Electrical Stamped Drawings GLRR Cistern_Part1.pdf
PDF 1 MB Posted
- Solicitation number
- RFP GCAA 2019000094 4
- Issued by
- Clear Creek County, Denver City, Colorado
About this file
This document is a set of electrical stamped construction drawings for the Devil's Gate Station Cistern project located in Georgetown, Colorado, prepared by electrical engineers and subject to approval by the building department, fire marshal, utility company, and other agencies having jurisdiction. The drawings include general construction notes and legend (E001), lighting plan (E200), power plan (E300), roof plan (E301), electrical one-line diagram (E500), and associated schedules and specifications. The project involves the installation of electrical systems for a cistern addition, including lighting outlets, receptacles, switches, panels, heat trace systems for gutters and downspouts, grounding systems, service entrance metering and disconnect equipment, and associated conduit and wiring infrastructure. The electrical service is specified as single-phase, 120/240V, 100-amp service entrance with a main circuit breaker feeding Panel C (Cistern Panel). The drawings are dated October 23, 2018, and are marked as 100 percent construction documents with review comments dated July 5, 2018.
The electrical contractor is responsible for coordinating all work with the architect, receiving wiring diagrams from system suppliers prior to rough-in, and providing written notification to the architect confirming receipt and review of all diagrams. The contractor must ensure that no additional fees or overtime will be paid for after-hours inspections and bears full responsibility for plan corrections and associated construction costs required by authorities having jurisdiction. Specific construction requirements include use of steel set screw type EMT couplers and connectors in dry locations and steel compression gland types in damp/wet locations; prohibition of MC or AC conduit; identification of switches and receptacles by panel and circuit breaker; and verification of all system and equipment locations through field coordination prior to installation. Underground utilities must be marked by utility companies prior to trenching, and any damaged utilities are the contractor's responsibility to repair or replace.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SC6.21 CONTRACTORS AGREEMENT- DBB A .docx | DOCX document | |
| 2015-026P14 Devil's Gate Station Cistern Intro for bid docs 10.31.2018.pdf | ||
| SC6.23DBB GENERAL CONDITONS.docx | DOCX document | |
| Structural_18001 Devils Gate Cistern 2018-08-10r.pdf | ||
| SC622PerfBond.docx | DOCX document | |
| Civil_Georgetown Loop 8-13-18 a_Part1.pdf | ||
| NOTICE.docx | DOCX document | |
| 17.193 Georgetown Loop Visitor's Center Addition Report 12.08.17 (reduced file size).pdf | ||
| Electrical Stamped Drawings GLRR Cistern_Part2.pdf | ||
| Devil's Gate Cistern Bid Sheet_Oct 2018.pdf | ||
| Architectural_2018 0711 Devil's Gate Cistern_Part1.pdf | ||
| sbp-612_0 Information for Bidders.doc | DOC document | |
| SC6221LMBond.docx | DOCX document | |
| Devil's Gate Station Cistern Q and A.pdf | ||
