Fire Panel Specifications.xlsx
XLSX spreadsheet 15 KB Posted
- Solicitation number
- FA251726A007
About this file
This file is a fire alarm system panel specifications spreadsheet for Cheyenne Mountain Space Force Station detailing the technical configuration of 25 fire alarm control panels across multiple buildings. The specifications document the physical location, cabinet size, and component requirements for each panel, including power supplies (3-PPS/M or 3-PPS/M variants), loop cards (3-SSDC1), and various specialized modules such as battery chargers (3-BBC/M), addressable modules (3-ZA95A and 3-ZA40A), communication modules (CT and CR modules), annunciator modules (UM modules and SIGA-MCCT2A), and notification devices (SIGA MAB 12-12 switches). Each panel is assigned to specific buildings (numbered B101 through B12099) with panel cabinet sizes of either Cabinet 14 or Cabinet 21, and the spreadsheet tracks the exact quantities of each component required per panel.
The specifications indicate that all 25 panels require mass notification and annunciator capabilities, with most panels equipped with switches located at building entrances and hallways across multiple floors. The document serves as a bill of materials and technical baseline for the EST-3 to EST-4 fire alarm system upgrade at Peterson Space Force Base's Cheyenne Mountain facility, as referenced in solicitation FA251726A007. This spreadsheet would enable vendors to provide accurate pricing, procurement timelines, and installation planning for the complete system upgrade across all specified building locations.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| BLDG | PANEL LOCATION | PANEL SIZE | POWER SUPPLIES | LOOP CARDS | 3-BBC/M | 3-BPS/M | 3-ZA95A | 3-ZA40A | CT MODULE | CR2 | CR1 | CR MOUDLE | CT2 | CT1 | UM MODULE | CC2A Moudle | SIGA-MCCT2A | SIGA MAB | 12-12 SWITCHES | LOC | ANNUNCIATOR | MASSNOTIFICATION | ASU | UIO6 Motherboard |
| 101 CE Building | Main mechanical room | Cab 21 | 3X 3-PPS/M | 3X 3-SSDC1 | 1 | 1 | 3 | 6 | 1 | 0 | 0 | 0 | 2 | 2X 1 in 1st and 1 in 2nd floor | 2X 1 in 1st and 1 in 2nd floor | Y | Y | |||||||
| B15 Visitor Center | Mechanical room inside the building | Cab 21 | 2x 3- PPS/M | 3X 3-SSDC1 | 1 | 3 | 6 | 1 | 0 | 0 | 0 | 1 | 1 at the main enterance | 1 at the main enterance | Y | Y | ||||||||
| B326 | Inside building by main enterance | Cab 14 | 2x 3- PPS/M | 1X 3-SSDC1 | 1 | 3 | 6 | 1 | 0 | 2 | 4 | 2 | 1 at the main enterance | 1 at the main enterance | Y | Y | UIO6 Motherboard | |||||||
| B309 | Main mechanical room | Cab 21 | 2x 3- PPS/M | 1X 3-SSDC1 | 2 | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 2X one at each enterance | 2X one at each enterance | Y | Y | ||||||||
| B322 | Main Enterance | Cab 14 | 2x 3- PPS/M | 1X 3-SSDC1 | 1 | 4 | 4 | 0 | 0 | 0 | 0 | 1 | 0 | 0 | y | Y | ||||||||
| B300 | Inside building in an office area | Cab 21 | 3X 3-PPS/M | 4X 3-SSDC1 | 4 | 0 | 0 | 0 | 0 | 0 | 0 | 3 | 0 | 0 | y | Y | ||||||||
| B315 | Main mechanical room | Cab 21 | 2x 3- PPS/M | 1X 3-SSDC1 | 2 | 2 | 4 | 1 | 2 | 0 | 0 | 2 | 1 at the main enterance | 1 at the main enterance | Y | Y | ||||||||
| B1000 | Mechanical room 11E | Cab 21 | 3X 3-PPS/M | 4X 3-SSDC1 | 4 | 0 | 8 | 1 | 5 | 0 | 2 | 2X-1FL HALL, 1X-2FL HALL, 2X-3FL HALL | 1X-RM1108 (recessed), 1X-2FR HALL | Y | Y | |||||||||
| B2000 | Mechanical room 21W | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 3 | 8 | 3 | 1 | 2 | 1X-2FL HALL | Y | Y | |||||||||||
| B3000 | Mechanical room 31 | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 3 | 9 | 1 | 5 | 2 | 2X-2FL HALL, 2X-3FL HALL | 1X-1FL HALL | Y | Y | ||||||||||
| B4000 | Mechanical room 42 | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 3 | 10 | 2 | 1 | 2 | 1X-1FL HALL, 1X-3FL HALL | 1X-1FL HALL | Y | Y | ||||||||||
| B5000 | Mechanical room 52 | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 3 | 9 | 1 | 5 | 2 | Y | Y | ||||||||||||
| B6000 | Mechanical room 61 | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 3 | 3 | 6 | 2 | 1X-1FL HALL | Y | Y | ||||||||||||
| B7000 | Mechanical room 72 | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 3 | 3 | 2 | 11 | 1 | 2 | 1X-1F HALL, 1X-2FL HALL, 1X-3FL HALL | 1X-1FL HALL | Y | Y | |||||||||
| B8000 | Mechanical room 82 | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 3 | 4 | 1 | 10 | 1 | 2 | 1X-1FL HALL, 1X-2FL HALL, 1X-3FL HALL | 1X-1FL HALL | Y | Y | |||||||||
| B9000 | Mechanical room 91 | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 3 | 10 | 3 | 3 | 2 | 1X-1FL HALL | Y | Y | |||||||||||
| B10000 | Mechanical room 10-2 | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 3 | 6 | 4 | 1 | 2 | 1X-1FL HALL, 1X-2FL HALL | 1X-1FL HALL | Y | Y | ||||||||||
| B11000 | Mechanical room 111 | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 3 | 10 | 4 | 1 | 1 | 2 | 1X-1FL HALL | Y | Y | ||||||||||
| B12104 | By tank 28 | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 2 | 2 | 2 | Y | Y | ||||||||||||||
| B12108 | West Hallway | Cab 21 | 1x 3-pps/M | 3X 3-SSDC1 | 1 | 1 | 1 | 8 | 1 | 4 | 3 | 2 | 1X-1FL HALL | Y | Y | |||||||||
| B12000 | PC-14 | Cab 21 | 1X 3-PPS/M | 1X 3-SSDC1 | 2 | 1 | 1 | 2 | 1X-1FL HALL | Y | Y | |||||||||||||
| B12099 | Bus stop / Main tunnel | Cab 21 | 1x 3-pps/M | 2X 3-SSDC1 | 1 | 3 | 2 | 5 | 2 | Y | Y | |||||||||||||
| B100 | Room 112A | Cab 21 | 1x 3-pps/M | 2X 3-SSDC1 | 2 | 1 | 2 | 1 | 6 | 6 | 2 | 1X-1FL HALL | 1X-1FL HALL | Y | Y |