Drawings_Electrical_Sheet_47_-_64.pdf

PDF 975 KB Posted

Attached to
MODERNIZE NATCHEZ MAINTENANCE FACILITY
Solicitation number
140P5226R0002
Issued by

About this file

This document is a comprehensive set of electrical construction drawings and specifications for the NPS - Natchez Maintenance Facility Renovation project, prepared by Henry Adams, LLC (Baltimore, MD) and Walker Architects (Gainesville, FL). The drawings establish detailed requirements for the complete renovation of electrical systems at the facility, including demolition of existing systems and installation of new power, lighting, security, and telecommunications infrastructure.

The scope of work encompasses removal of existing electrical panels (MF1, MF2, DP), a 125 KVA natural gas generator with automatic transfer switch, and associated air conditioning units, followed by installation of new panels, circuits, and equipment. New work includes a replacement 60-amp single-phase panel (MF2A), LED lighting systems with occupancy sensors and dimming controls, GFCI and weather-resistant receptacles, emergency exit signage, security systems with card readers and surveillance cameras, telecommunications infrastructure with CAT6A cabling and IT rack installation, and electrical connections for mechanical equipment including heat pump units (HPU-1, HPU-2), fan coil units (FCU-1.1, FCU-1.2, FCU-2.1), and various other HVAC and utility equipment. Disconnect switches are specified for all major equipment, with detailed schedules provided for panelboards MF1, MF2, MF2A, and associated disconnect switches (DS-ACCU-1, DS-HPU-1, DS-HPU-2). The drawings include standard NEC compliance requirements, coordination protocols with other trades, material specifications, mounting heights for all devices at 18" to 90" above finished floor, and detailed riser diagrams for telecommunications and security systems. All work must comply with local, state, and federal codes, with the facility remaining unoccupied during renovations and all demolition materials properly disposed of or salvaged as directed by the contracting officer.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P F

P F

NOTES: (APPLICABLE TO ELECTRICAL LEGEND ONLY)

1.

2.

3.

4.

THE MOUNTING HEIGHTS GIVEN ON THIS SHEET IN THE ELECTRICAL LEGEND ARE

GENERAL AND SHALL BE USED ONLY WHEN MOUNTING HEIGHTS CANNOT BE

ESTABLISHED BY REFERENCE TO DETAILS, ELEVATIONS, AND NOTES ON THE DRAWINGS.

ALL MOUNTING HEIGHTS, UNLESS OTHERWISE NOTED, SHALL BE MEASURED FROM THE

FINISHED FLOOR TO THE CENTERLINE OF THE OUTLET OR DEVICE.

HEIGHTS OF ALL ITEMS NOT COVERED BY THE ELECTRICAL LEGEND AND NOT SHOWN

ON THE DRAWINGS SHALL BE AS DIRECTED BY THE ARCHITECT OR ENGINEER.

WHERE PLACING ANY ITEM AT THE HEIGHTS LISTED OR NOTED WILL CAUSE

INTERFERENCE WITH THE WORK OF OTHER TRADES, OR IS NOT PHYSICALLY POSSIBLE

OR DESIRABLE FOR ONE REASON OR ANOTHER, THE ITEM SHALL BE INSTALLED AT A

LOCATION APPROVED BY THE ARCHITECT OR ENGINEER.

ELECTRICAL LEGEND

DESCRIPTION

MOUNTING

HEIGHT

SYMBOL DESCRIPTION

MOUNTING

HEIGHT

SYMBOL

ELECTRICAL LEGEND (CONTINUED)

ILLUMINATED EXIT SIGN, SINGLE FACE - ARROW INDICATES DIRECTIONAL

CHEVRON - CEILING/WALL MOUNTED

- - / 90"

ILLUMINATED EXIT SIGN, DOUBLE FACE - CEILING/WALL MOUNTED - - / 90"

$ SINGLE POLE TOGGLE SWITCH 46"

3 THREE-WAY TOGGLE SWITCH 46"

OS OCCUPANCY SENSOR SWITCH 46"

LV1

LIGHTING CONTROL SYSTEM - LOW VOLTAGE SWITCH FOR ONE ZONE,

ON/OFF CONTROL.

46"

LV1D

LIGHTING CONTROL SYSTEM - LOW VOLTAGE SWITCH FOR ONE ZONE,

ON/OFF AND UP/DOWN DIMMING.

46"

LV2D

LIGHTING CONTROL SYSTEM - LOW VOLTAGE SWITCH FOR TWO ZONES,

ON/OFF AND UP/DOWN DIMMING.

46"

OSD OCCUPANCY SENSOR SWITCH WITH 0-10V DIMMING 46"

(SIMPLEX)

(DUPLEX)

(QUAD)

RECEPTACLE - NEMA CONFIGURATION 5-20R (SHADING INDICATES

CONNECTED TO EMERGENCY/STANDBY POWER CIRCUIT)

SUBSCRIPTS:

GFI: WITH 5mA GROUND FAULT INTERRUPTER

TR: TAMPER-RESISTANT

WP: WEATHER-RESISTANT RECEPTACLE WITH WEATHERPROOF

WHILE-IN-USE COVER

18"

JUNCTION BOX (CEILING AND WALL MOUNTED)

- - / AS

NOTED

MS

EMERGENCY LUMINAIRE, BATTERY POWERED - - / 90"

LIGHTING CONTROL SYSTEM - RELAY PACK WITH POWER SUPPLY - -RPP

LIGHTING CONTROL SYSTEM - RELAY PACK WITH POWER SUPPLY FOR

DIMMING 0-10V LOADS

- -RPD

FRACTIONAL HORSEPOWER MANUAL MOTOR SWITCH 46"

MOTOR - -

COMBINATION MAGNETIC MOTOR STARTER AND SAFETY SWITCH 60" TO TOP

SAFETY SWITCH 60" TO TOP

ENCLOSED CIRCUIT BREAKER 60" TO TOP

SURGE PROTECTIVE DEVICE SEE DETAILSPD

PANELBOARD 78" TO TOP

DATA OUTLET, WALL MOUNTED 18"

DATA OUTLET, FLOOR MOUNTED (P = PEDESTAL, F = FLUSH) - -

COMBINATION TELEPHONE/DATA OUTLET, WALL MOUNTED 18"

COMBINATION TELEPHONE/DATA OUTLET, FLOOR MOUNTED

(P = PEDESTAL, F = FLUSH)

TELEPHONE TERMINAL BACKBOARD - -

GROUNDING SYSTEM - GROUND CONNECTION - -

MOLDED CASE CIRCUIT BREAKER (600V AND BELOW) - -

FIXED CURRENT TRANSFORMER WITH TURN RATIO - -

CURRENT LIMITING FUSE (600V AND BELOW) - -

DISCONNECT SWITCH (600V AND BELOW) - -

KILOWATT METER (KWH = KILOWATT HOURS) - -KW

TRANSFORMER - -

GROUNDING SYSTEM WYE GROUNDED NEUTRAL WINDING - -

DELTA WINDING - -

OCCUPANCY SENSOR (CEILING AND WALL MOUNTED)

SUBSCRIPTS:

DT: DUAL TECHNOLOGY (DEFAULT IF NO SUBSCRIPT INDICATED)

U: ULTRASONIC

P: PASSIVE INFRARED

- - / 92"

LUMINAIRE - -

CR SECURITY SYSTEM - CARD READER 46"

SECURITY SYSTEM - KEY PAD 46"KP

SECURITY SYSTEM PANEL 78" TO TOPSEC

AS NOTED

SECURITY SYSTEM - SURVEILLANCE CAMERA (CEILING/WALL MOUNT)

SUBSCRIPTS:

F: FIXED (DEFAULT IF NO SUBSCRIPT INDICATED)

PTZ: PAN - TILT - ZOOMD: DOME

D: DOME

HARDWIRED POWER CONNECTION TO SYSTEMS FURNITURE 6"

HARDWIRED COMMUNICATIONS CONNECTION TO SYSTEMS FURNITUREJ

C

6"

