This document is a structural design criteria and general notes sheet for the Natchez Maintenance Facility Renovation project, prepared by Henry Adams, LLC (Baltimore, MD) and Walker Architects (Gainesville, FL). The sheet establishes design standards and construction requirements for masonry reinforcement layout and related structural elements.
The masonry construction specifications require ASTM C90 hollow concrete masonry units with ASTM C270 Type "S" mortar and ASTM C476 grout with 3000 PSI compressive strength. Vertical reinforcement must be ASTM A615 Grade 60 steel (or ASTM A706 for welded applications per AWS D1.4), with specified lap lengths ranging from 16 inches for #3 bars to 63 inches for #7 bars depending on CMU width. Horizontal joint reinforcement must be installed at 16 inches on center vertically with at least two W1.7 wires minimum, plus additional reinforcement in the first two mortar joints above and below openings extending 24 inches beyond. Grout placement must occur in 5-foot maximum lifts with 3000 PSI design strength. Design parameters include F'M = 2000 PSI compressive strength, 20 PSF roof live load, wind loads of 109 MPH ultimate (93 MPH nominal) at 20-foot mean roof height, Risk Category II, enclosed building classification, and ±0.18 internal pressure coefficient. Fastener specifications detail approved products for expansion bolts (Hilti Kwik Bolt 3, Simpson Strong-Tie Strong-Bolt 2, DeWalt Power-Stud+ SD1), screw anchors, power actuated fasteners, and adhesive anchoring systems with specific embedment depths. All work must comply with 2018 International Building Code, TMS 402 Quality Assurance Level B, and TMS 602 masonry specifications, with shop drawings requiring professional engineer seals and general contractor approval prior to submission.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MASONRY REINFORCEMENT LAYOUT S/S SD
STRUCTURAL ABBREVIATIONS
GA
GALV
GB
GC
GT
HGT
HORIZ
HSA
HT
IF
INFO
INT
JNT
JST
LB
LG
LLH
LLV
LSH
LSV
MANUF
MAT'L
MAX
MECH
MIN
MISC
NIC
NO
NS
NTS
OC
OD
OF
O/O
OPNG
OPP
PEMB
PERP
PL
PNL
PREFAB
PSF
PSI
PT
QTY
R OR RAD
RD
REF
REINF
REQ
REQ'D
RET
REV
GAGE
GALVANIZED
GRADE BEAM
GENERAL CONTRACTOR
GIRDER TRUSS
HEIGHT
HORIZONTAL
HEADED STUD ANCHOR
HIP TRUSS
INSIDE FACE
INFORMATION
INTERIOR
JOINT
JOIST
POUND
LONG
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONG SIDE HORIZONTAL
LONG SIDE VERTICAL
MANUFACTURER
MATERIAL
MAXIMUM
MECHANICAL
MINIMUM
MISCELLANEOUS
NOT IN CONTRACT
NUMBER
NEAR SIDE
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
OUTSIDE FACE
OUT TO OUT
OPENING
OPPOSITE
PRE-ENGINEERED METAL
BUILDING
PERPENDICULAR
