Attachment 15 - Hangar 8 E Addendum 2.pdf

PDF 114 KB Posted

Attached to
CONSTRUCTION: Hangar 08 & 09 Mechanical Upgrades at the Mike Monroney Aeronautical Center, Oklahoma City, OK
Solicitation number
DTFAAC-17-R-00023
Issued by

About this file

Attachment 15 - Hangar 8 E Addendum 2 (pdf)

View the file

Other files

File Type Posted
ATTACHMENT 7 CONTRACTOR'S RELEASE.doc DOC document
Attachment 27 - 232500 fl - HVAC water treatment.pdf PDF
ATTACHMENT 6 SF25A.doc DOC document
SIR/RFO DTFAAC-17-R-00023.pdf PDF
Attachment 22 - Title Sheet.pdf PDF
ATTACHMENT 8 OPERATIONAL CONTROL DOCUMENTS.pdf PDF
Attachment 18 - M4-01 - Hangar 8 Details & Schedules.pdf PDF
Attachment 13 - Addendum 2.pdf PDF
ATTACHMENT 9 DBA WAGE DETERMINATION.pdf PDF
Attachment 20 - Section 237313 - Central Station Air Handling Units.pdf PDF
Attachment 28 - 236514.13 fl - open-circuit, induced-draft, counterflow cooling towers.pdf PDF
Pre-Proposal Conference Sign-In Sheet.pdf PDF
ATTACHMENT 3 DRAWINGS.pdf PDF
ATTACHMENT 4 CHAPTER 33.pdf PDF
Amendment 0001.pdf PDF
Attachment 17 - M2-01 - Hangar 9 Site Plan and First Floor Plan.pdf PDF
ATTACHMENT 12 CLIENT AUTHORIZATION LETTER.docx DOCX document
ATTACHMENT 10 PAST PERFORMANCE EXPERIENCE FORM.pdf PDF
Amendment 000002.pdf PDF
Attachment 23 - Addendum 3.pdf PDF
Attachment 30 - Hangar 9 M Addendum 3.pdf PDF
Attachment 29 - Hangar 9 E Addendum 3.pdf PDF
ATTACHMENT 5 SF25.pdf PDF
ATTACHMENT 2 SPECIFICATIONS.pdf PDF
Attachment 15 - Hangar 8 E Addendum 2.pdf PDF
Attachment 19 - Section 232113-Hydronic Piping.pdf PDF
Amendment 0003.pdf PDF
Attachment 21 - Section 237416.13-Packaged, Large-Capacity, Rooftop Air-Conditioning Units.pdf PDF
Amendment 0004.pdf PDF
Attachment 26 - 232123 FL Hydronic Pumps.pdf PDF
Attachment 14 - 16-044 Addendum #2.pdf PDF
Attachment 16 - Hangar 9 E Addendum 2.pdf PDF
ATTACHMENT 1 SECTION B SUPPLIES OR SERVICES-PRICES.xlsx XLSX spreadsheet
Attachment 24 - 16-044 Addendum #3.pdf PDF
Attachment 25 - 230719 fl - hvac piping insulation.pdf PDF
ATTACHMENT 11 PAST PERFORMANCE SURVEY.pdf PDF
Attachment 13 - Addendum 2.pdf PDF
Attachment 22 - Title Sheet.pdf PDF
ATTACHMENT 6 SF25A.doc DOC document
ATTACHMENT 12 CLIENT AUTHORIZATION LETTER.docx DOCX document
ATTACHMENT 9 DBA WAGE DETERMINATION.pdf PDF
Attachment 25 - 230719 fl - hvac piping insulation.pdf PDF
Attachment 19 - Section 232113-Hydronic Piping.pdf PDF
Attachment 29 - Hangar 9 E Addendum 3.pdf PDF
Attachment 24 - 16-044 Addendum #3.pdf PDF
Attachment 26 - 232123 FL Hydronic Pumps.pdf PDF
ATTACHMENT 5 SF25.pdf PDF
ATTACHMENT 3 DRAWINGS.pdf PDF
Attachment 30 - Hangar 9 M Addendum 3.pdf PDF
ATTACHMENT 8 OPERATIONAL CONTROL DOCUMENTS.pdf PDF
Show 40 more

