ESBD_384085_1736783015748_Eagle Landing Phase I - Fire Drawings.pdf
PDF 4 MB Posted
- Attached to
- Texas A&M- Texarkana Eagle Landing Phase II: Student Housing Construction or Modular Units
- Solicitation number
- TAMUT-RFP-0898_122024
- Issued by
- Blanco County, Waco City, Texas
About this file
This file contains fire sprinkler system drawings and hydraulic calculations submitted by Texican Fire Protection, LLC for Texas A&M's temporary housing and laundry facilities in Texarkana. The drawings detail the fire protection systems for 11 new dormitory buildings and one laundry building, with each dorm requiring an NFPA 13R compliant wet sprinkler system and the laundry building requiring an NFPA 13 compliant system. The dormitory designs show a light hazard classification with 0.05 gpm/ft² density, while the laundry facility has an Ordinary Group I classification with 0.15 gpm/ft² density. Each dorm building is approximately 280 square feet and includes bathrooms, closets, and patio areas, while the laundry facility is a converted shipping container structure.
The hydraulic calculations demonstrate system adequacy with a static pressure of 49 psi and residual pressure of 42 psi at 1060 gpm flow from the water supply. The dorm buildings each require 2 Victaulic V2740 pendent sprinklers (K-factor 4.9) and 3 Victaulic V3610 sidewall sprinklers (K-factor 5.6), while the laundry building uses 3 Victaulic V2708 pendent sprinklers and 1 V3610 sidewall sprinkler. The systems include 1.5-inch Watts backflow preventers, butterfly valves with tamper switches, inspectors test connections, and wall-mounted post indicators. The drawings include detailed pipe sizing, hanger spacing requirements, and fitting specifications for both black steel and galvanized piping systems.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
9' -1
1½ 44'-2
21'-5 8 77'-7
31'-1½
6'-
25'-6½
18'-4
2 4' -6
51'-3½
812'-9½
'-6
'-5 ½
1 2 3 4 5
BATHROOM
(27 SF)
DORM ROOM DORM ROOM
SEE SITE PLAN
FOR CONT.
3' -6
40'-0
7' -0
11'-0 11'-0 5'-05'-0
7' -7
CLOSET
PATIO
7'-1 7'-1
102 103
104 64
1 3' -0
1'-0½
1'-5½
4'-1½
3'
-1 1½ 1
3' -1
1½ 1 3'
-1 1½
11'-0
1'-5½
6'-10½
8'- 2 F
F
250'-0
9' -6
8'-0
7'-0
8' -8
STRAIGHT SAMMY SCREW
Pipe
Sammy XP-20
METAL STRUCTURE
Swivel Ring
3/8 ALL THREAD
XP-20
PIPE TO BE AS TIGHT AS POSSIBLE TO DECK
Sprinkler Legend Symbol Manufacturer SIN Model Quantity K-Factor Type Size Response Finish Temp
Victaulic V2740 V27 2 4.9 Pendent ½ Quick Chrome 155 °F Victaulic V3610 FL-QR/DRY/SW 3 5.6 Sidewall 1 Quick Chrome 155 °F
Total = 5
1½" WATTS BACKFLOW PREVENTER MODEL 2000B-FP
BUTTERBALL VALVES W/TAMPER
1" INSPECTORS TEST AND DRAIN VALVE ELECTRIC BELL
WIRING BY OTHERS
LOCATE ON EXTERIOR
OF SPRINKLER RM
WITH 1/2" TEST ORIFICE
TERMINATE TO EXTERIOR
1" TO SYSTEM
1½" RISER CHECK WITH SYS GAUGE
ACCESS PANEL BY OTHERS
2" GALVANIZED SCH40 PIPING FROM UNDERGROUND
FLOW SW.
1½" GALVANIZED SCH40 PIPE NIPPLE (THDXGRV)
FireLock™ Series 775 Butterfly Valve Wall Post Indicator Assembly
SET TO OPERATE BETWEEN 45-60 SEC
1½" X 1" REDUCER
2X1½ RED COUPLING
2x2x1 GALVANIZED TEE FOR DOM CONNECTION
DOM. CONNECTION AND CONTINUATION BY OTHERS
OCCUPANCY GROUP: R
TYPE OF CONSTRUCTION: iib
BUILDING SQ FT:
scope overview:
provide fire sprinkler system for each of the 11 new dormitories
FP-1 NOTE: 1/16" = 1'-0"
TEXICAN FP TO START 1'-0" AFF
PROJECT SITE PLAN1
SPRINKLERS NOT REQ'D IN
FP-1
1/4" = 1'-0"
TYPICAL FLOOR PLAN (BLDG 1-11)
NOTE:
ALL WIRING BY OTHERS
NOTE:
RISER DETAIL3
NTSFP-1
TEXICAN FP TO START 1'-0" AFF
PHASE II
BATHROOMS PER 13R - 8.15.8.1.1
LAUNDRY BLDG
(SEPARATE SUBMITTAL)
WALL MOUNTED POST INDICATOR
NOTE - INSTALL BETWEEN 3-5' CENTERLINE ABOVE GRADE
GATE VALVE
GATE VALVE
TRANSITION TO GALVANIZED
SCH 40 PIPING AT THIS LOCATION
AND CONTINUE INTO BUILDING
3X2 RED
8X8X3 TEE
USE CHAIN AND LOCK IN-LIEU OF TAMPER SW
ALL UNDERGROUND PIPING IS PVC UNO
ALL PIPING TO BE CONCEALED
SEE SECTION 4/FP-1
*DOMESTIC DEMAND 13.2GPM INCLUDED
DOMESTIC DEMAND
Supply Flow Test Data Static Pressure 49.000 Residual Pressure: 42.000 Flow 1060.00 Outside Hose Flow 100.00 Test Conducted By RYAN BEAN (TEXARKANA WATER UTIL) Date of Test 7/19/2024
AS-BUILT SUBMITTAL OTHER
N O
DESCRIPTION:
D
AT
E
SCALE: 1/8"=1'-0"
SITE PLAN & PROJECT INFORMATION
RME-SIGNATURE:
TEMP HOUSING - TEXAS A&M
236 E Frank StreetWILLS POINT, TEXAS 75169
(903) 829-6014 Grand Saline, Texas 75140
TEXICAN FIRE PROTECTION, LLC
R
EV
IS
IO
N
SCR-G-2217837
DRAWN BY: JCJ
I HAVE REVIEWED THESE PLANS AND
CERTIFY THAT THEY COMPLY WITH THE
ADOPTED NFPA STANDARDS.
