The lease is for 1,000 - 3,000 square feet of warehouse/flex space in Reno/Sparks, Nevada. The full lease term is 10 years with a firm term of 5 years. The government requires the space to meet specifications for fire safety, accessibility, seismic, and sustainability, and to have a minimum 10-foot ceiling height, a ground-level roll-up door of at least 10'x10', and the ability to accommodate interior storage and light maintenance of 2 vehicles up to 18'9" long and 6'9" wide. The government will be responsible for all tenant improvements. The lease is a fully serviced lease and the offered space must not be in a 100-year floodplain. Offers are due by July 26, 2024 for an estimated October 2025 occupancy. The contracting agency is the General Services Administration, Public Buildings Service Region 9.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEASE NO. GS-09P-LNV03410, PAGE 1 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
REQUIREMENTS
REV (10/2023)
TABLE OF CONTENTS – SUPPLEMENTAL LEASE REQUIREMENTS
SECTION 1 GENERAL TERMS, CONDITIONS, AND STANDARDS
1.01 DEFINITIONS AND GENERAL TERMS (SMALL) (OCT 2023)
1.02 INTENTIONALLY DELETED
1.03 AUTHORIZED REPRESENTATIVES (OCT 2016)
1.04 WAIVER OF RESTORATION (OCT 2023)
1.05 NOVATION AND CHANGE OF OWNERSHIP (SMALL) (OCT 2016)
1.06 ASBESTOS (SMALL) (OCT 2021)
1.07 ADJUSTMENT FOR VACANT PREMISES (SMALL) (OCT 2022)
1.08 ENTITY NAME (OCT 2023)
SECTION 2 CONSTRUCTION STANDARDS AND SHELL COMPONENTS
2.01 WORK PERFORMANCE (SMALL) (SEP 2015)
2.02 INTENTIONALLY DELETED
2.03 INTENTIONALLY DELETED
2.04 INTENTIONALLY DELETED
2.05 BUILDING SHELL REQUIREMENTS (SMALL) (OCT 2019)
2.06 RESPONSIBILITY OF THE LESSOR AND LESSOR’S ARCHITECT/ENGINEER (SMALL) (SEP 2015)
2.07 MEANS OF EGRESS (MAY 2015)
2.08 AUTOMATIC FIRE SPRINKLER SYSTEM (OCT 2023)
2.09 FIRE ALARM SYSTEM (SEP 2013)
2.10 ENERGY INDEPENDENCE AND SECURITY ACT (SMALL) (SEP 2015)
2.11 ELEVATORS (SMALL) (OCT 2020)
2.12 DEMOLITION (JUN 2012)
2.13 ACCESSIBILITY (FEB 2007)
2.14 INTENTIONALLY DELETED
2.15 EXTERIOR AND COMMON AREA DOORS AND HARDWARE (SEP 2013)
2.16 WINDOWS (SMALL) (OCT 2020)
2.17 INTENTIONALLY DELETED
2.18 INTENTIONALLY DELETED
2.19 PAINTING – SHELL (SMALL) (OCT 2020)
2.20 FLOORS AND FLOOR LOAD (SMALL) (OCT 2019) – MODIFIED
2.21 MECHANICAL, ELECTRICAL, PLUMBING: GENERAL (SMALL) (SEP 2015)
2.22 INTENTIONALLY DELETED
2.23 RESTROOMS (WAREHOUSE) (OCT 2022) – MODIFIED
2.24 HEATING, VENTILATION, AND AIR CONDITIONING – SHELL (SMALL) (OCT 2022)
2.25 TELECOMMUNICATIONS: DISTRIBUTION AND EQUIPMENT (SMALL) (SEP 2015)
2.26 TELECOMMUNICATIONS: LOCAL EXCHANGE ACCESS (SMALL) (OCT 2020)
2.27 LIGHTING: INTERIOR AND PARKING – SHELL (SMALL) (OCT 2022)
2.28 INTENTIONALLY DELETED
2.29 INTENTIONALLY DELETED
SECTION 3 DESIGN, CONSTRUCTION, AND POST AWARD ACTIVITIES
3.01 INTENTIONALLY DELETED
3.02 ACCESS BY THE GOVERNMENT PRIOR TO ACCEPTANCE (SMALL) (OCT 2020)
3.03 ACCEPTANCE OF SPACE AND CERTIFICATE OF OCCUPANCY (SMALL) (OCT 2021)
3.04 LEASE TERM COMMENCEMENT DATE AND RENT RECONCILIATION (SMALL) (OCT 2021)
3.05 INTENTIONALLY DELETED
3.06 SEISMIC RETROFIT (OCT 2020)
3.07 INTENTIONALLY DELETED
SECTION 4 TENANT IMPROVEMENT COMPONENTS
4.01 INTENTIONALLY DELETED
4.02 INTENTIONALLY DELETED
4.03 INTENTIONALLY DELETED
4.04 INTENTIONALLY DELETED
4.05 INTENTIONALLY DELETED
4.06 INTENTIONALLY DELETED
4.07 INTENTIONALLY DELETED
4.08 INTENTIONALLY DELETED
4.09 INTENTIONALLY DELETED
4.10 HEATING AND AIR CONDITIONING (SMALL) (OCT 2022) - MODIFIED
4.11 ELECTRICAL: DISTRIBUTION (SMALL) (SEP 2015)
4.12 TELECOMMUNICATIONS: DISTRIBUTION AND EQUIPMENT (JUN 2012)
4.13 TELECOMMUNICATIONS: LOCAL EXCHANGE ACCESS (AUG 2008)
4.14 INTENTIONALLY DELETED
4.15 INTENTIONALLY DELETED
LEASE NO. GS-09P-LNV03410, PAGE 2 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
4.16 INTENTIONALLY DELETED
SECTION 5 UTILITIES, SERVICES, AND OBLIGATIONS DURING THE LEASE TERM
5.01 PROVISION OF SERVICES, ACCESS, AND NORMAL HOURS (SMALL) (OCT 2020)
5.02 UTILITIES (SMALL) (OCT 2022)
5.03 HEATING AND AIR CONDITIONING (SMALL) (OCT 2022) - MODIFIED
5.04 INTENTIONALLY DELETED
5.05 INTENTIONALLY DELETED
5.06 MAINTENANCE OF PROVIDED FINISHES (SMALL) (SEP 2015)
5.07 IDENTITY VERIFICATION OF PERSONNEL (OCT 2022)
5.08 INTENTIONALLY DELETED
5.09 INDOOR AIR QUALITY (OCT 2023)
5.10 RADON IN AIR (OCT 2023)
5.11 RADON IN WATER (JUN 2012)
5.12 HAZARDOUS MATERIALS (OCT 2023)
5.13 MOLD AND WATER INTRUSION (OCT 2023)
5.14 OCCUPANT EMERGENCY PLANS (OCT 2020)
SECTION 6 ADDITIONAL TERMS AND CONDITIONS
6.01 SECURITY REQUIREMENTS (SMALL) (OCT 2019)
6.02 MODIFIED LEASE PARAGRAPHS (OCT 2016)
6.03 RENTAL CONSIDERATION FOR SMALL LEASES (OCT 2019)
6.04 INTENTIONALLY DELETED
6.05 INTENTIONALLY DELETED
LEASE NO. GS-09P-LNV03410, PAGE 3 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
SECTION 1 GENERAL TERMS, CONDITIONS, AND STANDARDS
1.01 DEFINITIONS AND GENERAL TERMS (SMALL) (OCT 2023)
Unless otherwise specifically noted, all terms and conditions set forth in this Lease shall be interpreted by reference to the following definitions, standards, and formulas:
A. Real Property Terms.
1. “ANSI/BOMA” is an acronym for American National Standards Institute/Building Owners and Managers Association.
2. “ANSI/BOMA Occupant Area” or “ABOA” means the measurement standard (Z65.1-2017) provided by ANSI/BOMA for Occupant Area, which is “the total aggregated area used by an Occupant before Load Factors are applied, consisting of Tenant Area and Tenant Ancillary Area.” The Method A – Multiple Load Factor Method shall apply.
3. “Common Area Factor (CAF)” means a conversion factor determined and applied by the building owner to determine the rentable square feet for the leased space. The CAF is expressed as a percentage of the difference between the amount of rentable square feet (SF) and ABOA SF, divided by the ABOA SF. The CAF shall be determined in accordance with the applicable ANSI/BOMA standard for the type of space to which the CAF shall apply.
4. “Rentable Space or Rentable Square Feet (RSF)” means the area for which a tenant is charged rent. It is determined by the building owner and may vary by city or by building within the same city. Rentable space may include a share of common areas such as elevator lobbies, building corridors, and floor service areas. Floor service areas typically include restrooms, janitor rooms, telephone closets, electrical closets, and mechanical rooms. Rentable space does not include vertical building penetrations and their enclosing walls, such as stairs, elevator shafts, and vertical ducts. To determine the RSF, the ABOA SF is multiplied by the sum of one (1) plus the CAF, for each type of space included in the premises.
5. “Space” means that part of the premises to which the Government has exclusive use, such as occupant area, or other types of space.
Appurtenant areas (e.g., parking areas) to which the Government has rights under the lease are not included in the space.
1.02 INTENTIONALLY DELETED
1.03 AUTHORIZED REPRESENTATIVES (OCT 2016)
Signatories to this Lease shall have full authority to bind their respective principals with regard to all matters relating to this Lease. No other persons shall be understood to have any authority to bind their respective principals except to the extent that such authority may be explicitly delegated by notice to the other party, or to the extent that such authority is transferred by succession of interest. The Government shall have the right to substitute its Lease Contracting Officer (LCO) by notice without an express delegation by the prior LCO.
1.04 WAIVER OF RESTORATION (OCT 2023)
Lessor shall have no right to require the Government to restore the Premises upon expiration or earlier termination (full or partial) of the Lease, and waives all claims against the Government for:
A. Waste, or, B. Damages or restoration arising from or related to:
1. The Government's normal and customary use of the Premises during the term of the Lease (including any extensions thereof), as well as
2. Any initial or subsequent alteration to the Premises regardless of whether such alterations are performed by the Lessor or by the
Government.
At its sole option, the Government may abandon property in the Space following expiration or earlier termination (full or partial) of the Lease, in which case the property will become the property of the Lessor, and the Government will be relieved of any liability in connection therewith.
1.05 NOVATION AND CHANGE OF OWNERSHIP (SMALL) (OCT 2016)
Consistent with GSAM 570.115, in the event of a transfer of ownership of the leased premises or a change in the Lessor’s legal name, FAR 42.12 applies.
1.06 ASBESTOS (SMALL) (OCT 2021)
The leased space shall be free of all asbestos containing materials, except undamaged asbestos flooring in the space or undamaged boiler or pipe insulation outside the space, in which case an asbestos management program conforming to Environmental Protection Agency guidance shall be implemented. The space shall be free of other hazardous materials and in compliance with applicable Federal, State, and local environmental laws and
LEASE NO. GS-09P-LNV03410, PAGE 4 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE regulations. If asbestos abatement work is to be performed in the Space after occupancy, the Lessor shall provide relocation and submit to the Government documentation that the abatement was done in accordance with OSHA, EPA, DOT, state, and local regulations and guidance and that final clearance for re-occupancy was achieved.
1.07 ADJUSTMENT FOR VACANT PREMISES (SMALL) (OCT 2022)
If the Government fails to occupy any portion of the leased Premises or vacates the Premises in whole or in part prior to expiration of the term of the Lease, the operating costs paid by the Government as part of the rent rental rate shall be reduced using the “Adjustment for Vacant Premises Rate” specified on GSA Form 3626 of this Lease. This reduction shall occur after the Government gives 30 calendar days’ prior notice to the Lessor and shall continue in effect until the Lease expires or is terminated.