Latest 50 of 174 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G

SC

J J J

F F F

SIMPLEX RECEPTACLE, NEMA 5-20R

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER

WEATHERPROOF DUPLEX RECEPTACLE WITH GROUND FAULT CIRCUIT INTERRUPTER

ELECTRICAL RECEPTACLE AT SPECIFIED HEIGHT

ELECTRICAL RECEPTACLE AT 2" ABOVE COUNTER OR BACKSPLASH

SPECIAL PURPOSE OUTLET WITH CONFIGURATION SHOWN ON PLANS PER NEMA

WD-6.

SIMPLEX FLOOR RECEPTACLE, NEMA 5-20R

DUPLEX FLOOR RECEPTACLE

QUADRUPLEX FLOOR RECEPTACLE

SPECIAL PURPOSE FLOOR OUTLET WITH CONFIGURATION SHOWN ON PLANS PER

NEMA WD-6.

DUPLEX CEILING RECEPTACLE

RECEPTACLE SYMBOLS

WP

44"

C

CONDUIT, BELOW GRADE OR FLOOR SLAB

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT TERMINATED AND CAPPED

CONDUIT CONTINUES AS INDICATED

JUNCTION BOX, MOUNTED ABOVE CEILING, WALL MOUNTED, OR

FLOOR MOUNTED

FURNITURE CONNECTION JUNCTION BOX, MOUNTED ABOVE CEILING, WALL

MOUNTED, OR FLOOR MTD

POWER POLE

HOME RUN, MIN 3/4" CONDUIT CONTAINING 2#12 AWG CU CONDUCTORS

PER

CIRCUIT AND 1#12 AWG CU GROUND, UNO

BRANCH CIRCUIT. SLASHES INDICATE THE NUMBER OF CONDUCTORS. MIN

3/4"

CONDUIT, 1#12 GND, 1#12 PH, 1#12 NEU CU, UNO

SPLIT CIRCUIT

CONDUIT & WIRING SYMBOLS

GROUNDING & LIGHTNING PROTECTION

T

GROUND LOOP CONDUCTOR, 2/0 AWG BARE CU, UNO,

BURIED MINIMUM 30" BELOW FINISHED GRADE.

EXOTHERMIC WELD CONNECTION

LIGHTNING PROTECTION MAIN CONDUCTOR

LIGHTNING PROTECTION CABLE CONNECTION

COPPER-CLAD GROUND ROD, 3/4" DIA X 10' L, DRIVEN 6"

