A06_DrawingS_WA22065-12_NPS_Natchez_MF_Modernization_100__CD_DWGS_-_Arch_S_S.pdf
PDF 11 MB Posted
- Attached to
- MODERNIZE NATCHEZ MAINTENANCE FACILITY
- Solicitation number
- 140P5226R0002
About this file
This document is a design development drawing set for the Natchez Maintenance Facility Renovation project at Natchez National Historical Park in Adams County, Mississippi. The project involves a Level 2 Alteration to approximately 2,415 gross square feet of an existing 4,307 GSF, one-story building classified as Building Occupancy Class B and F-1 (Business and Factory) with Type V-B construction. The building is non-sprinklered, with an allowable height of 40 feet and actual height of 18 feet.
The renovation includes mechanical, plumbing, electrical, fire alarm, and structural work. The total occupant load is 28 occupants distributed across spaces including a training room, kitchen, unisex toilet, lockers, two offices, corridor, electrical room, wood shop, telecom room, and mezzanine mechanical space. The drawing set comprises 69 sheets organized by discipline and includes demolition plans, new work plans, details, schedules, and code compliance documentation. Key consultants include Henry Adams, LLC (A/E Prime) in Baltimore, Maryland, and JOE WALKER AIA (Architect) in Gainesville, Florida. The drawings are dated March 20, 2024, and prepared by the National Park Service as the federal agency overseeing this project at the national historical park facility.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING INFORMATION AND LIMITATIONS
BUILDING OCCUPANCY CLASS: B and F-1
CONSTRUCTION TYPE: TYPE V-B
SPRINKLERED: N
ALLOWABLE BUILDING HEIGHT: 1 STORY, 40'
ACTUAL BUILDING HEIGHT: 1 STORY, 18'
ALLOWABLE BUILDING AREA (PER STORY): 8,500 GSF
ACTUAL BUILDING AREA (PER STORY): 4,307 GSF
RENOVATED AREA: 2,415 GSF
AREAS AND OCCUPANT LOAD
TOTAL GROSS FLOOR AREA: 4,307 GSF
TOTAL OCCUPANT LOAD: 28 OCCUPANTS
CHAIN-LINK FENCE
STORAGE CONTAINER
DUMPSTER
ENTRY GATE
M E
L R
O S
E M
O N
T E
B E
L L O
W P
K W
Y
MAINTENANCE FACILITY
ASPHALT PAVING
PARKIN
G
PARKIN
G
GATE
ABATEMENT SUITE
LOCATION MAP
PROJECT LOCATION
PROJECT INFORMATION
INDEX OF DRAWINGS
TITLE OF PROJECT: DRAWING NO.
PMIS/PKG NO.
OF
SHEET
NAME OF PARK
NATCHEZ NATIONAL HISTORICAL PARK
REGION COUNTY STATE
SE ADAMS MISSISSIPPI
NATIONAL PARK SERVICE
UNITED STATES
DEPARTMENT OF THE INTERIOR
A/E
PRIME
SUB
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER AIA
ARCHITECT
GAINESVILLE, FL
QUALITY DESIGN CERTIFICATION
Prepared in Accordance with Design Development (Title I) ________________ OR Drawing No.
Variance from Design Development (Title I) Approved by Superintendent on ___________ OR Date Construction Drawing Not Preceded by Design Development (Title I)
Project Manager
Date
Mark Sheet Date InitialREVISION
323963
/2
/2
:3
:2
A
M NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
DESIGN DEVELOPMENT G000
GENERAL
G000 COVER
G001 GENERAL NOTES, SYMBOL LEGEND AND ABBREVIATIONS
G002 TYPICAL TOILET ROOMS AND MOUNTING HEIGHTS
G003 TYPICAL MOUNTING HEIGHTS
G010 CODE COMPLIANCE
G011 CODE COMPLIANCE
G101 LIFE SAFETY PLAN
ARCHITECTURAL
AD101 DEMOLITION PLAN AND ELEVATIONS
AD121 CEILING DEMOLITION PLAN
A101 FLOOR PLAN AND ELEVATIONS
A121 PARTITION PLANS
A131 CEILING PLAN
A141 ROOF PLAN
A161 FINISH PLAN
A210 BUILDING SECTIONS AND PERSPECTIVES
A240 ROOF DETAILS
A241 ROOF DETAILS
A300 ENLARGED INTERIOR VIEWS
A400 PARTITION TYPES
A410 PARTITION DETAILS
A430 INTERIOR CASEWORK DETAILS
A500 OPENING TYPES AND SCHEDULE
A520 OPENING DETAILS
MD1.1 LEVEL 1 - DUCTWORK - DEMOLITION
MD1.2 MEZZANINE - DUCTWORK - DEMOLITION
NATIONAL PARK SERVICE
NATCHEZ MAINTENANCE
FACILITY RENOVATION
NATCHEZ NATIONAL HISTORICAL PARK
NATCHEZ, MISSISSIPPI
MECHANICAL
M0.1 MECHANICAL COVER SHEET
NO SCALEG000
2 SITE MAP
STRUCTURAL
S0.01 DESIGN CRITERIA & GENERAL NOTES
S1.01 FLOOR PLAN, ELEVATION AND DETAILS
FIRE ALARM
FA0.1 FIRE ALARM COVER SHEET
FA1.1 FIRST FLOOR - FIRE ALARM NEW WORK
FA1.2 MEZZANINE - FIRE ALARM NEW WORK
FA5.1 FIRE ALARM DETAILS
FA6.1 FIRE ALARM RISER DIAGRAM
M1.1 LEVEL 1 - DUCTWORK - NEW WORK
M1.2 MEZZANINE - DUCTWORK - NEW WORK
M2.1 LEVEL 1 - MECHANICAL PIPING - NEW WORK
M2.2 MEZZANINE - MECHANICAL PIPING - NEW WORK
M3.1 MECHANICAL SECTIONS
M5.1 MECHANICAL DETAILS
M6.1 AUTOMATIC TEMPERATURE CONTROLS
M7.1 MECHANICAL SCHEDULES
PLUMBING
P0.1 PLUMBING COVER SHEET
PD1.0 FOUNDATION - PLUMBING - DEMOLITION
PD1.1 LEVEL 1 - PLUMBING - DEMOLITION
PD1.2 MEZZANINE - PLUMBING - DEMOLITION
P1.0 FOUNDATION - PLUMBING - NEW WORK
P1.1 LEVEL 1 - PLUMBING - NEW WORK
P1.2 MEZZANINE - PLUMBING - NEW WORK
P5.1 PLUMBING DETAILS
P6.1 PLUMBING RISER DIAGRAMS
P7.1 PLUMBING SCHEDULES
ELECTRICAL
E0.1 ELECTRICAL COVER SHEET
E0.2 ELECTRICAL NOTES
ED1.1 FIRST FLOOR - ELECTRICAL DEMOLITION
ED1.2 MEZZANINE - ELECTRICAL DEMOLITION
E1.1 FIRST FLOOR - POWER NEW WORK
E1.2 MEZZANINE - POWER NEW WORK
E2.1 FIRST FLOOR - LIGHTING NEW WORK
E2.2 MEZZANINE - LIGHTING NEW WORK
E3.1 FIRST FLOOR - SECURITY NEW WORK
E3.2 MEZZANINE - SECURITY NEW WORK
E5.1 ELECTRICAL DETAILS
E6.1 ELECTRICAL ONE-LINE DIAGRAMS
E6.2 TELECOMMUNICATIONS AND SECURITY RISER DIAGRAMS
E7.1 LIGHTING CONTROL DIAGRAMS
E8.1 LUMINAIRE SCHEDULE
E8.2 ELECTRICAL EQUIPMENT SCHEDULES
E8.3 PANELBOARD SCHEDULES
E8.4 PANELBOARD SCHEDULES
WALL SECTION
DETAIL/ SECTION
NUMBER
SHEET NUMBER
BUILDING SECTION
EXTERIOR ELEVATION
SHEET NUMBER
