Exhibit F - MEP Drawings.pdf
PDF 16 MB Posted
- Solicitation number
- RFP202690000697
- Issued by
- Mingo County, West Virginia
About this file
Exhibit F contains Mechanical, Electrical, and Plumbing (MEP) drawings for the Evansdale Crossing Third and Fourth Floor Renovations project at West Virginia University in Morgantown, West Virginia. The drawings detail comprehensive renovations to support a new testing center, offices, meeting rooms, and support spaces across approximately 62 Morrill Way. The project encompasses fire protection systems complying with NFPA 1 (2021 Amended), NFPA 13 (2016), and NFPA 20 (2016) standards, with FM Global project fire protection requirements. The plumbing scope includes installation of new fixtures such as water closets, lavatories, instantaneous electric water heaters (8 kW, 240V), water coolers, and associated supply and waste piping. The mechanical systems involve relocation and rebalancing of existing Variable Air Volume (VAV) boxes and Fan Powered VAV units, installation of new electric heating coils in terminal units, and coordination with existing rooftop units. The electrical work includes new lighting fixtures, power distribution, signal systems, and control panels throughout the renovated areas, with multiple existing panels including L3PA, L3PB, L3PC, L3PD, H3MA, H3LA, HGS, and LGS serving the space.
The drawings establish detailed specifications for hydraulic calculations based on water flow tests conducted within the previous 12 months, with design densities ranging from 0.10 to 0.15 GPM/SF depending on occupancy classification (Light Hazard and Ordinary Group 1). Fire protection piping must be concealed above ceilings or within walls, with sprinkler contractors prohibited from installing piping above electrical equipment. The project requires coordination among fire protection, plumbing, mechanical, and electrical contractors, with minimum 24-hour advance notice required for system shutdowns and two-week notice for major systems. All demolition of existing systems must be completed back to main lines within the scope of work areas, with salvaged items stored on-site as designated by the owner. The drawings contain comprehensive legends, abbreviations, schedules, and technical details for fixture connections, ductwork configurations, conduit support systems, and outlet specifications, establishing clear installation standards and coordination requirements across all mechanical, electrical, and plumbing trades.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXHIBIT F - MEP DRAWINGS
• NFPA 1, 2021 - AMENDED
• NFPA 13, 2016 - NOT AMENDED
• NFPA 20, 2016 - NOT AMENDED
• FM GLOBAL PROJECT
FIRE PROTECTION - PROJECT CODES
FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR OBTAINING A CURRENT
WATER FLOW TEST FROM THE LOCAL WATER AUTORITY. THE OBTAINED FLOW
TEST MUST HAVE BEEN CONDUCTED WITHIN THE LAST 12-MONTHS OF THE
BEGINNING OF CONSTRUCTION OR A NEW FLOW TEST MUST BE PERFORMED
PRIOR TO PERFORMING HYDRAULIC CALCULATIONS FOR THIS PROJECT.
HYDRAULIC DESIGN DATA
CL
CONCEALED PIPING
CL
PIPING EXPOSED TO VIEW
SEAL SLEEVE THRU FIRE
RATED WALLS AND MAKE
FIREPROOF AND SMOKE TIGHT
PIPE TO BE CENTERED IN
SLEEVE. DO NOT
SUPPORT PIPE FROM
SLEEVE
TERMINATE SLEEVE
FLUSH WITH FINISH
WALL SURFACE
FINISHED WALL SURFACE
FIRE RATED PARTITION
SCHEDULE 40 STEEL PIPE
SLEEVE OF SIZE TO PASS PIPE.
ESCUTCHEON (TYPICAL)
PIPE
FINISHED ESCUTCHEON PLATE FLUSH
AGAINST WALL AND OF SIZE TO
COMPLETELY COVER OPENING (TYPICAL)
PROVIDE FIREPROOFING MATERIAL
BETWEEN PIPE SLEEVE AND PIPE.
FINISHED WALL SURFACE
CL
PIPE (SIZE AS INDICATED ON PLAN)
PROVIDE FIREPROOFING
MATERIAL BETWEEN
PIPE SLEEVE AND PIPE
SCHEDULE 40
STEEL PIPE SLEEVE
FINISHED FLOOR
TERMINATE PIPE SLEEVE
2" ABOVE FINISHED FLOOR
(SEE SPECIFICATIONS)
PIPE TO BE CENTERED IN
SLEEVE. DO NOT SUPPORT
PIPE FROM SLEEVE
PIPE INSULATION
SHALL TERMINATE
FLUSH AT FINISH
FLOOR
SCHEDULE 40 STEEL
PIPE SLEEVE
PROVIDE FIREPROOFING
MATERIAL BETWEEN PIPE SLEEVE
AND PIPE
INTERIOR WALLS
NOT TO SCALE NOT TO SCALE
PIPE SLEEVE THRU FLOOR DETAILPIPE SLEEVE THRU WALL DETAIL
SPRINKLER
BRANCH PIPING TEE CONNECTION
EXTENDED
ESCUTCHEON
SUSPENDED CEILING
RECESSED PENDENT
SPRINKLER
LENGTH AS
REQUIRED
RECESSED
PENDENT SPRINKLER
W/GUARD
RECESSED
PENDENT
SPRINKLER
CONCEALED
PENDENT
SPRINKLER
UPRIGHT
PENDENT
SPRINKLER
• LISTED/APPROVED: THE HOSES MUST BE LISTED FOR FIRE SPRINKLER USE (E.G., BY UL, FM).
• LENGTH: THE UNSUPPORTED LENGTH BETWEEN HANGERS CANNOT EXCEED 6 FEET (6'-0").
• ANCHORING: HANGERS MUST BE ATTACHED TO THE BUILDING STRUCTURE (JOISTS, BEAMS),
NOT JUST THE CEILING GRID, USING SECURE FASTENERS SUCH AS SELF-TAPPING SCREWS TO
ENSURE STABILITY
• CEILING STANDARDS: THE SUSPENDED CEILING ITSELF MUST MEET ASTM C635/C636
STANDARDS.
NFPA 13 KEY REQUIREMENTS FOR FLEXIBLE
SPRINKLER HOSE USAGE:
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C
U s e rs
\r s h o m o \A p p D a ta
\L o c a l\ A u to d e s k \R e v it L o c a l\ M
E P
-2 -1 x R rs h o m o .r v t
/3
/2
:3 :0
P
M
FP001
SYMBOLS AND
GENERAL NOTES
01/30/26
JMW
RGS
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
FIRE SPRINKLER DESIGN CATEGORY SCHEDULE
◊ CATEGORY
OCCUPANCY
CLASSIFICATION TYPE OF SPRINKLER SYSTEM
DESIGN AREA OF WATER
APPLICATION MINIMUM DENSITY
MAXIMUM AREA
PER SPRINKLER SPRINKLER TEMPERATURE RATING
SPRINKLER
"K" FACTOR SPRINKLER HEAD TYPE
HOSE STREAM
ALLOWANCE
HOSE STREAM ALLOWANCE
DURATION
2 MECHANICAL, ELECTRICAL, AND STORAGE ROOMS ORDINARY GROUP 1
HAZARD
WET PIPE 1500 SF .15 GPM/SF 130 SF 165 °F 5.6 STANDARD RESPONSE, STANDARD COVERAGE, BRONZE UPRIGHT 250 GPM 60 MINUTES
3 OFFICES, CORRIDORS AND RESTROOMS LIGHT HAZARD WET PIPE 1500 SF .10 GPM/SF 225 SF 155 °F 5.6 IN ACT OR GWB HARD CEILING - QUICK RESPONSE, STANDARD
COVERAGE, CONCEALED PENDENT WITH WHITE COVERPLATE, OR
BRONZE UPRIGHT IN AREAS WITH NO CEILING
100 GPM 60 MINUTES
FIRE PROTECTION DRAWING LIST - EVENSDALE
SHEET
NUMBER SHEET NAME 01/30/2026 - SET
FP001 SYMBOLS AND GENERAL NOTES X
FP103 THIRD FLOOR PLAN - AREA A - FIRE PROTECTION - DEMOLITION X
FP203 THIRD FLOOR PLAN - AREA A - FIRE PROTECTION - NEW WORK X
PIPE PENETRATION DETAIL
1. DO NOT SCALE DRAWINGS
2. ALL WORK PERFORMED ON THIS BUILDING SHALL BE IN COMPLIANCE WITH ALL PERTINENT CODES, RULES, ORDANCES, AND REGULATIONS OF THE LOCAL AND STATE GOVERNING AUTHORITIES.
3. ALL WORK PERFORMED AND IN CONNECTION WITH THESE DRAWINGS AND SPECIFICATIONS SHALL BE IN STRICT COMPLIANCE WITH THE LATEST OSHA SAFETY AND HEALTH STANDARDS MLS ELEC. SAFETY HANDBOOK
#GS-11294.
4. THE DRAWINGS, BY THEIR NATURE, CANNOT REVEAL ALL CONDITIONS THAT EXIST ON THE SITE. SHOULD CONDITIONS BE FOUND TO VARY SUBSTANTIALLY FROM THIS REPORT, CHANGES IN THE WORK WILL BE MADE WITH RESULTING CREDITS OR EXPENDITURES TO THE CONTRACT SUM ACCURING TO THE OWNER.
5. THE DRAWINGS INDICATE GENERAL LAYOUT AND DO NOT NECESSARILY REPRESENT A COMPLETE FIELD VERIFIED LAYOUT. THE MAJORITY OF FIRE PROTECTION ITEMS ARE SHOWN ON THE DRAWINGS. CERTAIN ITEMS ARE SHOWN AND INDICATED TO REMAIN OR BE REMOVED. GENERALLY, ALL FIRE PROTECTION DEMOLTION IS DESCRIBED BY THE NOTES. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS WIHTIN THE DEMOLITION AREAS. REPORT ANY DISCREPANCIES FOUND TO THE ARCHITECT FOR CLARIFICATION
BEFORE PROCEEDING.
6. ALL FIRE PROTECTION EQUIPMENT, PIPING, ETC. INDICATED ON THE DRAWINGS, DESCRIBED IN THE NOTES, AND WHICH IS NOT REQUIRED TO FUNCTION AS PART OF THE FINAL SYSTEM, SHALL BE REMOVED IN ITS ENTIRETY.
