This synopsis announces a solicitation for a Simplified Acquisition of Base Engineering Requirements (SABER) Indefinite Delivery/Indefinite Quantity (IDIQ) contract to provide maintenance, alterations, repair and minor construction work at Goodfellow Air Force Base and its recreation camp in Texas. The contractor will perform work on an as-needed basis using unit prices from a price book. This is a set-aside for certified 8(a) businesses located in Texas, with a NAICS code of 236220. A single award will be made for an initial 364-day period plus four one-year options. The minimum value is $300,000 and maximum is $10,000,000 over the life of the contract. An initial task order will meet the minimum. The request for proposal is expected on November 1st with a December 2nd closing date. Interested 8(a) businesses in Texas may submit proposals which will be considered by the Air Force. Questions must be submitted in writing to the listed Air Force points of contact by fax or email.
Attachment 7 - SABER Specifications Part 2
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SABER SPECIFICATIONS 2019
SECTION 10 28 13 Page 3 SPECIFICATIONS instructions for simplified wiring and control diagrams and other information necessary for unit maintenance.
1.3 CERTIFICATIONS
1.3.1 Baby Changing Stations
Provide certification that baby changing stations meet the performance criteria of ASTM F2285.
Provide certification that baby changing stations meet the requirements of ANSI Z535.4 Product Safety Signs and Labels.
Provide certification that baby changing stations meet the requirements of ASTM G21 Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi.
1.4 DELIVERY, STORAGE, AND HANDLING
Wrap toilet accessories for shipment and storage, then deliver to the jobsite in manufacturer's original packaging, and store in a clean, dry area protected from construction damage and vandalism.
1.5 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a 1 year period.
PART 2 PRODUCTS
2.1 MANUFACTURED UNITS
Provide toilet accessories where indicated in accordance with paragraph SCHEDULE. Porcelain type, tile-wall accessories are specified in Section 09 30 00 CERAMIC TILE QUARRY TILE, AND PAVER TILE. Provide each accessory item complete with the necessary mounting plates of sturdy construction with corrosion resistant surface.
2.1.1 Anchors and Fasteners
Provide anchors and fasteners capable of developing a restraining force commensurate with the strength of the accessory to be mounted and suited for use with the supporting construction. Provide tamperproof design exposed fasteners with finish to match the accessory.
2.1.2 Finishes
Except where noted otherwise, provide the following finishes on metal: Metal Finish Stainless steel No. 4 satin finish Carbon steel, copper alloy, Chromium plated, bright and brass.
2.2 ACCESSORY ITEMS
Conform to the requirements for accessory items specified below.
2.2.1 Facial Tissue Dispenser (FTD)
When required provide, per specific Task Order requirements, surface or recessed mounted facial tissue dispenser, Type 304 stainless steel face, satin finish. Secure face of recessed dispenser by friction with suitable spring steel clips. Provide a minimum capacity of 200 two-ply tissues for dispenser.
2.2.2 Grab Bar (GB)
When required, provide an 18 gauge, 1-1/4 inch grab bar OD Type 304 stainless steel. Provide form and length for grab bar as indicated.
Provide concealed mounting flange. Provide grab with satin finish. Furnish installed bars capable of withstanding a 500 pound vertical load without coming loose from the fastenings and without obvious permanent deformation. Allow 1-1/2 inch space between wall and grab bar.
2.2.3 Medicine Cabinet (MC)
SECTION 10 28 13 Page 4 SPECIFICATIONS
When required, construct medicine cabinet with cold-rolled carbon steel sheet of minimum 0.03 inch thickness, formed from a single sheet of steel or mechanically formed and spot welded. Provide width, height and depth of cabinet in accordance with specific Task Order requirements.
2.2.3.1 Sliding Door Cabinet, Class 1
When required, provide sliding door cabinet assembly with design and lighting arrangement per specific Task Order requirements. Provide a minimum of 2 shelves per cabinet. If required, provide a frame mirror per specific Task Order requirements.
2.2.3.2 Swinging Door Cabinet, Class 2
When required, furnish swinging door cabinet assembly, including the lighting arrangement, per specific Task Order requirements. Provide surface or recess mounted assembly per specific Task Order requirements. Locate cabinet centrally behind the door with a minimum of two shelves.
Provide stainless steel or carbon steel door hinges. Provide permanent type magnets used in door catches. Provide doors with or without a mirror per specific Task Order requirements.
2.2.4 Mirrors, Glass (MG)
When glass mirrors are required, provide Type I transparent flat type, Class 1-clear glass for mirrors. Glazing Quality q1 1/4 inch thick conforming to ASTM C 1036. Coat glass on one surface with silver coating, copper protective coating, and mirror backing paint. Provide highly adhesive pure silver coating of a thickness which provides reflectivity of 83 percent or more of incident light when viewed through 1/4 inch thick glass, free of pinholes or other defects. Provide copper protective coating with pure bright reflective copper, homogeneous without sludge, pinholes or other defects, of proper thickness to prevent "adhesion pull" by mirror backing paint. Provide mirror backing paint with two coats of special scratch and abrasion-resistant paint and baked in uniform thickness to provide a protection for silver and copper coatings which will permit normal cutting and edge fabrication.
2.2.5 Mirror, Metal (MM)
When metal mirrors are required, provide a brightly polished stainless steel metal mirror of 0.037 inch minimum thickness, edges turned back 1/4 inch and recess fitted with tempered hardboard backing, and theft-proof fasteners. Provide size per specific Task Order requirements.
2.2.6 Mirror, Tilt (MT)
When required, provide surface mounted tilt mirror with full visibility for persons in a wheelchair. Furnish adjustable tilt mirror, extending at least 4 inch from the wall at the top and tapering to 1 inch at the bottom.
