ESBD_474639_1770847294374_Attachment A_Academic Building A - Revised Drawing.pdf

PDF 471 KB Posted

Attached to
Evins Generator Upgrade
Solicitation number
RFP64425091525
Issued by
Hidalgo County, Texas

About this file

This is a revised electrical drawing for Academic Building A at the Texas Juvenile Justice Department's Evins Regional Juvenile Center located at 3801 E. Monte Cristo Road, Edinburg, Texas 78541. The document outlines comprehensive electrical work including the installation of standby diesel generators, automatic transfer switches (ATS), generator docking stations, and associated electrical infrastructure to support emergency power capability for the facility. The project involves the installation of two generator systems: GEN-07 (150KW, 208Y/120V, 3-phase) and GEN-23 (200KW, 208Y/120V, 3-phase), each with corresponding docking stations and automatic transfer switches rated for 600A and 800A respectively. The contractor is responsible for verifying all existing conditions, relocating utilities as necessary, coordinating feeder routings with existing infrastructure, and installing all required conduit, cabling, and control systems in compliance with National Electrical Code (NEC) Section 110.26.A.1 and UL-142 standards. Additional work includes the furnishing and installation of new panel MDP-07, concrete pads, generator load banks, power quality meters, surge protection devices, GFCI receptacles, and weatherproof equipment housings.

The electrical specifications are detailed in comprehensive feeder schedules and one-line diagrams across multiple sheets, with conductor sizes ranging from #1 to 4/0 and conduit sizes from three-quarters inch to three and one-half inches. The project requires coordination with existing pad-mounted transformers (75 KVA and 300 KVA), existing panelboards (Panel J, Panel C, Panel K, and main service board), and utility infrastructure, with all work to be performed at no additional cost to the owner unless discrepancies between actual field conditions and the plans are identified and documented with the engineer. General notes specify that the contractor shall provide temporary portable construction fencing and sandbags, verify equipment installation locations for NEC compliance, adjust concrete pads to accommodate purchased electrical equipment, and conduct short circuit analysis, coordination studies, and arc flash analysis in accordance with OSHA and NFPA 70-E requirements upon project completion.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES:

A. REFER TO SHEET E001 FOR ELECTRICAL GENERAL

NOTES.

B. INFORMATION ON THIS SHEET HAS BEEN TAKEN FROM

RECORD DRAWINGS, SITE SURVEY AND NEW WORK

PROPOSED. CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS. UNDERGROUND OR ABOVE

GROUND UTILITIES, ELECTRICAL EQUIPMENT,

CONDUIT, CONDUCTORS OR DEVICES NOT SHOWN

THAT REQUIRE RELOCATION DUE TO NEW WORK

SHALL BE DONE BY THE CONTRACTOR. ALL FINDINGS

SHALL BE ADDED TO FINAL BID OR SHALL BE AT NO

ADDITIONAL COST TO OWNER. RELOCATE ANY

UTILITIES, CIRCUITS, EQUIPMENT OR DEVICES FOUND

THAT ARE NOT ON PLANS BEFORE COMMENCING

WORK AND REPORT THE DISCREPANCIES BETWEEN

ACTUAL CONDITIONS AND THESE PLANS TO THE

ENGINEER IMMEDIATELY.

C. THE CONTRACTOR IS FULLY RESPONSIBLE FOR

VERIFYING THE FEASIBILITY OF ALL WORK AS SHOWN

IN THE DRAWINGS. ANY DISCREPANCIES WILL BE

NOTIFIED TO THE ENGINEER PRIOR TO ANY WORK

BEING PREFORMED.

D. CONTRACTOR SHALL FIELD IDENTIFY EXISTING

SANITARY SEWER LINE AND MAKE FIELD

ADJUSTMENT OF THE GENERATOR TO AVOID

INSTALLATION CONFLICT.

E. CONTRACTOR TO ADD ALL REQUIRED 240V AND/OR

120V CIRCUITS FROM AN EXISTING 240/120V

PANELBOARD TO FEED ALL AUXILIARY GENSET LOADS

(E.G., CONTROL PANEL, BLOCK HEATER, ETC.) REFER

TO THE GENSET INSTALLATION MANUAL.

F. CONTRACTOR TO ADD ALL REQUIRED

COMMUNICATION CABLING (E.G., ANNUNUCIATOR,

ETC.) REFER TO THE GENSET INSTALLATION MANUAL.