ALL REMOVED MATERIAL, UNLESS DESIGNATED FOR SALVAGE, SHALL BE IMMEDIATELY REMOVED FROM THE SITE AND DISPOSED OF IN ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL CODES AND REGULAITONS.
SALVAGED ITEMS SHALL BE STORED ON SITE IN A LOCATION DESIGNATED BY THE OWNER.
7. WHERE IT BECOMES NECESSARY TO TEMPORARILY DISTURB SYSTEMS TO PERMIT EXECUTION OF THE DEMOLITION PROCESS, IT SHALL BE RESPONSIBILITY OF THE CONTRACTOR TO CONTACT THE OWNER, THROUGH THE ARCHITECT, TO SCHEDULE A SHUTDOWN. THE DEMOLITION CONTRACTOR SHALL GIVE A MINIMUM OF 24-HOUR ADVANCE NOTICE FOR ANY SUCH GIVEN SHUTDOWN. IF THE SHUTDOWN INCLUDES MAJOR SYSTEMS, SUCH AS DOMESTIC FEED, STEAM, ELECTRICAL QMB PANELS, ETC., TWO-WEEK NOTICE SHALL
BE REQUIRED.
8. THE OWNER SHALL HAVE THE OPPORTUNITY TO TAG SPECIFIC ITEMS FOR SELECTIVE REMOVAL OF ITEMS WHICH SHALL REMAIN. THIS DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFE REMOVAL OF ANY SUCH TAGGED ITEMS. THIS CONTRACTOR SHALL PLACE IN STORAGE ON SITE ANY SUCH ITEMS AS DIRECTED BY THE OWNER. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL ITEMS TAGGED
TO REMAIN.
9. ALL EXISTING EXTERIOR WALLS AND SURFACES (EXCLUSIVE OR FURRED AREAS), SHAFT WALLS, WALLS ADJACENT TO DEMOLITION AREA TO REMAIN, SHALL BE PROTECTED FROM DAMAGE AND UNDISTURBED.
10. ANY SALVAGE VALUE ASSOCIATED WITH DEMOLITISHED ITEMS IS THE CONTRACTOR'S. THE CONTRACTOR
SHOULD USE ANY SALVAGE VALUE AS A MEAN OF REDUCING THEIR BID PRICE.
11. IF DURING THE COURSE OF DEMOLITION, EXISTING UTILITIES ARE ENCOUNTERED, WORK IN THAT AREA IS TO BE HALTED UNTIL THE STATUS OF THE THE UTILITIES HAS BEEN ASCERTAINED BY THE ARCHITECT AND AUTHORITY
TO PROCEED GIVEN BY THE ARCHITECT.
12. ALL CUTTING, DEMOLITION AND PATCHING OF EXISTING AND/OR EQUIPMENT IS TO BE PERFORMED BY THE
CONTRACTOR AND/OR EQUIPMENT UNLESS NOTED OTHERWISE.
13. WHERE DEMOLITION OF EXISTING CONSTRUCTION AND/OR EQUIPMENT OCCURS, PATCH AND REPAIR FLOOR, WALL AND CEILING CONSTRUCTION AND/OR FINISHES TO MATCH ADJACENT CONSTRUCTION AND/OR FINISHES.
FIRE PROTECTION DEMOLITION NOTES:
1. SPRINKLER SYSTEM COMPONENTS ARE INDICATED ON DRAWING FOR REVIEW AND INFORMATIONAL PURPOSES ONLY. THE CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL COMPONENTS FOR A COMPLETE
FIRE SUPPRESSION INSTALLATION AS PER THE INTENT OF THE PROJECT SCOPE OF WORK AND
SPECIFICATIONS. ALL SPRINKLER SYSTEM COMPONENT INSTALLATIONS SHALL CONFORM TO THE CODES AND AMENDMENTS INDICATED ON THIS SHEET, AND INSURANCE UNDERWRITER REQUIREMENTS. PIPE
SIZING SHALL BE BY HYDRAULIC CALCULATION.
2. ALL SPRINKLERS SHALL BE PLACED IN THE CENTER OF CEILING TILES WHERE CEILING TILES ARE LOCATED.
3. THE CONTRACTOR SHALL COORDINATE SPRINKLER INSTALLATION IN ALL AREAS WITH LIGHTING AND
DIFFUSER LOCATIONS.
4. ALL DIMENSIONS AND EXISTING CONDITIONS SHALL BE CHECKED AND VERIFIED BY CONTRACTOR AT THE
SITE.
5. ALL FIRE SPRINKLER PIPING SHALL BE CONCEALED ABOVE CEILING OR IN WALLS. IN AREAS WHERE THERE ARE NO CEILINGS, THE CONTRACTOR SHALL INSTALL THE FIRE SPRINKLER PIPING AS HIGH AS CONDITIONS
ALLOW.
6. THE CONTRACTOR SHALL OBTAIN CURRENT FIRE HYDRANT FLOW TEST DATA, WHICH MUST BE FROM A TEST PERFORMED WITHIN THE PAST YEAR PERIOD, OR SHALL PERFORM A NEW FIRE HYDRANT FLOW TEST
TO OBTAIN DATA.
7. THE CONTRACTOR SHALL LIMIT THE DESIGN WATER VELOCITIES OF HYDRAULICALLY DESIGNED SPRINKLER SYSTEMS TO NOT MORE THAN 20 FEET PER SECOND FOR ALL ABOVEGROUND SPRINKLER PIPING.
8. SPRINKLER CONTRACTOR SHALL BE PROHIBITED FROM THE INSTALLATION OF ANY AND ALL FIRE
SPRINKLER PIPING ABOVE ANY ELECTRICAL EQUIPMENT. THIS REQUIREMENT SHALL BE FULLY
COORDINATED BY SPRINKLER CONTRACTOR AND INDICATED AS SUCH AS PART OF SHOP DRAWING
SUBMITTALS.
9. SPRINKLER CONTRACTOR SHALL PROVIDE ALL DRY SPRINKLER SYSTEM INDIVIDUAL ZONE REMOTE INSPECTOR TEST CONNECTION(S) ALONG WITH ALL RELATED PIPING, AS REQUIRED PER NFPA 13, UNDERWRITER AND LOCAL AUTHORITY HAVING JURISDICTION. FULLY COORDINATE WITH PLUMBING
CONTRACTOR.
FIRE PROTECTION GENERAL NOTES:
TYPICAL PENDENT SPRINKLER DETAIL
BASIS OF DESIGNBASIS OF DESIGN
FM GLOBAL PROJECT
ANY FLEXIBLE PIPING USED ON THIS
PROJECT MUST SPECIFICALLY BE
FM GLOBAL APPROVED.
REVISIONS
1 2 3 4 5 6
A
B
C
D
SCOPE OF FIRE
PROTECTION
WORK AREA
SCOPE OF FIRE
PROTECTION
WORK AREA
SCOPE OF FIRE
PROTECTION
WORK AREA
SCOPE OF FIRE PROTECTION
WORK AREA
SYSTEM IMPAIRMENT:
• FIRE ALARM SYSTEM: IF OUT OF SERVICE FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD.
• AUTOMATIC SPRINKLER SYSTEM: IF OUT OF SERVICE FOR MORE THAN 10 HOURS IN A 24-HOUR PERIOD.
• LOCAL AUTHORITY: THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ) MAY HAVE STRICTER REQUIREMENTS.
HOT WORK REQUIREMENT:
• SPARKS/SLAG: IF SPARKS OR HOT MATERIALS MIGHT SPREAD TO COMBUSTIBLES WITHIN 35 FEET OR THROUGH OPENINGS.
• COMBUSTIBLE EXPOSURE: IF COMBUSTIBLES ARE EASILY IGNITED BY SPARKS, EVEN IF FURTHER AWAY.
• CONCEALED SPACES: IF OPENINGS COULD EXPOSE HIDDEN COMBUSTIBLE MATERIALS.
• DURATION: MUST CONTINUE FOR AT LEAST ONE HOUR (OR AS DIRECTED) AFTER HOT WORK IS FINISHED.
CONTRACTOR'S RESPONSIBILITIES DURING A FIRE WATCH:
• CONTINUOUS PATROLS: REGULARLY CHECK ALL AREAS FOR SMOKE, FIRE, OR ISSUES.
• IMMEDIATE ACTION: ALERT EMERGENCY SERVICES AND OCCUPANTS TO ANY FIRE.
• EQUIPMENT KNOWLEDGE: KNOW THE LOCATION OF ALARMS AND EXTINGUISHERS.
• DOCUMENTATION: KEEP DETAILED LOGS OF THE WATCH.
FIRE WATCH - CONTRACTOR'S RESPONSIBILITY (NFPA 13/ NFPA 72)
ALL EXISTING SPRINKLER, DROPS, ARM OVERS, AND BRANCH PIPING TO BE
DEMOLISHED BACK TO THE MAIN SPRINKLER LINE WITHIN THE SCOPE OF
WORK AREA. CONTRACTOR AT THEIR DISCRETION TO EITHER CAP OR PLUG
WHERE REQUIRED.
DEMOLITION NOTE FOR AREA OF WORK:
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C
U s e rs
\r s h o m o \A p p D a ta
\L o c a l\ A u to d e s k \R e v it L o c a l\ M
E P
-2 -1 x R rs h o m o .r v t
/3
/2
:3 :0
P
M
FP103
THIRD FLOOR PLAN -
AREA A - FIRE
PROTECTION -
DEMOLITION
01/30/26
JMW
RGS
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"
THIRD FLOOR - DEMOLITION
FIRE PROTECTION KEYNOTES
Key
Value Keynote Text
AA
BB
CC
D
ACCOMMODATIONS
BREAKROOM
TESTING CENTER
TESTING CENTER
MEN
WOMEN
MECH
IT CLOSET
OFFICE
STORAGE
KITCHEN
OFFICE
OFFICE
OFFICE
OFFICE
COLLABORATION
2 2
2 22
3 3
3 3 3 3
SCOPE OF FIRE
PROTECTION
WORK AREA
SCOPE OF FIRE
PROTECTION
WORK AREA
SCOPE OF FIRE
PROTECTION
WORK AREA
SCOPE OF FIRE PROTECTION
WORK AREA
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
3 3
11 2
FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR OBTAINING A CURRENT
WATER FLOW TEST FROM THE LOCAL WATER AUTORITY. THE OBTAINED FLOW
TEST MUST HAVE BEEN CONDUCTED WITHIN THE LAST 12-MONTHS OF THE
BEGINNING OF CONSTRUCTION OR A NEW FLOW TEST MUST BE PERFORMED
PRIOR TO PERFORMING HYDRAULIC CALCULATIONS FOR THIS PROJECT.