J P

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:2

A

M

JLW

JLW

03/14/2024

E0.1JST

ELECTRICAL COVER SHEET

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

A AMPERE

ACCU AIR COOLED CONDENSING

UNIT

ACU AIR CONDITIONING UNIT

ADA AMERICANS WITH

DISIBILITIES ACT

AF AMPERE FRAME, AMPERE

FUSE

AFCI ARC FAULT CIRCUIT

INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING

CAPACITY

AL ALUMINUM

ANSI AMERICAN NATIONAL

STANDARDS INSTITUTE

ASYM ASYMMETRICAL

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER

SWITCH

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

BOD BASIS OF DESIGN

C CONDUIT

CB CIRCUIT BREAKER

CCT CORRELATED COLOR

TEMPERATURE

CH CHILLER

CKT CIRCUIT

CMS COMBINATION MOTOR

STARTER

COMM COMMUNICATION

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CU COPPER

CX CONNECT TO EXISTING

DS DISCONNECT SWITCH

DWC DRINKING WATER COOLER

DWG DRAWING

E EMERGENCY

EBU EMERGENCY BATTERY UNIT

ECB ENCLOSED CIRCUIT

BREAKER

EF EXHAUST FAN

EMT ELECTRICAL METALLIC

TUBING

ENCL ENCLOSURE

ENT ELECTRICAL NONMETALLIC

TUBING

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EWH ELECTRIC WATER HEATER

EX EXISTING

F FUSED, FUSIBLE,

FAHRENHEIT

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR

PANEL

FACP FIRE ALARM CONTROL

PANEL

FCU FAN COIL UNIT

FDR FEEDER

FLA FULL LOAD AMPERAGE

FMC FLEXIBLE METAL CONDUIT

FSS FUSED SAFETY SWITCH

FT FEET

G GROUND

GB GROUND BAR

GEC GROUNDING ELECTRODE

CONDUCTOR

ELECTRICAL ABBREVIATIONS

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GFI GROUND FAULT

INTERRUPTER

GND GROUND

GRC GALVANIZED RIGID STEEL

GW GROUND WIRE

HD HEAVY DUTY

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HPU HEAT PUMP UNIT

HVAC HEATING VENTILATING AIR

CONDITIONING

HZ HERTZ

IBC INTERNATIONAL BUILDING

CODE

ICCB INSULATED CASE CIRCUIT

BREAKER

IEBC INTERNATIONAL EXISTING

BUILDING CODE

IECC INTERNATIONAL ENERGY

CONSERVATION CODE

IEEE INSTITUTE OF ELECTRICAL

AND ELECTRONICS

ENGINEERS

IMC INTERMEDIATE METALLIC

CONDUIT

IN INCH

JB JUNCTION BOX

K ONE THOUSAND, KELVIN

KAIC THOUSAND AMPERE

INTERRUPTING CAPACITY

KCMIL THOUSAND CIRCULAR MILS

KV KILOVOLTS

KVA KILOVOLT-AMPERES

KW KILOWATTS

LC LOAD CENTER

LED LIGHT EMITTING DIODE

LF LINEAR FEET

LFMC LIQUID TIGHT FLEXIBLE

METALLIC CONDUIT

LFNC LIQUID TIGHT FLEXIBLE

NON-METALLIC CONDUIT

LRA LOCKED ROTOR AMPS

LS LIMIT SWITCH, LONG

TIME-SHORT TIME

LTG LIGHTING

LTS LIGHTS

LV LOW VOLTAGE

MAX MAXIMUM

MC METAL CLAD, METER

CENTER

MCA MINIMUM CIRCUIT

AMPACITY

MCB MAIN CIRCUIT BREAKER

MCCB MOLDED CASE CIRCUIT

BREAKER

MDP MAIN DISTRIBUTION PANEL

MGB MAIN GROUND BAR

MIN MINIMUM

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOCP MAXIMUM OVERCURRENT

PROTECTION

MTD MOUNTED

N NEUTRAL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NF NON-FUSED

NFPA NATIONAL FIRE

PROTECTION ASSOCIATION

NFSS NON-FUSED SAFETY

SWITCH

NIC NOT IN CONTRACT

NM NON-METALLIC

NO NORMALLY OPEN

NTS NOT TO SCALE

OCP OVERCURRENT PROTECTION

OH OVERHEAD

OHE OVERHEAD ELECTRIC

P POLE(1P, 2P, 3P)

PF POWER FACTOR

PH PHASE

PIR PASSIVE INFRARED

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

QTY QUANTITY

R RACEWAY

REC RECEPTACLE

RGS RIGID GALVANIZED STEEL

RLA RATED LOAD AMPERES

RM ROOM

RMS ROOT MEAN SQUARE

RNC RIGID NONMETALLIC

CONDUIT

RX REMOVE EXISTING

SE SERVICE ENTRANCE

SF SQUARE FEET

SN SOLID NEUTRAL

SPD SURGE PROTECTION

DEVICE

SS SAFETY SWITCH

ST SINGLE-THROW

SW SWITCH

SYM SYMMETRICAL

T TRANSFORMER

TA TRIP AMPERES

TECH TECHNOLOGY

TGB TELECOMMUNICATIONS

GROUND BAR

TTB TELEPHONE TERMINAL

BOARD

TV TELEVISION

TYP TYPICAL

UG UNDERGROUND

UGE UNDERGROUND ELECTRIC

UH UNIT HEATER

UL UNDERWRITERS

LABORATORY

UON UNLESS OTHERWISE NOTED

UTP UNSHIELDED TWISTED PAIR

V VOLTS

VA VOLT-AMPERES

VSD VARIABLE SPEED DRIVE

W WIRE, WATTS

W/ WITH

WP WEATHERPROOF

WR WEATHER RESISTANT

XFMR TRANSFORMER

Y WYE

323963

DEVICE TYPE

5 INDICATES PANELBOARD CIRCUIT DESIGNATION

LIGHTING

REFERENCE

ELECTRICAL CONVENTIONS

A

1b

CIRCUIT NUMBER

CONTROL POINT DESIGNATION (IF MORE THAN ONE)

LUMINAIRE TYPE - SEE LUMINAIRE SCHEDULE

LUMINAIRE WITH INTEGRAL BATTERY BACKUP

A

NUMBER OF CONTROL POINTS

TYPE OF CONTROL

CONTROL ZONE REFERENCE

2$ ab

DRAWING NUMBER WHERE DETAIL IS LOCATED

NUMBER DENOTES SECTION IDENTIFICATION

SECTION DESIGNATION

E-1

E-1 DRAWING NUMBER WHERE DETAIL IS LOCATED

DETAIL DESIGNATION

NUMBER DENOTES DETAIL IDENTIFICATION

SPECIAL NOTE (APPLIES WHERE INDICATED

ON THE DRAWING)

WIRING

1,3,5(LP-1)

BRANCH CIRCUIT HOMERUN TO PANEL

"LP-1", CIRCUITS #1,3,5

NUMBER OF CIRCUITS INDICATED BY

QUANTITY OF ARROW HEADS.

CONCEALED CONDUIT IN CEILING OR WALLS

CONDUIT IN OR UNDER FLOOR

EXPOSED CONDUIT

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT, CAPPED

GENERAL NOTE: WHERE WIRE SIZE IS INDICATED AT THE

HOMERUN OR ON THE SCHEDULE TO BE LARGER THAN

THE SPECIFIED MINIMUM PROVIDE THE INDICATED WIRE SIZE

THROUGHOUT THE ENTIRE BRANCH CIRCUIT.

DEVICE TYPE

CANDELA RATING15cd

MOUNTING HEIGHTS

PRESENTATION

FIRE ALARM

DEVICE TYPE

+ INDICATES DEVICE TO BE MOUNTED

8" ABOVE COUNTERTOP BACKSPLASH

24"

DEVICE TYPE

INDICATES DEVICE MOUNTING HEIGHT ABOVE FINISHED FLOOR

OR ABOVE FINISHED GRADE (AS APPROPRIATE)

ELECTRICAL EQUIPMENT DESIGNATED BY SOLID HEAVY

LINEWEIGHT INDICATES NEW WORK TO BE PROVIDED.

ELECTRICAL EQUIPMENT DESIGNATED BY SOLID LIGHT

LINEWEIGHT INDICATES EXISTING EQUIPMENT TO REMAIN,

UNLESS OTHERWISE INDICATED.

ELECTRICAL EQUIPMENT DESIGNATED BY DASHED HEAVY

LINEWEIGHT REPRESENTS EXISTING EQUIPMENT TO BE

REMOVED AND DISPOSED, UNLESS INDICATED TO BE

REMOUNTED, RELOCATED, OR TURNED OVER TO OWNER.

STEM INDICATES WALL MOUNTED

LUMINAIRE, MOUNTING HEIGHT

AS NOTED

1. PROVIDE LABOR, MATERIALS, TOOLS, EQUIPMENT, COORDINATION, DELEGATED DESIGN AND INCIDENTALS NECESSARY TO PROVIDE A COMPLETE AND OPERABLE SYSTEM.

2. PERFORM WORK AS REQUIRED BY APPLICABLE CODES, REGULATIONS AND LAWS OF LOCAL, STATE AND FEDERAL GOVERNMENTS AND OTHER AUTHORITIES WITH

LAWFUL JURISDICTION.

3. MATERIAL AND EQUIPMENT SHALL BE LISTED AND LABELED BY NATIONALLY RECOGNIZED TESTING LABORATORIES FOR INTENDED SERVICE.

4. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS AND LICENSES, PAY FEES AND BACK CHARGES, AND OBTAIN NECESSARY APPROVALS FROM AUTHORITIES THAT HAVE

JURISDICTION.

5. MAINTAIN RECORD DRAWINGS ON SITE. RECORD SET SHALL BE COMPLETE, CURRENT, AND AVAILABLE UPON REQUEST.

6. SUBMIT FOR APPROVAL, SHOP DRAWINGS FOR EQUIPMENT AND MATERIALS USED ON PROJECT. OBTAIN APPROVAL BY CONTRACTING OFFICER PRIOR TO PURCHASE OF

EQUIPMENT AND MATERIALS.

7. REPAIR OR REPLACE DAMAGE TO FACILITIES AND EQUIPMENT AT NO ADDITIONAL EXPENSE TO GOVERNMENT.

8. PATCH AND REPAIR DISTURBED AREAS TO MATCH ADJACENT SURFACES AND FINISHES.

9. PROVIDE TEMPORARY POWER AND LIGHTING FOR OTHER TRADES AS REQUIRED TO COMPLETE PROJECT IN ACCORDANCE WITH APPLICABLE CODES AND STANDARDS.

10.

11. LOCATIONS SHOWN ON PLANS ARE APPROXIMATE AND REQUIRE COORDINATION WITH OTHER TRADES. ROUTING OF CONDUIT IS DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW REQUIRED OFFSETS AND DETAILS. OBTAIN DRAWINGS AND SPECIFICATIONS FROM OTHER TRADES AND COORDINATE WITH OTHER TRADES.

