Drawings_Electrical_Sheet_47_-_64.pdf
PDF 975 KB Posted
- Attached to
- MODERNIZE NATCHEZ MAINTENANCE FACILITY
- Solicitation number
- 140P5226R0002
About this file
This document is a comprehensive set of electrical construction drawings and specifications for the NPS - Natchez Maintenance Facility Renovation project, prepared by Henry Adams, LLC (Baltimore, MD) and Walker Architects (Gainesville, FL). The drawings establish detailed requirements for the complete renovation of electrical systems at the facility, including demolition of existing systems and installation of new power, lighting, security, and telecommunications infrastructure.
The scope of work encompasses removal of existing electrical panels (MF1, MF2, DP), a 125 KVA natural gas generator with automatic transfer switch, and associated air conditioning units, followed by installation of new panels, circuits, and equipment. New work includes a replacement 60-amp single-phase panel (MF2A), LED lighting systems with occupancy sensors and dimming controls, GFCI and weather-resistant receptacles, emergency exit signage, security systems with card readers and surveillance cameras, telecommunications infrastructure with CAT6A cabling and IT rack installation, and electrical connections for mechanical equipment including heat pump units (HPU-1, HPU-2), fan coil units (FCU-1.1, FCU-1.2, FCU-2.1), and various other HVAC and utility equipment. Disconnect switches are specified for all major equipment, with detailed schedules provided for panelboards MF1, MF2, MF2A, and associated disconnect switches (DS-ACCU-1, DS-HPU-1, DS-HPU-2). The drawings include standard NEC compliance requirements, coordination protocols with other trades, material specifications, mounting heights for all devices at 18" to 90" above finished floor, and detailed riser diagrams for telecommunications and security systems. All work must comply with local, state, and federal codes, with the facility remaining unoccupied during renovations and all demolition materials properly disposed of or salvaged as directed by the contracting officer.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P F
P F
NOTES: (APPLICABLE TO ELECTRICAL LEGEND ONLY)
1.
2.
3.
4.
THE MOUNTING HEIGHTS GIVEN ON THIS SHEET IN THE ELECTRICAL LEGEND ARE
GENERAL AND SHALL BE USED ONLY WHEN MOUNTING HEIGHTS CANNOT BE
ESTABLISHED BY REFERENCE TO DETAILS, ELEVATIONS, AND NOTES ON THE DRAWINGS.
ALL MOUNTING HEIGHTS, UNLESS OTHERWISE NOTED, SHALL BE MEASURED FROM THE
FINISHED FLOOR TO THE CENTERLINE OF THE OUTLET OR DEVICE.
HEIGHTS OF ALL ITEMS NOT COVERED BY THE ELECTRICAL LEGEND AND NOT SHOWN
ON THE DRAWINGS SHALL BE AS DIRECTED BY THE ARCHITECT OR ENGINEER.
WHERE PLACING ANY ITEM AT THE HEIGHTS LISTED OR NOTED WILL CAUSE
INTERFERENCE WITH THE WORK OF OTHER TRADES, OR IS NOT PHYSICALLY POSSIBLE
OR DESIRABLE FOR ONE REASON OR ANOTHER, THE ITEM SHALL BE INSTALLED AT A
LOCATION APPROVED BY THE ARCHITECT OR ENGINEER.
ELECTRICAL LEGEND
DESCRIPTION
MOUNTING
HEIGHT
SYMBOL DESCRIPTION
MOUNTING
HEIGHT
SYMBOL
ELECTRICAL LEGEND (CONTINUED)
ILLUMINATED EXIT SIGN, SINGLE FACE - ARROW INDICATES DIRECTIONAL
CHEVRON - CEILING/WALL MOUNTED
- - / 90"
ILLUMINATED EXIT SIGN, DOUBLE FACE - CEILING/WALL MOUNTED - - / 90"
$ SINGLE POLE TOGGLE SWITCH 46"
3 THREE-WAY TOGGLE SWITCH 46"
OS OCCUPANCY SENSOR SWITCH 46"
LV1
LIGHTING CONTROL SYSTEM - LOW VOLTAGE SWITCH FOR ONE ZONE,
ON/OFF CONTROL.
46"
LV1D
LIGHTING CONTROL SYSTEM - LOW VOLTAGE SWITCH FOR ONE ZONE,
ON/OFF AND UP/DOWN DIMMING.
46"
LV2D
LIGHTING CONTROL SYSTEM - LOW VOLTAGE SWITCH FOR TWO ZONES,
ON/OFF AND UP/DOWN DIMMING.
46"
OSD OCCUPANCY SENSOR SWITCH WITH 0-10V DIMMING 46"
(SIMPLEX)
(DUPLEX)
(QUAD)
RECEPTACLE - NEMA CONFIGURATION 5-20R (SHADING INDICATES
CONNECTED TO EMERGENCY/STANDBY POWER CIRCUIT)
SUBSCRIPTS:
GFI: WITH 5mA GROUND FAULT INTERRUPTER
TR: TAMPER-RESISTANT
WP: WEATHER-RESISTANT RECEPTACLE WITH WEATHERPROOF
WHILE-IN-USE COVER
18"
JUNCTION BOX (CEILING AND WALL MOUNTED)
- - / AS
NOTED
MS
EMERGENCY LUMINAIRE, BATTERY POWERED - - / 90"
LIGHTING CONTROL SYSTEM - RELAY PACK WITH POWER SUPPLY - -RPP
LIGHTING CONTROL SYSTEM - RELAY PACK WITH POWER SUPPLY FOR
DIMMING 0-10V LOADS
- -RPD
FRACTIONAL HORSEPOWER MANUAL MOTOR SWITCH 46"
MOTOR - -
COMBINATION MAGNETIC MOTOR STARTER AND SAFETY SWITCH 60" TO TOP
SAFETY SWITCH 60" TO TOP
ENCLOSED CIRCUIT BREAKER 60" TO TOP
SURGE PROTECTIVE DEVICE SEE DETAILSPD
PANELBOARD 78" TO TOP
DATA OUTLET, WALL MOUNTED 18"
DATA OUTLET, FLOOR MOUNTED (P = PEDESTAL, F = FLUSH) - -
COMBINATION TELEPHONE/DATA OUTLET, WALL MOUNTED 18"
COMBINATION TELEPHONE/DATA OUTLET, FLOOR MOUNTED
(P = PEDESTAL, F = FLUSH)
TELEPHONE TERMINAL BACKBOARD - -
GROUNDING SYSTEM - GROUND CONNECTION - -
MOLDED CASE CIRCUIT BREAKER (600V AND BELOW) - -
FIXED CURRENT TRANSFORMER WITH TURN RATIO - -
CURRENT LIMITING FUSE (600V AND BELOW) - -
DISCONNECT SWITCH (600V AND BELOW) - -
KILOWATT METER (KWH = KILOWATT HOURS) - -KW
TRANSFORMER - -
GROUNDING SYSTEM WYE GROUNDED NEUTRAL WINDING - -
DELTA WINDING - -
OCCUPANCY SENSOR (CEILING AND WALL MOUNTED)
SUBSCRIPTS:
DT: DUAL TECHNOLOGY (DEFAULT IF NO SUBSCRIPT INDICATED)
U: ULTRASONIC
P: PASSIVE INFRARED
- - / 92"
LUMINAIRE - -
CR SECURITY SYSTEM - CARD READER 46"
SECURITY SYSTEM - KEY PAD 46"KP
SECURITY SYSTEM PANEL 78" TO TOPSEC
AS NOTED
SECURITY SYSTEM - SURVEILLANCE CAMERA (CEILING/WALL MOUNT)
SUBSCRIPTS:
F: FIXED (DEFAULT IF NO SUBSCRIPT INDICATED)
PTZ: PAN - TILT - ZOOMD: DOME
D: DOME
HARDWIRED POWER CONNECTION TO SYSTEMS FURNITURE 6"
HARDWIRED COMMUNICATIONS CONNECTION TO SYSTEMS FURNITUREJ
C
6"
J P
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:2
A
M
JLW
JLW
03/14/2024
E0.1JST
ELECTRICAL COVER SHEET
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
A AMPERE
ACCU AIR COOLED CONDENSING
UNIT
ACU AIR CONDITIONING UNIT
ADA AMERICANS WITH
DISIBILITIES ACT
AF AMPERE FRAME, AMPERE
FUSE
AFCI ARC FAULT CIRCUIT
INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING
CAPACITY
AL ALUMINUM
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
ASYM ASYMMETRICAL
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER
SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BOD BASIS OF DESIGN
C CONDUIT
CB CIRCUIT BREAKER
CCT CORRELATED COLOR
TEMPERATURE
CH CHILLER
CKT CIRCUIT
CMS COMBINATION MOTOR
STARTER
COMM COMMUNICATION
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CU COPPER
CX CONNECT TO EXISTING
DS DISCONNECT SWITCH
DWC DRINKING WATER COOLER