| sbp-614 Bid Bond.docx | DOCX document | |
| sbp-613 BID.docx | DOCX document | |
| Civil_Georgetown Loop 8-13-18 a_Part2.pdf | ||
| Architectural_2018 0711 Devil's Gate Cistern_Part2.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2015-026P14
02-15-18
JOB
DATE
DRAWN
CHECKED
CAD
WMC
D E
V I L S
G
A T
E
S
T A
T I O
N
C
I S
T E
R N
G E
O R
G E
T O
W N
C
O L O
R A
D O
100% CONSTRUCTION
DOCUMENTS
REVIEW COMMENTS 07/05/18
GENERAL
CONSTRUCTION
NOTES & LEGEND
E001
AutoCAD SHX Text
ELECTRICAL METALLIC TUBING
AutoCAD SHX Text
EMT
AutoCAD SHX Text T
AutoCAD SHX Text
SURGE PROTECTION DEVICE
AutoCAD SHX Text
SPD
AutoCAD SHX Text
METER
AutoCAD SHX Text M
AutoCAD SHX Text R
AutoCAD SHX Text
RELAY
AutoCAD SHX Text
TIME CLOCK
AutoCAD SHX Text
TC
AutoCAD SHX Text
PHASE MONITOR
AutoCAD SHX Text
PH
AutoCAD SHX Text
OR
AutoCAD SHX Text C
AutoCAD SHX Text
CONTACTOR
AutoCAD SHX Text C
AutoCAD SHX Text P
AutoCAD SHX Text
PHOTO CELL - ELECTRIC
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
FLUORESCENT/LED STRIP
AutoCAD SHX Text
LIGHTING OUTLET: WALL MOUNTED
AutoCAD SHX Text
SURGE PROTECTION DEVICE
AutoCAD SHX Text
ELECTRICAL PANEL
AutoCAD SHX Text
TELEPHONE TERMINAL BOARD
AutoCAD SHX Text
PT'S
AutoCAD SHX Text
CT'S
AutoCAD SHX Text
MDP
AutoCAD SHX Text
MAIN DISTRIBUTION PANEL
AutoCAD SHX Text
MAIN CIRCUIT BREAKER
AutoCAD SHX Text
MCB
AutoCAD SHX Text
LTS
AutoCAD SHX Text
LIGHTS
AutoCAD SHX Text
EMERGENCY POWER OFF (MUSHROOM HEAD)
AutoCAD SHX Text
PWR
AutoCAD SHX Text
PT
AutoCAD SHX Text
BOTTOM
AutoCAD SHX Text
BTM
AutoCAD SHX Text
VOLTS-ALTERNATING CURRENT
AutoCAD SHX Text
VAC
AutoCAD SHX Text
VOLT-AMPERES
AutoCAD SHX Text
VA
AutoCAD SHX Text
TIME CLOCK
AutoCAD SHX Text
TC
AutoCAD SHX Text
TELEPHONE TERMINAL BACKBOARD
AutoCAD SHX Text
TTB
AutoCAD SHX Text
MCS
AutoCAD SHX Text
MOLDED CASE SWITCH
AutoCAD SHX Text
PHOTOCELL
AutoCAD SHX Text
PC
AutoCAD SHX Text
ELECTRICAL LEGEND
AutoCAD SHX Text
PUSH BUTTON STATION
AutoCAD SHX Text F
AutoCAD SHX Text
DISCONNECT SWITCH F - FUSED
AutoCAD SHX Text
DISCONNECT SWITCH
AutoCAD SHX Text
THERMOSTAT
AutoCAD SHX Text T
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
J-BOX: CEILING
AutoCAD SHX Text
J-BOX: WALL
AutoCAD SHX Text
DATA/VOICE OUTLET, + 16" AFF TO BOTTOM OF BOX (U.O.N.)
AutoCAD SHX Text
DUPLEX RECEPTACLE, INDIVIDUAL GROUND FAULT RECEPTACLE
AutoCAD SHX Text
DUPLEX RECEPTACLE, + 16" AFF TO BOTTOM OF BOX (U.O.N)
AutoCAD SHX Text
GFI
AutoCAD SHX Text S
AutoCAD SHX Text
SU
AutoCAD SHX Text S
AutoCAD SHX Text
TO
AutoCAD SHX Text
DOUBLE POLE SWITCH, 20 AMP U.O.N.
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
NOTE: ALL SWITCHES SHALL BE MOUNTED AT 48" AFF TO TOP OF BOX (U.O.N.)
AutoCAD SHX Text
MOTOR OUTLET AND CONNECTION
AutoCAD SHX Text
SPECIAL PURPOSE OUTLET AS NOTED, + 16" AFF TO BOTTOM OF BOX (U.O.N.)
AutoCAD SHX Text
SINGLE POLE SWITCH, 20 AMP U.O.N.
AutoCAD SHX Text
SWITCH WITH THERMAL OVERLOAD, 20 AMP U.O.N.
AutoCAD SHX Text
SWITCHED FUSED, 20 AMP U.O.N.
AutoCAD SHX Text
MAGNETIC STARTER OR CONTACTOR
AutoCAD SHX Text
MAIN DISTRIBUTION PANEL
AutoCAD SHX Text
A - PANEL DESIGNATION 1,3,5 - CIRCUIT NUMBER, 6 CONDUCTORS U.O.N.