12. COORDINATE ELECTRICAL INSTALLATION WITH FIELD CONDITIONS. LOCATIONS SHOWN ARE DIAGRAMMATIC AND MAY REQUIRE ADJUSTMENT IN FIELD.

13. COORDINATE LOCATIONS OF ELECTRICAL DEVICES WITH ARCHITECTURAL ELEVATIONS PRIOR TO INSTALLATION.

14. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF MECHANICAL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS.

15. PERMANENTLY LABEL NEW ELECTRICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO, DEVICE DESIGNATION AND SUPPLY CIRCUIT DESIGNATION.

16. CORE DRILL CONCRETE WALLS AND FLOORS TO PROVIDE OPENINGS FOR CONDUIT INSTALLATION. PRIOR TO CORE DRILLING, LOCATE REINFORCING BARS IN EXISTING WALLS AND FLOORS USING A NON-DESTRUCTIVE METHOD. COORDINATE AND OBTAIN FINAL APPROVAL OF CORE DRILL LOCATIONS FROM CONTRACTING OFFICER. DO NOT CUT THROUGH EXISTING REINFORCING BARS WITHOUT APPROVAL OF CONTRACTING OFFICER. MAXIMUM CORE DRILL SIZE SHALL BE 5-INCH DIAMETER. SPACE CORE DRILL LOCATIONS A MINIMUM OF 6 INCHES FROM EACH OTHER, MEASURED FROM CORE DRILL OPENINGS. PROPERLY SEAL OPENINGS ACCORDING TO LOCATION AND APPLICATION.

17. PROVIDE EACH CIRCUIT WITH A DEDICATED NEUTRAL UNLESS NOTED OTHERWISE.

18. CONDUIT HOMERUNS SHOWN ON DRAWINGS WITH MORE THAN 3 CURRENT CARRYING CONDUCTORS ARE SHOWN DIAGRAMMATICALLY. DO NOT INSTALL MORE THAN 3 CURRENT CARRYING CONDUCTORS IN A SINGLE RACEWAY UNLESS INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE.

19. PROVIDE FIRESTOPPING FOR ELECTRICAL PENETRATIONS IN FIRE RATED ASSEMBLIES.

20. INSTALL ELECTRICAL WORK IN A NEAT AND WORKMANLIKE MANNER, RECTILINEAR TO BUILDING STRUCTURE. INSTALL RACEWAYS TIGHT TO STRUCTURAL CEILING AND AS HIGH AS POSSIBLE WITHIN CEILING SPACES TO MAINTAIN MAXIMUM AMOUNT OF CLEAR SPACE BELOW RACEWAY.

21. INSTALL RACEWAYS CONCEALED IN BUILDING FINISHES FOR ALL EXTERIOR MOUNTED DEVICES. DO NOT ROUTE EXPOSED ON BUILDING EXTERIOR.

22. INSTALL RACEWAYS CONCEALED IN WALLS, UNDER FLOORS, ABOVE CEILINGS, ETC., EXCEPT AS FOLLOWS:

-WHERE SUSPENDED CEILINGS ARE NOT PROVIDED

-IN VERTICAL SHAFTS, ELECTRICAL CLOSETS, ETC., MECHANICAL AND ELECTRICAL EQUIPMENT SPACES WHERE CONCEALMENT IS NOT PRACTICAL.

-AT SURFACE-MOUNT PANELBOARDS IN OTHERWISE FINISHED SPACES LIMITED TO VERTICAL RUNS ABOVE AND BELOW PANEL

-WHERE REQUIRED FOR EQUIPMENT CONNECTIONS

-WHERE SPECIFICALLY INDICATED ON DRAWINGS

23.

24.

OWNER-FURNISHED EQUIPMENT: VERIFY AND COORDINATE ELECTRICAL ROUGH-IN REQUIREMENTS FOR OWNER-FURNISHED EQUIPMENT WITH CONTRACTING OFFICER PRIOR TO PULLING CONDUCTORS AND MAKING FINAL CONNECTIONS. LACK OF COORDINATION SHALL NOT JUSTIFY CHANGE ORDERS.

WHERE SUBMITTED EQUIPMENT REQUIRES REVISION TO OVERCURRENT PROTECTION, CONDUIT, AND WIRING, COORDINATE AND MAKE CHANGE TO PROVIDE A COMPLETE

INSTALLATION IN ACCORDANCE WITH APPLICABLE CODES.

DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS. PROVIDE COMPONENTS INDICATED ON RISER DIAGRAMS WHETHER OR NOT INDICATED

ON PLANS, AND VICE VERSA.

2.

3.

PRIOR TO DEMOLITION, FIELD VERIFY CONDUITS, CONDUCTORS, AND CABLES THAT PASS THROUGH AND SERVE AREAS OUTSIDE THE SCOPE OF WORK. MAINTAIN CONTINUITY OF SYSTEMS. PROTECT OR RELOCATE SYSTEMS TO PREVENT DAMAGE. RESTORE SYSTEMS TO NORMAL OPERATION. COORDINATE SYSTEM OUTAGES WITH CONTRACTING

OFFICER.

IDENTIFY NONFUNCTIONING EQUIPMENT AND DEVICES TO REMAIN AFTER DEMOLITION. NOTIFY CONTRACTING OFFICER IN WRITING PRIOR TO DEMOLITION. UPON COMPLETION

OF WORK, ENSURE THAT EXISTING EQUIPMENT AND DEVICES OPERATE PROPERLY.

4.

5.

6.

7.

13.

10.

9.

THE FACILITY WILL NOT REMAIN OCCUPIED DURING RENOVATIONS.

AFTER DEMOLITION VERIFY AND SUPPORT REMAINING CABLES, WIRES, AND CONDUIT IN ACCORDANCE WITH THE APPLICABLE VERSION OF THE NEC. DISCONNECT, MAKE

SAFE AND REMOVE ABANDONED AND TEMPORARY WIRE WITHIN SPACE.

WHERE CIRCUITS ARE REMOVED BACK TO PANELS, ASSOCIATED BREAKERS WILL BE UTILIZED FOR NEW CIRCUITING.

1.

EXISTING CONDITIONS REFLECT GENERAL OBSERVATIONS AND ARE NOT INTENDED TO INDICATE DETAILS OR DIMENSIONS. NO ATTEMPT HAS BEEN MADE TO SHOW ALL ELECTRICAL EQUIPMENT. VERIFY EXISTING CONDITIONS PRIOR TO PERFORMING WORK. NOTIFY CONTRACTING OFFICER IN WRITING IF CONDITIONS ARE DISCOVERED THAT

PREVENT EXECUTION OF WORK.

PROTECT REMAINING ELECTRICAL SYSTEMS AND COMPONENTS FROM DAMAGE. REMOVE PROTECTIVE MATERIALS UPON COMPLETION OF WORK.

8. DISPOSE OF LIGHTING BALLASTS AND CAPACITORS CONTAINING PCB'S, AS DEFINED BY THE ENVIRONMENTAL PROTECTION AGENCY (EPA), IN ACCORDANCE WITH

APPLICABLE LOCAL, STATE, FEDERAL AND EPA REGULATIONS.

PROVIDE CONTRACTING OFFICER WITH INVENTORY OF MAJOR ELECTRICAL ITEMS TO BE REMOVED. CONTRACTING OFFICER WILL SELECT ITEMS TO BE SALVAGED. TURN SALVAGED ITEMS OVER TO GOVERNMENT. ITEMS REJECTED BY THE CONTRACTING OFFICER SHALL BECOME THE PROPERTY OF THE CONTRACTOR. REMOVE DEMOLISHED

ITEMS FROM SITE.

12.

11. PROVIDE BLANK COVER PLATES FOR DEVICES REMOVED WHEN A REPLACEMENT DEVICE IS NOT INDICATED.

MAINTAIN CONTINUITY OF CIRCUITS AND FEEDERS REMAINING AFTER DEMOLITION IN PANELS INDICATED TO BE DEMOLISHED OR REPLACED. EXTEND EXISTING CIRCUITS AND FEEDERS REMAINING AFTER DEMOLITION TO NEW PANELS. CIRCUIT BREAKER, CONDUIT, AND WIRE SHALL MATCH EXISTING TYPES AND SIZES.

IN AREAS NOTED TO REMOVE ELECTRICAL WORK, REMOVE CONDUITS AND ASSOCIATED SUPPORTS BACK TO POINT OF CONCEALMENT AND REMOVE WIRING BACK TO

REMAINING ACTIVE DEVICES OR SOURCE.

REPAIR DISTURBED AREAS TO MATCH EXISTING CONDITIONS.

GENERAL ELECTRICAL NOTES

GENERAL ELECTRICAL DEMOLITION/RENOVATION NOTES

25. PROVIDE NECESSARY SUPPORTING STRUT CHANNEL AND ALL MISCELLANEOUS HARDWARE FOR MOUNTING ELECTRICAL EQUIPMENT. MAINTAIN NEC WORKING CLEARANCES.

COORDINATE EXACT LOCATION IN FIELD. DO NOT MOUNT ON EQUIPMENT ACCESS PANELS OR IN EQUIPMENT MANUFACTURER'S RECOMMENDED MAINTENANCE CLEARANCES.

(APPLICABLE TO ALL ELECTRICAL DRAWINGS)

(APPLICABLE TO ALL ELECTRICAL DRAWINGS)

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:2

A

M

JLW

JLW

03/14/2024

E0.2JST

ELECTRICAL NOTES

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

EX PANEL MF1

EX PANEL MF2

GFIGFI

WPWP

RX

ACCU

EX

ACCU

RX

ACCU

aa bb cc

++ GFIGFI

EX PANEL DP

EX ATS

RX ACU

RX ACU

RX PANEL MF2A

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

ED1.1JST

FIRST FLOOR - ELECTRICAL

DEMOLITION

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

DRAWING NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY DASHED

HEAVY LINEWEIGHT ( ) INDICATES EXISTING WORK TO BE

REMOVED. ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT

( ) INDICATES EXISTING ITEMS TO REMAIN.

