This is a set of construction/renovation drawings for a youth area lighting and fire door project at Building 707, prepared by EAPC Architects Engineers for the US Army Corps of Engineers. The drawings include architectural and electrical plans showing demolition and new work for lighting upgrades and fire door installations.
The plans detail the installation of new fire-rated doors (90-minute rating) at multiple locations, including double doors and single doors with specific hardware requirements. The electrical scope includes new LED lighting fixtures - both high bay lights (12,200 lumens) and linear surface-mounted fixtures (3,000 lumens) with motion sensors and wire guards. The project involves ceiling tile removal and replacement, masonry infill work, and associated electrical demolition and new work. The drawings are dated February 15, 2024 and include architectural floor plans, reflected ceiling plans, door schedules and details, electrical demolition plans, and new lighting plans with fixture schedules. The location appears to be at Cavalier Air Force Station, with contractor access routes clearly marked on the site plan.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
YOUTH AREA LIGHTING & FIRE DOORS - BLDG 707
EGYN 22-1004
SO
LI
C
IT
AT
IO
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K
AP
PR
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E
AP
PR
SHEET OF
US Army Corps of Engineers
AR
C
H
IT
EC
TS
E N
G
IN
EE
R
S
D
EM
ER
S
AV
E G
R
AN
D F
O R
KS
, N
D
YO
U
TH
A
R
EA
LI
G
H
TI
N G
F
IR
E
D O
O R
S
BL
D G
C O
VE
R
S H
EE
T
T-101 1 8
C . H ut to n
B.
N ic ke ls on
C . H ut to n
N O
N E
/1
5/
AN
SI
D
EG
YN
2-
T-
1.
dw g
/1
5/
EG
YN
EG
YN
0% D
ES
IG
N S
U
BM
IT
TA
L
/1 5/
TELE FAX
3100 DeMers Avenue, Grand Forks ND 58201
701.775.3000 701.772.3605
AutoCAD SHX Text
WH
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
WH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1 T-101 COVER SHEET T-101 COVER SHEET COVER SHEET 2 A-101 DEMOLITION PLANS A-101 DEMOLITION PLANS DEMOLITION PLANS 3 A-102 FLOOR PLANS A-102 FLOOR PLANS FLOOR PLANS 4 A-221 REFLECTED CEILING PLAN A-221 REFLECTED CEILING PLAN REFLECTED CEILING PLAN 5 E-001 ELECTRICAL LEGEND AND ABBREVIATIONS SHEET E-001 ELECTRICAL LEGEND AND ABBREVIATIONS SHEET ELECTRICAL LEGEND AND ABBREVIATIONS SHEET 6 E-002 ELECTRICAL ON DRAWING SPECIFICATIONS E-002 ELECTRICAL ON DRAWING SPECIFICATIONS ELECTRICAL ON DRAWING SPECIFICATIONS 7 E-101 ELECTRICAL DEMOLITION PLAN E-101 ELECTRICAL DEMOLITION PLAN ELECTRICAL DEMOLITION PLAN 8 E-301 ELECTRICAL LIGHTING PLANE-301 ELECTRICAL LIGHTING PLANELECTRICAL LIGHTING PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
PROJECT LOCATION
AutoCAD SHX Text
SHEET INDEX
AutoCAD SHX Text
BASE ENTRANCE
AutoCAD SHX Text
CONTRACTOR ACCESS ROUTE
AutoCAD SHX Text
CAVALIER AFS KEY PLAN
AutoCAD SHX Text
RECORD DRAWINGS
DEMOLITION NOTES:
REMOVE EX DOOR, FRAME & HARDWARE .
REMOVE EX FIRE SHUTTER.
REMOVE EX CEILINGS TILES, EX GRID TO REMAIN.
102 103
S-1
SCALE:
FIRST FLOOR DEMOLITION PLAN1 1/8" = 1'-0"
SCALE:
SECOND FLOOR DEMOLITION PLAN2 1/8" = 1'-0"
SO
LI
C
IT
AT
IO
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K
AP
PR
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E
AP
PR
SHEET OF
US Army Corps of Engineers
AR
C
H
IT
EC
TS
E N
G
IN
EE
R
S
D
EM
ER
S
AV
E G
R
AN
D F
O R
KS
, N
D
YO
U
TH
A
R
EA
LI
G
H
TI
N G
F
IR
E
D O
O R
S
BL
D G
D
EM
O
LI
TI
O
N P
LA
N
S
A-101 2 8
C . H ut to n
B.
N ic ke ls on
C . H ut to n
N O
N E
/1
5/
AN
SI
D
EG
YN
2-
A-
1.
dw g
/1
5/
EG
YN
EG
YN
0% D
ES
IG
N S
U
BM
IT
TA
L
/1 5/
TELE FAX
3100 DeMers Avenue, Grand Forks ND 58201
701.775.3000 701.772.3605
AutoCAD SHX Text
PLAN NORTH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PLAN NORTH
AutoCAD SHX Text
AutoCAD SHX Text
102 103
S-1
SCALE:
FIRST FLOOR PLAN1 1/8" = 1'-0"
SCALE:
SECOND FLOOR PLAN2 1/8" = 1'-0"
SCALE:
DOOR PANEL & FRAME2 3/8" = 1'-0" SCALE:
DOOR HEADER DETAIL (EXTERIOR)3 1-1/2" = 1'-0" SCALE:
DOOR HEADER DETAIL (INTERIOR)4 1-1/2" = 1'-0"
DOOR SCHEDULE
DR #
7/H5
4/H8
8/H8
6/H29
OPENING SIZE
3'-0" x 7'-0"
6'-0" x 7'-0"
6'-0" x 7'-0"
6'-0" x 7'-0"
MATL
HM
HM
HM
HM
TYPE
F
F
F
F
HEAD JAMB SILL
FIRE
RATINGNOTES
DETAILSDOOR PANEL
MATL
HM
HM
HM
HM
TYPE
F
F
F
F
DOOR FRAME
90 MIN.
90 MIN.
90 MIN.
90 MIN.
1. INSULATED DOORS WITH THERMAL BREAK FRAME.
DOOR HARDWARE
ALL CORES TO BE 6 OR 7-PIN TO MATCH EXISTING, COORDINATE FINAL KEYING AND LOCKSETS WITH 10 SWS/CE.
ALL HARDWARE SUBMITTED MUST MEET UFGS.