1.08 ENTITY NAME (OCT 2023)
Lessor may not use Federal agency name(s) and/or acronym(s), e.g., General Services Administration, GSA, in its entity name that owns and/or leases Space to GSA.
LEASE NO. GS-09P-LNV03410, PAGE 5 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
SECTION 2 CONSTRUCTION STANDARDS AND SHELL COMPONENTS
2.01 WORK PERFORMANCE (SMALL) (SEP 2015)
All work in performance of this Lease shall be done by skilled and licensed workers or mechanics and shall be acceptable to the LCO.
2.02 INTENTIONALLY DELETED
2.03 INTENTIONALLY DELETED
2.04 INTENTIONALLY DELETED
2.05 BUILDING SHELL REQUIREMENTS (SMALL) (OCT 2019)
A. The Building Shell shall be designed, constructed, and maintained in accordance with the standards set forth herein and completed prior to acceptance of Space.
B. Base structure and Building enclosure components shall be complete. All common areas accessible by the Government, such as lobbies, fire egress corridors and stairwells, elevators, garages, and service areas, shall be complete. Restrooms shall be complete and operational. All newly installed Building shell components, including but not limited to, heating, ventilation, and air conditioning (HVAC), electrical, ceilings, sprinklers, etc., shall be furnished, installed, and coordinated with TIs. Circulation corridors are provided as part of the base Building only on multi-tenanted floors where the corridor is common to more than one tenant. On single tenant floors, only the fire egress corridor(s) necessary to meet code is provided as part of the shell.
C. The Building Shell rental rate shall also include, but is not limited to, insurance, taxes, lease commission and management, in addition to profit, reserve costs and loan financing for the Building.
2.06 RESPONSIBILITY OF THE LESSOR AND LESSOR’S ARCHITECT/ENGINEER (SMALL) (SEP 2015)
The Lessor remains solely responsible for designing, constructing, operating, and maintaining the leased premises in full accordance with the requirements of the Lease. The Lessor shall, without additional compensation, correct or revise any errors or deficiencies in its designs, drawings, specifications, or other services, as noted by the Government’s review or otherwise.
2.07 MEANS OF EGRESS (MAY 2015)
A. Prior to occupancy, the Premises and any parking garage areas shall meet or will be upgraded to meet either the applicable egress requirements in the National Fire Protection Association, Life Safety Code (NFPA 101) or the International Code Council, International Building Code (IBC), each current as of the Lease Award Date, or use an alternative approach or method that achieves an equivalent level of safety deemed acceptable by the Government.
B. The Space shall have unrestricted access to a minimum of two remote exits on each floor of Government occupancy.
C. Interlocking or scissor stairs located on the floor(s) where Space is located shall only count as one exit stair.
D. A fire escape located on the floor(s) where Space is located shall not be counted as an approved exit stair.
E. Doors shall not be locked in the direction of egress unless equipped with special locking hardware in accordance with requirements of NFPA
101 or the IBC.
2.08 AUTOMATIC FIRE SPRINKLER SYSTEM (OCT 2023)
A. Any portion of the Space located below-grade, including parking garage areas, and all areas in a Building referred to as "hazardous areas"
(defined in National Fire Protection Association (NFPA) 101) that are located within the entire Building (including non-Government areas) shall be protected by an automatic fire sprinkler system or an equivalent level of safety.
B. For Buildings in which any portion of the Space on or above the sixth floor, then, at a minimum, the Building up to and including the highest floor of Government occupancy shall be protected by an automatic fire sprinkler system or an equivalent level of safety.
C. For Buildings in which the Government occupies, either through this Lease or in combination with other Government Leases in the Building any portion of the Space is on or above the sixth floor, and lease of the Space will result, either individually or in combination with other Government Leases in the Building, in the Government leasing 35,000 or more ANSI/BOMA Occupant Area SF of Space in the Building, then the entire Building shall be protected throughout by an automatic fire sprinkler system or an equivalent level of safety.
D. Automatic fire sprinkler system(s) shall be installed in accordance with the requirements of NFPA 13, Standard for the Installation of Sprinkler
Systems that was in effect on the actual date of installation.
E. Automatic fire sprinkler system(s) shall be maintained in accordance with the requirements of NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-based Fire Protection Systems (current as of the Lease Award Date).
LEASE NO. GS-09P-LNV03410, PAGE 6 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
F. "Equivalent level of safety" means an alternative design or system (which may include automatic fire sprinkler systems), based upon fire protection engineering analysis, which achieves a level of safety equal to or greater than that provided by automatic fire sprinkler systems.
2.09 FIRE ALARM SYSTEM (SEP 2013)
A. A Building-wide fire alarm system shall be installed in the entire Building in which any portion of the Space is located on the 3rd floor or higher.
B. The fire alarm system shall be installed in accordance with the requirements of NFPA 72, National Fire Alarm and Signaling Code, that was in effect on the actual date of installation.
C. The fire alarm system shall be maintained in accordance with the requirements of NFPA 72, National Fire Alarm and Signaling Code (current as of the Lease Award Date).
D. The fire alarm system shall transmit all fire alarm signals to the local fire department via any of the following means: directly to the local fire department, to the (911) public communications center, to a central station, to a remote supervising station, or to a proprietary supervising station.
E. If the Building’s fire alarm control unit is over 25 years old as of the date of award of this Lease, Lessor shall install a new fire alarm system in accordance with the requirements of NFPA 72, National Fire Alarm and Signaling Code (current as of the Lease Award Date), prior to Government acceptance and occupancy of the Space.
2.10 ENERGY INDEPENDENCE AND SECURITY ACT (SMALL) (SEP 2015)
The Lessor shall either earn the ENERGY STAR® Label or complete all cost-effective energy efficiency and conservation improvements, agreed to by Lessor prior to acceptance of the Space (or not later than one year after the Lease Award Date of a succeeding or superseding Lease).
2.11 ELEVATORS (SMALL) (OCT 2020)
A. The Lessor shall provide suitable passenger elevator and, when required by the Government, freight elevator service to any of the Premises not having ground level access. Service shall be available during the normal hours of operation specified in the in this Lease.