1.

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING

CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING

DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT

INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT

DIRECTION BEFORE PROCEEDING WITH THE WORK.

2.

ETR GENERATOR.

REMOVE AND SALVAGE EXISTING RACK, EQUIPMENT, AND UPS FOR

REINSTALLATION UNDER NEW WORK.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

SCALE AED1.1

1 FIRST FLOOR - ELECTRICAL DEMOLITION

SCALE OF FEET

4 0 4 8

SCALE A

3 EXISTING TELECOM SERVICE ENTRANCE EQUIPMENT AND

PUNCHDOWN BLOCKS.

a a a a a aa aa aa a bb b b b c c c c cccc

EX AHU

RX AHU

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

ED1.2JST

MEZZANINE - ELECTRICAL

DEMOLITION

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

DRAWING NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY DASHED

HEAVY LINEWEIGHT ( ) INDICATES EXISTING WORK TO BE

REMOVED. ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT

( ) INDICATES EXISTING ITEMS TO REMAIN.

1.

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING

CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING

DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT

INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT

DIRECTION BEFORE PROCEEDING WITH THE WORK.

2.

RX LIGHTING CONTACTOR FOR TRAINING ROOM.

ETR LIGHTING CONTACTOR FOR CARPENTRY SHOP.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

SCALE AED1.2

1 MEZZANINE - ELECTRICAL DEMOLITION

SCALE OF FEET

4 0 4 8

SCALE A

J

J J

J

J J

EX PANEL MF1

EX PANEL MF2

PANEL MF2A

GFIGFI

WPWP

EX

ACCU

EX ATS

EX PANEL DP

ELECTRICAL ROOM

KITCHEN

CORRIDOR

C01

WASHER

UNISEX TOILET

LOCKERS

OFFICE

TRAINING ROOM

OFFICE

HOOD-1

EF-1 EF-2

HPU-1 HPU-2

DS-HPU-1 DS-HPU-2

GFIGFI

GFIGFI

GFIGFIGFIGFI

PANTRY

GFIGFI++

GFIGFI GFIGFI

GFIGFI

GFIGFI

52"52" 52"52"

C

C

C

P

P

P

ACCU-1

2,4,6(MF2)2,4,6(MF2)

2,4,6

8,10,12(MF2)8,10,12(MF2)

18,20(MF2)18,20(MF2)

14,16(MF2)14,16(MF2)

ACU-1

DS-ACCU-1

7,9(MF2)7,9(MF2)

252525(MF2)25(MF2)

4(MF2A)4(MF2A)

24(MF2)24(MF2)

1(MF2A)1(MF2A)

3(MF2A)3(MF2A)

7(MF2A)7(MF2A)

5(MF2A)5(MF2A)

2(MF2A)2(MF2A)

23(MF2)23(MF2)

6(MF2A)6(MF2A)

8(MF2A)8(MF2A)

1111 1111

9(MF2A)9(MF2A)

11(MF2A)11(MF2A)

17(MF2A)17(MF2A)

13,15(MF2A)13,15(MF2A)

TMGB

WOOD SHOP

9TELECOM

TR01

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E1.1JST

FIRST FLOOR - POWER NEW

WORK

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

SCALE AE1.1

1 FIRST FLOOR - POWER - NEW WORK

DRAWING NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID

HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.

ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )

INDICATES EXISTING ITEMS TO REMAIN.

1.

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING

CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING

DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT

INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT

DIRECTION BEFORE PROCEEDING WITH THE WORK.

2.

ETR GENERATOR.

FOR RANGE GAS SHUT OFF ASSEMBLY BOX. LOCATE WITHIN LOWER

CABINETRY.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

SCALE OF FEET

4 0 4 8

SCALE A

3 FOR WASHER. MOUNT TO SUIT EQUIPMENT.

4 FOR DISHWASHER. MOUNT TO SUIT EQUIPMENT.

5 FOR REFRIGERATOR. MOUNT TO SUIT EQUIPMENT. PROVIDE 1P-20A

GFI CIRCUIT BREAKER.

6 LOCATION OF SYSTEM FURNITURE DATA CONNECTION. PROVIDE 2"

CONDUIT WITH PULL STRING TO TELECOM RACK.

7 FOR STACKED DRYER. MOUNT TO SUIT EQUIPMENT. PROVIDE NEMA

14-30R RECEPTACLE. PROVIDE 4-WIERE (2PH, N, G) CIRCUIT

WIRING.

8 FOR COPIER.

9 LOCATION OF EXISTING TELECOMMUNICATIONS RACK.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

EX AHU

DWH-1

FCU-1.2

FCU-1.1

FCU-2.1

GFIGFI

GFIGFI

GFIGFI

13,15(MF2)13,15(MF2)

13,15(MF2)13,15(MF2)

17,19(MF2)17,19(MF2)

12(MF2A)12(MF2A)

10(MF2A)10(MF2A)

PUMP-1

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E1.2JST

MEZZANINE - POWER NEW WORK

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

DRAWING NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID

HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.

ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )

INDICATES EXISTING ITEMS TO REMAIN.

1.

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING

CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING

DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT

INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT

DIRECTION BEFORE PROCEEDING WITH THE WORK.

2.

TEXT.

TEXT.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

SCALE AE1.2

1 MEZZANINE - POWER - NEW WORK

SCALE OF FEET

4 0 4 8

SCALE A

bb aa

ELECTRICAL ROOM

KITCHEN

TELECOM

TR01

CORRIDOR

C01

WASHER

UNISEX TOILET

LOCKERS

OFFICE

OFFICE

TRAINING ROOM

B1B1

B1B1

D1D1 D1D1

D1D1

D2D2

D3D3

D3D3

D3D3 D3D3

D3D3

B1B1 B1B1

B1B1 B1B1

B1B1 B1B1

B1B1 B2B2

B2B2 B2B2

B2B2

B1B1B1B1

LV1DLV1D

LV1DLV1D

LV1DLV1D

OS2OS2

OS2OS2

LV2d,eLV2d,e

LV1dLV1d

LV1DcLV1Dc

LV1DcLV1Dc

31d31d 31d31d

31d31d

31d31d 31d31d

B1B1

OSOS

OSOS

B1B1

OSOS

E1E1

E1E1

E1E1

E1E1

D1D1 D1D1 D1D1 ee ee ee

29c29c

29c29c

29c29c

29c29c

29c29c

29c29c

29c29c

29c29c 29c29c

29c29c

29c29c

29c29c

29c29c

AA AA AA

AAAAAA

AA

AA

AA AA

AA

AAAA

W1W1

29292929

29292929

29292929

2929 2929

3131 3131

PANTRY

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E2.1JLW

FIRST FLOOR - LIGHTING NEW

WORK

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

DRAWING NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID

HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.

ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )

INDICATES EXISTING ITEMS TO REMAIN.

1.

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING

CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING

DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT

INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT

DIRECTION BEFORE PROCEEDING WITH THE WORK.

2.

TEXT.

TEXT.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

SCALE AE2.1

1 FIRST FLOOR - LIGHTING - NEW WORK

SCALE OF FEET

4 0 4 8

SCALE A

AA

AA

AA

AA

AA

AA

AA

AA AA

AA

AA

AA

AA

bb bb bb bb bb aaaa aa aa aaaaaa aa aaaa aa aa

29c29c

29c29c

29c29c

29c29c

29c29c

29c29c

29c29c

29c29c 29c29c

29c29c

29c29c

29c29c

29c29c

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E2.2JLW

MEZZANINE - LIGHTING NEW

WORK

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

DRAWING NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID

HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.

ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )

INDICATES EXISTING ITEMS TO REMAIN.

1.

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING

CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING

DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT

INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT

DIRECTION BEFORE PROCEEDING WITH THE WORK.

2.

TEXT.

TEXT.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

SCALE AE2.2

1 MEZZANINE - LIGHTING - NEW WORK

SCALE OF FEET

4 0 4 8

SCALE A

ELECTRICAL ROOM

KITCHEN

TELECOM

TR01

CORRIDOR

C01

WASHER

UNISEX TOILET

LOCKERS

OFFICE

OFFICE

TRAINING ROOM

PANTRY

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E3.1JST

FIRST FLOOR - SECURITY NEW

WORK

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

DRAWING NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID

HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.

ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )

INDICATES EXISTING ITEMS TO REMAIN.

1.

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING

CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING

DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT

INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT

DIRECTION BEFORE PROCEEDING WITH THE WORK.

2.

TEXT.

TEXT.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

SCALE OF FEET

4 0 4 8

SCALE A

SCALE AE3.1

1 FIRST FLOOR - SECURITY - NEW WORK

MECHANICAL MEZZANINE

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E3.2JST

MEZZANINE - SECURITY NEW

WORK

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

DRAWING NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID

HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.

ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )

INDICATES EXISTING ITEMS TO REMAIN.

1.

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING

CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING

DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT

INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT

DIRECTION BEFORE PROCEEDING WITH THE WORK.

2.

TEXT.