AutoCAD SHX Text A-1,3,5
AutoCAD SHX Text G
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text
UG
AutoCAD SHX Text
SWITCH AND FUSE
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
HOME RUN
AutoCAD SHX Text
MOISTURE OR EXPLOSION PROOF SEAL
AutoCAD SHX Text
GROUND BUS
AutoCAD SHX Text
UNDERGROUND SECONDARY OR PRIMARY SERVICE
AutoCAD SHX Text
UNDERGROUND TELEPHONE RUN
AutoCAD SHX Text
CIRCUIT RUN: WALLS OR CEILING
AutoCAD SHX Text
CIRCUIT RUN: UNDERGROUND
AutoCAD SHX Text
WEATHERHEAD
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
FLAG NOTE
AutoCAD SHX Text
ELECTRICAL ABBREVIATIONS
AutoCAD SHX Text
AFG
AutoCAD SHX Text
AIC
AutoCAD SHX Text
AL
AutoCAD SHX Text
BFG
AutoCAD SHX Text
BKR
AutoCAD SHX Text C
AutoCAD SHX Text
CB
AutoCAD SHX Text
CKT
AutoCAD SHX Text
CP
AutoCAD SHX Text
CR
AutoCAD SHX Text
CT
AutoCAD SHX Text
CU
AutoCAD SHX Text
DISC
AutoCAD SHX Text
DN
AutoCAD SHX Text
EC
AutoCAD SHX Text
ELEC
AutoCAD SHX Text F.
AutoCAD SHX Text
FLR
AutoCAD SHX Text
FLUOR
AutoCAD SHX Text
GC
AutoCAD SHX Text
GFI
AutoCAD SHX Text
GRC
AutoCAD SHX Text
GRD
AutoCAD SHX Text
HOA
AutoCAD SHX Text
HOR
AutoCAD SHX Text
J-BOX
AutoCAD SHX Text
LTG
AutoCAD SHX Text
LTF
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
WP
AutoCAD SHX Text W
AutoCAD SHX Text
VFD
AutoCAD SHX Text V
AutoCAD SHX Text U.O.N.
AutoCAD SHX Text
TYP
AutoCAD SHX Text
T-STAT
AutoCAD SHX Text
SW
AutoCAD SHX Text
SPR
AutoCAD SHX Text
SPC
AutoCAD SHX Text S/N
AutoCAD SHX Text
SCA
AutoCAD SHX Text
RT
AutoCAD SHX Text
RECEPT, RCPT, REC
AutoCAD SHX Text
PNL
AutoCAD SHX Text
PH
AutoCAD SHX Text
PB
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text N.F.
AutoCAD SHX Text
MTD
AutoCAD SHX Text
MLO
AutoCAD SHX Text
MECH
AutoCAD SHX Text
LIQUID TIGHT FLEXIBLE CONDUIT
AutoCAD SHX Text
LIGHTING
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
HAND-OFF-REMOTE
AutoCAD SHX Text
HAND-OFF-AUTO
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
GALVANIZED RIGID CONDUIT
AutoCAD SHX Text
GROUND FAULT INTERRUPTER
AutoCAD SHX Text
GENERAL CONTRACTOR
AutoCAD SHX Text
FLUORESCENT
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
FUSED
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
ELECTRICAL CONTRACTOR
AutoCAD SHX Text
SOLID NEUTRAL
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SWITCH
AutoCAD SHX Text
THERMOSTAT
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
UNLESS OTHERWISE NOTED
AutoCAD SHX Text
VOLTS
AutoCAD SHX Text
VARIABLE FREQUENCY DRIVE
AutoCAD SHX Text
WATTS
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
ABOVE FINISHED GRADE
AutoCAD SHX Text
AFF
AutoCAD SHX Text
AMP. INTERRUPTING CAPACITY
AutoCAD SHX Text
ALUMINUM
AutoCAD SHX Text
BELOW FINISHED GRADE
AutoCAD SHX Text
BREAKER
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
CIRCUIT
AutoCAD SHX Text
CONTROL PANEL
AutoCAD SHX Text
CONTROL RELAY
AutoCAD SHX Text
COPPER
AutoCAD SHX Text
CURRENT TRANSFORMER
AutoCAD SHX Text
DISCONNECT
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
MAIN LUG ONLY
AutoCAD SHX Text
MOUNTED
AutoCAD SHX Text
NON FUSED
