This document outlines agency specific requirements for a lease solicitation by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4. Key requirements for the leased space in Huntingdon County, Pennsylvania include an ambulance entrance with minimum 76 inch width and two doors, an audiology booth meeting industrial acoustics standards, exterior and interior signage per VA guidelines, a nurse call alarm system reporting to operations and providing illuminated lights outside alarmed areas, and space and connections for security surveillance and three vending machines. The related federal contract opportunity is solicitation number 36C24423R0004 for a lease of approximately 20,162 rentable and 14,935 net usable square feet.

View the file

Other files

File Type Posted
36C24423R0004_4.docx DOCX document
36C24423R0004 Amendment 0003.pdf PDF
Exhibit D. GSA Template 3516 Solicitation Provisions (Oct. 2023). Huntingdon.pdf PDF
Exhibit E. GSA Form 3517B General Clauses (Oct. 2023). Huntingdon.pdf PDF
36C24423R0004_3.docx DOCX document
RLP Amendment 0002.pdf PDF
Attachment 1. Questions_Answers. Huntingdon County.pdf PDF
Attachment 2. Huntingdon CBOC Pre-Proposal Presentation REV 10-4-23.pdf PDF
Attachment 2. Questions_Answers. Huntingdon County.pdf PDF
36C24423R0004_2.docx DOCX document
36C24423R0004 0001 Amendment.pdf PDF
Attachment 1. Pre-Proposal Meeting. Huntingdon County.pdf PDF
Exhibit D. GSA Form 3516 SOLICITATION PROVISIONS July 2021. Huntingdon County.pdf PDF
Exhibit I. Addendum to SAM Rep and Cert. Huntingdon County.pdf PDF
Exhibit X. Interior Signage. Huntingdon County.pdf PDF
Attachment 1. Past Performance Questionnaire. Huntingdon County PA.docx DOCX document
Exhibit N. Tenant Improvements Cost Summary (TICS) Table (Jul.2022). Huntingdon County.xlsx XLSX spreadsheet
Exhibit E. GSA Form 3517B (Sep2022) General Clauses. Huntingdon County.pdf PDF
36C24423R0004_1.docx DOCX document
Exhibit AB. FAR 52.204-27 Prohibition on a ByteDance Covered Application.pdf PDF
Exhibit C. Security Requirements (FSL Level II) (Aug. 2022). Huntingdon County.pdf PDF
Exhibit F. GSA Form 1364 Proposal to Lease Space (Apr. 22). Huntingdon County.pdf PDF
Exhibit W. Program Management Plan. Huntingdon County.pdf PDF
Exhibit G. GSA Form 1217 Lessor Annual Cost. Huntingdon County.pdf PDF
Exhibit L. Unit Price List. Huntingdon County.pdf PDF
Exhibit Q. Space Requirement. Huntingdon County.pdf PDF
Exhibit A. Global Lease L100 (Oct. 2022) - 36C24423L0004 - Huntingdon County.pdf PDF
Exhibit M. DOL Wage Determination REV 9-15-23. Huntingdon County.pdf PDF
Exhibit K. Security Unit Price List FSL II (Jun. 2022). Huntingdon County.xlsx XLSX spreadsheet
Exhibit AA. FAR 52.204-24 Representation Digital Rev 10 20. Huntingdon County.pdf PDF
Exhibit H. GSA Form 1200 Prelease FPLS Evaluation (Part A _ Part B) (May 2015). Huntingdon County.pdf PDF
Global Request for Lease Proposal (RLP) R100 (Oct. 2022). 36C24423R0004 Huntingdon County.pdf PDF
Exhibit P. Government Typical Building Layout. Huntingdon County.pdf PDF
Exhibit O - Contract Submittal Schedule. Huntingdon County.docx DOCX document
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXHIBIT B Page 1 of 3

RLP NO. 36C24423R0004

LEASE NO. 36C24423L0004

Huntingdon Agency Specific Requirements (ASR)

List – 11-08-2022

ITEM HOW

MANY

DESCRIPTION

Ambulance Entrance 1 A Nonpublic access should be created which enters into the clinic in a nonpublic area. The entrance should have a minimum width of 76 inches and have two doors with no post between.

