05_50_13_-_Rev_19Jun18.pdf

PDF 580 KB Posted

Attached to
GFAFB Add/Repair Squadron Operations GSMP B541 Federal contract opportunity
Solicitation number
FA4659-18-R-0005
Issued by
Department of the Air Force Air Mobility Command

About this file

Section 05 50 13 Rev 19 June 2018

View the file

Other files for this federal contract opportunity

Other files attached to GFAFB Add/Repair Squadron Operations GSMP B541, newest first.
File Type Posted
135_JFSD_0541_EP403_-_Rev_26Jun18.pdf PDF
27_10_00_Rev_29Jun18.pdf PDF
19_JFSD_0541_A-101_-_Rev_26Jun18.pdf PDF
20_JFSD_0541_A-102_-_Rev_26Jun18.pdf PDF
155_JFSD_0541_E-601_-_Rev_27Jun18.pdf PDF
FA465918R00050003.pdf PDF
01_JFSD_0541_G-001COVR_-_Rev_26Jun18.pdf PDF
Amend_003_Questions_28Jun18.pdf PDF
134_JFSD_0541_EP402_-_Rev_26Jun18.pdf PDF
FA465918R00050002.pdf PDF
16_JFSD_0541_AD101_-_Rev_20Jun18.pdf PDF
08_34_73_-_Rev_21Jun18.pdf PDF
Amend_2_Questions_21Jun18.pdf PDF
Amendment_1_Q&A_18Jun18.pdf PDF
FA465918R0005P00001.pdf PDF
Attachment_10,_Updated_Specifications_and_Drawings.pdf PDF
Attachment_2h,_Electrical_Drawings.pdf PDF
Attachment_2c,_Architectural_Drawings.pdf PDF
Attachment_2a,_Schedule_of_Drawings.pdf PDF
Attachment_2f,_Plumbing_Drawings.pdf PDF
FA465918R0005.pdf PDF
Attachment_7,_PP_Questionnaire.pdf PDF
Attachment_9,_RFP_Cover_Letter.pdf PDF
Attachment_2g,_Mechanical_Drawings.pdf PDF
Attachment_1,_Technical_Specifications.pdf PDF
Attachment_2b,_Civil_and_Landscape_Drawings.pdf PDF
Attachment_2e,_Fire_Protection_Drawings.pdf PDF
Attachment_2d,_Structural_Drawings.pdf PDF
Attachment_8,_Construction_Wage_Rate_Determination.pdf PDF
Attachment_6,_Financial_Institution_Ref_Sheet.pdf PDF
Attachment_4,_Climatological_Summary.pdf PDF
Attachment_3,_Submittal_Register.pdf PDF
Attachment_5,_Green_Procurement_Waiver_Form.pdf PDF
Show all 33

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

{Add/Repair B541 Global Hawk GSMP - Grand Forks AFB, ND} {JFSD201801}

SECTION 05 50 13

MISCELLANEOUS METAL FABRICATIONS

05/10

PART 1 GENERAL

1.1 SCOPE

The work of this Section includes the following work items:

- Steel angles for floor infills

- Steel pipe bollards

- Expansion joint covers

- Exterior ramp/landing assembly at Server Rooms 163/164 exterior doors

1.2 RELATED WORK SPECIFIED ELSEWHERE

All other miscellaneous metal fabrications (for panel folding partition supports and exterior wall, window and louver supports, etc.) are included under Section 05 12 00 STRUCTURAL STEEL.

1.3 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN WELDING SOCIETY (AWS)

AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel

ASTM INTERNATIONAL (ASTM)

ASTM A123/A123M (2015) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products

ASTM A153/A153M (2016) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware

ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel

ASTM A47/A47M (1999; R 2014) Standard Specification for Ferritic Malleable Iron Castings

ASTM A500/A500M (2013) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes

ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless

SECTION 05 50 13 "REVISED 6.19.2018" Page 1

Attachment 10, FA465918R0005

ASTM A653/A653M (2015; E 2016) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM A780/A780M (2009; R 2015) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings

ASTM A924/A924M (2017a) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process

MASTER PAINTERS INSTITUTE (MPI)

MPI 79 (Oct 2009) Alkyd Anti-Corrosive Metal Primer

SOCIETY FOR PROTECTIVE COATINGS (SSPC)

SSPC SP 3 (1982; E 2004) Power Tool Cleaning

SSPC SP 6/NACE No.3 (2007) Commercial Blast Cleaning

1.4 QUALIFICATION OF WELDERS

Qualify welders in accordance with AWS D1.1/D1.1M. Use procedures, materials, and equipment of the type required for the work.