Provide size in accordance with specific Task Order requirements. Conform to ASTM C 1036 and paragraph Glass Mirrors.
2.2.7 Paper Towel Dispenser (PTD)
When required, provide paper towel dispenser constructed of a minimum 22 gauge carbon steel, surface or recessed mounted per specific Task Order requirements. Furnish locking mechanism.
2.2.8 Combination Paper Towel Dispenser/Waste Receptacle (PTDWR) When required per specific Task Order, provide recessed or semi-recessed dispenser/receptacle with a capacity per specific Task Order requirements of C-fold, single-fold, or quarter-fold towel. Design waste receptacle to be locked in unit and removable for service. Provide key locking mechanism. Provide waste receptacle capacity per specific Task Order requirements. Fabricate a minimum 0.03 inch stainless steel welded construction unit with all exposed surfaces having a satin finish.
Provide waste receptacle that accepts reusable liner standard for unit manufacturer.
2.2.9 Sanitary Napkin Disposer (SND)
When required, construct a Type 304 stainless steel sanitary napkin disposal with removable leak-proof receptacle for disposable liners. Provide fifty disposable liners of the type standard with the manufacturer.
Retain receptacle in cabinet by tumbler lock. Provide disposer with a door for inserting disposed napkins, mounting per specific Task Order requirements.
SECTION 10 28 13 Page 5 SPECIFICATIONS
2.2.10 Shower Curtain (SC)
Provide shower curtain, size to suit conditions. Provide anti-bacterial nylon/vinyl fabric curtain. Furnish color per specific Task Order requirements.
2.2.11 Shower Curtain Rods (SCR)
Provide Type 304 stainless steel shower curtain rods 1-1/4 inch OD by 0.049 inch minimum straight to meet installation conditions.
2.2.12 Soap Dispenser (SD)
When required, provide soap dispenser surface mounted, liquid type consisting of a vertical Type 304 stainless steel tank with holding capacity of 40 fluid ounces with a corrosion-resistant all-purpose valve that dispenses liquid soaps, lotions, detergents and antiseptic soaps.
2.2.13 Soap Holder (SH)
When required, provide surface mounted or recessed Type 304 stainless steel soap holder. Provide stainless steel separate supports.
2.2.14 Shelf, Metal, Heavy Duty (SMHD)
When required, furnish a minimum 18 gauge stainless steel heavy duty metal shelf with hemmed edges.
Provide shelves over 30 inch with intermediate supports. Provide minimum of 16 gauge supports, welded to the shelf, and spaced no more than 30 inch apart.
2.2.15 Soap and Grab Bar Combination, Recessed (SGR)
When required, provide recessed type, Type 304 stainless steel soap and grab bar combination satin finish.
2.2.15 .1 Hand Sanitizer Dispenser (HSD)
Provide hand sanitizer dispensers complete with mounting brackets, batteries as recommended by manufacturer, sanitizer solution, and one bottle of refill sanitizer solution for each dispenser installed.
Dispenser properties and characteristics:
a. Wall mounted
b. Battery operated
c. Automatic, touchless type that dispenses sanitizer when a hand is placed in proximity of a sensor
d. Integral tray below the dispensing portal to catch wasted sanitizer
e. Operated using standard size batteries such as AA cells
2.2.16 Towel Bar (TB)
When required, provide stainless steel towel bar with a minimum thickness of 0.015 inch. Provide minimum 3/4 inch diameter bar, or 5/8 inch square. Provide satin finish.
2.2.17 Towel Pin (TP)
When required, provide towel pin with conCEIled wall fastenings, and a pin integral with or permanently fastened to wall flange with maximum projection of 4 inch. Provide satin finish.
2.2.18 Toilet Tissue Dispenser (TTD)
When required, furnish Type II - surface mounted toilet tissue holder with two rolls of standard tissue mounted horizontally or stacked vertically per requirements. Provide stainless steel, satin finish cabinet.
2.2.19 Toilet Tissue Dispenser, Jumbo (TTDJ)
When required, provide surface mounted toilet tissue dispenser with 2 rolls of jumbo tissue. Fabricate cabinet of high-impact plastic body and transparent plastic front cover. Provide cover with key lock.
2.2.20 Toothbrush and Tumbler Holder (TTH)
When required, provide stainless steel, surface mounted toothbrush and tumbler holder. Furnish holder to hold a minimum of four toothbrushes in a vertical position. Provide 2-1/4 plus or minus 1/8 inch in diameter
SECTION 10 28 13 Page 6 SPECIFICATIONS size of hole for securing tumbler.
2.2.21 Waste Receptacle (WR)
When required, provide Type 304 stainless steel waste receptacle, designed for recessed or surface per specific Task Order requirement mounting.
Provide reusable liner, of the type standard with the receptacle manufacturer. Capacity per specific Task Order requirement. Provide receptacles with push doors and doors for access to the waste compartment with continuous hinges. Furnish locking mechanism.
2.2.22 Electric Hand Dryer (EHD)
When required, provide wall mount and electric hand dryer designed to operate at 110/125 volts, 60 cycle, single phase alternating current with a heating element core rating of a maximum 2100 watts. Provide dryer housing of single piece construction and of white porcelain enamel.
2.2.23 Folding Shower Seat (FSS)
Folding shower seat shall have a frame constructed of type-304 satin finish stainless steel, 16-gauge, 1-1/4 inch square tubing, and 18-gauge, 1 inch diameter seamless tubing. Seat shall be constructed of one-piece, 1/2 inch thick water-resistant, ivory colored solid phenolic with black edge. Clearance between back of shower seat and wall shall be 1-1/2 inches to comply with ADA Accessibility Guidelines (ADAAG). Seat supports shall not come into contact with the floor. Seat shall be able to lock in upright position when not in use. Seat shall be attached to wall by two 3 inch diameter mounting flanges constructed of type-304, 3/16 inch thick stainless steel with satin finish. Manufacturer's service and parts manual shall be provided to building owner/manager upon completion of project.