HYDRAULIC DESIGN DATA
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C
U s e rs
\r s h o m o \A p p D a ta
\L o c a l\ A u to d e s k \R e v it L o c a l\ M
E P
-2 -1 x R rs h o m o .r v t
/3
/2
:3 :3
P
M
FP203
THIRD FLOOR PLAN -
AREA A - FIRE
PROTECTION - NEW
WORK
01/30/26
JMW
RGS
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"
THIRD FLOOR - NEW WORK
FIRE PROTECTION KEYNOTES
Key
Value Keynote Text
1 NFPA 13 SMALL ROOM RULE (3.3.196) - CLASSIFICATION: LIGHT HAZARD,
UNOBSTRUCTED, LESS THAN 800 SQ. FT
2 CONCEALED PENDENT SPRINKLER (TYPICAL
3 SPRINKLER CONTRACTOR SHALL BE PROHIBITED FROM THE INSTALLATION OF
ANY AND FIRE SPRINKLER PIPING ABOVE ANY ELECTRICAL EQUIPMENT. THIS
REQUIREMENT SHALL BE FULLY COORDINATED BY SPRINKLER CONTRACTOR
AND INDICATED AS SUCH AS PART OF SHOP DRAWING SUBMITTALS. (TYPICAL)
PLUMBING LEGEND
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
3-WAY VALVE CARBON DIOXIDE OUTLET
3-WAY SOLENOID VALVE DEIONIZED WATER OUTLET
WATER RISER (SIZE 5") GAS OUTLET
SANITARY/WASTE OR VENT STACK (SIZE 6") MEDICAL AIR OUTLET
AUTOMATIC AIR VENT MEDICAL VACUUM OUTLET
BACK FLOW PREVENTER NITROGEN OUTLET
BALANCING VALVE NITROUS OXIDE OUTLET
BALL VALVE LEVER OXYGEN OUTLET
BALL VALVE LOCKING W/ IDENTIFICATION REVERSE OSMOSIS OUTLET
OS & Y VALVE VACUUM OUTLET
BALL VALVE SOLENOID WATER OUTLET
BUTTERFLY VALVE LEVER WASTE ANESTHETIC GAS DISPOSAL OUTLET
BUTTERFLY VALVE MOTORIZED ACCESS/ZONE PANEL BOX 12x4
CHECK VALVE ACCESS/PANEL BOX 18x4
CIRCULATING PUMP PILOT OPERATED VALVE
CLEANOUT IN RISER PIPE ANCHOR
CLEANOUT EXTENDED UP TO FLOOR/GRADE PIPE BOTTOM CONNECTION
COMBINATION HOSE BIBB PIPE DOWN
CONCENTRIC REDUCER PIPE GUIDE
DIAPHRAGM VALVE PLUG VALVE
DOUBLE CHECK VALVE PRESSURE GAUGE
ECCENTRIC REDUCER PRESSURE REDUCING VALVE
CAP OR PLUG PRESSURE SWITCH
EXPOSED MIXING VALVE RECESSED MIXING VALVE
FILTER RELIEF VALVE
FLEX CONNECTION ROOF DRAIN (RD)
FLOOR DRAIN W/ OUT TRAP SECONDARY ROOF DRAIN (SRD)
FLOOR DRAIN CORNER CONNECTION SHOWER HEAD
FLOOR DRAIN SIDE CONNECTION STRAINER
FLOOR SINK WITH 1/2 GRATE TOP TEMPERATURE GAUGE
FLOOR SINK WITH 3/4 GRATE TOP TEMPERATURE SWITCH
FLOW DIRECTION ARROW TRAP PRIMER
FUNNEL DRAIN UNION
GAS COCK VALVE VALVE AND VALVE BOX
GAS PRESSURE REGULATOR VENTED WASTE FLOW VALVE
GATE VALVE WASHING MACHINE SUPPLY AND DRAIN UNIT
MOTORIZED VALVE HOSE BIBB
GATE VALVE OS & Y WALL HYDRANT
PRESSURE REGULATOR VALVE NEW CONNECTION TO EXISTING
SOLENOID VALVE INDICATES NOTE LOCATED ELSEWHERE ON
DRAWING
AND NOTE NUMBER
HAMMER ARRESTER SQUARE FOOT
METER
DETAIL/PLAN REFERENCE SYMBOL
AIR OUTLET INDICATES DRAWING No. FOR WHICH
THE
DETAIL/PLAN IS LOCATED.
INDICATES DETAIL/PLAN NUMBER
S
BP
S
M
F
R
M
S
M
A
X
FXXX
X
WH
HB
TP
TS
PS
WAGD
W
V
RO
O
NO
N
MV
MA
G
DE
CO
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
EXTEND ALL CLEANOUTS ON SEWER LINES BELOW SLAB ON GRADE TO FINISHED FLOOR LEVEL.
COORDINATE LOCATIONS OF ALL LINES AND EQUIPMENT WITH OTHER CONTRACTORS.
AT LOCATIONS INDICATED TO CONNECT NEW PLUMBING LINES TO EXISTING LINES; CONTRACTOR TO DETERMINE EXACT SIZE, LOCATION AND ELEVATION OF EXISTING LINES AT SITE BEFORE INSTALLING NEW LINES.
THE LOCATIONS, SIZES AND ELEVATIONS OF EXISTING LINES SHOWN ON PLAN ARE RESULTS OF INFORMATION OBTAINED FROM EXISTING DRAWING AND FIELD SURVEYS. THE CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS, SIZE AND ELEVATIONS OF EXISTING LINES AT THE SITE BEFORE THE START OF NEW WORK.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH ALL UTILITY AUTHORITIES FOR INSTALLATION
REQUIREMENTS, REGULATIONS, FEES, PERMITS AND APPROVALS BEFORE THE START OF WORK.
ALL INTERIOR STORMWATER PIPING, 4" AND LARGER, SHALL BE SLOPED AT 1/8" PER FOOT, UNLESS NOTED OTHERWISE. ALL INTERIOR STORMWATER PIPING, 3" AND SMALLER, SHALL BE SLOPED AT 1/4" PER FOOT, UNLESS
OTHERWISE NOTED.
THE CONTRACTOR SHALL REFER TO APPLICABLE CODES DRAINAGE SYSTEM FITTINGS.
ALL INTERIOR, ABOVE GROUND, HORIZONTAL AND VERTICAL STORM DRAINAGE SYSTEMS SHALL BE INSULATED AS
SPECIFIED.
DIELECTRIC UNIONS AND FLANGES SHALL BE USED ON ALL CONNECTIONS BETWEEN DISSIMILAR METALS.
THE DRAWINGS ARE DIAGRAMMATIC AND SHOW ONLY THE GENERAL ARRANGEMENTS OF ALL PIPING AND EQUIPMENT. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO SHOW OR INDICATE ALL
OFFSETS, FITTINGS, AND ACCESSORIES WHICH MAY BE REQUIRED.
ALL PIPE PENETRATIONS THROUGH CHASE, WALLS OR FLOORS WHICH ARE FIRE-RATED, SHALL BE PROPERLY SEALED TO MAINTAIN FIRE PROTECTIONS. CONTRACTOR SHALL SUMMIT PROPOSED UL LISTED SYSTEM FOR
REVIEW.
REPORT AND DISCREPANCIES FOUND IN THE DRAWINGS AND/OR IN THE SPECIFICATIONS DURING THE BIDDING
PROCESS FOR CLARIFICATION BY THE ENGINEER AND/OR ARCHITECT.
MEANS OF ACCESS SHALL BE PROVIDED TO CONCEALED TRAPS, VALVES, CLEANOUTS, DRAIN POINTS OR SIMILAR ITEMS. CONTRACTORS SHALL COORDINATE THE LOCATIONS AND QUANTITIES OF ALL ACCESS PANELS DURING
BIDDING PHASE. ACCESS PANELS WILL BE FURNISHED AND INSTALLED BY OTHERS.
FOLLOW THE REQUIREMENTS OF THE LATEST EDITION OF INTERNATIONAL PLUMBING CODE.
PROVIDE CLEANOUTS IN SANITARY AND STORM PIPING SYSTEMS AT ENDS OF RUNS, AT CHANGES IN DIRECTION, AT BASE OF STACKS, AND AT 50 FOOT INTERVALS IN HORIZONTAL PIPING, AND ELSEWHERE AS INDICATED.
ALL PIPING NOTED ABOVE OR AT CEILING, SHALL BE TIGHT TO UNDERSIDE OF FLOOR SLAB WITH THE SPACE FOR
INSULATION AND HANGERS AS REQUIRED.
WHERE DOMESTIC COLD WATER, DOMESTIC HOT WATER, DOMESTIC HOT WATER RETURN, AIR OXYGEN, VACUUM AND NITROGEN LINES ARE NOTED TO BE RUN AT CEILING AND/OR ABOVE CEILING, RUN LINES AS HIGH AS POSSIBLE.
WHERE SANITARY SEWER, SANITARY AND VENT LINES ARE NOTED TO BE RUN AT CEILING, ABOVE CEILING AND/OR BELOW FLOOR, RUN LINES AS HIGH AS POSSIBLE UNLESS LINES ARE RUN BELOW SLAB ON GRADE.
PLUMBING GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
DO NOT SCALE DRAWINGS
ANY SALVAGE VALUE ASSOCIATED WITH DEMOLISHED ITEMS IS THE CONTRACTOR'S. THE CONTRACTOR SHOULD
USE ANY SALVAGE VALUE AS A MEANS OF REDUCING THEIR BID PRICE.
ALL WORK PERFORMED ON THIS BUILDING SHALL BE IN COMPLIANCE WITH ALL PERTINENT CODES, RULES, ORDINANCES, AND REGULATIONS OF THE LOCAL AND STATE GOVERNING AUTHORITIES.
