KSCC 18-1525 Construct Vehicle Barriers - Rev1 30 Jun.pdf
PDF 4 MB Posted
- Attached to
- KSCC 18-1525 Construct Vehicle Barriers Federal contract opportunity
- Solicitation number
- FA252125B0005
About this file
These construction design documents detail a vehicle barrier project for Cape Canaveral Space Force Station in Florida, specifically involving the construction of vehicle barriers at multiple locations including VIF North/South, Facility 29150 Pump Station, and Complex 41 South Gate. The project involves installing removable/lockable bollards, passive cable fence barriers, and swing gates across various roadways and railroad track intersections, with specific requirements for crash-rated barriers meeting UFC 4-022-02 standards.
The design documents specify technical details such as using Calpipe security bollards, hot-dipped galvanized steel components, concrete foundations, and cable barrier systems with specific installation requirements. The barriers are designed to provide security and controlled access, with features like removable cable barriers, gate keepers, warning signs, and storage systems for when barriers are not deployed. The design is at 100% review stage and marked "Not for Construction", indicating these are preliminary engineering drawings pending final review and approval.
View the file
Other files for this federal contract opportunity
Show all 31
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SKID STRIP
B A
N A
N A
R
I V
E R
B A
N A
N
V
E R
A T
L A
N T
C
O
E
A N
A T L
A N
T I
C O C
E A
N
TO
KENNEDY SPACE CENTER
INDUSTRIAL AREA
VISITOR CONTROL
CENTER
SOUTH GATE
NASA CSWY E
CCAFS
INDUSTRIAL
AREA
PORT CANAVERAL
SR A1A TO COCOA BEACH
F
IL
E N
A M
E X
P ro je ct s\
\2
-0
K S
C C
-1
C o n st ru ct
V e h ic le B a rr ie rs
\2
P ro d u ct io n \0
D e si g n \J
D ra w in g s\
T R
A C
E S
V
E H
IC
L E
B A
R R
IE
R
S \S h e e ts
\G -0
.d w g
L A
Y O
U T
N A
M E
G
-0
P
L O
T T
E D
T h u rs d a y, F e b ru a ry
:1 p m
U S
E R
JJ
a co b s
CAPE CANAVERAL SPACE FORCE STATION
CAPE CANAVERAL, FLORIDA
VICINITY MAP
N
PROJECT
LOCATION
BASE OPERATIONS:
COMMUNICATIONS:
PROJECT MANAGER:
CHIEF, ENGINEERING FLIGHT:
USER:
SAFETY:
SECURITY FORCES:
ATO:
OTHER:
ENVIRONMENTAL:
FIRE:
A P P R O V E D
KSCC 18-1525
CONSTRUCT VEHICLE
BARRIERS
TITAN III
ROAD
/3
/2
K S
-1
C C
S F
S
F L
U S
S F
T H
C
IV
IL
E
N G
IN
E
E R
S Q
U A
D R
O N
A S
B U
IL
T
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
R E
V
IE
W E
D B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C T
N O
F
A
-1
-D
-0
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
T R
A C
E S
T E
C H
N
IC
A L
R A
N G
E A
R C
H
IT
E C
T E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S rh o d e ri to
H
T
E
S
A
A F
P R
O
JE
C T
N o
R B
P R
O
JE
C T
N o
U N
IT
ED
STATES SPACE
FO
R
C E
E M
N
OF TH
AIR
FO
R
C
D E
E
E
A P
RT
T
M M X I X
K S
C C
-1
C O
N S
T R
U C
T V
E H
IC
L
E B
A R
R
IE
R S
NOT FOR CONSTRUCTION
DESIGN REVIEW ONLY
R
S U
L L
IV
A
N
K
F
IN
D L
A T
E R
J.
JA
C O
B S
K
F
IN
D L
A T
E R
DRAWING INDEX
REV INDEX DRAWING DESCRIPTION
- G-001 COVER SHEET AND INDEX
- S-001 ABBREVIATIONS, LEGENDS AND NOTES
- S-101 VIF NORTH BARRIER PLAN VIEW
- S-102 VIF SOUTH BARRIER PLAN VIEW
- S-103 FAC 29150 PUMP STATION
- S-104 COMPLEX 41 SOUTH GATE PLAN
- S-501 BARRIER DETAILS
- S-502 GATE DETAILS
- S-503 FIXED WIRE CABLE BARRIER DETAILS
- S-504 REMOVABLE WIRE CABLE BARRIER STORAGE DETAILS
C O
V E
R S
H E
E T
A N
D I
N D
E X
D B
E H
E S
-0
G-001
T
IT
A N
II
I R
O A
D
PERMIT(S)/ENVIRONMENTAL AND 45 SW ACTIONS
REQUIRED PRIOR TO CONSTRUCTION
ERP/STORMWATER
ERP/WETLANDS/DREDGE & FILL
FDEP/DRINKING WATER
FDEP/DOM. WASTE WATER ARCHEO./HISTORICAL
SURVEY/WILDLIFE
45SW RISK ASSESSMENT
NONE
FDEP/IND. WASTE WATER
IRP
FDEP/FUEL TANK
NOI/SWPPP
ASBESTOS
NOTE: IF IT IS SUSPECTED THAT ANY HAZARDOUS MATERIAL NOT
IDENTIFIED ON THESE DRAWINGS IS REQUIRED TO BE DISTURBED IN
ORDER TO PERFORM THE CONTRACT WORK, LEAVE MATERIAL
UNDISTURBED AND IMMEDIATELY INFORM THE CONTRACTING OFFICER.
HEAVY METALS
YES NO
LEAD
PCB
NOT
VERIFIED
HAZARDOUS MATERIALS
C A
P E
R O
A D
C A
P E
R O
A D
FAC. 29150 PUMP 7
BARRIER LOCATION
VIF NORTH
BARRIER LOCATION
COMPLEX 41 SOUTH
GATE LOCATIONVIF SOUTH
BARRIER LOCATION
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text 100%%%
/3
/2
K S
-1
C C
S F
S
F L
U S
S F
T H
C
IV
IL
E
N G
IN
E
E R
S Q
U A
D R
O N
A S
B U
IL
T
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
R E
V
IE
W E
D B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C T
N O
F
A
-1
-D
-0
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
T R
A C
E S
T E
C H
N
IC
A L
R A
N G
E A
R C
H
IT
E C
T E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S rh o d
A
A F
P R
O
JE
C T
N o
R B
P R
O
JE
C T
N o
U N
IT
ED
STATES SPACE
FO
R
C E
E M
N
OF TH
AIR
FO
R
C
D E
E
E
A P
RT
T
M M X I X
K S
C C
-1
C O
N S
T R
U C
T V
E H
IC
L
E B
A R
R
IE
R S
NOT FOR CONSTRUCTION
DESIGN REVIEW ONLY
R
S U
L L
IV
A
N
K
F
IN
D L
A T
E R
J.
JA
C O
B S
K
F
IN
D L
A T
E R
A B
B R
E V
IA
T
IO
N
S
L E
G E
N D
S A
N D
N O
T E
S
D B
E H
E S
-0
STRUCTURAL STEEL NOTES:
MIN. SERVICE DESIGN LOAD ON ANY CONNECTION
MIN. WELD SIZE
MIN. BOLT DIAMETER
MIN. PLATE THICKNESS
: 10 KIPS
: 3/16"
: 3/4" : 3/8"
1. ALL STRUCTURAL STEEL SHALL HAVE THE FOLLOWING MINIMUM YIELD STRENGTHS, UNLESS
OTHERWISE NOTED ON THE DRAWINGS:
A53, GRADE B (YIELD STRENGTH OF 35 KSI)
2. ALL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO AISC SPECIFICATIONS AND
CODES, INCLUDING THE SECTION ON COMMENTARY, LATEST EDITION.