PLATE
PANEL
PREFABRICATED
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POST TENSIONED
QUANTITY
RADIUS
ROUND
REFERENCE
REINFORCE(MENT)
REQUIRE
REQUIRED
RETAINING
REVISION
Ø
ALUM
AR
ARCH
ASSY
B/
BETWN
BLDG
BM
BOT
BPL
BRG
C TO C
CANT
CFS
CJ
CL
CLR
CMU
COL
CONC
CONN
CONST
CONT
CONTR
CTR
CTRD
DBA
DEFL
DET
DIA
DIAG
DIFF
DIM
DO
DWG
EA
EF
EJ
EL
ELEC
ELEV
ENGR
EOR
EQ
EQUIP
EXIST
EXP
EXT
EW
FB
FD
FDN
FF
FLR
FS
FTG
NUMBER OR POUND
ROUND OR DIAMETER
SQUARE
AND
AT
ALUMINUM
ANCHOR ROD
ARCHITECTURE
ASSEMBLY
BOTTOM OF
BETWEEN
BUILDING
BEAM
BOTTOM
BASE PLATE
BEARING
CENTER TO CENTER
CANTILEVER
COLD FORMED STEEL
CONSTRUCTION JOINT
CENTER LINE
CLEAR
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
CONTRACTION
CENTER
CENTERED
DEFORMED BAR ANCHOR
DEFLECTION
DETAIL
DIAMETER
DIAGONAL
DIFFERENT
DIMENSION
DITTO
DRAWING
EACH
EACH FACE
EXPANSION JOINT
ELEVATION
ELECTRICAL
ELEVATOR
ENGINEER
ENGINEER OF RECORD
EQUAL
EQUIPMENT
EXISTING
EXPANSION
EXTERIOR
EACH WAY
FLAT BAR
FLOOR DRAIN
FOUNDATION
FINISH FLOOR
FLOOR
FAR SIDE
FOOTING
SCHED
SECT
SIM
SOG
SPA
SPEC
SQ
STD
STIFF
STL
STR
STRUCT
SYM
T&B T/
T/U PANEL
TE
THK
THRD
TRANSV
TS
TYP
UON
VER
VERT
w/ w/O
WP
WS
WWF
SCHEDULE
SECTION
SIMILAR
SLAB ON GRADE
SPACE
SPECIFICATION
SQUARE
STANDARD
STIFFENER
STEEL
STRAIGHT
STRUCTURAL
SYMMETRICAL
TOP & BOTTOM
TOP OF
TILT-UP PANEL
THICKENED EDGE
THICK
THREADED
TRANSVERSE
THICKENED SLAB
TYPICAL
UNLESS OTHERWISE NOTED
VERIFY
VERTICAL
WITH
WITHOUT
WORK POINT
WATERSTOP
WELDED WIRE FABRIC
MASONRY
ALL LOAD BEARING WALLS AND EXTERIOR WALLS SHALL BE COMPOSED OF ASTM C90
HOLLOW CONCRETE MASONRY UNITS WITH ASTM C270 TYPE "S" MORTAR. GROUT SHALL
CONFORM TO THE REQUIREMENTS OF ASTM C476 AND HAVE A COMPRESSIVE STRENGTH OF
3000 PSI.
LAPPED BARS SHALL BE SECURED WITH WIRE TIES OR OTHER MEANS TO ENSURE THAT THE
BAR IS NOT DISPLACED DURING GROUT PLACEMENT OUTSIDE THE TOLERANCES
ESTABLISHED BY ACI 530. LAP BARS WITH THE FOLLOWING MINIMUM LENGTH.
BAR BARS CTR'D BARS CTR'D
BAR SIZE EA FACE 8" CMU 12" CMU
#3 16" 16" 16" #4 26" 21" 21" #5 40" 26" 26" #6 54" 43" 40"
#7 63" 60" 46"
GROUT ALL CELLS CONTAINING VERTICAL REINFORCEMENT IN 5'-0" MAXIMUM LIFTS. DO NOT
BEGIN PLACEMENT OF GROUT UNTIL ALIGNMENT OF CELLS ARE INSPECTED AND APPROVED.
PROVIDE HORIZONTAL JOINT REINFORCEMENT IN WALLS AT 16" OC VERTICALLY, UON. IN
ADDITION, INSTALL JOINT REINFORCING IN THE FIRST TWO MORTAR JOINTS ABOVE & BELOW
OPENINGS, EXTENDING AT LEAST 24 INCHES BEYOND THE OPENING.
LAP JOINT REINFORCEMENT 6" MINIMUM. HORIZONTAL REINFORCING SHALL CONSIST OF AT
LEAST TWO W1.7 WIRES OR GREATER.
MASONRY WORK SHALL BE INSPECTED IN ACCORDANCE WITH TMS 402 QUALITY ASSURANCE
LEVEL B.
