The key details are: The solicitation number is FA468624R0013, the project is titled "Cathodic Protection Wells", the NAICS code is 238190 for Cathodic Protection Installation, the estimated contract value is $300K - $500K, a site visit is scheduled for April 11, 2024, RFI responses are due by April 16, 2024, and proposals are due by April 22, 2024. The RFI provides information about the existing piping system, including approximate distances between wells, pipe depths, and available as-built drawings. It notes that accurate information required for design will need to be gathered through a site survey and investigation, which will be estimated if the approach to reconnect the existing system for 5 wells is offered.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Cathodic Protection RFI Questions
QuestionsAnswers
1Do you have the distance between all the wells?Approximate distance between wells is provided. See attached.
2Is svaled drawing of piping in detail available? The plan attached in Solicitation is not at all clear and very blurry to read.pdf as-built plan is attached for clear details.
3What is the Depth of piping system?See in the attached pdf as-built
4The existing rectifier is located near which well?The existing rectifier was removed in 2023 with the removal of the overhead electrical system from the area. Location of the old rectifier is shown in the attached as-built and map provided.
5Does this solicitation include removal/demo of existing rectifier?See response 4.
6What is the rating of the current rectifier?See response 4. further information regarding the old rectifier (already removed)

is not available.

7Are there any available AS-Builds for the piping system?See response 4.
8What are the dimensions of the piping?Sizes of the pipes are shown in the attached pdf as-built. Response to RFI-4.
9How old is the piping?Based on the only as-built (attached), 1st revision is from 1980. please

see in the attached pdf as-built.

10 Can you provide the location where the pipe transitions from metal to Asbestos Concrete? See the attached as-built.

Note: Since the SON is asking for the survey, investigation and design work; accurate information that will be required for the design can be collected through a site survey and investigation.

Survey and investigation will be estimated if the approach to reconnect the existing system for 5 wells is offered.