DWG DRAWING
E EMERGENCY
EBU EMERGENCY BATTERY UNIT
ECB ENCLOSED CIRCUIT
BREAKER
EF EXHAUST FAN
EMT ELECTRICAL METALLIC
TUBING
ENCL ENCLOSURE
ENT ELECTRICAL NONMETALLIC
TUBING
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EWH ELECTRIC WATER HEATER
EX EXISTING
F FUSED, FUSIBLE,
FAHRENHEIT
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR
PANEL
FACP FIRE ALARM CONTROL
PANEL
FCU FAN COIL UNIT
FDR FEEDER
FLA FULL LOAD AMPERAGE
FMC FLEXIBLE METAL CONDUIT
FSS FUSED SAFETY SWITCH
FT FEET
G GROUND
GB GROUND BAR
GEC GROUNDING ELECTRODE
CONDUCTOR
ELECTRICAL ABBREVIATIONS
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GFI GROUND FAULT
INTERRUPTER
GND GROUND
GRC GALVANIZED RIGID STEEL
GW GROUND WIRE
HD HEAVY DUTY
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPU HEAT PUMP UNIT
HVAC HEATING VENTILATING AIR
CONDITIONING
HZ HERTZ
IBC INTERNATIONAL BUILDING
CODE
ICCB INSULATED CASE CIRCUIT
BREAKER
IEBC INTERNATIONAL EXISTING
BUILDING CODE
IECC INTERNATIONAL ENERGY
CONSERVATION CODE
IEEE INSTITUTE OF ELECTRICAL
AND ELECTRONICS
ENGINEERS
IMC INTERMEDIATE METALLIC
CONDUIT
IN INCH
JB JUNCTION BOX
K ONE THOUSAND, KELVIN
KAIC THOUSAND AMPERE
INTERRUPTING CAPACITY
KCMIL THOUSAND CIRCULAR MILS
KV KILOVOLTS
KVA KILOVOLT-AMPERES
KW KILOWATTS
LC LOAD CENTER
LED LIGHT EMITTING DIODE
LF LINEAR FEET
LFMC LIQUID TIGHT FLEXIBLE
METALLIC CONDUIT
LFNC LIQUID TIGHT FLEXIBLE
NON-METALLIC CONDUIT
LRA LOCKED ROTOR AMPS
LS LIMIT SWITCH, LONG
TIME-SHORT TIME
LTG LIGHTING
LTS LIGHTS
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL CLAD, METER
CENTER
MCA MINIMUM CIRCUIT
AMPACITY
MCB MAIN CIRCUIT BREAKER
MCCB MOLDED CASE CIRCUIT
BREAKER
MDP MAIN DISTRIBUTION PANEL
MGB MAIN GROUND BAR
MIN MINIMUM
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOCP MAXIMUM OVERCURRENT
PROTECTION
MTD MOUNTED
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NF NON-FUSED
NFPA NATIONAL FIRE
PROTECTION ASSOCIATION
NFSS NON-FUSED SAFETY
SWITCH
NIC NOT IN CONTRACT
NM NON-METALLIC
NO NORMALLY OPEN
NTS NOT TO SCALE
OCP OVERCURRENT PROTECTION
OH OVERHEAD
OHE OVERHEAD ELECTRIC
P POLE(1P, 2P, 3P)
PF POWER FACTOR
PH PHASE
PIR PASSIVE INFRARED
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
QTY QUANTITY
R RACEWAY
REC RECEPTACLE
RGS RIGID GALVANIZED STEEL
RLA RATED LOAD AMPERES
RM ROOM
RMS ROOT MEAN SQUARE
RNC RIGID NONMETALLIC
CONDUIT
RX REMOVE EXISTING
SE SERVICE ENTRANCE
SF SQUARE FEET
SN SOLID NEUTRAL
SPD SURGE PROTECTION
DEVICE
SS SAFETY SWITCH
ST SINGLE-THROW
SW SWITCH
SYM SYMMETRICAL
T TRANSFORMER
TA TRIP AMPERES
TECH TECHNOLOGY
TGB TELECOMMUNICATIONS
GROUND BAR
TTB TELEPHONE TERMINAL
BOARD
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UGE UNDERGROUND ELECTRIC
UH UNIT HEATER
UL UNDERWRITERS
LABORATORY
UON UNLESS OTHERWISE NOTED
UTP UNSHIELDED TWISTED PAIR
V VOLTS
VA VOLT-AMPERES
VSD VARIABLE SPEED DRIVE
W WIRE, WATTS
W/ WITH
WP WEATHERPROOF
WR WEATHER RESISTANT
XFMR TRANSFORMER
Y WYE
323963
DEVICE TYPE
5 INDICATES PANELBOARD CIRCUIT DESIGNATION
LIGHTING
REFERENCE
ELECTRICAL CONVENTIONS
A
1b
CIRCUIT NUMBER
CONTROL POINT DESIGNATION (IF MORE THAN ONE)
LUMINAIRE TYPE - SEE LUMINAIRE SCHEDULE
LUMINAIRE WITH INTEGRAL BATTERY BACKUP
A
NUMBER OF CONTROL POINTS
TYPE OF CONTROL
CONTROL ZONE REFERENCE
2$ ab
DRAWING NUMBER WHERE DETAIL IS LOCATED
NUMBER DENOTES SECTION IDENTIFICATION
SECTION DESIGNATION
E-1
E-1 DRAWING NUMBER WHERE DETAIL IS LOCATED
DETAIL DESIGNATION
NUMBER DENOTES DETAIL IDENTIFICATION
SPECIAL NOTE (APPLIES WHERE INDICATED
ON THE DRAWING)
WIRING
1,3,5(LP-1)
BRANCH CIRCUIT HOMERUN TO PANEL
"LP-1", CIRCUITS #1,3,5
NUMBER OF CIRCUITS INDICATED BY
QUANTITY OF ARROW HEADS.
CONCEALED CONDUIT IN CEILING OR WALLS
CONDUIT IN OR UNDER FLOOR
EXPOSED CONDUIT
CONDUIT TURNING UP
CONDUIT TURNING DOWN
CONDUIT, CAPPED
GENERAL NOTE: WHERE WIRE SIZE IS INDICATED AT THE
HOMERUN OR ON THE SCHEDULE TO BE LARGER THAN
THE SPECIFIED MINIMUM PROVIDE THE INDICATED WIRE SIZE
THROUGHOUT THE ENTIRE BRANCH CIRCUIT.
DEVICE TYPE
CANDELA RATING15cd
MOUNTING HEIGHTS
PRESENTATION
FIRE ALARM
DEVICE TYPE
+ INDICATES DEVICE TO BE MOUNTED
8" ABOVE COUNTERTOP BACKSPLASH
24"
DEVICE TYPE
INDICATES DEVICE MOUNTING HEIGHT ABOVE FINISHED FLOOR
OR ABOVE FINISHED GRADE (AS APPROPRIATE)
ELECTRICAL EQUIPMENT DESIGNATED BY SOLID HEAVY
LINEWEIGHT INDICATES NEW WORK TO BE PROVIDED.
ELECTRICAL EQUIPMENT DESIGNATED BY SOLID LIGHT
LINEWEIGHT INDICATES EXISTING EQUIPMENT TO REMAIN,
UNLESS OTHERWISE INDICATED.
ELECTRICAL EQUIPMENT DESIGNATED BY DASHED HEAVY
LINEWEIGHT REPRESENTS EXISTING EQUIPMENT TO BE
REMOVED AND DISPOSED, UNLESS INDICATED TO BE
REMOUNTED, RELOCATED, OR TURNED OVER TO OWNER.
STEM INDICATES WALL MOUNTED
LUMINAIRE, MOUNTING HEIGHT
AS NOTED
1. PROVIDE LABOR, MATERIALS, TOOLS, EQUIPMENT, COORDINATION, DELEGATED DESIGN AND INCIDENTALS NECESSARY TO PROVIDE A COMPLETE AND OPERABLE SYSTEM.
2. PERFORM WORK AS REQUIRED BY APPLICABLE CODES, REGULATIONS AND LAWS OF LOCAL, STATE AND FEDERAL GOVERNMENTS AND OTHER AUTHORITIES WITH
LAWFUL JURISDICTION.
3. MATERIAL AND EQUIPMENT SHALL BE LISTED AND LABELED BY NATIONALLY RECOGNIZED TESTING LABORATORIES FOR INTENDED SERVICE.
4. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, AND OBTAIN NECESSARY APPROVALS FROM AUTHORITIES THAT HAVE
JURISDICTION.
5. MAINTAIN RECORD DRAWINGS ON SITE. RECORD SET SHALL BE COMPLETE, CURRENT, AND AVAILABLE UPON REQUEST.
6. SUBMIT FOR APPROVAL, SHOP DRAWINGS FOR EQUIPMENT AND MATERIALS USED ON PROJECT. OBTAIN APPROVAL BY CONTRACTING OFFICER PRIOR TO PURCHASE OF
EQUIPMENT AND MATERIALS.
7. REPAIR OR REPLACE DAMAGE TO FACILITIES AND EQUIPMENT AT NO ADDITIONAL EXPENSE TO GOVERNMENT.
8. PATCH AND REPAIR DISTURBED AREAS TO MATCH ADJACENT SURFACES AND FINISHES.
9. PROVIDE TEMPORARY POWER AND LIGHTING FOR OTHER TRADES AS REQUIRED TO COMPLETE PROJECT IN ACCORDANCE WITH APPLICABLE CODES AND STANDARDS.
10.
11. LOCATIONS SHOWN ON PLANS ARE APPROXIMATE AND REQUIRE COORDINATION WITH OTHER TRADES. ROUTING OF CONDUIT IS DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW REQUIRED OFFSETS AND DETAILS. OBTAIN DRAWINGS AND SPECIFICATIONS FROM OTHER TRADES AND COORDINATE WITH OTHER TRADES.
12. COORDINATE ELECTRICAL INSTALLATION WITH FIELD CONDITIONS. LOCATIONS SHOWN ARE DIAGRAMMATIC AND MAY REQUIRE ADJUSTMENT IN FIELD.
13. COORDINATE LOCATIONS OF ELECTRICAL DEVICES WITH ARCHITECTURAL ELEVATIONS PRIOR TO INSTALLATION.
14. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF MECHANICAL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS.
