ESBD_433095_1751482945934_SOL_EXH_F.13_405-25R0014809_Non Structural Metal Framing.pdf

PDF 399 KB Posted

Attached to
Sierra Blanca New office space remodel
Solicitation number
405-25R0014809
Issued by
Hidalgo County, Texas

About this file

This document is a technical specification section (Section 09 22 16) for Non-Structural Metal Framing issued by the Texas Department of Public Safety (TXDPS) Facilities Bureau in June 2016. The specification provides detailed requirements for steel framing systems used in interior construction, specifically covering non-load-bearing steel framing for gypsum board assemblies and suspension systems for interior gypsum ceilings, soffits, and grid systems. It outlines comprehensive technical standards for materials, performance requirements, installation methods, and tolerances, including specific guidelines for framing components such as studs, runners, furring channels, and suspension systems.

The specification details precise technical requirements including minimum base-metal thicknesses, protective coatings, attachment methods, and installation tolerances. Key technical standards referenced include ASTM C 754, ASTM C 645, and ASTM A 653/A 653M, which govern material properties, protective coatings, and installation practices. The document provides explicit instructions for installing framing in various contexts, such as fire-resistance-rated partitions, sound-rated assemblies, and around openings like doors, with specific guidance on spacing, attachment, and structural considerations. The specification ensures that metal framing will meet performance, safety, and construction quality standards for interior building systems.

View the file

Other files

File Type Posted
ESBD_433095_1751482954684_SOL_EXH_F.4_405-25R0014809_Direct Deposit Authorization.pdf PDF
ESBD_433095_1751482957635_SOL_EXH_F.6_405-25R0014809_Statement of Work.pdf PDF
ESBD_433095_1751482950313_SOL_EXH_F.10_405-25R0014809_Hollow Metal Doors.pdf PDF
ESBD_433095_1751482948877_SOL_EXH_F.21_405-25R0014809_Summary and Scope of Work.pdf PDF
ESBD_433095_1751482968097_SOL_EXH_F.19_405-25R0014809_Exterior Painting.pdf PDF
ESBD_433095_1751482962313_SOL_EXH_F.17_405-25R0014809_Resilient Athletic resurfacing.pdf PDF
ESBD_433095_1751482973840_SOL_EXH_F.7_405-25R0014809_Wage Determination.pdf PDF
ESBD_433095_1751482956132_SOL_EXH_F.11_405-25R0014809_Flush Wood Doors.pdf PDF
ESBD_433095_1751482947379_SOL_EXH_F.16_405-25R0014809_Resilient luxury vinyl tile flooring.pdf PDF
ESBD_433095_1751482966644_SOL_EXH_F.15_405-25R0014809_Resilience Base and Accessories.pdf PDF
ESBD_433095_1751482951761_SOL_EXH_F.8_405-25R0014809_Cleaning and Waste management.pdf PDF
ESBD_433095_1751482959126_SOL_PST_IFB INVITATION TO BID.pdf PDF
ESBD_433095_1751482970978_SOL_EXH_F.9_405-25R0014809_Selective Demolition.pdf PDF
ESBD_433095_1751482942923_SOL_EXH_F.2_405-25R0014809_Information and Certifications Form.pdf PDF
ESBD_433095_1751482944469_SOL_EXH_F.14_405-25R0014809_Gypsum Board.pdf PDF
ESBD_433095_1751482960572_SOL_EXH_F.12_405-25R0014809_Door Hardware.pdf PDF
ESBD_433095_1751482965204_SOL_EXH_F.5_405-25R0014809_Request for Taxpayer Identification Number and Certification.pdf PDF
ESBD_433095_1751482972423_SOL_EXH_F.20_405-25R0014809_Aluminum Mini Blind System.pdf PDF
ESBD_433095_1751482963730_SOL_EXH_F.18_405-25R0014809_Interior Painting.pdf PDF
ESBD_433095_1751482969533_SOL_EXH_F.1_405-25R0014809_DPS Standard Terms and Conditions.pdf PDF
ESBD_433095_1751482953281_SOL_EXH_F.3_405-25R0014809_Application for Texas Identification Number.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Date 06-2016 TXDPS Facilities Bureau

Spec Rev. 06-2016

1 09 22 16 Page

SECTION 09 22 16 - NON-STRUCTURAL METAL FRAMING

PART 1 – GENERAL

1.01 RELATED DOCUMENTS

A. Drawings, related specification sections and general provisions of the Contract, apply to this Section.

1.02 SUMMARY

A. Section Includes:

1. Non-load-bearing steel framing systems for interior gypsum board assemblies.

2. Suspension systems for interior gypsum ceilings, soffits, and grid systems.

PART 2 – PRODUCTS

2.01 PERFORMANCE REQUIREMENTS

A. Fire-Test-Response Characteristics: For fire-resistance-rated assemblies that incorporate non-load-bearing steel framing, provide materials and construction identical to those tested in assembly indicated, according to ASTM E 119.

B. STC-Rated Assemblies: For STC-rated assemblies, provide materials and construction identical to those tested in assembly indicated, according to ASTM E 90 and classified according to ASTM E 413.