BELOW FINISHED GRADE

LIGHTNING PROTECTION AIR TERMINAL

GROUND ELECTRODE

THRU ROOF UNIT WITH CABLE RUNNING TO LOWER LEVEL

THRU ROOF UNIT WITH CABLE RUNNING CONCEALED TO

GROUND ELECTRODE

COPPER GROUND BUS BAR ON INSULATED STANDOFF

INSULATORS

GROUND TEST WELL

LIGHTING SYMBOLS

CEILING LIGHT FIXTURE, 2' X 4', RECESSED OR SURFACE

MOUNTED AS SCHEDULED

CEILING LTG FIXTURE, 2' X 4', RECESSED OR SURFACE MTD

AS SCHEDULED, W/ EMERGENCY BATTERY PACK

CEILING LIGHT FIXTURE, 2' X 2', RECESSED OR SURFACE

MOUNTED AS SCHEDULED

CEILING LIGHT FIXTURE, 2' X 2', RECESSED OR SURFACE

MTD AS SCHEDULED, W/ EMERGENCY BATTERY PACK

LINEAR CEILING LIGHT FIXTURE, RECESSED OR SURFACE

MOUNTED AS SCHEDULED

LINEAR CEILING LIGHT FIXTURE, RECESSED OR SURFACE

MTD AS SCHED, W/ EMER BATTERY PACK

LINEAR LIGHT FIXTURE, WALL MOUNTED

LINEAR LIGHT FIXTURE, WALL MOUNTED, WITH

INTEGRAL EMERGENCY BATTERY PACK

STRIP LIGHT FIXTURE, SURFACE MOUNTED

STRIP LIGHT FIXTURE, SURFACE MOUNTED, WITH

INTEGRAL EMERGENCY BATTERY PACK

DOWNLIGHT FIXTURE, RECESSED

DOWNLIGHT FIXTURE, RECESSED, WITH INTEGRAL

EMERGENCY BATTERY PACK

LIGHT FIXTURE, WALL MOUNTED

LIGHT FIXTURE, WALL MOUNTED, WITH INTEGRAL

EMERGENCY

PENDANT LIGHT FIXTURE

RECESSED WALL WASH LIGHT FIXTURE

EMERGENCY DUAL-HEAD LIGHT FIXTURE, WALL MTD, WITH

INTEGRAL EMERGENCY BATTERY PACK

EXIT LIGHTING W/ DIRECTIONAL ARROWS, CEILING

MOUNTED. DARKENED SECTION(S) DENOTE FACE(S)

EXIT LIGHTING W/ DIRECTIONAL ARROWS, WALL

MOUNTED. DARKENED SECTION(S) DENOTE FACE(S)

POLE AND POLE MOUNTED EXTERIOR LIGHT FIXTURE

EXTERIOR LIGHT FIXTURE

EXISTING POLE AND POLE MOUNTED EXTERIOR LIGHT

FIXTURE

EXISTING EXTERIOR LIGHT FIXTURE

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

GENERAL NOTES:

1. PROVIDE A COMPLETE, OPERATIONAL AND TESTED ELECTRICAL SYSTEM. FURNISH AND INSTALL THE INDICATED LISTED AND TESTED EQUIPMENT AND SYSTEMS, COMPLETE WITH FINAL ELECTRICAL POWER AND

CONTROL CONNECTIONS. PROVIDE SPECIFICATION GRADE EQUIPMENT, UNLESS NOTED OTHERWISE.

2. MATERIALS PROVIDED IN THIS PROJECT SHALL BE NEW, UNLESS NOTED OTHERWISE.

3. WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE CURRENT EDITIONS BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION OF THE NATIONAL ELECTRICAL CODE, THE NATIONAL ELECTRICAL

SAFETY CODE, AND APPLICABLE LOCAL, STATE, AND FEDERAL CODES AND ORDINANCES.

4. INSTALLATION SHALL BE ACCORDING TO THE ACCEPTED INDUSTRY PRACTICES DESCRIBED IN NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION STANDARD ANSI/NECA 1-2015.

5. NOTIFY THE ELECTRIC UTILITY OF THIS PROJECT AND ARRANGE FOR INCOMING SERVICE. OBTAIN ANY REQUIRED INSTALLATION DETAILS. OBTAIN AND PAY THE FEES FOR THE REQUIRED ELECTRICAL PERMITS AND

CERTIFICATES.

6. COORDINATE THE EXACT LOCATION OF EQUIPMENT TO BE INSTALLED WITH OTHER TRADES FOR PROPER CLEARANCES.

7. COORDINATE POWER REQUIREMENTS FOR MECHANICAL EQUIPMENT PRIOR TO FINAL ROUGH IN AND INSTALLATION. LOCATE ROOF PENETRATIONS PER THE MANUFACTURER’S INSTALLATION INSTRUCTIONS.

REFER TO ARCHITECTURAL FOR ROOF PENETRATION REQUIREMENTS.

8. INSTALLATION OF MECHANICAL SYSTEMS, PLUMBING, AND FIRE-SUPPRESSION SYSTEMS HAVE PRIORITY OVER THE ELECTRICAL INSTALLATION. YIELD TO CONFLICTS WITH THEM AT NO ADDITIONAL COST TO THE

OWNER.

9. REFER TO THE MECHANICAL SHEETS FOR CONTROL DIAGRAMS AND WIRING TO THEIR EQUIPMENT.

10. REPLACE, AT NO ADDITIONAL EXPENSE TO THE OWNER, ANY ITEM THAT IS MARRED, DEFACED, OR BROKEN PRIOR TO ACCEPTANCE BY OWNER. AS AN ALTERNATE, REMEDIATION BY TOUCH-UP OR REFINISHING IS

AT THE SOLE DISCRETION OF THE ARCHITECT.