3. ALL BOLTS, NUTS AND WASHERS SHALL CONFORM TO THE REQUIREMENTS OF ASTM A325.
BOLTS, NUTS AND WASHERS SHALL BE STAINLESS STEEL WITH MATCHING NUTS.
4. ALL WELDING ELECTRODES SHALL BE E70XX.
5. ALL WELDING SHALL BE DONE BY AWS CERTIFIED WELDERS AND SHALL CONFORM TO THE AWS
"CODE FOR ARC AND GAS WELDING TO BUILDING CONSTRUCTION," LATEST EDITION.
6. ALL BEAM CONNECTIONS SHALL BE SIMPLE SHEAR CONNECTIONS WITH BOLTS IN BEARINGS.
THE DESIGN LOAD FOR CONNECTIONS SHALL BE AS INDICATED ON SECTIONS, DETAILS OR
STANDARD AISC CONNECTION.
7. ALL BEAM CONNECTIONS SHALL HAVE ENLARGED OR SLOTTED HOLES TO PROVIDE END
ROTATION AS PER THE REQUIREMENTS OF THE AISC SPECIFICATIONS, SECTION J1.2, AND THE
LATEST SUPPLEMENTS AND SHALL ALSO REFLECT THE LOAD ECCENTRICITY IN THE DESIGN OF
THE CONNECTION.
8. NO CONNECTION SHALL CONSIST OF LESS THAN (2) 3/4" DIA. (A325-X) BOLTS OR WELD
DEVELOPING A MINIMUM OF 10,000 LBS. UNLESS INDICATED ON THE DRAWINGS.
9. ALL FILLET WELDS SHALL BE A MINIMUM OF 3/16" UNLESS NOTED OTHERWISE, BUT NOT LESS
THAN THE AISC MINIMUM.
10. THE FABRICATOR SHALL FURNISH A STRUCTURAL SUBMITTAL WHICH SHALL BE CHECKED BY THE
CONTRACTOR FOR COMPLETENESS AND CONTENT PRIOR TO SUBMITTAL TO THE CONTRACTING
OFFICER FOR REVIEW. THE SUBMITTAL SHOULD INCLUDE FABRICATION AND ERECTION
DRAWINGS AND DESIGN CALCULATIONS FOR CONNECTIONS AS SPECIFIED ON THE
CONSTRUCTION DOCUMENTS. THE DESIGN CALCULATIONS SHALL BEAR THE SEAL AND
SIGNATURE OF A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF FLORIDA. FABRICATION
SHALL NOT COMMENCE UNTIL THIS REVIEW IS COMPLETED.
11. SIZES OF STRUCTURAL STEEL CANNOT BE VARIED FROM THOSE SHOWN ON THE DRAWINGS
WITHOUT WRITTEN PERMISSION FROM THE CONTRACTING OFFICE.
12. CUTS, HOLES AND THEIR REINFORCEMENT (REQUIRED BY OTHER TRADES) SHALL BE SHOWN ON THE STRUCTURAL STEEL SHOP DRAWINGS AND SHALL BE MADE IN THE SHOP. FIELD BURNING OF
HOLES AND CUTS IN STRUCTURAL STEEL SHALL NOT BE PERMITTED EXCEPT BY WRITTEN
PERMISSION FROM THE CONTRACTING OFFICER.
13. AFTER ERECTION, ALL STEEL SHALL BE INSPECTED, AND CLEANED OF ANY FOREIGN MATERIALS.
ANY SCUFFS, ABRASIONS, (AND DAMAGED FINISH) SHALL BE FIELD TOUCHED-UP WITH AN
APPROVED COATING REPAIR SYSTEM.
14. TESTING OF WELDS AND BOLTS SHALL BE AS FOLLOWS: CHECK 100% OF ALL STRUCTURAL STEEL
AND THEIR CONNECTIONS BY VISUAL INSPECTION AND REVIEW TEST REPORTS OF THE
FABRICATOR'S QUALITY CONTROL TESTS. CHECK ALL BOLTS IN 10% OF ALL CONNECTIONS BY
THE CALIBRATED TORQUE WRENCH METHOD OR BY THE TURN-OF-NUT METHOD.
15. THE FOLLOWING MINIMUM STANDARDS APPLY:
16. ALL STRUCTURAL STEEL SHALL BE HOT DIP GALVANIZED ASTM A123/A123M. REPAIR ANY
DAMAGED FINISH PER ASTM A780/A780M. STEEL POST SHALL BE HOT DIP GALVANIZED INSIDE AND
OUT.
(SOME MAY NOT BE USED)
STRUCTURAL ABBREVIATION LIST
A. A ANCHOR
AB ANCHOR BOLTS
ACI AMERICAN CONCRETE INSTITUTE
ADD'L ADDITIONAL
AFF ABOVE FINISH FLOOR
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
AL ALUMINUM
ALT ALTERNATE/ALTERNATIVE
APP'D APPROVED
ARCH ARCHITECTURAL, ARCHITECT
ASPH ASPHALT
ASTM AMERICAN SOCIETY OF TESTING
MATERIALS
AWS AMERICAN WELDING SOCIETY
B. B.M. BENCH MARK
B.⅊ BASE PLATE
B/ BOTTOM OF
BIT BITUMINOUS
BLDG BUILDING
BLK BLOCK
BM BEAM
BOT BOTTOM
BRG BEARING
BU BUILT UP
C. C/C CENTER TO CENTER
CB CONCRETE BEAM
CC CONCRETE COLUMN
CE CONCRETE ENCASED
CF CUBIC FOOT/FEET
C CHANNEL
CHK CHECKERED
CI CAST IRON
CIP CONCRETE IN PLACE
CJ CONTRACTION JOINT
CL CLEAR/CLEARANCE
℄ CENTER LINE
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CO COMPANY
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CON'T CONTINUOUS
COORD COORDINATE
CS CARBON STEEL
CJ CONSTRUCTION JOINT
CY CUBIC YARD
D. D DECK DIAPHRAGM LOAD (PLF)
DBA DOWEL BAR ANCHOR
DEG DEGREE
DEP DEPARTMENT
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIST DISTANCE
DN DOWN
DR DRAIN
DWG DRAWING
E. EA EACH
EE EACH END
EF EACH FACE
EJ EXPANSION JOINT
ELEV ELEVATION
ELEC ELECTRICAL/ELECTRIC
ENG ENGINEER
EOR CONTRACTING OFFICE
ES EQUAL SPACED
EQUIP EQUIPMENT
EW EACH WAY
EXCL EXCLUDING
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
F. FB FLAT BAR
FD FLOOR DRAIN
FF FINISHED FLOOR
FG FINISHED GRADE
FL FLOOR
FND FOUNDATION
FRP FIBERGLASS REINFORCED PLASTIC
FS FAR SIDE
FT FOOT/FEET
FTG FOOTING
G. GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GR GRADE
H. HORIZ HORIZONTAL
HDA HEADED STUD ANCHOR
HT HEIGHT
HDG HOT DIPPED GALVANIZED
I. ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INT INTERIOR
INV INVERT
J. JT JOINT
JST JOIST
K. K KIP
KO KNOCK OUT
KWY KEY WAY
L. L LENGTH
LDG LANDING
LONG LONGITUDE
LP LOW POINT
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LWIC LIGHT WEIGHT INSULATING
CONCRETE
M. MANUF MANUFACTURER
MAT MATERIAL
MAX MAXIMUM
MB MASONRY BEAM
MCJ MASONRY CONTROL JOINT
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MJ MASONRY JOINT
MO MASONRY OPENING
