Exhibit B_2-6-8 Floor Plans.pdf
PDF 775 KB Posted
- Solicitation number
- 372698_DG
About this file
These are architectural and engineering design drawings for the IERC CCD Space Humidification Project (Project No. 2-6-8) at Fermilab. The documents include a vicinity plan showing site entrances and access routes, and detailed ground floor plumbing and electrical plans for humidifier installation. The humidifier schedule indicates two electric steam humidifiers with specifications, including wall-mounted duct configuration and air proving switch. The electrical notes provide comprehensive guidelines for installation, including conduit requirements, wiring specifications, grounding procedures, receptacle standards, and safety protocols. The project involves installing humidification equipment in specific lab spaces including CCD Testing Project Lab G623, Support Lab G583, Dark Room G585, and Equipment Chase S G295, with electrical connections planned from specific panel boards (PP-IERC-A1-A1-7 and PP-IERC-B1-1-6-A2).
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IERC CCD SPACE HUMIDIFICATION
PROJECT NO.: 2-6-8
LIST OF DRAWINGS
G-01 COVER SHEET
PE-01 PLUMBING & ELECTRICAL PLANS
PROJECT
AREA
RAILYARD
STORAGE
AREA
ROAD
C
HWY. 56 BUTTERFIELD RD.
INDUSTRIAL
MAIN
TO
IN
TE
R
ST
AT
E I-8
FA
R N
SW
O
R
TH
KAUTZ RD.
CONSTRUCTION
ENTRANCE
INJECTOR
MAIN
SUBSTATION
KA
U
TZ
R
D
KAUTZ RD.
RING RD.
WILSON ST.
ENTRANCE
PINE ST.
ENTRANCE
(NO TRUCKS)
R O
AD
B
PINE ST. (OUT)
PINE ST. (IN)
KI
R
K R
D
ROAD
A
-2
ROAD
A -1
HOLTER RD
AREA
LABORATORY
CENTRAL
CDF
FE
LD
O
TT
R D
BATAVIA RD.
WILSON ST.
RECEIVING
SITE
BURLINGTON NORTHERN R.R.
TO ENTER THIS GATE
FA
RM
R D
LEGEND
SITE BOUNDARY LINES
ON SITE CONST. ROUTES
SW
ENSON
HOURS
(NO ACCESS)
EOLA RD.
ENTRANCE
TO RT. 59
HWY 38 ROOSEVELT RD.
BATAVIA RD.
EO
LA
R
D
FIXED
TARGET
AREA
ROAD D
FERMILAB
VILLAGE
LOCKED
GATE
WILSON ST.
NOTE: APPROPRIATE I.D. IS REQUIRED
(LOAD LIMIT-6 TONS)
C O
M M
O N
W
EA
LT
H
E D
IS
O
N P
O W
ER
L
IN
ES
BATAVIA RD.
ENTRANCE
TO HWY 59
EL
G
IN
J
O
LI
ET
E
AS
TE
R
N R
.R
WILSON ST 6 AM TO 6 PM
PINE ST 6 AM TO 8 PM
BATAVIA RD 6 AM TO 8 PM
KAUTZ RD CLOSED
NOTE: APPROPRIATE I.D.
IS REQUIRED TO ENTER
THIS GATE (REAL ID)
VICINITY PLAN
NOT TO SCALE
S ep
0,
- 1
2:
pm H
:\A ct iv e
Pr oj ec ts
\2 \6
IN
TE
G R
AT
ED
E N
G
IN
EE
R
IN
G
R
ES
ER
AC
H C
EN
TE
R (I
ER
C
)\8
IE
R C
C C
D L ab H im id ifi er
In st al la tio n\
- F in al
D es ig n\
D ra w in gs \2
-6 -8
G
EN
ER
AL
.d w g
----A TAYLOR
A TAYLOR
A BIELSKUS
J WILLS
2-6-8
IERC CCD SPACE HUMIDIFICATION
G-01
Se pt
. 1 0, IS
SU
ED
F O
R B
ID
COVER SHEET
SCALE:
PROJECT NO.