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
PUSH BUTTON
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
POWER
AutoCAD SHX Text
POTENTIAL TRANSFORMER
AutoCAD SHX Text
RECEPTACLE
AutoCAD SHX Text
RAIN TIGHT, NEMA 3R
AutoCAD SHX Text
SHORT CIRCUIT AVAILABLE
AutoCAD SHX Text
GENERAL CONSTRUCTION NOTES
AutoCAD SHX Text ALL PHASES OF THE ELECTRICAL WORK SHALL BE COORDINATED WITH THE ARCHITECT. WORK SHALL BE DONE IN A FASHION TO CAUSE AS LITTLE INCONVENIENCE AS POSSIBLE TO THE OWNER. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO REVIEW ALL DRAWINGS FOR WORK UNDER THIS CONTRACT. THE ELECTRICAL CONTRACTOR SHALL BE ON SITE DURING ALL ELECTRICAL INSPECTIONS. NO ADDITIONAL FEES OR OVERTIME WILL BE PAID FOR AFTER HOURS INSPECTIONS. TERMINATING AND SPLICING: MAKE ALL JOINTS AND SPLICES IN BRANCH CIRCUIT WIRING WITH APPROVED SOLDERLESS TOOL APPLIED OR TWIST-ON CONNECTORS, IN THE VARIOUS BOXES, GUTTERS, AND SIMILAR LOCATIONS, BUT NOT IN RACEWAYS. LEAVE SUFFICIENT SLACK TO PERMIT TWO (2) OR MORE SPLICES OR JOINTS TO BE REMADE IN CASE OF FAULT. MC OR AC CONDUIT WILL NOT BE ALLOWED ON THIS PROJECT. ELECTRICAL CONTRACTOR SHALL RECEIVE, FROM SYSTEM SUPPLIERS, ALL WIRING DIAGRAMS FOR ALL EQUIPMENT, PRIOR TO ANY ROUGH-IN, TO ASSURE PROPER ELECTRICAL CHARACTERISTICS ARE PROVIDED. ELECTRICAL CONTRACTOR SHALL PROVIDE ARCHITECT WRITTEN NOTIFICATION PRIOR TO ROUGH-IN, THAT ALL WIRING DIAGRAMS HAVE BEEN RECEIVED AND REVIEWED FOR CORRECTNESS. ANY INCORRECT WIRING OR DEVICES INSTALLED BY ELECTRICAL CONTRACTOR WITHOUT WIRING DIAGRAMS SHALL BE CORRECTED AT ELECTRICAL CONTRACTOR'S EXPENSE. PROVIDE BLANK COVER PLATES AND INSTALL THEM ON ALL UNUSED ROUGH-INS. INSTALL 6" PIGTAIL AT ALL RECEPTACLES FOR FINAL CONNECTIONS. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. EXACT LOCATION OF ALL SYSTEMS AND EQUIPMENT SHALL BE FIELD VERIFIED AND COORDINATED WITH OTHER TRADES PRIOR TO ANY INSTALLATION. CALL UTILITY COMPANIES (POWER, GAS, WATER, SEWER, TELEPHONE, CABLE TV, ETC.) IN ADVANCE BEFORE TRENCHING FOR THE MARKING OF THEIR UNDERGROUND UTILITIES. ALSO CONTRACTOR SHALL LOCATE ALL ON-SITE UTILITIES SUCH AS SECONDARY SERVICE FEEDERS, UNDERGROUND ELECTRICAL BRANCH CIRCUITS, SPRINKLER LINES, ETC. PRIOR TO TRENCHING. ANY CUT OR DAMAGED UNDERGROUND UTILITIES SHALL BE REPAIRED OR REPLACED AT CONTRACTOR'S EXPENSE. EMT CONDUIT FITTINGS: DRY LOCATIONS ALL EMT COUPLERS AND CONNECTORS SHALL BE STEEL SET SCREW TYPE. DIE CAST FITTINGS SHALL NOT BE USED ON THIS PROJECT. DAMP/WET LOCATIONS, USE STEEL COMPRESSION GLAND TYPE COUPLER AND CONNECTORS. SWITCHES AND RECEPTACLES SHALL BE IDENTIFIED AS TO PANEL AND CIRCUIT BREAKER FED FROM. LABEL COVERPLATE ON FRONT PER SPECIFICATION AND ON BACK WITH PERMANENT INK ENSURE NO BLEED THROUGH. THESE DRAWINGS ARE SUBJECT TO AN APPROVAL OF THE BUILDING DEPARTMENT, FIRE MARSHAL, UTILITY COMPANY, AND OTHER AGENCIES AUTHORITY HAVING JURISDICTION (AHJ). BY THE ACT OF SUBMITTING A BID PROPOSAL FOR WORK, THE CONTRACTOR HAS REVIEWED THE PLANS THOROUGHLY AND ACCEPTS FULL RESPONSIBILITY OF PLAN CORRECTIONS AND ASSOCIATED CONSTRUCTION COSTS REQUIRED BY AHJ.