SCHEDULE
DOOR 7/H5
3 EA. HEAVY-DUTY HINGES
1 EA. CYLINDER LOCKSET WITH LEVER HANDLE
1 EA. WALL OR OVERHEAD STOP
1 EA. CLOSER
1 SMOKE SEAL
F81 - OFFICE FUNCTION
DOOR 4/H8 - DOUBLE DOOR
3 EA. HEAVY-DUTY HINGES
1 EA. CYLINDER LOCKSET WITH LEVER HANDLE
1 EA. WALL OR OVERHEAD STOP
1 EA. CLOSER
1 SMOKE SEAL
F81 - OFFICE FUNCTION
DOOR 8/H8 - DOUBLE DOOR
3 EA. HEAVY-DUTY HINGES
1 EA. CYLINDER LOCKSET WITH LEVER HANDLE
1 EA. WALL OR OVERHEAD STOP
1 EA. CLOSER
1 SMOKE SEAL
F86 - STORAGE FUNCTION
DOOR 6/H29 - DOUBLE DOOR
3 EA. HEAVY-DUTY HINGES
1 EA. RIM PANIC DEVICE W/ LEVER HANDLE AND CYLINDER LOCKSET AT EXTERIOR
1 EA. WALL OR OVERHEAD STOP
1 EA. CLOSER
1 SMOKE SEAL
1 LOCAL ALARM
1 THRESHOLD
1 DRIP LEDGE
1 KEYED REMOVABLE MULLION
F81 - OFFICE FUNCTION
PLAN NOTES:
INFILL MASONRY WALL WITH 8" BLOCK, PRIME/PAINT TO MATCH EXISTING ON EACH SIDE. AT ROOM 101 SIDE, APPLY NEW 12" x 12" ACCOUSTICAL TILE TO MATCH EXISTING. REMOVE AND
REPLACE ANY TILES CUT AROUND OPENINGS, INFILL WITH ONLY FULL TILES.
6/H29
4/H8
7/H5
8/H8
DOOR TYPE 'F' FRAME TYPE HM-00
2"
5 3/4"
8" CMU
4" CMU
STEEL BEAM
(SEE STRUCT)
SEALANT
5-3/4" H.M. FRAME
FILL W/ MORTAR
HOLLOW METAL
DOOR
6" CMU
STEEL BEAM W/
PLATE (SEE STRUCT.)
5-3/4" H.M. FRAME
FILL W/ MORTAR
H.M. DOOR
SO
LI
C
IT
AT
IO
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K
AP
PR
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E
AP
PR
SHEET OF
US Army Corps of Engineers
AR
C
H
IT
EC
TS
E N
G
IN
EE
R
S
D
EM
ER
S
AV
E G
R
AN
D F
O R
KS
, N
D
YO
U
TH
A
R
EA
LI
G
H
TI
N G
F
IR
E
D O
O R
S
BL
D G
FL
O
O R
P
LA
N S
A-102 3 8
C . H ut to n
B.
N ic ke ls on
C . H ut to n
N O
N E
/1
5/
AN
SI
D
EG
YN
2-
A-
1.
dw g
/1
5/
EG
YN
EG
YN
0% D
ES
IG
N S
U
BM
IT
TA
L
/1 5/
TELE FAX
3100 DeMers Avenue, Grand Forks ND 58201
701.775.3000 701.772.3605
AutoCAD SHX Text
PLAN NORTH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PLAN NORTH
AutoCAD SHX Text
AutoCAD SHX Text
102 103
S-1
SCALE:
FIRST FLOOR REFLECTED CEILING PLAN1
1/8" = 1'-0"
RCP NOTES:
NEW 2x4 ARMSTRONG ULTIMA LAY-IN SQUARE, OR APPROVED EQUIVALENT, VERIFY
COMPATIBILITY WITH EXISTING GRID SYSTEM.
GENERAL NOTES:
EXISTING CEILING GRID IS TO BE REUSED, CONTRACTOR TO CLEAN AND WIPE DOWN ALL GRID
COMPONENTS.
ALL RETURNS AND LOUVERS ARE TO BE REUSED, CONTRACTOR TO CLEAN AND WIPE DOWN ALL
VISIBLE COMPONENTS.
1.
2.
SO
LI
C
IT
AT
IO
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K
AP
PR
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E
AP
PR
SHEET OF
US Army Corps of Engineers
AR
C
H
IT
EC
TS
E N
G
IN
EE
R
S
D
EM
ER
S
AV
E G
R
AN
D F
O R
KS
, N
D
YO
U
TH
A
R
EA
LI
G
H
TI
N G
F
IR
E
D O
O R
S
BL
D G
R
EF
LE
C
TE
D
C
EI
LI
N
G P
LA
N
A-221 4 8
C . H ut to n
B.
N ic ke ls on
C . H ut to n
N O
N E
/1
5/
AN
SI
D
EG
YN
2-
A-
1.
dw g
/1
5/
EG
YN
EG
YN
0% D
ES
IG
N S
U
BM
IT
TA
L
/1 5/
TELE FAX
3100 DeMers Avenue, Grand Forks ND 58201
701.775.3000 701.772.3605
AutoCAD SHX Text
PLAN NORTH
AutoCAD SHX Text
AutoCAD SHX Text
SO
LI
C
IT
AT
IO
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K
AP
PR
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E
AP
PR
SHEET OF
US Army Corps of Engineers
AR
C
H
IT
EC
TS
E N
G
IN
EE
R
S
D
EM
ER
S
AV
E G
R
AN
D F
O R
KS
, N
D
YO
U
TH
A
R
EA
LI
G
H
TI
N G
F
IR
E
D O
O R
S
BL
D G
EL
EC
TR
IC
AL
L
EG
EN
D A
N D
AB
BR
EV
IA
TI
O N
S
SH
EE
T
E-001 5 8
W . H am lin
C . R et he m ei er W
. H am lin
N O
N E
/0
3/
AN
SI
D
EG
YN
2-
E-
1.
dw g
/0
3/
EG
YN
EG
YN
0% D
ES
IG
N S
U
BM
IT
TA
L
/1 5/
TELE FAX
3100 DeMers Avenue, Grand Forks ND 58201
701.775.3000 701.772.3605
PROJECT NOTES:
ALL RUNS CONCEALED UNO.A.
VERIFY ALL LOCATIONS WITH ARCH.B.
VERIFY ALL COLORS WITH ARCH.C.
PROVIDE SLEEVES FOR ALL CABLING & CONDUITS INCLUDING THOSE FOR
USE OF OWNER & HIS OTHER CONTRACTORS. COORDINATE WITH OTHER
TRADES & OTHER CONTRACTORS. OBTAIN LOCATIONS FROM THEM.
D.
PROVIDE ALL SLEEVES THROUGH WALLS, FLOORS, CEILINGS & ACROSS
SOLID CEILING AREAS. COORDINATE INSTALLATION OF SLEEVES TO
ACCOMMODATE MULTIPLE SYSTEMS, I.E.; VOICE, DATA, SECURITY, CCTV,
SPEAKER, MICROPHONE, LINE LEVEL AUDIO, VIDEO & CONTROL WIRING.
E.
ALL SYSTEMS IN CONDUIT UNO. CONDUITS SIZED TO CODE OR LARGERF.
COMPLY WITH APPICABLE STANDARDS & CODES.G.
NOT EVERY PART OF EVERY SYSTEM IS SHOWN. PROVIDE
COMPLETE
SYSTEMS PROPERLY OPERATING TO OWNER SATISFACTION.
H.
ALL FINAL COLORS, FINISHES, MATERIAL SELECTIONS, TRIMS, HARDWARE
AND ACCESSORIES, SHALL BE DETERMINED BY ARCHITECT. SUBMIT SHOP
DRAWINGS AND SAMPLES.
J.
EC SHALL PROVIDE ALL FIRE STOPPING PER SPECIFICATIONS IN OTHER
DIVISIONS. ALSO SEAL ALL ELECTRICAL PENETRATIONS THROUGH SMOKE
AND OR FIRE PENETRATIONS AS SHOWN ON THE ARCHITECTURAL PLANS.
