ESBD_474639_1770847294374_Attachment A_Academic Building A - Revised Drawing.pdf
PDF 471 KB Posted
- Attached to
- Evins Generator Upgrade
- Solicitation number
- RFP64425091525
- Issued by
- Hidalgo County, Texas
About this file
This is a revised electrical drawing for Academic Building A at the Texas Juvenile Justice Department's Evins Regional Juvenile Center located at 3801 E. Monte Cristo Road, Edinburg, Texas 78541. The document outlines comprehensive electrical work including the installation of standby diesel generators, automatic transfer switches (ATS), generator docking stations, and associated electrical infrastructure to support emergency power capability for the facility. The project involves the installation of two generator systems: GEN-07 (150KW, 208Y/120V, 3-phase) and GEN-23 (200KW, 208Y/120V, 3-phase), each with corresponding docking stations and automatic transfer switches rated for 600A and 800A respectively. The contractor is responsible for verifying all existing conditions, relocating utilities as necessary, coordinating feeder routings with existing infrastructure, and installing all required conduit, cabling, and control systems in compliance with National Electrical Code (NEC) Section 110.26.A.1 and UL-142 standards. Additional work includes the furnishing and installation of new panel MDP-07, concrete pads, generator load banks, power quality meters, surge protection devices, GFCI receptacles, and weatherproof equipment housings.
The electrical specifications are detailed in comprehensive feeder schedules and one-line diagrams across multiple sheets, with conductor sizes ranging from #1 to 4/0 and conduit sizes from three-quarters inch to three and one-half inches. The project requires coordination with existing pad-mounted transformers (75 KVA and 300 KVA), existing panelboards (Panel J, Panel C, Panel K, and main service board), and utility infrastructure, with all work to be performed at no additional cost to the owner unless discrepancies between actual field conditions and the plans are identified and documented with the engineer. General notes specify that the contractor shall provide temporary portable construction fencing and sandbags, verify equipment installation locations for NEC compliance, adjust concrete pads to accommodate purchased electrical equipment, and conduct short circuit analysis, coordination studies, and arc flash analysis in accordance with OSHA and NFPA 70-E requirements upon project completion.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES:
A. REFER TO SHEET E001 FOR ELECTRICAL GENERAL
NOTES.
B. INFORMATION ON THIS SHEET HAS BEEN TAKEN FROM
RECORD DRAWINGS, SITE SURVEY AND NEW WORK
PROPOSED. CONTRACTOR SHALL FIELD VERIFY ALL
EXISTING CONDITIONS. UNDERGROUND OR ABOVE
GROUND UTILITIES, ELECTRICAL EQUIPMENT,
CONDUIT, CONDUCTORS OR DEVICES NOT SHOWN
THAT REQUIRE RELOCATION DUE TO NEW WORK
SHALL BE DONE BY THE CONTRACTOR. ALL FINDINGS
SHALL BE ADDED TO FINAL BID OR SHALL BE AT NO
ADDITIONAL COST TO OWNER. RELOCATE ANY
UTILITIES, CIRCUITS, EQUIPMENT OR DEVICES FOUND
THAT ARE NOT ON PLANS BEFORE COMMENCING
WORK AND REPORT THE DISCREPANCIES BETWEEN
ACTUAL CONDITIONS AND THESE PLANS TO THE
ENGINEER IMMEDIATELY.
C. THE CONTRACTOR IS FULLY RESPONSIBLE FOR
VERIFYING THE FEASIBILITY OF ALL WORK AS SHOWN
IN THE DRAWINGS. ANY DISCREPANCIES WILL BE
NOTIFIED TO THE ENGINEER PRIOR TO ANY WORK
BEING PREFORMED.
D. CONTRACTOR SHALL FIELD IDENTIFY EXISTING
SANITARY SEWER LINE AND MAKE FIELD
ADJUSTMENT OF THE GENERATOR TO AVOID
INSTALLATION CONFLICT.
E. CONTRACTOR TO ADD ALL REQUIRED 240V AND/OR
120V CIRCUITS FROM AN EXISTING 240/120V
PANELBOARD TO FEED ALL AUXILIARY GENSET LOADS
(E.G., CONTROL PANEL, BLOCK HEATER, ETC.) REFER
TO THE GENSET INSTALLATION MANUAL.