DATE:
149 PRIVATE ROAD 6127
DATE:
PROTECTION
SPRINKLERS SHALL BE LOCATED A MINIMUM OF 4" FROM A WALL
FSR# 04033
RME-
PROVIDE HEAD GUARDS TO SPRINKLERS SUBJECT TO DAMAGE
MATTHEW MEREDITH
CHECKED BY: M.M
TEXICAN FIRE
G-1742566
CONTRACT NAME:
12/9/24
TEXARCANA, TXBY
PRINTED RME NAME:
DWG. NO.: FP-1 OF 1
* PER BUILDING
JC
J 8/
/2
AH
J C
O M
M
EN
TS
/8 /2
AH
J C
O M
M
EN
TS
N
EW
W
AT
ER
M
AI
N
L O
C
AT
IO
N
JC
J
MAX STANDARD SPRINKLER 15X15 SPACING
/9 /2
JC
J C
O M
BI
N
ED
F
P
AN
D D
O M
ES
TI
C , A
D D
D O
M D
EM
AN
D T
O C
AL
C
U
LA
TI
O
N S
NFPA 13r (2019 EDITION)
0.05
BUILDING CODE DATA
MATERIAL NOTES
no fdc required per nfpa 13r (2019) § 6.11.1
GENERAL NOTES
FIRE SPRINKLER DESIGN CRITERIA
temporary dorms
LOCAL FM
each building - 280 SF wet two sprinkler heads (entire building)
100gpm + 13.2 OF DOMESTIC DEMAND
AUTHORITY HAVING JURISDICTION:
STANDARD:
SYSTEM TYPE:
DENSITY:
AREA OF APPLICATION:
HOSE ALLOWANCE:
FACILITY USAGE:
ADDITIONAL DESIGN NOTES:
1. SYSTEM DESIGN AND INSTALLATION PER NFPA 13r (2019)
2. TEXICAN FIRE PROTECTION IS TO PROVIDE ADEQUATE FIRE PROTECTION THROUGHOUT THE BUILDING.
3. ALL ELECTRICAL WIRING OF DEVICES IS PROVIDED BY OTHERS.
4. FIRE CAULK ALL PIPE PASSING THROUGH RATED ASSEMBLIES.
5. ALL HANGERS TO BE INSTALLED PER NFPA 13
6. all pipe and fittings as noted below
7. FLUSHING CONNECTIONS PROVIDED PER NFPA 13
8. ANY MECHANICAL TYPE FITTING CUT INTO EXISTING PIPING ARE TO HAVE CUTOUT DISCS ATTACHED TO THE FITTING IN
ORDER TO VERIFY CUTOUT RETRIEVAL.
9. TEXICAN FIRE PROTECTION IS NOT RESPONSIBLE FOR REMOVAL OR REPLACEMENT OF ACOUSTICAL CEILING TILES OR
CUTTING OR PATCHING OF SHEETROCK CEILINGS.
PIPE:
-New PIPE TO BE SCH 40 BLK STEEL / THREAD ENDS (UNO.)
FITTINGS:
-New FITTINGS TO BE STANDARD WT DUCTILE IRON THREADED FITTINGS (UNO.)