15. PERMANENTLY LABEL NEW ELECTRICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO, DEVICE DESIGNATION AND SUPPLY CIRCUIT DESIGNATION.
16. CORE DRILL CONCRETE WALLS AND FLOORS TO PROVIDE OPENINGS FOR CONDUIT INSTALLATION. PRIOR TO CORE DRILLING, LOCATE REINFORCING BARS IN EXISTING WALLS AND FLOORS USING A NON-DESTRUCTIVE METHOD. COORDINATE AND OBTAIN FINAL APPROVAL OF CORE DRILL LOCATIONS FROM CONTRACTING OFFICER. DO NOT CUT THROUGH EXISTING REINFORCING BARS WITHOUT APPROVAL OF CONTRACTING OFFICER. MAXIMUM CORE DRILL SIZE SHALL BE 5-INCH DIAMETER. SPACE CORE DRILL LOCATIONS A MINIMUM OF 6 INCHES FROM EACH OTHER, MEASURED FROM CORE DRILL OPENINGS. PROPERLY SEAL OPENINGS ACCORDING TO LOCATION AND APPLICATION.
17. PROVIDE EACH CIRCUIT WITH A DEDICATED NEUTRAL UNLESS NOTED OTHERWISE.
18. CONDUIT HOMERUNS SHOWN ON DRAWINGS WITH MORE THAN 3 CURRENT CARRYING CONDUCTORS ARE SHOWN DIAGRAMMATICALLY. DO NOT INSTALL MORE THAN 3 CURRENT CARRYING CONDUCTORS IN A SINGLE RACEWAY UNLESS INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE.
19. PROVIDE FIRESTOPPING FOR ELECTRICAL PENETRATIONS IN FIRE RATED ASSEMBLIES.
20. INSTALL ELECTRICAL WORK IN A NEAT AND WORKMANLIKE MANNER, RECTILINEAR TO BUILDING STRUCTURE. INSTALL RACEWAYS TIGHT TO STRUCTURAL CEILING AND AS HIGH AS POSSIBLE WITHIN CEILING SPACES TO MAINTAIN MAXIMUM AMOUNT OF CLEAR SPACE BELOW RACEWAY.
21. INSTALL RACEWAYS CONCEALED IN BUILDING FINISHES FOR ALL EXTERIOR MOUNTED DEVICES. DO NOT ROUTE EXPOSED ON BUILDING EXTERIOR.
22. INSTALL RACEWAYS CONCEALED IN WALLS, UNDER FLOORS, ABOVE CEILINGS, ETC., EXCEPT AS FOLLOWS:
-WHERE SUSPENDED CEILINGS ARE NOT PROVIDED
-IN VERTICAL SHAFTS, ELECTRICAL CLOSETS, ETC., MECHANICAL AND ELECTRICAL EQUIPMENT SPACES WHERE CONCEALMENT IS NOT PRACTICAL.
-AT SURFACE-MOUNT PANELBOARDS IN OTHERWISE FINISHED SPACES LIMITED TO VERTICAL RUNS ABOVE AND BELOW PANEL
-WHERE REQUIRED FOR EQUIPMENT CONNECTIONS
-WHERE SPECIFICALLY INDICATED ON DRAWINGS
23.
24.
OWNER-FURNISHED EQUIPMENT: VERIFY AND COORDINATE ELECTRICAL ROUGH-IN REQUIREMENTS FOR OWNER-FURNISHED EQUIPMENT WITH CONTRACTING OFFICER PRIOR TO PULLING CONDUCTORS AND MAKING FINAL CONNECTIONS. LACK OF COORDINATION SHALL NOT JUSTIFY CHANGE ORDERS.
WHERE SUBMITTED EQUIPMENT REQUIRES REVISION TO OVERCURRENT PROTECTION, CONDUIT, AND WIRING, COORDINATE AND MAKE CHANGE TO PROVIDE A COMPLETE
INSTALLATION IN ACCORDANCE WITH APPLICABLE CODES.
DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS. PROVIDE COMPONENTS INDICATED ON RISER DIAGRAMS WHETHER OR NOT INDICATED
ON PLANS, AND VICE VERSA.
2.
3.
PRIOR TO DEMOLITION, FIELD VERIFY CONDUITS, CONDUCTORS, AND CABLES THAT PASS THROUGH AND SERVE AREAS OUTSIDE THE SCOPE OF WORK. MAINTAIN CONTINUITY OF SYSTEMS. PROTECT OR RELOCATE SYSTEMS TO PREVENT DAMAGE. RESTORE SYSTEMS TO NORMAL OPERATION. COORDINATE SYSTEM OUTAGES WITH CONTRACTING
OFFICER.
IDENTIFY NONFUNCTIONING EQUIPMENT AND DEVICES TO REMAIN AFTER DEMOLITION. NOTIFY CONTRACTING OFFICER IN WRITING PRIOR TO DEMOLITION. UPON COMPLETION
OF WORK, ENSURE THAT EXISTING EQUIPMENT AND DEVICES OPERATE PROPERLY.
4.
5.
6.
7.
13.
10.
9.
THE FACILITY WILL NOT REMAIN OCCUPIED DURING RENOVATIONS.
AFTER DEMOLITION VERIFY AND SUPPORT REMAINING CABLES, WIRES, AND CONDUIT IN ACCORDANCE WITH THE APPLICABLE VERSION OF THE NEC. DISCONNECT, MAKE
SAFE AND REMOVE ABANDONED AND TEMPORARY WIRE WITHIN SPACE.
WHERE CIRCUITS ARE REMOVED BACK TO PANELS, ASSOCIATED BREAKERS WILL BE UTILIZED FOR NEW CIRCUITING.
1.
EXISTING CONDITIONS REFLECT GENERAL OBSERVATIONS AND ARE NOT INTENDED TO INDICATE DETAILS OR DIMENSIONS. NO ATTEMPT HAS BEEN MADE TO SHOW ALL ELECTRICAL EQUIPMENT. VERIFY EXISTING CONDITIONS PRIOR TO PERFORMING WORK. NOTIFY CONTRACTING OFFICER IN WRITING IF CONDITIONS ARE DISCOVERED THAT
PREVENT EXECUTION OF WORK.
PROTECT REMAINING ELECTRICAL SYSTEMS AND COMPONENTS FROM DAMAGE. REMOVE PROTECTIVE MATERIALS UPON COMPLETION OF WORK.
8. DISPOSE OF LIGHTING BALLASTS AND CAPACITORS CONTAINING PCB'S, AS DEFINED BY THE ENVIRONMENTAL PROTECTION AGENCY (EPA), IN ACCORDANCE WITH
APPLICABLE LOCAL, STATE, FEDERAL AND EPA REGULATIONS.
PROVIDE CONTRACTING OFFICER WITH INVENTORY OF MAJOR ELECTRICAL ITEMS TO BE REMOVED. CONTRACTING OFFICER WILL SELECT ITEMS TO BE SALVAGED. TURN SALVAGED ITEMS OVER TO GOVERNMENT. ITEMS REJECTED BY THE CONTRACTING OFFICER SHALL BECOME THE PROPERTY OF THE CONTRACTOR. REMOVE DEMOLISHED
ITEMS FROM SITE.
12.
11. PROVIDE BLANK COVER PLATES FOR DEVICES REMOVED WHEN A REPLACEMENT DEVICE IS NOT INDICATED.
MAINTAIN CONTINUITY OF CIRCUITS AND FEEDERS REMAINING AFTER DEMOLITION IN PANELS INDICATED TO BE DEMOLISHED OR REPLACED. EXTEND EXISTING CIRCUITS AND FEEDERS REMAINING AFTER DEMOLITION TO NEW PANELS. CIRCUIT BREAKER, CONDUIT, AND WIRE SHALL MATCH EXISTING TYPES AND SIZES.
IN AREAS NOTED TO REMOVE ELECTRICAL WORK, REMOVE CONDUITS AND ASSOCIATED SUPPORTS BACK TO POINT OF CONCEALMENT AND REMOVE WIRING BACK TO
REMAINING ACTIVE DEVICES OR SOURCE.
REPAIR DISTURBED AREAS TO MATCH EXISTING CONDITIONS.
GENERAL ELECTRICAL NOTES
GENERAL ELECTRICAL DEMOLITION/RENOVATION NOTES
25. PROVIDE NECESSARY SUPPORTING STRUT CHANNEL AND ALL MISCELLANEOUS HARDWARE FOR MOUNTING ELECTRICAL EQUIPMENT. MAINTAIN NEC WORKING CLEARANCES.
COORDINATE EXACT LOCATION IN FIELD. DO NOT MOUNT ON EQUIPMENT ACCESS PANELS OR IN EQUIPMENT MANUFACTURER'S RECOMMENDED MAINTENANCE CLEARANCES.
(APPLICABLE TO ALL ELECTRICAL DRAWINGS)
(APPLICABLE TO ALL ELECTRICAL DRAWINGS)
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:2
A
M
JLW
JLW
03/14/2024
E0.2JST
ELECTRICAL NOTES
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
EX PANEL MF1
EX PANEL MF2
GFIGFI
WPWP
RX
ACCU
EX
ACCU
RX
ACCU
aa bb cc
++ GFIGFI
EX PANEL DP
EX ATS
RX ACU
RX ACU
RX PANEL MF2A
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
ED1.1JST
FIRST FLOOR - ELECTRICAL
DEMOLITION
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
DRAWING NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY DASHED
HEAVY LINEWEIGHT ( ) INDICATES EXISTING WORK TO BE
REMOVED. ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT
( ) INDICATES EXISTING ITEMS TO REMAIN.