2.2.24 Diaper Changing Station (DCS)
Provide [recess mount] [surface mounted] diaper changing station fabricated of high impact plastic with no sharp edges. Provide fold down platform concave to the child's shape, equipped with nylon and hook and loop safety straps and engineered to withstand a minimum static load of[ 340 lb] [ 250 lb]. Provide an integral dispenser for sanitary liners for each unit. Provide pictorial for universal use of safety graphics.
Provide stations that comply with these standards: ASTM F2285 Standard Safety Performance Specification for Diaper Changing tables for Diaper Changing Tables for Commercial Use; ANSI Z535.4 Product Safety Signs and Labels; and ASTM G21 Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi.
PART 3 EXECUTION
3.1 INSTALLATION
Provide the same finish for the surfaces of fastening devices exposed after installation as the attached accessory.
Do not install items that show visual evidence of biological growth. Provide oval exposed screw heads. Install accessories at the location and height indicated. Protect exposed surfaces of accessories with strippable plastic or by other means until the installation is accepted. After acceptance of accessories, remove and dispose of strippable plastic protection. Coordinate accessory manufacturer's mounting details with other trades as their work progresses. Use sealants for brackets, plates, anchoring devices and similar items in showers (a silicone sealant) as they are set to provide a watertight installation. After installation, thoroughly clean exposed surfaces and restore damaged work to its original condition or replace with new work.
3.1.1 Recessed Accessories
Fasten accessories with wood screws to studs, blocking or rough frame in wood construction. Set anchors in mortar in masonry construction. Fasten to metal studs or framing with sheet metal screws in metal construction.
3.1.2 Surface Mounted Accessories
Mount on conCEIled backplates, unless specified otherwise. ConCEIl fasteners on accessories without backplates. Install accessories with sheet metal screws or wood screws in lead-lined braided jute, teflon or neoprene sleeves, or lead expansion shields, or with toggle bolts or other approved fasteners as required by
SECTION 10 28 13 Page 7 SPECIFICATIONS the construction. Install backplates in the same manner, or provide with lugs or anchors set in mortar, as required by the construction. Fasten accessories mounted on gypsum board and plaster walls without solid backing into the metal or wood studs or to solid wood blocking secured between wood studs, or to metal backplates secured to metal studs.
3.2 CLEANING
Clean material in accordance with manufacturer's recommendations. Do mot use alkaline or abrasive agents.
Take precautions to avoid scratching or marring exposed surfaces.
-- End of Section --
SECTION 10 44 15 Page 1 SPECIFICATIONS Total Pages 5
SECTION TABLE OF CONTENTS DIVISION 10 – SPECIALTIES
SECTION 10 44 16
FIRE EXTINGUISHERS
05/15
PART 1 GENERAL
1.1 .............................................REFERENCES
1.2 .............................................SUBMITTALS
1.3 .............................................DELIVERY, HANDLING, AND STORAGE
2.1 .............................................TYPES
2.2 .............................................MATERIAL
2.3 .............................................SIZE
2.4 .............................................ACCESSORIES
2.5 .............................................CABINETS
2.5.1 ..........................................Material
2.5.2 ..........................................Type
2.5.3 ..........................................Size
2.6 .............................................WALL BRACKETS
3.1 .............................................INSTALLATION
3.2 .............................................ACCEPTANCE PROVISIONS
3.2.1 ..........................................Repairing
3.2.2 ..........................................Cleaning
-- End of Section Table of Contents --
SECTION 10 44 15 Page 2 SPECIFICATIONS
SECTION TABLE OF CONTENTS DIVISION 10 – SPECIALTIES
SECTION 10 44 16
FIRE EXTINGUISHERS
05/15
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM E814 (2013a; R 2017) Standard Test Method for Fire Tests of
Penetration Firestop Systems
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 1 (2018) Fire Code
NFPA 10 (2018; TIA 18-1) Standard for Portable Fire Extinguishers
NFPA 101 (2018; TIA 18-1; TIA 18-2; TIA 18-3) Life Safety Code
NFPA 241 (2013; Errata 2015) Standard for Safeguarding Construction, Alteration, and Demolition Operations
NFPA 303 (2016) Fire Protection Standards for Marinas and Boatyards
NFPA 385 (2012) Standard for Tank Vehicles for Flammable and
Combustible Liquids
NFPA 409 (2016; ERTA 2016) Standard on Aircraft Hangars
NFPA 418 (2016) Standard for Heliports
NFPA 505 (2018) Fire Safety Standard for Powered Industrial Trucks
Including Type Designations, Areas of Use, Conversions, Maintenance, and Operations
NFPA 99 (2018; TIA 18-1) Health Care Facilities Code
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.106 Flammable Liquids
29 CFR 1910.157 (2003) Portable Fire Extinguishers
UNDERWRITERS LABORATORIES (UL)
UL 154 (2005; Reprint May 2014) Carbon-Dioxide Fire Extinguishers
UL 2129 (2017) UL Standard for Safety Halocarbon Clean Agent Fire Extinguishers
SECTION 10 44 15 Page 3 SPECIFICATIONS
UL 299 (2012) Dry Chemical Fire Extinguishers
UL 626 (2005; Reprint Mar 2012) 2-1/2 Gallon Stored-Pressure, Water-
Type Fire Extinguishers
UL 8 (2016) UL Standard for Safety Water Based Agent Fire
Extinguishers
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals Manufacturer's Data for each type of required Fire Extinguisher with all related details, cabinets, accessories, and recommended operation manuals.