TOILET 1.6GPM X 2 = 3.2GPM
SHOWER 2GPM X 2 = 4GPM
KITCHEN SINK 2GPM X 2 = 4GPM
BATH SINK 1GPM X 2 = 2GPM
tOTAL MAX DOM DEMAND = 13.2GPM
Hydraulic Information Remote Area 1A
OCCUPANCY CLASSIFICATION Light Hazard DENSITY (gpm/ft²) 0.05 for 1500 ft² (Actual 356 ft²)
TOTAL HOSE STREAMS 113.20
TOTAL HEADS FLOWING 4
K-FACTOR 5.6
TOTAL WATER REQUIRED 172.54
TOTAL PRESSURE REQUIRED 37.217
SAFETY MARGIN (psi) +11.539 (23.7%)
SECTION
FP-1 NOTE:
1/4" = 1'-0"
SHIPPING CONTAINER STRUCTURE
GYP CELING
NOTE:
ROTATED EXTERIOR VIEW
NTSFP-1
EXTERIOR PROJECTION IS WOODEN OPEN TRELLIS
WITH NO ROOF OR DECKING
GEN CONTRACTOR TO PROVIDE
GYP SOFFIT (8" X 8")
TO CONCEAL PIPING
DEFLECTOR TO BE = 12" FROM DECK
SCALE: 1/4" = 1'-0"
120 16 20 4084
MAXIMUM DISTANCE BETWEEN HANGERS (ft-in.)
15-0
3 1/2"
15-0 5-6
12-0
3-4
6"
12-08-0
N/A 12-0
10-0
N/AN/A
N/A
3-11
15-0
6-0 Copper Tube
5-5 Ductile Iron Pipe
N/A 15-0
Nominal Pipe Size (in.)
N/A Polybutylene (CTS)
3/4"
Polybutylene (IPS) N/A
15-0
N/A
15-0
15-0
9-0 N/A
4-5
12-0
N/A
N/A 15-0N/A
2 1/2"
N/A
N/A
Steel Pipe Except Threaded Lightwall
15-0
15-0
4" 8"1 1/2"
3-9 N/A
15-0
N/A N/A
N/A
12-0
8-0
12-0
N/A7-0
15-0
5-0
12-0
N/A
N/A
CPVC
15-0
5"
N/A
N/A
6-6
N/A N/A
15-0 3"
12-012-0
1"
N/A
N/A
2"
4-7 N/A
1 1/4"
5-11
15-0
8-0
N/A
10-0
15-0
N/A
N/A
N/A
15-0
12-0 N/A
12-0
N/A 15-0
Threaded Lightwall Steel Pipe
N/A 2-11
10-0
Hydraulic Calculations
Location: TEXARCANA, TX, , Project Name: TEMP HOUSING - TEXAS A&M
Drawing Name: FP Calculation Date: 12/9/2024 for
Design
Light Hazard
Area of Application: 1500 ft² (Actual 356 ft²)
Coverage per Sprinkler: 198 ft²
Type of sprinklers calculated:
1ARemote Area Number:
Occupancy Classification:
No. of sprinklers calculated:
Density 0.05 gpm/ft²
Pendent, Sidewall
No. of nozzles calculated: 0
In-rack Demand:
Hose Streams: at Node: Type: Allowance at Source
N/Aat Node:N/A gpm
1100.00
13.20 HoseType:70at Node:
(including Hose Streams where applicable):Total Water Required
37.217@172.54From Water Supply at Node 1: (Safety Margin = 11.539)
Type of System:
Volume of Dry/PreAction/Antifreeze/OtherAgent System:N/A
Source: RYAN BEAN (TEXARKANA WATER UTIL)
Location:
7/19/2024Date:for Node: 1
Name of Contractor:
Authority Having Jurisdiction:
Address:
Phone Number:
Name of designer:
N/A N/A Right:Left:Automatic peaking results
Notes:
12/9/2024© M.E.P.CAD, Inc. Page 1AutoSPRINK 2022 v17.1.17.0 5:27:34PM1A
Hydraulic Graph
Water Supply
Node: 1
Job Name: TEMP HOUSING - TEXAS A&M
Remote Area Number: 1A Date: 12/9/2024
Summary Sheet
N 1.85
© M.E.P.CAD, Inc. 12/9/2024 Page 2AutoSPRINK 2022 v17.1.17.0 5:27:36PM
Device (gpm)
Actual Flow Minimum Flow
(gpm) (K)
K-Factor
(psi)
Pressure
Summary Of Outflowing Devices Report Description: Light Hazard (1A)
Job Number: 6549874
Hose 70 13.20 13.20 0 28.446
Sprinkler 101 15.14 12.00 5.6 7.311
Sprinkler 102 15.59 12.00 5.6 7.755
Sprinkler 103 14.82 12.00 5.6 7.000
Sprinkler 104 13.78 9.92 4.9 7.913
Most Demanding Sprinkler Data
© M.E.P.CAD, Inc. 12/9/2024 Page 3AutoSPRINK 2022 v17.1.17.0 5:27:38PM
Job Name: TEMP HOUSING - TEXAS A&M
Remote Area Number: 1A Date: 12/9/2024
Node @ @
Supply Analysis
Static
(psi)
Required Pressure
(psi)(gpm)
Total DemandAvailable
(psi)
Flow
(gpm)
Residual
(psi) Name
42.0001 37.217172.541060.00 48.75649.000Water Supply
Node Analysis
NotesDischarge at
Node
(gpm)
Pressure at
Node
(psi)
Node TypeElevation (Foot)Node Number
0'-0 72.5437.217Supply1
2'-2½ 13.2028.446Hose70 Hos
8'-2 15.147.311Sprinkler101
8'-2 15.597.755Sprinkler102
8'-2 14.827.000Sprinkler103
8'-2 13.787.913Sprinkler104
-3'-0 38.4692
-3'-0 38.5173
-3'-0 38.4655
-3'-0 38.45015
-3'-0 33.61545
2'-2½ 30.65757
3'-0 30.28258
-3'-0 38.33663
8'-2 8.00864
8'-2 11.06865
8'-2 8.49166
5'-9½ 22.22774
© M.E.P.CAD, Inc. 12/9/2024 Page 4AutoSPRINK 2022 v17.1.17.0 5:27:41PM
Date: 12/9/2024
Remote Area Number: 1A
Pipe Information
Node 1
Node 2
Nominal ID
Actual ID
Fittings &
Devices
C Factor Total(Pt)
Elev(Pe)
Friction(Pf)
Fitting/Device (Equivalent
Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
NotesFlow added this step
(q)
K-Factor Elev 1
Elev 2 Total Flow
(Q)
Equiv.
