JB Charleston Question and Answer Final.xlsx
XLSX spreadsheet 31 KB Posted
- Attached to
- Repair MX Dock B578 and IMC Pavements Area F
- Solicitation number
- FA441825R0002
About this file
This document is a Questions and Answers (Q&A) file for a federal contract opportunity at Joint Base Charleston, South Carolina. The solicitation (FA441825R0002) involves repair and maintenance work for Dock B578 and IMC Pavements Area F, requiring comprehensive renovation services including structural, mechanical, electrical, and architectural modifications. Key project details include removing and replacing infrastructure elements such as a High Expansion Foam (HEF) concentrate tank, performing resinous flooring installation, updating door hardware, implementing lightning protection system updates, and renovating fire alarm systems.
The Q&A document addresses 32 specific contractor inquiries covering technical specifications, safety requirements, and project execution details. Notable requirements include: using Trane-standardized air cooled chillers, completing Level I Antiterrorism Awareness Training, submitting a cost-loaded Critical Path Method project schedule, and following specific surface preparation and coating standards for steel surfaces. The project will not occupy the building during renovation, and contractors must comply with base access and security protocols. The work is being executed by the Department of the Air Force Air Mobility Command, with an estimated project cost not disclosed in the document.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1 JB Charleston Offeror Question and Answer Form NOTICE TO OFFERORS Any offeror desiring an explanation or interpretation of the solicitation, drawings, specifications, etc., must request it in writing soon enough to allow a reply to reach all offerors before the submission of their proposals. Oral explanations or instructions given before the award of a contract will not be binding. Answers to offeror questions concerning a solicitation will be posted to sam.gov, if that information is necessary in preparing proposals or if the lack of it would be prejudicial to others.
| Solicitation Number | FA441825R0002 |
| Project Name: | Repair Maintenance Dock B578 and Repair IMC Pavements Area F |
| # | Specification Reference (Section & Paragraph Reference, i.e. 23 00 00, para 1.3) | Drawing Reference (Sheet and Detail or Note Reference, i.e. M-101, Detail 2) | Solicitation Reference (Section, paragraph, sub-paragraph Reference, i.e. Section M, Paragraph 2.3) | Attachments or Other (i.e. Submittal Register, Wage Determination, Site Visit Note, etc.) | |
| 1 | Question | ||||
| 4/A410 | The new 8'x8" access panel is shown behind the grab bar. 1. Confirm the chase wall construction is CMU. 2. Should this panel be below the grab bar so it can open? 3. Is there a valve in the wall to where this panel is required? | ||||
| Answer | |||||
| 22 00 00 | 3.3.6 | 1. Yes the chase wall for new 8'x8 access panel install is 6" CMU 2. Per Spec Section 22 00 00 Para 3.3.6 Access Panels shall be of sufficient size and located so that the concealed items may be serviced, maintained, or replaced. 3. Per Spec Section 22 00 00 Para 3.3.6 Access Panels shall be of sufficient size and located so that the concealed items may be serviced, maintained, or replaced. | ||||
| 2 | Question | ||||
| Keynote 8.30 on A400 | Any chance the base would have around 60 brick that already match for this CMU/ brick infill? | ||||
| Answer | |||||
| No | |||||
| 3 | Question | ||||
| Fuel Resistant Resinous Flooring 09 67 23.16 | Keynote 1.2 A100 | Please confirm the building will not be occupied during the renovation work. If the building is occupied, how many phases will the five coat floor system will we have to perform this in? | |||
| Answer | |||||
| Bldg will not be occupied | |||||
| 4 | Question | ||||
| G201 Security | States the contractor is provide and maintain security from a professional security firm at contractor access gates for the duration of use. Also states a guard stationed at each contractor access gate. 1. It papers the access for the bid option work will require a guard at Airfield gate V-4 as well as V-3, is this correct? | ||||
| Answer | |||||
| Gate guards will not be required. | |||||
| 5 | Question | ||||
| Solicitation - Bid Schedule | A413 blue keynote | Option Line Item 0003, states the structural steel to be painted as an option . A413 blue keynote also states apply new paint in entire hangar area. Please clarify if the wall panels and bottom of the roof deck is to be painted as well and if so, are the panels and deck to be in the base bid or bid option? | |||
| Answer | |||||
| The blue keynote on A413 through A416 applies to the structural members that are colored blue/purple in the pictures. "In entire hangar area" only intends to make it clear that this scope applies throughout the hangar bay area, not that the paint requirement extends beyond what is color-coded. | |||||
| 6 | Question | ||||
| FP051 | States to remove HEF concentrate tank. Please confirm the tank is empty and does contain hazardous material. If not FP051empty, are the contents of hazardous matinal, If so, what are the procedures disposing of the material? | ||||
| Answer | |||||
| For bid purposes the contractor shall assume that the tank is full (400 gallons). The High Expansion Foam (HEF) can be disposed of as a non-regulated waste (Non-RCRA). It shall be collected and disposed of IAW applicable local, state, and federal laws and regulations. It can be delivered to any class of landfill. Manifest shall be provided to 628 CES/CEIE | |||||
| 7 | Question | ||||
| Detail 2 on FP051 | On detail 2 there is a keynote 4, but cannot find what this is to be. Please clarify. | ||||
