Attachment 4 - Generator Scope Details Rev.1, 19Aug2024.pdf
PDF 264 KB Posted
- Attached to
- Repair Well #10 Federal contract opportunity
- Solicitation number
- FA301024R0013
About this file
This document is the Generator Scope Details for Solicitation FA301024R0013, Repair Well #10, a construction contract opportunity issued by the Department of the Air Force Air Education and Training Command.
The scope requires the contractor to provide and install a 150 kW standby diesel generator, automatic transfer switch, and 500-gallon diesel fuel tank for Building 7301. The generator and associated equipment must have redundant and separate components such as fuel pumps, oil sensors, spark plugs, and other sub-equipment. The contractor is also responsible for wiring the generator to the ATS and existing electrical system, as well as plumbing the diesel tank to the generator. The contractor must test the generator and provide a manufacturer's representative to witness the test. The contract value is between $250,000 and $500,000, and it is set aside for small businesses. An organized site visit is scheduled for August 12, 2024 at 9:00 AM Central Daylight Time.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Generator Scope Details Rev. 1 MAHG 231035 Repair Well #10
19 August 2024
1. SCOPE: Provide Generator, ATS, & Diesel Fuel Tank for Bldg 7301.
Notes:
A. Contractor shall provide and maintain filters, temporary dust barriers, etc. to prevent construction dust and debris from spreading throughout Bldg 7301, adjacent areas, Fire System Devices, and IT equipment, and other spaces.
B. Contractor shall provide constant daily cleaning of the work area.
C. Contractor is responsible for the repair/replacement of items damaged during construction at their own cost.
1.1 CONTRACTOR TO REMOVE & INSTALL:
Bldg 7301surrounding area
A. Install ATS outside Bldg 7301
B. Wire Generator to ATS and from existing electrical source, at Bldg 7301.
C. Wire ATS to existing electrical system.
D. Plumb Diesel Tank to generator.
E. Test run generator following manufacturer’s instructions, with manufacturer’s representative as a witness.
Mechanical / Electrical Demolition work shall be accomplished per drawings and specifications given in the SOW.
1.2 CONTRACTOR TO MODIFY EXISTING:
Mechanical / Electrical work to modify existing building components.
shall be accomplished per drawings and specifications given in the
SOW.
1.2.1 CONTRACTOR TO PROVIDE AND INSTALL NEW:
Building 7301 –
A. Generator
B. ATS, outside bldg. 7301.
C. Diesel tank immediately north of the generator
Mechanical / Electrical Installation work shall be accomplished per drawings and specifications given in the SOW.
Attachment 4
FA301024R0013
MAHG23-1035 Repair Well #10
Generator Scope Details Rev. 1 MAHG 231035 Repair Well #10
19 August 2024
4.1 SPECIAL GENERATOR CONSIDERATIONS
4.1.1 150 KW STANDY; 480 VAC WYE OUTPUT, 60 HERTZ, DIESEL FUEL WITH
DAY TANK AND 500 GALLON MAIN TANK PLUMBED TO DAY TANK.
4.1.2 TWO OF EACH OF THE FOLLOWING SUB EQUIPMENT: FUEL PUMPS
WITH DIFFERENT INJECTION LOCATIONS; EACH PUMP WITH ITS OWN
FUEL LINE; OIL SENSORS AT SEPARATE LOCATIONS; SPARK PLUGS AT
SEPARATE LOCATIONS; FUEL GAUGES AT SEPARATE LOCATIONS;
FUEL PRESSURE INDICATION AT SEPARATE BUT NEAR EQUAL
LOCATIONS; FUEL FILTERS AT SEPARATE LOCATIONS IN PARALLEL
FUEL LINES; FUEL VALVES FOR ALL FUEL LINES IN PARALLEL; OIL
LEVEL SENSORS AT SEPARATE LOCATIONS; ENGINE BLOCK HEATERS
AT SEPARATE LOCATIONS; BLOWBY STACKS AT SEPARATE
LOCATIONS; VOLTAGE REGULATORS AT SEPARATE LOCATIONS
AUTOMATICALLY SWITCHED BETWEEN EACH OTHER AS NEEDED;
AIR FILTERS AT SEPARATE LOCATIONS; ANTI CONDENSATION
HEATERS AT SEPARATE LOCATIONS; VIBRATION MEASUREMENT
NEAR BEARINGS AT SEPARATE LOCATIONS; DIODES CONDITION
REPORTING; GENERATOR WINDINGS REPORTING FROM TWO
SEPARATE LOCATONS INCLUDING CURRENT, RESISTANCE, AND
VOLTAGE. SENSORS FOR ALL OF THE ABOVE TO REPORT TO TWO
SEPARATE CONTROLLERS.
4.1.3 AUTOMATIC TRANSFER SWITCH (ATS) 480 VAC WYE MOUNTED
OUTSIDE; NEMA 3R; WIRED FOR POWER TRANSFER
4.1.4 500 GALLON DIESEL TANK NEXT TO DAY TANK WITH PLUMBING TO
DAY TANK.