Length
(Foot)
(Foot) (Foot)
(Foot)
Length
(Foot)
Fitting
(Foot)
Total (psi)
Pf Friction
Loss Per Unit
5'-0
8'-2 19'-11½ 1.491
8'-2 14'-11½
• • • • • Route 1 • • • • •
(See
Notes)
1.0490
7.000 14.82
0.074703
Sprinkler, 14.82
5.6
T(5'-0)
5'-0
8'-2 9'-1½ 2.577
8'-2 4'-1½
1 (See
Notes)
1.0490
8.491 15.59
0.282545
Flow (q) from Route 3
30.41 T(5'-0)
4'-0
5'-9½ 10'-5
1.026
10.133
8'-2 6'-5
1 (See
Notes)
1.0490
11.068 28.93
0.973019
Flow (q) from Route 2
59.34 2E(2'-0), f(-0.000)
9'-0
3'-0 11'-8
1.214
6.841
5'-9½ 2'-8
1½ (See
Notes)
1.6100
22.227
0.120797
59.34 sCV(9'-0), BFP(-5.432), BV
2'-2½ 0'-9½
0.347
0.029
3'-0 0'-9½
2.0670
30.282
0.035776 59.34
5'-0
-3'-0 13'-7
2.255
0.704
2'-2½ 8'-7
2 (See
Notes)
2.0670
30.657 13.20
0.051877
Flow (q) from Route 5
72.54 E(5'-0)
17'-0
-3'-0 117'-11½
0.000
4.721
-3'-0 100'-11½
2 (See
Notes)
2.0030
33.615
0.040014
72.54 E(11'-0), 2EE(2'-0), Tr(2'-0), GV
15'-0
-3'-0 15'-0 0.114
-3'-0 0'-0
3 (See
Notes)
3.0680
38.336
0.007580
72.54 T(15'-0)
72'-5
-3'-0 313'-4½
-0.000
0.015
-3'-0 240'-11½
8 (See
Notes)
7.9800
38.450
0.000048
72.54 EE(13'-7), GV(6'-0½), T(52'-10
36'-2½
-3'-0 566'-8 0.004
-3'-0 530'-6
12 (See
Notes)
11.6500
38.465
0.000008
72.54 E(36'-2½)
21'-7
-3'-0 271'-7 0.048
-3'-0 250'-0
6 (See
Notes)
6.0900
38.469
0.000178
72.54 E(21'-7)
© M.E.P.CAD, Inc. 12/9/2024 Page 5AutoSPRINK 2022 v17.1.17.0 5:27:44PM1A
Remote Area Number: 1A
Pipe Information
Node 1
Node 2
Nominal ID
Actual ID
Fittings &
Devices
C Factor Total(Pt)
Elev(Pe)
Friction(Pf)
Fitting/Device (Equivalent
Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
NotesFlow added this step
(q)
K-Factor Elev 1
Elev 2 Total Flow
(Q)
Equiv.