SD-02 Shop Drawings Submit fabrication drawings for the following items consisting of fabrication and assembly details performed in the factory. Submit installation drawings for the following items in accordance with the paragraph entitled, "Installation," of this section.
Fire Extinguishers Accessories Cabinets Wall Brackets
SD-03 Product Data Submit Manufacturer's catalog and warranty data for the following items:
Fire Extinguishers Accessories Cabinets Wall Brackets Replacement Parts
SD-04 Samples One of each type of Fire Extinguisher being installed One full-sized sample of each type of Cabinet being installed Three samples of Wall Brackets and Accessories of each type being used Approved samples may be used for installation, with proper identification and storage.
SD-07 Certificates Submit Certificates showing the following:
Certification that Fire Extinguishers comply with local codes and regulations.
Certification that Fire Extinguishers comply with OSHA, NFPA, and UL requirements.
Submit Manufacturer's Warranty with Inspection Tag on each extinguisher.
Guarantee that Fire Extinguishers are free of defects in materials, fabrication, finish, and installation and that they will remain so for a period of not less than 6 years after completion.
1.3 DELIVERY, HANDLING, AND STORAGE
Protect materials from weather, soil, and damage during delivery, storage, and construction.
Deliver materials in their original packages, containers, or bundles bearing the brand name and the name and type of the material.
1.3.1 Samples
Provide the following samples: one full-sized sample of each type of cabinet being installed; three samples of wall brackets and accessories of each type being used.
SECTION 10 44 15 Page 4 SPECIFICATIONS
Use approved samples for installation, with proper identification and storage.
2.1 TYPES
Provide Fire Extinguishers conforming to NFPA 10. Provide quantity and placement in compliance with the applicable sections of ICC IFC, Section 1414 and ICC IFC, Section 906, NFPA 1, NFPA 101,and 29 CFR 1910.157.
Provide manual handheld fire extinguishers equal to: 10 pound, multipurpose chemical, Class A, B, C equal to J.L.
Industries ACosmic 10E, Larsen's MP 10.
Submit Manufacturer's Data for each type of Fire Extinguisher required, detailing all related Cabinet, Wall Mounting and Accessories information, complete with Manufacturer's Warranty with Inspection Tag.
2.2 MATERIAL
Provide corrosion-resistant steel extinguisher shell.
2.3 SIZE
Provide size in accordance with specific Task Order requirements.
2.4 ACCESSORIES
Safety release
2.5 CABINETS
2.5.1 Material
Provide enameled steel cabinets.
2.5.2 Type
Provide recessed type cabinets.
2.5.3 Size
Dimension cabinets to accommodate the specified fire extinguishers.
2.6 WALL BRACKETS
Provide fire extinguisher wall brackets per specific Task Order requirements.
Provide wall bracket and accessories as approved.
Install Fire Extinguishers where indicated on the drawings. Verify exact locations prior to installation. Comply with the manufacturer's recommendations for all installations. Provide extinguishers which are fully charged and ready for operation upon installation. Provide extinguishers complete with Manufacturer's Warranty with Inspection Tag attached.
3.2 ACCEPTANCE PROVISIONS
3.2.1 Repairing
Remove and replace damaged and unacceptable portions of completed work with new work at no additional cost to the Government.
Provide Replacement Parts list indicating specified items replacement part, replacement cost, and name, address and contact for replacement parts distributor.
3.2.2 Cleaning
Clean all surfaces of the work, and adjacent surfaces which are soiled as a result of the work. Remove from the site all construction equipment, tools, surplus materials and rubbish resulting from the work.
SECTION 10 44 15 Page 5 SPECIFICATIONS
SECTION 12 21 00 Page 1 SPECIFICATIONS Total Pages 6
SECTION TABLE OF CONTENTS DIVISION 12 – FURNISHINGS
SECTION 12 21 00
WINDOW BLINDS
08/17
1.2 .............................................SUBMITTALS
1.3 .............................................SYSTEM DESCRIPTION
1.4 .............................................SUSTAINABLE DESIGN CERTIFICATION
1.5 .............................................DELIVERY, STORAGE, AND HANDLING
1.6 .............................................WARRANTY
2.1 .............................................WINDOW BLINDS
2.1.1 ..........................................Horizontal Blinds
2.1.1.1 .......................................Head Channel and Slats
2.1.1.2 .......................................Controls
2.1.1.3 .......................................Intermediate Brackets
2.1.1.4 .......................................Bottom Rail
2.1.1.5 .......................................Braided Ladders
2.1.1.6 .......................................Hold-Down Brackets
2.1.1.7 .......................................Audio Visual Blinds
2.1.2 ..........................................Vertical Blinds
2.1.2.1 .......................................Louvers
2.1.2.2 .......................................Carriers
2.1.2.3 .......................................Headrail System
2.1.2.4 .......................................Valance
2.1.2.5 .......................................Controls
2.1.2.6 .......................................Connectors and Spacers
2.1.2.7 .......................................Intermediate Brackets
2.2 .............................................COLOR
3.1 .............................................EXAMINATION
3.2 .............................................INSTALLATION
3.2.1 ..........................................Horizontal and Audio Visual Blinds 3..2.2 .........................................Vertical Blinds and Valance
3.2 .............................................CLEAN-UP
SECTION 12 21 00 Page 2 SPECIFICATIONS
SECTION 12 21 00
WINDOW BLINDS
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and
Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 701 (2015) Standard Methods of Fire Tests for Flame Propagation of
Textiles and Films
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical
Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES
SD-02 Shop Drawings Installation Drawings showing fabrication and installation details.
Show layout and locations of track, direction of draw, mounting heights, and details.
Window Blinds; G Recycled Content for aluminum components; S
Valance; G Samples of each type and color of window treatment.