G. CONTRACTOR SHALL INSTALL AUTOMATIC TRANSFER

SWITCH AND DOCKING STATION FRONT FACING TO

THE NEAREST ACCESSIBLE SIDEWALK, ROAD, OR

OPEN AREA IN COMPLIANCE WITH NEC WORKING

CLEARANCE REQUIREMENTS.

H. ELECTRICAL EQUIPMENT SHOWN HAS BEEN

DIMENSIONED AS PER MANUFACTURER BASIS OF

DESIGN. CONTRACTOR SHALL ADJUST EQUIPMENT

CONCRETE PADS AS PER PURCHASED ELECTRICAL

EQUIPMENT AT NO ADDITIONAL COST TO OWNER.

I. GENSET SHALL COMPLY WITH THE UL-142 STANDARD.

J. CONTRACTOR SHALL PROVIDE TEMPORARY

PORTABLE CONSTRUCTION FENCING, PADS, AND

SANDBAGS FOR ACTIVE WORKING AREAS.

K. CONTRACTOR SHALL FIELD VERIFY FINAL EQUIPMENT

INSTALLATION LOCATIONS COMPLY WITH WORKING

CLEARANCES AS PER NEC SECTION 110.26.A.1.

L. PROPOSED FEEDER ROUTINGS ARE DIAGRAMMATIC

IN NATURE AND DO NOT REFLECT ACTUAL FEEDER

ROUTING INSTALLATIONS. CONTRACTOR SHALL

COORDINATE FEEDER ROUTINGS WITH EXISTING

CONDITIONS PRIOR TO COMMENCING WORK.

KEY NOTES:

1. PROPOSED LOCATION OF NEW STANDBY GENERATOR

ON NEW GENERATOR PAD. REFER TO DETAIL 01 ON

SHEET E501 FOR GENERATOR PAD REQUIREMENTS.

2. PROPOSED ATS AND CONCRETE PAD LOCATION.

REFER TO ONE-LINE DIAGRAM FOR TRANSFER

SWITCH REQUIREMENTS. REFER TO DETAIL 05 ON

SHEET E502 FOR TRANSFER SWITCH PLACEMENT.

3. PROPOSED DOCKING STATION LOCATION. REFER TO

ONE-LINE DIAGRAM FOR DOCKING STATION

REQUIREMENTS.

4. CONTRACTOR SHALL FURNISH AND INSTALL A

WEATHER PROOF GFCI, WITH 2#12, #12G, 3/4" C TO

NEAREST AVAILABLE 20AMP, 120VAC CIRCUIT.

PROVIDE WITH 20AMP, 1 POLE BREAKER WITH

MATCHING PANELBOARD KAIC AS REQUIRED. MOUNT

GFCI ADJACENT TO AUTOMATIC TRANSFER SWITCH.

5. CONTRACTOR SHALL FURNISH AND INSTALL FEEDER

CONDUIT UNDERGROUND FROM ATS TO A

WALL-MOUNTED HINGED LOCKABLE COVER NEMA 3R

SQUARE 32-IN (MINIMUM) PULL BOX. REFER TO DETAIL

04 ON SHEET E403 FOR WALL PENETRATION DETAIL.

PROVIDE FIRE RATED SEALANT AND CONDUIT SLEEVE

WHEN PENETRATING THROUGH WALL. ROUTE

FEEDER ABOVE CEILING FROM PULL BOX TO NEW

PANEL 'MDP-07'.

6. CONTRACTOR SHALL FURNISH AND INSTALL FEEDER

CONDUIT UNDERGROUND FROM ATS TO A

WALL-MOUNTED HINGED LOCKABLE COVER NEMA 3R

SQUARE 32-IN (MINIMUM) PULL BOX. REFER TO DETAIL

04 ON SHEET E403 FOR WALL PENETRATION DETAIL.

PROVIDE FIRE RATED SEALANT AND CONDUIT SLEEVE

WHEN PENETRATING THROUGH WALL. ROUTE

FEEDER ABOVE CEILING FROM PULL BOX TO EXISTING

MSB.

7. CONTRACTOR SHALL FURNISH AND INSTALL A

CONCRETE PULL BOX TYPE "CHRISTI BR3048"

(30X48X24) WITH TRAFFIC RATED COVER.