MOM MOMENT
MTL METAL
N. NIC NOT IN CONTRACT
NS NEAR SIDE
N.T.S. NOT TO SCALE
O. OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
ORIENT ORIENTATION
P. P/C PRE CAST CONC
PAR PARALLEL
PENN PENETRATION
PERIM PERIMETER
⅊ PLATE
PLF POUNDS PER LINEAR FOOT
PLY PLYWOOD
PREFAB PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
Q. QTY QUANTITY
R. RA ROOF ACCESS
R/W REINFORCED WITH
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCING
REQ'D REQUIRED
RM ROOM
S. SCH SCHEDULE
SF SQUARE FEET
SIM SIMILAR
SJ SAW JOINT
SP SPACING
SPA SPACE(S)
SPEC SPECIFICATION
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIRR STIRRUPS
STL STEEL
SYM SYMMETRICAL
T. T&B TOP & BOTTOM
T/ TOP OF
T/C TOP OF CONCRETE
T/S TOP STEEL
TB TIE BEAM
TEMP TEMPORARY
TENS TENSION
THD THREAD(ED)
THK THICK
TJ TIE JOIST
TOL TOLERANCE
TOT TOTAL
TRANS TRANSVERSE
TS THICKENED SLAB
TYP TYPICAL
U. UON UNLESS OTHERWISE NOTED
U/N UNDERSIDE
V. VERT VERTICAL
VOL VOLUME
W. W WIDE
W/ WITH
W/O WITHOUT
WD WOOD
WF WIDE FLANGE
WH WEEP HOLE
WP WORKING POINT
WT WEIGHT
WWR WELDED WIRE REINFORCING
W FTG WALL FOOTING
X. XFMR TRANSFORMER
Y. Y WYE
Z. Z ZONE
1. THE DESIGN IS BASED ON THE FOLLOWING APPLICABLE CODES AND STANDARDS:
2. THE CABLE FENCE PASSIVE BARRIERS SHALL BE CRASH RATED IN ACCORDANCE WITH AND
MEET ASTM F2656, MP0/P2.
3. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH PROJECT DRAWINGS AND
SPECIFICATIONS. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO OBTAIN ALL
CONTRACT DOCUMENTS AND LATEST ADDENDA AND TO SUBMIT SUCH DOCUMENTS TO ALL
SUBCONTRACTORS AND MATERIALS SUPPLIERS PRIOR TO THE SUBMITTAL OF SHOP
DRAWINGS, FABRICATION OF ANY STRUCTURAL MEMBERS, AND ERECTION IN THE FIELD.
4. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONNECTIONS AND ANCHOR BOLT
LOCATIONS FROM CERTIFIED DRAWINGS AND FABRICATOR'S ANCHOR BOLT SETTING PLANS.
5. DETAILS LABELED "TYPICAL DETAILS" ON THE DRAWINGS SHALL APPLY TO ALL SITUATIONS
OCCURRING ON THE PROJECT THAT ARE THE SAME OR SIMILAR TO THOSE SPECIFICALLY
DETAILED. THE APPLICABILITY OF THE DETAIL TO ITS LOCATION ON THE PLANS CAN BE
DETERMINED BY THE TITLE OF THE DETAIL. SUCH DETAILS SHALL APPLY WHETHER OR NOT
THEY ARE KEYED IN AT EACH LOCATION. QUESTIONS REGARDING APPLICABILITY OF
TYPICAL DETAILS SHALL BE DETERMINED BY THE CONTRACTING OFFICE.
6. THE CONTRACTOR SHALL WORK STRUCTURAL DRAWINGS TOGETHER WITH ELECTRICAL
AND CIVIL DRAWINGS TO LOCATE DEPRESSED SLABS, SLOPES, DRAINS, REGLETS, BOLT
SETTINGS, GRADES, ETC., ANY DISCREPANCIES SHALL BE CALLED TO THE ATTENTION OF
THE CONTRACTING OFFICE BEFORE PROCEEDING WITH THE WORK.
7. THE STRUCTURAL INTEGRITY OF THE COMPLETED STRUCTURE DEPENDS UPON THE
INTERACTION OF VARIOUS CONNECTED COMPONENTS. PROVIDE ADEQUATE BRACING,
SHORING, AND OTHER TEMPORARY SUPPORTS AS REQUIRED TO SAFELY COMPLETE THE
WORK.
8. THE GENERAL CONTRACTOR SHALL COMPARE THE STRUCTURAL DRAWINGS WITH OTHER
DISCIPLINES AND REPORT ANY DISCREPANCIES BETWEEN EACH SET OF DRAWINGS AND
WITHIN EACH SET OF DRAWINGS TO THE CONTRACTING OFFICE PRIOR TO THE FABRICATION
AND INSTALLATION OF ANY STRUCTURAL MEMBERS. WHERE CONFLICTS EXIST AMONG
VARIOUS PARTS OF THE STRUCTURAL CONTRACT DOCUMENTS, STRUCTURAL DRAWINGS,
GENERAL NOTES AND SPECIFICATIONS, THE STRICTEST REQUIREMENTS SHALL GOVERN.
9. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE AND DO NOT INDICATE THE METHOD OR MEANS OF CONSTRUCTION. THE
CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE SOLELY
RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES,
SEQUENCE, AND SAFETY. THE ENGINEER DOES NOT HAVE CONTROL OR CHARGE OF, AND
SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES,
SEQUENCES, OR PROCEDURES, SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION
WITH THE WORK, THE ACTS OR OMISSION OF THE CONTRACTOR, SUBCONTRACTOR, OR ANY
OTHER PERSONS PERFORMING ANY OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM
TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DRAWINGS.
10. ALL STRUCTURES REQUIRE PERIODIC MAINTENANCE TO EXTEND LIFE SPAN AND TO ENSURE
STRUCTURAL INTEGRITY FROM EXPOSURE TO THE ENVIRONMENT. A PLANNED PROGRAM
OF MAINTENANCE SHALL BE ESTABLISHED BY THE OWNER. THIS PROGRAM SHALL INCLUDE
ITEMS SUCH AS, BUT NOT LIMITED TO, PAINTING OF STRUCTURAL STEEL, PROTECTIVE
COATINGS FOR CONCRETE, SEALANTS, CAULKED JOINTS, EXPANSION JOINTS, CONTROL
JOINTS, SPALLS AND CRACKS IN CONCRETE, AND PRESSURE WASHING OF EXPOSED
STRUCTURAL ELEMENTS EXPOSED TO SALT ENVIRONMENT OR OTHER HARSH CHEMICALS.
11. THE USE OF REPRODUCTIONS OF THESE CONTRACT DOCUMENTS AND USE OF CAD FILES
BY ANY CONTRACTOR, SUBCONTRACTOR, ERECTOR, FABRICATOR, OR MATERIAL SUPPLIER
IN LIEU OF PREPARATION OF SHOP DRAWINGS SIGNIFY HIS ACCEPTANCE OF ALL
INFORMATION SHOWN HEREON AS CORRECT, AND OBLIGATES HIM TO ANY JOB EXPENSE,
REAL OR IMPLIED, ARISING DUE TO ANY ERRORS THAT MAY OCCUR HEREON.