F. CONTRACTOR TO ADD ALL REQUIRED
COMMUNICATION CABLING (E.G., ANNUNUCIATOR,
ETC.) REFER TO THE GENSET INSTALLATION MANUAL.
G. CONTRACTOR SHALL INSTALL AUTOMATIC TRANSFER
SWITCH AND DOCKING STATION FRONT FACING TO
THE NEAREST ACCESSIBLE SIDEWALK, ROAD, OR
OPEN AREA IN COMPLIANCE WITH NEC WORKING
CLEARANCE REQUIREMENTS.
H. ELECTRICAL EQUIPMENT SHOWN HAS BEEN
DIMENSIONED AS PER MANUFACTURER BASIS OF
DESIGN. CONTRACTOR SHALL ADJUST EQUIPMENT
CONCRETE PADS AS PER PURCHASED ELECTRICAL
EQUIPMENT AT NO ADDITIONAL COST TO OWNER.
I. GENSET SHALL COMPLY WITH THE UL-142 STANDARD.
J. CONTRACTOR SHALL PROVIDE TEMPORARY
PORTABLE CONSTRUCTION FENCING, PADS, AND
SANDBAGS FOR ACTIVE WORKING AREAS.
K. CONTRACTOR SHALL FIELD VERIFY FINAL EQUIPMENT
INSTALLATION LOCATIONS COMPLY WITH WORKING
CLEARANCES AS PER NEC SECTION 110.26.A.1.
L. PROPOSED FEEDER ROUTINGS ARE DIAGRAMMATIC
IN NATURE AND DO NOT REFLECT ACTUAL FEEDER
ROUTING INSTALLATIONS. CONTRACTOR SHALL
COORDINATE FEEDER ROUTINGS WITH EXISTING
CONDITIONS PRIOR TO COMMENCING WORK.
KEY NOTES:
1. PROPOSED LOCATION OF NEW STANDBY GENERATOR
ON NEW GENERATOR PAD. REFER TO DETAIL 01 ON
SHEET E501 FOR GENERATOR PAD REQUIREMENTS.
2. PROPOSED ATS AND CONCRETE PAD LOCATION.
REFER TO ONE-LINE DIAGRAM FOR TRANSFER
SWITCH REQUIREMENTS. REFER TO DETAIL 05 ON
SHEET E502 FOR TRANSFER SWITCH PLACEMENT.
3. PROPOSED DOCKING STATION LOCATION. REFER TO
ONE-LINE DIAGRAM FOR DOCKING STATION
REQUIREMENTS.
4. CONTRACTOR SHALL FURNISH AND INSTALL A
WEATHER PROOF GFCI, WITH 2#12, #12G, 3/4" C TO
NEAREST AVAILABLE 20AMP, 120VAC CIRCUIT.
PROVIDE WITH 20AMP, 1 POLE BREAKER WITH
MATCHING PANELBOARD KAIC AS REQUIRED. MOUNT
GFCI ADJACENT TO AUTOMATIC TRANSFER SWITCH.
5. CONTRACTOR SHALL FURNISH AND INSTALL FEEDER
CONDUIT UNDERGROUND FROM ATS TO A
WALL-MOUNTED HINGED LOCKABLE COVER NEMA 3R
SQUARE 32-IN (MINIMUM) PULL BOX. REFER TO DETAIL
04 ON SHEET E403 FOR WALL PENETRATION DETAIL.
PROVIDE FIRE RATED SEALANT AND CONDUIT SLEEVE
WHEN PENETRATING THROUGH WALL. ROUTE
FEEDER ABOVE CEILING FROM PULL BOX TO NEW
PANEL 'MDP-07'.
6. CONTRACTOR SHALL FURNISH AND INSTALL FEEDER
CONDUIT UNDERGROUND FROM ATS TO A
WALL-MOUNTED HINGED LOCKABLE COVER NEMA 3R
SQUARE 32-IN (MINIMUM) PULL BOX. REFER TO DETAIL
04 ON SHEET E403 FOR WALL PENETRATION DETAIL.
PROVIDE FIRE RATED SEALANT AND CONDUIT SLEEVE
WHEN PENETRATING THROUGH WALL. ROUTE
FEEDER ABOVE CEILING FROM PULL BOX TO EXISTING
MSB.
7. CONTRACTOR SHALL FURNISH AND INSTALL A
CONCRETE PULL BOX TYPE "CHRISTI BR3048"
(30X48X24) WITH TRAFFIC RATED COVER.