B. Code. Elevators shall conform to the requirements of the American Society of Mechanical Engineers ASME A17.1/CSA B44, Safety Code for
Elevators and Escalators that were in effect based on the elevator installation date code year. Elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1/CSA B44. Fire alarm initiating devices (e.g., smoke detectors) used to initiate Phase I emergency recall operation shall be installed in accordance with the requirements of NFPA 72, National Fire Alarm and Signaling Code. The elevators shall be inspected and maintained in accordance with the current edition of the ASME A17.2, Inspector’s Manual for Elevators. Except for the reference to ASME A17.1 in ABAAS, Section F105.2.2, all elevators must meet ABAAS requirements for accessibility in Sections 407, 408, and 409 of ABAAS.
C. Safety Systems. Elevators shall be equipped with telephones or other two-way emergency communication systems. The system used shall be marked and shall reach an emergency communication location staffed 24 hours per day, 7 days per week.
2.12 DEMOLITION (JUN 2012)
The Lessor shall remove existing abandoned electric, telephone, and data cabling and devices, as well as any other improvements or fixtures in place to accommodate the Government’s requirements. Any demolition of existing improvements that is necessary to satisfy the Government’s layout shall be done at the Lessor’s expense.
2.13 ACCESSIBILITY (FEB 2007)
The Building, leased Space, and areas serving the leased Space shall be accessible to persons with disabilities in accordance with the Architectural Barriers Act Accessibility Standard (ABAAS), Appendices C and D to 36 CFR Part 1191 (ABA Chapters 1 and 2, and Chapters 3 through 10). To the extent the standard referenced in the preceding sentence conflicts with local accessibility requirements, the more stringent shall apply.
2.14 INTENTIONALLY DELETED
2.15 EXTERIOR AND COMMON AREA DOORS AND HARDWARE (SEP 2013)
A. Exterior Building doors and doors necessary to the lobbies, common areas, and core areas shall be required. This does not include suite entry or interior doors specific to TIs.
B. Exterior doors shall be weather tight and shall open outward. Hinges, pivots, and pins shall be installed in a manner which prevents removal when the door is closed and locked. These doors shall have a minimum clear opening of 32" clear wide x 80" high (per leaf). Doors shall be heavy duty, flush, 1) hollow steel construction, 2) solid core wood, or 3) insulated tempered glass. As a minimum requirement, hollow steel doors shall be fully insulated, flush, #16-gauge hollow steel. Solid-core wood doors and hollow steel doors shall be at least 1-3/4 inches thick. Door assemblies shall be of durable finish and shall have an aesthetically pleasing appearance acceptable to the LCO. The opening dimensions and operations shall conform to the governing building, fire safety, accessibility, and energy codes and/or requirements. Fire door assemblies shall be listed and labeled. Labels on fire door assemblies shall be maintained in a legible condition. Fire door assemblies and their accompanying hardware, including frames and closing devices shall be installed in accordance with the requirements of NFPA 80, Standard for Fire Doors and Other Opening Protectives.
LEASE NO. GS-09P-LNV03410, PAGE 7 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
C. Exterior doors and all common area doors shall have door handles or door pulls with heavyweight hinges. All doors shall have corresponding doorstops (wall or floor mounted) and silencers. All public use doors and restroom doors shall be equipped with kick plates. All doors shall have automatic door closers. All Building exterior doors shall have locking devices installed to reasonably deter unauthorized entry.
2.16 WINDOWS (SMALL) (OCT 2020)
All exterior window assemblies shall be locked, weather resistant and watertight. Windows intended for use as a secondary means of egress must be openable from the egress side (e.g., inside) of the Building without the use of a key, tool, or special knowledge or effort for operation from the egress side.
2.17 INTENTIONALLY DELETED
2.18 INTENTIONALLY DELETED
2.19 PAINTING – SHELL (SMALL) (OCT 2020)
The Lessor shall bear the expense for all painting associated with the Building shell, including all common areas. Exterior perimeter walls and interior core walls within the Space shall be spackled and prime painted. If any Building shell areas are already painted prior to TIs, then the Lessor shall repaint, at the Lessor’s expense, as necessary during TIs.
2.20 FLOORS AND FLOOR LOAD (SMALL) (OCT 2019) – MODIFIED
A. All adjoining floor areas shall be of a common level.
B. Warehouse areas shall have a minimum live load capacity to adequately support the weight per vehicle, number of vehicles, and intended use, as defined in the agency specific requirements.
2.21 MECHANICAL, ELECTRICAL, PLUMBING: GENERAL (SMALL) (SEP 2015)
A. The Lessor shall be responsible for meeting the applicable requirements of all federal, state, and local codes and ordinances. When codes conflict, the more stringent standard shall apply.
B. The Lessor shall provide and operate all Building equipment and systems in accordance with applicable technical publications, manuals, and standard procedures.
C. Convenience outlets shall be installed in accordance with NFPA Standard 70, National Electrical Code, or local code, whichever is more stringent.
The Lessor shall provide duplex utility outlets in restrooms, corridors, and dispensing areas.
2.22 INTENTIONALLY DELETED
2.23 RESTROOMS (WAREHOUSE) (OCT 2022) – MODIFIED
A. For Warehouse Area, Lessor shall provide at its cost, restroom facilities which are handicap accessible, with an adequate number of fixtures for men and women to meet current local codes based on general warehousing use.
2.24 HEATING, VENTILATION, AND AIR CONDITIONING – SHELL (SMALL) (OCT 2022)
A. Central HVAC systems shall be installed and operational, including, as appropriate, main and branch lines, VAV boxes, dampers, flex ducts, and diffusers, for an open office layout, including all Building common areas. Systems shall be designed with sufficient systems capacity to meet all requirements in this Lease; equipment shall be concealed. Areas having excessive heat gain or heat loss or affected by solar radiation at different times of the day, shall be independently controlled.