12. EXPANSION ANCHORS MAY BE SUBSTITUTED FOR ANCHOR BOLTS ONLY WITH THE WRITTEN
APPROVAL OF THE CONTRACTING OFFICE. EXPANSION ANCHORS USED SHALL BE HILTI,
RAWL, OR APPROVED EQUAL.
13. PROVIDE DISSIMILAR METAL SEPARATORS AT ALL JUNCTIONS OF ALUMINUM SOFFIT,
FRAMING, STRUCTURAL STEEL, AND DISSIMILAR METALS.
GENERAL NOTES
MULTIPLE SHEETS
= CUT FROM
DIRECTION OF CUT
CUT ON SHEET SHOWN ON SHEET
DESIGNATION
SECTION CALLOUT
1. ALL CONCRETE SHALL BE AS DESIGNED TO DEVELOP A COMPRESSIVE STRENGTH AS
FOLLOWS:
FOUNDATIONS 5000 PSI
2. ALL REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A-615 GRADE
60 (FY=60 KSI).
3. ALL CONCRETE REINFORCEMENT SHALL BE DETAILED, FABRICATED, LABELED, SUPPORTED
AND SPACED IN FORMS AND SECURED IN PLACE IN ACCORDANCE WITH THE PROCEDURES
AND REQUIREMENTS OUTLINED IN THE LATEST EDITION OF THE "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE", ACI 318-14 AND THE "MANUALS OF
STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES", ACI SP-66 (94).
SHOP DRAWINGS SHALL BE SUBMITTED TO THE CONTRACTING OFFICER FOR REVIEW PRIOR
TO FABRICATION.
4. ALL BAR SPLICES SHALL BE AS FOLLOWS:
A. HORIZONTAL BARS WHERE 12" OF CONCRETE WILL BE PLACED BELOW BOTTOM
B. ALL OTHER BARS
5. CALCIUM CHLORIDE SHALL NOT BE USED IN ANY FORM.
6. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS (U.O.N.):
7. UNLESS OTHERWISE PERMITTED OR SPECIFIED, THE CONCRETE SHALL BE PROPORTIONED
AND PRODUCED TO HAVE A SLUMP PER SPECIFICATIONS. IMMEDIATELY AFTER DEPOSITING,
CONCRETE SHALL BE THOROUGHLY CONSOLIDATED BY MEANS OF MECHANICAL VIBRATION.
8. NON-SHRINK GROUT FOR BASE PLATES AND BEARING PLATES SHALL MEET THE FOLLOWING:
A. NON-METALLIC, SHRINKAGE RESISTANT PREMIXES NON-CORROSIVE, NON-STAINING
PRODUCT CONTAINING PORTLAND CEMENT, SILICA SANDS, SHRINKAGE
COMPENSATING AGENTS, AND FLUIDITY IMPROVING COMPOUNDS, AND SHALL
CONFORM TO CORPS OF ENGINEERS SPECIFICATION FOR NON-SHRINK GROUT,
CRD-C621-83.
B. TWENTY-EIGHT DAY COMPRESSIVE STRENGTH SHALL BE A MINIMUM OF 10,000 PSI.
9. HOOKS SHOWN AT THE ENDS OF REINFORCING BARS SHALL BE ACI STANDARD 90° HOOKS
OF THE FOLLOWING LENGTHS, (U.O.N.):
10. ALL EMBEDDED ITEMS, SUCH AS PIPES, PLATES AND ANCHOR BOLTS, SHALL BE TIED TO
REINFORCING STEEL AND/OR FORMWORK PRIOR TO CONCRETE PLACEMENT. "WET"
PLACEMENT OF BARS OR EMBED ITEMS SHALL NOT BE PERMITTED.
11. CONCRETE SHALL BE SUITABLE FOR THE FOLLOWING EXPOSURE CATEGORIES: C2
11.1. REFERENCE ACI 318.14 TABLE 19.3.1.1 FOR EXPOSURE CLASS. CONCRETE SHALL BE
DESIGNED TO SPECIFICATIONS IN TABLE 19.3.2.1 FOR EXPOSURE CLASS C2.
12. TOLERANCE FOR CONCRETE COVER OVER REINFORCEMENT IS PER ACI 117.
4 INCHES
1.5 INCHES
MINIMUM CLEAR COVER
EXPOSED TO EARTH
ALL OTHER CONDITIONS
STRUCTURAL PART
CONCRETE CAST AGAINST AND PERMANENTLY
SLABS, WALLS, NOT EXPOSED TO EARTH OR WEATHER 1 INCHES
BARS SIZES (#)
LENGTH
3 4 5 6 7 8 9 10
22"19"16"14"12"10"8"6"
1098764 53BAR SIZES #
3 54 6 7 8 9 10BAR SIZES #
5000 PSI LAP (IN) 9122 3629 43 63 72 81
6355493322 2817 70LAP (IN)5000 PSI
CONCRETE NOTES
S-001
XX
DIRECTION OF CUT
DESIGNATION
X-X
SECTION CALLOUT WITHIN DETAIL
SECTION CUT LINE
• UFC 1-200-01 DOD BUILDING CODE (REVISION DATE: 1 OCTOBER 2020)
• UFC 3-301-01 STRUCTURAL ENGINEERING (REVISION DATE: 1 NOVEMBER 2019)
• INTERNATIONAL BUILDING CODE (IBC) 2021
• AMERICAN CONCRETE INSTITUTE (ACI) 318-14
• AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) 15TH EDITION
TITAN III ROAD
≈37'-9 7/8" ROADWAY
5'-11"
13'-7 7/8"
VEGETATION
RAILROAD
TRACKS
RAILROAD
TRACKS
RAILROAD TRACKS
FOOTER EDGE
RAILROAD TRACKS
FOOTER EDGE
6'-2 1/2"
13'-11 5/8"
8'-0"
8'-0"
VEGETATION
16"x16" TERMINAL POST
FOUNDATION MINIMUM 3'-6" AWAY
FROM RAILROAD FOUNDATION
16"x16" TERMINAL POST
FOUNDATION MINIMUM 3'-6" AWAY
FROM RAILROAD FOUNDATION
/3
/2
K S
-1
C C
S F
S
F L
U S
S F
T H
C
IV
IL
E
N G
IN
E
E R
S Q
U A
D R
O N
A S
B U
IL
T
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
R E
V
IE
W E
D B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C T
N O
F
A
-1
-D
-0
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
T R
A C
E S
T E
C H
N
IC
A L
R A
N G
E A
R C
H
IT
E C
T E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S rh o d
A
A F
P R
O
JE
C T
N o
R B
P R
O
JE
C T
N o
U N
IT
ED
STATESSPACE
FO
R
C E
E M
N
OF TH
AIR
FO
R
C
D E
E
E
A P
RT
T
M M X I X
K S
C C
-1
C O
N S
T R
U C
T V
E H
IC
L
E B
A R
R
IE
R S
NOT FOR CONSTRUCTION
DESIGN REVIEW ONLY
R
S U
L L
IV
A
N
K
F
IN
D L
A T
E R
J.
JA
C O
B S
K
F
IN
D L
A T
E R
V
IF
N O
R T
H B
A R
R
IE
R P
L A
N V
IE
W
D B
E H
E S
-0
S-101
1" = 10'
VIF NORTH BARRIER SITE PLAN
1"=10'
5' 10'0 20'
N
FLAG NOTE(S):
1. SAW CUT EXISTING PAVEMENT. THE WIDTH OF THE ROADWAY AS NEEDED TO FORM AND POUR
CONCRETE FOUNDATION FOR THE BOLLARDS.