8. CONTRACTOR SHALL FURNISH AND INSTALL 1"
CONDUIT AND CABLING AS REQUIRED BY
MANUFACTURER FOR START/STOP CIRCUIT.
9. CONTRACTOR SHALL FURNISH AND INSTALL 1"
CONDUIT 2 #8, #8G, FOR GENERATOR BLOCK HEATER
AND BATTERY CHARGER (LOAD CENTER).
10. CONTRACTOR SHALL FURNISH AND INSTALL NEW
PANEL 'MDP-07' IN NEMA 3R ENCLOSURE. FURNISH
AND INSTALL 'MDP-07' ON DOUBLE UNISTRUT
H-FRAME RACK ON CONCRETE PAD. REFER TO
ONE-LINE DIAGRAM ON SHEET E203 FOR PANEL
REQUIREMENTS.
X X
X X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
SECURITYACADEMIC A
EQUIPMENT YARD
MECHANICAL YARD
EX LP
MECHANICAL YARD
EQUIPMENT YARD
E103
LEGEND:
NEW EQUIPMENT & ABOVE CEILING
CONDUIT
EXISTING EQUIPMENT
UNDERGROUND FEEDER
CONCRETE PAD
GENERATOR YARD FENCING-REFER TO
DETAIL 01 & 02 ON SHEET E403
FEEDER TAG. REFER TO ONE-LINE
DIAGRAM
XX
XX-XXX
EXISTING TRANSFORMER
MECHANICAL RM
EXISTING MSB
EXISTING BTS
EXISTING PANEL 'EA'
J-BOX
J-B O
X
MDP7-100
UT23-100
ATS23-100
ATS23-100
EXISTING PANEL 'K'
EXISTING PANEL 'J'
MDP7-200
EXISTING PANEL 'C'
CONCRETE
HOUSEKEEPING PAD
X X
X X X X
X X
X X
X X
X X X X
X X X X
X X
X X
EXISTING PAD MOUNTED TRANSFORMER
GEN-07
GEN-23
MECHANICAL YARD
DS-07
DS-23
ATS-07
ATS-23
TO PANEL 'C' & 'J' IN ACADEMIC
A BUILDING, REFER TO 01/E103
FROM TRANSFORMER (IN
SECURITY EQUIPMENT YARD)
REFER TO 01/E103
G7-100 DS7-100
UT7-100
ATS7-100
G23-100
DS23-100
UT23-100
TO MSB IN SECURITY
BUILDING, REFER TO
01/E103
ATS23-100
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X X X X X X X X X X X
X
X
X
X
X X
X X
X X
X X
X X
X X
XXXXXXXXXXXX
EX LP
TO MSB IN SECURITY
BUILDING, REFER TO
01/E103
TO PANEL 'K' IN ACADEMIC
BUILDING, REFER TO
01/E103
8 9
PANEL
'MDP-07'
10 MDP7-100
MDP7-200
E103
ELECTRICAL POWER PLAN -
ACADEMIC A & SECURITY
MP, MH
GB
09/13/2024 54769.002
TE
X
A S
J U
V E
N
IL
E
JU
S
TI
C E
D E
P A
R
TM
E N
T E
V
IN
S R
E G
IO
N
A L
JU
V
E N
IL
E
C E
N
TE
R
E
. M O
N
TE
C R
IS
TO
R O
A D
, E D
IN
B
U R
G
TX
Sheet Number
Sheet Title
Checked By:
Drawn By:
Project No.:
Issued:
N o.
D at e D es cr ip tio n R ev is io n
Scale: AS NOTED
W E
S T
M
IL
IT
A
R Y
H W
Y
S U
IT
E
M C
A
LL
E N
, T E
X A
S
-7
TE
L.