DESIGN CRITERIA
CONCRETE MASONRY (DESIGN PER CURRENT EDITION TMS 402)
COMPRESSIVE STRENGTH
ALL REINFORCING STEEL ASTM A615 GRADE 60. REINFORCING STEEL SHOWN ON THESE
DRAWINGS TO BE WELDED SHALL BE ASTM A706 AND WELDING SHALL BE IN ACCORDANCE
WITH AWS D1.4.
F'M = 2000 PSI
109 MPH
93 MPH
20 FT
II
B
ENCLOSED
± 0.18
0.85
PER CODE
FASTENERS
EXPANSION BOLTS SHALL BE HILTI KWIK BOLT 3, SIMPSON STRONG-TIE STRONG-BOLT2,
DEWALT POWER-STUD+ SD1 OR APPROVED EQUAL, UON. EMBEDMENT DEPTH INTO
CONCRETE OR SOLID GROUTED MASONRY SHALL BE AT LEAST 7 TIMES THE BOLT DIAMETER,
UON. CLEAN HOLE AND INSTALL IN STRICT ACCORDANCE WITH MANUFACTURER'S PRINTED
INSTALLATION INSTRUCTIONS.
SCREW ANCHORS SHALL BE HILTI KWIK HUS-EZ, SIMPSON STRONG-TIE TITEN HD, DEWALT
SCREW-BOLT+ OR APPROVED EQUAL, UON. EMBEDMENT IN CONCRETE OR SOLID GROUTED
MASONRY SHALL BE AT LEAST 9 TIMES THE BOLT DIAMETER, UON. CLEAN HOLE AND INSTALL
IN STRICT ACCORDANCE WITH MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS.
POWER ACTUATED FASTENERS (PAF) SHALL BE 0.157" DIAMETER HILTI X-U, SIMPSON STRONG- TIE PDPA, DEWALT CSI PIN OR EQUAL, UON. EMBED MINIMUM 1 1/4" INTO CONCRETE AND CMU, UON. DO NOT PLACE WITHIN 1" OF CMU MORTAR JOINT. PAF SHALL COMPLETELY PENETRATE
STRUCTURAL STEEL.
ADHESIVE ANCHORING (EPOXY):
• ADHESIVE ANCHORING FOR CONCRETE SHALL BE HILTI RE-500 V3 CARTRIDGE SYSTEM,
SIMPSON STRONG-TIE SET-3G, DEWALT PURE 110+ (OR EQUIVLANT ACRYLIC AC200+, HY
200, OR ATXP) OR APPROVED EQUAL, UON. EMBEDMENT DEPTH SHALL BE AT LEAST 12
TIMES THE INSERT DIAMETER, UON. HOLE DIAMETER SHALL BE NO GREATER THAN
RECOMMENDED BY MANUFACTURER. THE HOLE SHALL BE CLEANED PER
MANUFACTURER'S RECOMMENDATIONS BY BRUSHING OUT WITH WIRE BOTTLE BRUSH
AND BLOWN OUT WITH AIR USING A COMPRESSOR WITH A FUNCTIONAL OIL TRAP (EXCEPT
WHERE PERMITTED WHEN USING A DUST EXTRACTION SYSTEM IN ACCORDANCE WITH
MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS).
• ADHESIVE ANCHORING FOR MASONRY SHALL BE HILTI HIT-HY 70 OR HY 270 CARTRIDGE
SYSTEM, SIMPSON STRONG-TIE SET-XP, DEWALT AC100+ OR APPROVED EQUAL, UON.
EMBEDMENT DEPTH INTO SOLID GROUTED MASONRY SHALL BE AT LEAST 9 TIMES THE
INSERT DIAMETER, UON. HOLE DIAMETER SHALL BE NO GREATER THAN RECOMMENDED
BY MANUFACTURER. HOLES SHALL NOT BE PLACED WITHIN 1" OF A VERTICAL MORTAR
JOINT. CLEAN HOLE IN ACCORDANCE WITH MANUFACTURER'S PRINTED INSTRUCTIONS.