ALL WORK PERFORMED AND IN CONNECTION WITH THESE DRAWINGS AND SPECIFICATIONS SHALL BE IN STRICT COMPLIANCE WITH THE LATEST OSHA SAFETY AND HEALTH STANDARDS MLS ELEC. SAFETY HANDBOOK #GS-11294.
THESE DRAWINGS, BY THEIR NATURE, CANNOT REVEAL ALL CONDITIONS THAT EXIST ON THE SITE. SHOULD CONDITIONS BE FOUND TO VARY SUBSTANTIALLY FROM THIS REPORT, CHANGES IN THE WORK WILL BE MADE WITH
RESULTING CREDITS OR EXPENDITURES TO THE CONTRACT SUM ACCRUING TO THE OWNER.
THE DRAWINGS INDICATE GENERAL LAYOUT AND DO NOT NECESSARILY REPRESENT A COMPLETE FIELD VERIFIED LAYOUT. THE MAJORITY OF MECHANICAL ITEMS ARE SHOWN ON THE DRAWINGS. CERTAIN ITEMS ARE SHOWN AND INDICATED TO REMAIN OR BE REMOVED. GENERALLY, ALL MECHANICAL DEMOLITION IS DESCRIBED BY THE NOTES.
THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS WITHIN THE DEMOLITION AREAS. REPORT ANY
DISCREPANCIES FOUND TO THE ARCHITECT FOR CLARIFICATION BEFORE PROCEEDING.
ALL PLUMBING FIXTURES, EQUIPMENT, PIPING, ETC. INDICATED ON THE DRAWINGS DESCRIBED IN THE NOTES AND WHICH IS NOT REQUIRED TO FUNCTION AS PART OF THE FINAL SYSTEM, SHALL BE REMOVED IN ITS ENTIRETY. ALL REMOVED MATERIAL, UNLESS DESIGNATED FOR SALVAGE, SHALL BE IMMEDIATELY REMOVED FROM THE SITE AND DISPOSED OF IN ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL CODES AND REGULATIONS. SALVAGED
ITEMS SHALL BE STORED ON SITE IN A LOCATION DESIGNATED BY THE OWNER.
WHERE IT BECOMES NECESSARY TO TEMPORARILY DISTURB SYSTEMS TO PERMIT EXECUTION OF THE DEMOLITION PROCESS, IT SHALL BE RESPONSIBILITY OF THE CONTRACTOR TO CONTACT THE OWNER, THROUGH THE ARCHITECT, TO SCHEDULE A SHUTDOWN. THE DEMOLITION CONTRACTOR SHALL GIVE A MINIMUM OF 24-HOUR ADVANCED NOTICE FOR ANY SUCH GIVEN SHUTDOWN. IF THE SHUTDOWN INCLUDES MAJOR SYSTEMS, SUCH AS DOMESTIC FEED, STEAM, ELECTRICAL QMB PANELS, ETC., TWO-WEEK NOTICE SHALL BE REQUIRED.
THE OWNER WILL BE TAGGING SPECIFIC ITEMS FOR SELECTIVE REMOVAL FOR ITEMS WHICH SHALL REMAIN. THIS DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFE REMOVAL OF ANY SUCH TAGGED ITEMS. THIS CONTRACTOR SHALL PLACE IN STORAGE ON SITE ANY SUCH ITEMS AS DIRECTED BY THE OWNER. THIS
CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL ITEMS TAGGED TO REMAIN.
ALL EXISTING EXTERIOR WALLS AND SURFACES (EXCLUSIVE OR FURRED AREAS), SHAFT WALLS, WALLS ADJACENT
TO DEMOLITION AREA TO REMAIN, SHALL BE PROTECTED FROM DAMAGE AND UNDISTURBED.
THE PLUMBING CONTRACTOR SHALL SCHEDULE HIS WORK WITH THE ARCHITECT IN ORDER TO HAVE THE ELECTRICAL CONTRACTOR DISCONNECT AND RECONNECT ALL CIRCUITS ASSOCIATED WITH THE FIRE ALARM SYSTEM. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ANY CONFLICTS WITH A LIFE SAFETY SYSTEM ON
ELEMENTS THAT ARE INDICATED TO BE REMOVED.
ALL RAIN WATER CONDUCTORS AND ASSOCIATED VENT STACKS SHALL REMAIN INTACT AND NOT BE DISTURBED THROUGHOUT THE DEMOLITION PROCESS. THE CONTRACTOR SHALL INSTALL BRACING AND BRACKETS AS NECESSARY FOR SUPPORT OF PIPING DUE TO IMPACT OF DEMOLITION OF WALL/CEILING SYSTEM.
THE PLUMBING CONTRACTOR SHALL INCLUDE IN HIS BID THE COST OF DISCONNECTING AND REMOVING ALL PLUMBING EQUIPMENT, PIPING, LOUVERS, DUCTWORK, GRILLES, CONTROLS, ETC., COMPLETE BUT NOT REQUIRED TO FUNCTION UNDER THIS CONTRACT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL AND CLEAN- UP OF ALL DEBRIS ASSOCIATED WITH THE DEMOLITION OF PLUMBING ITEMS. HE SHALL REFER TO THE ARCHITECT'S
PHASING PLAN FOR THE SCHEDULING OF HIS WORK.
THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND PAINTING ALL REMAINING OPENINGS IN THE INTERIOR WALLS, FLOORS, AND CEILINGS. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING, ETC., OF ALL REMAINING OPENINGS THROUGH EXTERIOR WALLS AND ROOF.
IF DURING THE COURSE OF DEMOLITION, EXISTING UTILITIES ARE ENCOUNTERED, WORK IN THAT AREA IS TO BE HALTED UNTIL THE STATUS OF THE UTILITIES HAS BEEN ASCERTAINED BY THE ARCHITECT AND AUTHORITY TO
PROCEED GIVEN BY THE ARCHITECT.
WHERE DEMOLITION OF EXISTING CONSTRUCTION AND/OR EQUIPMENT OCCURS, PATCH AND REPAIR FLOOR, WALL AND CEILING CONSTRUCTION AND/OR FINISHES TO MATCH ADJACENT CONSTRUCTION AND/OR FINISHES.
ALL CUTTING, DEMOLITION AND PATCHING OF EXISTING PLUMBING SYSTEMS AND/OR EQUIPMENT IS TO BE
PERFORMED BY THE PLUMBING CONTRACTOR UNLESS NOTED OTHERWISE.
PLUMBING DEMOLITION GENERAL NOTES :
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C :\U se rs
\p al ex an de r\A pp D at a\
Lo ca l\A ut od es k\ R ev it_
Lo ca l\M
EP
-2
5-x0
1_ R
_P
Al ex an de rV 8F
VS
.rv t 1/
/2
2:
:4
PM
P001
SYMBOLS,
ABBREVIATIONS AND
GENERAL NOTES
01/30/26
Checker
Author
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
PLUMBING ABBREVIATIONS
ABV ABOVE
AFF ABOVE FINISHED FLOOR
BLW BELOW
C COLD WATER
CLG CEILING
DN DOWN
DCVA DOUBLE CHECK VALVE ASSEMBLY
DFU DRAINAGE FIXTURE UNIT
DWH DOMESTIC WATER HEATER
E EXISTING
EF EMERGENCY FIXTURE
EWC ELECTRIC WATER COOLER
FLR FLOOR
FD FLOOR DRAIN
FNL FUNNEL DRAIN
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
H HOT WATER
HB HOSE BIBB
HC HEATING CONTRACTOR
HWBP HUMIDIFICATION WATER BOOSTER PUMP
HWR HOT WATER RETURN
INV ELEV INVERT ELEVATION
L LAVATORY
MC MECHANICAL CONTRACTOR
PC PLUMBING CONTRACTOR
RD ROOF DRAIN
RPZBP REDUCED PRESSURE ZONE BACKFLOW PREVENTER
S SINK
SC SITE CONTRACTOR
SH SHOWER
SS SANITARY CONTRACTOR
SPC SPRINKLER CONTRACTOR
SQ FT SQUARE FOOT
TYP TYPICAL
U URINAL
V VENT
VTR VENT THROUGH ROOF
W WATER CLOSET
WH WALL HYDRANT
WS WASTE STACK
WSFU WATER SUPPLY FIXTURE UNIT
B
C
D
E E
E
E
E E
E
E
E
WOMEN
MEN
CUSTODIAL
E4
MECH
IT CLOSET
OFFICE
TESTING CENTER
KITCHEN
359BREAKROOM
CUBICLE
333CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
STAIR
S01
CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
OFFICE
OFFICE
OFFICE
CUBICLE
CUBICLE
OFFICE
E
DEMOLISH EX REFRIGERATOR
AN REMOVE ASSOCIATED
COLD WATER LINE BACK TO
EX MAIN BRANCH AND CAP
EX SINK & EX EXINSTANTANEOUS
WATER HEATER UNDER
COUNTER TO REMAIN
CAP
1/2"CW
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"1 THIRD FLOOR - DEMOLITION
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C :\U se rs
\p al ex an de r\A pp D at a\
Lo ca l\A ut od es k\ R ev it_
Lo ca l\M
EP
-2
5-x0
1_ R
_P
Al ex an de rV 8F
VS
.rv t 1/
/2
2:
:5
PM
P103
THIRD FLOOR PLAN -
AREA A - PLUMBING -
DEMOLITION
01/30/26
Checker
Author
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
KEYNOTES
Key
B
C
D
E E
E
E
E E
E
E
E W-1
L-1
WOMEN
E4MECH
IT CLOSET
OFFICE
TESTING CENTER
ACCOMMODATIONS
318 BREAKROOM
STORAGE
KITCHEN
MEN
LOUNGE
CUBICLE
CUBICLE
COLLABORATION
CUBICLE
CUBICLE
OFFICE
OFFICE
350 OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
TESTING CENTER
OFFICE
OFFICE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
CUBICLE
STAIR
S01
S05
FLOOR
MOUNTED
ER
CUSTODIAL
P301
EX 3" VENT RISER
EX 4" SAN. RISER
EX 3" CW RISER
P301
D-1 2" W-DN
1 1/2" V-UP
DWH-1
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"1 THIRD FLOOR - NEW WORK
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C :\U se rs
\p al ex an de r\A pp D at a\
Lo ca l\A ut od es k\ R ev it_
Lo ca l\M
EP
-2
5-x0
1_ R
_P
Al ex an de rV 8F
VS
.rv t 1/
/2
2:
:5
PM
P203
THIRD FLOOR PLAN -
AREA A - PLUMBING -
NEW WORK
01/30/26
Checker
Author
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
KEYNOTES
Key
4 5 6
B
BREAKROOM
TESTING CENTER
STORAGE
KITCHEN
MEN
LOUNGE
CUSTODIAL
WOMEN
E E
E
E
E E
E
E
E
W-1
L-1
FLOOR
MOUNTED
ER
UNDERMOUNT W/
INSTANTANEOUS
WATER HEATER
(*DWH-1)
EX SINK & EX INSTANTANEOUS
WATER HEATER UNDER
COUNTER TO REMAIN
EX 3" CW RISER
ABV CLG
EX PIPING IN
CHASE TO REMAIN
E
E
1 1/4" CW
1 1/4" CW
EX 1/2" CW
1" CW-DN
DF-1
A.P.