(9
) 6
-0
/1 0/
A D
D E
N D
U M
01 ELECTRICAL POWER PLAN - ACADEMIC A & SECURITY
SCALE: 1/16" = 1'-0"
02 ELECTRICAL ENLARGED POWER PLAN - ACADEMIC A & SECURITY
SCALE: 1/8" = 1'-0"
02/10/2026
KEY NOTES: #
GENERAL NOTES:
EXISTING PAD-MOUNTED
TRANSFORMER
75 KVA
120/208Y
3PH, 4W
OH 12.47KV
3-PH, CIRCUIT
100 A 208Y/120V
3PH, 4W
EXISTING
PANEL 'J'
300A/3P
42KAIC
EXISTING
PANEL 'C'
225A BUS
800AF/
600AT
3P
LSI
ATS-07
600A, 208Y/120V, 3-PH, 4W, 42KAIC
SERVICE ENTRANCE RATED 100%
BYPASS ISOLATION
AUTOMATIC TRANSFER SWITCH
NEMA 3R
DS-07
600A, 208Y/120V, 3-PH, 4W, 42KAIC
PORTABLE GEN DOCKING STATION
BASIS OF DESIGN: TRYSTAR DBDS-5
NEMA 3R
DS7-100
G7-100
GEN-07
150KW
208Y/120V, 3-PH, 4W
DIESEL STANDBY GENERATOR
IN WEATHER PROOF SOUND
ATTENUATION ENCLOSURE
G~
KI
KI
TEMP GENSETLOAD BANK
600AT
600AF
600AT
3P
600AF
3P
600AF/
600AT
3P
#3/0G
M UTILITY METER
EXISTING PAD-MOUNTED
TRANSFORMER
300 KVA
208Y/120
3PH, 4W
OH 12.47KV
3-PH, CIRCUIT
EXISTING PANELBOARD 'MDP' 600A, 208Y/120V, 3PH, 4W
PNL
'LB'
PNL
'AC'
100A 3P
150A 3P
250A 3P
60A 3P
100A 3P
60A 3P
PNL
'LA'
PNL
'LC'
600A 3P
50 KAIC
800AF/
600AT
3P
LSI
ATS-09
800A, 208Y/120V, 3-PH, 4W, 65KAIC
SERVICE ENTRANCE RATED 100%
BYPASS ISOLATION
AUTOMATIC TRANSFER SWITCH
NEMA 3R
DS-09
800A, 208Y/120V, 3-PH, 4W, 65KAIC
PORTABLE GEN DOCKING STATION
BASIS OF DESIGN: TRYSTAR DBDS-5
NEMA 3R
DS9-100
G9-100
GEN-09
200KW
208Y/120V, 3-PH, 4W
DIESEL STANDBY GENERATOR
IN WEATHER PROOF SOUND
ATTENUATION ENCLOSURE
G~
KI
KI
TEMP GENSETLOAD BANK
600AT
800AF
600AT
3P
800AF
3P
800AF/
600AT
3P
#3/0G
N E
L
N E
L
CIRCUIT BREAKER
XX/XX INDICATES
(AMP RATING
/ # OF POLES)
CONTROL WIRING
EXISTING
SECONDARY
PANELBOARD
M
GENERATOR
DOCKING
STATION
G~
KI
KI
TEMP GENSETLOAD BANK
XXXA/3P
XXXA/3P
XX-YYYY
FEEDER (TAG)
PNL
'X'
ELECTRICAL LEGEND
TRANSFORMER
UTILITY
METER XX/XX
N E
L
SERVICE
DISCONNECT
FUSE
POWER
QUALITY
METER
SURGE
PROTECTION
DEVICESPDPQM
PNL
'K'
PNL
'C'
PNL
'J'
UT7-100
ATS7-100
UT9-100
ATS9-100
LEGEND:
EXISTING EQUIPMENT
NEW CONDUIT AND CABLING
NEW EQUIPMENT
A. REFER TO SHEET E001 FOR GENERAL ELECTRICAL
NOTES.
B. 120VAC AREA LIGHTING AND GFCI RECEPTACLES ARE
NOT SHOWN IN THIS DIAGRAM.
C. CONTRACTOR SHALL VERIFY ANY REQUIREMENTS
FROM POWER UTILITY AND NOTIFY OWNER.
D. EXISTING SECONDARY FEEDERS, SECONDARY PANEL
AND LOADS ARE NOT SHOWN IN THIS DIAGRAM.
E. A SHORT CIRCUIT ANALYSIS, A COORDINATION
STUDY, AND AN ARC FLASH ANALYSIS ON THE NEW
ELECTRICAL SYSTEM SHALL BE CONDUCTED, AS PER
OSHA AND NFPA 70-E REQUIREMENTS.
F. CONTRACTOR SHALL VERIFY ANY CODE OF
LOCATION REQUIREMENTS THAT APPLY ON EXISTING
EQUIPMENT, AND NOTIFY OWNER.
G. GENERATOR SET SHALL BE FURNISHED WITH
AUXILIARY LOADS INTEGRAL ELECTRICAL LOAD
CENTER.