ELEVATION NUMBER
INTERIOR ELEVATION
SHEET NUMBER
ELEVATION NUMBER
LARGE SCALE BLOWUP
OF PLAN OR DETAIL
PLAN OR DETAIL
NUMBER
SHEET NUMBER
LEVEL REFERENCE
LEVEL DESCRIPTION
LEVEL ELEVATION
NEW
STRUCTURAL GRID
GRID REFERENCE
GRID LINE
EXISTING
STRUCTURAL GRID
EXISTING GRID
REFERENCE
EXISTING GRID LINE
MATCH LINE 1 / A0103
1 / A0102
SHEET NUMBER
SHEET NUMBER
MATCH LINE
REVISION
CLOUDED AREA
OF REVISION
NORTH ARROW
SIMILAR INDICATION
DETAIL SECTION
DETAIL/ SECTION
NUMBER
SHEET NUMBER
A101
DETAIL NUMBER
SHEET NUMBER
Level 01
100' - 0"
A101
SIM
A101
A101
A101
A201
01 / A301
PARTITION PARTITION TYPE
DOOR
ASSEMBLY
EXTERIOR
GLAZED
OPENINGS
ROOM NAME
AND NUMBER
ROOM NAME
ROOM NUMBER
KEYNOTE
DEMOLITION
CONSTRUCTION
STOREFRONT
OPENINGS
OPENING TYPE
FURNITURE, FIXTURES &
EQUIPMENT
EQUIPMENT IDENTIFIER
DOOR NUMBER
OPENING TYPE
D01
M8G
1t
1t
1t
ROOM NAME
ROOM FINISHES TAG
ROOM NAME
ROOM NUMBER
FLOOR:
BASE:
WALL:
CONFERENCE
FLOORING
BASE
WALL
150 SF
APPROXIMATE ROOM AREA
ROOM FINISHES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE REMOVED
NEW CONSTRUCTION
NOT IN PROJECT
SCOPE
AC AIR CONDITIONING
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ARCH ARCHITECT, ARCHITECTURAL
AUTO AUTOMATIC
BLDG BUILDING
BRG BEARING
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CFCM COLD FORMED METAL FRAMING
CIP CAST-IN-PLACE (CONCRETE)
CJ CONTROL JOINT
CL CENTERLINE
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
DEMO DEMOLISH, DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DIM DIMENSION
DN DOWN
EA EACH
EJ EXPANSION JOINT
ELEC ELECTRIC, ELECTRICAL
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EXP EXPANSION
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FHC FIRE HOSE CABINET
FT FOOT/FEET
FURN FURNISH, FURNISHED, FURNISHINGS
GA GAUGE, GAGE
GWB GYPSUM WALL BOARD
HSS HOLLOW STRUCTURAL SECTION
HVAC HEATING-VENTILATING-AIR CONDITIONING
ID INSIDE DIAMETER
INT INTERIOR
LAV LAVATORY
LWIC LIGHTWEIGHT INSULATING CONCRETE
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER, MANUFACTURED
MIN MINIMUM
MISC MISCELLANEOUS
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
PCF POUNDS PER CUBIC FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
R RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIGERATOR
REV REVISE (ISION)
RO ROUGH OPENING
RTU ROOF TOP UNIT
SF SQUARE FOOT, FEET
SIM SIMILAR
SPEC SPECIFY, SPECIFICATION
SS STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STRUC STRUCTURE, STRUCTURAL
TBD TO BE DETERMINED
TEMP TEMPORARY
TOS TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
T&G TONGUE AND GROOVE
UC UNDERCOUNTER
UOI UNLESS OTHERWISE INDICATED
VIF VERIFY IN FIELD
VTR VENT THROUGH ROOF
WD WOOD
WP WEATHERPROOF
1. DO NOT SCALE DRAWINGS. RELY ON THE NUMERIC DIMENSIONS SHOWN FOR
MEASUREMENT. IF DIMENSIONS ARE IN QUESTION, OBTAIN CLARIFICATION FROM THE
ARCHITECT
2. REVIEW AND FIELD VERIFY ALL DIMENSIONS AND CONDITIONS RELATING TO THE
EXISTING BUILDINGS THAT INTERFACE WITH THE NEW CONSTRUCTION. NOTIFY THE
ARCHITECT WHEN EXISTING CONDITIONS VARY FROM THE PROJECT DRAWINGS.
3. DETAILED DRAWINGS AND LARGER SCALE DRAWINGS TAKE PRECEDENCE OVER
SMALLER SCALE DRAWINGS.
4. UNLESS INDICATED OTHERWISE, PLAN DIMENSIONS ARE TAKEN FROM CENTERLINE OF
STRUCTURE, FACE OF CONCRETE OR FACE OF STUD. PLAN DIMENSIONS TO PLUMBING
FIXTURES AND ACCESSORIES ARE TAKEN FROM FINISHED FACE OF WALL.
5. DOORS NOT OTHERWISE DIMENSIONED SHALL BE 8" FROM ADJACENT CMU OR
CONCRETE WALL TO ROUGH DOOR OPENING, AND 5" FROM FACE OF ADJACENT STUD
WALL TO ROUGH DOOR OPENING.
6. FINISH FLOOR ELEVATIONS ARE TO TOP OF CONCRETE SLAB UNLESS OTHERWISE
INDICATED.
7. PROVIDE BACKING/BLOCKING FOR THE ATTACHMENT OF MISCELLANEOUS ITEMS
INCLUDING, BUT NOT LIMITED TO: TOILET ACCESSORIES, DOOR HARDWARE,
ELECTRICAL DEVICES, GRAB BARS, CASEWORK, MILLWORK, AND LABORATORY
EQUIPMENT. SEE PARTITION DETAILS SHEET.
8. FOR CONSTRUCTION DETAILS NOT SHOWN, USE THE PRODUCT MANUFACTURER'S
WRITTEN INSTALLATION INSTRUCTIONS AND STANDARD DETAILS, IN STRICT
ACCORDANCE WITH THE PROJECT SPECIFICATION REQUIREMENTS AND DESIGN
INTENT.
9. PROVIDE ACCESS DOORS OF APPROPRIATE SIZE, TYPE AND FIRE RATING FOR ALL
CONCEALED ITEMS THAT REQUIRE ADJUSTMENT, MAINTENANCE, MONITORING, ETC.
COORDINATE LOCATIONS WITH ARCHITECT.
10. ENCLOSE DUCTS, PIPES, CONDUITS, AND OTHER UTILITIES IN FINISHED SPACES TO
MATCH ADJACENT FINISHES UNLESS INDICATED OTHERWISE. (FOR EXAMPLE DO NOT
LEAVE CONDUIT EXPOSED IN A ROOM THAT IS NOT A MECHANICAL ROOM, PROVIDE A
GYPSUM BOARD PARTITION ENCLOSURE TO CONCEAL.)
11. DO NOT SUPPORT/HANG ITEMS FROM ROOF DECK, SUPPORT FROM JOISTS OR
TRUSSES.
12. PROVIDE TERMITE TREATMENT UNDER NEW AND PATCHED CONCRETE SLABS ON
GRADE.
REFERENCE SYMBOLS (ALL DISCIPLINES) REFERENCE SYMBOLS (ARCHITECTURAL)
TYPICAL PHASING GRAPHICS
ABBREVIATIONS GENERAL NOTES
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:2
A
M MB
MB
03/14/2024
G001JMO
GENERAL NOTES, SYMBOL
LEGEND AND ABBREVIATIONS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
G001
SHELF/ MOP
HOLDER
SERVICE
FAUCET AND
CONTROLS
MOP BASIN
JANITOR CLOSETACCESSIBLE
URINAL
M A
X
WATER
CLOSET
PROVIDE
BLOCKING AS
REQUIRED
GRAB BAR
SINK/
LAVATORY
MIRROR AT
SINK/LAVATORY
T O
B O
T T
O M
O F
R
E F
L E
C T
IV
S
U R
F A
C E
TOILET PAPER DISPENSER
M
IN
SOAP OR
HAND SANITIZER
DISPENSER
PAPER TOWEL
DISPENSER
PLUMBING FIXTURES & ACCESSORIES NOTES:
1. VERIFY ALL PLACEMENT WITH PLAN, ELEVATION, AND
CURRENT CODES.
