ESBD_433095_1751482944469_SOL_EXH_F.14_405-25R0014809_Gypsum Board.pdf
PDF 408 KB Posted
- Attached to
- Sierra Blanca New office space remodel
- Solicitation number
- 405-25R0014809
- Issued by
- Hidalgo County, Texas
About this file
This document is a technical specification section for gypsum board installation for the Texas Department of Public Safety (TXDPS) Facilities Bureau, dated June 13, 2016. The specification provides comprehensive details for interior gypsum board installation, including requirements for product types, performance standards, materials, installation methods, and finishing techniques. It covers various gypsum board types including standard wallboard, Type X fire-resistant board, and sound attenuating gypsum board with specific performance characteristics such as fire resistance, sound transmission class (STC) ratings, and moisture resistance.
The specification outlines detailed technical requirements for materials like CertainTeed SilentFX QuickCut Gypsum Board, specific trim accessories, joint treatment materials, and auxiliary materials. Key technical specifications include 5/8-inch thick Type X gypsum board with tapered edges, sound attenuation requirements, mold resistance ratings, and precise installation guidelines. The document provides explicit instructions for panel application, finishing levels, protection of installed materials, and handling of potential moisture or mold damage. Specific manufacturers and product lines are referenced, with "or equal" alternatives permitted, providing flexibility for contractors while maintaining stringent quality standards.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date 00, 0000 TXDPS Facilities Bureau
Spec Rev. 06-13-2016
09 29 00 Page
SECTION 09 29 00 – GYPSUM BOARD
PART 1 – GENERAL
1.01 RELATED DOCUMENTS
A. Drawings, related specification sections and general provisions of the Contract, apply to this Section.
1.02 SUMMARY
A. Section Includes:
1. Interior gypsum board.
2. Tile backing panels.
B. Related Requirements:
1. Section 092216 "Non-Structural Metal Framing" for non-structural framing and suspension systems that support gypsum board panels.
2. Section 092116.23 "Gypsum Board Shaft Wall Assemblies" for metal shaft-wall framing, gypsum shaft liners, and other components of shaft-wall assemblies.
1.03 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.04 DELIVERY, STORAGE AND HANDLING
A. Store materials inside under cover and keep them dry and protected against weather, condensation, direct sunlight, construction traffic, and other potential causes of damage. Stack panels flat and supported on risers on a flat platform to prevent sagging.
1.05 FIELD CONDITIONS
A. Environmental Limitations: Comply with ASTM C 840 requirements or gypsum board manufacturer's written recommendations, whichever are more stringent.
B. Do not install paper-faced gypsum panels until installation areas are enclosed and conditioned.
C. Do not install panels that are wet, those that are moisture damaged, and those that are mold damaged.
1. Indications that panels are wet or moisture damaged include, but are not limited to, discoloration, sagging, or irregular shape.
2. Indications that panels are mold damaged include, but are not limited to, fuzzy or splotchy surface contamination and discoloration.
PART 2 – PRODUCTS
2.01 PERFORMANCE REQUIREMENTS
A. Fire-Resistance-Rated Assemblies: For fire-resistance-rated assemblies, provide materials and construction identical to those tested in assembly indicated according to ASTM E 119.
B. STC-Rated Assemblies: For STC-rated assemblies, provide materials and construction identical to those tested in assembly indicated according to ASTM E 90 and classified according to ASTM E 413.
2.02 GYPSUM BOARD, GENERAL
A. Size: Provide maximum lengths and widths available that will minimize joints in each area and that correspond with support system indicated.
2.03 INTERIOR GYPSUM BOARD
A. Gypsum Wallboard: ASTM C 1396/C 1396M.
B. Gypsum Board, Type X: ASTM C 1396/C 1396M.
1. Thickness: 5/8 inch.
2. Long Edges: Tapered.
2.05 SOUND ATTENUATING GYPSUM BOARD
A. Acceptable Manufacturers
1. CertainTeed Gypsum, Inc.
a. Basis of Design: CertainTeed SilentFX® QuickCut Gypsum Board OR EQUAL.