8. CONTRACTOR SHALL FURNISH AND INSTALL 1"

CONDUIT AND CABLING AS REQUIRED BY

MANUFACTURER FOR START/STOP CIRCUIT.

9. CONTRACTOR SHALL FURNISH AND INSTALL 1"

CONDUIT 2 #8, #8G, FOR GENERATOR BLOCK HEATER

AND BATTERY CHARGER (LOAD CENTER).

10. CONTRACTOR SHALL FURNISH AND INSTALL NEW

PANEL 'MDP-07' IN NEMA 3R ENCLOSURE. FURNISH

AND INSTALL 'MDP-07' ON DOUBLE UNISTRUT

H-FRAME RACK ON CONCRETE PAD. REFER TO

ONE-LINE DIAGRAM ON SHEET E203 FOR PANEL

REQUIREMENTS.

X X

X X

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X

SECURITYACADEMIC A

EQUIPMENT YARD

MECHANICAL YARD

EX LP

MECHANICAL YARD

EQUIPMENT YARD

E103

LEGEND:

NEW EQUIPMENT & ABOVE CEILING

CONDUIT

EXISTING EQUIPMENT

UNDERGROUND FEEDER

CONCRETE PAD

GENERATOR YARD FENCING-REFER TO

DETAIL 01 & 02 ON SHEET E403

FEEDER TAG. REFER TO ONE-LINE

DIAGRAM

XX

XX-XXX

EXISTING TRANSFORMER

MECHANICAL RM

EXISTING MSB

EXISTING BTS

EXISTING PANEL 'EA'

J-BOX

J-B O

X

MDP7-100

UT23-100

ATS23-100

ATS23-100

EXISTING PANEL 'K'

EXISTING PANEL 'J'

MDP7-200

EXISTING PANEL 'C'

CONCRETE

HOUSEKEEPING PAD

X X

X X X X

X X

X X

X X

X X X X

X X X X

X X

X X

EXISTING PAD MOUNTED TRANSFORMER

GEN-07

GEN-23

MECHANICAL YARD

DS-07

DS-23

ATS-07

ATS-23

TO PANEL 'C' & 'J' IN ACADEMIC

A BUILDING, REFER TO 01/E103

FROM TRANSFORMER (IN

SECURITY EQUIPMENT YARD)

REFER TO 01/E103

G7-100 DS7-100

UT7-100

ATS7-100

G23-100

DS23-100

UT23-100

TO MSB IN SECURITY

BUILDING, REFER TO

01/E103

ATS23-100

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X X X X X X X X X X X

X

X

X

X

X X

X X

X X

X X

X X

X X

XXXXXXXXXXXX

EX LP

TO MSB IN SECURITY

BUILDING, REFER TO

01/E103

TO PANEL 'K' IN ACADEMIC

BUILDING, REFER TO

01/E103

8 9

PANEL

'MDP-07'

10 MDP7-100

MDP7-200

E103

ELECTRICAL POWER PLAN -

ACADEMIC A & SECURITY

MP, MH

GB

09/13/2024 54769.002

TE

X

A S

J U

V E

N

IL

E

JU

S

TI

C E

D E

P A

R

TM

E N

T E

V

IN

S R

E G

IO

N

A L

JU

V

E N

IL

E

C E

N

TE

R

E

. M O

N

TE

C R

IS

TO

R O

A D

, E D

IN

B

U R

G

TX

Sheet Number

Sheet Title

Checked By:

Drawn By:

Project No.:

Issued:

N o.

D at e D es cr ip tio n R ev is io n

Scale: AS NOTED

W E

S T

M

IL

IT

A

R Y

H W

Y

S U

IT

E

M C

A

LL

E N

, T E

X A

S

-7

TE

L.

(9

) 6

-0

/1 0/

A D

D E

N D

U M

01 ELECTRICAL POWER PLAN - ACADEMIC A & SECURITY

SCALE: 1/16" = 1'-0"

02 ELECTRICAL ENLARGED POWER PLAN - ACADEMIC A & SECURITY

SCALE: 1/8" = 1'-0"

02/10/2026

KEY NOTES: #

GENERAL NOTES:

EXISTING PAD-MOUNTED

TRANSFORMER

75 KVA

120/208Y

3PH, 4W

OH 12.47KV

3-PH, CIRCUIT

100 A 208Y/120V

3PH, 4W

EXISTING

PANEL 'J'

300A/3P

42KAIC

EXISTING

PANEL 'C'