Provides lats and louvers 6 inch in length for each color.
Provide 6 inch sample of horizontal blind slats or vertical louvers in each color specified.
SD-06 Test Reports Window Blinds Fire resistance, Flame Spread, and smoke contribution data.
Indoor Air Quality for window blinds; S
SECTION 12 21 00 Page 3 SPECIFICATIONS
SD-08 Manufacturer's Instructions
SD-10 Operation and Maintenance Data
1.3 SYSTEM DESCRIPTION
Provide window treatment, conforming to NFPA 701, complete with necessary brackets, fittings, and hardware.
Each window treatment type shall be a complete unit provided in accordance with paragraph WINDOW TREATMENT PLACEMENT SCHEDULE. Mount and operate equipment in accordance with manufacturer's instructions. Windows to receive a treatment shall be completely covered.
1.4 SUSTAINABLE DESIGN CERTIFICATION
Product shall be third party certified by GEI Greenguard Indoor Air Quality Certified, SCS Scientific Certification Systems Indoor Advantage or equal. Certification shall be performed annually and shall be current.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver components to the jobsite in the manufacturer's original packaging with the brand or company name, item identification, and project reference clearly marked. Store components in a dry location that is adequately ventilated and free from dust, water, or other contaminants and has easy access for inspection and handling. Store materials flat in a clean dry area with temperature maintained above 50 degrees F. Do not open containers until needed for installation unless verification inspection is required.
1.6 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a 1 year period.
2.1 WINDOW BLINDS
Provide each blind, including hardware, accessory items, mounting brackets and fastenings, as a complete unit produced by one manufacturer. All parts shall be one color, unless otherwise indicated, to match the color of the blind slat. Treat steel features for corrosion resistance.
2.1.1 Horizontal Blinds
Provide horizontal blinds with 1 inch slats. Blind units shall be capable of nominally 180 degree partial tilting operation and full-height raising. Blinds shall be inside or outside mount per specific Task Order requirements. Provide tapes for 2 inch slats with longitudinal reinforced vinyl plastic in 1-piece turn ladder construction. Tapes for 1 inch slats shall be braided polyester or nylon.
2.1.1.1 Head Channel and Slats
Provide head channel made of steel or aluminum with corrosion-resistant finish nominal 0.024 inch for 1 inch slats. Provide slats of aluminum, not less than 0.006 inch thick, and of sufficient strength to prevent sag or bow in the finished blind. Provide a sufficient amount of slats to assure proper control, uniform spacing, and adequate overlap. Enclose all hardware in the headrail.
2.1.1.2 Controls
The slats shall be tilted by a transparent tilting wand, hung vertically by its own weight, and shall swivel for easy operation. Provide a tilter control of enclosed construction. Provide moving parts and mechanical drive made of compatible materials which do not require lubrication during normal expected life. The tilter shall tilt the slats to any desired angle and hold them at that angle so that any vibration or movement of ladders and slats will not drive the tilter and change the angle of slats.
Include a mechanism to prevent over tightening. Provide a wand of sufficient length to reach to within 5 feet of the floor.
2.1.1.3 Intermediate Brackets
Provide intermediate brackets for installation, as recommended by the manufacturer, of blinds over
SECTION 12 21 00 Page 4 SPECIFICATIONS
60 inch wide.
2.1.1.4 Bottom Rail
Provide bottom rail made of corrosion-resistant steel with factory applied finish. Provide closed oval shaped bottom rail with double-lock seam for maximum strength. Bottom rail and end caps to match slats in color.
2.1.1.5 Braided Ladders
Provide braided ladders of 100 percent polyester yarn, color to match the slat color. Space ladders
15.2 slats per foot of drop in order to provide a uniform overlap of the slats in a closed position.
2.1.1.6 Hold-Down Brackets
Provide universal type hold-down brackets for sill or jamb mount where indicated on placement list.
2.1.1.7 Audio Visual Blinds
In addition to requirements for blinds, each unit shall include light traps at sides, and sill. Provide privacy blinds which provide light enhancing capabilities by means of hidden slat holes. Construct light traps from aluminum or sheet steel, not less than 0.02 inch thick, shaped, with legs not less than
0.75 inches long for 1 inch blinds.
Round or bead edges in contact with blinds.
Finish inside surfaces of light traps in a dull gray or black color.
2.1.2 Light Control and Privacy Blinds
In addition to requirements for horizontal blinds, provide each unit with a feature that offers hidden slat holes for maximum light control and privacy.
2.1.3 Vertical Blinds
Provide vertical blind units capable of nominal 180 degree partial tilting operation and full stackback. The blinds shall be listed by the manufacturer as designed for heavy duty strength applications including heavy duty hardware. Provide wall mounted vertical blinds with inside brackets. Blinds shall be sill length.
Outside mount type installation shall provide adequate overlap to control light and privacy.
2.1.3.1 Louvers
Provide louvers which are flame retardant fabric having straight, flat, unfrayed edges and flat, without notiCEIble twists. Provide a weight at the bottom of the louver without the insert discoloring the fabric.
Louvers that are 3-1/2 inch shall overlap not less than 3/8 inch or 2 inch shall overlap not less than 1/4 inch and be dimensionally stable.
2.1.3.2 Carriers
Provide carriers to support each louver made of molded plastic to transverse on self-fabricated wheels for smooth, easy operation. The hook of the carrier shall have an automatic latch to permit easy installation and removal of the louver, and to securely lock the louver for tilting and traversing.
2.1.3.3 Headrail System
Provide headrail system not less than 0.047 inch thick and made of anodized aluminum alloy or
0.027 inch thick phosphate treated steel with a baked on ivory gloss enamel paint finish. The headrail shall extend the full width of the blind and be closed with an end cap at each end. One cap shall contain the traversing and tilting controls. The opposite cap will house the pulley for the traversing cord.