1.
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING
CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING
DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT
INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.
THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL
EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF
ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT
DIRECTION BEFORE PROCEEDING WITH THE WORK.
2.
ETR GENERATOR.
REMOVE AND SALVAGE EXISTING RACK, EQUIPMENT, AND UPS FOR
REINSTALLATION UNDER NEW WORK.
SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
SCALE AED1.1
1 FIRST FLOOR - ELECTRICAL DEMOLITION
SCALE OF FEET
4 0 4 8
SCALE A
3 EXISTING TELECOM SERVICE ENTRANCE EQUIPMENT AND
PUNCHDOWN BLOCKS.
a a a a a aa aa aa a bb b b b c c c c cccc
EX AHU
RX AHU
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
ED1.2JST
MEZZANINE - ELECTRICAL
DEMOLITION
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
DRAWING NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY DASHED
HEAVY LINEWEIGHT ( ) INDICATES EXISTING WORK TO BE
REMOVED. ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT
( ) INDICATES EXISTING ITEMS TO REMAIN.
1.
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING
CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING
DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT
INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.
THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL
EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF
ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT
DIRECTION BEFORE PROCEEDING WITH THE WORK.
2.
RX LIGHTING CONTACTOR FOR TRAINING ROOM.
ETR LIGHTING CONTACTOR FOR CARPENTRY SHOP.
SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
SCALE AED1.2
1 MEZZANINE - ELECTRICAL DEMOLITION
SCALE OF FEET
4 0 4 8
SCALE A
J
J J
J
J J
EX PANEL MF1
EX PANEL MF2
PANEL MF2A
GFIGFI
WPWP
EX
ACCU
EX ATS
EX PANEL DP
ELECTRICAL ROOM
KITCHEN
CORRIDOR
C01
WASHER
UNISEX TOILET
LOCKERS
OFFICE
TRAINING ROOM
OFFICE
HOOD-1
EF-1 EF-2
HPU-1 HPU-2
DS-HPU-1 DS-HPU-2
GFIGFI
GFIGFI
GFIGFIGFIGFI
PANTRY
GFIGFI++
GFIGFI GFIGFI
GFIGFI
GFIGFI
52"52" 52"52"
C
C
C
P
P
P
ACCU-1
2,4,6(MF2)2,4,6(MF2)
2,4,6
8,10,12(MF2)8,10,12(MF2)
18,20(MF2)18,20(MF2)
14,16(MF2)14,16(MF2)
ACU-1
DS-ACCU-1
7,9(MF2)7,9(MF2)
252525(MF2)25(MF2)
4(MF2A)4(MF2A)
24(MF2)24(MF2)
1(MF2A)1(MF2A)
3(MF2A)3(MF2A)
7(MF2A)7(MF2A)
5(MF2A)5(MF2A)
2(MF2A)2(MF2A)
23(MF2)23(MF2)
6(MF2A)6(MF2A)
8(MF2A)8(MF2A)
1111 1111
9(MF2A)9(MF2A)
11(MF2A)11(MF2A)
17(MF2A)17(MF2A)
13,15(MF2A)13,15(MF2A)
TMGB
WOOD SHOP
9TELECOM
TR01
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E1.1JST
FIRST FLOOR - POWER NEW
WORK
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
SCALE AE1.1
1 FIRST FLOOR - POWER - NEW WORK
DRAWING NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID
HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.
ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )
INDICATES EXISTING ITEMS TO REMAIN.
1.
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING
CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING
DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT
INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.
THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL
EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF
ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT
DIRECTION BEFORE PROCEEDING WITH THE WORK.
2.
ETR GENERATOR.
FOR RANGE GAS SHUT OFF ASSEMBLY BOX. LOCATE WITHIN LOWER
CABINETRY.
SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
SCALE OF FEET
4 0 4 8
SCALE A
3 FOR WASHER. MOUNT TO SUIT EQUIPMENT.
4 FOR DISHWASHER. MOUNT TO SUIT EQUIPMENT.
5 FOR REFRIGERATOR. MOUNT TO SUIT EQUIPMENT. PROVIDE 1P-20A
GFI CIRCUIT BREAKER.
6 LOCATION OF SYSTEM FURNITURE DATA CONNECTION. PROVIDE 2"
CONDUIT WITH PULL STRING TO TELECOM RACK.
7 FOR STACKED DRYER. MOUNT TO SUIT EQUIPMENT. PROVIDE NEMA
14-30R RECEPTACLE. PROVIDE 4-WIERE (2PH, N, G) CIRCUIT
WIRING.
8 FOR COPIER.
9 LOCATION OF EXISTING TELECOMMUNICATIONS RACK.
SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
EX AHU
DWH-1
FCU-1.2
FCU-1.1
FCU-2.1
GFIGFI
GFIGFI
GFIGFI
13,15(MF2)13,15(MF2)
13,15(MF2)13,15(MF2)
17,19(MF2)17,19(MF2)
12(MF2A)12(MF2A)
10(MF2A)10(MF2A)
PUMP-1
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E1.2JST
MEZZANINE - POWER NEW WORK
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
DRAWING NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID
HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.
ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )
INDICATES EXISTING ITEMS TO REMAIN.
1.
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING
CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING
DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT
INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.
THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL
EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF
ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT
DIRECTION BEFORE PROCEEDING WITH THE WORK.
2.
TEXT.
TEXT.
SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
SCALE AE1.2
1 MEZZANINE - POWER - NEW WORK
SCALE OF FEET
4 0 4 8
SCALE A
bb aa
ELECTRICAL ROOM
KITCHEN
TELECOM
TR01
CORRIDOR
C01
WASHER
UNISEX TOILET
LOCKERS
OFFICE
OFFICE
TRAINING ROOM
B1B1
B1B1
D1D1 D1D1
D1D1
D2D2
D3D3
D3D3
D3D3 D3D3
D3D3
B1B1 B1B1
B1B1 B1B1
B1B1 B1B1
B1B1 B2B2
B2B2 B2B2
B2B2
B1B1B1B1
LV1DLV1D
LV1DLV1D
LV1DLV1D
OS2OS2
OS2OS2
LV2d,eLV2d,e
LV1dLV1d
LV1DcLV1Dc
LV1DcLV1Dc
31d31d 31d31d
31d31d
31d31d 31d31d
B1B1
OSOS
OSOS
B1B1
OSOS
E1E1
E1E1
E1E1
E1E1
D1D1 D1D1 D1D1 ee ee ee
29c29c
29c29c
29c29c
29c29c
29c29c
29c29c
29c29c
29c29c 29c29c
29c29c
29c29c
29c29c
29c29c
AA AA AA
AAAAAA
AA
AA
AA AA
AA
AAAA
W1W1
29292929
29292929
29292929
2929 2929
3131 3131
PANTRY
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E2.1JLW
FIRST FLOOR - LIGHTING NEW
WORK
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
DRAWING NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID
HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.
ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )
INDICATES EXISTING ITEMS TO REMAIN.
1.
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING
CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING
DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT
INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.
THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL
EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF
ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT
DIRECTION BEFORE PROCEEDING WITH THE WORK.
2.
TEXT.
TEXT.
SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
SCALE AE2.1
1 FIRST FLOOR - LIGHTING - NEW WORK
SCALE OF FEET
4 0 4 8
SCALE A
AA
AA
AA
AA
AA
AA
AA
AA AA
AA
AA
AA
AA
bb bb bb bb bb aaaa aa aa aaaaaa aa aaaa aa aa
29c29c
29c29c
29c29c
29c29c
29c29c
29c29c
29c29c
29c29c 29c29c
29c29c
29c29c
29c29c
29c29c
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E2.2JLW
MEZZANINE - LIGHTING NEW
WORK
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
DRAWING NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID
HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.
ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )
INDICATES EXISTING ITEMS TO REMAIN.
1.
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING
CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING
DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT
INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.
THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL
EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF
ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT
DIRECTION BEFORE PROCEEDING WITH THE WORK.
2.
TEXT.
TEXT.
SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
SCALE AE2.2
1 MEZZANINE - LIGHTING - NEW WORK
SCALE OF FEET
4 0 4 8
SCALE A
ELECTRICAL ROOM
KITCHEN
TELECOM
TR01
CORRIDOR
C01
WASHER
UNISEX TOILET
LOCKERS
OFFICE
OFFICE
TRAINING ROOM
PANTRY
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E3.1JST
FIRST FLOOR - SECURITY NEW
WORK
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
DRAWING NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID
HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.
ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )
INDICATES EXISTING ITEMS TO REMAIN.
1.
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING
CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING
DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT
INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.
THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL
EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF
ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT
DIRECTION BEFORE PROCEEDING WITH THE WORK.
2.
TEXT.
TEXT.
SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
SCALE OF FEET
4 0 4 8
SCALE A
SCALE AE3.1
1 FIRST FLOOR - SECURITY - NEW WORK
MECHANICAL MEZZANINE
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E3.2JST
MEZZANINE - SECURITY NEW
WORK
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
DRAWING NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID
HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.
ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )
INDICATES EXISTING ITEMS TO REMAIN.
1.
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING
CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING
DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT
INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.
THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL
EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF
ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT
DIRECTION BEFORE PROCEEDING WITH THE WORK.
2.
TEXT.
TEXT.