• GENERAL - ANCHORS SHALL MEET THE REQUIREMENTS OF ACI 355.4. INSTALLATION SHALL
BE IN STRICT ACCORDANCE WITH MANUFACTURER'S PRINTED INSTRUCTIONS AND
PERFORMED BY AN INSTALLER TRAINED BY THE MANUFACTURER. INSTALLATION OF
ADHESIVE ANCHORS HORIZONTALLY OR UPWARDLY, WHICH SUPPORT SUSTAINED
TENSION LOADS SHALL BE PERFORMED BY A CERTIFIED ADHESIVE ANCHOR INSTALLER IN
ACCORDANCE WITH ACI318 AND CONTINUOUSLY INSPECTED PER ACI318. PROOF OF
CURRENT CERTIFICATION SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL.
• CAPACITIES - UON, DESIGN BOND STRENGTH OF ANCHORS HAVE BEEN BASED ON
CRACKED CONCRETE, ACI 355.4 TEMPERATURE CATEGORY B, AND INSTALLATIONS INTO
DRY HOLES DRILLED WITH A ROTARY IMPACT DRILL OR ROCK DRILL INTO CONCRETE THAT
HAS CURED AT LEAST 21 DAYS AND HAS A CONCRETE TEMPERATURE OF AT LEAST 50
DEGREES F AT TIME OF ANCHOR INSTALLATION.
LIVE LOADS:
ROOFS AND CANOPIES (REDUCIBLE)
WIND LOADS:
ULTIMATE WIND SPEED: (ASCE 7-16)
NOMINAL WIND SPEED
MEAN ROOF HEIGHT
RISK CATEGORY
WIND EXPOSURE
ENCLOSURE CLASSIFICATION
INTERNAL PRESSURE COEFFICIENT
DIRECTIONALITY FACTOR (Kd)
SHAPE FACTORS
20 PSF
DESIGN PER 2018 INTERNATIONAL BUILDING CODE, UNLESS OTHERWISE NOTED.
SUPPLEMENTARY NOTES
PROVIDE ALL TEMPORARY BRACING, SHORING, GUYING OR OTHER MEANS TO AVOID
EXCESSIVE STRESSES AND TO HOLD STRUCTURAL ELEMENTS IN PLACE DURING
CONSTRUCTION. THE STRUCTURE SHOULD NOT BE CONSIDERED STABLE UNTIL ALL
STRUCTURAL ELEMENTS HAVE BEEN CONSTRUCTED IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
IMEG OR ANY OF ITS EMPLOYEES SHALL NOT HAVE CONTROL OR BE RESPONSIBLE FOR
CONSTRUCTION MEANS, METHODS, TECHNIQUES, PROCEDURES OR SEQUENCES FOR THE
ACTS OR OMISSIONS OF THE CONTRACTOR OR ANY OTHER PERSONS PERFORMING THE
WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE
WITH THE CONTRACT DOCUMENTS.
VISUAL OBSERVATIONS OF THE STRUCTURAL SYSTEM BY IMEG FOR GENERAL
CONFORMANCE TO THE APPROVED PLANS AND SPECIFICATIONS DOES NOT INCLUDE OR
WAIVE THE RESPONSIBILITY FOR THE INSPECTIONS REQUIRED BY THE INTERNATIONAL
BUILDING CODE.
VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR EMBEDS,
OPENINGS, SLEEVES, ETC. NOT SHOWN ON THE STRUCTURAL DRAWINGS.
ALL STRUCTURAL OPENINGS AROUND OR AFFECTED BY MECHANICAL, ELECTRICAL AND
PLUMBING EQUIPMENT SHALL BE VERIFIED WITH EQUIPMENT PURCHASED BEFORE
PROCEEDING WITH STRUCTURAL WORK AFFECTED.
CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS OF EXISTING
STRUCTURE AND SITES THAT ARE AFFECTED BY NEW WORK BEFORE PROCEEDING WITH
FABRICATION AND CONSTRUCTION.
ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR
THE SEAL OF AN ENGINEER REGISTERED IN THE STATE OF THE PROJECT.
SHOP DRAWINGS AND SUBMITTALS
SHOP DRAWING SUBMITTALS ARE ONLY REVIEWED FOR GENERAL CONFORMANCE WITH THE
INFORMATION SHOWN ON THE CONSTRUCTION DOCUMENTS. THE GENERAL CONTRACTOR
MUST REVIEW AND APPROVE THE SHOP DRAWINGS PRIOR TO THEIR SUBMITTAL TO THE
ENGINEER. SUBMITTALS WHICH DO NOT CONTAIN THE CONTRACTOR'S SHOP DRAWING STAMP
SHALL BE RETURNED WITHOUT REVIEW. ANY REQUESTED CHANGES TO THE CONTRACT
DOCUMENTS SHALL BE COMMUNICATED IN WRITING PRIOR TO SUBMITTING THE SHOP
DRAWINGS AND CLOUDED ON THE SHOP DRAWINGS.
SHOP DRAWINGS MUST BE SUBMITTED FOR ENGINEER'S REVIEW OF THE FOLLOWING ITEMS:
(S/S = SIGNED & SEALED SHOP DRAWING WITH CALCS, SD = SHOP DRAWING FOR REVIEW
ONLY)
COMPLETE SHOP DRAWINGS FOR CONSTRUCTION OF EACH BUILDING COMPONENT NOT
DESIGNED BY THE DESIGN TEAM OF RECORD AND NOT SPECIFIED ON THE PROJECT
CONSTRUCTION DOCUMENTS SHALL BE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER
REGISTERED IN THE STATE OF THE PROJECT AND SHALL BE AVAILABLE AT THE JOB SITE
DURING TIMES OF INSPECTION.
SOME STRUCTURAL SYSTEMS ARE DEFINED AS VENDOR-DESIGNED COMPONENTS PER THE
STRUCTURAL DOCUMENTS. THESE ELEMENTS OF THE DESIGN ARE DEFERRED SUBMITTAL
COMPONENTS AND HAVE NOT BEEN PERMITTED UNDER THE BASE BUILDING APPLICATION.
VENDOR-DESIGNED COMPONENT SHOP DRAWINGS SHALL BE APPROVED BY THE COMPONENT
DESIGNER ENGINEER PRIOR TO CURSORY REVIEW BY THE ENGINEER OF RECORD FOR LOADS
IMPOSED ON THE BASE STRUCTURE. THE COMPONENT DESIGNER IS RESPONSIBLE FOR CODE
CONFORMANCE AND ALL NECESSARY CONNECTIONS NOT SPECIFICALLY CALLED OUT ON
ARCHITECTURAL OR STRUCTURAL DRAWINGS. SHOP DRAWINGS SHALL INDICATE MAGNITUDE
AND DIRECTION OF ALL LOADS IMPOSED ON BASIC STRUCTURE. THE CONTRACTOR SHALL
SUBMIT THE STAMPED COMPONENT SYSTEM DOCUMENTS TO THE BUILDING OFFICIAL FOR
APPROVAL.
GENERAL NOTES
SPECIFICATIONS
MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM TO THE REQUIREMENTS OF
"SPECIFICATIONS FOR MASONRY STRUCTURES - TMS 602 (LATEST EDITION), EXCEPT AS
MODIFIED BY REQUIREMENTS OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL
EMPLOY AND PAY AN INDEPENDENT TESTING LABORATORY TO PERFORM MASONRY TESTING.