1. Laminated noise-reducing gypsum board consisting of two layers of dense gypsum board encased in smooth, moisture and mold resistant paper facings laminated together with a viscoelastic polymer compound. Meeting ASTM C1766 and ASTM C1396.
2. Type and Thickness: Type X (where required by fire rating), 5/8 inch (15.9 mm) thick
3. Size: 48 by not less than 96 inches (1220 by not less than 2440 mm) longest length possible to minimize joints.
4. Surface Paper: 100% recycled moisture and mold resistant paper on face, back and long edges.
5. Mold Resistance Rating:
a. Score of 10 (best possible) tested in accordance with ASTM D3273
B. Acoustical Sealant
1. Acceptable Manufacturers
a. Green Glue Company OR EQUAL
1. Basis of Design: Green Glue Noise proofing Sealant
2.06 TRIM ACCESSORIES
A. Interior Trim: ASTM C 1047.
1. Material: Galvanized or aluminum-coated steel sheet or rolled zinc.
2. Shapes:
a. Cornerbead.
b. Bullnose bead.
c. LC-Bead: J-shaped; exposed long flange receives joint compound.
d. L-Bead: L-shaped; exposed long flange receives joint compound.
e. U-Bead: J-shaped; exposed short flange does not receive joint compound.
f. Expansion (control) joint.
B. Aluminum Trim: Extruded accessories of profiles and dimensions indicated.
1. Aluminum: Alloy and temper with not less than the strength and durability properties of ASTM B
221, Alloy 6063-T5.
2. Finish: Corrosion-resistant primer compatible with joint compound and finish materials specified.
2.07 JOINT TREATMENT MATERIALS
A. General: Comply with ASTM C 475/C 475M.
B. Joint Tape:
1. Interior Gypsum Board: Paper.
2. Glass-Mat Gypsum Sheathing Board: 10-by-10 glass mesh.
3. Tile Backing Panels: As recommended by panel manufacturer.
C. Joint Compound for Interior Gypsum Board: For each coat use formulation that is compatible with other compounds applied on previous or for successive coats.
1. Prefilling: At open joints, rounded or beveled panel edges, and damaged surface areas, use setting-type taping compound.
2. Embedding and First Coat: For embedding tape and first coat on joints, fasteners, and trim flanges, use setting-type taping compound.
a. Use setting-type compound for installing paper-faced metal trim accessories.
3. Fill Coat: For second coat, use setting-type, sandable topping compound.
4. Finish Coat Options:
a. Level 4 finish on walls to receive vinyl wallcovering
b. Level 5 finish as indicated by TXDPS.
c. Level 5 finish with stipple texture as indicated by TXDPS.
D. Joint Compound for Tile Backing Panels:
1. Cementitious Backer Units: As recommended by backer unit manufacturer.
2.08 AUXILIARY MATERIALS
A. General: Provide auxiliary materials that comply with referenced installation standards and manufacturer's written recommendations.
B. Laminating Adhesive: Adhesive or joint compound recommended for directly adhering gypsum panels to continuous substrate.
1. Laminating adhesive shall have a VOC content of 50 g/L or less when calculated according to 40
CFR 59, Subpart D (EPA Method 24).
C. Steel Drill Screws: ASTM C 1002, unless otherwise indicated.
1. Use screws complying with ASTM C 954 for fastening panels to steel members from 0.033 to
0.112 inch thick.
D. Sound Attenuation Blankets: ASTM C 665, Type I (blankets without membrane facing) produced by combining thermosetting resins with mineral fibers manufactured from glass, slag wool, or rock wool.
1. Fire-Resistance-Rated Assemblies: Comply with mineral-fiber requirements of assembly.
E. Acoustical Joint Sealant: Manufacturer's standard non-sag, paintable, non-staining latex sealant complying with ASTM C 834. Product effectively reduces airborne sound transmission through perimeter joints and openings in building construction as demonstrated by testing representative assemblies according to ASTM E 90.
1. Acoustical joint sealant shall have a VOC content of 250 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).
F. Acoustic Joint Sealant for use with High STC Interior Gypsum Board assemblies: Latex sealant, ASTM C834, Grade -18 degrees C.