2. SEE SPECIFICATIONS FOR ACCESSORY MANUFACTURER
AND MODEL.
3. INSULATE ALL EXPOSED PIPES.
4. COORDINATE ALL FIXTURES WITH PLUMBING DRAWINGS
AND SPECIFICATIONS.
5. PROVIDE AND INSTALL NON-COMBUSTIBLE INTERNAL WALL
BLOCKING AS REQUIRED TO ACHIEVE SECURE ATTACHMENT
MEETING STRENGTH REQUIREMENTS OF APPLICABLE
CODES FOR ALL WALL MOUNTED ACCESSORIES.
6. ORIENT FLUSH LEVER AT TOILET TO THE OPEN SIDE OF THE
ROOM.
T O
D
IS
P E
N S
E R
O U
T L
T
(I N
S T
A L L A
T
IO
N
M
IN
A
B O
V E
G R
A B
B A
R
COAT
HOOK
S
T A
N D
A R
D
A
C C
E S
S
IB
L E
T O
T
P
F
B O
W L
T O
T O
P O
F R
E F
L E
C T
IV
S
R
F A
C E
" 3
FIRE
EXTINGUISHER
WALL HUNG
FIRE EXTINGUISHER
IN RECESSED
CABINET
M
A X
T O
S P
O
T L E
T
T O
S P
O
T L E
T
DRINKING FOUNTAINS
WITH BOTTLE FILLER
M
IN
M A
X
CANE
APRON
M
IN
C L E
A R
M
IN
11" MIN 6" MIN
8" MIN
2"
9"
EQ EQ
SHOWER AND
CONTROLS
SHOWER SEAT
M A
X
M
IN
WC1
ACCESSIBLE
WATER CLOSET
1'-6"
1'-0" 2'-0"
60" WIDE x 56"
DEEP CLEAR
FLOOR SPACE
WC2
WATER CLOSET
WALL OR TOILET
PARTITION WHERE
SHOWN IN PLAN
CENTER WC IN
ROOMS 36"
WIDE OR LESS
U1 ACCESSIBLE
URINAL
3'-0"
WALL OR TOILET
PARTITION WHERE
SHOWN IN PLAN
1'-6"
30" WIDE x 48"
DEEP CLEAR
FLOOR SPACE
30" WIDE x 48"
DEEP CLEAR
FLOOR SPACE
ACCESSIBLE
SINK
1'-6" HOLD
S1
GB36
GB42
TPD
SND
TPD
SND
SD
PTD
LOCATE
ACCESSORIES
IN FIELD WITH
OWNER
CH COAT HOOK
GBxx GRAB BAR (xx INDICATES LENGTH)
MIR MIRROR
PTD PAPER TOWEL DISPENSER
SCD SEAT COVER DISPENSER
SD SOAP DISPENSER
SHRS SHOWER SEAT
SND SANITARY NAPKIN DISPOSAL
TPD TOILET PAPER DISPENSER
TOILET ACCESSORIES ABBREVIATIONS:
SCD SCD
MIR
TLT1
ACCESSIBLE
TOILET ROOM
SEE PLANS
7'-6" MIN
S E
E P
L A
N S
REFER TO DRAWING S1 THIS
SHEET FOR ADDITIONAL
SINK DETAILS AND RELATED
TOILET ACCESSORIES
S1WC1
REFER TO DRAWING WC1 THIS
SHEET FOR ADDITIONAL
WATER CLOSET AND RELATED
TOILET ACCESSORIES DETAILS
NOTE THAT THIS IS A GENERIC
LAYOUT SHOWING FIXTURES,
ACCESSORIES, AND POSSIBLE
DOOR LOCATIONS. SEE FLOOR
PLANS FOR ACTUAL PLAN
LAYOUT WITH DIMENSIONS.
TOILET TYPE TLT1 - SEE
FLOOR PLANS FOR TOILET
TYPE DESIGNATIONS ON
DRAWING.
CLEAR FLOOR SPACE
REQUIREMENTS
SHOWN DASHED
TOILET ROOM AND ACCESSORY NOTES:
1. ENLARGED PLANS INDICATE DIMENSIONS, TOILET ACCESSORY LOCATIONS,
AND REQUIRED CLEARANCES TO BE MAINTAINED.
2. ENLARGED SINK TYPES (S1, S2, ETC) ARE KEYED ONTO ENLARGED FLOOR
PLANS.
3. REFER TO ENLARGED FLOOR PLAN SHEETS FOR EXACT TOILET ROOM
AND/OR FIXTURE ORIENTATION, DOOR LOCATION(S), ADJACENT WALL
CONSTRUCTION, AND ADDITIONAL EQUIPMENT ITEMS.
4. DIMENSIONS INDICATED HERE ARE TYPICAL, UNLESS DIMENSIONED
OTHERWISE ON FLOOR PLAN SHEETS OR INTERIOR ELEVATIONS.
5. DIMENSIONS SHOWN FOR ACCESSORIES AND EQUIPMENT ITEMS AND CLEAR
FLOOR SPACE ARE FROM FACE OF ROOM FINISH (SUCH AS TILE).
6. NOTE THAT DOORS CANNOT INFRINGE UPON OR SWING INTO THE REQUIRED
RECTANGULAR "CLEAR FLOOR SPACE" AREAS SHOWN ON ENLARGED PLANS.
7. PLUMBING FIXTURES SHOWN HERE ARE GENERIC - SEE PLUMBING
DRAWINGS FOR ACTUAL SCHEDULED FIXTURES.
8. ORIENT FLUSH LEVER AT TOILETS TO THE OPEN SIDE OF THE ROOM.
30" WIDE x 48"
DEEP CLEAR
FLOOR SPACE
48" WIDE x 30"
DEEP CLEAR
FLOOR SPACE
ACCESSIBLE
SINK
GENERIC SINK SHOWN HERE IN
COUNTERTOP. SEE PLUMBING
FIXTURE SCHEDULE FOR ACTUAL
FIXTURE TYPE.
S3
PTD
SD1
LOCATE
ACCESSORIES
IN FIELD WITH
OWNER
1'-6"
SEE
ELEVATION
4"
SHR3 ACCESSIBLE STANDARD ROLL-
IN TYPE SHOWER
60" WIDE x 30"
DEEP CLEAR
FLOOR SPACE
5'-0"
M
IN
IM
U
M
C
L E
A R
M
IN
CLEAR
5'-0"
CH 6"
CONTROLS
LOCATED 42" AFF
TO CENTERLINE
GB48GB24
2'-2"
EQ EQ
2'-8" MIN
18" MAX
TOILET PARTITIONURINAL
PARTITION
M
A X
2'-0" A
F F
WALL
BRACKET
DOOR
PILASTER
HEADRAIL
FBC-B 2020 1210.3.2
M
IN
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:2
A
M MB
MB
03/14/2024
G002JMO
TYPICAL TOILET ROOMS AND
MOUNTING HEIGHTS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
G002
SCALE B
ACCESSORIES & PLUMBING FIXTURES
SCALE B
TOILET ROOM TYPICALS
SCALE B
TOILET PARTITION TYPICAL ELEVATIONS
SCALE OF FEET
4 0 4 8
SCALE B
PULL
8" 8"7
AUDIO/VISUAL
FIRE ALARM
EXIT SIGN WALL
SWITCH
WALL
PHONE
JACK
FIRE ALARM
PULL STATION
(GENERALLY
LOCATE UNDER
A/V ALARM)
W
IT
H O
W N
E R
C O
O R
D
IN
A T
E
8"
COMBINATION
POWER/SIGNAL/OUTLET
FOR WALL MOUNTED
TELEVISION OR
MONITOR
T.V./DATA/
PHONE
POWER
RECEPTACLES
LIGHT
SWITCHES
DOME
LIGHT
OCCUPANCY
SENSOR
CARD
READER
THERMOSTAT
" 5
POWER
DISCONNECT
REMOTE DOOR
RELEASE
"5
NIGHT
LIGHT
TV
D/V
TV E
E
ED/V
L L OS CR T DRLD/V
AREA OF
REFUGE
INTERCOM
M
IN
C L
E A
R
LOCATE ROOM
IDENTIFICATION
SIGN ON LATCH
SIDE OF DOOR
D
IM
E N
S
IO
N S
S E
E C
O D
E S
IG
N
A G
A D
A D
E T
A
IL
S F
O R
9"
SIGN
MEN
CORRESPONDING GRADE II BRAILLE. 1/10"
WITHIN CELL. 2/10" BETWEEN CELLS, 1/40"
MIN. RAISE ABOVE THE BACKGROUND.