The doors will have to be secured when not in use. This entrance shall also have an intercom system installed in order to communicate with individuals outside.

Audiology Booth

1 Lessor shall provide an Audiology Booth with all the appropriate data and electrical equipment to make it functional.

Industrial Acoustics Double Wall Suite. OD 16’6” X 10’2” X 8’ 1 ¼” and inside dimension of 8’-2” W x 6’-9”L X 6’6 ¾” H with a 36” clear opening width doors. Conduit for Fire Strobes, data and data drop for thermostat in suite. Closure plate on all side closures edges. Floor of booth to be flush with floor.

See Audiology and Speech Pathology Design Guide at:

https://www.cfm.va.gov/til/dGuide/dgAudio-spchPath.pdf

EN-09- Exterior Nonilluminated Dimensional Building Identification Letters

EN-09- Exterior Nonilluminated Dimensional Building Identification Letters:

Reference Document: VA Signage Design Guide – December 2021 at https://www.cfm.va.gov/til/dManual/dmSignage.pdf

Section – Exterior Signs – Dimensional Building Identification Letters (4-7-52) Message Layout:

Logo/Signature: Horizontal Sign Format (page 4-7-52)

Wall Mounted Monumental Signage: Sign to be appropriate size or ease of viewing. Facility exterior Architectural Entrance Sign to span minimum full width of door entrance opening of facility or as needed to be scaled in proportion to facility frontage.

Mounting – (page 4-9-17 through 4-10-11)

Sign Type EN-14 – Building Entrance Door Identification

Sign Type EN-14 – Building Entrance Door Identification Reference Document: VA Signage Design Guide – December 2021 at https://www.cfm.va.gov/til/dManual/dmSignage.pdf

EXHIBIT B Page 2 of 3

LEASE NO. 36C24423L0004

Section – Exterior Signs – Dimensional Building Identification Letters (page 4-7-61 through 4-7-63)

Sign Type Interior Signs Reference Document: VA Signage Design Guide – December 2021 at https://www.cfm.va.gov/til/dManual/dmSignage.pdf

Section – Interior Signs – Dimensional Building Identification Letters (starts on page 9-1-1)

Nurse Call

1 The Lessor shall provide a Nurse Call alarm system that reports to the central operation area and provides an illuminated light outside of the area alarmed. The following rooms shall be equipped with the nurse call alarm.

All restrooms – Restrooms shall have at a minimum a pull chord alarm to include the gynecology restroom and provider restrooms.

The lab room – Lab shall have push buttons located at the place of the blood draw are /chair

ASC-NGGTWY2-H/STATION GATEWAY II,

ASC-NUDL4S-H/DOME LIGHT 4 SECTIONS, SPEECH AND

BUZZER, and ASC-NUDUTY/DUTY STATION or approved equal.

Security Surveillance Television and Security Alarms

A Security Surveillance Television (SSTV) system shall be provided to monitor assigned areas.

The lessor shall allow the government to install an intrusion detection alarm system which detects entry into the room and which broadcasts a local alarm of sufficient volume to induce an illegal entrant to abandon a burglary attempt. The Intrusion detectors with have the following:

AA internal, automatic charging DC standby Power supply and a primary AC power operation.

A remote, key operated activation/deactivation switch Installed outside the rooms and adjacent to the room entrance door frame.

An automatic reset capability following an intrusion detection.

A local alam1 level of 80 dB (min) to 90 dB (max) up to 100 feet [30.48 m] from the protected room.

An Integral c:apability for the attachment of wiring for remote alarm and intrusion indicator equipment (visual or audio).

Intrusion detector equipment which operates on the principle of narrow beam interception, microwave, or photo eclectic eye is unacceptable.

EXHIBIT B Page 3 of 3

LEASE NO. 36C24423L0004

A locally sounding alarm should not be Installed in a room which is close to a cardiac care or other special treatment area where a loud alarm would have an injurious effect on patients.

Intrusion detector alarms will be remotely monitored by a commercial security alarm monitoring firm, a local police department, or a security office charged with building security.

The remoted alarms will be in addition to locally broadcast alarms in the protected areas.

Vending Facilities

1 Provide data, power and space for three vending machines.