SHEET NO.
DESIGNED
DRAWN
CHECKED
APPROVED
ISD ENGINEERING DATE PROJECT NAME.
SHEET NAME:
REVISIONS
REV. DESCRIPTION DATE
REVISION NO.FIMS. NO.
ISD
INFRASTRUCTURE
SERVICES DIVISION
5 6 7
B
D
E
C
7.3
B.9
EX. FD EX. FD EX. FD EX. FD
EX. FCO
EX. FCO
EX. FD
HUM-2HUM-1
EX. 3" CW
EX. 3 4" CW EX. 3" CW
EX. 3 4" CW
NEW 12" CW
NEW 12" DRAIN. ROUTE FROM
CONDENSATE PUMP
OVERHEAD TO FLOOR DRAIN.
ROUTE OUT OF PATH OF
PEOPLE AND EQUIPMENT.
TERMINATE DRAIN PIPE AT EXISTING
FLOOR DRAIN. ADD 4" ROUND WATTS
FD-F4-3 STAINLESS STEEL BOLT-ON
FUNNEL. TERMINATE PIPE WITH 1" AIR GAP
ABOVE LIP OF FUNNEL.
TERMINATE DRAIN PIPE AT EXISTING
FLOOR DRAIN. ADD 4" ROUND WATTS
FD-F4-3 STAINLESS STEEL BOLT-ON
FUNNEL. TERMINATE PIPE WITH 1" AIR GAP
ABOVE LIP OF FUNNEL.
NEW 1" DRAIN. ROUTE DRAIN
FROM EQUIPMENT ACROSS
FLOOR TO EXISTING FLOOR
DRAIN.NEW FACTORY SUPPLIED
CONDENSATE PUMP.
CCD TESTING
PROJECT LAB
G623
SUPPORT
LAB
G583
DARK
ROOM
G585
EQUIPMENT
CHASE S
G295
NEW 12" CW
NEW 5 8" DRAIN
H H HUM-2HUM-1
GROUND FLOOR PLUMBING PLAN
1/8" = 1' - 0"
5 6 7
B
D
E
C
7.3
B.9
CCD TESTING
PROJECT LAB
G623
SUPPORT
LAB
G583
DARK
ROOM
G585
EQUIPMENT
CHASE S
G295
GROUND FLOOR ELECTRICAL PLAN
1/8" = 1' - 0"
PP-IERC-A1-A1-7
HUMIDIFIER: CKT 18, 20, 22 (30A BREAKER)
BLOWER: CKT 24 (15A BREAKER)
PUMP: CKT 26 (15A BREAKER)
PROVIDE NEW CONDUIT
AND CONDUCTORS FROM
PP-IERC-A1-A1-7 TO
HUMIDIFIER AND BLOWER
(PROVIDED BY M.C.)
PROVIDE NEW CONDUIT AND
CONDUCTORS FROM PP-IERC-A1-A1-7 TO
CONDENSATE PUMP (PROVIDED BY M.C.)
PP-IERC-B1-1-6-A2
HUMIDIFIER: CKT 13, 15, 17 (30A BREAKER)
BLOWER: CKT 19 (15A BREAKER)
PROVIDE NEW CONDUIT
AND CONDUCTORS FROM
PP-IERC-B1-1-6-A2 TO
HUMIDIFIER AND BLOWER
(PROVIDED BY M.C.)
1. LOCATION OF FIXTURES AND OTHER PIECES OF ELECTRICAL
EQUIPMENT AS SHOWN ON THE DRAWINGS ARE APPROXIMATE
AND SHALL BE COORDINATED IN THE FIELD WITH THE LOCATION
OF PIPES, VENTILATION DUCTS AND MECHANICAL EQUIPMENT
TO AVOID INTERFERENCES. ANY CONFLICTS DERIVING FROM
EQUIPMENT INSTALLATION SHALL BE BROUGHT IMMEDIATELY
TO THE ATTENTION OF THE FERMILAB CONSTRUCTION
COORDINATOR.