WALL MOUNTED SIGNAGE TO BE LOCATED ON LATCH SIDE OF DOOR, CLEAR OF DOOR SWING.
WOMEN
H
IG
H E
S T
L
IN
E O
F T
E X
T
M
A X
T O
B O
T T
O M
O F
O F
L O
W E
S T
L
IN
E O
F T
E X
T
M
IN
T O
B O
T T
O M
ROOM
NAME
NUMBER
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:2
A
M MB
MB
03/14/2024
G003JMO
TYPICAL MOUNTING HEIGHTS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
G003
SCALE B
ELECTRICAL CONTROL DEVICES
SCALE B
SPACE SIGNAGE
NO SCALE
CODE SIGNAGE ADA DETAILS
SCALE OF FEET
4 0 4 8
SCALE B
10. FIRE AND SMOKE PROTECTION FEATURES
2. AUTHORITIES HAVING JURISDICTION
12. MEANS OF EGRESS
MINIMUM NUMBER OF EXITS REQUIRED
IBC - 1017.2
IEBC - 804.4.1.1(2)
BUILDING - TABLE 1020.2
200 FEET
75 FEET
44 INCHES REQUIRED / 56 INCHES PROVIDED
NOT APPLICABLE
1 REQUIRED - 2 PROVIDED IEBC - 804.4.1.1(2)
MAXIMUM TRAVEL DISTANCE TO EXIT
MAXIMUM COMMON PATH OF TRAVEL
MINIMUM EGRESS WIDTH
CORRIDORS
STAIRS
BUILDING - SECTION 1008REQUIRED AND PROVIDEDEMERGENCY LIGHTING OF EGRESS
11. FIRE PROTECTION SYSTEMS
FIRE SPRINKLERS
IEBC - 803.3 AND IBC - 905.3
IBC - 906.1
IEBC - 803.4.1
NOT REQUIRED AND NOT PROVIDED
MINIMUM ABC AT 75' MAXIMUM TRAVEL DISTANCE
NOT REQUIRED AND NOT PROVIDED IEBC - 803.2 AND IBC - 903.2
STANDPIPES
PORTABLE FIRE EXTINGUISHERS
FIRE ALARM AND DETECTION NOT REQUIRED AND NOT PROVIDED
13. PLUMBING FIXTURES
NFPA 101, 39.2.6.2
NFPA 101, 39.2.5.3
NFPA 101, 7.3.4.1
200 FEET
75 FEET
2 REQUIRED - 2 PROVIDED NFPA 101, 39.2.4.1
NFPA 101, 39.2.9.1NOT REQUIRED AND PROVIDED
NFPA 101, 9.9 AND 39.3.5/NFPA 10
NFPA 101, 39.3.4 AND 40.3.4
MINIMUM ABC AT 75' MAXIMUM TRAVEL DISTANCE
NFPA 101, 39.3.5 AND 40.3.5
NOT REQUIRED AND NOT PROVIDED
NFPA 101, 39.3.5 AND 40.3.5
YES
BUILDING CODE AUTHORITY: NATIONAL PARK SERVICE
FIRE CODE AUTHORITY: NATIONAL PARK SERVICE
1. THE INTENDED USE OF THE BUILDING IS BASED ON INFORMATION FROM THE OWNER.
2. THE INTENDED USE OF THE BUILDING IS BUSINESS (B) AND FACTORY (F-1).
3. THE RENOVATION WORK AREA FOR THE PROJECT IS BUSINESS (B).
4. ALL DEMOLITION AND CONSTRUCTION INVOLVED TO COMPLETE THIS PROJECT SHALL CONFORM TO ALL
APPLICABLE CODES.
5. EXISTING RESTROOM PLUMBING FIXTURE COUNT IS BEING MAINTAINED. CHANGES TO LAYOUT ARE TO PROVIDE
ACCESSIBILITY. ONE (1) LAVATORY HAS BEEN ADDED TO THE ACCESSIBLE TOILET STALL. EXISTING WATER
CLOSET AND URINAL COUNT REMAIN UNCHANGED, AS PERMITTED BY IEBC - 808.
6. MEANS OF EGRESS REQUIREMENTS ARE LISTED FOR THE WORK AREA, PER IEBC - 804.1. EXISTING AREAS
OUTSIDE OF THE WORK AREA ARE TO REMAIN UNCHANGED, WHERE APPROVED BY THE AHJ.
3. APPLICABLE CODES & STANDARDS
ARCHITECTURAL
INTERNATIONAL BUILDING CODE (IBC) (2024)
INTERNATIONAL EXISTING BUILDING CODE (IEBC) (2024)
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (2015)
INTERNATIONAL ENERGY CONSERVATION CODE (IECC) (2021)
INTERNATIONAL FIRE CODE (IFC) (2024)
NFPA 101 (2024)
MECHANICAL / PLUMBING / ELECTRICAL
REFER TO EACH DISCIPLINE'S SHEETS FOR LIST OF APPLICABLE CODES
1. PROJECT SUMMARY
THE PROPOSED PROJECT IS LOCATED WITHIN AN EXISTING NON-SPRINKLERED ONE STORY 4,307 GROSS SQUARE FOOT BUILDING WITH A 997 GROSS SQUARE FOOT MECHANICAL MEZZANINE SPACE. THE PROJECT CONSISTS OF A LEVEL 2 ALTERATION TO 2,415 SQUARE FEET FOR BUSINESS USE. THE EXISTING BUILDING INCLUDES UNSEPARATED
MIXED OCCUPANCIES, BUSINESS (B) AND FACTORY (F-1).
4. CLASSIFICATION OF THE WORK
BUILDING CODE CLASSIFICATION OF THE WORK:
EXISTING BUILDING ALTERATION LEVEL 2 (IEBC CHAPTER 8): WORK AREA CONTAINING RECONFIGURED SPACE IS < 50%
OF BUILDING AREA (IEBC 603.1).
EXISTING BUILDING CODE REQUIREMENTS:
ALTERATION LEVEL 2 SHALL COMPLY WITH IEBC CHAPTERS 7 AND 8.
LIFE SAFETY CODE CLASSIFICATION OF THE WORK:
EXISTING BUSINESS OCCUPANCY SHALL COMPLY WITH NFPA 101, CHAPTER 39
INDUSTRIAL OCCUPANCIES SHALL COMPLY WITH NFPA 101, CHAPTER 40
BUILDING RENOVATION SHALL COMPLY WITH NFPA 101, CHAPTER 43.4
7. OCCUPANCY AND HAZARD OF CONTENTS CLASSIFICATION
BUILDING USE AND OCCUPANCY:
THE BUILDING CONTAINS MORE THAN 1 OCCUPANCY GROUP
THE BUILDING OCCUPANCIES ARE BUSINESS GROUP B AND FACTORY GROUP F-1 (IBC - 304.1 AND 306.2)
MIXED USE AND OCCUPANCY:
THE MULTIPLE BUILDING OCCUPANCIES ARE NON-SEPARATED OCCUPANCIES (IBC 508.3)
Multiple occupancies need not be separated when the most restrictive provision of area, height, and fire protection are applied for any relevant occupancies to the whole building. All other code provisions apply individually to each of the non-separated occupancies.
