Attch 6- Asbestos Report.pdf
PDF 242 KB Posted
- Attached to
- Asbestos, Carpet, and Furniture removal
- Solicitation number
- FA468625Q0006
About this file
This is an asbestos survey report for Building 2419 at Beale AFB in California, which identifies asbestos-containing materials that require abatement prior to carpet installation. The report documents that carpet glue containing 1% Chrysotile asbestos (categorized as CAT II non-friable) was found in approximately 450 square feet of the conference room floor, while trace amounts (<1%) were detected in the court reporter office floor covering approximately 150 square feet.
The report specifies that all floor mastic throughout the building should be treated as Asbestos Containing Material (ACM) based on visual observations and sample results. Any asbestos abatement must be performed by a Licensed Asbestos Abatement Contractor certified by California DOSH, in accordance with State OSHA and Federal regulations. The work must comply with Local EPA (Air Quality Management District) requirements for containment and disposal. The report notes that any building materials not specifically mentioned should be assumed to contain asbestos until proven otherwise through proper sampling and analysis.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS REPORT
The below table lists identified asbestos containing material with concentrations of asbestos greater than one percent. The building material tested ls hereafter quantified and categorized according to the present physical conditions, physical characteristic properties, and potential ability to be rendered airborne otherwise know as friability.
Friable asbestos containing material is the more hazardous than non-friable asbestos and can be rendered airborne by hand pressure. According to the local AOMD, the abbreviation RACM is used to classify friable or/and the potential to become friable asbestos containing material and is therefore categorized as Regulated Asbestos Containing Material (RACM).
Sample Number
Suspect Material
Asbestos Content
(PLMIPC)
EPA
Category
Total Quantity
SqJLn/Cu.
Feet
1 Carpet Glue 1% CAT II 450 Sq Foot
NOTE: Based on visual observations and sample results, treat all floor mastic as Asbestos Containing Material throughout building.
Employed asbestos abatement must be performed in accord with State OSHA, and Federal Regulations (CCR & CFR) by a Licensed Asbestos Abatement Contractor certified by the State of Callfomla Division of Occupational Safety and Health (DOSH). Containment and disposal of ACM must be in accordance with Local EPA (Air Quality Management District).
An Asbestos Abatement Plan can be provided by request, If so please contact us at the number provided in the letterhead.
Any building materials not mentioned in this report should be assumed as ACM until proven otherwise through proper sampling and analysis. This includes other areas that are not mentioned with similar materials. Upon discovery of unmentioned material, work must cease until further sampling Is conducted.
This document le filed underlab identification number ABR-129031