QAs Part II FA465924R0005 JFSD2011551 Bunch Hall Dorm 221.pdf

PDF 446 KB Posted

Attached to
JFSD201151 Repair (R&M) Bunch Hall Dorm 221 at Grand Forks AFB, ND
Solicitation number
FA465924R0005
Issued by

About this file

This document contains Questions and Answers (Q&As) from the Department of the Air Force 319th Contracting Squadron at Grand Forks Air Force Base related to Solicitation FA465924R0005 for the repair of Bunch Hall Dorm 221.

The key details are:

  • The solicitation is for a Firm-Fixed-Price Contract to repair Bunch Hall Dorm 221 at Grand Forks AFB, ND.
  • Questions were asked and answered regarding the coating required over the attic space foam, sidewalk reinforcement details, firestopping manufacturers, window specifications, stairwell tile and grid work, electrical/telecom requirements, and HVAC system cleaning.
  • No testing of installed windows is required, and the NETA certification requirement for the commissioning company will remain as specified.
  • Removal and disposal of existing furniture and appliances is to be addressed in a later amendment to the solicitation.

View the file

Other files

File Type Posted
Solicitation Amendment - FA465924R00050005.pdf PDF
38_JFSD_0221_A-205 Rev 18Sep24.pdf PDF
Solicitation Amendment FA465924R00050005 SF 30.pdf PDF
JFSD201151 Bid Schedule Rev 10Sep24.pdf PDF
QAs Part III FA465924R0005 JFSD2011551.pdf PDF
Solicitation Amendment FA465924R00050004 SF 30.pdf PDF
Solicitation Amendment - FA465924R00050004.pdf PDF
Solicitation Amendment - FA465924R00050003.pdf PDF
43_JFSD_0221_A-501 Rev 4Sep24.pdf PDF
JFSD201151 Wage Determination ND20240014 08302024.pdf PDF
22_JFSD_0221_AD 105 Rev 4Sep24.pdf PDF
46_JFSD_0221_A-601 Rev 4Sep24.pdf PDF
23_JFSD_0221_AD106 Rev 4Sep24.pdf PDF
Solicitation Amendment FA465924R00050003 SF 30.pdf PDF
UFGS 06 61 16 Rev 27Aug24.pdf PDF
Solicitation Amendment - FA465924R00050002.pdf PDF
Solicitation Amendment FA465924R00050002 SF 30.pdf PDF
FA465924R0005 Site Visit Sign-In Sheet.pdf PDF
Sheet P-302 revised 20 Aug 24.pdf PDF
Solicitation Amendment - FA465924R00050001.pdf PDF
QAs FA465924R0005 JFSD2011551 Bunch Hall Dorm 221.pdf PDF
Sheet PS102 revised 20 Aug 24.pdf PDF
Sheet E-503 revised 16 Aug 24.pdf PDF
Sheet P-501 revised 20 Aug 24.pdf PDF
Solicitation Amendment FA465924R00050001 SF 30.pdf PDF
Sheet S-102 revised 19 Aug 24.pdf PDF
UFGS 08 71 00 revised 21 Aug 24.pdf PDF
UFGS 01 45 00.00 10 revised 13 Aug 24.pdf PDF
Sheet ES101 revised 16 Aug 24.pdf PDF
Solicitation - FA465924R0005.pdf PDF
JFSD201151 Bid Schedule 06132024.pdf PDF
JFSD201151 Wage Determination ND20240014 07122024.pdf PDF
JFSD201151 Submittal Register.pdf PDF
JFSD201151 Specifications Rev 07172024.pdf PDF
JFSD201151 Past Performance Questionnaire Rev 06242024.docx DOCX document
JFSD201151 Financial Institution Reference Sheet.docx DOCX document
Solicitation - FA465924R0005.pdf PDF
JFSD201151 Drawings Revised 06172024.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF THE AIR FORCE

319TH CONTRACTING SQUADRON (ACC)

GRAND FORKS AIR FORCE BASE NORTH DAKOTA

06 September 2024

MEMORANDUM FOR CONTRACTORS

FROM: 319 CONS/PKA

295 Steen Blvd, Bldg. 242 Grand Forks AFB, ND 58205-6222

SUBJECT: Questions and Answers (Q&As) Part II for Solicitation FA465924R0005 JFSD201151 Repair Bunch Hall Dorm 221

1. Could you please provide clarification as to the coating required over the foam in the attic space? Are you looking for a weather protectant coating or are you looking for a fire protectant intumescent coating?

Response: Per section 07 57 13, part 2.4, provide intumescent coating.

2. Could you let us know what size and spacing reinforcing is in the sidewalks around Bunch Hall?

Response: Construction of sidewalks is not detailed in available as-built drawings.