INTERNATIONAL BUILDING CODE
BUILDING USE AND OCCUPANCY:
THE BUILDING CONTAINS MORE THAN 1 OCCUPANCY GROUP
THE BUILDING OCCUPANCIES ARE EXISTING BUSINESS AND INDUSTRIAL (NFPA 101 6.1.11, 6.1.12, AND CHAPTERS 39 AND 40)
MIXED USE AND OCCUPANCY:
THE MULTIPLE BUILDING OCCUPANCIES ARE MIXED (NFPA 101 6.1.14.3)
Multiple occupancies need not be separated when the most restrictive requirements of the occupancies involved are applied. All other code provisions apply individually to each of the non-separated occupancies.
HAZARD OF CONTENTS:
THE CLASSIFICATION OF HAZARD OF CONTENTS IS ORDINARY HAZARD (NFPA 101 6.2)
NFPA 101 LIFE SAFETY CODE
8. TYPE OF CONSTRUCTION
THE TYPE OF CONSTRUCTION IS V-B (IBC - 602)
BUILDING ELEMENT HOURLY RATING
PRIMARY STRUCTURAL FRAME 0
BEARING WALLS, EXTERIOR SEE BELOW
BEARING WALLS, INTERIOR 0
NONBEARING WALLS, EXTERIOR SEE BELOW
NONBEARING WALLS, INTERIOR 0
FLOOR CONSTRUCTION 0
ROOF CONSTRUCTION 0
EXTERIOR WALLS (IBC - 705.5)
FIRE SEPARATION DISTANCE HOURLY RATING
X < 5' 1 (B) / 2 (F-1) 5' < X < 10' 1 (B) / 1 (F-1) 10' < X < 30' 0 (B) / 0 (F-1) X > 30' 0 (B) / 0 (F-1)
EXISTING FIRE SEPARATION DISTANCES
NORTH WALL > 10'
EAST WALL 5' < X < 10' (+/- 9'-0")
SOUTH WALL > 30'
WEST WALL > 30'
INTERNATIONAL BUILDING CODE
9. BUILDING HEIGHT AND AREA
BUILDING HEIGHT (504.3)
ALLOWABLE: 40' (B AND F)
ACTUAL: 24'-6" (UNCHANGED)
NUMBER OF STORIES ABOVE GRADE (504.4)
ALLOWABLE: 1 (F-1)
ACTUAL: 1 (UNCHANGED)
BUILDING AREA (506)
ALLOWABLE, UNDER ROOF PER FLOOR: 8,500 GSF (F-1)
ACTUAL, UNDER ROOF PER FLOOR: 4,307 GSF (UNCHANGED)
TOTAL BUILDING AREA, ALL FLOORS: 4,307 GSF (UNCHANGED)
INTERNATIONAL BUILDING CODE
REFERENCE PROJECT COMPLIES?NFPA 101REFERENCEIEBC AND IBC
NOT APPLICABLERAMPS, MEANS OF EGRESS
NOT APPLICABLERAMPS
YES
YES
YES
YES
YES
36 INCHES REQUIRED / 56 INCHES PROVIDED
MAXIMUM DEAD END CORRIDOR IEBC - 804.735 FEET NFPA 101, 39.2.5.250 FEET
NOT APPLICABLE
NOT REQUIRED AND NOT PROVIDED
NOT REQUIRED AND NOT PROVIDED
PROJECT COMPLIES?6. OCCUPANT LOAD CALCULATIONS
EXISTING EXTERIOR WALLS (IEBC CHAPTER 8)
NO SPECIAL REQUIREMENTS PER IEBC CHAPTER 8.
THE FIRE SEPARATION DISTANCE IS +/- 9'-0" AT THE EAST WALL. THIS CONDITION IS EXISTING AND UNCHANGED.
EXISTING EXTERIOR EAST WALL FIRE RESISTANCE RATING SHALL BE MAINTAINED.
EXISTING UNPROTECTED EXTERIOR OPENINGS SHALL REMAIN UNCHANGED.
FIRE WALLS (IEBC CHAPTER 8 AND IBC 706)
NO NEW OR EXISTING FIRE WALLS IN PROJECT.
FIRE BARRIERS (IEBC CHAPTER 8 AND IBC 707)
NO NEW OR EXISTING FIRE BARRIERS IN PROJECT.
FIRE PARTITIONS (IEBC CHAPTER 8 AND IBC 708)
CORRIDORS 0 HOUR - CORRIDOR SERVES LESS THAN 30 OCCUPANTS (IBC 1020.2)
SMOKE BARRIERS (IEBC CHAPTER 8 AND IBC 709)
NO NEW OR EXISTING SMOKE BARRIERS IN PROJECT.
SMOKE PARTITIONS (IEBC CHAPTER 8 AND IBC 710)
NO NEW OR EXISTING SMOKE PARTITIONS IN PROJECT.
FLOOR AND ROOF ASSEMBLIES (IEBC CHAPTER 8 AND IBC 711.3)
FIRE RESISTANCE RATED (YES/NO) NO
SUPPORTING CONSTRUCTION SEE SECTION 8 ABOVE
SEPARATED OCCUPANCIES NOT APPLICABLE
FIRE AREAS NOT APPLICABLE
SMOKE COMPARTMENTS NOT APPLICABLE
INCIDENTAL USES NOT APPLICABLE
VERTICAL OPENING ENCLOSURE (IEBC CHAPTER 8 AND IBC 712.1.11)
MEZZANINE NO ENCLOSURE REQUIRED (IEBC 802.2.1, EXCEPTION 3.1)
PENETRATIONS THROUGH RATED ASSEMBLIES (IEBC CHAPTER 8 AND IBC 714)
NOT APPLICABLE
FIRE RESISTANT JOINT SYSTEMS (IBC 715)
NOT APPLICABLE
FIRE CODE COMPARISON:
OCCUPANCY SEPARATION (101, TABLE 6.1.14.4.1b) PROJECT USES MIXED OCCUPANCIES PER 101, 6.1.14.3.2 (SAME AS BLDG CODE)
CORRIDORS (101, 39.3.6) NO REQUIREMENTS (SAME AS BLDG CODE)
VERTICAL OPENINGS - SHAFTS (101, 8.6.4 and 8.6.5) NOT APPLICABLE VERTICAL OPENINGS - MEZZANINE (101, 8.6.10) NO SEPARATION OR ENCLOSURE REQUIREMENTS (SAME AS BLDG CODE)
REFERENCE PROJECT COMPLIES?NFPA 101REFERENCEIEBC AND IBC
5. GENERAL PROJECT NOTES
1. CALCULATED OCCUPANT LOAD = 27.12 ROUNDED UP TO NEAREST WHOLE NUMBER = 28 OCCUPANTS
YES
YES
YES
YES
YES
YES
YES
NOT APPLICABLE
NOT APPLICABLE
FIXTURE PLUMBING CODE REQUIREMENT
WATER CLOSETS 1 PER 25 FOR THE FIRST 50 AND 1 PER 50 FOR THE REMAINDER
CONFIRMATION OF PROJECT COMPLIANCECALCULATION
14/25 = .56 = 1 PER SEX
LAVATORIES 1 PER 40 FOR THE FIRST 80 AND 1 PER 80 FOR THE REMAINDER 14/40 = .35 = 1 PER SEX
WATERCLOSETS: REQUIRED: 1 PER SEX
PROVIDED: UNISEX = 2 (1 WC + 1 URINAL)
LAVATORIES: REQUIRED: 1 PER SEX
PROVIDED: UNISEX = 2
DRINKING FOUNTAINS 1 PER 100 OCCUPANTS 28/100 = .28 = 1 REQUIRED
BUILDING OCCUPANT LOAD = 28 PERSONS
SERVICE SINK 1 REQUIRED IN BUILDING N/A
PROJECT CONDITION
COMPLIES?