| Answer | |||||
| Each keynote 4 should be another keynote 3: "existing automatic wet-pipe sprinkler system to remain." | |||||
| 8 | Question | ||||
| AD120 | Keynote D01 does not state the frames to be removed while in the door and hardware specs, welded frames are stated. Please confirm the door frames are to remain in place. | ||||
| Answer | |||||
| Correct - the frames are existing to remain. | |||||
| 9 | Question | ||||
| Wage Scale Buildings | We do not have the Wage Scale for the Building, just Highway. Did we miss it? | ||||
| Answer | |||||
| 628 CONS has provided. | |||||
| 10 | Question | ||||
| G-200 - Keynote 3 | Keynote 3 states "contractor shall keep door on B578 accessible for duration of construction? 1. Please provide the needed width of the area that must be left accusable. 2. Is needed path for access to be hard surface, in otherwards the entire area is not to be removed at one time? | ||||
| Answer | |||||
| With Area F and B.578 being awarded to one contractor, KN #3 can be deleted. | |||||
| 11 | Question | ||||
| Lead Based Paint 02 02 00 00 | According to the abatement report, the paint on the building walls and CMU do not contain lead. Please confirm the shot blasting of the CMU walls for the resinous base as well as pressure washing the interior & exterior, no cost need to be included for testing or containment other than what is stated on the drawings to keep the debris from reaching the storm system | ||||
| Answer | |||||
| Correct | |||||
| 12 | Question | ||||
| 08 71 00, Door Hardware | A100 | Sheet A100 door schedule shows 14 doors to be replaced. Spec section 07 71 00 only shows hardware schedule for door 102B. Is the existing hardware to be reused on the other 13 doors? If to be new hardware, please provide the hardware schedule to be followed. | |||
| Answer | |||||
| See attached revised specification 08 71 00 Door Hardware and revised drawing A100 First Floor Plan | |||||
| 13 | Question | ||||
| 09 51 00 Acoustical Ceilings | Is there acoustical ceilings to be provided for the project? The ceiling plan is only showing gyp ceilings. | ||||
| Answer | |||||
| Install per Finish Schedule (A100) and Enlarged Floor Plan A400 | |||||
| 14 | Question | ||||
| 26 41 00 Lightning Protection System | A spec is provided for a lightning protection system but not noted on any of the drawings. 1. Is there to be a new lightning protection system for the building? 2.. Where is the desired location for the grounding system? Is there anywhere around the building where there is not existing concrete? Can the existing grounding system be reused? | ||||
| Answer | |||||
| Install lightning protection system per plans and specifications. Work is limited to the replacement of air terminals and conductors at the rooftop. Existing downleads are to be reused. See E001 and E004 | |||||
| 15 | Question | ||||
| M101 | In other buildings it has been standard to disconnect heating abilities when the hangar doors are left open by installing door switches. Will we need to install door switches to disable the infrared heaters? If so, do you want them on each roll up door and the hangar door, or only the hangar door? | ||||
| Answer | |||||
| Door switches to disable the infrared heaters will only be installed on the hangar doors. | |||||
| 16 | Question | ||||
| M003 BACnet Device Schedule | Will we be able to reuse existing controls conduits and wiring if they are in good shape? | ||||
| Answer | |||||
| Install per plans and specifications. | |||||
| 17 | Question | ||||
| 23 64 10 Section 2.4 | Will the air cooled chiller need to meet Joint Base Charleston's requirement to be standardized on Trane? | ||||
| Answer | |||||
| Yes. | |||||
| 18 | Question | ||||
| M003 BACnet Device Schedule | Is it the intention for the devices on this list to be connected to the existing Trane building controller and campus control system? | ||||
| Answer | |||||
| Yes | |||||
| 19 | Question | ||||
| Site Attendance List | Can you please add the contact information so we can get in touch with the contractors that attended? | ||||
| Answer | |||||
| Posted on Sam.gov | |||||
| 20 | Question | ||||
| E301 | E301 Fire Alarm Renovation Key note 1 states Install Duct Mounted Smoke Detector in Supply air Duct of AHU-1. Coordinate install with mechanical Contractor. Please confirm this is the only F/A Scope. | ||||
| Answer | |||||
| Refer to E053 and E301 for fire alarm scope | |||||
| 21 | Question | ||||
| FP051 | How big is the HEF tank? | ||||
| Answer | |||||
| 400 gallons | |||||
| 22 | Question | ||||
| 01 45 00 | Section 01 45 00 - Quality Control. Please confirm if a Quality Control Manager independent of the Project Superintendent is required or can one person dual hat the two roles. | ||||
| Answer | |||||
| 01 45 00 para. 3.2.5.1 | The QC Manager may not perform the duties of project superintendent. | ||||
| 24 | Question | ||||
| 01 14 00 para 1.3.1.3 | Are there any security/base access requirements to be aware of beyond the background check and Real ID required for badging? | ||||
| Answer | |||||
| Yes: JS-US007 - Level I Antiterrorism Awareness Training is required to be completed by all contractors within 30 days of requiring access, and annually thereafter. Coordination for training shall be by the contractor after contract award. This provision shall not apply to deliveries, contractors requiring access using single day passes, or any contractors requiring access for less than or equal to 180 continuous calendar days in a 1 year period. JS-US007 - Level I Antiterrorism Awareness Training can be located here: |
https://jko.jten.mil/courses/AT-level1/launch.html Submit all completion certificates to the Contracting Officer for information only.
