness of sheet steel shall be in accordance with UL 50.

2.3.1.9 Cast-iron enclosures shall be gray-iron castings conforming to ASTM A 48 with tensile-strength classification recognized as suitable for the application. Cast-metal enclosures shall be not less than (1/8-inch) thick at every point, of greater thickness at reinforcing ribs and door edges, and not less than (1/4-inch) thick at tapped holes for conduits.

2.4 CIRCUIT BREAKERS

2.4.1 Circuit breakers shall conform to UL 489, NEMA AB 1, and NEMA AB 3.

2.4.2 Molded-Case Circuit Breakers

2.4.2.1 Circuit breakers shall be molded case, manually operated, trip-free, with inverse-time thermal-overload protection and instantaneous magnetic short-circuit protection as required. Circuit breakers shall be completely enclosed in a molded case, with the calibrated sensing element factory-sealed to prevent tampering.

2.4.2.2 Thermal-magnetic tripping elements shall be located in each pole of the circuit breaker and shall provide inverse-time-delay thermal overload protection and instantaneous magnetic short-circuit protection. Instantaneous magnetic tripping element shall be adjustable and accessible from the front of the breaker on frame sizes larger than 100 amperes.

2.4.2.3 Breaker size shall be as required for the continuous current rating of the circuit. Breaker class shall be as required.

2.4.2.4 Interrupting capacity of the panel and lighting branch circuit breakers shall be sufficient to successfully interrupt the maximum short-circuit current imposed on the circuit at the breaker terminals. Circuit breaker interrupting capacities shall be a minimum of 10,000 amperes and shall conform to NEMA AB 3.

2.4.2.5 Multipole circuit breakers shall be of the common-trip type having a single operating handle and shall a have two-position on/off indication. Circuit breakers shall have temperature compensation for operation in an ambient temperature of (104 degrees F). Circuit breakers shall have root mean square (rms) symmetrical interrupting ratings sufficient to protect the circuit being supplied. Interrupting ratings may have selective type tripping (time delay, magnetic, thermal, or ground fault).

2.4.2.6 Breaker body shall be of phenolic composition. Breakers shall be capable of having such accessories as handle-extension, handle-locking, and padlocking devices attached where required.

2.4.2.7 Circuit breakers used for motor-circuit disconnects shall meet the applicable requirements of NFPA 70 and shall be of the motor-circuit protector type.

2.4.2.8 Circuit breakers used for service disconnection shall be the enclosed circuit-breaker type with external handle for manual operation. Enclosures shall be sheet metal with a hinged cover suitable for surface mounting.

2.4.3 Enclosed Molded-Case Circuit Breakers

2.4.3.1 Enclosed circuit breakers shall be thermal-magnetic molded-case circuit breakers in surface-mounted, non-ventilated enclosures conforming to the appropriate articles of NEMA 250 and NEMA AB 1.

2.4.4 Power Circuit Breakers

NOTE: Specify when or where breakers equipped with current-limiting fuses shall be installed and requirements for coordination with other system protective devices.

Edit breaker description to suit project requirements.

2.4.4.1 Power circuit breakers rated below 600 volts shall be the air-break type enclosed in ventilated housings. Current, voltage, and interrupting ratings shall be as required.

2.4.4.2 Power circuit breakers shall comply with IEEE C37.16 and IEEE C37.13.

2.4.4.3 Power circuit breakers shall be equipped with electromechanical or static trip (solid-state) devices as appropriate with long-time or short-time instantaneous elements. Breakers shall be electrically and mechanically trip-free in any position of the closing stroke. Ground fault protection shall be included in either type trip device. Main contacts shall be silver-plated. Arcing contacts shall be sintered tungsten alloy. Tripping shall be accomplished by a shunt-trip device. Closing shall be by manual or electrical operation as appropriate.

2.4.4.4 Breakers installed in metal housings such as unit substations shall be the drawout type. Breakers installed in isolated locations or not as units of a central distribution center shall be wall-mounted, provided a correctly ventilated protective metal cover is installed.