R
E
E
E
E
1/2" CW-DN
ABV CLG
4 5 6
B
E E E
E E
E
W-1
EX 3" VENT STACK
BLW FLR
EX PIPING IN
CHASE TO REMAIN
E
E4" W
2"W TOP
CONNECTION
2"W-DN
2"V-UP
CO
RE
E E
E
E
E
E
L-1
D-1
2"W-DN1
1/2"V-UP
4" W-DN
BLW
FLR
BREAKROOM
TESTING CENTER
STORAGE
KITCHEN
MEN
CUSTODIAL
WOMEN
LOUNGE
ABV CLG
EX 4" WASTE STACK
E
EX V HIGH IN CHASE
EX W BLW FLR
EX 2"V-UP
EX WATER
HEATER
1 1/2" W
2" SV
BLW FLR
ABV CLG
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C :\U se rs
\p al ex an de r\A pp D at a\
Lo ca l\A ut od es k\ R ev it_
Lo ca l\M
EP
-2
5-x0
1_ R
_P
Al ex an de rV 8F
VS
.rv t 1/
/2
2:
:5
PM
P301
ENLARGED PLANS -
PLUMBING
01/30/26
Checker
Author
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
KEYNOTES
Key
Value Keynote Text
SCALE: 1/4" = 1'-0"1 ENLARGED PLAN - DOMESTIC WATER
SCALE: 1/4" = 1'-0"2 ENLARGED PLAN - SANITARY & VENT
AS SPECIFIED.
EXISTING FIXTURE TO REMAIN
SUFFIXES FOR FIXTURE LETTERS
REFER TO PROJECT SPECIFICATIONS
SPECIALTIES AND EQUIPMENT.
FOR PLUMBING ACCESSORIES,
2.
NOTE:
E
1.
1/2"H & C
REFER TO SPECIFICATIONS FOR REQUIREMENTS OF MATERIALS, COLOR, FINISHES, INSTALLATION, APPROVED EQUAL MANUFACTURERS, ETC..
PROVIDE COMPLETE WITH SUPPLY AND WASTE ROUGH-IN ASSEMBLIES IN ACCORDANCE WITH SPECIFICATIONS.
3.
1.
2.
LAVATORY
WATER CLOSET 1"C
REQUIREMENTS
L-1
IDENTIFICATION
FIXTURE
21 1/4" OVAL
LAVATORY
VITREOUS CHINA
COUNTER
UNDERMOUNT
ADA
DESCRIPTION MOUNTING FOOTNOTES AND REMARKS
FIXTURE MANUFACTURER AND
MODEL NUMBER
(OR APPROVED EQUAL)
1, 2, 3
(OR APPROVED EQUAL)
AND MODEL NUMBER
FIXTURE ACCESSORIES MAKE
WATER CLOSET
LAVATORY
1 1/2"W & V 4"S & 2"V
L W
Caxton®
21-1/4" OVAL UNDERMOUNT
BATHROOM SINK
K-2211-0 Z81101-XL-HCT-3M
ZURN
4" CENTERSET FAUCET
PROVIDE WITH ASSE 1070 THERMOSTATIC MIXING VALVE AT EACH FAUCET: Leonard's ECO-MIX™ (Model 270-LF) 0.25 GPM.
WATER
PLUMBING FIXTURE CONNECTION SCHEDULE
LAVATORIES AND SINK FOOTNOTES:
FIXTURE
LAVATORIES AND SINKS
PLUMBING FIXTURE ABBREVIATIONS
WASTE, SOIL & VENT (UNO)
WATER CLOSETS
WATER CLOSETS AND URINAL FOOTNOTES:
FIXTURE
IDENTIFICATION DESCRIPTION
MOUNTING
REQUIREMENT
S
FIXTURE MANUFACTURER
AND
MODEL NUMBER
(OR APPROVED EQUAL)
FIXTURE ACCESSORIES
MAKE
AND MODEL NUMBER
(OR APPROVED EQUAL)
FOOTNOTE
S
AND
REMARKS
W-1 WATER CLOSET
1.6/1.1 GALLON PER FLUSH
ZURN
Z5655
SLOAN UPPERCUT
WES-111 1, 2
1. REFER TO SPECIFICATIONS FOR REQUIREMENTS OF MATERIALS, COLOR, FINISHES, INSTALLATION, APPROVED EQUAL MANUFACTURERS, ETC..
2. PROVIDE COMPLETE WITH SEAT, SUPPLY ROUGH-IN AND WASTE ROUGH-IN ASSEMBLIES IN ACCORDANCE WITH SPECIFICATIONS.
FLR MTD
STD HT
INSTANTANEOUS ELECTRIC POINT OF USE WATER HEATER SCHEDULE
TOILET ROOM
WATER
HEATER
NUMBER
LOCATION FUEL TYPE
IN OUT
WATER TEMP
DEG F MIN/MAX GPM
FLOW REMARKS
ELECTRIC
8 kW, 240VDWH-1 0.3/4.812045
Eemax ProSeries™ For Single Point-of-Use Tankless Electric Water Heater Model# PR008240
WATER COOLER FOOTNOTES :
WATER COOLERS/BOTTLE FILLERS SCHEDULE
PROVIDE WITH SUPPLY AND WASTE ROUGH-IN ASSEMBLIES IN ACCORDANCE WITH SPECIFICATIONS.
REFER TO SPECIFICATIONS FOR REQUIREMENTS OF MATERIALS, COLOR, FINISHES, INSTALLATION, APPROVED EQUAL MANUFACTURERS, ETC..
3.
2.
1.
CONTRACTOR TO ENSURE THAT INSTALLATION MEETS OR EXCEEDS ALL ADA GUIDELINES.
FIXTURE
IDENTIFICATION DESCRIPTION
(OR APPROVED EQUAL)
AND MODEL NUMBER
FIXTURE ACCESSORIES MAKE
MODEL NUMBER
(OR APPROVED EQUAL)
FIXTURE MANUFACTURER ANDMOUNTING
REQUIREMENTS FOOTNOTES AND REMARKS
D-1 1, 2, 3
WALL MTD
ADA
ACCESSIBLE
OASIS, VERSACOOLER™ SINGLE DRINKING
FOUNTAIN, REFRIGERATED & ELECTRONIC
BOTTLE FILLER, TOTAL PFAS FILTER
MODEL PG8FEBF-FPF
BOTTLE FILLING STATION &
ELECTRIC WATER COOLER
OASIS TOTAL PFAS REPLACEMENT
CARTRIDGE (2)
(L-1) LAVATORY
1/2" 1/2"
1/2" COLD WATER SUPPLY
LINE. RUN ALONG WALL
FOR CONTINUATION OF
PIPING SEE FLOOR PLAN
FINISHED FLOOR
VALVE (TYP)
RUN 1/2" COLD WATER LINE ALONG WALL
AND CONNECT TO WATER HEATER
INSTANTANEOUS POINT OF USE WATER
HEATER: FOR (L-1) LAVATORY
MOUNTED ON WALL BELOW SINK (SEE
SCHEDULE AND SPECIFICATION)
THERMOSTATIC MIXING VALVE
CERTIFIED TO MEET ASSE 1070.
SET OUTLET TEMPERATURE TO 105°
OR AS DIRECTED BY OWNER PERSONNEL.
UNION (TYP)
PROVIDE TRUEBRO LAV GUARD (OR
APPROVED EQUAL) ON ALL EXPOSED
PIPING BENEATH HANDICAPPED
ACCESSIBLE LAVATORY(S)
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C :\U se rs
\p al ex an de r\A pp D at a\
Lo ca l\A ut od es k\ R ev it_
Lo ca l\M
EP
-2
5-x0
1_ R
_P
Al ex an de rV 8F
VS
.rv t 1/
/2
2:
:5
PM
P500
SCHEDULES &
DETAILS - PLUMBING
01/30/26
Checker
Author
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
SCALE: 1/8" = 1'-0"4 INSTANTANEOUS WATER HEATER DETAIL (DWH-1)
MECHANICAL LEGEND (Misc.)