K.
TEST ALL SYSTEMS TO OWNER'S SATISFACTION IN THE PRESENCE OF
OWNER'S FIELD REPRESENTATIVE.
L.
SATISFY APPLICABLE CODES.M.
LABEL EVERYTHING.N.
PROVIDE PULL CORDS IN EMPTY CONDUITSP.
SUBMIT SHOP DWGS FOR ALL ITEMSQ.
ELECTRICAL LEGEND
ABBREVIATIONS NOTE: 1. NOT ALL ABBREVIATIONS MAY BE USED ON THIS PROJECT
LUMINAIRE IDENTIFICATION LEGEND
LUMINAIRE TYPE
(UPPERCASE
LETTER)
SWITCHING CONTROL
TAG
(LOWERCASE LETTER) Aa
HA(2)
BRANCH CIRCUIT
TAG
(PANEL AND CIRCUIT)
A
A
A
LCP
SCP
PP
PP T
OE
UE
CO
SS
NS
NCA
MP
CB
N3
N4
N5
DS
N2
NCMC
N1
NCTC
T-TIMER
WF-WEATHERPROOF FUSED SWITCH
SURFACE MOUNTED PANELBOARD
FLUSH MOUNTED PANELBOARD
PLYWOOD BACKBOARD
PANELS/EQUIPMENT
MANUAL MOTOR STARTER
GD-GARBAGE DISPOSAL
EF-BATHROOM EXHAUST FAN
SUB AS FOLLOWS:
MAGNETIC MOTOR STARTER
PROTECTION
TEMPERATURE CONTROL PANEL
DISCONNECT SWITCH
THERMOSTAT
DRY TRANSFORMER
MAIN DISTRIBUTION PANEL
MOTOR CONTROL CENTER
ELECTRIC HEATER/REHEATER
BACK BOX FOR FUTURE WIRING DEVICE
SMALL MOTOR-XX LETTERS INDICATE SERVICE
MOTOR-# INDICATES MOTOR NUMBER
STARTER/DISCONNECT COMBINATION UNIT
MANUAL MOTOR DISCONNECT W/THERMAL
WP-WEATHERPROOF
PENDANT MOUNTED EMERGENCY
PENDANT MOUNTED
BB
T
MCC
M
H
M METER
MDP
SOUND CONTROL PANEL
EXTERIOR UTILITY POWER POLE W/XFMR
EXTERIOR UTILITY POWER POLE
LIGHTING CONTROL PANEL
FAN
SUB=SUBSCRIPT AS FOLLOWS:
A-AUDIBLE ALARM
CARBON MONOXIDE DETECTORS
UNDERGROUND ELECTRICAL
OVERHEAD ELECTRICAL
GUY WIRE
POST
V-VISUAL
L-LOCAL
R
TCP
T
RELAY
OL
M
XX
MOTORS & HVAC EQUIPMENT & CONTROLS
JUNCTION BOXES
DOUBLE DUPLEX RECEPTACLE-20A, 125V
RECEPTACLES
EXPLOSION PROOF SEAL OFF
RACEWAY
-WALL MOUNTED HEIGHTS UNLESS NOTED
HOMERUN-TEXT DESIGNATES PANEL AND CIRCUIT
BREAKER NUMBER. HASH MARKS INDICATE
CONDUIT. NO HASH MARKS INDICATE 2 #12
AWG IN A 3/4" CONDUIT UNLESS NOTED
NUMBER OF #12 AWG CONDUCTORS IN A 3/4"
OTHERWISE. PROVIDE A CODE SIZED GROUND IN
H-HORZONTALLY MOUNTED
W-WELDING RECEPTACLE
SUB= SUBSCRIPT AS FOLLOWS:
10-NUMBER INDICATES CIRCUIT NUMBER
DUPLEX RECEPTACLE - 20A, 125V
G-GROUND FAULT INTERRUPTER
EWC-ELECTRIC WATER COOLER
HALF-SWITCHED RECEPTACLE-20A, 120V
BOX SURROUNDING DEVICE DEPICTS FLOOR
SS-SURGE SUPPRESSION RECEPTACLE
FLOOR MOUNTED JUNCTION BOX
RECESSED WALLA
F-FUSED
LV-LOW VOLTAGE
FLOOD LIGHT
COMBINATION FAN/LIGHT
TRACK LIGHTING
EXIT - EMERGENCY
REMOTE HEAD FOR EMERGENCY FIXTURE
RECESSED EMERGENCY LIGHT
SURFACE MOUNTED EMERGENCY LIGHT
CEILING MOUNTED EXIT LIGHT
WALL MOUNTED EXIT LIGHT
SURFACE MOUNTED LIGHT FIXTURE
STRIP LIGHT OR INDUSTRIAL FIXTURE
RECESSED WALL EMERGENCY
POLE WITH LIGHT FIXTURE(S)
4-FOUR-WAY, 120V,20A
2-TWO-POLE, 120V, 20A
K-KEYED TYPE
L-LIGHTED TOGGLE
P-SWITCH W/PILOT LIGHT
ORIENTATION.
3-THREE-WAY, 120V, 20A
SUB= SUBSCRIPT AS FOLLOWS:
SINGLE POLE SWITCH, 120V, 20A
NONE-SINGLE-POLE, 120V, 20A
FIXTURE SHOWN DEFINE QUANTITY AND
EMERGENCY/BATH STATION PUSH BUTTON
STAFF REGISTRATION STATION(IN ROOMS)
MULTIPLE PURPOSE STATION
Z-ZONE ADDRESSABLE
MISCELLANEOUS
GROUND/ROD CONNECTION POINT
CORRIDOR DOME LIGHT
CODE BLUE STATION
NURSE CALL ANNUNCIATOR
SPEAKER
DOUBLE PATIENT BED STATION
STAFF ASSIST STATION
NURSE CALL MASTER CONSOLE
NURSES CALL TERMINAL CABINET
SINGLE PATIENT BED STATION
EMERGENCY/BATH PULL CORD STATION
DUTY STATION
SUB
A
A
A
BOLLARD
NURSE CALL
A
A A
A
A
A
A
A
A
LIGHTING CONTROL
LARGE JUNCTION BOX
JUNCTION BOX
J
J
J
TP-TAMPER PROOF
OTHERWISE
WP-WEATHERPROOF
S-SURFACE MOUNTED
P-PLUG MOLD
XP-EXPLOSION PROOF
EXTERIOR/SITE
SPECIAL LIGHTING
SPECIAL RECEPTACLE
MOUNTED
AC-ABOVE COUNTER
CLG-CEILING OUTLET
EM-EMERGENCY
SINGLE RECEPTACLE
ISOLATED GROUND
CONDUIT/BRANCH CIRCUIT
FLEX CONDUIT
CONDUIT DOWN
WALL MOUNTED FIXTURE EMERGENCY
RECESSED DOWN LIGHT EMERGENCY
RECESSED DOWN LIGHT
UNDER CABINET
WALL MOUNTED FIXTURE
A
A
A
CONDUIT UP
EACH CONDUIT.