11. ELECTRICAL PLANS ARE DIAGRAMMATIC; FOLLOW THEM AS CLOSELY AS ACTUAL CONDITIONS WILL ALLOW. THE APPROVAL OF THE ARCHITECT MUST BE OBTAINED BEFORE DEVIATIONS FROM THESE PLANS ARE

MADE.

12. VERIFY FIELD CONDITIONS BEFORE BEGINNING WORK.

13. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION.

14. INFORM THE ARCHITECT OF EXISTING CONDITIONS THAT ARE DISCOVERED DURING WORK IN PROGRESS THAT WOULD REQUIRE DEVIATIONS AND ADDITIONAL COSTS FROM THE ORIGINAL CONSTRUCTION

DOCUMENTS BEFORE PROCEEDING WITH WORK.

15. WHERE DEVICES ARE SHOWN SIDE BY SIDE CONTROLLING DIFFERENT VOLTAGES, OR WHERE NORMAL AND EMERGENCY SYSTEMS ARE PRESENT, PROVIDE SEPARATE BOXES AND PLATES. DO NOT RUN

EMERGENCY POWER SYSTEMS IN THE SAME RACEWAYS AS NORMAL POWER SYSTEMS.

16. COORDINATE MOUNTING OF OUTLETS OVER COUNTERS WITH ARCHITECTURAL ELEVATIONS BEFORE INSTALLATION.

17. PROVIDE PVC COATED OR TAPED RGS ELBOWS WHERE STUBBED UP THROUGH SLAB. EXPOSED EXTERIOR CONDUIT MUST BE RGS, RMC OR SCHEDULE 40 PVC, UNLESS NOTED OTHERWISE.

18. DEVICES AND APPLIANCES SHALL BE UL LISTED AND SUITABLE FOR THE USE INTENDED.

19. ELECTRICAL EQUIPMENT SHALL BE IDENTIFIED WITH LAMINATED MELAMINE PLASTIC NAMEPLATES, WHITE WITH BLACK CENTER CORE, MINIMUM SIZE 1 BY 2.5 INCHES. ENGRAVE INTO THE CORE MINIMUM ¼”

NORMAL BLOCK STYLE LETTERING.

20. LABEL BACK SIDE OF COVER PLATES OF RECEPTACLES WITH THE CIRCUIT NUMBER SERVING THE DEVICE. PERMANENTLY MARK JUNCTION BOXES WITH CIRCUIT NUMBERS ON THE OUTSIDE OF THE BOX WHEN

ABOVE CEILING AND LABEL ON THE INSIDE OF THE BOX WHEN CONCEALED IN WALL. CONDUIT CONTAINING CIRCUITS FOR THE EMERGENCY SYSTEM SHALL BE MARKED ACCORDINGLY.

21. CONDUIT STUB-UPS FOR SPECIAL SYSTEMS AND OTHER EQUIPMENT MUST HAVE ROUNDED PROTECTIVE BUSHINGS AT THE TOP OF CONDUIT. PROVIDE PULL WIRES IN EMPTY CONDUIT RESERVED FOR FUTURE

INSTALLATION.

22. WHERE TRANSFORMERS HAVE IMPEDANCES SPECIFIED, THE INTERRUPTING CAPACITY OF THE DOWNSTREAM EQUIPMENT HAS BEEN CALCULATED ACCORDINGLY. IF THE MANUFACTURER HAS PROVIDED A

TRANSFORMER OUTSIDE OF NORMAL IMPEDANCE TOLERANCES (+/- 7.5%), THE DOWNSTREAM EQUIPMENT MAY NOT HAVE SUFFICIENT INTERRUPTING CAPACITY. CONTACT THE ARCHITECT BEFORE

PROCEEDING WITH WORK ON THE AFFECTED EQUIPMENT.