SYMBOL DESCRIPTION
SPACE STATIC PRESSURE SENSOR
STATIC PRESSURE SENSOR
THERMOSTAT, ELECTRIC
THERMOSTAT, PNEUMATIC
SUPPLY DIFFUSER; 4-WAY THROW UNLESS
NOTED OTHERWISE
THERMOSTAT, PNEUMATIC
AIR FLOW ARROW
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
INDICATES NOTES ELSEWHERE ON DRAWING
DIFFERENTIAL PRESSURE SENSOR
CONNECTION BETWEEN NEW AND EXISTING
DOOR UNDERCUT 1" ABOVE FINISHED FLOOR
DISCONNECTION POINT
DUCT MOUNTED STATIC PRESSURE SENSOR
REVISION NUMBER
FLOW METER, DDC
HUMIDISTAT, ELECTRIC
HUMIDISTAT, PNEUMATIC
PE SWITCH ABOVE CEILING (WITH ACCESS PANEL)
PE SWITCH EXPOSED
PRESSURE SENSOR
REFRIGERANT SENSOR
SMOKE DETECTOR
C O
DP
UC
S D
FM
H
H
P S
R
S
SD
SP
T
T
C O 2
M-501
DETAIL NUMBER OR SECTION LETTER
DRAWING NUMBER WHERE DETAIL IS
DRAWN
M501
DETAIL NUMBER OR SECTION LETTER
DRAWING NUMBER WHERE DETAIL IS DRAWN
DRAWING NUMBER WHERE SYMBOL IS USED
M101
M-501
SECTION LETTER
DRAWING NUMBER WHERE SECTION IS
DRAWN
M501
SECTION LETTER
DRAWING NUMBER WHERE SECTION IS DRAWN
DRAWING NUMBER WHERE SECTION IS CUT
M101
DUCTWORK LEGEND
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
CONICAL TAKEOFF CONNECTION
CONICAL TAKEOFF CONNECTION
BELLMOUTH TAKEOFF CONNECTION
STRAIGHT ROUND TAKEOFF CONNECTION
STRAIGHT "T" CONNECTION
PNEUMATIC OPERATED DAMPER
COMBINATION FIRE / SMOKE DAMPER
SMOKE DAMPER
FIRE DAMPER
MOTOR OPERATED DAMPER
HUMIDIFIER IN DUCT
FILTER SECTION IN DUCT
DUCT TRANSITION
PERFORATED PLATE DAMPER
VOLUME CONTROL DAMPER
ELECTRIC COIL IN DUCT
COIL IN DUCT
ACOUSTIC DUCT LINING
FLEXIBLE CONNECTION
FLAT OVAL (SHOWN x HIDDEN)
ROUND DUCT (DIAMETER)
EXISTING DUCT TO REMAIN (LIGHT LINE WORK)
DUCTWORK TO BE REMOVED
FLEXIBLE DUCTWORK
DUCT (SHOWN x HIDDEN)
SUPPLY/OUTDOOR/MAKE-UP AIR RECTANGULAR
DUCT SECTION
RETURN/TRANSFER/RELIEF AIR RECTANGULAR
DUCT SECTION
EXHAUST AIR RECTANGULAR DUCT
SECTION
SUPPLY/OUTDOOR/MAKE-UP AIR OVAL DUCT
SECTION
RETURN/TRANSFER/RELIEF AIR OVAL DUCT
SECTION
EXHAUST AIR OVAL DUCT SECTION
SUPPLY/OUTDOOR/MAKE-UP AIR ROUND DUCT
SECTION
RETURN/TRANSFER/RELIEF AIR ROUND DUCT
SECTION
EXHAUST AIR ROUND DUCT SECTION
LOUVER IN WALL
SQUARE ELBOW WITH TURNING VANES
RADIUS ELBOW
RECTANGULAR BOOT CONNECTION
CONICAL "T" CONNECTION
12x8
12ᴓ
12/8
FC
CONTROL PANEL
VCD
PPD
M
F
S
C
MECHANICAL ABBREVIATIONS
ABV ABOVE
AHC AUXILIARY HEATING COIL
AHU AIR HANDLING UNIT
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CFM CUBIC FEET PER MINUTE
CHAR CHARACTERISTIC
COL COLUMN
DN DOWN
EA EXHAUST AIR
EAT ENTERING AIR TEMP
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EGC EXHAUST GRILLE CEILING
ELEC ELECTRICAL
ESP EXTERNAL STATIC PRESSURE
FD FIRE DAMPER
FP FAN POWERED
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
HP HORSEPOWER
HUH HORIZONTAL UNIT HEATER
HWP HOT WATER PUMP
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
IN INCH
KHE KITCHEN HOOD EXHAUST
LAT LEAVING AIR TEMP
LF LINEAR FEET
LP LOW PRESSURE
MAX MAXIMUM
MBH THOUSAND BRITISH THERMAL UNITS PER HOUR
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPERAGE
MIN MINIMUM
MOCP MAXIMUM OVERLOAD CIRCUIT PROTECTION
OA OUTDOOR AIR
PC PLUMBING CONTRACTOR
RA RETURN AIR
RGC RETURN GRILLE CEILING
RPM REVOLUTIONS PER MINUTE
RTU ROOFTOP UNIT
SA SUPPLY AIR
SD SMOKE DETECTOR
SDC SUPPLY DIFFUSER CEILING - (THROWS)
SSAHU SPLIT SYSTEM AIR HANDLING UNIT
TGC TRANSFER GRILLE CEILING
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
VCD VOLUME CONTROL DAMPER
VVB VARIABLE VOLUME BOX
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
THE HEATING CONTRACTOR SHALL COORDINATE WITH THE OTHER CONTRACTORS IN THE LOCATION OF DUCTWORK, PIPING, ETC.
THE HEATING CONTRACTOR SHALL VISIT AND THOROUGHLY ACQUAINT HIMSELF WITH THE EXISTING SYSTEM AND CONDITIONS IN THE AREAS HE
WILL BE REQUIRED TO WORK BEFORE ISSUING HIS BID.
THE HEATING CONTRACTOR SHALL RELOCATE EXISTING SYSTEMS WHERE CONFLICTS WITH NEW WORK EXIST TO ACCOMMODATE NEW WORK.
ALL INTERRUPTIONS OF EXISTING SYSTEMS SHALL BE SCHEDULED IN ADVANCE WITH THE OWNER AND APPROVED BEFORE WORK COMMENCES.
ALL DUCTWORK SHALL BE INSTALLED AS HIGH AS POSSIBLE UNLESS NOTED OTHERWISE.
DO NOT SCALE DRAWINGS - ALL DIMENSIONS AND EXISTING CONDITIONS SHALL BE CHECKED AND VERIFIED BY THE CONTRACTOR AT THE SITE.
NOTIFY ARCHITECT OF ANY DEVIATIONS FROM THE DRAWINGS.
THE DRAWINGS ARE DIAGRAMMATIC AND SHOW ONLY THE GENERAL ARRANGEMENTS OF ALL EQUIPMENT. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO SHOW OR INDICATE ALL OFFSETS, FITTINGS, AND ACCESSORIES WHICH MAY BE REQUIRED TO AVOID
STRUCTURAL FEATURES.
ALL CONDUIT, DUCTWORK, ETC., SHALL BE INSTALLED IN A MANNER WHICH WILL NOT DEFACE OR ALTER ANY AREAS. ROUTING OF THE ABOVE
EQUIPMENT SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION.
ALL WORK PERFORMED ON THIS BUILDING SHALL BE IN COMPLIANCE WITH ALL PERTINENT CODES, RULES, ORDINANCES, AND REGULATIONS OF
THE LOCAL, STATE, AND NATIONAL GOVERNING AUTHORITIES.
ALL WORK PERFORMED UNDER AND IN CONNECTION WITH THESE DRAWINGS AND SPECIFICATIONS SHALL BE IN STRICT COMPLIANCE WITH THE
LATEST SAFETY AND HEALTH STANDARDS.
REPORT ANY DISCREPANCIES FOUND IN THE DRAWINGS AND/OR IN THE SPECIFICATIONS DURING THE BIDDING PROCESS FOR CLARIFICATION BY
THE ARCHITECT.
HEATING CONTRACTOR SHALL PROVIDE AND INSTALL ACCESS PANELS AS REQUIRED FOR ACCESS TO VALVE, TRAPS, CLEAN-OUTS, CONTROLS, FIRE DAMPERS, ETC. THE CONTRACTOR SHALL COORDINATE INSTALLATION OF ACCESS PANELS WITH FINISH WORK AND ALL OTHER TRADES.
THE HEATING CONTRACTOR SHALL FURNISH SHOP DRAWINGS OF ANY RELOCATED DUCTWORK, EQUIPMENT, ETC. FOR APPROVAL PRIOR TO
RELOCATION OF ITEM.
ALL DUCTWORK TO BE LOCATED AND COORDINATED WITH ARCHITECTURAL PLANS. ALL DUCTWORK SHALL BE CONCEALED IN FINISHED AREA.
ALL DUCTS THAT PENETRATE CHASES, WALLS, OR FLOORS WHICH ARE FIRE RATED, SHALL BE INSTALLED WITH FIRE DAMPERS IN ACCORDANCE WITH NFPA 90A. THIS APPLIES EVEN IF THEY ARE NOT SPECIFICALLY SHOWN ON THE DRAWING.
ANY PHYSICAL INSTALLATION MODIFICATIONS, DUE TO FIELD CONDITIONS, SHALL BE RESOLVED BY THE HEATING CONTRACTOR IN ACCORDANCE
WITH THE RECOMMENDATIONS OF THE MECHANICAL ENGINEER.
THE HEATING CONTRACTOR SHALL PAY FOR ALL FEES AND PERMITS AS NECESSARY TO COMPLETE THE INSTALLATION.
THE HEATING CONTRACTOR SHALL COORDINATE THE LOCATION OF DUCTWORK WITH ALL EXISTING PIPING.
ALL DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN FURRED CHASES OR ABOVE SUSPENDED CEILING.
ALL LIGHT LINES SHOWN ON DRAWINGS INDICATE EXISTING EQUIPMENT CONSTRUCTION OR EQUIPMENT TO REMAIN. ALL HEAVY LINES INDICATE NEW CONSTRUCTION OR EQUIPMENT. ALL CROSS-HATCHED LINES INDICATE REMOVAL OF EXISTING CONSTRUCTION OR EQUIPMENT.
MECHANICAL GENERAL NOTES :
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
ALL DUCTWORK SIZES NOTED ARE FREE AREA SIZES.
RADIUS ELBOWS SHALL BE PROVIDED. TURNING VANES SHALL NOT BE PROVIDED UNLESS APPROVED BY ENGINEER.
ALL DUCT JUNCTIONS SHALL BE CONSTRUCTED OF STANDARD 45 DEGREES ENTRY BRANCHES WITH BALANCING DAMPERS DOWNSTREAM OF DUCT BRANCH ENTRY.
MAXIMUM LENGTH OF FLEXIBLE DUCTWORK SHALL CONTAIN IN ANY ONE SUPPLY BRANCH SHALL BE THREE (3) FEET.