SPECIAL NOTES:
(APPLICABLE TO THIS DRAWING ONLY)
SCALE OF FEET
4 0 4 8
SCALE A
SCALE AE3.2
1 MEZZANINE - SECURITY - NEW WORK
POWER TYPE
PANEL #XX
P O
W E
R T
Y P
E
P A
N E
L
X X
ALTERNATE
LOCATION
P O
W E
R T
Y P
E
P A
N E
L
X X
ALTERNATE
LOCATION
POWER TYPE
PANEL #XX
P O
W E
R T
Y P
E
P A
N E
L
X X
PROVIDE 0.59" WIDE POLYESTER ADHESIVE TAPE LABELS, 1.77" LONG
WITH BLACK 1/8" HIGH TIMES NEW ROMAN TEXT. REPLACE POWER
TYPE WITH PANEL SOURCE, EXAMPLE: "NORMAL POWER", "PANEL"
WITH THE PANEL NAME, AND "XX" WITH THE CIRCUIT NUMBER OR
NUMBERS SEPARATED BY COMMAS. DO NOT COVER SCREWS.
2-1/2"
5"
SELF-ADHESIVE
ENGRAVED
PLASTIC LABEL
EQUIPMENT
DESIGNATION
FED FROM ####
###V, 3PH, #W ELECTRICAL
CHARACTERISTICS
POWER SOURCE; PANEL NAME
AND CIRCUIT #
GENERAL NOTES:
A. ALL NEW SAFETY SWITCHES, STARTERS, ENCLOSED CIRCUIT BREAKERS, AND
VARIABLE SPEED MOTOR CONTROLLERS SHALL BE PROVIDED WITH LABELS.
B. CENTER ALL TEXT HORIZONTALLY.
C. MODIFY TEXT AS REQUIRED.
D. EQUIPMENT CONNECTED TO NORMAL POWER SYSTEMS SHALL HAVE BLACK
LETTERS ON WHITE BACKGROUND.
E. EQUIPMENT CONNECTED TO EMERGENCY POWER SYSTEMS SHALL HAVE WHITE
LETTERS ON RED BACKGROUND.
2-1/2"
MIN 5"
FED FROM ####
###Y/###V, 3PH, #W
PANEL ####
SYSTEM TYPE
PANEL DESIGNATION
SELF-ADHESIVE ENGRAVED
PLASTIC LABEL
ELECTRICAL CHARACTERISTICS
PANEL LABEL PER THIS DETAIL
"NORMAL POWER" OR
"EMERGENCY POWER"
POWER SOURCE; PANEL NAME AND
CIRCUIT # OR TRANSFORMER NAME IF
FED FROM TRANSFORMER
GENERAL NOTES:
A. ALL NEW PANELBOARDS SHALL BE PROVIDED
WITH LABELS.
B. CENTER ALL TEXT HORIZONTALLY.
C. MODIFY TEXT AS REQUIRED.
D. PANELBOARDS CONNECTED TO NORMAL
POWER SYSTEMS SHALL HAVE BLACK
LETTERS ON WHITE BACKGROUND.
NEUTRAL
GROUND
PHASE PHASE PHASE
A B C
CIRCUIT A
L1 N1 G1
CIRCUIT B
L2 N2 G1
CIRCUIT C
L3 N3 G1
SYSTEM GROUND-G1-BARE
NEUTRAL-N2-WHITE/RED
NEUTRAL-N1-WHITE
HOT-L3-BLUE
HOT-L2-RED
HOT-L1-BLACK
THREE PHASE 240/120V CIRCUIT PANEL
RECPTACLE CONNECTIONS (LOAD)
NEUTRAL-N3-WHITE/BLUE
3'-6"
MAGNETIC
SWITCH
FLOOR
CEILING
SECURITY SYSTEM EQUIPMENT WILL BE PURCHASED AND
INSTALLED BY OWNER/OPERATOR.
CONTRACTOR SHALL PROVIDE EMPTY CONDUIT SYSTEM.
SINGLE GANG JUNCTION
BOX FOR CARD READER
NOTE:
21mm (3/4")
CONDUIT HOME RUN
TO PANELBOARD
21mm (3/4") CONDUIT TO
"REQUEST TO EXIT" DEVICE
21mm (3/4") CONDUIT
TO CARD READER
21mm (3/4") CONDUIT
TO MAGNETIC SWITCH
"REQUEST TO EXIT" DEVICE LOCATED
ON SECURE SIDE OF DOOR.
300mm (12") X 300mm (12") X 100mm
(4") DOOR CONTROL JUNCTION BOX.
(LOCATE ON SECURE SIDE OF DOOR)
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E5.1JST
ELECTRICAL DETAILS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
NO SCALEE5.1
1 WIRING DEVICES COVER PLATE MARKING
NO SCALEE5.1
2 DISCONNECT/STARTER/SWITCH/VSMC LABEL
NO SCALEE5.1
3 PANELBOARD LABELS
NO SCALEE5.1
4 SYSTEMS FURNITURE POWER SUPPLY
NO SCALEE5.1
5 CARD READER RACEWAY DETAIL
KW
ETR PANEL DP
240/120V, 600A,3PH,4W
EX UTILITY METER
P A
P A
P A
P A
P A
G
EX NATURAL
GAS GENERATOR
125KVA
EX ATS
600A
ETR PANEL MF1
240/120V, 200A,3PH,4W3
P
A ETR PANEL MF2
240/120V, 200A,3PH,4W3
P
A ETR PANEL ES1
240/120V, 225A,3PH,4W3
P
A ETR PANEL BAL
240/120V, 200A,3PH,3W3
P A
RX PANEL MF2A
240/120V, 60A,1PH,3W
P A
KW
ETR PANEL DP
240/120V, 600A,3PH,4W
EX UTILITY METER
P A
P A
P A
P A
P A
G
EX NATURAL
GAS GENERATOR
125KVA
EX ATS
600A
ETR PANEL MF1
240/120V, 200A,3PH,4W3
P
A ETR PANEL MF2
240/120V, 200A,3PH,4W3
P
A ETR PANEL ES1
240/120V, 225A,3PH,4W3
P
A ETR PANEL BAL
240/120V, 200A,3PH,3W3
P A
PANEL MF2A
240/120V, 60A,1PH,3W
P A
CX
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E6.1JST
ELECTRICAL ONE-LINE
DIAGRAMS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
NO SCALEE6.1
1 ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION
NO SCALEE6.1
2 ELECTRICAL ONE-LINE DIAGRAM - NEW WORK 323963
5 6 10 11 14 15 18 21
26 27 28 29 31 32 34 36 38 39 40 41 44 46 48
1 2 3 4 7 8 9 12 13 16 17 19 20 22 23 24
25 30 33 35 37 42 43 45 47
48 PORT DATA PATCH
PANEL CAT6A RATED.
LOCATED IN IT RACK.
LABEL
BLUE RJ45 CAT6 OUTLETS
CONNECTOR, TYPICAL.
SYMBOL ON FLOOR PLANS:
CAT6A CABLE 4 PAIR (CMP) BLUE SHEATH, TYPICAL.
5 6 10 11 14 15 18 21
26 27 28 29 31 32 34 36 38 39 40 41 44 46 48
1 2 3 4 7 8 9 12 13 16 17 19 20 22 23 24
25 30 33 35 37 42 43 45 47
48 PORT PHONE PATCH
PANEL CAT 6A RATED.
LOCATED IN IT RACK.
LABEL
BLUE RJ45 CAT6 OUTLETS
CONNECTOR, TYPICAL.
SYMBOL ON FLOOR PLANS:
5 6 10 11 14 15 18 21
26 27 28 29 31 32 34 36 38 39 40 41 44 46 48
1 2 3 4 7 8 9 12 13 16 17 19 20 22 23 24
25 30 33 35 37 42 43 45 47
FIRE RATED
PLYWOOD BACKBOARD
WALL MOUNTED
GROUND BAR
RELOCATED RACK
AND EQUIPMENT
IT RACK
TR01
TELECOM
WOODSHOP
OFFICE
EX
KITCHEN
OFFICE
ELEC
TRAINING ROOM
JJJ
1-1/4"C FOR IT
CONDUIT, TYPICAL
2"C FOR SYSTEMS
FURNITURE CONDUIT,
TYPICAL
IT RACK
TR01
TELECOM
C01
CORRIDOR
TRAINING ROOM
WOODSHOP
POE
NETWORK
VIDEO RECORDER
UPS
VIDEO
MANAGEMENT
SOFTWARE
MONITOR
CAT6A CABLE IN
1" CONDUIT, TYPICAL
MECH MEZZ
CRDPKMSMSMSDP
MS
TO ELEC RM
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E6.2JST
TELECOMMUNICATIONS AND
SECURITY RISER DIAGRAMS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
NO SCALEE6.2
TYPICAL TELEPHONE AND DATA OUTLET WIRING
DIAGRAM
NO SCALEE6.2
3 TYPICAL IT RACK INSTALLATION
NO SCALEE6.2
1 TELECOM RISER DIAGRAM
NO SCALEE6.2
4 SECURITY RISER DIAGRAM
$OS
NEUTRAL
LINE
BUTTON FOR
OVERRIDE
CONTROL
STATUS INDICATOR LIGHT
SENSOR LENS
LUMINAIRE(S)
BASIS OF DESIGN PRODUCT: SENSOR SWITCH MODEL #WSX PDT
NOTE: GROUND WIRE NOT SHOWN, HOWEVER SHALL
BE PROVIDED WITH ALL CIRCUIT WIRING PER NEC.
ON
OFF
CAT 5 CAT 5
BLUE
BLUE
LINE
BLK/ORN
WHT
NEUTRAL
RELAY PACK
BLK-120V
ORN-277V
(CAP UNUSED)
WIRING NOTE: PROVIDE GROUND WIRE WITH ALL LINE VOLTAGE WIRING.