NEW PANEL "MDP-07" 600A, 208Y/120V, 3PH, 4W, NEMA 3R, 42KAIC
3P 225A
3P 300A
7 6 7 6
5 5
30A 2P
SPARE SPARE
DIESEL
STANDBY
GENERATOR
AUTOMATIC
TRANSFER
SWITCH
#3/0G #3/0G
1. CONTRACTOR SHALL RE-CIRCUIT EXISTING
EQUIPMENT AS INDICATED.
2. CONTRACTOR SHALL FURNISH AND INSTALL NEW
30A/2P BREAKER FOR GENSET LOAD CENTER.
BREAKER SHALL MATCH OR EXCEED EXISTING
PANEL KAIC RATING. ANY DISCREPANCIES SHALL BE
NOTIFIED TO ENGINEER.
3. CONTRACTOR SHALL FURNISH AND INSTALL A
SURGE PROTECTION DEVICE (SPD) TYPE EATON,
TYPE 1, 100KA, 3-PHASE, NEMA 3R OR EQUAL.
4. THE NEW ATS SHALL HAVE A POWER QUALITY
METER. TYPE: ALLEN BRADLEY 500 SERIES, MODEL
M6 OF EQUAL FEATURES (PQM).
5. CONTRACTOR SHALL FURNISH AND INSTALL 1"
CONDUIT AND CABLING AS REQUIRED BY
MANUFACTURER FOR START/STOP CIRCUIT.
6. CONTRACTOR SHALL FURNISH AND INSTALL 1-1/2"
CONDUIT AND CABLING FOR ANNUNCIATOR AS PER
MANUFACTURER INSTALLATION REQUIREMENTS.
COORDINATE FINAL ANNUNCIATOR LOCATION WITH
OWNER.
7. CONTRACTOR SHALL FURNISH AND INSTALL A 1"
CONDUIT WITH 2#8, #8G, FOR GENERATOR BLOCK
HEATER AND BATTERY CHARGER (LOAD CENTER).
M UTILITY METER
MDP7-100 MDP7-200
E203
ELECTRICAL PROPOSED ONE-LINE
DIAGRAM - ACADEMIC A &
ACADEMIC B
MP, MH
GB
09/13/2024 54769.002
TE
X
A S
J U
V E
N
IL
E
JU
S
TI
C E
D E
P A
R
TM
E N
T E
V
IN
S R
E G
IO
N
A L
JU
V
E N
IL
E
C E
N
TE
R
E
. M O
N
TE
C R
IS
TO
R O
A D
, E D
IN
B
U R
G
TX
Sheet Number
Sheet Title
Checked By:
Drawn By:
Project No.:
Issued:
N o.
D at e D es cr ip tio n R ev is io n
Scale: AS NOTED
W E
S T
M
IL
IT
A
R Y
H W
Y
S U
IT
E
M C
A
LL
E N
, T E
X A
S
-7
TE
L.
(9
) 6
-0
/1 0/
A D
D E
N D
U M
N.T.S.01
PROPOSED ELECTRICAL ONE-LINE DIAGRAM -
ACADEMIC A
N.T.S.02
PROPOSED ELECTRICAL ONE-LINE DIAGRAM -
ACADEMIC B
E301
ELECTRICAL FEEDER SCHEDULES
MP, MH
GB
09/13/2024 54769.002
TE
X
A S
J U
V E
N
IL
E
JU
S
TI
C E
D E
P A
R
TM
E N
T E
V
IN
S R
E G
IO
N
A L
JU
V
E N
IL
E
C E
N
TE
R
E
. M O
N
TE
C R
IS
TO
R O
A D
, E D
IN
B
U R
G
TX
Sheet Number
Sheet Title
Checked By:
Drawn By:
Project No.:
Issued:
N o.
D at e D es cr ip tio n R ev is io n
Scale: AS NOTED
W E
S T
M
IL
IT
A
R Y
H W
Y
S U
IT
E
M C
A
LL
E N
, T E
X A
S
-7
TE
L.
(9
) 6
-0
/1 0/
A D
D E
N D
U M
POWER FEEDER SCHEDULE
NO.