SURFACE RACEWAY - DATA/TELEPHONE
A-1,3,5
A
WALL MOUNTED FIXTURE
A SPOT LIGHT
PENDANT MOUNT FIXTURE
RECESSED DOWN LIGHT WALL WASH
MAGNETIC CONTACTORC
EMERGENCY SHUNT TRIP
CONDUIT STUB
F-FLOOR
CEILING DUPLEX - 20A, 125V
CEILING DOUBLE DUPLEX -20A, 125V
HD-HAND DRYER
HAND DRYERHD
A COMBINATION EXIT/EMERGENCY
N6 STAFF ASSIST/CODE BLUE COMBO
DEAD FRONT GFCI DEVICE
M MICROPHONE OUTLET
DATA/VOICE OUTLET FLOOR BOX
M-VOICE OUTLET/MULTI
P-VOICE OUTLET/PUBLIC
W-VOICE OUTLET/WALL
SUB= SUBSCRIPT AS FOLLOWS:
TELEPHONE TERMINAL BLOCK
DIGITAL COMMUNICATIONS PATCH PANEL
TTB/D UTILITY DEMARK
DATA OUTLET FLOOR BOX
VOICE OUTLET
VOICE/DATA/VIDEO
TERMINAL CABINET
CPP
SUB
TELEPHONE/DATA
DATA/VOICE/DUPLEX FLOOR BOX
DATA/VOICE/QUADPLEX FLOOR BOX
MD-MASTER DESK MOUNT
SUB= SUBSCRIPT AS FOLLOWS:
TV TELEVISION OUTLET
#-INDICATES NUMBER OF OUTLETS
DATA/VOICE OUTLET
DATA
M-MASTER
VOLUME CONTROL
INTERCOM HANDSET
AUXILIARY INPUT
VIDEO OUTLET
SOUND SYS. PATCH PNL
A
VB
SPP
DM-DESK MOUNTED
H-HORN
PAGING/SOUND/DATA/SURVEILLANCE
FIRE ALARM SHUTDOWN RELAY
FIRE ALARM JUNCTION BOX
INDIVIDUAL ADDRESSABLE MODULE
SPRINKLER OR HOSE FLOW ALARM SWITCH
NOTIFICATION APPLIANCE CIRCUIT PANEL
P-SPEAKER WITH PUSHBUTTON
SUB= SUBSCRIPT AS FOLLOWS:
IAM
WP-WEATHERPROOF
MASTER INTERCOM AND DIRECTORY UNIT
SPEAKER - CEILING MOUNTEDS
SUB
WG-WIREGUARD
N-NURSE CALL
H-HORN SPEAKER
FIRE ALARM RELAY
ZONE ADAPTER MODULE
FIRE ALARM BELL
TRANSPONDER
TAMPER SWITCH
ZAM
FAJB
F
TRP
FR
FAR
NAC
AUTOMATIC SMOKE DETECTOR-WALL MOUNT
NONE-FIXED TEMP & 135°F RATE OF RISE
AUTOMATIC SMOKE DETECTOR
SUB= SUBSCRIPT AS FOLLOWS:
AUTOMATIC HEAT DETECTOR-CEILING MOUNT
SUB= SUBSCRIPT AS FOLLOWS:
MAIN SPRINKLER VALVE SUPERVISION
FIRE ALARM MAGNETIC DOOR HOLDER
SUB= SUBSCRIPT AS FOLLOWS:
REMOTE INDICATOR
F-FIXED TEMP 190°F
LED
M
S
WP-WEATHERPROOF
MH-MINI-HORN
NO SUB-75 CANDELA
L-LOCAL
ID-IONIZATION
LSR-LASER
MANUAL PULL STATION
FIRE ALARM VISUALF
F
SUB
FIRE ALARM CONTROL PANEL
SUB= SUBSCRIPT AS FOLLOWS:
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM
SUB= SUBSCRIPT AS FOLLOWS:
FIRE ALARM AUDIO/VISUAL
FIRE ALARM AUDIO DEVICE
WG-WIREGUARD
F
F
SUB
SUB
FACP
SUB
SC-SELF CONTAINED
E-ELEVATOR RECALL
TS
FS
BEAM DETECTOR
SUB
S-SENDING UNIT
SUB= SUBSCRIPT AS FOLLOWS:
R-RECEIVER
MI
IC
SUB
SUB
SUB
SUB= SUBSCRIPT AS FOLLOWS:
#D/#V-INDICATES # & TYPE OF OUTLETS
SUB= SUBSCRIPT AS FOLLOWS:
TCC
3/4" PLYWOOD BACKBOARD
EQUIPMENT RACK - FREE STANDING
EQUIPMENT RACK - WALL MOUNTED
F
F
F
F
WP-WEATHERPROOFWG-WIREGUARD
S
SUB
FAA
LOW PRESSURE SWITCHPS
B
W-WALL MOUNTED
D-DUCT SMOKE DETECTOR W/2 AUX CONTACTS
WG-WIRE GUARD
VC
W/ 2 COATS RETARDANT
S
SUB
SPEAKER - WALL MOUNTED
WAP WIRELESS ACCESS POINT
SUB= SUBSCRIPT AS FOLLOWS:
O-OUTPUT
I-INPUT
SUB
CO-COMBINATION CO DETECTOR
SB-SOUNDER BASE
SUB
SUB
SUB
SUB
SUB
SUB
SUB
SUB
DF
SUB
POST TOP FIXTURE
S-SPEAKER
S-SPEAKER
PS PILLOW SPEAKER
SURFACE RACEWAY - RECEPTACLES
DATA OUTLET CEILING
CABLE TRAY
REFERENCE NOTE
REVISION NUMBER
SECTION DESIGNATION
DETAIL DESIGNATION
REVISION INDICATOR
INTERIOR ELEVATION
ROOM NAME
VIEW REFERENCE
ENLARGED AREA
ROOM NUMBER
2 1 3
E200
E200
XX
XXX
XX
MATCH LINE
ENCLOSE THE
ELEVATION NUMBER
SECTION NUMBER
DRAWING NUMBER
DRAWING NUMBER
DRAWING NUMBER
DETAIL NUMBER
DRAWING NUMBER
SECTION NUMBER
REFERENCE SYMBOLS
POINT OF CONNECTION
N/E
NOT ALL SYMBOLS AND ABBREVIATIONS MAY
NOTE:
BE USED ON THIS PROJECT
(NEW TO EXISTING)
VIEW REFERENCE
VIEW REFERENCE OF-/---
ADJACENT SHEET
POWER LIGHTING
A
A
A
A
NUMBER, LAMPS, MOUNTING, LOCATION AND COMMENTS.