1.5 DELIVERY, STORAGE, AND PROTECTION

Protect from corrosion, deformation, and other types of damage. Store items in an enclosed area free from contact with soil and weather. Remove and replace damaged items with new items.

PART 2 PRODUCTS

2.1 MATERIALS

2.1.1 Structural Carbon Steel

ASTM A36/A36M.

2.1.2 Structural Tubing

ASTM A500/A500M.

2.1.3 Steel Pipe

ASTM A53/A53M, Type E or S, Grade B.

2.1.4 Fittings for Steel Pipe

Standard malleable iron fittings ASTM A47/A47M.

SECTION 05 50 13 "REVISED 6.19.2018" Page 2

2.2 FABRICATION FINISHES

2.2.1 Galvanizing

Hot-dip galvanize items specified to be zinc-coated, after fabrication where practicable. Galvanizing: ASTM A123/A123M, ASTM A153/A153M, ASTM A653/A653M or ASTM A924/A924M, G90, as applicable.

2.2.2 Galvanize

Anchor bolts, grating fasteners, washers, and parts or devices necessary for proper installation, unless indicated otherwise.

2.2.3 Repair of Zinc-Coated Surfaces

Repair damaged surfaces with galvanizing repair method and paint conforming to ASTM A780/A780M or by application of stick or thick paste material specifically designed for repair of galvanizing, as approved by Contracting Officer. Clean areas to be repaired and remove slag from welds. Heat surfaces to which stick or paste material is applied, with a torch to a temperature sufficient to melt the metallics in stick or paste; spread molten material uniformly over surfaces to be coated and wipe off excess material.

2.2.4 Shop Cleaning and Painting

2.2.4.1 Surface Preparation

Blast clean surfaces in accordance with SSPC SP 6/NACE No.3. Surfaces that will be exposed in spaces above ceiling or in attic spaces, crawl spaces, furred spaces, and chases may be cleaned in accordance with SSPC SP 3 in lieu of being blast cleaned. Wash cleaned surfaces which become contaminated with rust, dirt, oil, grease, or other contaminants with solvents until thoroughly clean. Steel to be embedded in concrete shall be free of dirt and grease. Do not paint or galvanize bearing surfaces, including contact surfaces within slip critical joints, but coat with rust preventative applied in the shop.

2.2.4.2 Pretreatment, Priming and Painting

Apply pretreatment, primer, and paint in accordance with manufacturer's printed instructions.

2.2.5 Nonferrous Metal Surfaces

Protect by plating, anodic, or organic coatings.

2.3 ACCESS DOORS AND PANELS

Provide flush type access doors and panels unless otherwise indicated.

Fabricate frames for access doors of steel not lighter than 14 gage with welded joints and anchorage for securing into construction. Provide access doors with a minimum of 14 by 20 inches and of not lighter than 14 gage steel, with stiffened edges and welded attachments. Provide access doors hinged to frame and with a flush-face, turn-screw-operated latch. Provide exposed metal surfaces with a shop applied prime coat. Provide a quantity of ten such access doors and panels for use in this project as described in Part 3 of this Section.

SECTION 05 50 13 "REVISED 6.19.2018" Page 3

2.4 INTERIOR EXPANSION JOINT COVERS

Provide expansion joint covers constructed of extruded aluminum with anodized satin aluminum finish for walls and ceilings. Furnish plates, backup angles, expansion filler strip and anchors as indicated.

2.5 BOLLARDS

Provide 6 inch galvanized standard weight steel pipe as specified in ASTM A53/A53M. Anchor posts in concrete as indicated and fill solidly with concrete with minimum compressive strength of 2500 psi.