2. ALL CONDUITS SHALL CONTAIN AN INSULATED, GREEN
COLORED EQUIPMENT GROUNDING CONDUCTOR.
3. ALL WIRING SHALL BE COPPER, 600 VOLTS, TYPE THHN/THWN
INSULATION. MINIMUM SIZE SHALL BE NO. 12 AWG. FOR POWER
AND NO. 14 FOR CONTROL, UNLESS NOTED OTHERWISE.
4. FINAL CONNECTION TO TRANSFORMERS, MOTORS OR OTHER
VIBRATION GENERATING DEVICES SHALL BE MADE WITH USE OF
STRANDED CONDUCTORS IN LIQUID TIGHT FLEXIBLE CONDUIT.
5. ALL EQUIPMENT SHALL BE CONNECTED TO AN EQUIPMENT
GROUNDING CONDUCTOR AT THE EQUIPMENT'S GROUNDING
LUG OR BY SPLICE TO THE EQUIPMENT'S GREEN COLORED OR
BARE COPPER FIXTURE GROUNDING WIRE.
6. ALL CONDUCTORS TO BE RUN IN 3/4" MINIMUM METALLIC
CONDUIT.
6.1. EMT Indoor, dry, locations not subject to damage
6.2. RGS Outdoor, wet, locations subject to damage
7. ALL PULL BOXES AND JUNCTION BOXES SHALL BE SIZED PER
THE LATEST EDITION OF THE NEC. SUBCONTRACTOR SHALL
SIZE, FURNISH AND INSTALL ALL PULL BOXES OR JUNCTION
BOXES AS REQUIRED BY Y THE NEC.
8. ALL MATERIAL AND ELECTRICAL EQUIPMENT SHALL BE LISTED
BY UNDERWRITERS LABORATORIES, INC. OR CERTIFIED BY A
NATIONALLY RECOGNIZED TESTING LABORATORY. ALL
INSTALLATIONS SHALL COMPLY WITH THE RULES AND
REGULATIONS OF THE LATEST EDITION OF THE NEC AND OSHA.
9. ALL ELECTRICAL INSTALLATIONS SHALL BE SUBJECT TO THE
REVIEW AND APPROVAL OF THE FERMILAB CONSTRUCTION
COORDINATOR. ANY ELECTRICAL INSTALLATION NOT MEETING
THE APPROVAL OF THE FERMILAB CONSTRUCTION
COORDINATOR SHALL BE REMOVED AND REINSTALLED TO THE
SATISFACTION OF FERMILAB BY THE SUBCONTRACTOR, AT NO
COST TO FERMILAB.
10. SUBCONTRACTOR TO SEAL AROUND CONDUIT PENETRATION
THROUGH FIREWALL WITH UL APPROVED FIRE BARRIER
CAULKING.
11. COORDINATE ALL CIRCUIT NUMBERS FOR NEW RECEPTACLES
WITH CONSTRUCTION COORDINATOR.
12. PANELS, RECEPTACLES, LIGHT SWITCHES, EQUIPMENT, ETC. TO
BE LABELED WITH POWER SOURCE. LABELING TAPE SHALL BE
USED FOR DEVICE LABELING AND LAMACOID SHALL BE USED
FOR EQUIPMENT LABELING. TAPES SHALL INDICATE THE FULL
PANEL DESIGNATION AND INDICATED ON THE DRAWINGS AS
WELL AS THE CIRCUIT BREAKER NUMBER AND VOLTAGE.
13. NO ELECTRICAL WORK SHALL BE PERFORMED ON ENERGIZED
CIRCUITS. ALL CIRCUITS MUST BE LOCKED OUT AND TAGGED
OUT BEFORE WORK CAN BEGIN. AFTER CIRCUITS ARE LOCKED
OUT, VERIFY WITH A TEST INSTRUMENT THAT ALL CONDUCTORS
ARE ACTUALLY DE-ENERGIZED. ALL WORK SHALL BE
PERFORMED IN ACCORDANCE WITH FERMILAB'S (ES & H)
SAFETY PROGRAM.