SURFACE MOUNTED LIGHT FIXT EMERGENCY
RECESSED TROFFER EMERGENCY
RECESSED TROFFER
SURFACE MOUNTED LIGHT FIXTURE
ALL LIGHTING FIXTURES ARE IDENTIFIED BY A LETTER(S)
COORDINATE WITH LUMINAIRE SCHEDULE AS TO THE
FIXTURES: IDENTIFICATION, MANUFACTURER, CATALOG
INTERIOR LIGHTING
RECESSED LED STRIP LIGHT EMERGENCY
RECESSED LED STRIP LIGHTA
A
SYSTEMS
C
C
SUB
TC
MC
CS
C
DC
SMON
IC
BG
K
ES
MD
DO
X
CLOCK/PROGRAM
WG-WITH WIREGUARD
WALL MOUNTED CLOCK
SUB= SUBSCRIPT AS FOLLOWS:
CLOCK WITH SPEAKER
TIME CLOCK
MASTER CLOCK
R-RECESSED
B-WITH BUZZER
SECURITY DOOR CONTACTS
BREAK GLASS DETECTOR
ELECTRIC STRIKE DOOR LATCH
MOTION DETECTOR
SECURITY MONITOR
SECURITY CAMERA
INTERCOM
DOOR KEYPAD
HAND STATION (NORMALLY PUSH BUTTONS)
DOOR SECURITY/SECURITY EXIT
SUB= SUBSCRIPT AS FOLLOWS:
D-DOOR CHIME/BELL
E-ELEVATOR CHIME
P-PROGRAM BELL
B-BUZZER
DOOR OPENER
PUSHBUTTON
BELL
CR CARD READER
SUB= SUBSCRIPT AS FOLLOWS:
C-CEILINGHS-HIGH SECURITY
CCTV CCTV CABLE OUTLET
SUB= SUBSCRIPT AS FOLLOWS:
WP-WEATHERPROOF
I-INTERCOM
SUB
ML
P
MAGNETIC LOCK
PANIC BAR
W-WALL
WP-WEATHERPROOF
PTZ-PAN TILT ZOOM
FP FINGER PRINT SCANNER
REX REQUEST TO EXIT SENSOR
W WANDER GUARD
SYSTEMS
ELECTRICAL MOUNTING HEIGHT NOTES:
HEIGHTS SHOWN ARE TYPICAL TO BOTTOM OF DEVICE UNLESS NOTED
OTHERWISE.
MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL
GOVERN OVER ALL ELEVATIONS SHOWN OR INDICATED ON ELECTRICAL
DRAWINGS.
INSTALL FIRE ALARM NOTIFICATION APPLIANCES AT 80" AFF, OTHERWISE
INSTALL AT 6" BELOW CEILING, WHICH EVER IS LOWER.
VERIFY EXIT LIGHT HEIGHTS WITH ARCHITECT.
TYPICAL HEIGHTS SHOWN, HEIGHTS ON PLANS SHALL GOVERN OVER
THESE. DEVICES WITH KNOW OBSTRUCTIONS SUCH AS, BUT NOT LIMITED
TO COUNTERTOPS & SHELVING MAY REQUIRE A LOWER HEIGHT, VERIFY
WITH ARCHITECT/ENGINEER.
SYMBOLS NOT SHOWN SHALL BE VERIFIED WITH ARCHITECT/ENGINEER.
A.
B.
C.
D.
E.
F.
AREA A
AREA B
AREA B
E100
LINE VOLTAGE DIMMER
CEILING MOUNTED DUAL TECHNOLOGY
OCCUPANCY SENSOR
DAYLIGHT SENSORDH
OS
D
UL 924 DEVICEUL
WALL MOUNTED DUAL TECHNOLOGY
OCCUPANCY SENSOR WITH INTEGRAL DIMMING
OD
WALL MOUNTED DUAL TECHNOLOGY
OCCUPANCY SENSOR WITH ON/OFF SWITCH
OS
DIGITAL SWITCH (CAT6)$
DIGITAL DIMMER (CAT6)D
WALL MOUNTED MULTI-BUTTON SWITCH, # TO
INDICATE QUANTITY OF BUTTONS (CAT6)
TOUCH SCREEN (CAT6)TS
DIGITAL CEILING MOUNTED DUAL
TECHNOLOGY OCCUPANCY SENSOR (CAT6)OS
DIGITAL NETWORK BRIDGE TIE TO DIGITAL
LIGHTING CONTROL SYSTEM (CAT6)NB
DIGITAL DIMMING ROOM CONTROLLER, #
INDICATES QUANTITY OF RELAYS (CAT6)RC#
DIGITAL UL 924 DEVICE (CAT6)UL
RGB DMX TOUCHSCREEN CONTROLLERRG
DIGITAL DAYLIGHT SENSORDH
EE
A AMPERES
AC ABOVE COUNTER
ACCU AIR COOLED CONDENSING UNIT
AF AMP-FUSE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
ALT ALTERNATE
AL ALUMINUM
AMP AMPLIFIER
ANN ANNUNCIATOR
AFF ABOVE FINISHED FLOOR
ARCH ARCHITECT(URAL)
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO VISUAL
AUX AUXILIARY
BFG BELOW FINISHED GRADE
BK BLACK
BKR BREAKER
BR BRANCH
BTU BRITISH THERMAL UNIT
CAB CABINET
CALC CALCULATION
CAT CATALOG
CB CIRCUIT BREAKER
CBIC CIRCUIT BREAKER INTERRUPTING CIRCUIT
CCT CIRCUIT
CFL COMPACT FLOURESCENT LIGHT
CKT CIRCUIT
CLG/C CEILING
COMM COMMUNICATIONS
COMP COMPRESSOR
CONN CONDUCTOR
CONN CONNECTOR
CR CARD READER
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
CUH CABINET UNIT HEATER
dB DECIBEL
DED DEDICATED CIRCUIT
DEV DEVICE
DIA DIAMETER
DISC DISCONNECT
DISP DISPOSAL
DISTR DISTRIBUTION
DN DOWN
DS DUTY STATION
DTL DETAIL
DWG DRAWING
EF EXHAUST FAN
EC ELECTRICAL CONTRACTOR
EL ELECTRICAL, ELECTRIC
ELEV ELEVATOR OR ELEVATION
EM EMERGENCY
EQ EQUAL, EQUIPMENT
ERU ENERGY RECOVERY UNIT
EUH ELECTRIC UNIT HEATER
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXITING
EXH EXHAUST
EXPL EXPLOSION PROOF
F FUSE OR FRONT
°F DEGREES FARENHEIT
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FD FIRE DAMPER
FIXT FIXTRUE, LUMINAIRE
FLA FULL LOAD AMPERES
FL FLOOR
FO FIBER OPTICS
FS FLOW SWTICH
FT FEET
FUT FUTURE
FURN FURNISHED
FUS FUSE, FUSED, FUSIBLE
GND/G GROUND
GAL GALLONS
GARB GARBAGE DISPOSAL
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERUPTOR
GFP GROUND FAULT PROTECTION
GPM GALLONS PER MINUTE
H HIGH,HOT
HC HEATING COIL
HD HEAVY DUTY
HID HIGH INTENSITY DISCHARGE
HP HORSE POWER
HPS HIGH PRESSURE SODIUM
HOA HAND-OFF-AUTO
HT HEIGHT
HTR HEATER
HVU HEATING & VENTILATING UNIT
HW HOT WATER
HWH HOT WATER HEATER
ID INSIDE DIMENSION
IDF INTERMEDIATE DISTRIBUTION FRAME
IN INCHES