225A BUS

800AF/

600AT

3P

LSI

ATS-07

600A, 208Y/120V, 3-PH, 4W, 42KAIC

SERVICE ENTRANCE RATED 100%

BYPASS ISOLATION

AUTOMATIC TRANSFER SWITCH

NEMA 3R

DS-07

600A, 208Y/120V, 3-PH, 4W, 42KAIC

PORTABLE GEN DOCKING STATION

BASIS OF DESIGN: TRYSTAR DBDS-5

NEMA 3R

DS7-100

G7-100

GEN-07

150KW

208Y/120V, 3-PH, 4W

DIESEL STANDBY GENERATOR

IN WEATHER PROOF SOUND

ATTENUATION ENCLOSURE

G~

KI

KI

TEMP GENSETLOAD BANK

600AT

600AF

600AT

3P

600AF

3P

600AF/

600AT

3P

#3/0G

M UTILITY METER

EXISTING PAD-MOUNTED

TRANSFORMER

300 KVA

208Y/120

3PH, 4W

OH 12.47KV

3-PH, CIRCUIT

EXISTING PANELBOARD 'MDP' 600A, 208Y/120V, 3PH, 4W

PNL

'LB'

PNL

'AC'

100A 3P

150A 3P

250A 3P

60A 3P

100A 3P

60A 3P

PNL

'LA'

PNL

'LC'

600A 3P

50 KAIC

800AF/

600AT

3P

LSI

ATS-09

800A, 208Y/120V, 3-PH, 4W, 65KAIC

SERVICE ENTRANCE RATED 100%

BYPASS ISOLATION

AUTOMATIC TRANSFER SWITCH

NEMA 3R

DS-09

800A, 208Y/120V, 3-PH, 4W, 65KAIC

PORTABLE GEN DOCKING STATION

BASIS OF DESIGN: TRYSTAR DBDS-5

NEMA 3R

DS9-100

G9-100

GEN-09

200KW

208Y/120V, 3-PH, 4W

DIESEL STANDBY GENERATOR

IN WEATHER PROOF SOUND

ATTENUATION ENCLOSURE

G~

KI

KI

TEMP GENSETLOAD BANK

600AT

800AF

600AT

3P

800AF

3P

800AF/

600AT

3P

#3/0G

N E

L

N E

L

CIRCUIT BREAKER

XX/XX INDICATES

(AMP RATING

/ # OF POLES)

CONTROL WIRING

EXISTING

SECONDARY

PANELBOARD

M

GENERATOR

DOCKING

STATION

G~

KI

KI

TEMP GENSETLOAD BANK

XXXA/3P

XXXA/3P

XX-YYYY

FEEDER (TAG)

PNL

'X'

ELECTRICAL LEGEND

TRANSFORMER

UTILITY

METER XX/XX

N E

L

SERVICE

DISCONNECT

FUSE

POWER

QUALITY

METER

SURGE

PROTECTION

DEVICESPDPQM

PNL

'K'

PNL

'C'

PNL

'J'

UT7-100

ATS7-100

UT9-100

ATS9-100

LEGEND:

EXISTING EQUIPMENT

NEW CONDUIT AND CABLING

NEW EQUIPMENT

A. REFER TO SHEET E001 FOR GENERAL ELECTRICAL

NOTES.

B. 120VAC AREA LIGHTING AND GFCI RECEPTACLES ARE

NOT SHOWN IN THIS DIAGRAM.

C. CONTRACTOR SHALL VERIFY ANY REQUIREMENTS

FROM POWER UTILITY AND NOTIFY OWNER.

D. EXISTING SECONDARY FEEDERS, SECONDARY PANEL

AND LOADS ARE NOT SHOWN IN THIS DIAGRAM.

E. A SHORT CIRCUIT ANALYSIS, A COORDINATION

STUDY, AND AN ARC FLASH ANALYSIS ON THE NEW

ELECTRICAL SYSTEM SHALL BE CONDUCTED, AS PER

OSHA AND NFPA 70-E REQUIREMENTS.

F. CONTRACTOR SHALL VERIFY ANY CODE OF

LOCATION REQUIREMENTS THAT APPLY ON EXISTING

EQUIPMENT, AND NOTIFY OWNER.

G. GENERATOR SET SHALL BE FURNISHED WITH

AUXILIARY LOADS INTEGRAL ELECTRICAL LOAD

CENTER.