23. PROVIDE PULL-BOXES, SUPPORTS, HANGERS AND OTHER NECESSARY ACCESSORIES FOR A COMPLETE INSTALLATION. ADJUST WIRING SIZES AND PROTECTIVE DEVICES AS NECESSARY TO SUPPORT THE

REQUIREMENTS OF THE SUPPLIED EQUIPMENT. IF THE SUPPLIED EQUIPMENT DIFFERS FROM THE BASIS OF DESIGN, PROVIDE REVISED WIRING AND PROTECTIVE DEVICES AT NO ADDITIONAL COST.

24. CONDUIT MUST BE CONCEALED IN FINISHED SPACES, UNLESS NOTED OTHERWISE. CONDUIT MAY BE EXPOSED IN EXISTING SPACES, UNLESS NOTED OTHERWISE. CONDUIT MUST BE CONCEALED ON EXTERIOR

WALLS UNLESS OTHERWISE EXPRESSLY PERMITTED BY THE ARCHITECT.

25. COORDINATE WITH THE ARCHITECT COLOR SELECTIONS OF COVER PLATES; RECEPTACLE BODIES; SWITCH BODIES; AND ELECTRICAL EQUIPMENT IN FINISHED SPACES.

26. UPDATE CIRCUIT DIRECTORIES AFFECTED BY THIS PROJECT WITH TYPED ENTRIES. HAND LETTERING IS UNACCEPTABLE.

27. MINIMUM WIRING IS #12 AWG CU WITH THHN/THWN-2 INSULATION IN 3/4” TRADE SIZE CONDUIT, UNLESS NOTED OTHERWISE. TYPE MC CABLE MAYBE USED WITH PRIOR WRITTEN APPROVAL OF THE ARCHITECT IF

THE COST SAVINGS ARE JUSTIFIED.

28. PATCH AND REPAIR PENETRATIONS REQUIRED BY THE WORK. WIRING PENETRATIONS THROUGH FIRE RATED WALLS & FLOORS SHALL UTILIZE UL APPROVED FIRESTOP SEALANT AT FIREWALL PENETRATIONS IN

ACCORDANCE WITH APPLICABLE UL ASSEMBLIES. IF A PRODUCT DOES NOT HAVE A UL LISTED SYSTEMS DESIGN TO COVER A SPECIFIC APPLICATION, THE PRODUCT CANNOT BE USED FOR THAT APPLICATION.

29. DO NOT CUT STRUCTURAL ELEMENTS WITHOUT PRIOR APPROVAL OF THE ARCHITECT.

30. WIRE-PULLING COMPOUNDS SHALL BE UL 267 LISTED.

31. MULTIWIRE CIRCUITS (SHARED NEUTRALS) ARE NOT PERMITTED.

32. PROVIDE EXPANSION JOINT FITTINGS AT EXPANSION JOINTS AND SECURE AT BOTH ENDS OF THE JOINT.

33. LOW VOLTAGE WIRING NOT RUN IN CABLE TRAY MUST BE SUPPORTED BY J-HOOKS MOUNTED ON WALLS ABOVE THE CEILING OR SUSPENDED FROM STRUCTURE. PROVIDE J-HOOK SUPPORTS MIN 3 FT OC.

ELECTRICAL ABBREVIATIONS:

A

A AMPERE

AC ALTERNATING CURRENT

ACB AIR CIRCUIT BREAKER

ACS ACCESS CONTROL SYSTEM

ACT ACOUSTICAL CEILING TILE

ADDL ADDITIONAL

ADJ ADJACENT

AF AMPERE FRAME

AFC AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERES INTERRUPTING

CAPACITY, SYMMETRICAL

ALUM ALUMINUM

APPROX APPROXIMATE

ARCH ARCHITECT/ARCHITECTURAL

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

B

BKBD BACKBOARD

BKR BREAKER

BLDG BUILDING

BMS BALANCED MAGNETIC SWITCH

BSMT BASEMENT

C

C CONDUIT

CAB CABINET

CAT 6 4 PAIR, CATEGORY 6 UTP CABLE

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCT CIRCUIT

CCTV CLOSED CIRCUIT TELEVISION

CD CABLE DUCT/CANDELA

CER COMMUNICATIONS

EQUIPMENT ROOM

CFCI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CFL COMPACT FLUORESCENT

CLG CEILING

CLR CLEAR

CMH COMMUNICATIONS

MAINTENANCE HOLE

CNTL CONTROL

COL COLUMN

COMM COMMUNICATIONS

CONC CONCRETE

CONF CONFERENCE

CONT CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

CORR CORRIDOR

CP CONTROL PANEL

CR CONTROL

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

D

D DEPTH/DIMMER

DB DECIBEL

DBL DOUBLE

DEG DEGREE

DEMARC DEMARCATION

DEMO DEMOLITION

DEPT DEPARTMENT

DE DETAIL

DIA DIAMETER

DIM DIMENSION

DIST DISTRIBUTION

DS DISCONNECT SWITCH

DWG DRAWING

E

E EAST

EES EARTH ELECTRODE SYSTEM

EF ENTRANCE FACILITY

ELEC ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ENGR ENGINEER

EO ELECTRICALLY OPERATED

EPO EMERGENCY POWER OFF

EQ EQUAL

EQUIP EQUIPMENT

EQUIV EQUIVALENT

EXIST EXISTING

EXT EXTERIOR

F

FA FIRE ALARM

FCU FAN COIL UNIT

FLR FLOOR

FMC FLEXIBLE METAL CONDUIT

FOC FIBER OPTIC CABLE

FS FLOW SWITCH

FT FEET/FOOT

FU FUSE

FV FIELD VERIFY

G

GA GAUGE

GALV GALVANIZED

GEN GENERATOR/GENERAL

GF GROUND FAULT

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GND GROUND

H

HH HAND HOLE

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC SWITCH

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HR HOUR

HT HEIGHT

I

IBC INTERNATIONAL BUILDING CODE

IC INTERMEDIATE CROSS-CONNECT

IDC INSULATION DISPLACEMENT

CONNECTOR

IDF INTERMEDIATE DISTRIBUTION FRAME

IDS INTRUSION DETECTION SYSTEM

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IN INCH/INCHES

INST INSTANTANEOUS

J

J-BOX JUNCTION BOX

K

KA KILOAMPERE

KAIC THOUSAND AMPERES

INTERRUPTING CAPACITY

SYMMETRICAL

KCMIL THOUSAND CIRCULAR MILLS

KS KEY SWITCH

KV KILOVOLT

KVA KILOVOLT-AMPERE

KW KILOWATT

L

L LENGTH

LA LIGHTNING ARRESTER

LAN LOCAL AREA NETWORK

LBS POUND/POUNDS

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/LINEAR FOOT

LFMC LIQUID-TIGHT FLEXIBLE

METAL CONDUIT

LTG LIGHTING

M

M METER

MAINT MAINTENANCE

MAX MAXIMUM

MC METAL-CLAD CABLE

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MECH MECHANICAL

MEZZ MEZZANINE

MFD MANUFACTURED

MFR MANUFACTURER

MH METAL HALIDE/MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MM MULTIMODE FIBER