DEAD LOADS:
ROOF (ASSUMED) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 PSF
COMPONENT & CLADDING DESIGN
NEGATIVE ZONE 3
NEGATIVE ZONE 2
NEGATIVE ZONE 1'
ZONE
WIND PRESSURES (PSF)
NEGATIVE 5
NEGATIVE 4
ZONE
WALL
POSITIVE 4 & 5
OVERHANG ZONE 2
OVERHANG ZONE 3
POSITIVE ALL ZONES
OVERHANG ZONE 1 & 1'
-30.3
-17.4
-40
-54.5
-27.4
-37.1
-51.6
10 SF 20 SF
10 SF
-18.9
-23.2
17.4
NOTES:
1) TABLE PRESSURES ARE FOR THE SQUARE FOOT (SF)
TRIBUTARY AREA SHOWN. FOR OTHER TRIBUTARY
AREAS, LINEARLY INTERPOLATE BETWEEN VALUES
SHOWN ABOVE.
2) POSITIVE PRESSURES ACT TOWARD THE BUILDING.
NEGATIVE PRESSURES ACT AWAY FROM THE BUILDING.
3) SEE DIAGRAMS FOR LOCATION OF ZONES.
4) PRESSURES SHOWN ARE ULTIMATE PRESSURES.
MULTIPLY VALUES BY 0.6 FOR NOMINAL PRESSURES
ROOF
a=3'-7 1/4"
100 SF
-16.3
-18.1
16.0
200 SF
-16.0
-16.6
16.0
500 SF
-16.0
-16.0
16.0
200 SF 350 SF 500 SF 1000 SF
-21.7
-16.0
-28.9
-32.3
-21.6
-22.3
-25.7
-20.1
-16.0
-26.8
-28.1
16.0
-18.3
-19.5
-20.8
-19.0
-16.0
-25.5
-25.5
-16.1
-17.7
-17.7
-19.0
-16.0
-25.5
-25.5
-16.1
-17.7
-17.7
-28.3
-17.4
-37.4
-49.4
-26.9
-33.7
-45.6
-25.7
-17.4
-34
-42.6
-26.3
-29.1
-37.7
50 SF 100 SF
-23.7
-17.4
-31.5
-37.4
-25.8
-25.7
-31.7 h=20'-0" a a a a a a h a a
ROOF PLAN (GENERIC BUILDING SHOWN) WALLS (GENERIC BUILDING SHOWN)
2eO
3eO 2nO 3rO
2eO
3rO 2nO 3eO
2e 1 2r 2r 1 2e
3e 2n 3r 3r 2n 3e
3e 2n 3r 3r 2n 3e a a4
NEGATIVE ZONE 1
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:1
:2
P
M
JWL
FPA
03/14/2024
S0.01ABB
DESIGN CRITERIA & GENERAL
NOTES
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
Zac Lane, PE #20786
NO SCALE
WIND PRESSURE DIAGRAMS
24 69
323963
S0.01 zac Text Box This file has been digitally signed and sealed by Zachary Paul Lane a Mississippi Licensed Professional Engineer, License No. 20786, on the date of the electronic signature. Printed copies of this document are not considered signed and sealed. The signature must be verified on any electronic copies.
zac Image
S1.01
S1.01 EXISTING CMU WALL
S1.01
#5 X 1' BARS
EPOXIED INTO
GROUTED CELLS
OF THE EXISTING
MASONRY WALL AT
2' ON CENTER
EMBED = 6"
CMU
LAP PER GENERAL
NOTES
16" CONT BOND
BEAM W/ 1-#5 CONT
T&B
T/EXIST OPNG,
SEE ARCH
EXTERIOR FACE
OF EXIST CMU
#5 DOWEL (MATCH WALL
REINFORCING SPA) EMBED 6"
& SECURE W/ EPOXY ADHESIVE.
ACI STD HOOK AT OTHER END
(T&B OF CMU INFILL)
EXTERIOR FACE
OF EXIST CMU
T Y
P S
E E
A R
C H
F O
R I N
F
IL
L L
O C
A T
IO
N
S
C M
U I N
F
IL
L W
G
R O
U T
F
IL
L E
D C
E L L
S
V
E R
T R
E
IN
F H
O O
K T
O P
O F
R E
IN
F
EXISTING THICKENED
EDGE
KNOCK OUT FACE SHELL
AS REQUIRED TO INSTALL
REINF AND GROUT.