NO RUN OF FLEXIBLE DUCTWORK SHALL CONTAIN MORE THAN A TOTAL OF 90 DEGREES OF TURN. INSULATED RIGID SHALL BE USED WHERE MORE THAN 90 DEGREES IS REQUIRED.
TOTAL STATIC PRESSURE NOTED IN SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL UNITS, FILTERS, COILS, ETC.
CEILING DIFFUSER SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.
REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF CEILING DIFFUSERS, REGISTERS AND GRILLES.
PROVIDE FLEXIBLE DUCT CONNECTION BETWEEN AHU/EXH FAN AND DUCTWORK.
FIRE DAMPERS SHALL BE TYPE 'C'
DUE TO THE SMALL SCALE OF THE DRAWINGS, RISERS, AND DROPS ARE NOT ALL SHOWN. PROVIDE RISERS AND DROPS FOR COORDINATION.
FIRST FIGURE OF DUCT SIZE INDICATES DIMENSIONS OF FACE SHOWN OR INDICATED.
MECHANICAL DUCTWORK NOTES :
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C :\U se rs
\le ic he lb er ge r\A pp
D at a\ Lo ca l\A ut od es k\
R ev it_ Lo ca l\M
EP
-2
5-x0 1_
R
_L Ei ch el be rg er
BV
FX
Q
.rv t
1/
/2
2:
:4
PM
M001
SYMBOLS , NOTES , &
ABBREVIATIONS
01/30/26
JMW
MMR
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1 2 3 4 5 6
A
B
C
D
28x16 SA 40x16 SA x2
SA
x2
R
A
24x14 SA x1
SA
EX.
FPVAV-3W4
EX.
FPVAV-3W5
EX. VAV-3W5
EX. VAV-3W4
EX.
FPVAV-3W6
EX. VAV-3W6
EX. VAV-3W7
EX. VAV-3W8
EX. VAV-3W1
EX.
FPVAV-3W1
EX.
FPVAV-3W2
EX. VAV-3W3
EX.
FPVAV-3W3
8x
EA
8x
EA
12x10 EA
8x8 EA x1
SA
x1
SA
8ø SA 6ø SA
8ø SA 6ø SA
8ø SA
8ø SA 8x
S A x1
SA
8ø SA 8ø SA
8ø SA
16x14 SA ø
SA
ø
SA
x1
SA
8ø S
A
8ø S
A
10x10 SA 8ø SA 8ø
S A 6ø
S A
6ø S
A
6ø S
A
6ø S
A 8ø
S A
6ø SA
6ø S
A x1
SA 6ø
S A
6ø SA
6ø SA
6ø S
A
8ø SA x1
SA
8ø S
A ø
SA
ø
SA
ø
SA
FROM BLW
TO ABV
20x20 EA
14x10 SA
10x8 SA
6ø S
A
6ø S
A
8ø SA
6ø SA
8ø S
A
6ø SA
6ø S
A
10ø SA
8ø S
A
14x10 SA
6ø S
A
6ø S
A
6ø S
A
6ø S
A
6ø S
A
6ø S
A
6ø S
A 6ø
S A
6ø S
A 6ø
S A
6ø S
A 6ø
S A
6ø S
A 6ø
S A 18 x1
SA
16x12 SA 12x10 SA
8ø S
A
8ø S
A
8ø S
A
14x10 SA
8x10 SA
8ø S
A 8ø
S A
8ø S
A
18x12 SA
14x10 SA
8ø S
A
8ø S
A
8ø S
A
8ø S
A
8ø S
A
8ø SA 10ø SA
10x12 SA
8ø S
A
8ø SA
8ø S
A x1
SA
ø
SA
x1
SA
6ø S
A
8ø SA
16x12 SA
6ø S
A
12ø SA ø
SA
6x
SA
6ø SA
6ø SA
14x15 SA
6ø S
A
6ø S
A
6ø S
A
10x10 SA 6ø
S A
6ø S
A
6x
SA
6ø SA
6ø SA
FROM BLW
TO ABV
80x30 SA
FROM ABV
TO BLW
80x30 RA
EX. AC-3W1
EX. CU-3W1
EX. RTU-02
C C
10ø SA
6ø S
A 6ø
S A
8ø SA10x8 SA 18x10 SA
12x8 SA
8ø SA
18x12 SA
EX. VAV-3W2
3 3
6 6
8x
EA
8Ø SDC-2
200 CFM
(TYP OF 6)
6Ø SDC-4
100 CFM
(TYP OF 9)
8Ø SDC-2
225 CFM
(TYP OF 4)
6Ø SDC-4
100 CFM
(TYP OF 16)
6Ø SDC-4
100 CFM
8Ø SDC-4
200 CFM
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"1 THIRD FLOOR - DEMOLITION
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C :\U se rs
\le ic he lb er ge r\A pp
D at a\ Lo ca l\A ut od es k\
R ev it_ Lo ca l\M
EP
-2
5-x0 1_
R
_L Ei ch el be rg er
BV
FX
Q
.rv t
1/
/2
2:
:5
PM
M103
THIRD FLOOR PLAN -
AREA A -
MECHANICAL -
DEMOLITION
01/30/26
JMW
MMR
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
KEYNOTES
Key
Value Keynote Text
1 EXISTING VAV BOX SHALL REMAIN
2 EXISTING FPVAV SHALL REMAIN
3 EXISTING VAV BOX SHALL BE REMOVED AND RELOCATED. REFER TO SHEET
M203 FOR RELOCATION.
4 EXISTING FPVAV BOX SHALL BE REMOVED AND RELOCATED. REFER TO SHEET
M203 FOR RELOCATION.
5 EXISTING VAV SHALL BE DEMOED
6 DEMO EXISTING RETURN GRILLE AND ASSOCIATED DUCTWORK
7 DEMO EXISTING TRANSFER DUCTWORK
8 EXISTING COMBINATION FIRE SMOKE DAMPERS SHALL REMAIN
9 EXISTING THERMOSTAT SHALL REMAIN
10 EXISTING THERMOSTAT SHALL BE REMOVED AND RELOCATED. REFER TO
SHEET M203 FOR RELOCATION.
11 DEMO EXISTING THERMOSTAT AND ASSOCIATED CONTROL WIRING, ETC.
12 RTU-02 THIRD FLOOR CENTRAL CONTROL CONSOL SHALL REMAIN
B
C
D
E
F
G
H
I
J
K
L
EXISTING FPVAV
SHALL REMAIN
EXISTING 320 CFM LINEAR SLOT
DIFFUSERS SHALL REMAIN (TYP OF 4)
56x34 RA
38x34 SA
30x16 RA
30x34 SA
FROM BLW
TO ABV
38x34 SA
FROM BLW
TO ABV
56x34 RA ø
SA
ø
SA
14ø SA
14ø SA
SHELL
MAKER SPACE
CLASSROOM
STORAGE
MEETING
MEETING
STUDY SPACE
MEETING
MEETING
LOBBY
STAIR
S03
RECEPTION
ELEVATOR
E1
E2
ELEVATOR
E3
MEETING
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"1 THIRD FLOOR - DEMOLITION
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C :\U se rs
\le ic he lb er ge r\A pp
D at a\ Lo ca l\A ut od es k\
R ev it_ Lo ca l\M
EP
-2
5-x0 1_
R
_L Ei ch el be rg er
BV
FX
Q
.rv t
1/
/2
2:
:5
PM
M104
THIRD FLOOR PLAN -
AREA B -
MECHANICAL -
DEMOLITION
01/30/26
JMW
MMR
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
KEYNOTES
Key
Value Keynote Text
1 EXISTING WALL RETURN TRANSFER GRILLE SHALL REMAIN (TYP)
2 DEMO AND REMOVE ENDCAP
3 EXISTING LINEAR SLOT DIFFUSER AND ASSOCIATED DUCTWORK SHALL BE
DEMOED
T
T
T
T
T T
TT
T
T
T
T
T
T
1 2 3 4 5 6
A
B
C
TESTING CENTER
TESTING CENTER
ACCOMMODATIONS
BREAKROOM
KITCHEN
OFFICE
IT CLOSET
MECH
E4
CUSTODIAL
MEN
WOMEN
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
EX. VAV-3W3
EX.
FPVAV-3W3
EX. VAV-3W2
EX.
FPVAV-3W2
EX. VAV-3W1
x2
SA
8Ø SDC-4
200 CFM
(TYP OF 2)
12Ø SDC-4
350 CFM
12Ø SDC-4
450 CFM
12Ø SDC-4
500 CFM
(TYP OF 2)
8Ø SDC-4
200 CFM
x2
R
A
FROM BLW
TO ABV
80x30 SA
FROM ABV
TO BLW
80x30 RA
EX.
FPVAV-3W4
EX. VAV-3W7
EX. VAV-3W5
x1
SA
24x16 SA x1
SA
ø
SA
6ø S
A
14x10 SA12ø SA
40x16 SA
16Ø SDC-4
750 CFM
(TYP OF 4)
VAV-3W9 VAV-3W10
12Ø SDC-4
500 CFM
(TYP OF 6)
EX.
FPVAV-3W1
8Ø SDC-2
300 CFM
(TYP OF 4)
24x14 SA
EX.
FPVAV-3W5
EX.
