The document is an architectural drawing (A-310) detailing wall sections and plan details for the DTRA Renovation project on the 3rd floor of Building 13A at Eglin Air Force Base, Florida. The drawing provides technical specifications for security wall construction, including:
Key technical specifications include 3 5/8" 16Ga galvanized metal studs at 16" on center, two layers of 5/8" gypsum wallboard, RF shielding, acoustical sealant, and sound insulation. The wall types are designed for Sound Group 4 with a minimum Sound Transmission Class (STC) of 50, and are compliant with ICS 705 and UFC-4-010-05 standards. The drawing includes details for wall sections, column enclosures, control joints, and specific requirements for secure areas like SCIF (Sensitive Compartmented Information Facility) spaces, with particular attention to sound isolation, RF shielding, and construction techniques for secure environments.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 04 20 00.pdf | ||
| 08 71 00.pdf | ||
| 06 41 16.00 10.pdf | ||
| AD-101 DEMOLITION PLAN.pdf | ||
| A-110 NEW WORK REFLECTED CEILING PLAN.pdf | ||
| DTRA 13A 3rd Floor RFIs_all_Contracting_FINAL.docx | DOCX document | |
| A-311 WALL SECTIONS.pdf | ||
| EGLIN EMCS AND-OR DDC SYSTEM REQUIREMENTS.pdf | ||
| A-312 WALL SECTIONS.pdf | ||
| 22 00 00.pdf | ||
| Addendum 1 _DTRA Renovation 3rd Floor Bldg 13a.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KEYNOTES:
3 5/8" 16Ga GALVANIZED STUD TRACK SET IN 2 BEADS ACOUSTICAL SEALANT
RUBBER WALL BASE, SEE FINISH SCHEDULE SHEET I-601.
2' X 2' X 3/4" THICK LAY-IN ACOUSTICAL CEILING TILE AND GRID SYSTEM, TYPICAL.
SEE FINISH SCHEDULE SHEET I-601. GYPSUM WALLBOARD CEILING AT COMM
ROOMS 382 AND 382A.
ACOUSTICAL SEALANT, CONTINUOUS EACH SIDE, TOP AND BOTTOM OF WALL
EXISTING CONCRETE DECK
EXISTING FLOOR SLAB
(2) LAYERS 5/8" GYPSUM WALL BOARD, EXTEND TO EXISTING CONCRETE
STRUCTURE ABOVE WITH ACOUSTICAL SEALANT AT FLOOR AND CONCRETE DECK
ABOVE. FIRST LAYER SHALL BE TAPED AND MUDDED BUT NOT FINISHED. SECOND
LAYER SHALL BE TAPED AND MUDDED AND FINISHED CONTINUOUS TO UNDERSIDE
OF EXISTING CONCRETE STRUCTURE ABOVE AND SEAL. ALL JOINTS SHALL BE
STAGGERED ON BOTH LAYERS.
3 1/2" SAFB INSULATION WHERE INDICATED
EXISTING CONCRETE COLUMN
2 1/2" 16Ga GALVANIZED METAL STUDS
3 5/8" 16Ga GALVANIZED METAL STUDS @ 16" O.C.
14 FRICTION FIT SAFB, FILL CAVITY COMPLETELY
EXISTING WALL CONSTRUCTION
rFOIL SHIELDING (PERFORATED), WRAP AT FLOOR AND SECURE GYPSUM BOARD
CEILING ABOVE. LAP 8" MIN. PROVIDE CONT. RF SHIELDING OVER EXISTING
CONCRETE DECK INSIDE SECURE BOUNDARY.
15 GALVANIZED UNISTRUT SYSTEM (1 5/8" X 1 5/8" 12 GA. P1000) AT 24"
ATTACHED TO GYPSUM BOARD CEILING STUD JOISTS. SECURE W/ 1/4"
HEX WASHER HEAD SCREWS AT EACH JOIST
16 MITEK RT/S7A S/2.5 W/ (2) 3/16" x1" EMBEDMENT TAPCON ANCHOR TO CONCRETE
JOIST & #10 SCREWS TO LTGA JOIST, @EA. INTERSECTION
17 (2) LAYERS 5/8" GYPSUM WALL BOARD, SECURE TO UNDERSIDE OF CEILING JOIST
FRAMING. FIRST LAYER SHALL BE TAPED AND MUDDED BUT NOT FINISHED.
SECOND LAYER SHALL BE TAPED AND MUDDED AND FINISHED CONTINUOUS,
SEAL. ALL JOINTS SHALL BE STAGGERED ON BOTH LAYERS.
3 5/8" 16Ga GALVANIZED METAL STUDS @ 16" O.C.18
A-310
3"=1'-0"
SECURITY WALL SECTION
PER ICS 705 WALL TYPE "A" -SOUND GROUP 4
STC 50 (MIN)
WALL TYPE - W1
A-310
3"=1'-0"
TYPICAL COLUMN ENCLOSURE
A-310
3"=1'-0"
PLAN DETAIL
THIRD FLOOR
COMM/
ELEC
SECURE
ROOM
A-310
3"=1'-0"
SECURITY WALL SECTION
PER ICS 705 WALL TYPE "A" -SOUND GROUP 4
STC 50 (MIN)
WALL TYPE (RF SHIELDED) - W2
THIRD FLOOR
181217
CORR.
EXIST. CORR.
E379
A-310
3"=1'-0"
SECURITY WALL SECTION
PER ICS 705 WALL TYPE "A" -SOUND GROUP 4
STC 50 (MIN)
W3
THIRD FLOOR
181217
SCIF
E396
EXIST.
SHARED VAULT
E397
WALL TYPE (RF SHIELDED) -
16 16
'-0
'-0
'-0
ACOUSTICAL SEALANT
CONTROL JOINT
ACOUSTICAL SEALANT (FIRE
CAULK AT RATED ASSEMBLIES)
CONTROL JOINT (30'-0" MAX.)
SOUND INSULATION
COMPRESSED TO FIT OPENING
METAL STUD FRAMING
GYPSUM WALLBOARD AS
REQUIRED BY WALL ASSEMBLY RF SHIELDING
1/2"
UNCONTROLLED
SIDE
CONTROLLED SIDE
A-310
3"=1'-0"
CONTROL JOINT DETAIL
A-310
WALL SECTIONS AND PLAN DETAILS
BWA
SCALE: 3" = 1'-0"
2" 4"0 8"
96 CEG, OFFICE FORM 002, FY2013
AS-BUILT
PDM
REVISION DATE DESCRIPTION BY APPR'D
23AJ FTFA23-VH79 23AJ
23 OCT. 2024
AS SHOWN
DTRA RENOVATION
3RD FLOOR BLDG 13A
BASE CIVIL ENGINEER EGLIN
AIR FORCE BASE, FLORIDA
BWA
CONSTRUCTION WILL BE IAW
ICD/IDS 705 AND UFC-4-010-05
NOTE:
1 05/22/25 RFI ADJUSTMENTS KRW PDM
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
CENM
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
PROJ. ENGR.
AutoCAD SHX Text
CONTENTS
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
SPEC. NO.
AutoCAD SHX Text
INDEX NO.
AutoCAD SHX Text
PROJ. NO.
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
96 CEG/CEN
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
BASE CIVIL ENGINEER
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
FILE NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
SHEET OF
| Sheets and Views |
| A-310 |