14. RECEPTACLES SHALL HAVE THE FOLLOWING CHARACTERISTICS:
14.1. ALL RECEPTACLES SHALL BE FROM THE SAME
MANUFACTURER AND HAVE IDENTICAL PHYSICAL
APPEARANCE AND CHARACTERISTIC.
14.2. CONVENIENCE RECEPTACLES FOR BUILDING SERVICES
SHALL BE GROUNDING TYPE, RATED AS SPECIFIED AND
NEMA PERFORMANCE SPECIFICATION GRADE.
14.3. CONVENIENCE RECEPTACLES HOUSINGS SHALL BE HEAVY
GRADE UREA OR CERAMIC, IVORY COLOR.
14.4. THE FOLLOWING STANDARD RECEPTACLES OR THEIR
EQUIVALENT SHALL BE USED AS INDICATED ON THE
DRAWINGS, COMPLETE WITH BOXES, ANGLE ADAPTERS AND
ASSOCIATED HARDWARE:
14.4.1. CONVENIENCE (DUPLEX): 120V, 20A, 1Ø, 2-WIRE WITH
GROUND, HUBBELL HBL5362W.
14.5. ALL COVERS FOR WIRING DEVICES HOUSING RECEPTACLES
SHALL BE OF THE METALLIC TYPE. PLASTIC COVERS ARE
UNACCEPTABLE.
15. PROVIDE NEW CIRCUIT DIRECTORIES IN ACCORDANCE WITH
NEC.
15.1. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
SPECIFIC PURPOSE OR USE.
15.2. THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO
ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL
OTHERS.
15.3. SPARE POSITIONS THAT CONTAIN UNUSED OVERCURRENT
DEVICES OR SWITCHES BE DESCRIBED ACCORDINGLY.
15.4. THE IDENTIFICATION SHALL BE INCLUDED IN A CIRCUIT
DIRECTORY THAT IS LOCATED ON THE FACE OR INSIDE OF
THE PANEL DOOR AND LOCATED AT EACH SWITCH ON A
SWITCH BOARD.
15.5. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER THAT
DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY (I.E
OCCUPANT OR OFFICE NAME OR NUMBER).
15.6. SUBMIT DIRECTORY FOR REVIEW AND APPROVAL PRIOR TO
INSTALLATION.
ELECTRICAL SHEET NOTES
S ep
0,
- 1
2:
pm H
:\A ct iv e
Pr oj ec ts
\2 \6
IN
TE
G R
AT
ED
E N
G
IN
EE
R
IN
G
R
ES
ER
AC
H C
EN
TE
R (I
ER
C
)\8
IE
R C
C C
D L ab H im id ifi er
In st al la tio n\
- F in al
D es ig n\
D ra w in gs \2
-6 -8
P
LU
M
BI
N G
.d w g
1/8"=1'-0" 8 0 8 16
SCALE FEET
SCALE:
PROJECT NO.
SHEET NO.
DESIGNED
DRAWN
CHECKED
APPROVED
ISD ENGINEERING DATE
PROJECT NAME.
SHEET NAME:
REVISIONS
REV. DESCRIPTION DATE
REVISION NO.FIMS. NO.
ISD
INFRASTRUCTURE
SERVICES DIVISION
----A TAYLOR
A TAYLOR
A BIELSKUS
J WILLS
2-6-8
IERC CCD SPACE HUMIDIFICATION
PE-01
Se pt
. 1 0, IS
SU
ED
F O
R B
ID
PLUMBING & ELECTRICAL
FLOOR PLANS---- ----
004-
W
S
E
PN
TN
| Sheets and Views |
| G-01 COVER SHEET |
| PE-01 PLUMBING & ELECTRICAL FLOOR PLANS |
File details come from the government source that posted it. Updated .