2. PROVIDE 4" REMOVABLE LOCKABLE BOLLARDS. CALPIPE - IBP04080 OR APPROVED EQUAL. SEE
SHEET C-501.
3. PROVIDE PASSIVE BARRIER SYSTEM THAT MEET THE REQUIREMENTS OF UFC 4-022-02. SEE
SHEET S-502 FOR MORE DETAILS.
4. REMOVE VEGETATION AS REQUIRED TO INSTALL PASSIVE BARRIER SYSTEM. COORDINATE
REMOVAL OF VEGETATION WITH THE OWNERS ENVIRONMENTAL DEPARTMENT. BURNING OF ANY
REMOVED VEGETATION IS NOT PERMITTED, AND WILL NEED TO BE LOADED INTO A DUMPSTER
AND REMOVED FROM THE SITE.
5. REMOVABLE CABLE BARRIER ACROSS RAILROAD TRACK WHEN BOLLARDS ARE DEPLOYED. SEE
SHEET S-503 FOR ADDITIONAL DETAILS.
6. WHEN BOLLARDS ARE NOT DEPLOYED, BOLLARDS AND CABLE BARRIER WILL BE STORED IN
ADJACENT BOLLARD STORAGE SYSTEM. REMOVE GRASS UNDER CABLES BETWEEN POSTS AND
INSTALL #57 STONE. SEE SHEET S-504 FOR ADDITIONAL DETAILS.
7. ATTACH WARNING STOP SIGN TO DEPLOYABLE CABLE TO WARN VEHICLES OF UPCOMING ROAD
BARRIERS.
8. PROVIDE 10'x10'x4" WWF CONC. BOLLARD STORAGE AREA PAD AND STORAGE SLEEVES. TYPE
AND INSTALLATION OF SLEEVES TO BE DETERMINED BY BOLLARD MANUFACTURER'S
SPECIFICATIONS AND PRODUCT DETAILS. LOCATION OF PAD TO BE COORDINATED BY
CONTRACTOR, CONTRACTING OFFICER AND FACILITY MANAGER PRIOR TO CONSTRUCTION
N.T.S.
KEY PLAN
N
T
IT
A N
II
I R
O A
D
FAC. 29401
AREA
OF WORK
FAC. 29402
TITAN III ROAD
GENERAL NOTE(S):
1. THE FOLLOWING IS THE BASIS OF DESIGN FOR THE BOLLARDS: CALPIPE SECURITY BOLLARD.
2. STRUCTURAL STEEL AND CONNECTION BOLTS SHALL BE HOT-DIPPED GALVANIZED AFTER
FABRICATION IN ACCORDANCE WITH ASTM A123 AND ASTMA153 FOR IRON AND STEEL
HARDWARE.
3. SEE SHEET S-501 FOR BARRIER FOUNDATIONS WHICH SUPPORT THE REACTIONS SHOWN
FOR THE CONDITIONS EXISTING AT THE SITE.
4. DRAWING IS REPRESENTATIVE. FINAL SHOP DRAWINGS SHALL BE PROVIDED BY THE
BOLLARD MANUFACTURER FOR ASSEMBLY AND CONSTRUCTION. SHOP DRAWINGS SHALL BE
REVIEWED AND APPROVED BY OWNER PRIOR TO FABRICATION.
5. THE CONTRACTOR SHALL SUBMIT A MAINTENANCE OF TRAFFIC PLAN FOR GOVERNMENT
APPROVAL TO PHASE WORK AS TO HAVE MINIMAL IMPACT TO TRAFFIC.
TYP. (7) 5
AutoCAD SHX Text 100%%%
1229810819C Polygon
1229810819C Polygon
1229810819C Polygon
1229810819C Polygon
1229810819C Polygon
IT
A N
II
I R
O A
D
VEGETATION
RAILROAD
TRACKS
RAILROAD
TRACKS
35'-7 7/8" ROADWAY
RAILROAD TRACKS
FOOTER EDGE
8'-0"
8'-0"
RAILROAD TRACKS
FOOTER EDGE
VERTICAL INTEGRATION FACILITY PARKING
'-3
/8
14'-1 3/8"
14'-1 3/8"
VEGETATION
6'-1 1/8"
6'-0 1/2"
16"x16" TERMINAL POST
FOUNDATION MINIMUM 3'-6" AWAY
FROM RAILROAD FOUNDATION
16"x16" TERMINAL POST
FOUNDATION MINIMUM 3'-6" AWAY
FROM RAILROAD FOUNDATION
/3
/2
K S
-1
C C
S F
S
F L
U S
S F
T H
C
IV
IL
E
N G
IN
E
E R
S Q
U A
D R
O N
A S
B U
IL
T
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
R E
V
IE
W E
D B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C T
N O
F
A
-1
-D
-0
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
T R
A C
E S
T E
C H
N
IC
A L
R A
N G
E A
R C
H
IT
E C
T E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S rh o d
A
A F
P R
O
JE
C T
N o
R B
P R
O
JE
C T
N o
U N
IT
ED
STATESSPACE
FO
R
C E
E M
N
OF TH
AIR
FO
R
C
D E
E
E
A P
RT
T
M M X I X
K S
C C
-1
C O
N S
T R
U C
T V
E H
IC
L
E B
A R
R
IE
R S
NOT FOR CONSTRUCTION
DESIGN REVIEW ONLY
R
S U
L L
IV
A
N
K
F
IN
D L
A T
E R
J.
JA
C O
B S
K
F
IN
D L
A T
E R
V
IF
S O
U T
H B
A R
R
IE
R P
L A
N V
IE
W
D B
E H
E S
-0
S-102
1" = 10'
VIF SOUTH BARRIER SITE PLAN
1"=10'
5' 10'0 20'
N
TYP. (7)
N.T.S.
KEY PLAN
N
T
IT
A N
II
I R
O A
D
AREA
OF WORK
FAC. 29402
GENERAL NOTE(S):
1. THE FOLLOWING IS THE BASIS OF DESIGN FOR THE BOLLARDS: CAPPIPE SECURITY BOLLARD.
2. STRUCTURAL STEEL AND CONNECTION BOLTS SHALL BE HOT-DIPPED GALVANIZED AFTER
FABRICATION IN ACCORDANCE WITH ASTM A123 AND ASTMA153 FOR IRON AND STEEL
HARDWARE.
3. SEE SHEET S-501 FOR BARRIER FOUNDATIONS WHICH SUPPORT THE REACTIONS SHOWN
FOR THE CONDITIONS EXISTING AT THE SITE.
4. DRAWING IS REPRESENTATIVE. FINAL SHOP DRAWINGS SHALL BE PROVIDED BY THE
BOLLARD MANUFACTURER FOR ASSEMBLY AND CONSTRUCTION. SHOP DRAWINGS SHALL BE
REVIEWED AND APPROVED BY OWNER PRIOR TO FABRICATION.
5. THE CONTRACTOR SHALL SUBMIT A MAINTENANCE OF TRAFFIC PLAN FOR GOVERNMENT
APPROVAL TO PHASE WORK AS TO HAVE MINIMAL IMPACT TO TRAFFIC.
FLAG NOTE(S):
1. SAW CUT EXISTING PAVEMENT. THE WIDTH OF THE ROADWAY AS NEEDED TO FORM AND POUR
CONCRETE FOUNDATION FOR THE BOLLARDS.