Length
(Foot)
(Foot) (Foot)
(Foot)
Length
(Foot)
Fitting
(Foot)
Total (psi)
Pf Friction
Loss Per Unit
0'-0 3'-0
-1.301
0.000
-3'-0 3'-0
6 (See
Notes)
6.3400
38.517
0.000166
72.54 Water Supply
100.00 Hose Allowance At Source
172.54 Route 1Total(Pt)
37.217
5'-0
8'-2 8'-11½ 0.697
8'-2 3'-11½
• • • • • Route 2 • • • • •
(See
Notes)
1.0490
7.311 15.14
0.077770
Sprinkler, 15.14
5.6
T(5'-0)
5'-0
8'-2 11'-10½ 3.060
8'-2 6'-10½
1 (See
Notes)
1.0490
8.008 13.78
0.257537
Flow (q) from Route 4
28.93 T(5'-0)
11.068 Total(Pt) Route 2
5'-0
8'-2 8'-11½ 0.736
8'-2 3'-11½
• • • • • Route 3 • • • • •
(See
Notes)
1.0490
7.755 15.59
0.082129
Sprinkler, 15.59
5.6
T(5'-0)
8.491 Total(Pt) Route 3
8'-2 1'-5½ 0.095
8'-2 1'-5½
• • • • • Route 4 • • • • •
(See
Notes)
1.0490
7.913 13.78
0.065355
Sprinkler
13.78
4.9
8.008 Total(Pt) Route 4
36'-0
2'-2½ 36'-8
0.000
2.211
2'-2½ 0'-8
• • • • • Route 5 • • • • •
(See
Notes)
1.0490
28.446 13.20
0.060331
Hose(31'-0)
13.20 T(5'-0)
30.657 Total(Pt) Route 5
© M.E.P.CAD, Inc. 12/9/2024 Page 6AutoSPRINK 2022 v17.1.17.0 5:27:44PM1A
Remote Area Number: 1A
Equivalent Pipe Lengths of Valves and Fittings (C=120 only)
1.51
Fittings Legend
ALV Alarm Valve AngV Angle Valve b Bushing
BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve
C Cross Flow Turn 90° cplg Coupling Cr Cross Run
CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve
E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow
Ee2 22½° Elbow f Flow Device fd Flex Drop
FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve
Ho Hose Hose Hose HV Hose Valve
Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee
Noz Nozzle P1 Pump In P2 Pump Out
PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve
PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve SFx Seismic Flex Spr Sprinkler
St Strainer T Tee Flow Turn 90° Tr Tee Run
U Union WirF Wirsbo WMV Water Meter Valve
Z Cap
4.87
1.33
1.16
0.713
100Actual Inside Diameter
Schedule 40 Steel Pipe Inside Diameter = Factor
C Value Multiplier
Value Of C
Multiplying Factor
© M.E.P.CAD, Inc. 12/9/2024 Page 7AutoSPRINK 2022 v17.1.17.0 5:27:43PM1A
9' -6
8'-0
7'-0
8' -8
77'-7
9' -1
1½ 21'-5
51'-3½
44'-2
31'-1½
12'-9½
9'-11
27'-6½
2'
-1 1½
4'-0
'-4
'-2
1 2 3 4 5
SEE SITE PLAN
FOR CONT.
LAUNDRY
40'-0
7' -0
8'-0
7' -7
Abbreviated Crosshatch
PATIO
3' -65'-6½ 60
102 103 104
14'-0
1¼ 14'-0
1¼ 2'-0
1¼ 3' -0
3'
-1 1½
1¼ 3'-0½
250'-0
STRAIGHT SAMMY SCREW
Pipe
Sammy XP-20
METAL STRUCTURE
Swivel Ring
3/8 ALL THREAD
XP-20
PIPE TO BE AS TIGHT AS POSSIBLE TO DECK
Sprinkler Legend Symbol Manufacturer SIN Model Quantity K-Factor Type Size Response Finish Temp
Victaulic V2708 V27 3 5.6 Pendent ½ Quick Chrome 155 °F Victaulic V3610 FL-QR/DRY/SW 1 5.6 Sidewall 1 Quick Chrome 155 °F
Total = 4
Wall Post Indicator Assembly FireLock™ Series 775 Butterfly Valve
FLOW SW.
SET TO OPERATE BETWEEN 45-60 SEC
GALV NIPPLE
1-1/4" WATTS BACKFLOW PREVENTER MODEL 2000B-FP
BUTTERBALL VALVES W/TAMPER
1" INSPECTORS TEST AND DRAIN VALVE
ELECTRIC BELL
WIRING BY OTHERS
LOCATE ON EXTERIOR
OF SPRINKLER RM
WITH 1/2" TEST ORIFICE
TERMINATE TO EXTERIOR
1-1/4" TO SYSTEM
1-1/4" RISER CHECK WITH SYS GAUGE
2" GALVANIZED SCH40 PIPING
FROM UNDERGROUND
2x2x1 GALVANIZED TEE FOR DOM CONNECTION
DOM. CONNECTION AND CONTINUATION BY OTHERS
OCCUPANCY GROUP: B
TYPE OF CONSTRUCTION: iib
BUILDING SQ FT:
scope overview:
provide fire sprinkler system for laundry building (converted shipping container)
FP-1 NOTE:
TEXICAN FP TO START 1'-0" AFF
PROJECT SITE PLAN1
FP-1
1/4" = 1'-0"
TYPICAL FLOOR PLAN (BLDG 7)
ALL WIRING BY OTHERS
NOTE:
RISER DETAIL3
NTSFP-1
TEXICAN FP TO START 1'-0" AFF
PHASE II
SECTION
FP-1 NOTE:
1/4" = 1'-0"
SHIPPING CONTAINER STRUCTURE
GYP CELING
LAUNDRY BUILDING
DORMITORY BUILDING
TYP.
