16170 Final Circuit and Motor Disconnects.pdf

PDF 38 KB Posted

Attached to
RECOVERY - SGBP080011 - Repair H Wing Elec, Lemay Fac
Solicitation number
FA4600-09-B-0007
Issued by

About this file

Attachment 1 Specs

View the file

Other files

File Type Posted
QA RECOVERY Repair H Wing Electrical RFI Final.doc DOC document
OFF-B-6072 Sheet 01 - Amendment 1 - May 09.dwf DWF file
OFF-B-6072 Sheet 04 - Amendment 1 - May 09.dwf DWF file
OFF-B-6072 Sheet 02 - Amendment 1 - May 09.dwf DWF file
FA4600-09-B-0007-0003.pdf PDF
Amendment 2.doc DOC document
Site Visit Sign in.pdf PDF
Amendment 1.doc DOC document
09000.pdf PDF
Atch 5 NCIC Data.doc DOC document
09250.pdf PDF
16124 Final Medium Voltage Cables.pdf PDF
Sheet 07-7.dwf DWF file
Section 1C H-WING.pdf PDF
16190 Final Supporting Devices.pdf PDF
Atch 4 offeror checklist.doc DOC document
08210.pdf PDF
08100.pdf PDF
16010 Final General Electrical.pdf PDF
Sheet 03-3.dwf DWF file
07900.pdf PDF
Section 1A H-WING.pdf PDF
09900.pdf PDF
Sheet 06-6.dwf DWF file
16452 Final Grounding.pdf PDF
Atch 3 General Decision Number.doc DOC document
06100.pdf PDF
Sheet 04-4.dwf DWF file
TOC - Repair Electrical H-Wing Stratcom.pdf PDF
08700.pdf PDF
16470 Final Panelboards.pdf PDF
06300.pdf PDF
Sheet 05-5.dwf DWF file
Cover Repair Electrical H-Wing STRATCOM.pdf PDF
16110 Final Raceways.pdf PDF
16460 Final Transformers.pdf PDF
Sheet 08-Layout.dwf DWF file
16135 Final Electrical Boxes and Fittings.pdf PDF
16482 Final Motor Control Centers.pdf PDF
Section 1B H-WING.pdf PDF
16361 Final Secondary Unit Substations.pdf PDF
02110.pdf PDF
Sheet 01-01.dwf DWF file
Solicitation.doc DOC document
16425 Final Switchboards.pdf PDF
Sheet 02-2.dwf DWF file
09650.pdf PDF
16120 Final Wires and Cables.pdf PDF
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

16170-1 (072125) 2009 by FEI

SECTION 16170

CIRCUIT AND MOTOR DISCONNECTS

PART 1 - GENERAL

1.1 SUMMARY

A. Extent of circuit and motor disconnect switch work is indicated on drawings and schedules.

B. Types of circuit and motor disconnect switches in this section include the following:

1. Equipment disconnects.

2. Appliance disconnects.

3. Motor-circuit disconnects.

C. Wires/cables, raceways and electrical boxes and fittings required in connection with circuit and motor disconnect work are specified in other Division 16 Sections.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS

A. Manufacturer: Subject to compliance with requirements, provide circuit and motor disconnects of one (1) of the following:

1. General Electric Co.

2. Siemens.

3. Square D Company.

4. Cutler-Hammer.

2.2 DISCONNECT SWITCHES

A. General-Duty Disconnect Switches: For switches rated less than 100-amps provide surface-mounted, general-duty type, sheet-steel enclosed switches, of types, sizes and electrical characteristics indicated; rated for system voltage, 60 Hz, with required number of poles and solid neutral incorporating spring assisted, quick-make, quick-break switches. Equip with operating handle which is integral part of enclosure base and whose operating position is easily recognizable and is capable of being padlocked in OFF position. Construct current carrying parts of high-conductivity copper, with silver-tungsten type switch contacts and positive pressure type reinforced fuse clips where fusing is required. The enclosure shall be NEMA rated to suit the atmospheric conditions of the equipment surroundings and of the manufacturer's standard finish.

When used as service disconnect, provide with UL markings indicating "suitable for use as service equipment".

B. Heavy-Duty Disconnect Switches: For switches rated 100-amps or greater provide surface-mounted, heavy-duty type, sheet-steel enclosed switches, of types, sizes and electrical characteristics indicated; rated for system voltage 60 Hz, with required number of poles and solid neutral incorporating quick-make, quick-break type switches. Equip with operating handle which is integral part of enclosure base and whose position is easily recognizable, and is padlockable in OFF position; construct current carrying parts of high-conductivity copper, with silver-tungsten type switch contacts, and positive pressure type reinforced fuse clips where fusing is required.

The enclosure shall be NEMA rated to suit the atmospheric conditions of the equipment

16170-2 (072125) 2009 by FEI surroundings and of the manufacturer's standard finish. When used as service disconnect, provide with UL markings indicating "suitable for use as service equipment".

C. Motor-circuit disconnect switches must be HP rated.

D. Fuses: Provide fuses for disconnect switches, as recommended by switch manufacturer, of classes, types and ratings needed to fulfill electrical requirements for service indicated.

PART 3 - EXECUTION

3.1 INSTALLATION OF MOTOR AND CIRCUIT DISCONNECT SWITCHES

A. Install circuit and motor disconnect switches where indicated, complying with manufacturer's written instructions, applicable requirements of NEC, NEMA and NECA's "Standard of Installation" and in accordance with recognized industry practices.

B. Coordinate motor and circuit disconnect switch installation work with electrical raceway work, location of equipment and as necessary for proper interface. Provide U-channel supports from floor and/or structure where required to mount disconnects at free-standing equipment.

C. Install disconnect switches used with motor-driven appliances, and motors and controllers within sight of controller position for motors greater than 1/8 HP.

3.2 GROUNDING

A. Provide equipment grounding connections, sufficiently tight to assure a permanent and effective ground as required by NEC and in Grounding Section of Division 16.

3.3 FIELD QUALITY CONTROL

A. Subsequent to completion of installation of electrical disconnect switches, energize circuitry and demonstrate capability and compliance with requirements. Where possible, correct malfunctioning units at Project Site, then retest to demonstrate compliance; otherwise remove and replace with new units and retest.

END OF SECTION