INB/OUT INBOARD/OUTBARD
INCAND INBOARD/OUTBARD
INFO INFORMATION
INST INSTALLATION
INSUL INSULATION
INV INVERTER
JB JUNCTION BOX
KA THOUSAND AMPS
KS KNEE SPACE
L LAMP
LCP LIGHTING CONTROL PANEL
LI LAY IN
LOC LOCATION, LOCATE
LRA LOCKED ROTOR AMPS
LTG LIGHTING
LTS LIGHTS
LV LOW VOLTAGE
M,MAINT MAINTENANCE
MAG MAGNETIC
MAU MAKE UP AIR UNIT
MAX MAXIMUM
MC MECHANICAL CONTACTOR
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDF MAIN DISTRIBUTION FRAME
MDP MAIN DISTRIBUTION PANEL
MIC MICROWAVE
MRF MANUFACTURER
MFS MAXIMUM FUSE SIZE
MH METAL HALIDE, MOUNTING HEIGHT, MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOP MAXIMUM OVERCURRENT PROTECTION
MSB MAIN SWITCHBOARD
MTD MOUNTED
MTG MOUNTING
MATL MATERIAL
MTR MOTOR OR METER
N NEUTRAL
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NF NON FUSED
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NORM NORMAL(LY)
NTS NOT TO SCALE
OC ON CENTER
OCP OVERCURRENT PROTECTION
OD OUTSIDE DIMENSION, OUTSIDE DIAMETER
OH OVERHEAD
OL OUTLET, OVERLOAD
OP OPERATOR
P PUMP,POLE
PC PHOTO CONTROL
∅ , PH PHASE
P.H. PENTHOUSE
PNL PANEL, PANELBOARD
PR PAIR
PRI PRIMARY
PRIV PRIVATE
PROJ PROJECTOR
PRV POWER ROOF VENT
PS PULSE START/POWER SUPPLY
QTY QUANTITY
R REFRIGERATOR
RA RETURN AIR
REC RECESSED
RCVR RECEIVER
RECEPT RECEPTACLE
REF REFERENCE, REFER TO
REQ/RQDREQUIRE(D)
REV REVISION
REX REQUEST TO EXIT
RLA RUNNING LOAD AMPS
RM ROOM
RTU ROOF TOP UNIT
SA SUPPLY AIR
SC SHORT CIRCUIT
SF SQUARE FEET
SHT SHEET
SD SMOKE DAMPER
SP SUMP PUMP
SPEC SPECIFICATION
SSTL STAINLESS STEEL
STD STANDARD
SURF SURFACE MOUNT
SW SWITCH
SWBD SWITCHBOARD
SYS SYSTEM
TCC TEMPERATURE CONTROL CONTRACTOR
TCP TEMPERATURE CONTROL PANEL
TD TIME DELAY
TEL TELEPHONE
TEMP TEMPORARY, TEMPERATURE
TP TAMPERPROOF
TRT TRIPLE TUBE
TS TIME SWITCH
TSTAT THERMOSTAT
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYP TYPICAL
U URINAL
UBC UNITED BUILDING CODE
UG UNDERGROUND
UH UNIT HEATER
UNV UNIVERSAL
UTIL UTILITY
UTP UNSHIELDED TWISTED PAIR
V VOLT
VA VOLT--AMPS
VAV VAV BOX
VERT VERITCAL
VFD VARIABLE FREQUENCY DRIVE
WG WIRE GUARD
WC WATER CLOSET
WH WATER HEATER
WP WEATHER PROOF, NEMA 3R IF ENCLOSED
W/ WITH
W/O WITHOUT
XFMR TRANSFORMER
SO
LI
C
IT
AT
IO
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K
AP
PR
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E
AP
PR
SHEET OF
US Army Corps of Engineers
AR
C
H
IT
EC
TS
E N
G
IN
EE
R
S
D
EM
ER
S
AV
E G
R
AN
D F
O R
KS
, N
D
YO
U
TH
A
R
EA
LI
G
H
TI
N G
F
IR
E
D O
O R
S
BL
D G
EL
EC
TR
IC
AL
O
N D
R
AW
IN
G
SP
EC
IF
IC
AT
IO
N S
E-002 6 8
W . H am lin
C . R et he m ei er W
. H am lin
N O
N E
/0
3/
AN
SI
D
EG
YN
2-
E-
2.
dw g
/0
3/
EG
YN
EG
YN
0% D
ES
IG
N S
U
BM
IT
TA
L
/1 5/
TELE FAX
3100 DeMers Avenue, Grand Forks ND 58201
701.775.3000 701.772.3605
SECTION DIVISIONS 26, 27, AND 28
ELECTRICAL SPECIFICATIONS
26 0000 SCOPE OF WORK:
1.1THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL MATERIALS, LABOR, AND EQUIPMENT NECESSARY TO COMPLETE THE PROJECT IN CONFORMITY WITH THE DRAWINGS, SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
a. MATERIALS FURNISHED SHALL INCLUDE, BUT NOT BE LIMITED TO RACEWAYS, CONDUCTORS, SWITCHES, RECEPTACLES, LIGHT FIXTURES, NECESSARY HANGERS AND SUPPORTS, SERVICE ENTRANCE, PANELS, ELECTRIC HEAT, ETC.
b. LABOR SHALL INCLUDE THE INSTALLING AND CONNECTING OF MATERIALS NOTED IN PARAGRAPH (1.) AND AS SHOWN ON THE
DRAWINGS.
1.2THE INSTALLATION SHALL COMPLY WITH LOCAL, STATE AND NATIONAL ELECTRICAL CODES. THE ELECTRICAL CONTRACTOR
SHALL SECURE AND PAY FOR FEES, PERMITS AND INSPECTIONS.
1.3BEFORE SUBMITTING A PROPOSAL ON THE WORK CONTEMPLATED, EACH BIDDER SHALL VISIT THE SITE(S) AND FAMILIARIZE THEMSELF WITH ALL EXISTING CONDITIONS AND LIMITATIONS, NO EXTRA COMPENSATION WILL BE ALLOWED BECAUSE OF THE
CONTRACTOR'S KNOWLEDGE OF ANY EXISTING CONDITIONS.
1.4THE CONTRACTOR SHALL COORDINATE AND COOPERATE WITH ALL OTHER TRADES. CONTRACTOR TO COORDINATE SCHEDULING
OF THE WORK AND TENANT'S SECURITY VENDOR.
1.5SCOPE OF WORK IS COMPRISED OF THE FOLLOWING: [insert project scope]
26 0010 SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL:
1.1SEQUENCING - CONDUCT AND SUBMIT RESULTS OF POWER SYSTEM STUDIES PRIOR TO SUBMITTING PRODUCT DATA AND SHOP
DRAWINGS FOR ELECTRICAL EQUIPMENT.
1.2CLOSE OUT SUBMITTALS - CONTRACTOR TO PROVIDE OPERATION AND EQUIPMENT MANUALS TO OWNER ON USB MEDIA WHICH IS
CLEARLY AND PERMANENTLY LABELED.