NEW PANEL "MDP-07" 600A, 208Y/120V, 3PH, 4W, NEMA 3R, 42KAIC

3P 225A

3P 300A

7 6 7 6

5 5

30A 2P

SPARE SPARE

DIESEL

STANDBY

GENERATOR

AUTOMATIC

TRANSFER

SWITCH

#3/0G #3/0G

1. CONTRACTOR SHALL RE-CIRCUIT EXISTING

EQUIPMENT AS INDICATED.

2. CONTRACTOR SHALL FURNISH AND INSTALL NEW

30A/2P BREAKER FOR GENSET LOAD CENTER.

BREAKER SHALL MATCH OR EXCEED EXISTING

PANEL KAIC RATING. ANY DISCREPANCIES SHALL BE

NOTIFIED TO ENGINEER.

3. CONTRACTOR SHALL FURNISH AND INSTALL A

SURGE PROTECTION DEVICE (SPD) TYPE EATON,

TYPE 1, 100KA, 3-PHASE, NEMA 3R OR EQUAL.

4. THE NEW ATS SHALL HAVE A POWER QUALITY

METER. TYPE: ALLEN BRADLEY 500 SERIES, MODEL

M6 OF EQUAL FEATURES (PQM).

5. CONTRACTOR SHALL FURNISH AND INSTALL 1"

CONDUIT AND CABLING AS REQUIRED BY

MANUFACTURER FOR START/STOP CIRCUIT.

6. CONTRACTOR SHALL FURNISH AND INSTALL 1-1/2"

CONDUIT AND CABLING FOR ANNUNCIATOR AS PER

MANUFACTURER INSTALLATION REQUIREMENTS.

COORDINATE FINAL ANNUNCIATOR LOCATION WITH

OWNER.

7. CONTRACTOR SHALL FURNISH AND INSTALL A 1"

CONDUIT WITH 2#8, #8G, FOR GENERATOR BLOCK

HEATER AND BATTERY CHARGER (LOAD CENTER).

M UTILITY METER

MDP7-100 MDP7-200

E203

ELECTRICAL PROPOSED ONE-LINE

DIAGRAM - ACADEMIC A &

ACADEMIC B

MP, MH

GB

09/13/2024 54769.002

TE

X

A S

J U

V E

N

IL

E

JU

S

TI

C E

D E

P A

R

TM

E N

T E

V

IN

S R

E G

IO

N

A L

JU

V

E N

IL

E

C E

N

TE

R

E

. M O

N

TE

C R

IS

TO

R O

A D

, E D

IN

B

U R

G

TX

Sheet Number

Sheet Title

Checked By:

Drawn By:

Project No.:

Issued:

N o.

D at e D es cr ip tio n R ev is io n

Scale: AS NOTED

W E

S T

M

IL

IT

A

R Y

H W

Y

S U

IT

E

M C

A

LL

E N

, T E

X A

S

-7

TE

L.

(9

) 6

-0

/1 0/

A D

D E

N D

U M

N.T.S.01

PROPOSED ELECTRICAL ONE-LINE DIAGRAM -

ACADEMIC A

N.T.S.02

PROPOSED ELECTRICAL ONE-LINE DIAGRAM -

ACADEMIC B

E301

ELECTRICAL FEEDER SCHEDULES

MP, MH

GB

09/13/2024 54769.002

TE

X

A S

J U

V E

N

IL

E

JU

S

TI

C E

D E

P A

R

TM

E N

T E

V

IN

S R

E G

IO

N

A L

JU

V

E N

IL

E

C E

N

TE

R

E

. M O

N

TE

C R

IS

TO

R O

A D

, E D

IN

B

U R

G

TX

Sheet Number

Sheet Title

Checked By:

Drawn By:

Project No.:

Issued:

N o.

D at e D es cr ip tio n R ev is io n

Scale: AS NOTED

W E

S T

M

IL

IT

A

R Y

H W

Y

S U

IT

E

M C

A

LL

E N

, T E

X A

S

-7

TE

L.

(9

) 6

-0

/1 0/

A D

D E

N D

U M

POWER FEEDER SCHEDULE

NO.