MMS MANUAL MOTOR STARTER

MOCP MAXIMUM OVERCURRENT

PROTECTION

MTD MOUNTED

MTR MOTOR

MTS MANUAL TRANSFER SWITCH

N

N NORTH

NA NOT APPLICABLE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NESC NATIONAL ELECTRICAL SAFETY CODE

NEU NEUTRAL

NF NON-FUSED

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER/NORMALLY OPEN

NOM NOMINAL

NTS NOT TO SCALE

O

OC ON CENTER/OVERCURRENT

OD OUTSIDE DIAMETER

OH OVERHEAD

OPER OPERATOR

OPT OPTIONAL

OSP OUTSIDE PLANT

OZ OUNCE/OUNCES

P

P POLE

PB PUSHBUTTON/PULLBOX

PC PHOTOELECTRIC CELL

PCU PREMISE CONTROL UNIT

PF POWER FACTOR

PH PHASE

PN PART NUMBER

PNL PANEL

PNLBRD PANELBOARD

PR PAIR

PT POINT

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT POTENTIAL TRANSFORMER

PTZ PAN, TILT, ZOOM

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

Q

Q QUANTITY

R

R RADIUS

REF REFERENCE

REQD REQUIRED

RCP REFLECTED CEILING PLAN

RFI REQUEST FOR INTERPRETATION

RGS GALVANIZED STEEL RMC

RM ROOM

RMC RIGID METAL CONDUIT

RTU ROOF TOP UNIT

RU RACK UNIT

S

S SOUTH

SA SURGE ARRESTER

SC SPLIT CIRCUIT

SCHED SCHEDULE/SCHEDULED

SCTP SCREENED TWISTED PAIR

SF SQUARE FOOT/SQUARE FEET

SHFT SHAFT

SHLD SHIELDED

SIM SIMILAR

SM SINGLE MODE FIBER

SPD SURGE PROTECTIVE DEVICE

SPEC SPECIFICATION

SQIN SQUARE INCH

STD STANDARD

STP SHIELDED TWISTED PAIR

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

T

TB TERMINAL BOARD

TC TERMINAL CABINET

TD TIME DELAY

TEL TELEPHONE

TEMP TEMPORARY

TGB TELECOMMUNICATIONS

GROUNDING BUSBAR

THK THICKNESS/THICK

THRU THROUGH

TMGB TELECOMMUNICATIONS

MAIN GROUNDING BUSBAR

TR TELECOMMUNICATIONS ROOM

TV TELEVISION

TYP TYPICAL

U

UC UNDER COUNTER

UL UNDERWRITERS LABORATORIES

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTABLE POWER SUPPLY

UTIL UTILITY

UTP UNSHIELDED TWISTED PAIR

V

V VOLT

VAR VARIES

VCB VACUUM CIRCUIT BREAKER

VER VERIFY

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W

W WEST/WIRE/WATT/WIDTH

W/ WITH

W/O WITHOUT

WP WATERPROOF

WT WEIGHT

X

XFMR TRANSFORMER

XP EXPLOSION PROOF

N O

T

FO

R

CONST RUCT ION

NOT FOR CONST

R U C

T I O

N

R E V

IE

W

S ET

REV

IEW

S

ET

THIS

DOCUMENT IS

PRELIMINARY IN

NATURE AND IS NOT

A FINAL, SIGNED

AND SEALED

DOCUMENT

920 W. Main

Oklahoma City, Oklahoma 73106 phone: 405.232.5700 web: www.adgokc.com

ADG

CA: #6447 Exp. 6/18

DESIGNED

WORK ORDER NO.

DRAWN

ISSUED BY OFFICE OF: DATE:

PREPARED BY

REV DATE

APPROVED BY

DESCRIPTION APP'DCHECK

OF2014-014040

REVIEWED BY

DRAWING NO.

MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA

FACILITY MANAGEMENT

AMP-400

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

SMALL ARCHITECTS MARK McDANIEL

SENSITIVE SECURITY INFORMATION WARNING:

This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S.

government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.

E0.00

ELECTRICAL LEGENDS, ABBREVIATIONS, AND INDEX

MAY 11, 2017MJN

RJV

MJN

009-H08 & 010-H09

HANGARS 8 & 9

MECHANICAL UPGRADES

SHEET INDEX

009-H08

E0.00 ELECTRICAL LEGENDS, ABBREVIATIONS, AND INDEX

E2.01 HANGAR 8 ELECTRICAL FIRST FLOOR PLAN

E2.03 HANGAR 8 ELECTRICAL THIRD FLOOR PLAN

E2.08 HANGAR 8 ELECTRICAL ROOF PLAN

E5.01 FEEDER SCHEDULE

E6.01 HANGAR 8 PANELBOARD SCHEDULES

E6.02 HANGAR 8 PANELBOARD SCHEDULES

E6.03 HANGAR 8 PANELBOARD SCHEDULES

010-H09

E2.10 HANGAR 9 FIRST FLOOR POWER PLAN

E2.11 HANGAR 9 SWITCHGEAR INFORMATION

E2.20 HANGAR 9 PENTHOUSE TO ROOF ELECTRICAL PLAN

E4.10 HANGAR 9 ELECTRICAL ROOF PLAN

E6.10 HANGAR 9 PANELBOARD SCHEDULES

1 8/14/2017 Addendum #2 MJN MJN

Sheets
E0.00 - ELECTRICAL LEGENDS, ABBREVIATIONS, AND INDEX