EXHIBIT M - Pre-Lease Building Security Plan.pdf

PDF 104 KB Posted

Attached to
New Lease for VA Clinic (CBOC) Tarrant County, Texas
Solicitation number
36C24W26R0055
Issued by

About this file

This is Exhibit M, a Pre-Lease Building Security Plan template for federal lease proposals.

The document establishes minimum security requirements that lessors must satisfy for new lease proposals. A licensed professional engineer must certify compliance with specifications including: window glazing and façade protection levels using WINGARD 4.1 or later or WINLAC 4.3 software; setback distances from the building's exterior to protected perimeters with bollards, planters, or street furniture to prevent vehicle access; separate HVAC systems for lobbies, mailrooms, and loading docks with low leakage isolation dampers, with air intakes positioned on the fourth floor or higher for buildings exceeding four stories, or on the roof for buildings of three stories or less; and grade-level windows and doors meeting current VA security requirements. The offeror must submit a Pre-Lease Building Security Plan addressing compliance with lease security standards, provide all design and engineering documents including structural calculations, supply bollards as required by the Contracting Officer's Representative (COR), and include an itemized cost estimate for all security items designated as "shell" and any Special Requirements in the Lease Security Standards section of the Request for Lease Proposal (RLP).

View the file

Other files

File Type Posted
S03 - Solicitation Amendment 0004 - Government Responses to Offerors Questions.pdf PDF
EXHIBIT R - PFD Tarrant County CBOC.pdf PDF
S03 - Solicitation Amendment 0003 - Government Responses to Offerors and RLP Solicitation Deadline Date Extended.pdf PDF
S03 - Solicitation Amendment 0002 - Government Responses to Offerors and RLP Solicitation Deadline Date Extended.pdf PDF
RLP 36C24W26R0055 - Solicitation Amendment 0001 - Government Responses to Offeror Questions.pdf PDF
36C24W26R0055 - RLP - AUG 2026.pdf PDF
36C24W26R0055 - RLP - AUG 2026.pdf PDF
EXHIBIT D - 3516 Solicitation Provisions - MAR 2026.pdf PDF
EXHIBIT I - Security Unit Price List FSL II - Oct 2024.xlsx XLSX spreadsheet
EXHIBIT J - Tarrant County Wage Determination - Building.pdf PDF
EXHIBIT A - Lease No- 36C24W26L0044 - Tarrant County Lease Proposal.pdf PDF
EXHIBIT F - Form 1364 Proposal to Lease Space.pdf PDF
EXHIBIT H - Prelease FPLS Evaluation Form 12000 - Parts A and B.pdf PDF
EXHIBIT L - FAR 52.204-24 Representation Digital Rev 10 20.pdf PDF
EXHIBIT N - Life Safety and Environment of Care Document List and Review Tool 10-2023 (R0).pdf PDF
EXHIBIT B - Agency Specific Requirements.pdf PDF
EXHIBIT B1 - Agency Specific Requirements - Document Hyperlinks.pdf PDF
EXHIBIT C - Security Requirements (FSL Level II).pdf PDF
EXHIBIT O - VHA Infection Control Risk Assessment ICRA 2023-1.0.pdf PDF
EXHIBIT P - VHA PCRA 31May2023-Final.pdf PDF
EXHIBIT Q - ADA Certification.pdf PDF
EXHIBIT E - 3517B General Clauses - APR 2026.pdf PDF
EXHIBIT G - Form 1217 - Lessor Annual Cost Statement.pdf PDF
EXHIBIT K - Delineated Area Map.pdf PDF
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXHIBIT M – PRE-LEASE BUILDING SECURITY PLAN

INITIALS: LESSOR: ________ GOVERNMENT: ________

PRE-LEASE BUILDING SECURITY PLAN

SECURITY FOR NEW LEASE PROPOSAL

The Lessor shall provide a written certification from a licensed professional engineer that the building conforms to a minimum of:

A. Window glazing and façade protection level, with a performance condition as specified in this Lease, as prescribed by WINGARD 4.1 or later or WINLAC 4.3 software.

B. Setback distance, as specified in this Lease, from the face of the building’s exterior to the protected/defended perimeter (i.e., any potential point of explosion). This means the distance from the building to the curb or other boundary protected by bollards, planters, or other street furniture. Such potential points of explosion may be, but are not limited to, such areas that could be accessible by any motorized vehicle (i.e., street, alley, sidewalk, driveway, parking lot).

C. Lobbies, mailrooms, and loading docks shall not share a return-air system with the remaining areas of the building. The Lessor shall provide lobby, mailroom, and loading dock ventilation systems outside air intakes and exhausts with low leakage, fast acting, isolation dampers that can be closed to isolate their systems.

Dedicated HVAC shall be required for mailrooms only when the Government specifically requires a centrally operated mailroom. On Buildings of more than four stories, air intakes shall be located on the fourth floor or higher. On Buildings of three stories or less, air intakes shall be located on the roof or as high as practical. Locating intakes high on a wall is preferred over a roof location.

D. The Offeror shall provide a Pre-Lease Building Security Plan (BSP) with its offer that addresses its compliance with the lease security standards, as described in this RLP and its attachments.

E. The Offeror shall provide the Government with all design and engineering documents, including structural engineering calculations.

F. All windows and doors at grade level shall be the most current VA security requirements.

The Offeror shall provide bollards around the property as required by the COR. Offers must include an itemized estimate for the costs of each security item identified as “shell” in the Lease Security Standards section elsewhere in this RLP and for any security item identified as a Special Requirement.

File details come from the government source that posted it. Updated .