FPVAV-3W6
24x16 SA
20x20 EA
8x
EA
8x
EA
8x
EA
12x10 EA
8x8 EA
8x8 EGC
50 CFM
8Ø SDC-2
225 CFM
(TYP OF 2)
8Ø SDC-2
200 CFM
(TYP OF 3)
14x12 SA
20x14 SA 14x12 SA12 x8 S
A x8
S A x8
S A x1
SA
x1
SA
20x12 SA
12x8 SA 14x12 SA x8
S A
12ø SA x1
SA
x1
SA
x1
SA
EX. CU-3W1
EX. RTU-02
8ø SA
8ø SA
8ø SA
8ø SA ø
SA20
x1
SA
x1
SA
ø
SA
EX. AC-3W1
x2
R
A
56x18 RA
C C
12x6 SA
8ø SA
10ø SA
8x
SA
10x8 SA x8
S A x8
S A x8
S A x1
SA
24x16 SA x1
SA
x1
SA
x1
SA
40x16 SA x1
SA
14x10 SA 8x10 SA
8ø S
A
8ø S
A
8ø S
A
8ø S
A
8ø SA
8ø S
A 10x10 SA
6ø SA
6ø SA
6x
SA
6ø SA
6ø S
A
6ø S
A
6ø S
A
14x15 SA
6ø SA 6ø SA
6x
SA
6ø
S A
8ø S
A
8x
SA
6ø SA 16x12 SA
12ø SA
12x12 TA 12x12 RGC
8x8 RGC
8x8 TA
32x32 RGC
40x16 TA
32x32 RGC
40x16 TA
LOUNGE
COLLABORATION
8x6 SA
12x12 RGC
12x12 TA
EX. VAV-3W8
12x12 RGC
12x12 TA
8x
SA
EX. VAV-3W4
8ø S
A x8
S A ø
SA
12x12 RGC
450 CFM
12x12 RA
18x12 SA ø
SA
x1
SA
8ø S
A
8ø S
A ø
SA
8ø S
A
10x8 SA 8ø SA x8
S A x8
S A
10ø SA
6ø S
A 6ø
S A
6ø S
A
8ø SA10x8 SA6ø S
A 6ø
S A
18x10 SA14x10 SA
6ø S
A 6ø
S A
6ø S
A
6ø S
A
6ø S
A
6ø S
A
6ø S
A
6ø S
A
12x8 SA
6ø S
A 6ø
S A x1
SA
x1
SA
10x12 SA
8ø S
A
8ø S
A
10x12 SA ø
SA
8ø S
A
1 1 1 1 1
6ø SA
12ø SA
7 7
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"1 THIRD FLOOR - NEW WORK
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C :\U se rs
\le ic he lb er ge r\A pp
D at a\ Lo ca l\A ut od es k\
R ev it_ Lo ca l\M
EP
-2
5-x0 1_
R
_L Ei ch el be rg er
BV
FX
Q
.rv t
1/
/2
2:
:5
PM
M203
THIRD FLOOR PLAN -
AREA A -
MECHANICAL - NEW
WORK
01/30/26
JMW
MMR
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
KEYNOTES
Key
Value Keynote Text 1 10"x10" RGC WITH 10"x10" TA DUCT INTO PLENUM (TYP) 2 20"x20" RGC WITH 20"x20" TA DUCT INTO PLENUM (TYP) 3 64"x 20" RETURN AIR DUCT OPEN TO PLENUM. OPENING SHALL BE PROVIDED
WITH 1/2" GALVANIZED STEEL MESH SCREEN SET IN REMOVABLE FRAME.
REFER TO OPEN END DUCT INLET DETAIL FOR INSTALLATION REQUIREMENTS.
4 66"x 18" RETURN AIR DUCT OPEN TO PLENUM. OPENING SHALL BE PROVIDED
WITH 1/2" GALVANIZED STEEL MESH SCREEN SET IN REMOVABLE FRAME.
REFER TO OPEN END DUCT INLET DETAIL FOR INSTALLATION REQUIREMENTS.
5 RELOCATED EXISTING THERMOSTAT. CONFIGURE RELOCATED EXISTING
THERMOSTAT TO CONTROL ASSOCIATED MECHANICAL EQUIPMENT (TYP).
6 NEW THERMOSTAT
7 NEW VAV BOX
8 RELOCATED AND RECONFIGURED VAV BOX
9 RELOCATED AND RECONFIGURED FPVAV BOX
10 RE-BALANCE EXISTING EXHAUST FAN TO ACCOMODATE ADDITIONAL
RESTROOM EXHAUST AIRFLOW.
11 RE-BALANCE EXISTING RTU-02 OUTSIDE AIR TO 6,000 CFM.
B
C
D
E
F
G
H
I
J
K
L
SHELL
STORAGE
MEETING
364 MEETING
STAIR
S03
RECEPTION
ELEVATOR
E3
E2
ELEVATOR
E1
MEETING
CLASSROOM
MAKER SPACE
MEETING
STORAGE
MEETING
STUDY SPACE
MEETING
304MEETING
LOBBY
56x34 RA
38x34 SA
30x16 RA
30x25 SA ø
SA
ø
SA
EXISTING FPVAV
SHALL REMAIN
14ø SA
14ø SA
EXISTING 320 CFM
LINEAR SLOT
DIFFUSERS (TYP OF 4)
14ø SA
FROM BLW
TO ABV
38x34 SA
FROM BLW
TO ABV
56x34 RA
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"1 THIRD FLOOR - NEW WORK
Sheet Title:
Project Number:
Drawn By:
Checked By:
Date:
Drawing Number
Project Identification:
Seal:
Consultants:
B
ISSUES
1 3 4 5
C
D
A
COA #: C00773-00 - Expires: 12/31/2025
H.F. Lenz Co.
1407 Scalp Avenue Johnstown, PA 15904 814-269-9300 hflenz.com
Key Plan:
DOCUMENT EXCLUSIVE PROPERTY OF H.F. LENZ CO., UNAUTHORIZED USE IS NOT PERMITTED
C :\U se rs
\le ic he lb er ge r\A pp
D at a\ Lo ca l\A ut od es k\
R ev it_ Lo ca l\M
EP
-2
5-x0 1_
R
_L Ei ch el be rg er
BV
FX
Q
.rv t
1/
/2
2:
:0
PM
M204
THIRD FLOOR PLAN -
AREA B -
MECHANICAL - NEW
WORK
01/30/26
JMW
MMR
2025-1782.01
WVU EVANSDALE
CROSSING THIRD &
FOURTH FLOOR
RENOVATIONS
62 MORRILL WAY,
MORGANTOWN, WEST VIRGINIA
26505
WEST VIRGINIA
UNIVERSITY
KEYNOTES
Key
Value Keynote Text
1 EXISTING WALL RETURN TRANSFER GRILLE SHALL BE CLEANED (TYP)
2 INSTALL NEW LINEAR SLOT DIFFUSER TO NEW 14Ø SUPPLY DUCTWORK.
BALANCE TO 320 CFM.
SYMBOL LOCATION
BOX DIMENSIONS
H (IN)L (IN)MAXMIN
CFM
W (IN)
DUCT
INLET
(IN) W x H (IN)
OUTLET DUCT
SIZE
ELECTRIC HEATING COIL
CFM °F °F
EAT LAT MCA
SP LOSS
MAX
(IN)
BASIS OF DESIGN
MOPKW VOLTS/Ph.ROOM
SERVES
VAV-3W9 TESTING CENTER - 320 30001650 24 1839.5320 16 24x18 1650 55 81.8 21.0 0.25 TITUS DESV2514 480/3
VARIABLE VOLUME BOX WITH ELECTRIC HEATING COIL SCHEDULE
VAV-3W10 TITUS DESV
ELECTRICAL
30001650 24 1839.5 16 24x18 1650 55 81.8 21.0 0.252514 480/3TESTING CENTER - 320 320
1.
2.
3.
4.
NOTES:
SELECTIONS ARE BASED ON TITUS AS MANUFACTURER.
ALL PERFORMACE BASED ON TESTS CONDUCTED IN ACCORDANCE WITH ASHRAE 130-2008 AND AHRI 880-2011.
ALL NC LEVELS DETERMINED USING AHRI 885-2008 APPENDIX E.
ALL AIRFLOW, PRESSURE LOSSES AND HEATING PERFORMANCE VALUES HAVE BEEN CORRECTED FOR ALTITUDE.
AIR FLOWAIR FLOW
AIR FLOWAIR FLOW
SIDE VIEW
TOP VIEW
SECTION VIEW
SPIRAL SEAM
DOUBLE WALL
DUCTWORK
30 DEGREE
ANGULAR
POSITION OF GRILLE
ON DUCTWORK
COMBINATION VOLUME
DAMPER / EXTRACTOR
DIRECT SPIRAL DUCT-MOUNTED
SUPPLY GRILLE WITH CURVED
BORDER
SUPPLY AIR DUCT
DUCT SIZE AS
INDICATED ON
FLOOR PLANS, TYP.
ADJUSTABLE DOUBLE
DEFLECTION BARS, TYP
NOTES:
1. ADJUST REAR VERTICAL BARS TO PRODUCE EVEN AIRFLOW ACROSS FACE OF GRILLE AND
IN THE DESIRED HORIZONTAL SPREAD. ADJUST FRONT HORIZONTAL BARS TO PRODUCE THE
DESIRED VERTICAL SPREAD AND DIRECTION.
2. PAINT ALL EXPOSED SHEET METAL DUCTWORK, PLENUMS AND HANGERS / SUPPORTS.
THE COLOR SHALL MATCH EXISTING.
3. NO FLEXIBLE DUCT IS PERMITTED.
4. EXPOSED EXHAUST AND RETURN DUCTS SHALL BE SIMILAR EXCEPT THAT THE GRILLE
SHALL CONTAIN AN OPPOSED BLADE DAMPER, AND SHALL BE SINGLE DEFLECTION WITH
FIXED BARS. THE DUCT MAY BE SINGLE WALL, UN-INSULATED.
FC FC
ELECTRIC HEATING COIL. SEE
SCHEDULE FOR CAPACITIES.
BRANCH PIPING CONNECTING TO
COIL SHALL BE AS SCHEDULED.
TRANSITION
CLEARANCE PER
REQUIREMENTS
OF NEC
CONTROL PANEL
AND FAN MOTOR
STARTER
INDUCED AIR
INLET WITH
FILTER
AIR FLOW DIRECTION
45 DEG. TAP-IN FOR
RECTANGULAR DUCT OR
ROUND CONICAL TAP
WHERE DUCT SIZE PERMITS.
SUPPLY DUCT SIZE AS
NOTED ON FLOOR PLANS
MIN 1.5 DIAMETERS LENGTH
OF INLET DUCT OR AS
RECOMMENDED BY MFGR,
SIZE OF INLET DUCT SHALL
MATCH UNIT INLET SIZE.
SUPPLY DUCT.
SIZE AS NOTED ON
FLOOR PLANS.
FPB
SPRING VIBRATION ISOLATOR WITH
MIN. 1" STATIC DEFLECTION ON EACH
ROD. (MAY BE OMITTED WITH
APPROVAL IF THE FAN IS INTERNALLY
ISO…
This is the start of the file's text. The full file is on GovTribe.