2.02 FRAMING SYSTEMS

A. Framing Members, General: Comply with ASTM C 754 for conditions indicated.

1. Steel Sheet Components: Comply with ASTM C 645 requirements for metal unless otherwise indicated.

2. Protective Coating: ASTM A 653/A 653M, G60, hot-dip galvanized unless otherwise indicated.

B. Studs and Runners: ASTM C 645.

1. Steel Studs and Runners:

a. Minimum Base-Metal Thickness: 0.027 inch.

C. Slip-Type Head Joints: Where indicated, provide the following:

1. Single Long-Leg Runner System: ASTM C 645 top runner with 2-inch-deep flanges in thickness not less than indicated for studs, installed with studs friction fit into top runner and with continuous bridging located within 12 inches of the top of studs to provide lateral bracing.

D. Firestop Tracks: Top runner manufactured to allow partition heads to expand and contract with movement of the structure while maintaining continuity of fire-resistance-rated assembly indicated; in thickness not less than indicated for studs and in width to accommodate depth of studs.

E. Flat Strap and Backing Plate: Steel sheet for blocking and bracing in length and width indicated.

1. Minimum Base-Metal Thickness: 0.027 inch.

F. Cold-Rolled Channel Bridging: Steel, 0.053-inch minimum base-metal thickness, with minimum 1/2-inch- wide flanges.

1. Depth: 1-1/2 inches.

2. Clip Angle: Not less than 1-1/2 by 1-1/2 inches, 0.068-inch- thick, galvanized steel.

G. Hat-Shaped, Rigid Furring Channels: ASTM C 645.

1. Minimum Base-Metal Thickness: 0.018 inch.

H. Resilient Furring Channels: 1/2-inch- deep, steel sheet members designed to reduce sound transmission.

1. Configuration: Asymmetrical or hat shaped.

I. Cold-Rolled Furring Channels: 0.053-inch uncoated-steel thickness, with minimum 1/2-inch- wide flanges.

1. Depth: As indicated on Drawings.

2 09 22 16 Page

2. Furring Brackets: Adjustable, corrugated-edge type of steel sheet with minimum uncoated-steel thickness of 0.033 inch.

3. Tie Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.062-inch-diameter wire, or double strand of 0.048-inch- diameter wire.

J. Z-Shaped Furring: With slotted or non-slotted web, face flange of 1-1/4 inches, wall attachment flange of 7/8 inch, minimum uncoated-metal thickness of 0.018 inch, and depth required to fit insulation thickness.

2.03 SUSPENSION SYSTEMS

A. Tie Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.062-inch- diameter wire, or double strand of 0.048-inch- diameter wire.

B. Hanger Attachments to Concrete:

1. Anchors: Fabricated from corrosion-resistant materials with holes or loops for attaching wire hangers and capable of sustaining, without failure, a load equal to 5 times that imposed by construction as determined by testing according to ASTM E 488.

a. Type: Post-installed, chemical anchor or Post-installed, expansion anchor.

2. Powder-Actuated Fasteners: Suitable for application indicated, fabricated from corrosion-resistant materials with clips or other devices for attaching hangers of type indicated, and capable of sustaining, without failure, a load equal to 10 times that imposed by construction as determined by testing according to ASTM E 1190.

C. Wire Hangers: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.16 inch in diameter.

D. Carrying Channels: Cold-rolled, commercial-steel sheet with a base-metal thickness of 0.053 inch and minimum 1/2-inch- wide flanges.

1. Depth: 2-1/2 inches unless otherwise indicated.

E. Furring Channels (Furring Members):

1. Hat-Shaped, Rigid Furring Channels: ASTM C 645, 7/8 inch deep.

a. Minimum Base-Metal Thickness: 0.018 inch

2. Resilient Furring Channels: 1/2-inch- deep members designed to reduce sound transmission.

a. Configuration: Asymmetrical or hat shaped.

2.04 AUXILIARY MATERIALS

A. General: Provide auxiliary materials that comply with referenced installation standards. Fasteners for Metal

Framing: Of type, material, size, corrosion resistance, holding power, and other properties required to fasten steel members to substrates.

B. Isolation Strip at Exterior Walls: Provide one of the following:

1. Asphalt-Saturated Organic Felt: ASTM D 226, Type I (No. 15 asphalt felt), no perforation.

1. Foam Gasket: Adhesive-backed, closed-cell vinyl foam strips that allow fastener penetration without foam displacement, 1/8 inch thick, in width to suit steel stud size.

PART 3 – EXECUTION

3.01 EXAMINATION

A. Examine areas and substrates, including welded hollow-metal frames, cast-in anchors, and structural framing, for compliance with requirements and other conditions affecting performance of the Work.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.02 PREPARATION

A. Suspended Assemblies: Coordinate installation of suspension systems with installation of overhead structure to ensure that inserts and other provisions for anchorages to building structure have been

3 09 22 16 Page installed to receive hangers at spacing required to support the work and that hangers will develop their full strength.