2.4.4.5 Alarms, auxiliary switches, interlocks, and similar devices shall be supplied.

2.4.4.6 Breakers shall have a removable operating handle, provision for padlocking, and position indicator.

2.4.4.7 Power Circuit Breakers shall be factory tested in accordance with IEEE C37.09.

2.4.5 Air Circuit Breakers

2.4.5.1 Circuit breakers shall include a ground-fault system or ground-sensing relays.

2.4.5.2 Stored-Energy-Operated Type

a. Air circuit breakers with stored-energy-operated mechanisms shall conform to IEEE C37.121 for metal-clad switchgear.

b. Metal-clad air circuit breakers shall be mounted on a mobile frame with primary and secondary disconnecting devices, automatic shutters, and mechanical interlocks to allow complete removal of the unit for inspection and maintenance. Circuit breakers shall be three-pole, single-throw, electrically operated, with a motor-charged spring, stored-energy mechanism, and electric release coils for tripping and closing operations.

c. A motor-operated position-changing mechanism shall be provided that will move the breaker between the test and operating position by means of a levering device. Interlocks shall be provided to prevent the complete withdrawal of the circuit breaker from its compartment when the stored-energy mechanism is in the fully charged position. Circuit breakers shall be designed to prevent the release of stored energy unless the mechanism is fully charged.

d. Circuit breakers shall have mechanically trip-free mechanisms with direct-current potential trip coils of the voltage indicated, auxiliary switches, latch-checking switches, control relays, and operation counters.

2.4.5.3 Solenoid-Operated Type

a. Air circuit breakers with solenoid-operated mechanisms shall conform to IEEE C37.121 and the appropriate articles for metal-clad switchgear.

b. Metal-clad air circuit breakers shall be mounted on a mobile frame with primary and secondary disconnecting devices, automatic shutters, and mechanical interlocks to allow complete removal of the unit for inspection and maintenance. Circuit breakers shall be three-pole single-throw, with solenoid-operated tripping/closing mechanism designed for operation on a direct-current station battery power supply.

c. Mechanism closing coils shall be rated 125 volts and shall be operable at voltages as low as 90 volts. Mechanism trip coils shall be rated 125 volts and shall be operable at voltages as low as 70 volts. Operating mechanism for ac control circuits shall be as provided by the manufacturer.

d. Circuit breakers shall be mechanically trip-free mechanisms with auxiliary switches, latch-checking switches, control relays, and operation counters. Solid-state tripping devices may be used.

2.4.6 Oil Circuit Breakers

2.4.6.1 Oil circuit breakers shall use control voltage as indicated. Tripping mechanism shall consist of a magnet acting as a trigger to release a latch, permitting the breaker to open. A pneumatic operating system shall be provided with compressors and reservoirs as needed. Tripping/closing control shall be integrally provided with the breakers.

2.4.6.2 Distribution-voltage breakers shall be three phase with all three interrupters mounted in the same tank. Transmission-voltage oil circuit breakers shall have the phase interrupters mounted in separate tanks.

2.4.6.3 Circuit-breaker bushings shall be equipped with bushing current transformers and shall have standard secondary taps. Taps shall be terminated outside the tank housing on terminal blocks and shall be identified for short circuiting.

2.4.6.4 Operating mechanism shall be enclosed in a waterproof housing mounted on the breaker framework. Heaters shall be provided to prevent condensation of moisture. Breaker mechanism shall be mechanically trip-free.

2.4.6.5 Each breaker shall be equipped with complete relaying and controls. Relaying shall consist of instantaneous and overcurrent time-delay relays plus others as indicated. Controls shall consist of a reclosing relay, control switch, indicating lights, ammeters, and as approved. Relays and controls shall be installed in a control cabinet mounted on the breaker housing (and may be solid-state type) or shall be installed remotely. An externally operable manual trip device shall be provided.