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text 3.
AutoCAD SHX Text 4.
AutoCAD SHX Text 5.
AutoCAD SHX Text 6.
AutoCAD SHX Text 7.
AutoCAD SHX Text 8.
AutoCAD SHX Text 9.
AutoCAD SHX Text 10.
AutoCAD SHX Text 11.
AutoCAD SHX Text 12.
AutoCAD SHX Text 13.
AutoCAD SHX Text
LOCATION
AutoCAD SHX Text
LOC
AutoCAD SHX Text
SPD
AutoCAD SHX Text
ELECTRICAL DRAWING INDEX
AutoCAD SHX Text
E001 GENERAL CONSTRUCTION NOTES AND LEGENDGENERAL CONSTRUCTION NOTES AND LEGEND
AutoCAD SHX Text
E800 ELECTRICAL SPECIFICATIONSELECTRICAL SPECIFICATIONS
AutoCAD SHX Text
E301 ROOF PLANROOF PLAN
AutoCAD SHX Text
E200 LIGHTING PLANLIGHTING PLAN
AutoCAD SHX Text
E801 ELECTRICAL SPECIFICATIONSELECTRICAL SPECIFICATIONS
AutoCAD SHX Text
E500 ELECTRICAL ONE-LINEELECTRICAL ONE-LINE
AutoCAD SHX Text
E600 ELECTRICAL SCHEDULESELECTRICAL SCHEDULES
AutoCAD SHX Text
HEAT TRACE
AutoCAD SHX Text
HT
AutoCAD SHX Text
E300 POWER PLANPOWER PLAN
AutoCAD SHX Text
E501 ELECTRICAL ONE-LINE SHORT CIRCUITELECTRICAL ONE-LINE SHORT CIRCUIT
AutoCAD SHX Text
AutoCAD SHX Text
6801 W 20TH STREET, UNIT #212
AutoCAD SHX Text
GREELEY, COLORADO 80634
AutoCAD SHX Text
GREELEY: (970) 330-3266
AutoCAD SHX Text
& ASSOCIATES, LLC
AutoCAD SHX Text
ELECTRICAL ENGINEERS
AutoCAD SHX Text G:\Projects 2018\Devils Gate Renovation - Cistern Addition (W) - 18003\Drawings\18003 - E001.dwg Oct 23,2018 - 2:07pm tan
AutoCAD SHX Text
AutoCAD SHX Text 10/23/2018
10 11
2015-026P14
02-15-18
JOB
DATE
DRAWN
CHECKED
CAD
WMC
D E
V I L
T
E
S
T A
T I O
N
C
I S
T E
R N
G E
O R
G E
T O
W N
C
O L O
R A
D O
100% CONSTRUCTION
DOCUMENTS
REVIEW COMMENTS 07/05/18
LIGHTING PLAN
E200
AutoCAD SHX Text
AA
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FLAG NOTES - THIS SHEET ONLY
AutoCAD SHX Text
AutoCAD SHX Text
CONNECT VIA UNSWITCHED PORTION OF LOCAL LIGHTING CIRCUIT.