B. Any ductwork to be reused and/or to remain in place shall be cleaned, tested, and demonstrated to be clean in accordance with the standards set forth by NADCA. The cleaning, testing, and demonstration shall occur immediately prior to Government occupancy to avoid contamination from construction dust and other airborne particulates.
C. During working hours in periods of heating and cooling, ventilation shall be provided in accordance with the American National Standards Institute, American Society of Heating, Refrigeration and Air-Conditioning Engineers (ANSI/ASHRAE) Standard 62.1, Ventilation for Acceptable Indoor Air Quality Lessors must comply with: (a) the version of ASHRAE Standard 62.1 that corresponds with how the HVAC system was designed to perform, or (b) ASHRAE Standard 62.1-2004 – whichever is later.
D. Heating and air-conditioning air distribution systems (air handling units, VAV boxes, fan coil units, etc.) for the Space shall be equipped with particulate matter air filters that meet the Minimum Efficiency Reporting Value (MERV) specified in the ANSI/ASHRAE Standard 62.1 version referenced in the sub-paragraph above. Where practicable, the Lessor is encouraged to use a MERV 13 air filter or the highest-level filter that is compatible with the HVAC system. Locations that do not meet the EPA National Ambient Air Quality Standards (NAAQS) for particulates (PM 10 or PM 2.5) must be equipped with additional filtration on outdoor air intakes as required in ANSI/ASHRAE Standard 62.1. NAAQS information can be found at HTTPS://WWW.EPA.GOV/GREEN-BOOK.
https://www.epa.gov/green-book
LEASE NO. GS-09P-LNV03410, PAGE 8 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
E. For all refrigerant-containing equipment with over 50 pounds of ozone-depleting substances (including chlorofluorocarbons- CFCs or hydrochlorofluorocarbons- HCFCs), the Lessor shall comply with the U.S. Environmental Protection Agency (EPA)’s Significant New Alternative Policy (SNAP) Program for acceptable substitutes and alternatives to ozone-depleting substances when equipment is replaced, comes to its end of useful life, or when newly purchased. The Lessor must track the type of refrigerant used in chillers and HVAC systems, and the date that the Lessor plans to replace ozone depleting substances with acceptable refrigerant substitutes in accordance with EPA’s SNAP program.
2.25 TELECOMMUNICATIONS: DISTRIBUTION AND EQUIPMENT (SMALL) (SEP 2015)
A. Building telecommunication rooms must be completed, operational, and ready for use by Government’s telecommunications provider. The telephone closets shall be equipped with deadlocking latch bolt and include a telephone backboard.
B. Telecommunications switch rooms, wire closets, and related spaces shall meet applicable Telecommunications Industry Association (TIA), Electronic Industries Alliance (EIA) and NFPA standards. Bonding and grounding shall be in accordance with NFPA Standard 70, NEC National Electrical Code, and other applicable NFPA standards and/or local code requirements.
2.26 TELECOMMUNICATIONS: LOCAL EXCHANGE ACCESS (SMALL) (OCT 2020)
A. The Government may elect to contract its own telecommunications service in the Space.
B. The Lessor shall allow the Government’s designated telecommunications providers access to utilize existing Building wiring to connect its services to the Government’s Space, or, if existing Building wiring is insufficient, the Lessor shall provide access from the point of entry into the Building to the Government’s floor Space, subject to any inherent limitations in the pathway involved.
C. The Lessor shall allow the Government’s designated telecommunications providers to affix telecommunications antennas to roof, parapet, or
Building envelope (access from the antennas to the Premises shall be provided) and to affix transmission devices in appropriate common areas so as to allow the use of cellular telephones and other emerging technologies.
2.27 LIGHTING: INTERIOR AND PARKING – SHELL (SMALL) (OCT 2022)
Note. for pricing estimating purposes, fixtures will be installed at the average ratio of 1 fixture per 80 ABOA sf.
A. Interior Fixtures. Light fixtures (and associated ballasts or drivers) shall be installed to match the other luminaries in the Space as either ceiling grid or pendant mounted for an open-office plan. Ceiling grid fixtures shall be either 2’ wide by 4’ long or 2’ wide by 2’ long. Lessor shall provide, as part of Shell Rent, a minimum overall lighting fixture efficiency of 85 percent. Lamps shall maintain a uniform color level throughout the lease term.
B. Lighting Levels. Fixtures shall have a minimum of two tubes and shall provide 50 foot-candles at desktop level (30” above finished floor) with a maximum uniformity ratio of 1.5:1. Lessor shall provide, as part of Shell Rent, 10 average foot-candles in all other Building areas within the Premises with a uniformity ratio of 4:1. Emergency egress lighting levels shall be provided in accordance with the local applicable building codes (but not less than 1 foot-candle, measured at the floor) by either an onsite emergency generator or fixture mounted battery packs.
C. Power Density. The maximum fixture power density shall not exceed 1.4 watts per ABOA SF.
D. Building Perimeter. Exterior parking areas, vehicle driveways, pedestrian walks, and the Building perimeter lighting levels shall be designed per
Illuminating Engineering Society (IES) standards. Provide 5 foot-candles for doorway areas, 3 foot-candles for transition areas and at least 1 foot-candle at the surface throughout the parking lot. Parking lot fixtures shall provide a maximum to minimum uniformity ratio of 15:1 and a maximum to average uniformity ratio of 4:1.
E. Parking Structures. The minimum illuminance level for parking structures is 5 foot-candles as measured on the floor with a uniformity ratio of
10:1.
F. Exterior Power Backup. Exterior egress, walkway, parking lot, and parking structure lighting must have emergency power backup to provide for safe evacuation of the Building.
G. Video Surveillance System (VSS). Lighting shall be provided in such a manner to adequately support VSS operations, and not limit or preclude adequate fields of view.