(SEPARATE SUBMITTAL)
LAUNDRY IS OH I
HAZARD CLASSIFICATION:
1/16" = 1'-0"
NOTE - INSTALL BETWEEN 3-5' CENTERLINE ABOVE GRADE
USE CHAIN AND LOCK IN-LIEU OF TAMPER SW
WALL MOUNTED POST INDICATOR
ALL UNDERGROUND PIPING IS PVC UNO
GATE VALVE
8X8X3 TEE
3X2 RED
PATIO IS LIGHT HAZARD
GATE VALVE
AND CONTINUE INTO BUILDING
SCH 40 PIPING AT THIS LOCATION
TRANSITION TO GALVANIZED
*INCLUDES 10.66GPM DOM DEMAND
Hydraulic Information Remote Area 1A
OCCUPANCY CLASSIFICATION Ordinary Group I DENSITY (gpm/ft²) 0.15 for 1500 ft² (Actual 336 ft²)
TOTAL HOSE STREAMS 260.66
TOTAL HEADS FLOWING 4
K-FACTOR 5.6
TOTAL WATER REQUIRED 324.71
TOTAL PRESSURE REQUIRED 33.855
SAFETY MARGIN (psi) +14.360 (29.8%)
Supply Flow Test Data Static Pressure 49.000 Residual Pressure: 42.000 Flow 1060.00 Outside Hose Flow 100.00 Test Conducted By RYAN BEAN (TEXARKANA WATER UTIL) Date of Test 7/19/2024
AS-BUILT SUBMITTAL OTHER
N O
DESCRIPTION:
D
AT
E
SCALE: 1/8"=1'-0"
MAX STANDARD SPRINKLER 15X15 SPACING
SITE PLAN & PROJECT INFORMATION
RME-SIGNATURE:
LAUNDRY BLDG - TEXAS A&M
236 E Frank StreetWILLS POINT, TEXAS 75169
(903) 829-6014 Grand Saline, Texas 75140
TEXICAN FIRE PROTECTION, LLC
R
EV
IS
IO
N
SCR-G-2217837
DRAWN BY: JCJ
I HAVE REVIEWED THESE PLANS AND
CERTIFY THAT THEY COMPLY WITH THE
ADOPTED NFPA STANDARDS.
DATE:
149 PRIVATE ROAD 6127
DATE:
PROTECTION
SPRINKLERS SHALL BE LOCATED A MINIMUM OF 4" FROM A WALL
FSR# 04033
RME-
PROVIDE HEAD GUARDS TO SPRINKLERS SUBJECT TO DAMAGE
MATTHEW MEREDITH
CHECKED BY: M.M
TEXICAN FIRE
G-1742566
CONTRACT NAME:
TEXARCANA, TXBY
PRINTED RME NAME:
DWG. NO.: FP-1 OF 11
JC
J 8/
/2
AH
J C
O M
M
EN
TS
/8
/2
JC
J
AH
J
C O
M M
EN
TS
N
EW
W
AT
ER
M
AI
N L
O C
AT
IO
N C
O M
BI
N
ED
F
P
AN
D D
O M
ES
TI
C , A
D D
D O
M D
EM
AN
D T
O C
AL
C
U
LA
TI
O
N S
JC
J
12/9/2024
/9
/2 no fdc required per nfpa 13r (2019) § 6.11.1
NFPA 13 (2019 EDITION)
0.15
BUILDING CODE DATA
MATERIAL NOTES
GENERAL NOTES
FIRE SPRINKLER DESIGN CRITERIA
laundry facility
LOCAL FM
each building - 280 SF wet
1500 sf (entire building)
250gpm + 10.66gpm domestic demand
AUTHORITY HAVING JURISDICTION:
STANDARD:
SYSTEM TYPE:
DENSITY:
AREA OF APPLICATION:
HOSE ALLOWANCE:
FACILITY USAGE:
ADDITIONAL DESIGN NOTES:
1. SYSTEM DESIGN AND INSTALLATION PER NFPA 13 (2019)
2. TEXICAN FIRE PROTECTION IS TO PROVIDE ADEQUATE FIRE PROTECTION THROUGHOUT THE BUILDING.
3. ALL ELECTRICAL WIRING OF DEVICES IS PROVIDED BY OTHERS.
4. FIRE CAULK ALL PIPE PASSING THROUGH RATED ASSEMBLIES.
5. ALL HANGERS TO BE INSTALLED PER NFPA 13 (2019)
6. all pipe and fittings as noted below
7. FLUSHING CONNECTIONS PROVIDED PER NFPA 13
8. ANY MECHANICAL TYPE FITTING CUT INTO EXISTING PIPING ARE TO HAVE CUTOUT DISCS ATTACHED TO THE FITTING IN
ORDER TO VERIFY CUTOUT RETRIEVAL.
9. TEXICAN FIRE PROTECTION IS NOT RESPONSIBLE FOR REMOVAL OR REPLACEMENT OF ACOUSTICAL CEILING TILES OR
CUTTING OR PATCHING OF SHEETROCK CEILINGS.
PIPE:
-New PIPE TO BE SCH 40 BLK STEEL / THREAD ENDS (UNO.)
FITTINGS:
-New FITTINGS TO BE STANDARD WT DUCTILE IRON THREADED FITTINGS (UNO.)
NO SPRINKLERS REQUIRED
FP-1
ROTATED EXTERIOR VIEW
WITH NO ROOF OR DECKING
NOTE:
EXTERIOR PROJECTION IS WOODEN OPEN TRELLIS
NTS
GYP SOFFIT (8" X 8")
DEFLECTOR TO BE < 12" FROM DECK
GEN CONTRACTOR TO PROVIDE
TO CONCEAL PIPING
SCALE: 1/4" = 1'-0"
4 4020
MAXIMUM DISTANCE BETWEEN HANGERS (ft-in.)
15-0
3 1/2"
15-0 5-6
12-0
3-4
6"
12-08-0
N/A 12-0
10-0
N/AN/A
N/A
3-11
15-0
6-0 Copper Tube
5-5 Ductile Iron Pipe
N/A 15-0
Nominal Pipe Size (in.)