2.1.3.4 Valance
Attach the manufacturer's standard valance to the headrail by metal or plastic holders which grip the top and bottom edge of the valance and accept an insert of the same material as the slats. Provide sufficient clearance behind the valance to permit the louvers to tilt without interference. Extend the
SECTION 12 21 00 Page 5 SPECIFICATIONS headrail cover the full width of the blind..
2.1.3.5 Controls
Provide tilting and traversing controls that hang compactly at the side of the blinds and reach within 5 feet of the floor. The tilt/traverse control or bead chain tilting control shall tilt all vanes simultaneously to any desired angle and hold them at that angle. Provide louvers that traverse one way to the right, one way to the left, or two-way split per specific Task Order requirements. The traversing control cord shall be minimum 0.070 inch in diameter with a minimum breaking strength of 125 pounds. Anchor the cord to a lead carrier linked to all adjacent carriers. Provide louvers that traverse along the headrail by pulling one side of the looped cord. Sliding glass doors shall have a one way draw with stackback occurring opposite door openings.
2.1.3.6 Connectors and Spacers
The connector shall be flexible, smooth and flat to slide unhindered when carriers move independently of each other, and to nest compactly when carriers are stacking. Relate the length of the links to the louver width in order to equally space the traversing louvers, to maintain uniform and adequate overlap of louvers, and to fully cover the width of the opening.
2.1.3.7 Intermediate Brackets
Provide intermediate installation brackets for blinds over 62 inches wide.
2.2 COLOR
Provide color, pattern and texture per specific Task Order requirements.
3.1 EXAMINATION
After becoming familiar with details of the work, verify all dimensions in the field, and advise the Contracting Officer of any discrepancy before performing the work.
3.2 INSTALLATION
3.2.1 Horizontal and Audio Visual Blinds
Perform installation of Horizontal and Audio Visual Blinds in accordance with the approved detail drawings and manufacturer's installation instructions. Install units level, plumb, secure, and at proper height and location relative to window units. Provide and install supplementary or miscellaneous items in total, including clips, brackets, or anchorages incidental to or necessary for a sound, secure, and complete installation. Do not start installation until completion of room painting and finishing operations.
3.2.2 Vertical Blinds and Valance
Perform installation of Vertical Blinds and Valance in accordance with the approved detail drawings and manufacturer's installation instructions.
Install units level, plumb, secure, and at proper height and location relative to window units. Provide and install supplementary or miscellaneous items in total, including clips, brackets, or anchorages incidental to or necessary for a sound, secure, and complete installation. Do not start installation until completion of room painting and finishing operations.
3.3 CLEAN-UP
Upon completion of the installation, free window treatments from soiling, damage or blemishes; and adjust them for form and appearance and proper operating condition. Repair or replace damaged units as directed by the Contracting Officer. Isolate metal parts from direct contact with concrete, mortar, or dissimilar metals. Ensure blinds installed in recessed pockets can be removable without disturbing the pocket. The entire blind, when retracted, shall be contained behind the pocket. For blinds installed outside the jambs and mullions, overlap each jamb and mullion 0.75 inch or more when the jamb and mullion sizes permit. Include all hardware, brackets, anchors, fasteners, and accessories necessary for a complete, finished installation.
SECTION 12 21 00 Page 6 SPECIFICATIONS
SECTION 12 48 13.13 Page 1 SPECIFICATIONS Total Pages 5
SECTION 12 36 00.00 20
MANUFACTURED VANITIES
08/18
1.3 .............................................DELIVERY, STORAGE, AND HANDLING
2.1 .............................................VANITIES
2.1.1 ..........................................Quantity
2.2 .............................................FINISHES
2.2.1 ..........................................Exposed Surfaces
2.2.2 ..........................................ConCEIled Surfaces
2.3 .............................................END CURBS
2.4 .............................................DRAWERS
2.5 .............................................SOURCE QUALITY CONTROL
3.1.1 ..........................................Final Assembly
3.1.2 ..........................................Fastening
SECTION 12 36 00.00 20 Page 2 SPECIFICATIONS
SECTION 12 36 00.00 20
MANUFACTURED VANITIES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN FOREST FOUNDATION (AFF)
ATFS STANDARDS (2015) American Tree Farm System Standards of Sustainability
2015-2020
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI A161.2 (1998) Decorative Laminate Countertops, Performance
Standards for Fabricated High Pressure
ASME INTERNATIONAL (ASME)
ASME B18.6.1 (2016) Wood Screws (Inch Series)
ASTM INTERNATIONAL (ASTM)
ASTM A1008/A1008M (2016) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM A167 (2011) Standard Specification for Stainless and Heat-Resisting
Chromium-Nickel Steel Plate, Sheet, and Strip
ASTM A325 (2014) Standard Specification for Structural Bolts, Steel, Heat