S E

TS CONDUCTORS SIZE FROM TO REMARKS

G 1-100 2

PH: 350

3 1/2'' GEN-01 PORTABLE GEN DOCKING

STATION DS-01N: 350

G: 1

DS 1-100 2

PH: 350

3 1/2'' PORTABLE GEN DOCKING

STATION DS-01 ATS-01N: 350

G: 1

UT 1-100 2

PH: 350

3 1/2'' EXISTING PAD MOUNTED ATS-01N: 350

G: 1

ATS 1-100 2

PH: 350

3 1/2'' ATS-01 NEMA 1 SERVICE

DISCONNECTN: 350

G: 1

G 3-100 4

PH: 350

3 1/2'' GEN-03 PORTABLE GEN DOCKING

STATION DS-03N: 350

G: 3/0

DS 3-100 4

PH: 350

3 1/2'' PORTABLE GEN DOCKING

STATION DS-03 ATS-03N: 350

G: 3/0

UT 3-100 4

PH: 350

3 1/2'' EXISTING PAD MOUNTED ATS-03N: 350

G: 3/0

ATS 3-100 4

PH: 350

3 1/2'' ATS-03 EXISTING MDPN: 350

G: 3/0

MDP 3-100 2

PH: 4/0

2 1/2'' EXISTING MDP PNL 'K'N: 4/0

G: 3

G 5-100 1

PH: 300

3'' GEN-05 PORTABLE GEN DOCKING

STATION DS-05

N: 300 G: 4

DS 5-100 1

PH: 300

3'' PORTABLE GEN DOCKING

STATION DS-05 ATS-05N: 300

G: 4

UT 5-100 1

PH: 300

3'' EXISTING PAD MOUNTED ATS-05N: 300

G: 4

ATS 5-100 1

PH: 300

3'' ATS-05 EXISTING PANEL 'C'N: 300

G: 4

PC 5-100 1

PH: 2/0

2" EXISTING PANEL 'C' EXISTING PANEL 'A'N: 2/0

G: 6

G 7-100 2

PH: 350

4'' GEN-07 PORTABLE GEN DOCKING

STATION DS-07N: 350

G: 1

DS 7-100 2

PH: 350

4'' PORTABLE GEN DOCKING

STATION DS-07 ATS-07N: 350

G: 1

UT 7-100 2

PH: 350

4'' EXISTING PAD MOUNTED ATS-07N: 350

G: 1

ATS 7-100 2

PH: 350

4'' ATS-07 NEW WIREWAY NEMA 3RN: 350

G: 1

MDP 7-100 1

PH: 4/0

2-1/2" MDP-07 PANEL 'C'N: 4/0

G: 4

MDP 7-200 1

PH: 350

3-1/2" MDP-07 PANEL 'J'N: 350

G: 4

G 9-100 3

PH: 300

3'' GEN-09 PORTABLE GEN DOCKING

STATION DS-09N: 300

G: 1/0

DS 9-100 3

PH: 300

3'' PORTABLE GEN DOCKING

STATION DS-09 ATS-09N: 300

G: 1/0

UT 9-100 3

PH: 300

3'' EXISTING PAD MOUNTED ATS-09N: 300

G: 1/0

ATS 9-100 3

PH: 300

3'' ATS-09 EXISTING PANEL 'MDP'N: 300

G: 1/0

G 11-100 5

PH: 400

3-1/2'' GEN -11 PORTABLE GEN DOCKING

STATION DS-11N: 400

G: 4/0

DS 11-100 5

PH: 400

3-1/2'' PORTRABLE GEN DOCKING

STATION DS-11 ATS-11N: 400

G: 4/0

UT 11-100 5

PH: 400

3-1/2'' EXISTING PAD MOUNTED ATS-11N: 400

G: 4/0

ATS 11-100 5

PH: 400

3-1/2'' ATS-11 MCB-2 SERVICE

DISCONNECTN: 400

G: 4/0

PE 11-100 1

PH: 4/0

2-1/2'' PNL 'E' EXISTING WIREWAYN: 4/0

G: 6

POWER FEEDER SCHEDULE

NO.