TEXT.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

SCALE OF FEET

4 0 4 8

SCALE A

SCALE AE3.2

1 MEZZANINE - SECURITY - NEW WORK

POWER TYPE

PANEL #XX

P O

W E

R T

Y P

E

P A

N E

L

X X

ALTERNATE

LOCATION

P O

W E

R T

Y P

E

P A

N E

L

X X

ALTERNATE

LOCATION

POWER TYPE

PANEL #XX

P O

W E

R T

Y P

E

P A

N E

L

X X

PROVIDE 0.59" WIDE POLYESTER ADHESIVE TAPE LABELS, 1.77" LONG

WITH BLACK 1/8" HIGH TIMES NEW ROMAN TEXT. REPLACE POWER

TYPE WITH PANEL SOURCE, EXAMPLE: "NORMAL POWER", "PANEL"

WITH THE PANEL NAME, AND "XX" WITH THE CIRCUIT NUMBER OR

NUMBERS SEPARATED BY COMMAS. DO NOT COVER SCREWS.

2-1/2"

5"

SELF-ADHESIVE

ENGRAVED

PLASTIC LABEL

EQUIPMENT

DESIGNATION

FED FROM ####

###V, 3PH, #W ELECTRICAL

CHARACTERISTICS

POWER SOURCE; PANEL NAME

AND CIRCUIT #

GENERAL NOTES:

A. ALL NEW SAFETY SWITCHES, STARTERS, ENCLOSED CIRCUIT BREAKERS, AND

VARIABLE SPEED MOTOR CONTROLLERS SHALL BE PROVIDED WITH LABELS.

B. CENTER ALL TEXT HORIZONTALLY.

C. MODIFY TEXT AS REQUIRED.

D. EQUIPMENT CONNECTED TO NORMAL POWER SYSTEMS SHALL HAVE BLACK

LETTERS ON WHITE BACKGROUND.

E. EQUIPMENT CONNECTED TO EMERGENCY POWER SYSTEMS SHALL HAVE WHITE

LETTERS ON RED BACKGROUND.

2-1/2"

MIN 5"

FED FROM ####

###Y/###V, 3PH, #W

PANEL ####

SYSTEM TYPE

PANEL DESIGNATION

SELF-ADHESIVE ENGRAVED

PLASTIC LABEL

ELECTRICAL CHARACTERISTICS

PANEL LABEL PER THIS DETAIL

"NORMAL POWER" OR

"EMERGENCY POWER"

POWER SOURCE; PANEL NAME AND

CIRCUIT # OR TRANSFORMER NAME IF

FED FROM TRANSFORMER

GENERAL NOTES:

A. ALL NEW PANELBOARDS SHALL BE PROVIDED

WITH LABELS.

B. CENTER ALL TEXT HORIZONTALLY.

C. MODIFY TEXT AS REQUIRED.

D. PANELBOARDS CONNECTED TO NORMAL

POWER SYSTEMS SHALL HAVE BLACK

LETTERS ON WHITE BACKGROUND.

NEUTRAL

GROUND

PHASE PHASE PHASE

A B C

CIRCUIT A

L1 N1 G1

CIRCUIT B

L2 N2 G1

CIRCUIT C

L3 N3 G1

SYSTEM GROUND-G1-BARE

NEUTRAL-N2-WHITE/RED

NEUTRAL-N1-WHITE

HOT-L3-BLUE

HOT-L2-RED

HOT-L1-BLACK

THREE PHASE 240/120V CIRCUIT PANEL

RECPTACLE CONNECTIONS (LOAD)

NEUTRAL-N3-WHITE/BLUE

3'-6"

MAGNETIC

SWITCH

FLOOR

CEILING

SECURITY SYSTEM EQUIPMENT WILL BE PURCHASED AND

INSTALLED BY OWNER/OPERATOR.

CONTRACTOR SHALL PROVIDE EMPTY CONDUIT SYSTEM.

SINGLE GANG JUNCTION

BOX FOR CARD READER

NOTE:

21mm (3/4")

CONDUIT HOME RUN

TO PANELBOARD

21mm (3/4") CONDUIT TO

"REQUEST TO EXIT" DEVICE

21mm (3/4") CONDUIT

TO CARD READER

21mm (3/4") CONDUIT

TO MAGNETIC SWITCH

"REQUEST TO EXIT" DEVICE LOCATED

ON SECURE SIDE OF DOOR.

300mm (12") X 300mm (12") X 100mm

(4") DOOR CONTROL JUNCTION BOX.

(LOCATE ON SECURE SIDE OF DOOR)

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E5.1JST

ELECTRICAL DETAILS

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

NO SCALEE5.1

1 WIRING DEVICES COVER PLATE MARKING

NO SCALEE5.1

2 DISCONNECT/STARTER/SWITCH/VSMC LABEL

NO SCALEE5.1

3 PANELBOARD LABELS

NO SCALEE5.1

4 SYSTEMS FURNITURE POWER SUPPLY

NO SCALEE5.1

5 CARD READER RACEWAY DETAIL

KW

ETR PANEL DP

240/120V, 600A,3PH,4W

EX UTILITY METER

P A

P A

P A

P A

P A

G

EX NATURAL

GAS GENERATOR

125KVA

EX ATS

600A

ETR PANEL MF1

240/120V, 200A,3PH,4W3

P

A ETR PANEL MF2

240/120V, 200A,3PH,4W3

P

A ETR PANEL ES1

240/120V, 225A,3PH,4W3

P

A ETR PANEL BAL

240/120V, 200A,3PH,3W3

P A

RX PANEL MF2A

240/120V, 60A,1PH,3W

P A

KW

ETR PANEL DP

240/120V, 600A,3PH,4W

EX UTILITY METER

P A

P A

P A

P A

P A

G

EX NATURAL

GAS GENERATOR

125KVA

EX ATS

600A

ETR PANEL MF1

240/120V, 200A,3PH,4W3

P

A ETR PANEL MF2

240/120V, 200A,3PH,4W3

P

A ETR PANEL ES1

240/120V, 225A,3PH,4W3

P

A ETR PANEL BAL

240/120V, 200A,3PH,3W3

P A

PANEL MF2A

240/120V, 60A,1PH,3W

P A

CX

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E6.1JST

ELECTRICAL ONE-LINE

DIAGRAMS

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

NO SCALEE6.1

1 ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION

NO SCALEE6.1

2 ELECTRICAL ONE-LINE DIAGRAM - NEW WORK 323963

5 6 10 11 14 15 18 21

26 27 28 29 31 32 34 36 38 39 40 41 44 46 48

1 2 3 4 7 8 9 12 13 16 17 19 20 22 23 24

25 30 33 35 37 42 43 45 47

48 PORT DATA PATCH

PANEL CAT6A RATED.

LOCATED IN IT RACK.

LABEL

BLUE RJ45 CAT6 OUTLETS

CONNECTOR, TYPICAL.

SYMBOL ON FLOOR PLANS:

CAT6A CABLE 4 PAIR (CMP) BLUE SHEATH, TYPICAL.

5 6 10 11 14 15 18 21

26 27 28 29 31 32 34 36 38 39 40 41 44 46 48

1 2 3 4 7 8 9 12 13 16 17 19 20 22 23 24

25 30 33 35 37 42 43 45 47

48 PORT PHONE PATCH

PANEL CAT 6A RATED.

LOCATED IN IT RACK.

LABEL

BLUE RJ45 CAT6 OUTLETS

CONNECTOR, TYPICAL.

SYMBOL ON FLOOR PLANS:

5 6 10 11 14 15 18 21

26 27 28 29 31 32 34 36 38 39 40 41 44 46 48

1 2 3 4 7 8 9 12 13 16 17 19 20 22 23 24

25 30 33 35 37 42 43 45 47

FIRE RATED

PLYWOOD BACKBOARD

WALL MOUNTED

GROUND BAR

RELOCATED RACK

AND EQUIPMENT

IT RACK

TR01

TELECOM

WOODSHOP

OFFICE

EX

KITCHEN

OFFICE

ELEC

TRAINING ROOM

JJJ

1-1/4"C FOR IT

CONDUIT, TYPICAL

2"C FOR SYSTEMS

FURNITURE CONDUIT,

TYPICAL

IT RACK

TR01

TELECOM

C01

CORRIDOR

TRAINING ROOM

WOODSHOP

POE

NETWORK

VIDEO RECORDER

UPS

VIDEO

MANAGEMENT

SOFTWARE

MONITOR

CAT6A CABLE IN

1" CONDUIT, TYPICAL

MECH MEZZ

CRDPKMSMSMSDP

MS

TO ELEC RM

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E6.2JST

TELECOMMUNICATIONS AND

SECURITY RISER DIAGRAMS

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

NO SCALEE6.2

TYPICAL TELEPHONE AND DATA OUTLET WIRING

DIAGRAM

NO SCALEE6.2

3 TYPICAL IT RACK INSTALLATION

NO SCALEE6.2

1 TELECOM RISER DIAGRAM

NO SCALEE6.2

4 SECURITY RISER DIAGRAM

$OS

NEUTRAL

LINE

BUTTON FOR

OVERRIDE

CONTROL

STATUS INDICATOR LIGHT

SENSOR LENS

LUMINAIRE(S)

BASIS OF DESIGN PRODUCT: SENSOR SWITCH MODEL #WSX PDT

NOTE: GROUND WIRE NOT SHOWN, HOWEVER SHALL

BE PROVIDED WITH ALL CIRCUIT WIRING PER NEC.

ON

OFF

CAT 5 CAT 5

BLUE

BLUE

LINE

BLK/ORN

WHT

NEUTRAL

RELAY PACK

BLK-120V

ORN-277V

(CAP UNUSED)

WIRING NOTE: PROVIDE GROUND WIRE WITH ALL LINE VOLTAGE WIRING.