N/A Polybutylene (CTS)
3/4"
Polybutylene (IPS) N/A
15-0
N/A
15-0
15-0
9-0 N/A
4-5
12-0
N/A
N/A 15-0N/A
2 1/2"
N/A
N/A
Steel Pipe Except Threaded Lightwall
15-0
15-0
4" 8"1 1/2"
3-9 N/A
15-0
N/A N/A
N/A
12-0
8-0
12-0
N/A7-0
15-0
5-0
12-0
N/A
N/A
CPVC
15-0
5"
N/A
N/A
6-6
N/A N/A
15-0 3"
12-012-0
1"
N/A
N/A
2"
4-7 N/A
1 1/4"
5-11
15-0
8-0
N/A
10-0
15-0
N/A
N/A
N/A
15-0
12-0 N/A
12-0
N/A 15-0
Threaded Lightwall Steel Pipe
N/A 2-11
10-0
Hydraulic Calculations
Location: TEXARCANA, TX, , Project Name: LAUNDRY BLDG - TEXAS A&M
Drawing Name: FP - Laundry Building Calculation Date: 12/9/2024 for
Design
Ordinary Group I
Area of Application: 1500 ft² (Actual 336 ft²)
Coverage per Sprinkler: 98 ft²
Type of sprinklers calculated:
1ARemote Area Number:
Occupancy Classification:
No. of sprinklers calculated:
Density 0.15 gpm/ft²
Pendent, Sidewall
No. of nozzles calculated: 0
In-rack Demand:
Hose Streams: at Node: Type: Allowance at Source
N/Aat Node:N/A gpm
1250.00
10.66 HoseType:62at Node:
(including Hose Streams where applicable):Total Water Required
33.855@324.71From Water Supply at Node 1: (Safety Margin = 14.360)
Type of System:
Volume of Dry/PreAction/Antifreeze/OtherAgent System:N/A
Source: RYAN BEAN (TEXARKANA WATER UTIL)
Location:
7/19/2024Date:for Node: 1
Name of Contractor:
Authority Having Jurisdiction:
Address:
Phone Number:
Name of designer:
N/A N/A Right:Left:Automatic peaking results
Notes:
12/9/2024© M.E.P.CAD, Inc. Page 1AutoSPRINK 2022 v17.1.17.0 6:01:12PM1A
Hydraulic Graph
Water Supply
Node: 1
Job Name: LAUNDRY BLDG - TEXAS A&M
Remote Area Number: 1A Date: 12/9/2024
Summary Sheet
N 1.85
© M.E.P.CAD, Inc. 12/9/2024 Page 2AutoSPRINK 2022 v17.1.17.0 6:01:14PM
Device (gpm)
Actual Flow Minimum Flow
(gpm) (K)
K-Factor
(psi)
Pressure
Summary Of Outflowing Devices Report Description: Ordinary Group I (1A)
Job Number: 6549874
Hose 62 10.66 10.66 0 24.461
Sprinkler 101 16.45 12.00 5.6 8.633
Sprinkler 102 14.82 14.70 5.6 7.000
Sprinkler 103 15.88 14.70 5.6 8.046
Sprinkler 104 16.90 14.70 5.6 9.105
Most Demanding Sprinkler Data
© M.E.P.CAD, Inc. 12/9/2024 Page 3AutoSPRINK 2022 v17.1.17.0 6:01:16PM
Job Name: LAUNDRY BLDG - TEXAS A&M
Remote Area Number: 1A Date: 12/9/2024
Node @ @
Supply Analysis
Static
(psi)
Required Pressure
(psi)(gpm)
Total DemandAvailable
(psi)
Flow
(gpm)
Residual
(psi) Name
42.0001 33.855324.711060.00 48.21649.000Water Supply
Node Analysis
NotesDischarge at
Node
(gpm)
Pressure at
Node
(psi)
Node TypeElevation (Foot)Node Number
0'-0 74.7133.855Supply1
0'-10 10.6624.461Hose62 Hos
8'-2 16.458.633Sprinkler101
8'-2 14.827.000Sprinkler102
8'-2 15.888.046Sprinkler103
8'-2 16.909.105Sprinkler104
-3'-0 35.1042
-3'-0 35.1553
-3'-0 35.1005
-3'-0 35.08913
-3'-0 28.28147
-3'-0 34.96957
8'-2 9.44560
1'-7½ 25.57665
0'-10 25.95066
© M.E.P.CAD, Inc. 12/9/2024 Page 4AutoSPRINK 2022 v17.1.17.0 6:01:19PM
Remote Area Number: 1A
Pipe Information
Node 1
Node 2
Nominal ID
Actual ID
Fittings &
Devices
C Factor Total(Pt)
Elev(Pe)
Friction(Pf)
Fitting/Device (Equivalent
Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
NotesFlow added this step
(q)
K-Factor Elev 1
Elev 2 Total Flow
(Q)
Equiv.