Treated, 120/105 ksi Minimum Tensile Strength
ASTM A325M (2014) Standard Specification for Structural Bolts, Steel, Heat
Treated, 830 MPa Minimum Tensile Strength (Metric)
ASTM D13 (2002) Standard Specification for Spirits of Turpentine
ASTM D2583 (2013a) Indentation Hardness of Rigid Plastics by Means of a
Barcol Impressor
ASTM D4689 (2012) Standard Specification for Adhesive, Casein-Type
ASTM D4690 (2012) Standard Specification for Urea Formaldehyde Resin
Adhesives
ASTM D570 (1998; E 2010; R 2010) Standard Test Method for Water
Absorption of Plastics
ASTM D638 (2014) Standard Test Method for Tensile Properties of Plastics
ASTM E84 (2018a) Standard Test Method for Surface Burning
Characteristics of Building Materials
SECTION 12 36 00.00 20 Page 3 SPECIFICATIONS
ASTM F594 (2009; E 2015) Standard Specification for Stainless Steel Nuts
ASTM F836M (2016, E 2018) Standard Specification for Style 1 Stainless Steel
Metric Nuts (Metric)
CALIFORNIA AIR RESOURCES BOARD (CARB)
CARB 93120 (2007) Airborne Toxic Control Measure (ATCM) to Reduce
Formaldehyde Emissions from Composite Wood Products
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and
COMPOSITE PANEL ASSOCIATION (CPA)
CPA A208.1 (2016) Particleboard
CSA GROUP (CSA)
CSA Z809-08 (R2013) Sustainable Forest Management
FOREST STEWARDSHIP COUNCIL (FSC)
FSC STD 01 001 (2015) Principles and Criteria for Forest Stewardship
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS (IAPMO)
IAPMO Z124.3 (2005) Plastic Lavatories
INTERNATIONAL CODE COUNCIL (ICC)
ICC IPC (2018) International Plumbing Code
KITCHEN CABINET MANUFACTURERS ASSOCIATION (KCMA)
KCMA A161.1 (2017) Performance & Construction Standards for Kitchen and
Vanity Cabinets
MASTER PAINTERS INSTITUTE (MPI)
MPI 28 (2012) Varnish, Marine Spar, Exterior, Gloss (MPI Gloss Level
6)
MPI 91 (2012) Paste, Wood Filler
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI/NEMA LD 3 (2005) Standard for High-Pressure Decorative Laminates
PROGRAMME FOR ENDORSEMENT OF FOREST CERTIFICATION (PEFC)
PEFC ST 2002:2013 (2015) PEFC International Standard Chain of Custody of Forest
Based Products Requirements
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SCIENTIFIC EQUIPMENT AND FURNITURE ASSOCIATION (SEFA)
SEFA 7 (2007) Recommended Practice for Laboratory and Hospital
Fixtures
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
SECTION 12 36 00.00 20 Page 4 SPECIFICATIONS
SUSTAINABLE FOREST INITIATIVE (SFI)
SFI 2015-2019 (2015) Standards, Rules for Label Use, Procedures and Guidance
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
CID A-A-59295 Corrosion Preventive Compounds, Cold Application(For New
And Fielded Motor Vehicles And Trailers)
FS FF-S-325 (Basic; Int Amd 3; Notices 3, 4) Shield, Expansion; Nail, Expansion; and Nail, Drive Screw (Devices, Anchoring, Masonry)
FS MM-L-736 (Rev D; Notice 1) Lumber; Hardwood
FS TT-C-490 (Rev F; Am 3) Cleaning Methods for Ferrous Surfaces and
Pretreatments for Organic Coatings
FS WW-P-541 (Rev E; Am 1; Notice 1) Plumbing Fixtures
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
40 CFR 770 Formaldehyde Standards for Composite Wood Products
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical
Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings Vanities; G Show configuration, materials, thicknesses, hardware, finishes, and colors of vanities for the project.
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver vanities undamaged and store in a safe, dry, and clean location. Handle so as to prevent damage.
2.1 VANITIES
CID A-A-50567, Type I (single lavatory, double doors), Size per specific Task Order requirements, and except as specified herein. Wood construction shall be used. Particleboard shall not be used. Doors, and all wood panels shall be 3/4 inch plywood, APA PS 1, Exterior Type, Grade A-A. Counter tops shall be medium density fiberboard (MDF). Chromium-plated brass pulls or aluminum pulls and chromium-plated, spring-loaded, self-closing, adjustable, European type hinges may be used in lieu of pulls, hinges, and magnetic catches specified in
CID A-A-50567.
2.1.1 Quantity
Per specific Task Order requirements.
2.2 FINISHES
Five-digit designations refer to FED-STD-595.
2.2.1 Exposed Surfaces
Exterior of doors and exposed surfaces of cabinet body shall be decorative laminated plastic of color and
SECTION 12 36 00.00 20 Page 5 SPECIFICATIONS pattern per specific Task Order requirements.
2.2.2 ConCEIled Surfaces
Interior of doors and cabinet body, and conCEIled exterior surfaces of cabinet body, shall be nondecorative laminated plastic.
2.3 END CURBS
Provide end curbs to match back splash where end of countertop abuts a wall.
2.4 DRAWERS
Where drawers are indicated in vanities, comply with CID A-A-50565 for drawers, drawer slides, and slide supports.
2.5 SOURCE QUALITY CONTROL
Sampling and Examination: CID A-A-50567.
3.1.1 Final Assembly
Distribute vanities to rooms per specific Task Order requirements. Uncrate, assemble, adjust as necessary, and place as specified or indicated, complete with accessories and hardware. Position vanities per specific Task Order requirements.
3.1.2 Fastening
Fasten wood vanities as specified in CID A-A-50567. Fasten steel vanities through the holes in vanity back flanges. Fasteners shall be appropriate for use with the wall construction. Seal joint between back splash and wall and between end curb and wall as specified in Section 07 92 00 JOINT SEALANTS.