2.4.6.6 Each oil circuit breaker shall be supplied with tank-lowering and tank-lifting devices. Where applicable, a tank drain valve and an oil level indicator shall be provided on each tank.

2.4.6.7 Oil for oil circuit breakers shall conform to ASTM D 3487.

2.4.6.8 Oil circuit breakers shall be factory tested in accordance with IEEE C37.09

2.5 FUSES

2.5.1 A complete set of fuses for all switches and switchgear shall be provided. Fuses shall have a voltage rating not less than the circuit voltage.

2.5.2 Fuses rated 30 amperes, 125 volts or less shall be the nonrenewable cartridge type. Fuses rated above 30 amperes 600 volts or less shall be the renewable cartridge type with time-delay dual elements, except where otherwise indicated. Fuses shall conform to NEMA FU 1.

2.5.3 Special fuses such as extra-high interrupting-capacity fuses, fuses for welding machines, and capacitor fuses shall be installed where required. Plug fuses are not permitted.

2.5.4 Power fuses on ac systems above 600 volts shall be in accordance with NEMA SG 2.

2.5.5 Fuses shall be labeled showing UL class, interrupting rating, and time-delay characteristics, when applicable. Additionally, fuse information shall be clearly listed on equipment drawings.

2.5.6 Fuse holders field-mounted in a cabinet or box shall be porcelain. Field installation of fuse holders made of such materials as ebony asbestos, Bakelite, or pressed fiber shall not be used.

2.6 CONTROL DEVICES

2.6.1 Magnetic Contactors

2.6.1.1 Magnetic contactors for the control of low-voltage, 60-hertz, tungsten-lamp loads, fluorescent-lamp loads, resistance-heating loads, and the primary windings of low-voltage transformers shall be in accordance with NEMA ICS 1 and NEMA ICS 2 as required.

2.6.1.2 Core-and-coil assembly shall operate satisfactorily with coil voltage between 85 and 110 percent of its voltage rating.

2.6.1.3 Contactor shall be designed with a normally open holding circuit auxiliary contact for control circuits. Rating of the auxiliary contact shall be in accordance with NEMA ICS 1 and NEMA ICS 2.

2.6.1.4 Solderless pressure wire terminal connectors shall be furnished or made available for line-and-load connections to contactors in accordance with NEMA ICS 1 and NEMA ICS 2.

2.6.1.5 Rating of magnetic contactors shall be in accordance with NEMA ICS 1and NEMA ICS 2.

2.6.2 Control-Circuit Transformers

2.6.2.1 Control-circuit transformers shall be provided within the enclosure of magnetic contactors and motor controllers when the line voltage is in excess of 120 volts. Transformer shall be encapsulated dry type, single-phase, 60-hertz, with a 120-volt (or 24-volt) isolated secondary winding.

2.6.2.2 Rated primary voltage of the transformer shall be not less than the rated voltage of the controller. Rated secondary current of the transformer shall be not less than continuous-duty current of the control circuit.

2.6.2.3 Voltage regulation of the transformer shall be such that, with rated primary voltage and frequency, the secondary voltage shall not be less than 95 percent nor more than 105 percent of rated secondary voltage.

2.6.2.4 Source of supply for control-circuit transformers shall be the load side of the main disconnecting device. Secondary winding of the transformer and control-circuit wiring shall be protected against overloads and short circuits with fuses selected in accordance with NEMA ICS 6. Secondary winding of the control-circuit transformer shall be grounded in accordance with NEMA ICS 6.

2.6.3 Magnetic Control Relays

2.6.3.1 Magnetic control relays for energizing and de-energizing the coils of magnetic contactors or other magnetically operated devices in response to variations in the conditions of electric control devices shall be in accordance with NEMA ICS 1, and NEMA ICS 2.

2.6.3.2 Core-and-coil assembly shall operate satisfactorily with coil voltages between 85 and 110 percent of their voltage rating.