2.28 INTENTIONALLY DELETED
2.29 INTENTIONALLY DELETED
LEASE NO. GS-09P-LNV03410, PAGE 9 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
SECTION 3 DESIGN, CONSTRUCTION, AND POST AWARD ACTIVITIES
3.01 INTENTIONALLY DELETED
3.02 ACCESS BY THE GOVERNMENT PRIOR TO ACCEPTANCE (SMALL) (OCT 2020)
Subject to the Lessor's permission, which shall not be unreasonably withheld, the Government or its contractors shall have access to the Premises prior to acceptance of the Space to prepare the Space for occupancy. If the work to be completed by the Government is a prerequisite for the issuance of a Certificate of Occupancy, or its equivalent, the Government shall be entitled to at least 10 Working Days to complete work by its own contractors.
3.03 ACCEPTANCE OF SPACE AND CERTIFICATE OF OCCUPANCY (SMALL) (OCT 2021)
A. The Government shall accept the Space only if the construction of Building shell and TIs, as applicable, conforming to this Lease and any layout drawings is substantially complete, as determined by the Lease Contracting Officer, and a Certificate of Occupancy (C of O) has been issued.
The Space shall be considered substantially complete only if the Space may be used for its intended purpose and completion of remaining work will not interfere unreasonably with the Government's enjoyment of the Space.
B. The Lessor shall provide a valid C of O, issued by the local jurisdiction, for the intended use of the Government. If the local jurisdiction does not issue C of O’s or if the C of O is not available, the Lessor may satisfy this condition by providing a report prepared by a licensed fire protection engineer that indicates the Space and Building are compliant with all applicable local codes and ordinances and all fire protection and life safety-related requirements of this Lease.
C. If applicable, upon acceptance of the Space, the Government will issue lump sum payment to the Lessor after substantial completion, in accordance with invoicing procedures outlined under any lease amendment(s) authorizing such lump sum payment. The Government shall not issue this payment in increments or as partial payments.
3.04 LEASE TERM COMMENCEMENT DATE AND RENT RECONCILIATION (SMALL) (OCT 2021)
The Lease Term Commencement Date, and final measurement verification of the Space, shall be memorialized by Lease Amendment.
3.05 INTENTIONALLY DELETED
3.06 SEISMIC RETROFIT (OCT 2020)
The following requirements apply to Leases requiring seismic retrofit:
A. The Lessor shall provide a final construction schedule, all final design and construction documents for the seismic retrofit, including structural calculations, drawings, and specifications to the Government for review and approval prior to the start of construction. When required by local building code, a geotechnical report shall be made available to the Government.
B. The Lessor’s registered civil or structural engineer shall perform special inspections to meet the requirements of Chapter 17 of the International
Building Code (IBC).
C. For Leases requiring seismic retrofit, the Space will not be considered substantially complete until a Seismic Form E - Certificate of Seismic
Compliance - Retrofitted Building, certifying that the Building meets the Basic Safety Objective of ASCE/SEI 41, executed by a registered civil or structural engineer, has been delivered to the LCO.
3.07 INTENTIONALLY DELETED
LEASE NO. GS-09P-LNV03410, PAGE 10 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
SECTION 4 TENANT IMPROVEMENT COMPONENTS
4.01 INTENTIONALLY DELETED
4.02 INTENTIONALLY DELETED
4.03 INTENTIONALLY DELETED
4.04 INTENTIONALLY DELETED
4.05 INTENTIONALLY DELETED
4.06 INTENTIONALLY DELETED
4.07 INTENTIONALLY DELETED
4.08 INTENTIONALLY DELETED
4.09 INTENTIONALLY DELETED
4.10 HEATING AND AIR CONDITIONING (SMALL) (OCT 2022) - MODIFIED
The Lessor shall ensure that individual thermostat controls for Space Areas that routinely have extended hours of operation are environmentally controlled through dedicated heating and air conditioning equipment. A supplemental HVAC unit is authorized depending on the climate and specific location. To be determined on case-by-case basis by tenant agency. Portable space heaters are prohibited.
4.11 ELECTRICAL: DISTRIBUTION (SMALL) (SEP 2015)
A. All electrical outlets shall be installed in accordance with NFPA Standard 70.
B. The Lessor shall in all cases safely conceal outlets and associated wiring (for electricity, voice, and data) to the workstation(s) in a method acceptable to the Government.
4.12 TELECOMMUNICATIONS: DISTRIBUTION AND EQUIPMENT (JUN 2012)
Telecommunications floor or wall outlets shall be provided as part of the TIs. At a minimum, each outlet shall house one 4-pair wire jack for voice and one 4-pair wire jack for data. The Lessor shall ensure that all outlets and associated wiring, copper, coaxial cable, optical fiber, or other transmission medium used to transmit telecommunications (voice, data, video, Internet, or other emerging technologies) service to the workstation shall be safely concealed under raised floors, in floor ducts, walls, columns, or molding. All outlets/junction boxes shall be provided with rings and pull strings to facilitate the installation of cable. Some transmission mediums may require special conduit, inner duct, or shielding as specified by the Government.
4.13 TELECOMMUNICATIONS: LOCAL EXCHANGE ACCESS (AUG 2008)
Provide sealed conduit to house the agency telecommunications system when required.
4.14 INTENTIONALLY DELETED
4.15 INTENTIONALLY DELETED
4.16 INTENTIONALLY DELETED
LEASE NO. GS-09P-LNV03410, PAGE 11 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
SECTION 5 UTILITIES, SERVICES, AND OBLIGATIONS DURING THE LEASE TERM
5.01 PROVISION OF SERVICES, ACCESS, AND NORMAL HOURS (SMALL) (OCT 2020)
The Government’s normal hours of operations are established as 12:00 AM to 12:00 AM (24/7), Monday through Friday, with the exception of Federal holidays. Services, maintenance, and utilities shall be provided during these hours. The Government shall have access to the Premises and its Appurtenant Areas at all times without additional payment, including the use, during other than normal hours, of necessary services and utilities such as elevators, restrooms, lights, and electric power. Cleaning shall be performed during normal hours.
5.02 UTILITIES (SMALL) (OCT 2022)
The Lessor is responsible for providing all utilities necessary for base Building and tenant operations as part of the rental consideration.