26 0050 BASIC ELECTRICAL REQUIREMENTS
1.1TEMPORARY POWER - THE CONTRACTOR SHALL BE RESPONSIBLE FOR TEMPORARY POWER AND LIGHTING AS MAY BE REQUIRED FOR CONSTRUCTION OR AS REQUIRED TO MAINTAIN CRITICAL OPERATIONS DURING CHANGEOVER OF FEEDERS OR SERVICES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL EQUIPMENT, MAKING ALL ARRANGEMENTS, AND MAKING ALL
CONNECTIONS REQUIRED FOR TEMPORARY POWER AND LIGHTING OF ALL TRADES.
1.2ALL MATERIALS AND EQUIPMENT SHALL CONFORM TO UL OR NRTL STANDARDS AND BE CLEARLY IDENTIFIED WITH NRTL LABEL.
1.3THE CONTRACTOR SHALL CONFIRM THE LOCATIONS OF ALL EXISTING UTILITIES. CONTRACTOR IS RESPONSIBLE FOR REPAIRING
ANY DAMAGE TO EXISTING UTILITIES AND TO THE BUILDING.
1.4CONTRACTOR SHALL BE RESPONSIBLE FOR ELECTRICAL INSPECTION BY AN INDEPENDENTLY APPROVED INSPECTION AGENCY.
UPON COMPLETION OF THE WORK THE CONTRACTOR SHALL ADJUST ALL EQUIPMENT AND TEST ALL SYSTEMS AT THE DIRECTION OF
OWNER/ENGINEER.
1.5ALL WORK SHALL BE PERFORMED BY EXPERIENCED AND QUALIFIED PERSONNEL IN A NEAT AND WORKMANLIKE MANNER.
1.6ALL CIRCUITING SHOWN IS DIAGRAMMATICAL. THE CONTRACTOR SHALL PROVIDE JUNCTION AND PULL BOXES AS REQUIRED BY NFPA 70, NATIONAL ELECTRICAL CODE CURRENT EDITION. ALL SYMBOLS AND ABBREVIATIONS SHOWN ON DRAWINGS ARE NOT
NECESSARILY USED HEREIN.
1.7THE CONTRACTOR SHALL REFER TO DIVISION 23 HVAC MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND MOUNTING OF HVAC
MECHANICAL EQUIPMENT.
1.8PROVIDE ALL MATERIALS, LABOR, EQUIPMENT AND TOOLS NECESSARY FOR A COMPLETE AND WORKABLE ELECTRICAL SYSTEM AS INDICATED ON THE DRAWINGS. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC), LOCAL AND STATE CODES HAVING JURISDICTION AND APPLICABLE MANUFACTURER'S
RECOMMENDATIONS.
1.9IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY THE ELECTRICAL CHARACTERISTICS OF ALL EQUIPMENT PROVIDED BY THE ELECTRICAL CONTRACTOR OR FURNISHED BY OTHERS, INCLUDING THE OWNER / TENANT. COORDINATE ANY
INCOMPATIBLE ELECTRICAL CHARACTERISTICS WITH ENGINEER PRIOR TO INSTALLATION.
1.10 WHERE CONDUITS PASS THROUGH FIRE RESISTING PORTIONS OF THE STRUCTURE, THE ANNULAR SPACE BETWEEN THE
STRUCTURE AND THE CONDUITS SHALL BE FILLED WITH AN APPROVED FIREPROOF MATERIAL.
1.11THE ELECTRICAL CONTRACTOR SHALL FURNISH THE OWNER WITH A WRITTEN GUARANTEE FOR THE PERIOD OF ONE YEAR AGAINST THE FAILURE OF THE ELECTRICAL SYSTEM DUE TO FAULTY MATERIALS OR WORKMANSHIP. GUARANTEE PERIOD SHALL START AT THE DATE OF THE FINAL ACCEPTANCE BY THE ARCHITECT/ENGINEER. ALL SUCH DEFECTS MUST BE REPAIRED OR
DEFECTIVE MATERIALS REPLACED BY THE ELECTRICAL CONTRACTOR AT HIS EXPENSE.
26519 LOW VOLTAGE - ELECTRICAL POWER CONDUCTORS AND CABLES
2.1 ALL CONDUCTORS AND CABLE SHALL BE DRAWN COPPER CURRENT - CARRYING CONDUCTOR WITH AN OVERALL INSULATION
LAYER OR JACKET, OR BOTH RATED 600V OR LESS.
a. LISTED AND LABELED AS DEFINED IN NFFA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND
USE.
b. CONDUCTOR AND CABLE MARKING: COMPLY WITH WIRE AND CABLE MARKING ACCORDING TO UL'S “WIRE AND CABLE MARKING
AND APPLICATION GUIDE.”
c. THE MINIMUM WIRE SIZE SHALL NOT BE SMALLER THAN #12 AWG GAUGE CONDUCTOR, UNLESS OTHERWISE NOTED ON DRAWINGS. LARGER SIZES SHALL BE USED AS INDICATED ON THE DRAWINGS, BUT IN NO CASE SHALL THE CONDUCTOR BE
SMALLER THAN THAT IS REQUIRED BY THE N.E.C.
2.2CONDUCTOR INSULATION ON SIZE 4 AWG AND SMALLER SHALL BE TYPE THW, THHN, OR THWN-2. COMPLY WITH UL 83.
2.3CONDUCTOR INSULATION ON SIZE 2 AWG AND LARGER SHALL BE XHHW-2. COMPLY WITH UL 44.
2.4CONDUCTOR INSULATION FOR VFD BRANCH CIRCUITS SHALL BE XHHW-2.
2.5CONDUCTORS INSTALLED IN DAMP AND WET LOCATIONS SHALL BE THW AND THW-2.
2.6 MANUFACTURERS - COPPER BUILDING WIRE:
a. ALPHA WIRE COMPANY.
b. BELDEN INC.
c. GENERAL CABLE.
d. OKONITE COMPANY.
e. SOUTHWIRE COMPANY.
3.1 CONDUCTOR MATERIAL APPLICATIONS
a. FEEDERS AND BRANCH CIRCUITS SHALL BE SOLID COPPER FOR 10 AWG AND SMALLER; STRANDED FOR 8 AWG OR LARGER.
3.2 CONDUCTOR INSULATION APPLICATIONS AND WIRING METHODS
a. SERVICE ENTRANCE: TYPE XHHW-2, SINGLE CONDUCTORS IN RACEWAY
b. EXPOSED FEEDERS: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY
c. FEEDERS CONCEALED IN CEILINGS, WALLS, PARTITIONS, AND CRAWLSPACES: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN
RACEWAY
d. FIRE ALARM: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RED RACEWAY
26 0533 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
1.1 CONDUIT FOR BRANCH CIRCUITS SHALL BE EMT WITH STEEL CONNECTORS AND FITTINGS, PROVIDE BUSHINGS AT BOXES AND
CABINETS.