2.6.3.3 Relays shall be designed to accommodate normally open and normally closed contacts.

2.6.3.4 Magnetic control relays shall be Class AIB devices with a continuous contact rating of 10 amperes and with current-making and -breaking ability in accordance with NEMA ICS 1 and NEMA ICS 2, two normally open and two normally closed.

2.6.4 Pushbuttons and Switches

NOTE: Specify electrically held, magnetic latch, plug-in, or hermetically sealed.

2.6.4.1 Pushbuttons

a. Pushbuttons for low-voltage ac full-voltage magnetic controllers shall be heavy-duty oiltight NEMA 250, Type 12, momentary-contact devices rated 600 volts, with pilot light, and with the number of buttons and the marking of identification plates as shown. Color code for pushbuttons shall be in accordance with NEMA ICS 6.

b. Pushbuttons shall be designed with normally open, circuit-closing contacts; normally closed circuit-opening contacts; and two-circuit normally open and normally closed circuit-closing and -opening contacts. Pushbutton-contact ratings shall be in accordance with NEMA ICS 1 and NEMA ICS 2 with contact designation A600.

c. Pushbuttons in remote control stations shall be identified with identification plates affixed to front cover in a prominent location. Identification plate shall carry the identification of the system being controlled.

2.6.4.2 Selector Switches

a. Selector switches for low-voltage control circuits shall be heavy-duty oiltight maintained-contact devices with the number of positions and the marking of identification plates in accordance with NEMA ICS 1 and NEMA ICS 2.

b. Selector switches in remote control stations shall be identified with engraved identification plates affixed to front cover in a prominent location. Identification plate shall carry the identification of the system being controlled.

2.6.4.3 Ammeter Selector Switches

a. Ammeter selector switches for switchgear shall be rotary multistage snap-action type in accordance with UL 20 with silver-plated contacts rated for 600 volts ac or dc. Selector switch shall be a manually operated, four-position device rated for 600 volts, 20 amperes, minimum, and designed to permit current readings on each bus of the main bus from a single indicating instrument. Ammeter switch shall be mounted on the hinged front panel of the switchgear compartment and shall be completely isolated from high-voltage circuits, with engraved escutcheon plate.

b. Selector switch handle shall be oval type.

2.6.4.4 Voltmeter Selector Switches

a. Voltmeter selector switches for switchgear shall be rotary snap-action type in accordance with UL 20 with silver-plated contacts rated for 600 volts ac or dc. Switch shall be a manually operated, four-position device designed to permit voltage readings on each phase of the main bus from a single indicating instrument. Voltmeter switch shall be mounted on the hinged front panel of the switchgear compartment and shall be completely isolated from high-voltage circuits, and with engraved escutcheon plate.

b. Selector switch handle shall be oval type.

2.6.4.5 Miscellaneous Switches

a. Float, limit, door, pressure, proximity, and other types of switches shall be in accordance with IPC D330 and of the types and classes indicated.

2.7 PROTECTIVE RELAYS

2.7.1 Overcurrent Relays

2.7.1.1 Overcurrent relays shall conform to IEEE C37.90.

2.7.1.2 Overcurrent relays for protection against phase and ground faults shall be single-phase nondirectional removable induction type with built-in testing facilities. Relays shall be designed for operation on the dc or ac control circuit indicated.

2.7.1.3 Ground-fault overcurrent relays shall have short-time inverse time characteristics with adjustable current tap range as required.

2.7.1.4 Phase-fault overcurrent relays shall have varied inverse-time characteristics with adjustable current tap range as required and indicating instantaneous-trip attachments with adjustable current range as required.

2.7.1.5 Case shall be semiflush-mounted to the hinged instrument panel and shall have matching cover.

2.7.1.6 Solid-state static-type trips for low-voltage power circuit breakers shall be in accordance with EIA 443 and IEEE C37.17.

2.7.1.7 Trip unit shall employ a combination of discreet components and integrated circuits to provide the time-current protection functions required in a modern selectively coordinated distribution system.

2.7.1.8 Complete system selective coordination shall be provided by utilizing a combination of the following time-current curve-shaping adjustments: ampere setting; long-time delay; short-time pickup; short-time delay; instantaneous pickup; and ground fault.