AutoCAD SHX Text
6801 W 20TH STREET, UNIT #212
AutoCAD SHX Text
GREELEY, COLORADO 80634
AutoCAD SHX Text
GREELEY: (970) 330-3266
AutoCAD SHX Text
& ASSOCIATES, LLC
AutoCAD SHX Text
ELECTRICAL ENGINEERS
AutoCAD SHX Text G:\Projects 2018\Devils Gate Renovation - Cistern Addition (W) - 18003\Drawings\18003 - E200.dwg Oct 23,2018 - 2:07pm tan
AutoCAD SHX Text
AutoCAD SHX Text 10/23/2018
AutoCAD SHX Text
LIGHTING PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text Scale: 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 5'
10'
2015-026P14
02-15-18
JOB
DATE
DRAWN
CHECKED
CAD
WMC
D E
V I L
T
E
S
T A
T I O
N
C
I S
T E
R N
G E
O R
G E
T O
W N
C
O L O
R A
D O
100% CONSTRUCTION
DOCUMENTS
REVIEW COMMENTS 07/05/18
POWER PLAN
E300
AutoCAD SHX Text S
AutoCAD SHX Text
TO
AutoCAD SHX Text
PUMP CONTROL PANEL, NEMA 12
AutoCAD SHX Text
PANEL 'C' NEMA 3R
AutoCAD SHX Text S
AutoCAD SHX Text
TO
AutoCAD SHX Text S
AutoCAD SHX Text
TO
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
BBH
AutoCAD SHX Text
AutoCAD SHX Text
BBH
AutoCAD SHX Text
AutoCAD SHX Text
BBH
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text
UG
AutoCAD SHX Text
METER DISCONNECT AND UTILITY METER
AutoCAD SHX Text S
AutoCAD SHX Text
TO
AutoCAD SHX Text
AutoCAD SHX Text
BBH
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
+36" GFI
AutoCAD SHX Text
NEMA 3R
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
AutoCAD SHX Text
NEMA 12
AutoCAD SHX Text
NEMA 12
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
+24" WP GFI
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FLAG NOTES - THIS SHEET ONLY
AutoCAD SHX Text
AutoCAD SHX Text HEAT TRACE CONTROLLER. SEE HEAT TRACE DETAIL, SHEET E600. PROVIDE WITH CAST METAL WEATHERPROOF WHILE-IN-USE COVER.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
6801 W 20TH STREET, UNIT #212
AutoCAD SHX Text
GREELEY, COLORADO 80634
AutoCAD SHX Text
GREELEY: (970) 330-3266
AutoCAD SHX Text
& ASSOCIATES, LLC
AutoCAD SHX Text
ELECTRICAL ENGINEERS
AutoCAD SHX Text G:\Projects 2018\Devils Gate Renovation - Cistern Addition (W) - 18003\Drawings\18003 - E300.dwg Oct 23,2018 - 2:07pm tan
AutoCAD SHX Text
AutoCAD SHX Text 10/23/2018
AutoCAD SHX Text
POWER PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text Scale: 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 5'
2015-026P14
02-15-18
JOB
DATE
DRAWN
CHECKED
CAD
WMC
D E
V I L
T
E
S
T A
T I O
N
C
I S
T E
R N
G E
O R
G E
T O
W N
C
O L O
R A
D O
100% CONSTRUCTION
DOCUMENTS
REVIEW COMMENTS 07/05/18
ROOF PLAN
E301
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
TO SNOWMELT CONTROLLER
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
HT
AutoCAD SHX Text
HT
AutoCAD SHX Text
HEAT TRACE IN GUTTERS
AutoCAD SHX Text
AutoCAD SHX Text
HEAT TRACE IN DOWN SPOUT
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
WP
AutoCAD SHX Text
FLAG NOTES - THIS SHEET ONLY
AutoCAD SHX Text
AutoCAD SHX Text DOWNSPOUTS AND GUTTERS SHALL BE HEAT TRACED- VERIFY ROUGH-IN LOCATION WITH ARCHITECT PRIOR TO BEGINNING WORK, SEE DETAIL, SHEET E600. ICE SENSOR, SEE HEAT TRACE DETAIL, SHEET E600.