1.2 PROVIDE A GROUNDING CONDUCTOR IN EACH CONDUIT.
1.3 ALL WIRING CONCEALED UNLESS NOTED OTHERWISE.
26 5619 LED LIGHTING FIXTURES
1.1 THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL LIGHT FIXTURES AS INDICATED ON THE DRAWINGS.
1.2 LIGHT FIXTURES SHALL BE SECURELY FASTENED TO WALL OR CEILING.
E301
ELECTRICAL DEMOLITION PLAN
1/8" = 1'-0"
TELE FAX
3100 DeMers Avenue, Grand Forks ND 58201
701.775.3000 701.772.3605
SO
LI
C
IT
AT
IO
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K
AP
PR
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E
AP
PR
SHEET OF
US Army Corps of Engineers
AR
C
H
IT
EC
TS
E N
G
IN
EE
R
S
D
EM
ER
S
AV
E G
R
AN
D F
O R
KS
, N
D
YO
U
TH
A
R
EA
LI
G
H
TI
N G
F
IR
E
D O
O R
S
BL
D G
EL
EC
TR
IC
AL
D
EM
O
LI
TI
O N
P
LA
N
E-101 7 8
W . H am lin
C . R et he m ei er W
. H am lin
1/ 8"
=1 '-0
/0 3/
AN
SI
D
EG
YN
2-
E-
1.
dw g
/0
3/
EG
YN
EG
YN
0% D
ES
IG
N S
U
BM
IT
TA
L
/1 5/
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S-1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
EL
AutoCAD SHX Text
EL
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
PANEL
AutoCAD SHX Text L5
AutoCAD SHX Text
EL
AutoCAD SHX Text
TO 3-WAY
AutoCAD SHX Text
SWITCH IN
AutoCAD SHX Text
PROJ. BOOTH
AutoCAD SHX Text E-2
AutoCAD SHX Text
LTG.
AutoCAD SHX Text
PNL.
AutoCAD SHX Text L3
AutoCAD SHX Text K
AutoCAD SHX Text
UP TO RM. 201
AutoCAD SHX Text
LTG. CKT.
AutoCAD SHX Text
UP
AutoCAD SHX Text
PANEL L2
AutoCAD SHX Text GENERAL DEMO NOTES: A. INDICATES ITEM TO BE REMOVED. DEMOLITION SHOWN ON THIS DRAWING INDICATES ITEM TO BE REMOVED. DEMOLITION SHOWN ON THIS DRAWING IS INTENDED ONLY AS A GUIDE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VISIT & FAMILIARIZE THEMSELF WITH THE SITE PRIOR TO BIDING THEREIN DETERMINE THE AMOUNT OF WORK OF DEMOLITION REQUIRED. NO EXTRA COMPENSATION WILL BE ALLOWED BECAUSE OF THE CONTRACTOR MISUNDERSTANDING AS TO THE AMOUNT OF WORK INVOLVED OR THEIR LACK OF KNOWLEDGE OF ANY EXISTING CONDITION.
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text REFERENCE NOTES: REMOVE EXISTING PENDANT MOUNTED FLUORESCENT LUMINAIRES. MAINTAIN EXISTING CIRCUITRY FOR CONNECTION TO NEW. REMOVE EXISTING SURFACE MOUNTED FLUORESCENT LUMINAIRES. MAINTAIN EXISTING CIRCUITRY FOR CONNECTION TO NEW. EXISTING CEILING MOUNTED FIRE ALARM DEVICE SHALL BE REMOVED AND REINSTALLED FOR REPLACEMENT OF CEILING BY GC. COORDINATE WITH GC. EXISTING CEILING MOUNTED DUPLEX RECEPTACLE SHALL BE REMOVED AND REINSTALLED FOR REPLACENT OF CEILING BY GC. CORDINATE WITH GC.
AutoCAD SHX Text
NORTH
E301
LIGHTING PLAN
1/8" = 1'-0"
SO
LI
C
IT
AT
IO
N N
O
FI
LE
N
AM
E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K
AP
PR
D
AT
E:
FI
LE
N U
M
BE
R
SI
ZE
SU
BM
IT
TE
D B
Y:
PL
O
T
SC
AL
E:
PL
O
T D
AT
E:
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E
AP
PR
SHEET OF
US Army Corps of Engineers
AR
C
H
IT
EC
TS
E N
G
IN
EE
R
S
D
EM
ER
S
AV
E G
R
AN
D F
O R
KS
, N
D
YO
U
TH
A
R
EA
LI
G
H
TI
N G
F
IR
E
D O
O R
S
BL
D G
EL
EC
TR
IC
AL
L
IG
H
TI
N
G P
LA
N
E-301 8 8
W . H am lin
C . R et he m ei er W
. H am lin
1/ 8"
=1 '-0
/0 3/
AN
SI
D
EG
YN
2-
E-
1.
dw g
/0
3/
EG
YN
EG
YN
0% D
ES
IG
N S
U
BM
IT
TA
L
/1 5/
TELE FAX
3100 DeMers Avenue, Grand Forks ND 58201
701.775.3000 701.772.3605
LUMINAIRE SCHEDULE
TYPE MANUFACTURER CATALOG NAME LAMP MOUNTING LOCATION VOLTAGE CCT LUMENS* WATTS* NOTES DESCRIPTION
A LITHONIA CPHB 12000LM SEF GCL MD MVOLT GZ10 40K 80CRI
BAA LSXR6 DWH WGCPHBSM LED PENDANT CEILING MVOLT 4000 12,200 87
LED HIGH BAY WITH INTEGRAL MOTION SENSOR AND WIREGUARD
A/NL LITHONIA CPHB 12000LM SEF GCL MD MVOLT GZ10 40K 80CRI
BAA DWH WGCPHBSM LED PENDANT CEILING MVOLT 4000 12,200 87
LED HIGH BAY WITH WIREGUARD
B LITHONIA CSS L48 AL03 MBOLT SWW3 80CRI SFR7CSS WG BAA LED SURFACE CEILING MVOLT 4000 3000 26.3
4' SURFACE MOUNT LINEAR LED WITH MOTION SENSOR AND
WIREGUARD
*VARIES PER MANUFACTURER, FOR DESIGN PURPOSES ONLY.
REFERENCE NOTES:
1.
2.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S-1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
EL
AutoCAD SHX Text
EL
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text
PANEL
AutoCAD SHX Text L5
AutoCAD SHX Text
EL
AutoCAD SHX Text
LTG.
AutoCAD SHX Text
PNL.
AutoCAD SHX Text L3
AutoCAD SHX Text K
AutoCAD SHX Text
UP
AutoCAD SHX Text
PANEL L2
AutoCAD SHX Text REFERENCE NOTES: CONNECT NEW LUMINAIRES TO EXISTING CIRCUITRY LUMINAIRE TYPE A/NL SHALL REMAIN ON CONTINUALLY AS A NIGHT LIGHT. REVISE SWITCH CIRCUITRY AS NEEDED.
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text
A/NL
AutoCAD SHX Text
A/NL
AutoCAD SHX Text
A/NL
AutoCAD SHX Text
A/NL
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
NORTH
| EGYN 22-1004 - T-101-T-101 |
| EGYN 22-1004 - A-101-A-101 |
| EGYN 22-1004 - A-101-A-101 |
| EGYN 22-1004 - A-102-A-102 |
| EGYN 22-1004 - A-221-A-201 |
| EGYN 22-1004 - ELEC |
| EGYN 22-1004 - E-001-E-001 |
| EGYN 22-1004 - E-002-E-002 |
| EGYN 22-1004 - E-101-E-101 |
| EGYN 22-1004 - E-301-E-301 |