5.03 HEATING AND AIR CONDITIONING (SMALL) (OCT 2022) - MODIFIED
A. Warehouse or garage areas require heating and cooling. Temperature of warehouse or garage areas shall be maintained at a minimum of 50°
Fahrenheit and are not to exceed 85° Fahrenheit. An installed dual HVAC system supporting both heating and cooling is the preferred method of control. A supplemental HVAC unit is authorized depending on the climate and specific location. To be determined on case-by-case basis by tenant agency. Thermostats shall be secured from manual operation by key or locked cage. A key shall be provided to the Government’s designated representative.
B. The Lessor shall conduct HVAC system balancing after any HVAC system alterations during the term of the Lease and shall make a reasonable attempt to schedule major construction outside of office hours.
C. Normal HVAC systems’ maintenance shall not disrupt tenant operations.
F. INTENTIONALLY DELETED
G. INTENTIONALLY DELETED
H. The 24 hour, 365 days a year HVAC service(s) stated above shall be provided by the Lessor as part of the operating rent established under the
Lease.
5.04 INTENTIONALLY DELETED
5.05 INTENTIONALLY DELETED
5.06 MAINTENANCE OF PROVIDED FINISHES (SMALL) (SEP 2015)
A. Paint, wall coverings. Lessor shall maintain all wall coverings and high-performance paint coatings in “like new” condition for the life of the Lease.
All painted surfaces, shall be repainted at the Lessor's expense, including the moving and returning of furnishings, any time during the occupancy by the Government if the paint is peeling or permanently stained, except where damaged due to the negligence of the Government. All work shall be done after normal working hours as defined elsewhere in this Lease.
B. Carpet and flooring.
1. Except when damaged by the Government, the Lessor shall repair or replace flooring at any time during the Lease term when:
a. Backing or underlayment is exposed;
b. There are noticeable variations in surface color or texture;
c. It has curls, upturned edges, or other noticeable variations in texture;
d. Tiles are loose; or,
e. Tears or tripping hazards are present.
2. Repair or replacement shall include the moving and returning of furnishings, including disassembly and reassembly of systems furniture per manufacturer’s warranty, if necessary. Work shall be performed after normal hours.
5.07 IDENTITY VERIFICATION OF PERSONNEL (OCT 2022)
A. The Government reserves the right to verify identities of personnel with routine and/or unaccompanied access to the Government's Space, including both pre and post occupancy periods. The Lessor shall comply with GSA personal identity verification requirements, identified in the GSA Order 2181.1 GSA HSPD-12 Personal Identity Verification and Credentialing Handbook. The Lessor can find the policy and additional information at HTTP://WWW.GSA.GOV/HSPD12. This policy requires the Government to conduct background investigations and make HSPD- 12 compliant suitability determinations for all persons with routine or unaccompanied access to Government leased Space. By definition, this includes at a minimum each employee of the Lessor, as well as employees of the Lessor's contractors or subcontractors who will provide building operating services requiring routine access to the Government’s leased Space for a period greater than 6 months. The Government may also require this information for the Lessor's employees, contractors, or subcontractors who will be engaged to perform alterations or emergency repairs in the Government’s Space.
http://www.gsa.gov/hspd12
LEASE NO. GS-09P-LNV03410, PAGE 12 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
B. Application Process: The background investigation will be done using the Government's prescribed process. The Lessor must provide information on each of their contractor/personnel meeting the above criteria to the Government, whereupon each identified contractor/personnel will be notified with instructions for completing the identity verification application within a given time frame. The application process will include completing supplemental information forms that must be inputted into the identity verification system in order for the application to be considered complete. Additionally, the Lessor must ensure prompt completion of the fingerprint process for their contractor/personnel. Email notifications will be sent with instructions on the steps to be taken to schedule an appointment for fingerprinting at an approved regional location along with instructions on how to complete the background investigation application.
C. The Lessor must ensure the Lease Contracting Officer (or the Lease Contracting Officer's designated representative) has all of the requested documentation timely to ensure the completion of the investigation.
D. Based on the information furnished, the Government will conduct background investigations. The Lease Contracting Officer will advise the Lessor in writing if a person fails the investigation, and, effective immediately, that person will no longer be allowed to work or be assigned to work in the Government’s Space.
E. Throughout the life of the Lease, the Lessor shall provide the same data for any new employees, contractors, or subcontractors who will be assigned to the Government’s Space in accordance with the above criteria. All Lessor's contractor(s) and subcontractor(s) shall follow the requirements of background investigation in accordance with GSA HSPD-12 policy.
F. The Lessor is accountable for not allowing contractors to start work without the successful completion of the appropriate background investigation as required by GSA policy.
G. Access Card Retrieval/Return: Upon an Entry on Duty notification, the Government will issue a Personal Identity Verification (PIV) credential that is sometimes referred to as a GSA Access card. Lessors are responsible for all PIV credential issued to their contractors/personnel pursuant to this Lease. Lessors are specifically responsible for ensuring that all GSA PIV access cards are returned to the Lease Contracting Officer or their designee whenever their employees or a contractor no longer require access to the Space (such as when no longer needed for contract performance, upon completion of the Contractor employee’s employment, and upon contract completion or termination). Additionally, the Lessor must notify the Lease Contracting Officer or their designee whenever a GSA PIV Access card is lost or stolen in which event the Lessor may be responsible for reimbursing the Government for replacement credentials at the current cost per PIV HSPD12 credential. Unreturned PIV Access cards will be considered as lost or stolen cards.
H. The Government reserves the right to conduct additional background checks on Lessor personnel and contractors with routine access to
Government leased Space throughout the term of the Lease to determine who may have access to the Premises.
I. The Lease Contracting Officer may delay final payment under a contract if the Contractor fails to comply with these requirements.
J. The Lessor shall insert this paragraph in all subcontracts when the subcontractor is required to have physical access to a federally controlled facility or access to a federal information system.
5.08 INTENTIONALLY DELETED
5.09 INDOOR AIR QUALITY (OCT 2023)
A. The Lessor shall control airborne contaminants at the source and/or operate the Space in such a manner that indoor air quality action limits identified in the PBS Desk Guide for Indoor Air Quality Management (Companion to GSA Order PBS 1000.8), OSHA regulatory limits, and generally accepted consensus standards are not exceeded.