CAT 5
ADDITIONAL OCCUPANCY SENSORS AS
INDICATED ON FLOOR PLANS. DAISY
CHAIN MULTIPLE SENSORS TOGETHER.
LOW VOLTAGE SWITCH
TYPE LV1
CEILING OR WALL MOUNTED
OCCUPANCY SENSOR
REFER TO FLOOR PLANS
FOR TYPE(S)
CEILING OR WALL MOUNTED
OCCUPANCY SENSOR
REFER TO FLOOR PLANS
FOR TYPE(S)
LUMINAIRE(S)
W
ALL
B
OX O
CCUPANCY S
ENSOR(S
) W
ITH S
IN
GLE
O
UTPUT R
ELA
Y
W
ALL
B
OX O
CCUPANCY S
ENSOR(S
) W
IT
H D
UAL O
UTPUT R
ELA
YS
TOGGLE
S
W
ITCH(E
S)
LU
MIN
AIR
E W
ITH B
UILT
-IN
O
CCUPANCY S
ENSOR
CEILI
NG/W
ALL
M
OUNTED O
CCUPANCY S
ENSOR
- DIG
IT
AL S
W
IT
CH(E
S)
CEILI
NG/W
ALL
M
OUNTED O
CCUPANCY S
ENSORS
-IN
DOOR P
HOTOSENSORS
OUTDOOR P
HOTOCELL
S
ASTRONOMIC
AL T
IM
ECLO
CK
SW
IT
CHIN
G
STEP-D
IM
MIN
G
FULL
R
ANGE D
IM
MIN
G
OCCUPANCY S
ENSOR T
IM
EOUT/D
ELA
Y (IN
M
IN
UTES)
TIM
ECLO
CK S
CHEDULE
D 'O
FF' T
IM
E
OCC. S
ENSOR O
VERRID
E T
IM
ECLO
CK D
URIN
G 'O
FF' H
OURS
TIM
ECLO
CK S
CHEDULE
D 'O N' T
IM
E
DAYLIG
HTIN
G-D
IM
LI
GHTS TO M
AIN
TAIN
M
IN
IM
UM 50
FC A
T 30
"A
FF
- - - - - - - X - - - - X - - - - - - - - -
X - - - - - - - - - - - X - - - - - - - -
- - - - - - - - - X - - X - - - - - - - - - -
X
X
ELECTRICAL
RESTROOM
EXTERIOR
LIG
HTS M
ANUAL O
N
LIG
HTS A
UTOMATIC
O
N 10 0%
LI
GHT LE
VEL U
PON O
CCUPANCY
LIG
HTS A
UTO O
N 50
U
PON O
CCUPANCY, 1
M
ANUAL O
N
LINE VOLTAGE
CONTROL DEVICES
LOW VOLTAGE
CONTROL DEVICES
MISCELLANEOUSSWITCHING/DIMMING NOTES
TYPICAL SPACE TYPE
- - - - - - X X - - - - - - X - 15 - - - - - -X - -OFFICE
- - - - - - X X - - - - - - X - 15 6AM 5PM X - - -X - -CORRIDOR
- - X - - - - - - - - - X - - - 5 - - - - - -- X -STORAGE/TELECOM
- - - - - - - X - - - - X - - - 15 - - - - - -X - -LOCKERS
- - - - - - X X - - - - - - X - 15 - - - - - -X - -TRAINING ROOM
$OS2
BASIS OF DESIGN PRODUCT:
SENSOR SWITCH MODEL #WSX PDT 2P FAN-ASHRT
NOTE: GROUND WIRE NOT SHOWN, HOWEVER SHALL BE
PROVIDED WITH ALL CIRCUIT WIRING PER NEC.
NEUTRAL
LINE
STATUS INDICATOR LIGHT
SENSOR LENS
BUTTON FOR
OVERRIDE CONTROL
OF LUMINAIRE(S)
BUTTON FOR OVERRIDE
CONTROL OF FAN
LUMINAIRE(S)
BATHROOM
FAN
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E7.1JST
LIGHTING CONTROL DIAGRAMS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
NO SCALEE7.1
1 OCCUPANCY SENSOR WALL SWITCH
NO SCALEE7.1
ONE ZONE SWITCHING LIGHTING CONTROL WITH
OCCUPANCY SENSOR(S) AND SWITCH(ES)
NO SCALEE7.1
3 OCCUPANCY SENSOR WALL SWITCH WITH FAN
NOTES: (APPLICABLE TO LUMINAIRE SCHEDULE ONLY)
LAMP TYPES ARE INDICATED BY INDUSTRY GENERIC DESIGNATIONS; SEE SPECIFICATIONS FOR APPROVED MANUFACTURERS.1.
A.
CATALOG NUMBERS FOR LUMINAIRES INDICATE THE TYPE AND QUALITY OF THE LUMINAIRE TO BE PROVIDED BY THE CONTRACTOR AND ARE GENERAL IN NATURE. THE CATALOG NUMBERS ARE NOT INTENDED TO INDICATE AN ACTUAL ORDER MODEL NUMBER. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE LUMINAIRES WITH THE TYPE OF LAMP, BALLAST, LENS OR DIFFUSER, AND CONSTRUCTION FEATURES AS INDICATED IN THE SPECIFICATIONS.
2.
WHERE A LUMINAIRE IS NOTED AS "NO EQUAL," SUBSTITUTIONS WILL NOT BE ACCEPTED. EQUIVALENT LUMINAIRES WILL BE ACCEPTED PROVIDED THEY ARE PROVEN TO BE EQUAL TO, OR BETTER THAN, THE SPECIFIED LUMINAIRE IN ALL RESPECTS. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, CONSTRUCTION FEATURES, APPEARANCE, AND PERFORMANCE. SUBMIT THE FOLLOWING FOR
EACH PROPOSED SUBSTITUTION:
3.
SAMPLE OF PROPOSED EQUIVALENT LUMINAIRE FOR TABLE-TOP EVALUATION. SAMPLE SHALL BE AN EXACT MATCH TO THE PROPOSED SUBSTITUTION INCLUDING ALL FEATURES, FINISHES, LAMPING, OPTIONS, ACCESSORIES, MOUNTING BRACKETS, ETC. SAMPLE SHALL INCLUDE 120V CORD AND NEMA 5-20P PLUG FOR OPERATIONAL TEST DURING TABLE-TOP EVALUATION.
B.POINT-BY-POINT LIGHT LEVEL CALCULATIONS IN 3-DIMENSIONAL LIGHTING CALCULATION SOFTWARE TO ILLUSTRATE GUARANTEED ILLUMINATION LEVELS. EACH SPACE AFFECTED BY A SUBSTITUTION SHALL BE MODELED AND CALCULATED USING INDUSTRY STANDARD VALUES FOR REFLECTANCES, LIGHT LOSS FACTOR, ETC. ENGINEER WILL COMPARE TO BASIS OF DESIGN LUMINAIRE AND ENGINEER'S CALCULATIONS TO APPROVE OR REJECT SUBSTITUTE LUMINAIRE. PROVIDE IES FILE TO ENGINEER FOR PROPOSED SUBSTITUTE ALONG WITH CALCULATION
RESULTS.
C. POINT-BY-POINT COMPARATIVE DATA IN SIDE-BY-SIDE FORMAT COMPARING FEATURES OF SUBSTITUTE LUMINAIRE TO BASIS-OF-DESIGN LUMINAIRE.
D. ALL REQUIREMENTS OF DIVISION 1 SECTION "SUBSTITUTION PROCEDURES."
COORDINATE CONTROL COMPATIBILITY BETWEEN BALLAST/DRIVER TYPES FOR ALL DIMMED LUMINAIRES WITH MANUFACTURER AND MODEL OF DIMMING CONTROL DEVICES.4.
PROVIDE EXIT SIGNS WITH SINGLE FACE OR DOUBLE FACE AND WITH OR WITHOUT CHEVRONS AS INDICATED ON THE DRAWINGS. PROVIDE RED OR GREEN LETTERING AS REQUIRED BY AHJ.5.
ALL MOUNTING HEIGHTS SHALL BE AS INDICATED ON THE DRAWINGS OR AS DIRECTED BY THE CONTRACTING OFFICER. MOUNTING HEIGHTS OF WALL MOUNTED LUMINAIRES SHALL BE MEASURED FROM THE FINISHED FLOOR TO THE CENTERLINE OF THE LUMINAIRE. MOUNTING HEIGHTS OF CEILING SUSPENDED LUMINAIRES SHALL BE MEASURED FROM THE FINISHED FLOOR TO THE BOTTOM
OF THE LUMINAIRE.
6.
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E8.1JST
LUMINAIRE SCHEDULE
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
LUMINAIRE SCHEDULE
TYPE MOUNTING LUMINAIRE DESCRIPTION MANUFACTURER CATALOG NUMBER
LAMP DRIVER / BALLAST
VOLTAGE
INPUT
WATTS NOTES
TYPE CRI CCT QTY
WATTS /
LAMP
LUMENS
/ LAMP
TYPE QTY
BALLAST
FACTOR
A RECESSED
24" X 48" X 3-1/4" VOLUMETRIC TROFFER LUMINAIRE WITH
EXTRUDED ALUMINUM HOUSING, ANGLED ACRYLIC LENS, 3000
LUMEN PACKAGE, INTEGRAL DRIVER, AND WHITE FINISH.