SECTION 12 48 13.13
ENTRANCE FLOOR MATS
1.3 .............................................QUALITY ASSURANCE
2.1 .............................................AFFIRMATIVE PROCUREMENT
2.2 .............................................TYPE OF MATS
2.2.1 ..........................................Entrance and Floor Mats
2.2.1.1 .......................................Carpet-Type Mats
3.1 .............................................DELIVERY OF MATERIALS
3.2 .............................................EXAMINATION
3.3 .............................................INSTALLATION
SECTION 12 48 13.13 Page 2 SPECIFICATIONS
SECTION 12 48 13.13
ENTRANCE FLOOR MATS
The publications listed below form a part of this specification to the extent referenced. The publications are
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum- Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM B221M (2013) Standard Specification for Aluminum and Aluminum-
Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric)
ASTM D2047 (2017) Standard Test Method for Static Coefficient of Friction of
Polish-Coated Floor Surfaces as Measured by the James Machine
ASTM E648 (2017a) Standard Test Method for Critical Radiant Flux of
Floor-Covering Systems Using a Radiant Heat Energy Source
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility GuidelinesASTM C 501 (1984; R 2009) Relative Resistance to Wear of Unglazed Ceramic Tile by the Taber Abraser
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings Installation Drawings; G Detail Drawings; G Custom Graphics Drawings; G
Entrance Floor Mats G Adhesives and Concrete Primers; G Submit Manufacturer's Data and indicate percentage of recycled material content in protective flooring materials Entrance and Floor Mats to verify affirmative procurement compliance.
Submit total weight and volume quantities of protective flooring materialswith recycle materials content.
SECTION 12 48 13.13 Page 3 SPECIFICATIONS
Entrance Floor Mats ; G Custom Graphics; G Submit manufacturer's standard color charts for Entrance and Floor Mats showing the manufacturer's recommended color and finish selections.
Submit one sample 12 inch square, assembled sections of floor mat to show corners, intersections, and other details of construction.
Provide any graphics in drawing for approval.
SD-08 Manufacturer's Instructions Manufacturer's Instructions
Protection, Maintenance, and Repair Information
1.3 QUALITY ASSURANCE
Comply with Section 4.5 in the U.S. Architectural & Transportation Barriers Compliance Board's "Americans with Disabilities Act (ADA), Accessibility Guidelines for Buildings and Facilities (ADAAG) for installed entrance and floor mats.
Submit documentation of testing and compliance with the following standards:
a. Rubber based products: ASTM C 501, ASTM D 2047, ASTM D 2240.
b. Carpet based products: ASTM E 648, ASTM F 150, CRI 104.
c. Other materials: ASTM C 501, ASTM D 2047, ASTM D 2240, ASTM E 648, ASTM F 150, ASTM F 1869.
Deliver materials to the project site in their original packages or containers bearing labels clearly identifying the manufacturer, brand name, and quality or grade.
Store materials in their original unbroken packages or containers in the area in which they will be installed.
Unwrap, inspect, and place mats at indicated locations. Remove all excess packing materials.
2.1 AFFIRMATIVE PROCUREMENT
The Environmental Protection Agency (EPA) has designated certain items which must contain a specified percent range of recovered or recycled materials. EPA designated products specified in this contract comply with the stated policy and with the EPA guidelines. Make all reasonable efforts to use recycled and recovered materials in providing the EPA designated products and in otherwise utilizing recycled and recovered materials in the execution of the work. These items, when incorporated into the work under this contract, are to contain at least the specified percentage of recycled or recovered materials unless adequate justification (non-availability) for non-use is provided, per 40 CFR 247.
Mats are listed in the EPA's Comprehensive Procurement Guidelines (CPG ) at http://www.epa.gov/epaoswer/non-hw/procure/products/mats.htm.
EPA's recommended Recovered Materials Content Levels for Mats.
Product Material Percent Of Post Percent Of Total Consumer Materials Recovered Materials Mats Rubber 75 - 100 85 - 100
Plastic 10 - 100 100
Rubber/ 100 100
SECTION 12 48 13.13 Page 4 SPECIFICATIONS
Plastic composite
The recommended recovered materials content levels are based on the dry weight of the raw materials, exclusive of any additives such as adhesives, binders, or coloring agents.EPA's recommendation does not preclude procuring agencies from purchasing mats manufactured from another material. It simply recommends that procuring agencies, when purchasing mats made from rubber or plastic, purchase these items made from recovered materials.
For informational purposes, a list of known sources for mats using recycled material is provided in the EPA/CPG Supplier database at http://www.ergweb2.com/cpg4review/user/cpg_search.cfm.
Note that the Contractor is not limited to these sources. A product meeting CPG recycle requirements from other sources may be submitted for the Government's approval.
Submit recycled material content data for protective flooring materials indicating compliance with affirmative procurement.
Submit total weight and volume quantities of protective flooring materials with recycle material.
2.2 TYPE OF MATS
2.2.1 Entrance and Floor Mats
Furnish the following type of entrance mat :
2.2.1.1 Carpet-Type Mats
a. Carpet shall meet the Carpet and Rug Institute's standard for indoor air quality.
Fibers shall include a minimum of 100, 12 mil monofilament fibers per aquare inch and colorfast, solution-dyed nylon. Each carpet fiber and monfilament shall be fusion-bonded to a rigid two-ply backing to prevent fraying and supplied in continuous splice-free lengths. Carpet weight shall be 33 -oz per square yard.
b. Bond carpet mats to 1/8 inch to 1/4 inch thick flexible vinyl backing to form mats 3/8 inch or 7/16 inch thick with non-raveling edges.
c. Color of Carpet-Type Mats - per specific Task Order requirements.
d. Size of Carpet-Type Mats - per specific Task Order requirements
Floor Grid shall be extruded 6105-T5 aluminum alloy tread rails joined mechanically by extruded 6106-T6 aluminum alloy key lock bars (welding or bolting shall not be permitted). Rail finish to be anodized bronze.
Grid Frame to be level base frame and shall be 6063-T5 aluminum alloy with 1/2 inch exposed surface and a depth of 1-13/16 inch. These assemblies recieve 1/4" thick heavy gauge support cushions 1 inch long mounted to each continuous foot at 20 inches on center. Frame color should be supplied in anodized bronze finish.
3.1 DELIVERY OF MATERIALS
Deliver materials to the project site in their…