FOUNTAINS: REQUIRED: .28 = 1
PROVIDED: 2 (1 HIGH + 1 LOW + 1 BOTTLE FILLERS)
28/2 = 14 PER SEX
YES
YES
YES
SHOWERS / BATHTUBS NOT REQUIRED N/A SHOWERS: REQUIRED: 0 PER SEX
PROVIDED: UNISEX = 1
YES
YESSERVICE SINKS: 1 EXISTING IN WOOD SHOP
(FIXTURE CALCULATIONS ARE BASED ON MOST RESTRICTIVE OCCUPANCY CRITERIA, BUSINESS (B). SEPARATE FACILITIES NOT REQUIRED PER IBC 403.2 EXCEPTION 6.)
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:2
A
M MB
MB
03/14/2024
G010JMO
CODE COMPLIANCE
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
G010
OCCUPANT LOAD SCHEDULE
LEVEL
FUNCTION OF SPACE (IBC
1004.5) AREA
OCCUPANT LOAD
FACTOR (IBC 1004.5)
OCCUPANT
LOAD
LEVEL 1 ACCESSORY EQUIPMENT 25 SF 300 SF 0.08
LEVEL 1 ACCESSORY MECHANICAL 106 SF 300 SF 0.35
LEVEL 1 ACCESSORY STORAGE 36 SF 300 SF 0.12
LEVEL 1 BUSINESS 2,070 SF 150 SF 13.80
LEVEL 1 INDUSTRIAL 1,277 SF 100 SF 12.77
3,512 SF 27.12
15. ENERGY EFFICIENCY - COMMERCIAL14. INTERIOR FINISHES
WALL AND CEILING FINISHES (IBC TABLE 803.13)
CLASS A = FLAME SPREAD 0-25, SMOKE DEVELOPED 0-450
CLASS B = FLAME SPREAD 26-75, SMOKE DEVELOPED 0-450
CLASS C = FLAME SPREAD 76-200, SMOKE DEVELOPED 0-450
GROUP: B
SPRINKLERED: NO
SPACE CLASS REQUIRED CLASS SPECIFIED
INTERIOR EXITS A A
CORRIDORS AND EXIT ACCESS B B
ROOMS AND SPACES C C
GROUP: F-1
NO NEW FINISHES IN THE F-1 AREA OF THE BUILDING.
CLIMATE ZONE: 3A
COMPLIANCE PATH: PERFORMANCE
OPAQUE THERMAL ENVELOPE ASSEMBLIES (C402.2, PRESCRIPTIVE)
ELEMENT REQUIRED PROVIDED
ROOF, INSULATION IN ATTIC NA* EXISTING TO REMAIN
WALLS, MASS NA* EXISTING TO REMAIN
WALLS, BELOW GRADE NA* EXISTING TO REMAIN
FLOORS, JOIST/FRAMING NA* EXISTING TO REMAIN
FLOORS, SLAB ON GRADE NA* EXISTING TO REMAIN
DOORS, OPAQUE NA* EXISTING TO REMAIN
* PROJECT FOLLOWS PERFORMANCE ENERGY MODEL PATH, NO PRESCRIPTIVE REQUIREMENT
FENESTRATION (C402.4, PRESCRIPTIVE)
ELEMENT REQUIRED PROVIDED
U-FACTOR
FIXED NA* 0.50
OPERABLE NA* 0.65
ENTRANCE DOORS NA* 0.83
SHGC
SOUTH, EAST, WEST NA* 0.25
NORTH NA* 0.33
SKYLIGHTS
U-FACTOR NA* NO SKYLIGHTS
SHGC NA* NO SKYLIGHTS
MAXIMUM AREA, VERTICAL NA*
MAXIMUM AREA, SKYLIGHTS NA*
* PROJECT FOLLOWS PERFORMANCE ENERGY MODEL PATH, NO PRESCRIPTIVE REQUIREMENT
FLOOR FINISHES (IBC 804.4.2)
CLASS I = MINIMUM CRITICAL RADIANT FLUX 0.45 WATTS/CM2
CLASS II = MINIMUM CRITICAL RADIANT FLUX 0.22 WATTS/CM2
GROUP: B
SPRINKLERED: NO
CLASS REQUIRED CLASS SPECIFIED
II II
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:2
A
M MB
MB
03/14/2024
G011JMO
CODE COMPLIANCE
NPS - NATCHEZ MAINTENANCE
G011
UP
TOTAL EXIT ACCESS TRAVEL DISTANCE
(Two distinct paths to exit available.)
Maximum: 200'
EGRESS WIDTH PROVIDED
(INCHES, xx")
EGRESS CAPACITY PROVIDED
(PERSONS)
EGRESS CAPACITY UTILIZED
(PERSONS)
COMMON PATH OF EGRESS
TRAVEL DISTANCE
(Portion of exit access travel distance prior to having two distinct paths to exit) Maximum: 100' (B), 75' (F-1)
GENERAL NOTE:
PROVIDE TACTILE EXIT SIGNAGE AT EACH REQUIRED EXIT DOOR.
CITATION REFERENCE: IBC (2021) 1013.4, & NFPA 101 (2018) 7.10.1.3.
PLAN LEGEND
FIRE EXTINGUISHER CABINET
(MOUNT WITH CENTER OF CABINET 36"
ABOVE FINISH FLOOR)
E
F.E.C.
LIGHTED EXIT SIGN WITH BATTERY BACK-UP
(SEE ELECTRICAL)
EXIT
D EXIT DISCHARGE
WALL-MOUNTED FIRE EXTINGUISHER
(MOUNT WITH TOP OF HANDLE 48"
ABOVE FINISH FLOOR)
0 0
F.E.
Distance: x'-x"
Total
Distance: x'-x"
Common
2,070 SF
BUSINESS
106 SF
ACCESSORY
MECHANICAL
AREA LEGEND
ACCESSORY EQUIPMENT
ACCESSORY MECHANICAL
ACCESSORY STORAGE
BUSINESS
INDUSTRIAL
1,277 SF
INDUSTRIAL
NO WORK THIS AREA
TRAINING
ROOM
OFFICE
OFFICE
CORRIDOR
C01
KITCHEN
LOCKERS
UNISEX
TOILET
TELECOM
TR01
Distance: 54' - 2"
Common
Distance: 79' - 11"
Common
F.E.
F .E
.C
F.E.
F.E.C.
EXISTING
EXISTING
33 165
33 165
33 165
E
E
25 SF
ACCESSORY
EQUIPMENT
36 SF
ACCESSORY
STORAGE
WOOD SHOP
SCALE AG101
2 LEVEL 1 LIFE SAFETY PLAN
OCCUPANT LOAD SCHEDULE
LEVEL
FUNCTION OF SPACE (IBC
1004.5) AREA
OCCUPANT LOAD
FACTOR (IBC 1004.5)
OCCUPANT
LOAD
LEVEL 1 ACCESSORY EQUIPMENT 25 SF 300 SF 0.08
LEVEL 1 ACCESSORY MECHANICAL 106 SF 300 SF 0.35
LEVEL 1 ACCESSORY STORAGE 36 SF 300 SF 0.12
LEVEL 1 BUSINESS 2,070 SF 150 SF 13.80
LEVEL 1 INDUSTRIAL 1,277 SF 100 SF 12.77
3,512 SF 27.12
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:2
A
M MB
MB
03/14/2024
G101JMO
LIFE SAFETY PLAN
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
G101
SCALE A 8 0 8 16
1/8" = 1'-0"
DEMOLITION PLAN SHEET NOTES
1. REFER TO DEMOLITION DOCUMENTS FROM ALL DISCIPLINES.
2. REFER TO SPECIFICATIONS FOR ADDITIONAL DEMOLITION REQUIREMENTS.
3. COORDINATE DEMOLITION WORK AND REQUIRED SHUTDOWNS WITH OWNER,
PROVIDE 72 HOURS NOTIFICATION MINIMUM.