Length
(Foot)
(Foot) (Foot)
(Foot)
Length
(Foot)
Fitting
(Foot)
Total (psi)
Pf Friction
Loss Per Unit
8'-2 14'-0 1.046
8'-2 14'-0
• • • • • Route 1 • • • • •
(See
Notes)
1.0490
7.000 14.82
0.074703
Sprinkler
14.82
5.6
8'-2 14'-0 1.059
8'-2 14'-0
1¼ (See
Notes)
1.3800
8.046 15.88
0.075625
Sprinkler
30.70
5.6
8'-2 2'-0 0.340
8'-2 2'-0
1¼ (See
Notes)
1.3800
9.105 16.90
0.170209
Sprinkler
47.60
5.6
13'-0
1'-7½ 25'-5½
2.833
13.299
8'-2 12'-5½
1¼ (See
Notes)
1.3800
9.445 16.45
0.294796
Flow (q) from Route 2
64.05 2E(3'-0), sCV(7'-0), BFP(-5.79
8), BV
0'-10 0'-8
0.347
0.027
1'-7½ 0'-8
2.0670
25.576
0.041212 64.05
5'-0
-3'-0 12'-2½
1.662
0.668
0'-10 7'-2½
2 (See
Notes)
2.0670
25.950 10.66
0.054791
Flow (q) from Route 3
74.71 E(5'-0)
45'-0
-3'-0 158'-3
0.000
6.689
-3'-0 113'-3
2 (See
Notes)
2.0030
28.281
0.042262
74.71 3E(11'-0), Tr(2'-0), T(10'-0), GV
15'-0
-3'-0 15'-0
-0.000
0.120
-3'-0 0'-0
3 (See
Notes)
3.0680
34.969
0.008006
74.71 T(15'-0)
72'-5
-3'-0 203'-4
-0.000
0.010
-3'-0 130'-11
8 (See
Notes)
7.9800
35.089
0.000050
74.71 EE(13'-7), GV(6'-0½), T(52'-10
36'-2½
-3'-0 566'-8
-0.000
0.005
-3'-0 530'-6
12 (See
Notes)
11.6500
35.100
0.000008
74.71 E(36'-2½)
21'-7
-3'-0 271'-7 0.051
-3'-0 250'-0
6 (See
Notes)
6.0900
35.104
0.000188
74.71 E(21'-7)
© M.E.P.CAD, Inc. 12/9/2024 Page 5AutoSPRINK 2022 v17.1.17.0 6:01:22PM1A
Remote Area Number: 1A
Pipe Information
Node 1
Node 2
Nominal ID
Actual ID
Fittings &
Devices
C Factor Total(Pt)
Elev(Pe)
Friction(Pf)
Fitting/Device (Equivalent
Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
NotesFlow added this step
(q)
K-Factor Elev 1
Elev 2 Total Flow
(Q)
Equiv.
Length
(Foot)
(Foot) (Foot)
(Foot)
Length
(Foot)
Fitting
(Foot)
Total (psi)
Pf Friction
Loss Per Unit
0'-0 3'-0
-1.301
0.001
-3'-0 3'-0
6 (See
Notes)
6.3400
35.155
0.000176
74.71 Water Supply
250.00 Hose Allowance At Source
324.71 Route 1Total(Pt)
33.855
5'-0
8'-2 8'-11½ 0.812
8'-2 3'-11½
• • • • • Route 2 • • • • •
(See
Notes)
1.0490
8.633 16.45
0.090689
Sprinkler, 16.45
5.6
T(5'-0)
9.445 Total(Pt) Route 2
36'-0
0'-10 36'-8 1.489
0'-10 0'-8
• • • • • Route 3 • • • • •
(See
Notes)
1.0490
24.461 10.66
0.040628
Hose(31'-0)
10.66 T(5'-0)
25.950 Total(Pt) Route 3
© M.E.P.CAD, Inc. 12/9/2024 Page 6AutoSPRINK 2022 v17.1.17.0 6:01:22PM1A
Remote Area Number: 1A
Equivalent Pipe Lengths of Valves and Fittings (C=120 only)
1.51
Fittings Legend
ALV Alarm Valve AngV Angle Valve b Bushing
BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve
C Cross Flow Turn 90° cplg Coupling Cr Cross Run
CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve
E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow
Ee2 22½° Elbow f Flow Device fd Flex Drop
FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve
Ho Hose Hose Hose HV Hose Valve
Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee
Noz Nozzle P1 Pump In P2 Pump Out
PIV Post Indicating Valve PO Pipe Outlet PrV Pressure Relief Valve
PRV Pressure Reducing Valve red Reducer/Adapter S Supply sCV Swing Check Valve SFx Seismic Flex Spr Sprinkler
St Strainer T Tee Flow Turn 90° Tr Tee Run
U Union WirF Wirsbo WMV Water Meter Valve
Z Cap
4.87
1.33
1.16
0.713
100Actual Inside Diameter
Schedule 40 Steel Pipe Inside Diameter = Factor
C Value Multiplier
Value Of C
Multiplying Factor
© M.E.P.CAD, Inc. 12/9/2024 Page 7AutoSPRINK 2022 v17.1.17.0 6:01:22PM1A
| A&M DORM FP.pdf |
| CALC.PDF.pdf |
| FP - Laundry Building.pdf |
| CALC.PDF.pdf |
File details come from the government source that posted it. Updated .