METALUX 24EN-LD2-30-UNV-L835-CD1-U LED 80 3500 1 25 3117 0-10V DIMMING 1 1.00 120 25 -
B1 RECESSED
24" X 24" X 3-1/4" VOLUMETRIC TROFFER LUMINAIRE WITH
EXTRUDED ALUMINUM HOUSING, ANGLED ACRYLIC LENS, 1900
LUMEN PACKAGE, INTEGRAL DRIVER, AND WHITE FINISH.
METALUX 22EN-LD2-19-UNV-L835-CD1-U LED 80 3500 1 17 2091 0-10V DIMMING 1 1.00 120 17 -
B2 RECESSED
24" X 24" X 3-1/4" VOLUMETRIC TROFFER LUMINAIRE WITH
EXTRUDED ALUMINUM HOUSING, ANGLED ACRYLIC LENS, 2500
LUMEN PACKAGE, INTEGRAL DRIVER, AND WHITE FINISH.
METALUX 22EN-LD2-25-UNV-L835-CD1-U LED 80 3500 1 20 2701 0-10V DIMMING 1 1.00 120 20 -
D1 RECESSED
4" DOWNLIGHT LUMINAIRE WITH STEEL HOUSING, 1000 LUMEN
PACKAGE, WIDE DISTRIBUTION, INTEGRAL DRIVER, AND CLEAR TRIM
FINISH.
GOTHAM EVO4-35-10-AR-LSS-WD-MVOLT-GZ10 LED 80 3500 1 9 1000 0-10V DIMMING 1 1.00 120 9 -
D2 RECESSED
4" DOWNLIGHT LUMINAIRE WITH STEEL HOUSING, SHOWER RATED,
MEDIUM WIDE DISTRIBUTION, INTEGRAL DRIVER, AND CLEAR TRIM
FINISH.
GOTHAM EVO4SH-35-10-DFR-SOL-MVOLT-EZ1 LED 80 3500 1 9 843 0-10V DIMMING 1 1.00 120 9 -
D3 RECESSED
4" DOWNLIGHT LUMINAIRE WITH STEEL HOUSING, 1400 LUMEN
PACKAGE, WIDE DISTRIBUTION, INTEGRAL DRIVER, AND CLEAR TRIM
FINISH.
GOTHAM EVO4-35-15-AR-LSS-WD-MVOLT-GZ10 LED 80 3500 1 14 1527 0-10V DIMMING 1 1.00 120 14 -
E1 WALL
12" X 8" X 2" LED EXIT SIGN WITH THERMOPLASTIC HOUSING,
RED OR GREEN LETTERS AS REQUIRED BY AHJ, DIRECTIONAL
CHEVRONS AS INDICATED ON DRAWINGS, NICAD BATTERY, AND
WHITE FINISH.
LITHONIA LQM-S-W-3-R/G-MVOLT-EL-N-SD LED - - - - - - - - 120 3 -
W1 WALL
24" X 5" X 4" WALL WRAPAROUND LUMINAIRE WITH STEEL
HOUSING, ACRYLIC LENS, INTEGRAL DRIVER, AND WHITE FINISH. LITHONIA WL2-12L-GZ10-LP835 LED 80 3500 1 12 1249 0-10V DIMMING 1 1.00 120 12 -
NOTES: (APPLICABLE TO MECHANICAL EQUIPMENT ELECTRICAL CONNECTION SCHEDULE ONLY)
REVIEW EQUIPMENT SUBMITTALS FROM OTHER TRADES PRIOR TO ORDERING OR INSTALLING ASSOCIATED ELECTRICAL WORK. ELECTRICAL CONTRACTOR SHALL MODIFY COMPONENTS OF THE ELECTRICAL CONNECTIONS AS NECESSARY TO MATCH NAMEPLATE DATA OF APPROVED EQUIPMENT AND PROVIDE A CODE COMPLIANT INSTALLATION, INCLUDING BUT NOT LIMITED TO CIRCUIT BREAKERS, WIRE, CONDUITS, CONNECTION TYPES, SWITCHES, AND FUSES. CHANGE ORDERS AND EXTRAS WILL NOT BE AWARDED FOR FAILURE TO COORDINATE
WITH OTHER TRADES' EQUIPMENT SUBMITTALS.
1.
PROVIDE NECESSARY SUPPORTING STRUT CHANNEL AND ALL MISCELLANEOUS HARDWARE FOR MOUNTING ELECTRICAL EQUIPMENT. MAINTAIN NEC WORKING CLEARANCES. FIELD COORDINATE EXACT LOCATIONS. DO NOT MOUNT ON EQUIPMENT ACCESS PANELS OR IN EQUIPMENT MANUFACTURERS' RECOMMENDED MAINTENANCE
CLEARANCES. COORDINATE EXACT LOCATION OF SAFETY SWITCHES WITH MECHANICAL
EQUIPMENT/CONTRACTOR.
2.
NOTES: (APPLICABLE TO DISCONNECT SWITCH SCHEDULE ONLY)
PROVIDE FUSE AND COORDINATE EXACT EQUIPMENT FUSE SIZE WITH MOTOR
OR EQUIPMENT NAMEPLATE DATA DURING CONSTRUCTION.
1.
ALL DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE WITH GROUND LUG.2.
PROVIDE ALL FUSIBLE DISCONNECT SWITCHES WITH CLASS R FUSE KIT.3.
LABEL DISCONNECT SWITCHES WITH THE DESIGNATION IDENTIFIED IN THIS
SCHEDULE AND THE CIRCUIT NUMBER AND PANELBOARD FROM WHICH IT IS
FED, INCLUDING VOLTAGE AND PHASE.
4.
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E8.2JST
ELECTRICAL EQUIPMENT
SCHEDULES
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
MECHANICAL EQUIPMENT ELECTRICAL CONNECTION SCHEDULE
EQUIPMENT
DESIGNATION KW HP MCA MOCP FLA VOLTAGE PHASE LOAD (kVA) WIRING DISCONNECTING MEANS CONTROL MEANS NOTES
ACCU-1 16.4 20 13.1 240 1 3.15 2#12 + #12GW IN 3/4"C DS-ACCU-1
ACU-1 - 20 0.0 240 1 0.00 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH FED FROM OUTDOOR UNIT
DWH-1 15 1.7 120 1 0.20 2#12 + #12GW IN 3/4"C RECEPTACLE EXISTING/RELOCATE
EF-1 2.25 15 1.8 120 1 0.21 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH
EF-2 2.25 15 1.8 120 1 0.21 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH
FCU-1.1 1.6 15 1.3 240 1 0.31 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH
FCU-1.2 2.8 15 2.3 240 1 0.54 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH
FCU-2.1 8.6 15 6.9 240 1 1.65 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH
HOOD-1 1.5 15 1.2 120 1 0.14 2#12 + #12GW IN 3/4"C -
HPU-1 29.1 35 23.3 240 1 5.59 2#8 + #10GW IN 3/4"C DS-HPU-1
HPU-2 29.1 35 23.3 240 1 5.59 2#8 + #10GW IN 3/4"C DS-HPU-2
PUMP-1 20 1.5 120 1 0.18 2#12 + #12GW IN 3/4"C -
DISCONNECT SWITCH SCHEDULE
DESIGNATION
AMP
RATING
POLES
VOLT
RATING
FUSE
AMPS
FUSE
CLASS
NEMA
ENCLOSURE
NOTES
DS-ACCU-1 60 2 240 20 RK5 3R
DS-HPU-1 60 2 240 35 RK5 3R
DS-HPU-2 60 2 240 35 RK5 3R
FEED THROUGH LUGS
DEMAND AMPS: 0 A
ISOLATED GROUND BUS d SHUNT TRIP BREAKER
DEMAND LOAD: 0.00 kVA
200% NEUTRAL BUS & LUGS c GFEP BREAKER (30mA) g RED BREAKER LOCKOUT
CONNECTED LOAD: 0.00 kVA
INTEGRAL SPD/TVSS b GFCI BREAKER (5mA) f HANDLE CLAMP
SERVICE ENTRANCE LABEL a AFCI BREAKER e HANDLE PADLOCK
PANEL TOTALS
X GROUND BUS AUXILIARIES:
PHASE AMPS: 0 A 0 A 0 A
PHASE LOAD: 0.00 kVA 0.00 kVA 0.00 kVA
41 0.00 0.00 20 1 EX AUTO TRANSFER SWITCH 42
EX HVAC 2 50
0.00 0.00 20 1 EX REC: ADT 40
37 EX AC BLOWER CARP SHOP 1 20 0.00 0.00 38
35 EX REC: CARP SHOP E WALL 1 20 0.00 0.00
60 2 EX LOAD CENTER
33 EX LOAD 1 20 0.00 0.00 20 1 EX LTG: CARP SHOP CENTER 34
31 EX LTG: GARAGE BAY E 1 20 0.00 0.00 30 1 EX LTG: CARP SHOP W 32
29 EX LTG: GARAGE BAY W 1 20 0.00 0.00 30 1 EX LTG: CARP SHOP E 30
27 EX LOAD 1 20 0.00 0.00 20 1 EX LTG: UPPER STORAGE 28
25 EX LTG: KITCHEN EAST 1 20 0.00 0.00 20 1 EX AC BLOWER STORAGE 26
23 EX REC: COFFEE POT 1 20 0.00 0.00 20 1 EX REC: MICROWAVE 24
21 EX POWER VENT CARP 1 20 0.00 0.00 20 1 EX REC: GARAGE INNER WALL 22
19 EX REC: BOOK HALL 1 20 0.00 0.00 20 1 EX LTG: CUSTODIAL 20
17 EX COMPUTER 1 20 0.00 0.00 20 1 EX LTG: OFF/KIT/SHWR 18
15 EX REC: N/W WALL, FAX 1 20 0.00 0.00 20 1 EX REC: COPY MACHINE 16
13 EX COMP COOLER 1 20 0.00 0.00 20 1 EX REC: WEST WALL GARAGE 14
11 EX OVERHEAD DOOR 1 20 0.00 0.00 20 1 EX OVERHEAD DOOR 1/2 12
9 EX REC: S WALL 1 20 0.00 0.00 20 1 EX REC: LOUNGE 10
7 EX REC: SE WALL 1 20 0.00 0.00 20 1 EX REC: N WALL GARAGE, NE 8
5 0.00 0.00 20 1 EX LTG: LOUNGE OUTSIDE 6
EX LOAD 2 40
0.00 0.00 4
1 EX LOAD 1 20 0.00 0.00
60 2 RX HVAC
CKT LOAD DESCRIPTION P TA AUX/NOTE A B C AUX/NOTE TA P LOAD DESCRIPTION CKT
FED FROM:
MANUFACTURER:
TYPE:
SERVICE TYPE: NORMAL
MIN. RATING: 10K AIC RMS SYMMETRICAL AMPS LOCATION: ELECTRICAL ROOM 108
SERVICE: 240 VOLTS W/ CENTER TAP 120 VOLTS, 3 PHASE, ... ENCLOSURE: NEMA 1
MAIN TYPE: 200 A MCB SECTIONS: 1EX PANEL MF2
BUS AMPACITY: 225 A MOUNTING: SURFACE
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
WALKER
ARCHITECTS,
GAINESVILLE, FL
/1
/2
:2
:3
A
M
JLW
JLW
03/14/2024
E8.3JST
PANELBOARD SCHEDULES
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
PANEL SCHEDULE NOTES (APPLICABLE TO PANEL SCHEDULES NOTE COLUMN ON THIS DRAWING ONLY):