3. I wasn’t able to find specific fire stop manufacturers called out in the specification. Are you accepting bids with different manufacturers? Or can you point me to where in the specification it specifically calls out the fire stop manufacturers?

Response: There is no requirement for specific firestopping manufactures. Firestopping must comply with section 07 84 00, Firestopping.

4. The plans and specifications are unclear as to whether the new “fixed aluminum F04” will be storefront such as Tubelite T14000 or aluminum windows such as Kawneer 5500. The specification seems to be a aluminum window number but doesn’t have a manufacturer nor model listed. The plan details are drawn as storefront but are tagged both ways. Please let us know how we should proceed.

Response: The specs are standard UFGS that call out performance criteria that the windows have to meet and will not say brand names or models of products. Drawings are generic window framing, and details were not specific to any particular brand or model of framing system.

5. Please confirm, are the end stairwells to receive new tiles in existing grid according to finish schedule note #1?

Response: Replace the grid. See revised sheets AD105, AD106, and A-601. Changes are identified with revision clouds.

6. Please confirm, are the center stairwells to receive new grid and tiles?

Response: Correct.

7. Please confirm, no ACT over the actual stairs (just the landing portion) on 1st and 2nd levels, but

ACT throughout entire stairwells on 3rd level?

Response: Correct.

8. On drawing E-503, it shows a 1 1/2" conduit with conductors going to the hinged consolidation box. It also shows dashed lines as future access control cabling. Are any access control cables required to be installed for this project?

Response: Access control cabling is not part of this project.

9. Please clarify the strand count for the fiber optic cables to the new telecommunications racks on

2nd and 3rd floor.

Response: Per section 27 10 00, a minimum 12 fiber cable to each comm room unless indicated otherwise and it is not indicate otherwise in the drawings, therefore, 12 fibers is the count.

10. Please clarify what is required for racks for the new telecommunication rooms- are they floor racks, wall mount, cabinets?

Response: Units are floor racks except NIPR wall cabinet in room 122.

11. Please confirm, is the contractor is responsible for rough-in only for the CCTV and card reader systems as part of this contract? Or is the contractor responsible for CCTV and card reader devices as well?

Response: The contractor is only responsible for the rough-in.

12. In the commissioning, It calls out for the commissioning company to be NETA certified. I have contacted MBN Engineering, and CMTA as well, and they are not NETA certified, but have commissioned electrical systems. Is there any way to relax that requirement a little so more regional companies are available to give pricing on that? Or is it a, “it is what it is”, type of thing?

Response: The NETA certification requirement will remain as specified.

13. I am unable to find anything in regards to what sink is to be used in the vanities. A color is listed that doesn’t exist anymore but no model of sink.

Response: Detail 2/A-401 Keynote 5 indicates that an integral solid surface sink is to be used in the dorm bathroom vanities. This is also shown and noted elsewhere in the architectural drawings.

Plumbing sheets also note it in the same manner. See revised spec section 06 61 16 for additional information. Changes are identified with a line in the left margin.

14. For window testing, will there be testing of installed windows, and how many would be tested?

Would the installed windows be tested for water and air infiltration, or just water? Can you tell us the exact AAMA test methods that are required?

Response: No testing of installed windows is required. Manufacturers should have necessary test reports available.

15. There is a spec section labeled “23 01 30.41 – HVAC SYSTEM CLEANING”, however, I am not seeing anything called out in the plans for cleaning the ductwork. My understanding of the project is that it is a complete removal/replacement of all of the HVAC ductwork and equipment and that none of the existing ductwork will be salvaged and reused. Do you know if this spec section was accidentally included in the spec book and is not applicable, or if there is in fact ductwork that will need to be cleaned?

Response: Spec section 23 01 30.41 applies to cleaning of newly installed HVAC during the final stages of construction.

16. Wall type 5A on sheet A-501 shows two instances of drywall, one layer in some locations and two layers in some locations. The corridor walls are wall type 5A. The door details on sheet A-701 show a single layer? What walls are the double layer used on?

Response: Only one layer of GWB is required. See revised sheet A-501. Changes are identified with revision clouds.

17. Does the Air Force have a list of approved commissioning companies to use that would cover the electrical requirement? Having a hard time finding one approved for electrical certification.

Response: GFAFB does not maintain, or know of, a list of approved commissioning companies.

18. Will the existing furniture and loose appliances be removed from the facility prior to the contractor’s arrival? Or will removal and disposal of these items be the contractor’s responsibility?

Response: An answer will be provided at a later date with another amendment to this solicitation notice.

Attachments:

1. UFGS 06 61 16 Rev 27Aug24

2. 22_JFSD_0221_AD 105 Rev 4Sep24

3. 23_JFSD_0221_AD106 Rev 4Sep24

4. 43_JFSD_0221_A-501 Rev 4Sep24

5. 46_JFSD_0221_A-601 Rev 4Sep24