S E
TS CONDUCTORS SIZE FROM TO REMARKS
G 1-100 2
PH: 350
3 1/2'' GEN-01 PORTABLE GEN DOCKING
STATION DS-01N: 350
G: 1
DS 1-100 2
PH: 350
3 1/2'' PORTABLE GEN DOCKING
STATION DS-01 ATS-01N: 350
G: 1
UT 1-100 2
PH: 350
3 1/2'' EXISTING PAD MOUNTED ATS-01N: 350
G: 1
ATS 1-100 2
PH: 350
3 1/2'' ATS-01 NEMA 1 SERVICE
DISCONNECTN: 350
G: 1
G 3-100 4
PH: 350
3 1/2'' GEN-03 PORTABLE GEN DOCKING
STATION DS-03N: 350
G: 3/0
DS 3-100 4
PH: 350
3 1/2'' PORTABLE GEN DOCKING
STATION DS-03 ATS-03N: 350
G: 3/0
UT 3-100 4
PH: 350
3 1/2'' EXISTING PAD MOUNTED ATS-03N: 350
G: 3/0
ATS 3-100 4
PH: 350
3 1/2'' ATS-03 EXISTING MDPN: 350
G: 3/0
MDP 3-100 2
PH: 4/0
2 1/2'' EXISTING MDP PNL 'K'N: 4/0
G: 3
G 5-100 1
PH: 300
3'' GEN-05 PORTABLE GEN DOCKING
STATION DS-05
N: 300 G: 4
DS 5-100 1
PH: 300
3'' PORTABLE GEN DOCKING
STATION DS-05 ATS-05N: 300
G: 4
UT 5-100 1
PH: 300
3'' EXISTING PAD MOUNTED ATS-05N: 300
G: 4
ATS 5-100 1
PH: 300
3'' ATS-05 EXISTING PANEL 'C'N: 300
G: 4
PC 5-100 1
PH: 2/0
2" EXISTING PANEL 'C' EXISTING PANEL 'A'N: 2/0
G: 6
G 7-100 2
PH: 350
4'' GEN-07 PORTABLE GEN DOCKING
STATION DS-07N: 350
G: 1
DS 7-100 2
PH: 350
4'' PORTABLE GEN DOCKING
STATION DS-07 ATS-07N: 350
G: 1
UT 7-100 2
PH: 350
4'' EXISTING PAD MOUNTED ATS-07N: 350
G: 1
ATS 7-100 2
PH: 350
4'' ATS-07 NEW WIREWAY NEMA 3RN: 350
G: 1
MDP 7-100 1
PH: 4/0
2-1/2" MDP-07 PANEL 'C'N: 4/0
G: 4
MDP 7-200 1
PH: 350
3-1/2" MDP-07 PANEL 'J'N: 350
G: 4
G 9-100 3
PH: 300
3'' GEN-09 PORTABLE GEN DOCKING
STATION DS-09N: 300
G: 1/0
DS 9-100 3
PH: 300
3'' PORTABLE GEN DOCKING
STATION DS-09 ATS-09N: 300
G: 1/0
UT 9-100 3
PH: 300
3'' EXISTING PAD MOUNTED ATS-09N: 300
G: 1/0
ATS 9-100 3
PH: 300
3'' ATS-09 EXISTING PANEL 'MDP'N: 300
G: 1/0
G 11-100 5
PH: 400
3-1/2'' GEN -11 PORTABLE GEN DOCKING
STATION DS-11N: 400
G: 4/0
DS 11-100 5
PH: 400
3-1/2'' PORTRABLE GEN DOCKING
STATION DS-11 ATS-11N: 400
G: 4/0
UT 11-100 5
PH: 400
3-1/2'' EXISTING PAD MOUNTED ATS-11N: 400
G: 4/0
ATS 11-100 5
PH: 400
3-1/2'' ATS-11 MCB-2 SERVICE
DISCONNECTN: 400
G: 4/0
PE 11-100 1
PH: 4/0
2-1/2'' PNL 'E' EXISTING WIREWAYN: 4/0
G: 6
POWER FEEDER SCHEDULE
NO.