1. PROVIDE NEW CIRCUIT BREAKER IN EXISTING AVAILABLE SPACE. MATCH PANELBOARD MANUFACTURER, TYPE, AND AIC RATING.
2. REMOVE EXISTING CIRCUIT BREAKER AND PROVIDE NEW IN SAME LOCATION. MATCH PANELBOARD MANUFACTURER, TYPE, AND AIC RATING. TURN OVER EXISTING CIRCUIT BREAKER TO OWNER FOR
USE AS SPARE.
3. CONNECT NEW LOAD TO EXISTING SPARE CIRCUIT BREAKER.
4. CONNECT NEW LOAD TO EXISTING CIRCUIT BREAKER MADE SPARE AFTER DEMOLITION.
5. REMOVE EXISTING LOAD AND RELABEL EXISTING CIRCUIT BREAKER AS "SPARE".
FEED THROUGH LUGS
DEMAND AMPS: 0 A ISOLATED GROUND BUS d SHUNT TRIP BREAKER DEMAND LOAD: 0.00 kVA 200% NEUTRAL BUS & LUGS c GFEP BREAKER (30mA) g RED BREAKER LOCKOUT
CONNECTED LOAD: 0.00 kVA INTEGRAL SPD/TVSS b GFCI BREAKER (5mA) f HANDLE CLAMP SERVICE ENTRANCE LABEL a AFCI BREAKER e HANDLE PADLOCK
PANEL TOTALS X GROUND BUS AUXILIARIES:
PHASE AMPS: 0 A 0 A 0 A
PHASE LOAD: 0.00 kVA 0.00 kVA 0.00 kVA
41 0.00 0.00 42
39 0.00 0.00 40
EX DELTA RADIAL ARM SAW 3 15
0.00 0.00
15 3 EX COMPRESSOR
35 0.00 0.00 36
33 0.00 0.00 34
EX DELTA RADIAL ARM SAW 2 3 15
0.00 0.00
15 3 EX MORTISE MACHINE
29 0.00 0.00 30
27 0.00 0.00 28
EX JOINER 3 15
0.00 0.00
15 3 EX UNISAW 10
23 0.00 0.00 24
21 0.00 0.00 22
EX LATHE 3 15
0.00 0.00
15 3 EX BAND SAW
17 0.00 0.00 18
15 0.00 0.00 16
EX OUTSIDE VAC 3 15
0.00 0.00
15 3 EX DUAL SANDER
11 0.00 0.00 12
9 0.00 0.00 10
EX DRILL PRESS 3 20
0.00 0.00
20 3 EX SCROLL SAW
5 0.00 0.00 6
3 0.00 0.00 4
EX BIG MAMA SAW 3 30
0.00 0.00
30 3 EX PLANER
CKT LOAD DESCRIPTION P TA AUX/NOTE A B C AUX/NOTE TA P LOAD DESCRIPTION CKT
FED FROM:
MANUFACTURER: TYPE:
SERVICE TYPE: NORMAL MIN. RATING: 10K AIC RMS SYMMETRICAL AMPS LOCATION: ELECTRICAL ROOM 109
SERVICE: 240 VOLTS W/ CENTER TAP 120 VOLTS, 3 PHASE, ... ENCLOSURE: NEMA 1
MAIN TYPE: 200 A MCB SECTIONS: 1EX PANEL MF1
BUS AMPACITY: 225 A MOUNTING: SURFACE
FEED THROUGH LUGS
DEMAND AMPS: 90 A ISOLATED GROUND BUS d SHUNT TRIP BREAKER DEMAND LOAD: 37.58 kVA 200% NEUTRAL BUS & LUGS c GFEP BREAKER (30mA) g RED BREAKER LOCKOUT
CONNECTED LOAD: 37.58 kVA INTEGRAL SPD/TVSS b GFCI BREAKER (5mA) f HANDLE CLAMP SERVICE ENTRANCE LABEL a AFCI BREAKER e HANDLE PADLOCK
PANEL TOTALS X GROUND BUS AUXILIARIES:
PHASE AMPS: 108 A 65 A 98 A
PHASE LOAD: 14.99 kVA 9.05 kVA 13.55 kVA
41 2.00 0.00 20 1 EX AUTO TRANSFER SWITCH 42
EX HVAC 2 50
2.00 0.00 20 1 EX REC: ADT 40
37 EX AC BLOWER CARP SHOP 1 20 0.00 3.63 38
35 EX REC: CARP SHOP E WALL 1 20 0.00 3.95
60 2 PANEL MF2A
33 EX LOAD 1 20 0.00 0.00 20 1 EX LTG: CARP SHOP CENTER 34
31 LTG: CORR/KIT/RR 1 20 4 0.27 0.00 30 1 EX LTG: CARP SHOP W 32
29 LTG: TRAINING/OFFICES 1 20 4 0.47 0.00 30 1 EX LTG: CARP SHOP E 30
27 EX LOAD 1 20 0.00 0.00 20 1 EX LTG: UPPER STORAGE 28
25 MECH: EF-1/EF-2 1 20 4 0.42 0.00 20 1 EX AC BLOWER STORAGE 26
23 REC: CORR/KIT/RR 1 20 4 0.90 0.36 4 20 1 REC: TELECOM 24
21 EX POWER VENT CARP 1 20 0.00 0.00 20 1 EX REC: GARAGE INNER WALL 22
19 0.83 2.80 20
FCU-2.1 2 15 2
0.83 2.80
2 35 2 MECH: HPU-2
15 0.43 2.80 16
MECH: FCU-1.1/1.2 2 15 2
0.43 2.80
2 35 2 MECH: HPU-1
11 EX OVERHEAD DOOR 1 20 0.00 0.75 4 20 1 SYS FURN: TRAINING 108 12
9 1.58 0.75 4 20 1 SYS FURN: TRAINING 108 10
MECH: ACCU-1/ACU-1 2 20 2
1.58 0.75 4 20 1 SYS FURN: TRAINING 108 8
5 0.00 1.50 4 20 1 SYS FURN: TRAINING 108 6
EX LOAD 2 40
0.00 1.50 2 20 1 SYS FURN: TRAINING 108 4
1 EX LOAD 1 20 0.00 1.50 2 20 1 SYS FURN: TRAINING 108 2
CKT LOAD DESCRIPTION P TA AUX/NOTE A B C AUX/NOTE TA P LOAD DESCRIPTION CKT
FED FROM:
MANUFACTURER: TYPE:
SERVICE TYPE: NORMAL MIN. RATING: 10K AIC RMS SYMMETRICAL AMPS LOCATION: ELECTRICAL ROOM 109
SERVICE: 240 VOLTS W/ CENTER TAP 120 VOLTS, 3 PHASE, ... ENCLOSURE: NEMA 1
MAIN TYPE: 200 A MCB SECTIONS: 1EX PANEL MF2
BUS AMPACITY: 225 A MOUNTING: SURFACE
MODIFICATIONS
6. PROVIDE LISTED HANDLE TIE FOR SYSTEMS FURNITURE CIRCUIT FEEDS TO COMPLY WITH ARTICLE
210.4 OF THE NATIONAL ELECTRICAL CODE FOR MULTIWIRE BRANCH CIRCUITS.
FEED THROUGH LUGS
DEMAND AMPS: ISOLATED GROUND BUS d SHUNT TRIP BREAKER
DEMAND LOAD: 200% NEUTRAL BUS & LUGS c GFEP BREAKER (30mA) g RED BREAKER LOCKOUT
CONNECTED LOAD: INTEGRAL SPD/TVSS b GFCI BREAKER (5mA) f HANDLE CLAMP
SERVICE ENTRANCE LABEL a AFCI BREAKER e HANDLE PADLOCK
PANEL…