4. PROVIDE CONSTRUCTION BARRIERS PRIOR TO DEMOLITION. COORDINATE WITH
OWNER AND ARCHITECT.
5. RESTORE ANY DISTURBANCE OR DAMAGE TO EXISTING FACILITY UTILITIES
RESULTING DIRECTLY OR INDIRECTLY FROM THE OPERATION OF THIS CONTRACT.
6. MAINTAIN ACCESS TO AND FROM EXISTING EMERGENCY EGRESSES AND FIRE LANES.
7. COORDINATE MATERIAL AND EQUIPMENT SALVAGE WITH OWNER. DISPOSE OF
REMAINING MATERIAL AND EQUIPMENT.
8. PRIOR TO BID, VISIT THE SITE TO SURVEY THE EXTENT OF REMOVAL REQUIRED.
9. CONDUCT EXPLORATORY INVESTIGATION INTO AREAS SCHEDULED FOR DEMOLITION
PRIOR TO REMOVAL AND CONTACT OWNER AND ARCHITECT IMMEDIATELY IF
HAZARDOUS MATERIALS ARE UNCOVERED.
10. REMOVE ELEMENTS AS INDICATED. TYPICAL WALL REMOVAL INCLUDES FINISHES AND
MECHANICAL, PLUMBING, AND ELECTRICAL SYSTEMS WITHIN THE WALL. REMOVE
DOORS, CASEWORK, WINDOWS, FRAMES, AND FIXTURES. REMOVE MECHANICAL,
ELECTRICAL, AND PLUMBING ELEMENTS INDICATED.
11. PATCH EXISTING SURFACES WHERE ELEMENTS ARE REMOVED AND NEW FINISHES
ARE REQUIRED.
12. CUT AND PATCH EXISTING WALLS AS REQUIRED TO INSTALL NEW MECHANICAL,
ELECTRICAL, AND PLUMBING ELEMENTS INDICATED.
13. CUT AND PATCH EXISTING FLOORS AS REQUIRED TO INSTALL NEW MECHANICAL,
ELECTRICAL, AND PLUMBING ELEMENTS INDICATED.
14. TREATMENT OF EXISTING FLOORS AND WALL BASE:
A. REMOVE EXISTING FINISH FLOORING AND WALL BASE IN AREAS SHOWN TO
RECEIVE NEW FINISH FLOORING AND WALL BALL BASE.
B. PATCH AND FLOAT EXISTING FLOORS LEVEL TO RECEIVE NEW FINISH
15. TREATMENT OF EXISTING WALLS AND CEILINGS:
A. REMOVE EXISTING SIGNS, VISUAL DISPLAY BOARDS, WALL COVERINGS, AND
OTHER ITEMS AND FINISHES ATTACHED TO EXISTING TO REMAIN SURFACES.
B. PREPARE SURFACES TO RECEIVE NEW FINISH INDICATED
16. OWNER SALVAGE RIGHTS: REFER ALSO TO DEMOLITION SPECIFICATION. PRIOR TO
THE START OF DEMOLITION CONDUCT A MEETING WITH THE OWNER TO IDENTIFY
ELEMENTS TO REMOVE AND SALVAGE. ELEMENTS TO SALVAGE INCLUDE:
A. FIXTURES
B. FURNISHINGS
C. OFFICE EQUIPMENT
D. APPLIANCES
LEVEL 1
0"
ROOF
12'-0"
D01
D02D02
D10
D11
D11
D12
D13
D11 D11
LEVEL 1
0"
ROOF
12'-0"
D10
D11
D11
AD101
AD101
NO WORK THIS AREA
AD101
AD101
D01
D06
D03 D04
D03 D04
D03 D04
D03 D04
D03
D04
D03
D04
D03
D04
D05
D07
D08
D01
D02D02
LEVEL 1
0"
ROOF
12'-0"
D11
D11
D12
LEVEL 1
0"
ROOF
12'-0"
D11
D11
D12
KEYNOTE LEGEND
D01 REMOVE OVERHEAD DOOR AND METAL PERIMETER FRAME
COMPLETE.
D02 REMOVE PIPE BOLLARD.
D03 REMOVE FLOORING, WALL BASE COMPLETE.
D04 REMOVE CEILING AND FIXTURES COMPLETE.
D05 REMOVE WATER COOLER AND BOTTLE FILLER.
D06 REMOVE CABINETS COMPLETE.
D07 REMOVE TOILET FIXTURES AND ACCESSORIES.
D08 REMOVE SLAB AS REQUIRED FOR DEMO AND INSTALL OF
UNDERSLAB PIPING. AREA SHOWN SHADED.
D10 REMOVE ROOFING TO EXPOSE DECK. REPLACE DAMAGED
ROOF DECK IN KIND.
D11 REMOVE ROOF EDGE TRIM, FASCIA AND SUBFASCIA,
SOFFITS, BIRD BOXES, GUTTERS AND DOWNSPOUTS.
D12 REMOVE WOOD TRIM AT PORCH SOFFIT.
D13 REMOVE WOOD SIDING AT PORCH GABLE. REMOVE
WEATHER BARRIER TO EXPOSE SHEATHING. REPLACE
DAMAGED SHEATHING IN KIND.
SCALE AAD101
2 DEMO SOUTH ELEVATION
SCALE AAD101
4 DEMO NORTH ELEVATION
SCALE AAD101
1 LEVEL 1 DEMOLITION PLAN
SCALE AAD101
3 DEMO WEST ELEVATION
SCALE AAD101
5 DEMO EAST ELEVATION
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:2
A
M MB
MB
03/14/2024
AD101JMO
DEMOLITION PLAN AND
ELEVATIONS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
AD101
NO WORK THIS AREA
D11
D11
D12
D04
D04
D04
D04
D04
D04
D04
DEMOLITION PLAN SHEET NOTES
1. REFER TO DEMOLITION DOCUMENTS FROM ALL DISCIPLINES.
2. REFER TO SPECIFICATIONS FOR ADDITIONAL DEMOLITION REQUIREMENTS.
3. COORDINATE DEMOLITION WORK AND REQUIRED SHUTDOWNS WITH OWNER,
PROVIDE 72 HOURS NOTIFICATION MINIMUM.
4. PROVIDE CONSTRUCTION BARRIERS PRIOR TO DEMOLITION. COORDINATE WITH
OWNER AND ARCHITECT.
5. RESTORE ANY DISTURBANCE OR DAMAGE TO EXISTING FACILITY UTILITIES
RESULTING DIRECTLY OR INDIRECTLY FROM THE OPERATION OF THIS CONTRACT.
6. MAINTAIN ACCESS TO AND FROM EXISTING EMERGENCY EGRESSES AND FIRE LANES.
7. COORDINATE MATERIAL AND EQUIPMENT SALVAGE WITH OWNER. DISPOSE OF
REMAINING MATERIAL AND EQUIPMENT.
8. PRIOR TO BID, VISIT THE SITE TO SURVEY THE EXTENT OF REMOVAL REQUIRED.
9. CONDUCT EXPLORATORY INVESTIGATION INTO AREAS SCHEDULED FOR DEMOLITION
PRIOR TO REMOVAL AND CONTACT OWNER AND ARCHITECT IMMEDIATELY IF
HAZARDOUS MATERIALS ARE UNCOVERED.
10. REMOVE ELEMENTS AS INDICATED. TYPICAL WALL REMOVAL INCLUDES FINISHES AND
MECHANICAL, PLUMBING, AND ELECTRICAL SYSTEMS WITHIN THE WALL. REMOVE
DOORS, CASEWORK, WINDOWS, FRAMES, AND FIXTURES. REMOVE MECHANICAL,
ELECTRICAL, AND PLUMBING ELEMENTS INDICATED.
11. PATCH EXISTING SURFACES WHERE ELEMENTS ARE REMOVED AND NEW FINISHES
ARE REQUIRED.