CAT 5

ADDITIONAL OCCUPANCY SENSORS AS

INDICATED ON FLOOR PLANS. DAISY

CHAIN MULTIPLE SENSORS TOGETHER.

LOW VOLTAGE SWITCH

TYPE LV1

CEILING OR WALL MOUNTED

OCCUPANCY SENSOR

REFER TO FLOOR PLANS

FOR TYPE(S)

CEILING OR WALL MOUNTED

OCCUPANCY SENSOR

REFER TO FLOOR PLANS

FOR TYPE(S)

LUMINAIRE(S)

W

ALL

B

OX O

CCUPANCY S

ENSOR(S

) W

ITH S

IN

GLE

O

UTPUT R

ELA

Y

W

ALL

B

OX O

CCUPANCY S

ENSOR(S

) W

IT

H D

UAL O

UTPUT R

ELA

YS

TOGGLE

S

W

ITCH(E

S)

LU

MIN

AIR

E W

ITH B

UILT

-IN

O

CCUPANCY S

ENSOR

CEILI

NG/W

ALL

M

OUNTED O

CCUPANCY S

ENSOR

- DIG

IT

AL S

W

IT

CH(E

S)

CEILI

NG/W

ALL

M

OUNTED O

CCUPANCY S

ENSORS

-IN

DOOR P

HOTOSENSORS

OUTDOOR P

HOTOCELL

S

ASTRONOMIC

AL T

IM

ECLO

CK

SW

IT

CHIN

G

STEP-D

IM

MIN

G

FULL

R

ANGE D

IM

MIN

G

OCCUPANCY S

ENSOR T

IM

EOUT/D

ELA

Y (IN

M

IN

UTES)

TIM

ECLO

CK S

CHEDULE

D 'O

FF' T

IM

E

OCC. S

ENSOR O

VERRID

E T

IM

ECLO

CK D

URIN

G 'O

FF' H

OURS

TIM

ECLO

CK S

CHEDULE

D 'O N' T

IM

E

DAYLIG

HTIN

G-D

IM

LI

GHTS TO M

AIN

TAIN

M

IN

IM

UM 50

FC A

T 30

"A

FF

- - - - - - - X - - - - X - - - - - - - - -

X - - - - - - - - - - - X - - - - - - - -

- - - - - - - - - X - - X - - - - - - - - - -

X

X

ELECTRICAL

RESTROOM

EXTERIOR

LIG

HTS M

ANUAL O

N

LIG

HTS A

UTOMATIC

O

N 10 0%

LI

GHT LE

VEL U

PON O

CCUPANCY

LIG

HTS A

UTO O

N 50

U

PON O

CCUPANCY, 1

M

ANUAL O

N

LINE VOLTAGE

CONTROL DEVICES

LOW VOLTAGE

CONTROL DEVICES

MISCELLANEOUSSWITCHING/DIMMING NOTES

TYPICAL SPACE TYPE

- - - - - - X X - - - - - - X - 15 - - - - - -X - -OFFICE

- - - - - - X X - - - - - - X - 15 6AM 5PM X - - -X - -CORRIDOR

- - X - - - - - - - - - X - - - 5 - - - - - -- X -STORAGE/TELECOM

- - - - - - - X - - - - X - - - 15 - - - - - -X - -LOCKERS

- - - - - - X X - - - - - - X - 15 - - - - - -X - -TRAINING ROOM

$OS2

BASIS OF DESIGN PRODUCT:

SENSOR SWITCH MODEL #WSX PDT 2P FAN-ASHRT

NOTE: GROUND WIRE NOT SHOWN, HOWEVER SHALL BE

PROVIDED WITH ALL CIRCUIT WIRING PER NEC.

NEUTRAL

LINE

STATUS INDICATOR LIGHT

SENSOR LENS

BUTTON FOR

OVERRIDE CONTROL

OF LUMINAIRE(S)

BUTTON FOR OVERRIDE

CONTROL OF FAN

LUMINAIRE(S)

BATHROOM

FAN

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E7.1JST

LIGHTING CONTROL DIAGRAMS

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

NO SCALEE7.1

1 OCCUPANCY SENSOR WALL SWITCH

NO SCALEE7.1

ONE ZONE SWITCHING LIGHTING CONTROL WITH

OCCUPANCY SENSOR(S) AND SWITCH(ES)

NO SCALEE7.1

3 OCCUPANCY SENSOR WALL SWITCH WITH FAN

NOTES: (APPLICABLE TO LUMINAIRE SCHEDULE ONLY)

LAMP TYPES ARE INDICATED BY INDUSTRY GENERIC DESIGNATIONS; SEE SPECIFICATIONS FOR APPROVED MANUFACTURERS.1.

A.

CATALOG NUMBERS FOR LUMINAIRES INDICATE THE TYPE AND QUALITY OF THE LUMINAIRE TO BE PROVIDED BY THE CONTRACTOR AND ARE GENERAL IN NATURE. THE CATALOG NUMBERS ARE NOT INTENDED TO INDICATE AN ACTUAL ORDER MODEL NUMBER. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE LUMINAIRES WITH THE TYPE OF LAMP, BALLAST, LENS OR DIFFUSER, AND CONSTRUCTION FEATURES AS INDICATED IN THE SPECIFICATIONS.

2.

WHERE A LUMINAIRE IS NOTED AS "NO EQUAL," SUBSTITUTIONS WILL NOT BE ACCEPTED. EQUIVALENT LUMINAIRES WILL BE ACCEPTED PROVIDED THEY ARE PROVEN TO BE EQUAL TO, OR BETTER THAN, THE SPECIFIED LUMINAIRE IN ALL RESPECTS. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, CONSTRUCTION FEATURES, APPEARANCE, AND PERFORMANCE. SUBMIT THE FOLLOWING FOR

EACH PROPOSED SUBSTITUTION:

3.

SAMPLE OF PROPOSED EQUIVALENT LUMINAIRE FOR TABLE-TOP EVALUATION. SAMPLE SHALL BE AN EXACT MATCH TO THE PROPOSED SUBSTITUTION INCLUDING ALL FEATURES, FINISHES, LAMPING, OPTIONS, ACCESSORIES, MOUNTING BRACKETS, ETC. SAMPLE SHALL INCLUDE 120V CORD AND NEMA 5-20P PLUG FOR OPERATIONAL TEST DURING TABLE-TOP EVALUATION.

B.POINT-BY-POINT LIGHT LEVEL CALCULATIONS IN 3-DIMENSIONAL LIGHTING CALCULATION SOFTWARE TO ILLUSTRATE GUARANTEED ILLUMINATION LEVELS. EACH SPACE AFFECTED BY A SUBSTITUTION SHALL BE MODELED AND CALCULATED USING INDUSTRY STANDARD VALUES FOR REFLECTANCES, LIGHT LOSS FACTOR, ETC. ENGINEER WILL COMPARE TO BASIS OF DESIGN LUMINAIRE AND ENGINEER'S CALCULATIONS TO APPROVE OR REJECT SUBSTITUTE LUMINAIRE. PROVIDE IES FILE TO ENGINEER FOR PROPOSED SUBSTITUTE ALONG WITH CALCULATION

RESULTS.

C. POINT-BY-POINT COMPARATIVE DATA IN SIDE-BY-SIDE FORMAT COMPARING FEATURES OF SUBSTITUTE LUMINAIRE TO BASIS-OF-DESIGN LUMINAIRE.

D. ALL REQUIREMENTS OF DIVISION 1 SECTION "SUBSTITUTION PROCEDURES."

COORDINATE CONTROL COMPATIBILITY BETWEEN BALLAST/DRIVER TYPES FOR ALL DIMMED LUMINAIRES WITH MANUFACTURER AND MODEL OF DIMMING CONTROL DEVICES.4.

PROVIDE EXIT SIGNS WITH SINGLE FACE OR DOUBLE FACE AND WITH OR WITHOUT CHEVRONS AS INDICATED ON THE DRAWINGS. PROVIDE RED OR GREEN LETTERING AS REQUIRED BY AHJ.5.

ALL MOUNTING HEIGHTS SHALL BE AS INDICATED ON THE DRAWINGS OR AS DIRECTED BY THE CONTRACTING OFFICER. MOUNTING HEIGHTS OF WALL MOUNTED LUMINAIRES SHALL BE MEASURED FROM THE FINISHED FLOOR TO THE CENTERLINE OF THE LUMINAIRE. MOUNTING HEIGHTS OF CEILING SUSPENDED LUMINAIRES SHALL BE MEASURED FROM THE FINISHED FLOOR TO THE BOTTOM

OF THE LUMINAIRE.

6.

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E8.1JST

LUMINAIRE SCHEDULE

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

LUMINAIRE SCHEDULE

TYPE MOUNTING LUMINAIRE DESCRIPTION MANUFACTURER CATALOG NUMBER

LAMP DRIVER / BALLAST

VOLTAGE

INPUT

WATTS NOTES

TYPE CRI CCT QTY

WATTS /

LAMP

LUMENS

/ LAMP

TYPE QTY

BALLAST

FACTOR

A RECESSED

24" X 48" X 3-1/4" VOLUMETRIC TROFFER LUMINAIRE WITH

EXTRUDED ALUMINUM HOUSING, ANGLED ACRYLIC LENS, 3000

LUMEN PACKAGE, INTEGRAL DRIVER, AND WHITE FINISH.