S E
TS CONDUCTORS SIZE FROM TO REMARKS
G 13-100 5
PH: 400
3-1/2'' GEN-13 PORTABLE GEN DOCKING
STATION DS-13N: 400
G: 4/0
DS 13-100 5
PH: 400
3-1/2'' PORTABLE GEN DOCKING
STATION DS-13 ATS-13N: 400
G: 4/0
UT 13-100 5
PH: 400
3-1/2'' EXISTING PAD MOUNTED ATS-13N: 400
G: 4/0
ATS 13-100 5
PH: 400
3-1/2'' ATS-13 MCB-2 SERVICE
DISCONNECTN: 400
G: 4/0
PE 13-100 1
PH: 4/0
2-1/2'' PNL 'E' EXISTING WIREWAYN: 4/0
G: 6
G 15-100 4
PH: 350
3-1/2'' GEN-15 PORTABLE GEN DOCKING
STATION DS-15N: 350
G: 3/0
DS 15-100 4
PH: 350
3-1/2'' PORTABLE GEN DOCKING
STATION DS-15
EMERGENCY POWER
SWITCHBOARD EPS-15N: 350
G: 3/0
UT 15-100 4
PH: 350
3-1/2'' EXISTING PAD MOUNTED ATS-15N: 350
G: 3/0
ATS 15-100 4
PH: 350
3-1/2'' ATS-15 EXISTING PANELN: 350
G: 3/0
EP 15-100 1
PH: 250
3'' EXISTING PANEL PNL 'A'N: 250
G: 4
G 17-100 4
PH: 350
3-1/2'' GEN-17 PORTABLE GEN DOCKING
STATION DS-17N: 350
G: 3/0
DS 17-100 4
PH: 350
3-1/2'' PORTABLE GEN DOCKING
STATION DS-17
EMERGENCY POWER
SWITCHBOARD EPS-17N: 350
G: 3/0
UT 17-100 4
PH: 350
3-1/2'' EXISTING PAD MOUNTED ATS-17N: 350
G: 3/0
ATS 17-100 4
PH: 350
3-1/2'' ATS-17 EXISTING PANELN: 350
G: 3/0
EP 17-100 1
PH: 250
3'' EXISTING PANEL PNL 'A'N: 250
G: 4
POWER FEEDER SCHEDULE
NO.
S E
TS CONDUCTORS SIZE FROM TO REMARKS
G 19-100 2
PH: 350
3-1/2'' GEN-19 PORTABLE DOCKING
STATION DS-19N: 350
G: 1
DS 19-100 2
PH: 350
3-1/2'' PORTABLE GEN DOCKING
STATION DS-19 ATS-19N: 350
G: 1
UT 19-100 2
PH: 350
3-1/2'' EXISTING PAD MOUNTED ATS-19N: 350
G: 1
ATS 19-100 2
PH: 350
3-1/2'' ATS-19 PNL 'A'N: 350
G: 1
G 21-100 2
PH: 350
3-1/2'' GEN-21 PORTABLE GEN DOCKING
STATION DS-21N: 350
G: 1
DS 21-100 2
PH: 350
3-1/2'' PORTABLE GEN DOCKING
STATION DS-21 ATS-21N: 350
G: 1
UT 21-100 2
PH: 350
3-1/2'' EXISTING PAD MOUNTED ATS-21N: 350
G: 1
ATS 21-100 2
PH: 350
3-1/2'' ATS-21 EXISTING PANEL DPN: 350
G: 1
PN 21-100 1
PH: 1
1-1/2'' PNL 'N' PNLN: 1
G: 8
G 23-100 3
PH: 400
3-1/2'' GEN-23 PORTABLE GEN DOCKING
STATION DS-23N: 400
G: 2/0
DS 23-100 3
PH: 400
3-1/2'' PORTABLE GEN DOCKING
STATION DS-23 ATS-23N: 400
G: 2/0
UT 23-100 3
PH: 400
3-1/2'' EXISTING PAD MOUNTED ATS-23N: 400
G: 2/0
ATS 23-100 3
PH: 400
3-1/2'' ATS-23 EXISTING PANEL 'MSB'N: 400
G: 2/0
MSB 23-100 1
PH: 2/0
2'' EXISTING PANEL 'MSB' PNL 'EA'N: 2/0
G: 6
GENERAL NOTES:
| Sheets and Views |
| E103 ELECTRICAL POWER PLAN - ACADEMIC A & SECURITY |
| ELECTRICAL POWER PLAN - ACADEMIC A |
| ELECTRICAL POWER PLAN - ACADEMIC A ENLARGEMENT DETAIL |
| E203 ELECTRICAL PROPOSED ONE-LINE DIAGRAM - ACADEMIC A & ACADEMIC B |
| PROPOSED ELECTRICAL ONE-LINE DIAGRAM III - ACADEMIC A & B |
E301 ELECTRICAL FEEDER SCHEDULES