S E

TS CONDUCTORS SIZE FROM TO REMARKS

G 13-100 5

PH: 400

3-1/2'' GEN-13 PORTABLE GEN DOCKING

STATION DS-13N: 400

G: 4/0

DS 13-100 5

PH: 400

3-1/2'' PORTABLE GEN DOCKING

STATION DS-13 ATS-13N: 400

G: 4/0

UT 13-100 5

PH: 400

3-1/2'' EXISTING PAD MOUNTED ATS-13N: 400

G: 4/0

ATS 13-100 5

PH: 400

3-1/2'' ATS-13 MCB-2 SERVICE

DISCONNECTN: 400

G: 4/0

PE 13-100 1

PH: 4/0

2-1/2'' PNL 'E' EXISTING WIREWAYN: 4/0

G: 6

G 15-100 4

PH: 350

3-1/2'' GEN-15 PORTABLE GEN DOCKING

STATION DS-15N: 350

G: 3/0

DS 15-100 4

PH: 350

3-1/2'' PORTABLE GEN DOCKING

STATION DS-15

EMERGENCY POWER

SWITCHBOARD EPS-15N: 350

G: 3/0

UT 15-100 4

PH: 350

3-1/2'' EXISTING PAD MOUNTED ATS-15N: 350

G: 3/0

ATS 15-100 4

PH: 350

3-1/2'' ATS-15 EXISTING PANELN: 350

G: 3/0

EP 15-100 1

PH: 250

3'' EXISTING PANEL PNL 'A'N: 250

G: 4

G 17-100 4

PH: 350

3-1/2'' GEN-17 PORTABLE GEN DOCKING

STATION DS-17N: 350

G: 3/0

DS 17-100 4

PH: 350

3-1/2'' PORTABLE GEN DOCKING

STATION DS-17

EMERGENCY POWER

SWITCHBOARD EPS-17N: 350

G: 3/0

UT 17-100 4

PH: 350

3-1/2'' EXISTING PAD MOUNTED ATS-17N: 350

G: 3/0

ATS 17-100 4

PH: 350

3-1/2'' ATS-17 EXISTING PANELN: 350

G: 3/0

EP 17-100 1

PH: 250

3'' EXISTING PANEL PNL 'A'N: 250

G: 4

POWER FEEDER SCHEDULE

NO.

S E

TS CONDUCTORS SIZE FROM TO REMARKS

G 19-100 2

PH: 350

3-1/2'' GEN-19 PORTABLE DOCKING

STATION DS-19N: 350

G: 1

DS 19-100 2

PH: 350

3-1/2'' PORTABLE GEN DOCKING

STATION DS-19 ATS-19N: 350

G: 1

UT 19-100 2

PH: 350

3-1/2'' EXISTING PAD MOUNTED ATS-19N: 350

G: 1

ATS 19-100 2

PH: 350

3-1/2'' ATS-19 PNL 'A'N: 350

G: 1

G 21-100 2

PH: 350

3-1/2'' GEN-21 PORTABLE GEN DOCKING

STATION DS-21N: 350

G: 1

DS 21-100 2

PH: 350

3-1/2'' PORTABLE GEN DOCKING

STATION DS-21 ATS-21N: 350

G: 1

UT 21-100 2

PH: 350

3-1/2'' EXISTING PAD MOUNTED ATS-21N: 350

G: 1

ATS 21-100 2

PH: 350

3-1/2'' ATS-21 EXISTING PANEL DPN: 350

G: 1

PN 21-100 1

PH: 1

1-1/2'' PNL 'N' PNLN: 1

G: 8

G 23-100 3

PH: 400

3-1/2'' GEN-23 PORTABLE GEN DOCKING

STATION DS-23N: 400

G: 2/0

DS 23-100 3

PH: 400

3-1/2'' PORTABLE GEN DOCKING

STATION DS-23 ATS-23N: 400

G: 2/0

UT 23-100 3

PH: 400

3-1/2'' EXISTING PAD MOUNTED ATS-23N: 400

G: 2/0

ATS 23-100 3

PH: 400

3-1/2'' ATS-23 EXISTING PANEL 'MSB'N: 400

G: 2/0

MSB 23-100 1

PH: 2/0

2'' EXISTING PANEL 'MSB' PNL 'EA'N: 2/0

G: 6

GENERAL NOTES:

Sheets and Views
E103 ELECTRICAL POWER PLAN - ACADEMIC A & SECURITY
ELECTRICAL POWER PLAN - ACADEMIC A
ELECTRICAL POWER PLAN - ACADEMIC A ENLARGEMENT DETAIL
E203 ELECTRICAL PROPOSED ONE-LINE DIAGRAM - ACADEMIC A & ACADEMIC B
PROPOSED ELECTRICAL ONE-LINE DIAGRAM III - ACADEMIC A & B

E301 ELECTRICAL FEEDER SCHEDULES