2. PROVIDE 4" REMOVABLE LOCKABLE BOLLARDS. CALPIPE - IBP04080 OR APPROVED EQUAL. SEE
SHEET C-501.
3. PROVIDE PASSIVE BARRIER SYSTEM THAT MEET THE REQUIREMENTS OF UFC 4-022-02. SEE
SHEET S-502 FOR MORE DETAILS.
4. REMOVE VEGETATION AS REQUIRED TO INSTALL PASSIVE BARRIER SYSTEM. COORDINATE
REMOVAL OF VEGETATION WITH THE OWNERS ENVIRONMENTAL DEPARTMENT. BURNING OF ANY
REMOVED VEGETATION IS NOT PERMITTED, AND WILL NEED TO BE LOADED INTO A DUMPSTER
AND REMOVED FROM THE SITE.
5. REMOVABLE CABLE BARRIER ACROSS RAILROAD TRACK WHEN BOLLARDS ARE DEPLOYED. SEE
SHEET S-503 FOR ADDITIONAL DETAILS.
6. WHEN BOLLARDS ARE NOT DEPLOYED CABLE BARRIER WILL BE STORED ON CABLE BARRIER
STORAGE SYSTEM. REMOVE GRASS UNDER CABLES BETWEEN POSTS AND INSTALL #57 STONE.
SEE SHEET S-504 FOR ADDITIONAL DETAILS.
7. ATTACH WARNING STOP SIGN TO DEPLOYABLE CABLE TO WARN VEHICLES OF UPCOMING ROAD
BARRIERS.
8. PROVIDE 10'x10'x4" WWF CONC. BOLLARD STORAGE AREA PAD AND STORAGE SLEEVES. TYPE
AND INSTALLATION OF SLEEVES TO BE DETERMINED BY BOLLARD MANUFACTURER'S
SPECIFICATIONS AND PRODUCT DETAILS. LOCATION OF PAD TO BE COORDINATED BY
CONTRACTOR, CONTRACTING OFFICER AND FACILITY MANAGER PRIOR TO CONSTRUCTION
AutoCAD SHX Text 100%%%
1229810819C Polygon
1229810819C Polygon
1229810819C Polygon
1229810819C Polygon
P E
R O
A D
11'-9 1/2" R O
A D
W A
Y
VEGETATION
VEGETATION
1'-0" M
IN
1'-0" M
IN
75'-1"
/3
/2
K S
-1
C C
S F
S
F L
U S
S F
T H
C
IV
IL
E
N G
IN
E
E R
S Q
U A
D R
O N
A S
B U
IL
T
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
R E
V
IE
W E
D B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C T
N O
F
A
-1
-D
-0
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
T R
A C
E S
T E
C H
N
IC
A L
R A
N G
E A
R C
H
IT
E C
T E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S rh o d
A
A F
P R
O
JE
C T
N o
R B
P R
O
JE
C T
N o
U N
IT
ED
STATES SPACE
FO
R
C E
E M
N
OF TH
AIR
FO
R
C
D E
E
E
A P
RT
T
M M X I X
K S
C C
-1
C O
N S
T R
U C
T V
E H
IC
L
E B
A R
R
IE
R S
NOT FOR CONSTRUCTION
DESIGN REVIEW ONLY
R
S U
L L
IV
A
N
K
F
IN
D L
A T
E R
J.
JA
C O
B S
K
F
IN
D L
A T
E R
F A
C
P U
M P
S T
A T
IO
N
B A
R R
IE
R
P L
A N
V
IE
W
D B
E H
E S
-0
S-103
1" = 10'
FAC 29150 PUMP STATION #7 BARRIER SITE PLAN
1"=10'
5' 10'0 20'
N
TYP. (4)
N.T.S.
KEY PLAN
N
FAC. 29150
AREA
OF WORK
C A
P E
R O
A D
GENERAL NOTE(S):
1. THE FOLLOWING IS THE BASIS OF DESIGN FOR THE BOLLARDS: CALPIPE SECURITY BOLLARD.
2. STRUCTURAL STEEL AND CONNECTION BOLTS SHALL BE HOT-DIPPED GALVANIZED AFTER
FABRICATION IN ACCORDANCE WITH ASTM A123 AND ASTMA153 FOR IRON AND STEEL
HARDWARE.
3. SEE SHEET S-501 FOR BARRIER FOUNDATIONS WHICH SUPPORT THE REACTIONS SHOWN
FOR THE CONDITIONS EXISTING AT THE SITE.
4. DRAWING IS REPRESENTATIVE. FINAL SHOP DRAWINGS SHALL BE PROVIDED BY THE
BOLLARD MANUFACTURER FOR ASSEMBLY AND CONSTRUCTION. SHOP DRAWINGS SHALL BE
REVIEWED AND APPROVED BY OWNER AND PRIOR TO FABRICATION.
5. THE CONTRACTOR SHALL SUBMIT A MAINTENANCE OF TRAFFIC PLAN FOR GOVERNMENT
APPROVAL TO PHASE WORK AS TO HAVE MINIMAL IMPACT TO TRAFFIC.
FLAG NOTE(S):
1. SAW CUT EXISTING PAVEMENT. THE WIDTH OF THE ROADWAY AS NEEDED TO FORM
AND POUR CONCRETE FOUNDATION FOR THE BOLLARDS.
2. PROVIDE 4" REMOVABLE LOCKABLE BOLLARDS. CALPIPE - IBP04080 OR APPROVED
EQUAL. SEE SHEET C-501.
3. PROVIDE PASSIVE BARRIER SYSTEM THAT MEET THE REQUIREMENTS OF UFC
4-022-02. SEE SHEET S-502 FOR MORE DETAILS.
4. REMOVE VEGETATION AS REQUIRED TO INSTALL PASSIVE BARRIER SYSTEM.
COORDINATE REMOVAL OF VEGETATION WITH THE OWNERS ENVIRONMENTAL
DEPARTMENT. BURNING OF ANY REMOVED VEGETATION IS NOT PERMITTED, AND
WILL NEED TO BE LOADED INTO A DUMPSTER AND REMOVED FROM THE SITE.
5. PROVIDE 10'x10'x4" WWF CONC. BOLLARD STORAGE AREA PAD AND STORAGE
SLEEVES. TYPE AND INSTALLATION OF SLEEVES TO BE DETERMINED BY BOLLARD
MANUFACTURER'S SPECIFICATIONS AND PRODUCT DETAILS. LOCATION OF PAD TO
BE COORDINATED BY CONTRACTOR, CONTRACTING OFFICER AND FACILITY
MANAGER PRIOR TO CONSTRUCTION
AutoCAD SHX Text 100%%%
1229810819C Polygon
1229810819C Polygon
1229810819C Polygon
1229810819C Polygon
63'-0" GATE OPENING
RAILROAD
TRACKS
SWING GATE RANGE
OF MOTION 0°-180°
SWING GATE RANGE
OF MOTION 0°-180°
VEGETATION
RAILROAD
TRACKS
VEGETATION
TITAN III ROAD
T
IT
A N
II
I R
O A
D
/3
/2
K S
-1
C C
S F
S
F L
U S
S F
T H
C
IV
IL
E
N G
IN
E
E R
S Q
U A
D R
O N
A S
B U
IL
T
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
R E
V
IE
W E
D B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C T
N O
F
A
-1
-D
-0
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
T R
A C
E S
T E
C H
N
IC
A L
R A
N G
E A
R C
H
IT
E C
T E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S rh o d
A
A F
P R
O
JE
C T
N o
R B
P R
O
JE
C T
N o
U N
IT
ED
STATES SPACE
FO
R
C E
E M
N
OF TH
AIR
FO
R
C
D E
E
E
A P
RT
T
M M X I X
K S
C C
-1
C O
N S
T R
U C
T V
E H
IC
L
E B
A R
R
IE
R S
NOT FOR CONSTRUCTION
DESIGN REVIEW ONLY
R
S U
L L
IV
A
N
K
F
IN
D L
A T
E R
J.