2.7.1.9 Instantaneous and ground fault trips shall be switchable or easily overriden.

2.7.1.10 All adjustments shall be made using non-removable, discrete step, highly reliable switching plugs for precise settings. A sealable, transparent cover shall be provided over the adjustments to prevent tampering.

2.7.1.11 Trip devices shall be furnished with three visual indicators to denote the automatic tripping mode of the breaker including: overload; short circuit; and ground fault.

2.7.1.12 Trip unit shall be wired to appropriate terminals whereby an optional remote automatic trip accessory can be utilized to provide the same indication.

2.7.1.13 A series of optional automatic trip relays shall be available for use with the trip unit to provide remote alarm and lockout circuits.

2.7.1.14 All trip units shall be provided with test jacks for in-service functional testing of the long-time instantaneous and ground fault circuits using a small hand-held test kit.

2.7.2 Directional Overcurrent Relays

2.7.2.1 Directional overcurrent relays shall be in accordance with IEEE C37.90.

2.7.2.2 Directional overcurrent relays for protection against reverse-power faults shall be single-phase induction type with adjustable time-delay and instantaneous trip attachments. Relays shall be removable type with inverse-time directional and overcurrent units with built-in testing facilities.

2.7.2.3 Case shall be semiflush-mounted to the hinged instrument panel and shall have matching cover.

2.7.3 Reclosing Relays

2.7.3.1 Reclosing relays shall conform to IEEE C37.90.

2.7.3.2 Reclosing relays shall be designed to reclose circuit breakers that have tripped from overcurrent. This device shall automatically reclose the breaker at adjustable time intervals between reclosures and then lock out the breaker in the open position if the fault persists. If the fault disappears after any reclosure, the circuit breaker shall remain closed and the reclosing relay shall reset automatically and be ready to start a new sequence of operation.

2.7.3.3 Reclosing relays shall be removable with built-in testing facilities and shall consist of a timing unit rated at 120/240 volts, single-phase, ac and solenoid and contactor units with dc rating as indicated. Contacts shall be arranged for one instantaneous reclosure and two subsequent reclosures at 15 and 45 seconds, respectively. Time dial shall be set for 60-second drum speed.

2.7.3.4 Case shall be semiflush-mounted to the hinged instrument panel and shall have a matching cover.

2.7.4 Undervoltage Relays

2.7.4.1 Undervoltage relays shall conform to IEEE C37.90.

2.7.4.2 Undervoltage relays shall be three-phase induction type inverse timing with adjustable high- and low-voltage contacts and calibrated scale for protection against loss of voltage, undervoltage, and overvoltage. Relays shall be equipped with indicating contactor and voltage switches to provide electrically separate contact circuits. Relays shall be removable type with built-in testing facilities and shall be suitable for operation on 120-volt ac circuits. Contacts shall be suitable for operation on dc or ac control circuits.

2.7.4.3 Case shall be semiflush-mounted to the hinged instrument panel and shall have a matching cover.

2.8 INDICATING INSTRUMENTS

2.8.1 Ammeters

2.8.1.1 Ammeters shall conform to ANSI C39.1.

2.8.1.2 Switchboard indicating ammeters shall be approximately (4-1/2 inches) square with 250-degree scale and recessed cases suitable for flush mounting. Dials shall be white with black figures and black pointers. Instruments shall be mounted on the hinged front panel of the switchgear compartment and shall be completely isolated from high-voltage circuits. Meters shall be standard 5-ampere type for a zero to full-scale normal movement, 60 hertz.

2.8.2 Voltmeters

2.8.2.1 Voltmeters shall conform to ANSI C39.1.

2.8.2.2 Switchboard indicating voltmeters shall be approximately (4-1/2-inches) square with 250-degree scale and recessed cases suitable for flush mounting. Dials shall be white with black figures and black pointers. Instruments shall be mounted on the hinged front panel of the switchgear compartment and shall be completely isolated from high-voltage circuits. Voltmeters shall be standard 120-volt type for a zero to full-scale normal movement, 60 hertz.