2.6 MISCELLANEOUS PLATES AND SHAPES

Provide for items that do not form a part of the structural steel framework, such as lintels, sill angles, miscellaneous mountings and frames. Provide lintels fabricated from structural steel shapes over openings in masonry walls and partitions as indicated and as required to support wall loads over openings. Provide with connections and fasteners.

Construct to have at least 8 inches bearing on masonry at each end.

Provide angles and plates, ASTM A36/A36M, for embedment as indicated.

Galvanize embedded items exposed to the elements according to

ASTM A123/A123M.

PART 3 EXECUTION

3.1 GENERAL INSTALLATION REQUIREMENTS

Install items at locations indicated, according to manufacturer's instructions. Verify all measurements and take all field measurements necessary before fabrication. Exposed fastenings shall be compatible materials, shall generally match in color and finish, and harmonize with the material to which fastenings are applied. Include materials and parts necessary to complete each item, even though such work is not definitely shown or specified. Poor matching of holes for fasteners shall be cause for rejection. Conceal fastenings where practicable. Thickness of metal and details of assembly and supports shall provide strength and stiffness.

Form joints exposed to the weather shall be formed to exclude water. Items listed below require additional procedures.

3.2 WORKMANSHIP

Provide miscellaneous metalwork that is well formed to shape and size, with sharp lines and angles and true curves. Drilling and punching shall produce clean true lines and surfaces. Provide continuous welding along the entire area of contact except where tack welding is permitted. Do not tack weld exposed connections of work in place and ground smooth. Provide a smooth finish on exposed surfaces of work in place and unless otherwise approved, flush exposed riveting. Mill joints where tight fits are required. Corner joints shall be coped or mitered, well formed, and in true alignment. Accurately set work to established lines and elevations and securely fastened in place. Install in accordance with manufacturer's installation instructions and approved drawings, cuts, and details.

3.3 ANCHORAGE, FASTENINGS, AND CONNECTIONS

Provide anchorage where necessary for fastening miscellaneous metal items securely in place. Include for anchorage not otherwise specified or

SECTION 05 50 13 "REVISED 6.19.2018" Page 4 indicated slotted inserts, expansion shields, and powder-driven fasteners, when approved for concrete; toggle bolts and through bolts for masonry;

machine and carriage bolts for steel; through bolts, lag bolts, and screws for wood. Do not use wood plugs in any material. Provide non-ferrous attachments for non-ferrous metal. Make exposed fastenings of compatible materials, generally matching in color and finish, to which fastenings are applied. Conceal fastenings where practicable.

3.4 BUILT-IN WORK

Form for anchorage metal work built-in with concrete or masonry, or provide with suitable anchoring devices as indicated or as required. Furnish metal work in ample time for securing in place as the work progresses.

3.5 WELDING

Perform welding, welding inspection, and corrective welding, in accordance with AWS D1.1/D1.1M. Use continuous welds on all exposed connections.

Grind visible welds smooth in the finished installation.

3.6 FINISHES

3.6.1 Dissimilar Materials

Where dissimilar metals are in contact, protect surfaces with a coat conforming to MPI 79 to prevent galvanic or corrosive action.

3.6.2 Field Preparation

Remove rust preventive coating just prior to field erection, using a remover approved by the rust preventive manufacturer. Surfaces, when assembled, shall be free of rust, grease, dirt and other foreign matter.

3.6.3 Environmental Conditions

Do not clean or paint surface when damp or exposed to foggy or rainy weather, when metallic surface temperature is less than 5 degrees F above the dew point of the surrounding air, or when surface temperature is below 45 degrees F or over 95 degrees F, unless approved by the Contracting Officer.

3.7 ACCESS PANELS

Install a removable access panel not less than 12 by 12 inches directly below each valve, flow indicator, damper, or air splitter that is located above the ceiling, other than an acoustical ceiling, and that would otherwise not be accessible.

3.8 INSTALLATION OF BOLLARDS

Set pipe guards vertically in concrete piers. Construct piers of, and the hollow cores of the pipe filled with, concrete having a compressive strength of 3000 psi.

-- End of Section --