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Pabsco Gypsum; QuietSeal Pro.
2. Extrudability (ASTM C1183 Method B): ≥2.1 g/s Extrusion Rate
3. Artificial Weathering (ASTM C732 500 Hours): No wash-out, slump, or cracking. Also ≤25% total bond area loss.
4. Volume Shrinkage (ASTM C1241 Type OP): ≤30% volume shrinkage.
5. Low Temperature Flexibility (ASTM C734): No adhesion loss or cracking through to substrate after
500 hours.
6. Recovery and Adhesion Loss (ASTM C736): ≥75% recovery and ≤25% total bond area loss.
7. Slump (ASTM D2202): No slump observed.
8. Stain Index (ASTM D2203): Maximum allowable stain index of 1.
9. Surface Burning Characteristics (ASTM E84): Meets NFPA Class A Fire-Rating.
G. Acoustic Putty Pads for use with High STC Interior Gypsum Board assemblies:
1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
a. Pabsco Gypsum; QuietPutty.
2. Thickness: 1/8 inch.
3. Weight: 6 oz. per pad.
4. Size: 7 inch by 7 inch.
5. Density: 1 oz. per cu. inch.
6. STC-rated: 47–63, ASTM E90
PART 3 – EXECUTION
3.01 EXAMINATION
A. Examine areas and substrates including welded hollow-metal frames and framing, with Installer present, for compliance with requirements and other conditions affecting performance.
B. Examine panels before installation. Reject panels that are wet, moisture damaged, and mold amaged.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.02 APPLYING AND FINISHING PANELS, GENERAL
A. Comply with ASTM C 840.
B. Install ceiling panels across framing to minimize the number of abutting end joints and to avoid abutting end joints in central area of each ceiling. Stagger abutting end joints of adjacent panels not less than one framing member.
C. Install panels with face side out. Butt panels together for a light contact at edges and ends with not more than 1/16 inch of open space between panels. Do not force into place.
D. Locate edge and end joints over supports, except in ceiling applications where intermediate supports or gypsum board back-blocking is provided behind end joints. Do not place tapered edges against cut edges or ends. Stagger vertical joints on opposite sides of partitions. Do not make joints other than control joints at corners of framed openings.
E. Form control and expansion joints with space between edges of adjoining gypsum panels.
F. Cover both faces of support framing with gypsum panels in concealed spaces (above ceilings, etc.), except in chases braced internally.
1. Unless concealed application is indicated or required for sound, fire, air, or smoke ratings, coverage may be accomplished with scraps of not less than 8 sq. ft. in area.
2. Fit gypsum panels around ducts, pipes, and conduits.
3. Where partitions intersect structural members projecting below underside of floor/roof slabs and decks, cut gypsum panels to fit profile formed by structural members; allow 1/4- to 3/8-inch- wide joints to install sealant.
G. Isolate perimeter of gypsum board applied to non-load-bearing partitions at structural abutments, except floors. Provide 1/4- to 1/2-inch- wide spaces at these locations and trim edges with edge trim where edges of panels are exposed. Seal joints between edges and abutting structural surfaces with acoustical sealant.
H. Attachment to Steel Framing: Attach panels so leading edge or end of each panel is attached to open (unsupported) edges of stud flanges first.
I. STC-Rated Assemblies: Seal construction at perimeters, behind control joints, and at openings and penetrations with a continuous bead of acoustical sealant. Install acoustical sealant at both faces of partitions at perimeters and through penetrations. Comply with ASTM C 919 and with manufacturer's written recommendations for locating edge trim and closing off sound-flanking paths around or through assemblies, including sealing partitions above acoustical ceilings.
1. For assemblies that include High STC Interior Gypsum Board, utilize acoustic sealant designed for use with that product.
2. For receptacles, junction boxes, and other penetrations or joints that are larger than 3/4 inch in assemblies that include High STC Interior Gypsum Board, utilize acoustic putty pads.
a. At electrical boxes, wrap the putty completely around the back side of the box.