JA
C O
B S
K
F
IN
D L
A T
E R
C O
M P
L E
X
S
O U
T H
G A
T E
P L
A N
D B
E H
E S
-0
S-1041" = 10'
COMPLEX 41 SOUTH GATE PLAN - NEW
1"=10'
5' 10'0 20'
N N.T.S.
KEY PLAN
N
T
IT
A N
II
I R
O A
D
AREA
OF WORK
GENERAL NOTE(S):
1. STRUCTURAL STEEL AND CONNECTION BOLTS SHALL BE HOT-DIPPED GALVANIZED AFTER
FABRICATION IN ACCORDANCE WITH ASTM A123 AND ASTMA153 FOR IRON AND STEEL
HARDWARE. CONTACT SURFACES FOR SLIP CRITICAL CONNECTIONS SHALL NOT BE OILED
OR PAINTED AND FOR GALVANIZED MATERIAL, THE CONTACT SURFACES SHALL BE
PREPARED IN ACCORDANCE WITH AISC-LRFD-99.
2. SEE SHEET S-502 FOR GATE DETAILS.
3. DRAWING IS REPRESENTATIVE. SHOP DRAWINGS SHALL BE PROVIDED. FOR ALL ASSEMBLY
AND CONSTRUCTION. SHOP DRAWINGS SHALL BE REVIEWED AND APPROVED BY OWNER
AND PRIOR TO FABRICATION.
#FLAG NOTE(S):
1. PROVIDE NEW CABLE REINFORCEMENT AND CONC. BARRIERS PER DETAILS AND
UFC 4-022-03 AND MIL-HDBK-1013/10.
2. PROVIDE NEW CABLE GUIDE PLATES TO FENCE LINE POSTS AS SHOWN.
3. PROVIDE GATE KEEPERS TO HOLD GATE OPEN. SEE DETAILS ON SHEET S-502.
20'-0" M
AX.
/3
/2
K S
-1
C C
S F
S
F L
U S
S F
T H
C
IV
IL
E
N G
IN
E
E R
S Q
U A
D R
O N
A S
B U
IL
T
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
R E
V
IE
W E
D B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C T
N O
F
A
-1
-D
-0
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
T R
A C
E S
T E
C H
N
IC
A L
R A
N G
E A
R C
H
IT
E C
T E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S rh o d
A
A F
P R
O
JE
C T
N o
R B
P R
O
JE
C T
N o
U N
IT
ED
STATES SPACE
FO
R
C E
E M
N
OF TH
AIR
FO
R
C
D E
E
E
A P
RT
T
M M X I X
K S
C C
-1
C O
N S
T R
U C
T V
E H
IC
L
E B
A R
R
IE
R S
NOT FOR CONSTRUCTION
DESIGN REVIEW ONLY
R
S U
L L
IV
A
N
K
F
IN
D L
A T
E R
J.
JA
C O
B S
K
F
IN
D L
A T
E R
B A
R R
IE
R
D E
T A
IL
S
D B
E H
E S
-0
S-501
3'-0"
'-0
" 4 '-0
'-0
16"x16" TERMINAL
POST
2'-0"
'-0
'-0
'-0
(3) 1-1/8" STEEL
CABLE
6"x12" LINE
POST
CABLE FENCE BARRIER NOTE(S):
1. CABLE-BASED PASSIVE BARRIER SHALL BE CRASH RATED; M50 RATED; P2 PENETRATION.
2. STEEL COMPONENTS CABLE SHALL BE GALVANIZED PRIOR TO FORMING PER ASTM
A653/A653M WITH A MIN YIELD STRENGTH OF 45,000 PSI WITH A MIN ZINC COATING WIGHT
OF 0.90 OZ. TAMPERPROOF FASTENERS SHALL BE USED TO FASTEN ALL COMPONENTS.
3. GALV STEEL COMPONENTS SHALL BE PROVIDED WITH ZINC PHOSPHATEPRE-TREATMENT
AND SHALL BE FINISHED 2 MIL THERMOSETTING POWDER COATING BASE AND 2 MIL
POLYESTER TOP COAT.
4. CABLE MATERIAL SHALL BE INDEPENDENT WIRE ROPE CORE WIRE ROPE CONFORMING TO
FED SPEC RR-W-410E, PREFORMED, RIGHT RECTANGULAR LAY, MED LUBRICATION, EXTRA
IMPROVED PLOW STEEL (EIPS) WITH BREAKING STRENGTH OF 103,400 POUNDS.
5. CONCRETE FOUNDATIONS SHALL BE CALCULATED AND SHALL BE CERTIFIED BY THE
CABLE BARRIER MANUFACTURER AS PART OF THE COMPLETE AND FUNCTIONING SYSTEM.
6. MANUFACTURER'S WARRANTY SHALL COVER ALL SYSTEM COMPONENTS FOR 15 YEARS
FROM DATE OF ACCEPTANCE.
N.T.S.
BARRIER SYSTEM DETAIL
PASSIVE CABLE FENCE
S-501 S-501
NSS K12/M50 P2 ANTI RAM CABLE
FENCE OR APPROVED EQUAL.
TOP OF FOUNDATION = EXISTING GRADE
NOTE(S):
DETAIL IS NOTATIONAL ONLY. ACTUAL FOUNDATION AND BARRIER
CONFIGURATION (INCLUDING FOUNDATION REBAR SIZES AND SPACING) WILL
DEPEND ON ACTUAL SELECTED MANUFACTURER'S TESTED ASSEMBLY
REQUIREMENTS AND FIELD CONDITIONS. CONTRACTOR SHALL ENSURE THE
COMPLETE INSTALLED ASSEMBLY MEETS THE ASTM F2656, M50/P2.
1.75'
EXISTING GRADE
WHERE APPLICABLE
#4 REBAR HORIZONTAL
REINFORCEMENT
#4 REBAR STIRRUPS
10" ON CENTER
4.00'
4" 3000 PSI CONCRETE
COMPACTED CLEAN FILL
95% DENSITY
3' MAX TYP.
NOTES:
1. INSTALLATION TO BE COMPLETED IN ACCORDANCE WITH BOLLARD MANUFACTUR
SPECIFICATIONS AND DETAILS.
2. ALL DIMENSIONS BASED ON MANUFACTURES REQUIREMENTS FOR PARTICUL
BOLLARD MODEL NUMBER.
3. SAW CUT EXISTING PAVEMENT OR EXCAVATE EXISTING GRADE BASED ON BOLLA
PLACEMENT LOCATION.
4" REMOVABLE BOLLARD
HINGED LOCKING
COVER
SCALE:
REMOVABLE/ LOCKABLE BOLLARD DETAIL
NONE
EXISTING ASPHALT
AutoCAD SHX Text 100%%%
/3
/2
K S
-1
C C
S F
S
F L
U S
S F
T H
C
IV
IL
E
N G
IN
E
E R
S Q
U A
D R
O N
A S
B U
IL
T
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
R E
V
IE
W E
D B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C T
N O
F
A
-1
-D
-0
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
T R
A C
E S
T E
C H
N
IC
A L
R A
N G
E A
R C
H
IT
E C
T E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S rh o d
A
A F
P R
O
JE
C T
N o
R B
P R
O
JE
C T
N o
U N
IT
ED
STATES SPACE
FO
R
C E
E M
N
OF TH
AIR
FO
R
C
D E
E
E
A P
RT
T
M M X I X
K S
C C
-1
C O
N S
T R
U C
T V
E H
IC
L
E B
A R
R
IE
R S
NOT FOR CONSTRUCTION
DESIGN REVIEW ONLY
R
S U
L L
IV
A
N
K
F
IN
D L
A T
E R
J.