3.03 INSTALLATION, GENERAL

A. Installation Standard: ASTM C 754.

1. Gypsum Board Assemblies: Also comply with requirements in ASTM C 840 that apply to framing installation.

A. Install supplementary framing, and blocking to support fixtures, equipment services, heavy trim, grab bars, toilet accessories, furnishings, or similar construction.

B. Install bracing at terminations in assemblies.

C. Do not bridge building control and expansion joints with non-load-bearing steel framing members. Frame both sides of joints independently.

3.04 INSTALLING FRAMED ASSEMBLIES

A. Install framing system components according to spacing indicated, but not greater than spacing required by referenced installation standards for assembly types.

1. Single-Layer Application: 16 inches o.c. unless otherwise indicated.

2. Multilayer Application: 16 inches o.c. unless otherwise indicated.

3. Tile Backing Panels: 16 inches o.c. unless otherwise indicated.

B. Where studs are installed directly against exterior masonry walls or dissimilar metals at exterior walls, install isolation strip between studs and exterior wall.

C. Install studs so flanges within framing system point in same direction.

D. Install tracks (runners) at floors and overhead supports. Extend framing full height to structural supports or substrates above suspended ceilings except where partitions are indicated to terminate at suspended ceilings. Continue framing around ducts penetrating partitions above ceiling.

1. Slip-Type Head Joints: Where framing extends to overhead structural supports, install to produce joints at tops of framing systems that prevent axial loading of finished assemblies.

2. Door Openings: Screw vertical studs at jambs to jamb anchor clips on door frames; install runner track section (for cripple studs) at head and secure to jamb studs.

a. Install two studs at each jamb unless otherwise indicated.

b. Install cripple studs at head adjacent to each jamb stud, with a minimum 1/2-inch clearance from jamb stud to allow for installation of control joint in finished assembly.

c. Extend jamb studs through suspended ceilings and attach to underside of overhead structure.

3. Other Framed Openings: Frame openings other than door openings the same as required for door openings unless otherwise indicated. Install framing below sills of openings to match framing required above door heads.

4. Fire-Resistance-Rated Partitions: Install framing to comply with fire resistance rated assembly as indicated on drawings and support closures and to make partitions continuous from floor to underside of solid structure.

a. Firestop Track: Where required, install to maintain continuity of fire-resistance-rated assembly indicated.

5. Sound-Rated Partitions: Install framing to comply with sound-rated assembly as indicated on drawings.

E. Direct Furring:

1. Screw to wood framing.

2. Attach to concrete or masonry with stub nails, screws designed for masonry attachment, or powder-driven fasteners spaced 24 inches O.C.

F. Z-Furring Members:

1. Erect insulation, specified in Section 072100 "Building Insulation," vertically and hold in place with Z-furring members spaced 24 inches O.C.

4 09 22 16 Page

2. Except at exterior corners, securely attach narrow flanges of furring members to wall with concrete stub nails, screws designed for masonry attachment, or powder-driven fasteners spaced 24 inches O.C.

3. At exterior corners, attach wide flange of furring members to wall with short flange extending beyond corner; on adjacent wall surface, screw-attach short flange of furring channel to web of attached channel. At interior corners, space second member no more than 12 inches from corner and cut insulation to fit.

G. Installation Tolerance: Install each framing member so fastening surfaces vary not more than 1/8 inch from the plane formed by faces of adjacent framing.

3.05 INSTALLING SUSPENSION SYSTEMS

A. Install suspension system components according to spacing indicated, but not greater than spacing required by referenced installation standards for assembly types.

1. Hangers: 48 inches O.C.

2. Carrying Channels (Main Runners): 48 inches O.C.

3. Furring Channels (Furring Members): 16 inches O.C.

B. Isolate suspension systems from building structure where they abut or are penetrated by building structure to prevent transfer of loading imposed by structural movement.

C. Suspend hangers from building structure as follows:

1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structural or suspension system.

a. Splay hangers only where required to miss obstructions and offset resulting horizontal forces by bracing, counter-splaying, or other equally effective means.

2. Where width of ducts and other construction within ceiling plenum produces hanger spacing that interfere with locations of hangers required to support standard suspension system members, install supplemental suspension members and hangers in the form of trapezes or equivalent devices.

a. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced installation standards.

3. Wire Hangers: Secure by looping and wire tying, either directly to structures or to inserts, eye screws, or other devices and fasteners that are secure and appropriate for substrate, and in a manner that will not cause hangers to deteriorate or otherwise fail.

4. Do not attach hangers to steel roof deck.

5. Do not attach hangers to rolled-in hanger tabs of composite steel floor deck.

6. Do not connect or suspend steel framing from ducts, pipes, or conduit.

D. Fire-Resistance-Rated Assemblies: Wire tie furring channels to supports.

E. Grid Suspension Systems: Attach perimeter wall track or angle where grid suspension systems meet vertical surfaces. Mechanically join main beam and cross-furring members to each other and butt-cut to fit into wall track.

F. Installation Tolerances: Install suspension systems that are level to within 1/8 inch in 12 feet measured lengthwise on each member that will receive finishes and transversely between parallel members that will receive finishes.

END OF SECTION