J. Install sound attenuation blankets before installing gypsum panels unless blankets are readily installed after panels have been installed on one side.
3.03 APPLYING INTERIOR GYPSUM BOARD
A. Install interior gypsum board in the following locations:
1. Type X: Vertical surfaces unless otherwise indicated.
2. Type C: Where required for specific fire-resistance-rated assembly indicated.
B. Single-Layer Application:
1. On ceilings, apply gypsum panels before wall/partition board application to greatest extent possible and at right angles to framing unless otherwise indicated.
2. On partitions/walls, apply gypsum panels vertically (parallel to framing) unless otherwise indicated or required by fire-resistance-rated assembly, and minimize end joints.
a. Stagger abutting end joints not less than one framing member in alternate courses of panels.
b. At stairwells and other high walls, install panels horizontally unless otherwise indicated or required by fire-resistance-rated assembly.
3. On Z-furring members, apply gypsum panels vertically (parallel to framing) with no end joints.
Locate edge joints over furring members.
4. Fastening Methods: Apply gypsum panels to supports with steel drill screws.
C. Multilayer Application:
1. On ceilings, apply gypsum board indicated for base layers before applying base layers on walls/partitions; apply face layers in same sequence. Apply base layers at right angles to framing members and offset face-layer joints one framing member, 16 inches minimum, from parallel base-layer joints, unless otherwise indicated or required by fire-resistance-rated assembly.
2. On partitions/walls, apply gypsum board indicated for base layers and face layers vertically (parallel to framing) with joints of base layers located over stud or furring member and face-layer joints offset at least one stud or furring member with base-layer joints, unless otherwise indicated or required by fire-resistance-rated assembly. Stagger joints on opposite sides of partitions.
3. On Z-furring members, apply base layer vertically (parallel to framing) and face layer either vertically (parallel to framing) or horizontally (perpendicular to framing) with vertical joints offset at least one furring member. Locate edge joints of base layer over furring members.
4. Fastening Methods: Fasten base layers and face layers separately to supports with screws.
3.05 INSTALLING TRIM ACCESSORIES
A. General: For trim with back flanges intended for fasteners, attach to framing with same fasteners used for panels. Otherwise, attach trim according to manufacturer's written instructions.
B. Control Joints: Install control joints at locations indicated on Drawings and at other locations according to ASTM C 840 and in specific locations approved by TXDPS for visual effect.
C. Interior Trim: Install in the following locations:
1. Cornerbead: Use at outside corners unless otherwise indicated.
2. Bullnose Bead: Use where indicated.
3. LC-Bead: Use at exposed panel edges.
4. L-Bead: Use where indicated.
5. U-Bead: Use where indicated.
D. Aluminum Trim: Install in locations indicated on Drawings.
3.06 FINISHING GYPSUM BOARD
A. General: Treat gypsum board joints, interior angles, edge trim, control joints, penetrations, fastener heads, surface defects, and elsewhere as required to prepare gypsum board surfaces for decoration. Promptly remove residual joint compound from adjacent surfaces.
B. Prefill open joints, rounded or beveled edges, and damaged surface areas.
C. Apply joint tape over gypsum board joints, except for trim products specifically indicated as not intended to receive tape.
D. Gypsum Board Finish Levels: Finish panels to levels indicated below and according to ASTM C 840:
1. Level 1: Ceiling plenum areas, concealed areas, and where indicated.
2. Level 4: At panel surfaces that will be exposed to view unless otherwise indicated.
3.07 PROTECTION
A. Protect adjacent surfaces from drywall compound and promptly remove from floors and other non-drywall surfaces. Repair surfaces stained, marred, or otherwise damaged during drywall application.
B. Protect installed products from damage from weather, condensation, direct sunlight, construction, and other causes during remainder of the construction period.
C. Remove and replace panels that are wet, moisture damaged, and mold damaged.
1. Indications that panels are wet or moisture damaged includes, but are not limited to, discoloration, sagging, or irregular shape.
2. Indications that panels are mold damaged include, but are not limited to, fuzzy or splotchy surface contamination and discoloration.
END OF SECTION