JA
C O
B S
K
F
IN
D L
A T
E R
G A
T E
D E
T A
IL
S
D B
E H
E S
-0
S-50210
N.T.S.
SHOULDER NUT EYE BOLT
A
A
N.T.S.
DOUBLE LEAF GATE CABLE DETAIL
N.T.S.
SECTION A
N.T.S.
LOCK BAR DETAIL
N.T.S.
SWING GATE BOLLARD DETAIL
N.T.S.
SWING GATE CABLE DETAIL
NOTE(S):
1. CONTRACTOR TO FIELD VERIFY GATE FRAMING AND
DIMENSIONS.
2. REINFORCEMENT CABLES AND HARDWARE BASED ON UFC
4-022-03 APPENDIX C GATE AND FENCE DETAILS DRAWINGS
UFC 710 - UFC 714.
3. REINFORCEMENT CABLES TO BE ATTACHED TO GATE POSTS
GATE FRAMING AND END POSTS IN MANNER TO ALLOW
CLEARANCE FOR NORMAL GATE OPERATION.
2'-0"
'-0
GROUT FILL
AND WASH
8" DIA. (1/2" WALL THK) STEEL
PIPE BOLLARD W/ CONCRETE
FILL FY= MIN 36 KSI
0.50mm (MIN.)
CORROSION
SHRINK SLEEVE
FINISH GRADE
#4 TIES @ 4" O.C. (TYP.)
(6) #6 BARS
EVENLY SPACED
24" x 24" CONTINUOUS
CONCRETE FOOTING 3
2" CLR
'-0
'-0
'-0
1 1/8" THIMBLE AND
WIRE ROPE CLAMPS
1" DIA. WIRE ROPE
ANCHOR PIN
N.T.S.
GATE KEEPER DETAILS
/3
/2
K S
-1
C C
S F
S
F L
U S
S F
T H
C
IV
IL
E
N G
IN
E
E R
S Q
U A
D R
O N
A S
B U
IL
T
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
R E
V
IE
W E
D B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C T
N O
F
A
-1
-D
-0
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
T R
A C
E S
T E
C H
N
IC
A L
R A
N G
E A
R C
H
IT
E C
T E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S rh o d
A
A F
P R
O
JE
C T
N o
R B
P R
O
JE
C T
N o
U N
IT
ED
STATES SPACE
FO
R
C E
E M
N
OF TH
AIR
FO
R
C
D E
E
E
A P
RT
T
M M X I X
K S
C C
-1
C O
N S
T R
U C
T V
E H
IC
L
E B
A R
R
IE
R S
NOT FOR CONSTRUCTION
DESIGN REVIEW ONLY
R
S U
L L
IV
A
N
K
F
IN
D L
A T
E R
J.
JA
C O
B S
K
F
IN
D L
A T
E R
F
IX
E D
W
IR
E C
A B
L E
B A
R R
IE
R
D E
T A
IL
S
D B
E H
E S
-0
S-503
GUIDE PLATE
(3) U-BOLT CLAMP
/3
/2
K S
-1
C C
S F
S
F L
U S
S F
T H
C
IV
IL
E
N G
IN
E
E R
S Q
U A
D R
O N
A S
B U
IL
T
D A
T E
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
R E
V
IE
W E
D B
Y
D A
T E
SHEET
IDENTIFICATION
C O
N T
R A
C T
N O
F
A
-1
-D
-0
B
2 3
C
1 2 3
4 5
4 5
C
D
A
B
D
T R
A C
E S
T E
C H
N
IC
A L
R A
N G
E A
R C
H
IT
E C
T E
N G
IN
E
E R
IN
G
S E
R V
IC
E
S rh o d
A
A F
P R
O
JE
C T
N o
R B
P R
O
JE
C T
N o
U N
IT
ED
STATES SPACE
FO
R
C E
E M
N
OF TH
AIR
FO
R
C
D E
E
E
A P
RT
T
M M X I X
K S
C C
-1
C O
N S
T R
U C
T V
E H
IC
L
E B
A R
R
IE
R S
NOT FOR CONSTRUCTION
DESIGN REVIEW ONLY
R
S U
L L
IV
A
N
K
F
IN
D L
A T
E R
J.
JA
C O
B S
K
F
IN
D L
A T
E R
R E
M O
V A
B L
E W
IR
E
C A
B L
E B
A R
R
IE
R S
T O
R A
G E
D E
T A
IL
S
D B
E H
E S
-0
S-504
N.T.S.
BOLLARD TO PASSIVE CABLE BARRIER SYSTEM DETAIL
A S-504 S-504
A S-504 S-504
8'-0" RAILROAD TRACK FOOTER
N.T.S.
BOLLARD TO PASSIVE CABLE BARRIER SYSTEM SECTION
4"x3"x3/4 STEEL PLATE WELDED TO 16"x16" TERMINAL POST
WITH 1" DIA. LOCKING PIN 16"x16" TERMINAL POST
6" SCHEDULE 80 PIPE
BOLLARD
N.T.S.
REMOVABLE WIRE CABLE BARRIER SYSTEM IN STORAGE POSITION DETAIL
B S-504 S-504
B S-504 S-504
DISTANCE TO BE SET AFTER BOLLARD &
TERMINAL POST HAVE BEEN CONNECTED
N.T.S.
REMOVABLE WIRE CABLE BARRIER SYSTEM IN STORAGE POSITION DETAIL
16"x16" TERMINAL POST
6" FENCE POST
3/4" WIRE CABLE
ASSEMBLY
16"x16" TERMINAL POST
6" SCHEDULE 80 PIPE
BOLLARD
REMOVABLE WIRE
ROPE PIN
FIXED WIRE
ROPE PIN
'-3
3/4" WIRE CABLE
ASSEMBLY
TOP OF FOUNDATION = EXISTING GRADE
3/4" WIRE CABLE
ASSEMBLY
REMOVABLE WIRE
ROPE PIN
FIXED WIRE
ROPE PIN
REMOVABLE WIRE
ROPE PIN
FIXED WIRE
ROPE PIN
16"x16" TERMINAL POSTREMOVABLE WIRE
ROPE PIN
FIXED WIRE
ROPE PIN
3/4" WIRE CABLE
ASSEMBLY
6" FENCE POST
'-4
/8
3'-6" MIN.
| Sheets and Views |
| G-001 COVER SHEET AND INDEX |
| S-001 ABBREVIATIONS, LEGENDS AND NOTES |
| S-101 VIF NORTH BARRIER PLAN VIEW |
| S-102 VIF SOUTH BARRIER PLAN VIEW |
| S-103 FAC 29150 PUMP STATION #7 BARRIER PLAN VIEW |
| S-104 COMPLEX 41 SOUTH GATE PLAN |
| S-501 BARRIER DETAILS |
| S-502 GATE DETAILS |
| S-503 FIXED WIRE CABLE BARRIER DETAILS |
| S-504 REMOVABLE WIRE CABLE BARRIER STORAGE DETAILS |