B. The Lessor shall avoid the use of products containing toxic, hazardous, carcinogenic, flammable, or corrosive ingredients as determined from the product label or manufacturer’s safety data sheet. The Lessor shall use available odor-free or low odor products when applying paints, glues, lubricants, and similar wet products. When such equivalent products are not available, lessor shall use the alternate products outside normal working hours. Except in an emergency, the Lessor shall provide at least 72 hours advance notice to the Government before applying chemicals or products with noticeable odors in occupied Spaces and shall adequately ventilate those Spaces during and after application.
C. The Lessor shall serve as first responder to any occupant complaints about indoor air quality (IAQ). The Lessor shall promptly investigate such complaints and implement the necessary controls to address each complaint. Investigations shall include testing as needed, to ascertain the source and severity of the complaint. The Lessor shall provide written results of any testing along with recommendations to GSA.
D. The Government reserves the right to conduct independent IAQ assessments and detailed studies in Space that it occupies, as well as in space serving the Space (e.g., common use areas, mechanical rooms, HVAC systems, etc.). The Lessor shall assist the Government in its assessments and detailed studies by:
1. Making available information on Building operations and Lessor activities;
2. Providing access to Space for assessment and testing, if required; and
3. Implementing corrective measures required by the LCO. The Lessor shall take corrective action to correct any tests or measurements that do not meet GSA policy action limits in the PBS Desk Guide for Indoor Air Quality Management (Companion to GSA Order PBS 1000.8), OSHA regulatory limits, and generally accepted consensus standards.
LEASE NO. GS-09P-LNV03410, PAGE 13 LESSOR: ________ GOVERNMENT: ________ SUPPLEMENTAL LEASE
E. The Lessor shall provide to the Government safety data sheets (SDS) upon request for the following products prior to their use during the term of the Lease: adhesives, caulking, sealants, insulating materials, fireproofing or firestopping materials, paints, carpets, floor, and wall patching or leveling materials, lubricants, clear finish for wood surfaces, janitorial cleaning products, pesticides, rodenticides, and herbicides. The Government reserves the right to review such products used by the Lessor within the Space, common building areas, ventilation systems and zones serving the Space, and the area above suspended ceilings and engineering space in the same ventilation zone as the Space.
D. The Lessor shall use high efficiency (HEPA) filtration vacuums for cleaning.
E. Air handling units shall have the highest-level MERV filtration that is compatible with the HVAC system and does not significantly diminish airflow.
Upon request, the Lessor shall provide to the Government a list of the highest-level of MERV filtration that each air handling unit is designed to handle.
H. The Lessor is encouraged to comply with best practices outlined in Appendix D- Indoor Air Quality in GSA Leased Facilities (Best Practices) within the PBS Desk Guide for Indoor Air Quality Management (Companion to GSA Order PBS 1000.8).
5.10 RADON IN AIR (OCT 2023)
A. The radon concentration in the air of the Space shall be less than 4 picoCuries per liter (pCi/L) for childcare and 25 pCi/L for all other space, herein called “GSA action levels.” For further information on radon, go to HTTP://WWW.EPA.GOV/RADON.
B. Testing Procedures. For the purposes of this paragraph, the following testing procedures shall be used when space planned for occupancy by the Government is located at or below grade level:
1. Standard Test. Place alpha track detectors throughout the required area for 91 or more days so that each covers no more than 2,000 ABOA SF. Use only devices and laboratories listed in the National Radon Proficiency Program (NRPP), National Radon Safety Board (NRSB) or as required by local jurisdictions that have a program for evaluating and approving devices. Submit the results and supporting data (sample location, device type, duration, radon measurements, laboratory proficiency certification number, and the signature of a responsible laboratory official) within 30 days after the measurement.
2. Short Test. Place alpha track detectors for at least 14 days, or charcoal canisters for 2 days to 3 days, throughout the required area so that each covers no more than 2,000 ABOA SF, starting not later than 7 days after award. Use only devices and laboratories listed in the National Radon Proficiency Program (NRPP), National Radon Safety Board (NRSB) or as required by local jurisdictions that have a program for evaluating and approving devices. Submit the results and supporting data within 30 days after the measurement. In addition, complete the standard test not later than 150 days after Government occupancy.
C. Initial Testing.
1. The Lessor shall:
a. Test for radon any portion of Space planned for occupancy by the Government at or below grade level;
b. Report the results to the LCO upon award; and
c. Promptly carry out a corrective action program for any radon concentration which equals or exceeds the GSA action levels.
2. Testing sequence. The Lessor shall measure radon by the standard test in sub-paragraph B.1, completing the test not later than 150 days after award, unless the LCO decides that there is not enough time to complete the test before Government occupancy, in which case the Lessor shall perform the short test in sub-paragraph B.2, in addition to the standard test.
3. If the Space offered for Lease to the Government is in a Building under construction or proposed for construction, the Lessor, if possible, shall perform the standard test during buildout before Government occupancy of the Space. If the LCO decides that it is not possible to complete the standard test before occupancy, the Lessor shall complete the short test before occupancy and the standard test not later than 150 days after occupancy.
D. Additional Testing.
1. After a major disturbance (e.g., earthquake, road construction, seismic shift, etc.) or a construction or renovation project that could impact radon gas levels in the building (e.g., building foundation, subsurface plumbing, basement structure, or negative changes to the building air pressure, etc.), the Lessor shall:
a. Re-Test for radon that portion of Space occupied by the Government at or below grade level;
b. Report the results to the LCO; and
c. Promptly carry out a corrective action program for any radon concentration which equals or exceeds the GSA action levels.
2. Testing Sequence. The Lessor shall measure radon by the standard test outlined in paragraph B.1, completing the test not later than
150 days after the event outlined in D.1.
E. Corrective Action Program.
http://www.epa.gov/RADON
LEASE…