THEN FILL W/ GROUT TO
EDGE OF CMU FACE.
NOTES:
1) FOR OPNG LOCATIONS SEE ARCH DWGS.
2) PROVIDE 8" BEARING EA SIDE OF OPNG.
MASONRY OPNG LESS THAN 5'-0"
FILL CELLS
W/ CONC
PRECAST OR
CMU U-BLOCK
VERT REINF, SEE
CMU
1-#5 EF CONT
3/S1.01
NOTES:
1. 5' MAX IF LOW LIFT GROUTING IS USED.
2. IF HIGH LIFT GROUTING IS USED, REINFORCING SHALL BE FULL
HEIGHT & A CLEANOUT HOLE IS REQ'D @ CELLS w/ REBAR.
GROUT SHALL BE PLACED IN LIFTS TO PREVENT BLOWOUTS.
3. SEE GENERAL NOTES FOR BAR LAPS.
4. SEE GENERAL NOTES FOR HORIZONTAL JOINT REINFORCING
AND LAP LENGTH.
PLAN
OPENING
DOWELS TO
MATCH VERT
REINF (TYP, UON)
FTG, SEE PLAN
CLEANOUT HOLE
AS REQUIRED
JOINT REINF @
16" OC, UON
HORIZ JOINT REINF
COORD W/ ARCH
FILL ALL CELLS
W/ VERTICAL
REINFORCING SOLID
MASONRY
CONTROL JOINT
T/SLAB EL,
SEE PLAN
FTG, SEE PLAN KNOCK-OUT
BLOCK W/ #5 EF
TYP WALL REINF,
SEE
FOR SIZE & SPACING
ADD 1-#5 FULL HEIGHT
WHEN OPENING
EXCEEDS 5'-4"
WALL SECTION
SEE GENERAL
NOTES & SECTIONS
SEE GENERAL
NOTES & SECTIONS
T/FTG EL,
SEE PLAN
T/WALL EL,
SEE PLAN
VERT WALL REINF, LINTEL,
SEE
MASONRY
BOND BEAM
A S
R E
Q 'D
S E
E N
O T
E
S E
E N
O T
E
L A
P
L A
P
1-#5 FULL HEIGHT,
GROUT CELL FULL
DOOR OPNG
WINDOW OR
DOWELS TO
MATCH VERT
REINF
S E
E P
L A
N
TYP WALL OPENING
3/S1.01
3/S1.01 4/S1.01
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:1
:3
P
M
JWL
FPA
03/14/2024
S1.01ABB
FLOOR PLAN, ELEVATION AND
DETAILS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
LEVEL 1 FLOOR PLAN
SOUTH ELEVATION - NEW WORK
NO SCALE
TYP INFILL AT CMU OPENING
NO SCALE
TYP MASONRY LINTEL
NO SCALE
TYP REINF MASONRY WALL
Zac Lane, PE #20786
25 69
323963
S1.01
S1.01
S1.01
S1.01 SCALE A
S1.01 SCALE A
SCALE A 8 0 8 16
1/8" = 1'-0" zac Text Box This file has been digitally signed and sealed by Zachary Paul Lane a Mississippi Licensed Professional Engineer, License No. 20786, on the date of the electronic signature. Printed copies of this document are not considered signed and sealed. The signature must be verified on any electronic copies.
zac Image
| Sheets |
| S0.01 - DESIGN CRITERIA & GENERAL NOTES |
| S1.01 - FLOOR PLAN, ELEVATION AND DETAILS |
| zac.p.lane@imegcorp.com | |
| 2024-03-19T14:32:14-0500 | |
| Pensacola, FL | |
| Zachary P Lane | |
| I have reviewed this document |
File details come from the government source that posted it. Updated .