METALUX 24EN-LD2-30-UNV-L835-CD1-U LED 80 3500 1 25 3117 0-10V DIMMING 1 1.00 120 25 -

B1 RECESSED

24" X 24" X 3-1/4" VOLUMETRIC TROFFER LUMINAIRE WITH

EXTRUDED ALUMINUM HOUSING, ANGLED ACRYLIC LENS, 1900

LUMEN PACKAGE, INTEGRAL DRIVER, AND WHITE FINISH.

METALUX 22EN-LD2-19-UNV-L835-CD1-U LED 80 3500 1 17 2091 0-10V DIMMING 1 1.00 120 17 -

B2 RECESSED

24" X 24" X 3-1/4" VOLUMETRIC TROFFER LUMINAIRE WITH

EXTRUDED ALUMINUM HOUSING, ANGLED ACRYLIC LENS, 2500

LUMEN PACKAGE, INTEGRAL DRIVER, AND WHITE FINISH.

METALUX 22EN-LD2-25-UNV-L835-CD1-U LED 80 3500 1 20 2701 0-10V DIMMING 1 1.00 120 20 -

D1 RECESSED

4" DOWNLIGHT LUMINAIRE WITH STEEL HOUSING, 1000 LUMEN

PACKAGE, WIDE DISTRIBUTION, INTEGRAL DRIVER, AND CLEAR TRIM

FINISH.

GOTHAM EVO4-35-10-AR-LSS-WD-MVOLT-GZ10 LED 80 3500 1 9 1000 0-10V DIMMING 1 1.00 120 9 -

D2 RECESSED

4" DOWNLIGHT LUMINAIRE WITH STEEL HOUSING, SHOWER RATED,

MEDIUM WIDE DISTRIBUTION, INTEGRAL DRIVER, AND CLEAR TRIM

FINISH.

GOTHAM EVO4SH-35-10-DFR-SOL-MVOLT-EZ1 LED 80 3500 1 9 843 0-10V DIMMING 1 1.00 120 9 -

D3 RECESSED

4" DOWNLIGHT LUMINAIRE WITH STEEL HOUSING, 1400 LUMEN

PACKAGE, WIDE DISTRIBUTION, INTEGRAL DRIVER, AND CLEAR TRIM

FINISH.

GOTHAM EVO4-35-15-AR-LSS-WD-MVOLT-GZ10 LED 80 3500 1 14 1527 0-10V DIMMING 1 1.00 120 14 -

E1 WALL

12" X 8" X 2" LED EXIT SIGN WITH THERMOPLASTIC HOUSING,

RED OR GREEN LETTERS AS REQUIRED BY AHJ, DIRECTIONAL

CHEVRONS AS INDICATED ON DRAWINGS, NICAD BATTERY, AND

WHITE FINISH.

LITHONIA LQM-S-W-3-R/G-MVOLT-EL-N-SD LED - - - - - - - - 120 3 -

W1 WALL

24" X 5" X 4" WALL WRAPAROUND LUMINAIRE WITH STEEL

HOUSING, ACRYLIC LENS, INTEGRAL DRIVER, AND WHITE FINISH. LITHONIA WL2-12L-GZ10-LP835 LED 80 3500 1 12 1249 0-10V DIMMING 1 1.00 120 12 -

NOTES: (APPLICABLE TO MECHANICAL EQUIPMENT ELECTRICAL CONNECTION SCHEDULE ONLY)

REVIEW EQUIPMENT SUBMITTALS FROM OTHER TRADES PRIOR TO ORDERING OR INSTALLING ASSOCIATED ELECTRICAL WORK. ELECTRICAL CONTRACTOR SHALL MODIFY COMPONENTS OF THE ELECTRICAL CONNECTIONS AS NECESSARY TO MATCH NAMEPLATE DATA OF APPROVED EQUIPMENT AND PROVIDE A CODE COMPLIANT INSTALLATION, INCLUDING BUT NOT LIMITED TO CIRCUIT BREAKERS, WIRE, CONDUITS, CONNECTION TYPES, SWITCHES, AND FUSES. CHANGE ORDERS AND EXTRAS WILL NOT BE AWARDED FOR FAILURE TO COORDINATE

WITH OTHER TRADES' EQUIPMENT SUBMITTALS.

1.

PROVIDE NECESSARY SUPPORTING STRUT CHANNEL AND ALL MISCELLANEOUS HARDWARE FOR MOUNTING ELECTRICAL EQUIPMENT. MAINTAIN NEC WORKING CLEARANCES. FIELD COORDINATE EXACT LOCATIONS. DO NOT MOUNT ON EQUIPMENT ACCESS PANELS OR IN EQUIPMENT MANUFACTURERS' RECOMMENDED MAINTENANCE

CLEARANCES. COORDINATE EXACT LOCATION OF SAFETY SWITCHES WITH MECHANICAL

EQUIPMENT/CONTRACTOR.

2.

NOTES: (APPLICABLE TO DISCONNECT SWITCH SCHEDULE ONLY)

PROVIDE FUSE AND COORDINATE EXACT EQUIPMENT FUSE SIZE WITH MOTOR

OR EQUIPMENT NAMEPLATE DATA DURING CONSTRUCTION.

1.

ALL DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE WITH GROUND LUG.2.

PROVIDE ALL FUSIBLE DISCONNECT SWITCHES WITH CLASS R FUSE KIT.3.

LABEL DISCONNECT SWITCHES WITH THE DESIGNATION IDENTIFIED IN THIS

SCHEDULE AND THE CIRCUIT NUMBER AND PANELBOARD FROM WHICH IT IS

FED, INCLUDING VOLTAGE AND PHASE.

4.

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E8.2JST

ELECTRICAL EQUIPMENT

SCHEDULES

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

MECHANICAL EQUIPMENT ELECTRICAL CONNECTION SCHEDULE

EQUIPMENT

DESIGNATION KW HP MCA MOCP FLA VOLTAGE PHASE LOAD (kVA) WIRING DISCONNECTING MEANS CONTROL MEANS NOTES

ACCU-1 16.4 20 13.1 240 1 3.15 2#12 + #12GW IN 3/4"C DS-ACCU-1

ACU-1 - 20 0.0 240 1 0.00 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH FED FROM OUTDOOR UNIT

DWH-1 15 1.7 120 1 0.20 2#12 + #12GW IN 3/4"C RECEPTACLE EXISTING/RELOCATE

EF-1 2.25 15 1.8 120 1 0.21 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH

EF-2 2.25 15 1.8 120 1 0.21 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH

FCU-1.1 1.6 15 1.3 240 1 0.31 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH

FCU-1.2 2.8 15 2.3 240 1 0.54 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH

FCU-2.1 8.6 15 6.9 240 1 1.65 2#12 + #12GW IN 3/4"C MANUAL MOTOR SWITCH

HOOD-1 1.5 15 1.2 120 1 0.14 2#12 + #12GW IN 3/4"C -

HPU-1 29.1 35 23.3 240 1 5.59 2#8 + #10GW IN 3/4"C DS-HPU-1

HPU-2 29.1 35 23.3 240 1 5.59 2#8 + #10GW IN 3/4"C DS-HPU-2

PUMP-1 20 1.5 120 1 0.18 2#12 + #12GW IN 3/4"C -

DISCONNECT SWITCH SCHEDULE

DESIGNATION

AMP

RATING

POLES

VOLT

RATING

FUSE

AMPS

FUSE

CLASS

NEMA

ENCLOSURE

NOTES

DS-ACCU-1 60 2 240 20 RK5 3R

DS-HPU-1 60 2 240 35 RK5 3R

DS-HPU-2 60 2 240 35 RK5 3R

FEED THROUGH LUGS

DEMAND AMPS: 0 A

ISOLATED GROUND BUS d SHUNT TRIP BREAKER

DEMAND LOAD: 0.00 kVA

200% NEUTRAL BUS & LUGS c GFEP BREAKER (30mA) g RED BREAKER LOCKOUT

CONNECTED LOAD: 0.00 kVA

INTEGRAL SPD/TVSS b GFCI BREAKER (5mA) f HANDLE CLAMP

SERVICE ENTRANCE LABEL a AFCI BREAKER e HANDLE PADLOCK

PANEL TOTALS

X GROUND BUS AUXILIARIES:

PHASE AMPS: 0 A 0 A 0 A

PHASE LOAD: 0.00 kVA 0.00 kVA 0.00 kVA

41 0.00 0.00 20 1 EX AUTO TRANSFER SWITCH 42

EX HVAC 2 50

0.00 0.00 20 1 EX REC: ADT 40

37 EX AC BLOWER CARP SHOP 1 20 0.00 0.00 38

35 EX REC: CARP SHOP E WALL 1 20 0.00 0.00

60 2 EX LOAD CENTER

33 EX LOAD 1 20 0.00 0.00 20 1 EX LTG: CARP SHOP CENTER 34

31 EX LTG: GARAGE BAY E 1 20 0.00 0.00 30 1 EX LTG: CARP SHOP W 32

29 EX LTG: GARAGE BAY W 1 20 0.00 0.00 30 1 EX LTG: CARP SHOP E 30

27 EX LOAD 1 20 0.00 0.00 20 1 EX LTG: UPPER STORAGE 28

25 EX LTG: KITCHEN EAST 1 20 0.00 0.00 20 1 EX AC BLOWER STORAGE 26

23 EX REC: COFFEE POT 1 20 0.00 0.00 20 1 EX REC: MICROWAVE 24

21 EX POWER VENT CARP 1 20 0.00 0.00 20 1 EX REC: GARAGE INNER WALL 22

19 EX REC: BOOK HALL 1 20 0.00 0.00 20 1 EX LTG: CUSTODIAL 20

17 EX COMPUTER 1 20 0.00 0.00 20 1 EX LTG: OFF/KIT/SHWR 18

15 EX REC: N/W WALL, FAX 1 20 0.00 0.00 20 1 EX REC: COPY MACHINE 16

13 EX COMP COOLER 1 20 0.00 0.00 20 1 EX REC: WEST WALL GARAGE 14

11 EX OVERHEAD DOOR 1 20 0.00 0.00 20 1 EX OVERHEAD DOOR 1/2 12

9 EX REC: S WALL 1 20 0.00 0.00 20 1 EX REC: LOUNGE 10

7 EX REC: SE WALL 1 20 0.00 0.00 20 1 EX REC: N WALL GARAGE, NE 8

5 0.00 0.00 20 1 EX LTG: LOUNGE OUTSIDE 6

EX LOAD 2 40

0.00 0.00 4

1 EX LOAD 1 20 0.00 0.00

60 2 RX HVAC

CKT LOAD DESCRIPTION P TA AUX/NOTE A B C AUX/NOTE TA P LOAD DESCRIPTION CKT

FED FROM:

MANUFACTURER:

TYPE:

SERVICE TYPE: NORMAL

MIN. RATING: 10K AIC RMS SYMMETRICAL AMPS LOCATION: ELECTRICAL ROOM 108

SERVICE: 240 VOLTS W/ CENTER TAP 120 VOLTS, 3 PHASE, ... ENCLOSURE: NEMA 1

MAIN TYPE: 200 A MCB SECTIONS: 1EX PANEL MF2

BUS AMPACITY: 225 A MOUNTING: SURFACE

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

E8.3JST

PANELBOARD SCHEDULES

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

PANEL SCHEDULE NOTES (APPLICABLE TO PANEL SCHEDULES NOTE COLUMN ON THIS DRAWING ONLY):

1. PROVIDE NEW CIRCUIT BREAKER IN EXISTING AVAILABLE SPACE. MATCH PANELBOARD MANUFACTURER, TYPE, AND AIC RATING.

2. REMOVE EXISTING CIRCUIT BREAKER AND PROVIDE NEW IN SAME LOCATION. MATCH PANELBOARD MANUFACTURER, TYPE, AND AIC RATING. TURN OVER EXISTING CIRCUIT BREAKER TO OWNER FOR

USE AS SPARE.

3. CONNECT NEW LOAD TO EXISTING SPARE CIRCUIT BREAKER.

4. CONNECT NEW LOAD TO EXISTING CIRCUIT BREAKER MADE SPARE AFTER DEMOLITION.

5. REMOVE EXISTING LOAD AND RELABEL EXISTING CIRCUIT BREAKER AS "SPARE".

FEED THROUGH LUGS

DEMAND AMPS: 0 A ISOLATED GROUND BUS d SHUNT TRIP BREAKER DEMAND LOAD: 0.00 kVA 200% NEUTRAL BUS & LUGS c GFEP BREAKER (30mA) g RED BREAKER LOCKOUT

CONNECTED LOAD: 0.00 kVA INTEGRAL SPD/TVSS b GFCI BREAKER (5mA) f HANDLE CLAMP SERVICE ENTRANCE LABEL a AFCI BREAKER e HANDLE PADLOCK

PANEL TOTALS X GROUND BUS AUXILIARIES:

PHASE AMPS: 0 A 0 A 0 A

PHASE LOAD: 0.00 kVA 0.00 kVA 0.00 kVA

41 0.00 0.00 42

39 0.00 0.00 40

EX DELTA RADIAL ARM SAW 3 15

0.00 0.00

15 3 EX COMPRESSOR

35 0.00 0.00 36

33 0.00 0.00 34

EX DELTA RADIAL ARM SAW 2 3 15

0.00 0.00

15 3 EX MORTISE MACHINE

29 0.00 0.00 30

27 0.00 0.00 28

EX JOINER 3 15

0.00 0.00

15 3 EX UNISAW 10

23 0.00 0.00 24

21 0.00 0.00 22

EX LATHE 3 15

0.00 0.00

15 3 EX BAND SAW

17 0.00 0.00 18

15 0.00 0.00 16

EX OUTSIDE VAC 3 15

0.00 0.00

15 3 EX DUAL SANDER

11 0.00 0.00 12

9 0.00 0.00 10

EX DRILL PRESS 3 20

0.00 0.00

20 3 EX SCROLL SAW

5 0.00 0.00 6

3 0.00 0.00 4

EX BIG MAMA SAW 3 30

0.00 0.00

30 3 EX PLANER

CKT LOAD DESCRIPTION P TA AUX/NOTE A B C AUX/NOTE TA P LOAD DESCRIPTION CKT

FED FROM:

MANUFACTURER: TYPE:

SERVICE TYPE: NORMAL MIN. RATING: 10K AIC RMS SYMMETRICAL AMPS LOCATION: ELECTRICAL ROOM 109

SERVICE: 240 VOLTS W/ CENTER TAP 120 VOLTS, 3 PHASE, ... ENCLOSURE: NEMA 1

MAIN TYPE: 200 A MCB SECTIONS: 1EX PANEL MF1

BUS AMPACITY: 225 A MOUNTING: SURFACE

FEED THROUGH LUGS

DEMAND AMPS: 90 A ISOLATED GROUND BUS d SHUNT TRIP BREAKER DEMAND LOAD: 37.58 kVA 200% NEUTRAL BUS & LUGS c GFEP BREAKER (30mA) g RED BREAKER LOCKOUT

CONNECTED LOAD: 37.58 kVA INTEGRAL SPD/TVSS b GFCI BREAKER (5mA) f HANDLE CLAMP SERVICE ENTRANCE LABEL a AFCI BREAKER e HANDLE PADLOCK

PANEL TOTALS X GROUND BUS AUXILIARIES:

PHASE AMPS: 108 A 65 A 98 A

PHASE LOAD: 14.99 kVA 9.05 kVA 13.55 kVA

41 2.00 0.00 20 1 EX AUTO TRANSFER SWITCH 42

EX HVAC 2 50

2.00 0.00 20 1 EX REC: ADT 40

37 EX AC BLOWER CARP SHOP 1 20 0.00 3.63 38

35 EX REC: CARP SHOP E WALL 1 20 0.00 3.95

60 2 PANEL MF2A

33 EX LOAD 1 20 0.00 0.00 20 1 EX LTG: CARP SHOP CENTER 34

31 LTG: CORR/KIT/RR 1 20 4 0.27 0.00 30 1 EX LTG: CARP SHOP W 32

29 LTG: TRAINING/OFFICES 1 20 4 0.47 0.00 30 1 EX LTG: CARP SHOP E 30

27 EX LOAD 1 20 0.00 0.00 20 1 EX LTG: UPPER STORAGE 28

25 MECH: EF-1/EF-2 1 20 4 0.42 0.00 20 1 EX AC BLOWER STORAGE 26

23 REC: CORR/KIT/RR 1 20 4 0.90 0.36 4 20 1 REC: TELECOM 24

21 EX POWER VENT CARP 1 20 0.00 0.00 20 1 EX REC: GARAGE INNER WALL 22

19 0.83 2.80 20

FCU-2.1 2 15 2

0.83 2.80

2 35 2 MECH: HPU-2

15 0.43 2.80 16

MECH: FCU-1.1/1.2 2 15 2

0.43 2.80

2 35 2 MECH: HPU-1

11 EX OVERHEAD DOOR 1 20 0.00 0.75 4 20 1 SYS FURN: TRAINING 108 12

9 1.58 0.75 4 20 1 SYS FURN: TRAINING 108 10

MECH: ACCU-1/ACU-1 2 20 2

1.58 0.75 4 20 1 SYS FURN: TRAINING 108 8

5 0.00 1.50 4 20 1 SYS FURN: TRAINING 108 6

EX LOAD 2 40

0.00 1.50 2 20 1 SYS FURN: TRAINING 108 4

1 EX LOAD 1 20 0.00 1.50 2 20 1 SYS FURN: TRAINING 108 2

CKT LOAD DESCRIPTION P TA AUX/NOTE A B C AUX/NOTE TA P LOAD DESCRIPTION CKT

FED FROM:

MANUFACTURER: TYPE:

SERVICE TYPE: NORMAL MIN. RATING: 10K AIC RMS SYMMETRICAL AMPS LOCATION: ELECTRICAL ROOM 109

SERVICE: 240 VOLTS W/ CENTER TAP 120 VOLTS, 3 PHASE, ... ENCLOSURE: NEMA 1

MAIN TYPE: 200 A MCB SECTIONS: 1EX PANEL MF2

BUS AMPACITY: 225 A MOUNTING: SURFACE

MODIFICATIONS

6. PROVIDE LISTED HANDLE TIE FOR SYSTEMS FURNITURE CIRCUIT FEEDS TO COMPLY WITH ARTICLE

210.4 OF THE NATIONAL ELECTRICAL CODE FOR MULTIWIRE BRANCH CIRCUITS.

FEED THROUGH LUGS

DEMAND AMPS: ISOLATED GROUND BUS d SHUNT TRIP BREAKER

DEMAND LOAD: 200% NEUTRAL BUS & LUGS c GFEP BREAKER (30mA) g RED BREAKER LOCKOUT

CONNECTED LOAD: INTEGRAL SPD/TVSS b GFCI BREAKER (5mA) f HANDLE CLAMP

SERVICE ENTRANCE LABEL a AFCI BREAKER e HANDLE PADLOCK

PANEL…