AutoCAD SHX Text
AutoCAD SHX Text
6801 W 20TH STREET, UNIT #212
AutoCAD SHX Text
GREELEY, COLORADO 80634
AutoCAD SHX Text
GREELEY: (970) 330-3266
AutoCAD SHX Text
& ASSOCIATES, LLC
AutoCAD SHX Text
ELECTRICAL ENGINEERS
AutoCAD SHX Text G:\Projects 2018\Devils Gate Renovation - Cistern Addition (W) - 18003\Drawings\18003 - E301.dwg Oct 23,2018 - 2:08pm tan
AutoCAD SHX Text
AutoCAD SHX Text 10/23/2018
AutoCAD SHX Text
ROOF PLAN
AutoCAD SHX Text
NORTH
AutoCAD SHX Text Scale: 1/4"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 5'
2015-026P14
02-15-18
JOB
DATE
DRAWN
CHECKED
CAD
WMC
D E
V I L
T
E
S
T A
T I O
N
C
I S
T E
R N
G E
O R
G E
T O
W N
C
O L O
R A
D O
100% CONSTRUCTION
DOCUMENTS
REVIEW COMMENTS 07/05/18
ELECTRICAL
ONE-LINE
E500
AutoCAD SHX Text
EXISTING PAD MOUNT TRANSFORMER
AutoCAD SHX Text
(2) 3/4" X 10'-0" COPPER GROUND RODS MIN 6'-0" APART
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
BLDG STEEL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COLD WATER PIPE
AutoCAD SHX Text
AutoCAD SHX Text
UFER GROUND PER NEC 250.52A-3
AutoCAD SHX Text
SERVICE GROUND BAR
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ELECTRICAL ONE-LINE
AutoCAD SHX Text
N.TS.
AutoCAD SHX Text
SECONDARY VOLTAGE 120/240V, 1PH, 3W
AutoCAD SHX Text
100/2 100A FRN-R SERVICE ENTRANCE METER/DISCONNECT
AutoCAD SHX Text
100/3 MCB
AutoCAD SHX Text
CISTERN PANEL 'C'
AutoCAD SHX Text 7,032
AutoCAD SHX Text
SCA @240 =
AutoCAD SHX Text X
AutoCAD SHX Text NOTE: INITIAL SCA FROM EXCEL DATA. NOTIFY ENGINEER OF ANY DISCREPANCIES IMMEDIATELY
AutoCAD SHX Text 22,000 @ 240V
AutoCAD SHX Text
SCA =
AutoCAD SHX Text X
AutoCAD SHX Text 32,600 @ 120V
AutoCAD SHX Text
AutoCAD SHX Text 30/2
AutoCAD SHX Text 4,461
AutoCAD SHX Text
SCA @120 =
AutoCAD SHX Text X
AutoCAD SHX Text 6,509
AutoCAD SHX Text
SCA @240 =
AutoCAD SHX Text X
AutoCAD SHX Text 4,048
AutoCAD SHX Text
SCA @120 =
AutoCAD SHX Text X
AutoCAD SHX Text 4,191
AutoCAD SHX Text
SCA @240 =
AutoCAD SHX Text X
AutoCAD SHX Text 2,398
AutoCAD SHX Text
SCA @120 =
AutoCAD SHX Text X
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text (3 #1 XHHW CU) 1 1/2"C. (#6 CU GRD) 3/4"C. (3 #1 THWN CU & #8 CU GRD) 2"C. (2 #10 CU & #10 CU GRD) 3/4"C.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
FEEDER SCHEDULE
AutoCAD SHX Text
KEY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
6801 W 20TH STREET, UNIT #212
AutoCAD SHX Text
GREELEY, COLORADO 80634
AutoCAD SHX Text
GREELEY: (970) 330-3266
AutoCAD SHX Text
& ASSOCIATES, LLC
AutoCAD SHX Text
ELECTRICAL ENGINEERS
AutoCAD SHX Text G:\Projects 2018\Devils Gate Renovation - Cistern Addition (W) - 18003\Drawings\18003 - E500.dwg Oct 23,2018 - 2:08pm tan
AutoCAD SHX Text
10/23/2018
| Sheets and Views |
| 1 18003 - E001 - E001 |
| 2 18003 - E200 - E200 |
| 3 18003 - E300 - E300 |
| 4 18003 - E301 - E301 |
| 5 18003 - E500 - E500 |
File details come from the government source that posted it. Updated .