| 27 | Question | |||
| 01 32 00, Para 3.2 | 01 32 00, Para 3.2 states "The Baseline Cost Loaded CPM Project Schedule shall be submitted for approval within 30 Calendar Days after the Notice of Award has been acknowledged." Please confirm the intent is for the Contractor to submit a cost loaded CPM Schedule prior to issuing Notice to Proceed (45-Calendar days after award). | |||
| Answer | ||||
| Correct. | ||||
| 28 | Question | |||
| 01 32 00, Para 1.1 | 01 32 00, Para 1.1 does not indicate an AF Form 3065 / AF Form 3064 to be submitted. Please confirm that this specification is for a Cost Loaded Critical Path Method (CPM) schedule to be utilized on a monthly basis for invoicing. | |||
| Answer | ||||
| Correct. | ||||
| 29 | Question | |||
| Wage Determination | After reviewing the project specification, could not find the Davis Bacon Wage & Determination for ( Construction Type Building) the only one provided as Wage & Determination for ( Highway). Please provide the wage determination for Construction Type: Building. | |||
| Answer | ||||
| 628 CONS has provided. | ||||
| 30 | Question | |||
| DWG G201 | Airspace 7460 notification by Contractors. Can we combined the site B 578 Hanger Renovation & IMC Pavement Area F as one 7460 notification to the FAA? | |||
| Answer | ||||
| If required the FAA 7460-1 could be combined. Unless a crane is being utilized a 7460-1 is not anticipated to be required. This project is approximately 2300 ft. from nearest runway and as long as the contractor stays below the height of the surrounding buildings the FAA Notification of Construction will not be required. | ||||
| 31 | Question | |||
| 09 97 13.00 40 | Specified steel coating primer is an inorganic zinc and is designed to be applied to abrasive blasted surface. Given the condition of the existing steel, the surface prep could be downgraded to an SP1, followed by an SP2 handtool cleaning and SP3 powertool clean of rusted surfaces. This would allow for a different coating system (surface tolerate epoxy): 1. Spot Prime with Carbomastic 94 epoxy or equal at 4-6 mils DFT 2. Full prime with the Carbomastic 94 epoxy or equal at 2-4 mils DFT 3. Finish coat with the carbothane 134HG or equal at 2-4 mils DFT . This would reduce the cost of the painting shop substantially. Would this be an acceptable to the Government? | |||
| Answer | ||||
| The Government will accept a surface tolerant polyamide epoxy for prime coat in lieu of the specified inorganic zinc primer. Surface prep can be downgraded from the specified SSPC-SP-10 (Near white metal blast cleaning) to SSPC-SP-1 (Solvent Cleaning), SSPC-SP-2 (Hand Tool Cleaning), and SSPC-SP-3 (Powertool Cleaning). Aliphatic polyurethane is specified for the top/finish coat, which this recommended system appears to include. | ||||
| 32 | Question | |||
| 09 67 23.16 / 1.3.5.5 | Qualification of Coating Contractors , All contractors that perform surface preperation or coating application must be certified to SSPC QP 8 and should also be SSPC QS 1 certified. Is this coating ceritification required for spec.(09 90 00 Paint and Coatings) and (09 97 13.00 40 Steel Coating) or just 09 67 23.16? | |||
| Answer | ||||
| There is no intent to make the coating requirements of the resinous flooring specification (09 67 23.16) apply to the paint (09 90 00) or steel coating (09 97 13.00 40) sections. |