2.8.3 Graphic Demand Meters

2.8.3.1 Impulse-totalizing graphic demand meters shall conform to NEMA C12.1.

2.8.3.2 Impulse-totalizing graphic demand meters shall be suitable for use with switchboard watt-hour meters and shall include a two-circuit totalizing relay, cyclometer for cumulative record of impulses, four-dial totalizing kilowatt-hour register, synchronous motor for timing mechanism, torque motor, and chart drive. A positive chart-drive mechanism consisting of chart spindles and drive sprockets shall maintain the correct chart speed for roll strip charts. Instrument shall record as well as indicate on clearly legible graph paper the 15-minute integrated kilowatt demand of the totalized system.

2.8.3.3 Torque motor shall furnish the motive power for advancing the register and pen-movement mechanism. Pen shall be the capillary type and shall contain a 1-month ink supply. Roll charts shall provide a 31-day continuous record of operation.

2.8.3.4 Case shall be semiflush-mounted to the hinged instrument panel and shall have a matching cover.

2.8.4 Specialty-Type Meters

2.8.4.1 Specialty meters shall conform to ANSI C39.1. Specialty-type meters are panel meters applicable to specific situations, such as pyrometers and dc parameter meters. These meters shall conform to the panel layout specified. Meter scales shall be not less than 180 degrees. Edgewise meters shall not be used for circuit current and voltage measurements.

2.9 FACTORY TESTING

2.9.1 Factory tests on control and low voltage protective devices shall be performed in accordance with the manufacturer's recommendations.

2.9.2 Short-circuit tests shall be in accordance with Section 2 of NEMA ICS 1.

2.9.3 Factory tests on power, high-voltage, and oil circuit breakers shall be in accordance with IEEE C37.09.

2.10 INDICATING LIGHTS

2.10.1 General-Purpose Type

2.10.1.1 Indicating lights shall be oiltight instrument devices with threaded base and collar for flush-mounting, translucent convex lens, candelabra screw-base lampholder, and 120-volt, 6-watt, Type S-6 incandescent lamp in accordance with NEMA C78.23. Color code for indicating lights shall be in accordance with NEMA ICS 6.

2.10.1.2 Indicating lights shall be provided in remote-control stations when pushbuttons and selector switches are out of sight of the controller.

2.10.2 Switchboard Indicating Lights

2.10.2.1 Switchboard indicating lights shall be the manufacturer's standard transformer type units utilizing low-voltage lamps and convex lenses of the colors indicated. Indicating lights shall be capable of being relamped from the switchboard front. Indicating lights utilizing resistors in series with the lamps are not permitted except in direct-current control circuits. Lights shall have a press-to-test feature.

2.11 FINISH

NOTE: For all outdoor applications and all indoor applications in a harsh environment refer to Section 09 96 00 HIGH-PERFORMANCE COATINGS. High performance coatings are specified for all outdoor applications because ultraviolet radiation will break down most standard coatings, causing a phenomena known as chalking, which is the first stage of the corrosion process. For additional information contact The Coatings Industry Alliance, specific suppliers such as Keeler and Long and PPG, and NACE International (NACE).

2.11.1 Metallic materials shall be protected against corrosion. Equipment shall have the standard finish by the manufacturer when used for most indoor installations.

PART 3 EXECUTION

3.1 INSTALLATION

3.1.1 Control devices and protective devices not factory installed in equipment shall be installed in accordance with the manufacturer's recommendations and shall be field adjusted and operation tested. Installations shall conform to NFPA 70, NEMA ICS 1, NEMA ICS 2, and NEMA ICS 3 requirements for installation of control and protective devices.

3.2 FIELD TESTING

3.2.1 Control and protective devices not factory installed in equipment shall be demonstrated to operate as indicated.

3.2.2 Instrumentation, potential, and current transformers shall be…