12. CUT AND PATCH EXISTING WALLS AS REQUIRED TO INSTALL NEW MECHANICAL,
ELECTRICAL, AND PLUMBING ELEMENTS INDICATED.
13. CUT AND PATCH EXISTING FLOORS AS REQUIRED TO INSTALL NEW MECHANICAL,
ELECTRICAL, AND PLUMBING ELEMENTS INDICATED.
14. TREATMENT OF EXISTING FLOORS AND WALL BASE:
A. REMOVE EXISTING FINISH FLOORING AND WALL BASE IN AREAS SHOWN TO
RECEIVE NEW FINISH FLOORING AND WALL BALL BASE.
B. PATCH AND FLOAT EXISTING FLOORS LEVEL TO RECEIVE NEW FINISH
15. TREATMENT OF EXISTING WALLS AND CEILINGS:
A. REMOVE EXISTING SIGNS, VISUAL DISPLAY BOARDS, WALL COVERINGS, AND
OTHER ITEMS AND FINISHES ATTACHED TO EXISTING TO REMAIN SURFACES.
B. PREPARE SURFACES TO RECEIVE NEW FINISH INDICATED
16. OWNER SALVAGE RIGHTS: REFER ALSO TO DEMOLITION SPECIFICATION. PRIOR TO
THE START OF DEMOLITION CONDUCT A MEETING WITH THE OWNER TO IDENTIFY
ELEMENTS TO REMOVE AND SALVAGE. ELEMENTS TO SALVAGE INCLUDE:
A. FIXTURES
B. FURNISHINGS
C. OFFICE EQUIPMENT
D. APPLIANCES
D04
N O
W O
R K
T H
IS
A
R E
A
REMOVE LOW
GUARD WALL
SCALE AAD121
1 LEVEL 1 DEMOLITION CEILING PLAN
KEYNOTE LEGEND
D04 REMOVE CEILING AND FIXTURES COMPLETE.
D11 REMOVE ROOF EDGE TRIM, FASCIA AND SUBFASCIA, SOFFITS, BIRD BOXES,
GUTTERS AND DOWNSPOUTS.
D12 REMOVE WOOD TRIM AT PORCH SOFFIT.
SCALE AAD121
2 MEZZANINE DEMOLITION PLAN
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:2
A
M MB
MB
03/14/2024
AD121JMO
CEILING DEMOLITION PLAN
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
AD121
FLOOR PLAN SHEET NOTES
1. PROVIDE CONCRETE SPLASH BLOCKS AT ALL
DOWNSPOUTS.
A210
A210
OFFICE
OFFICE
TRAINING
ROOM
TELECOM
TR01
PANTRY
A101
A101
A101
A101
KITCHEN
LOCKERS
106UNISEX TOILET
NO WORK THIS AREA
WASHER
A300
LED MONITOR LED MONITOR
NEW STOREFRONT
WINDOWS, SILLS
AND CMU INFILL
A210
A210
NEW CONCRETE PAD
NEW SILLNEW SILL
NEW SILL
NEW SILL NEW SILL
LEVEL 1
0"
ROOF
12'-0"
A210
A210
A03
A04
A01
A02
A04
A05
A06PAINT DOOR
AND FRAME
A06
PRESSURE WASH EXTERIOR CMU AND
APPLY CLEAR WATER REPELLENT TO
NEW AND EXISTING CMU CONSTRUCTION,
TYP. ALL SIDES OF BUILDING
ALL NEW CEMENTITOUS SIDING,
PANELING AND TRIM SHALL BE BY
JAMES HARDIE INDUSTRIES, OR EQUAL
STRIP, REPAIR AND REPAINT ALL
EXISTING EXTERIOR ATTIC LOUVERS
LEVEL 1
0"
ROOF
12'-0"
A210
A210
A03
A04
A04
PROVIDE BACKER ROD AND
SEALANT AROUND EVERY EXTERIOR
WALL PENETRATION, TYP.
LEVEL 1
0"
ROOF
12'-0"
A03
A04
A04
A02
PAINT DOOR
AND FRAME2
A210
A210
LEVEL 1
0"
ROOF
12'-0"
A04
A03
A04
A02
PAINT DOOR
AND FRAME 2
A210
A210
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:2
A
M MB
MB
03/14/2024
A101JMO
FLOOR PLAN AND ELEVATIONS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
A101
KEYNOTE LEGEND
A01 NEW CEMENTITIOUS PLANK SIDING ON NEW
WEATHER BARRIER.
A02 NEW CEMENTITIOUS TRIM AND PANEL AT
SOFFIT.
A03 NEW ROOFING ON NEW UNDERLAYMENT.
A04 NEW ROOF EDGE TRIM, FASCIA AND
SUBFASCIA, SOFFITS, BIRD BOXES, GUTTERS
AND DOWNSPOUTS.
A05 NEW ALUMINUM STOREFRONT WINDOWS.
A06 NEW CMU INFILL TO MATCH EXISTING.
SCALE AA101
1 LEVEL 1 FLOOR PLAN
SCALE AA101
2 SOUTH ELEVATION - NEW WORK
SCALE AA101
4 NORTH ELEVATION - NEW WORK
SCALE AA101
3 WEST ELEVATION - NEW WORK
SCALE AA101
5 EAST ELEVATION - NEW WORK
A3D
C2DC2D
C2D
C2D
A300
TRAINING
ROOM
OFFICE
NO WORK THIS AREA
.1
.1
.1
T R
.1
108.2
101.1
UNISEX TOILET
LOCKERS
KITCHEN
OFFICE
CORRIDOR
C01
TELECOM
TR01
ELECTRICAL
ROOM
WOOD SHOP
WASHER
107.1
108.1
C01.1
PANTRY
109.1
110.1
C2D
C2D
A3D
/8
ALIGN
21'-0" 31'-0"
SF01SF01SF01SF01
+/-5'-4"
8"
4'-0" 1'-4" 4'-0"
8"
2'-0" 4'-0" 1'-4" 4'-0" 1'-4"
4'-4" 5'-7"
/8
EQ EQ
PATCH EXISTING
CONCRETE FLOOR SLAB
WHERE REQUIRED TO
MAKE PLUMBING
MODIFICATIONS. SEE
DETAIL 3/A121
PARTITION PLAN SHEET NOTES
1. PROVIDE IN WALL BACKING FOR WALL MOUNTED ITEMS.
2. PARTITIONS NOT DIMENSIONED ARE GENERALLY LOCATED BY ONE OF
THE FOLLOWING CRITERIA:
A. CENTERLINE - CENTER OF PARTITION ALIGNS WITH A STRUCTURAL
GRIDLINE OR OBJECT CENTERLINE (SUCH AS WINDOW MULLION OR
COLUMN).
B. ALIGN - LOCATE PARTITION FLUSH WITH FACE OF GYPSUM BOARD OR
OTHER SURFACE INDICATED
C. MAINTAIN DIMENSIONS NOTED AS "MINIMUM" OR "CLEAR"
3. PROVIDE MINIMUM 1'-0" CLEAR AT PUSH SIDES OF DOORS AND 1'-6"
CLEAR AT PULL SIDES OF DOORS UNLESS INDICATED OTHERWISE.
4. MOUNT SINKS AND LAVATORIES WITH A MINIMUM OF 1'-3" FROM THE
CENTERLINE OF THE FIXTURE TO THE FINISH SURFACE OF ADJACENT
WALLS.
5. WHERE NEW PARTITIONS EXTEND OR ABUT EXISTING PARTITIONS, ALIGN
THE FINISH FACE OF THE NEW PARTITION WITH THE EXISTING PARTITION
AND PROVIDE A TRANSITION WITHOUT VISIBLE SEAMS OR JOINTS.
A210
A210
997 SF
MECHANICAL
MEZZANINE
N O
W O
R K
T H
IS
A
R E
A
A3D
A210
A210
PATCH EXISTING
PLYWOOD FLOOR IN
KIND FOR SOLID
FLOOR DECK
CONCRETE WITH 6X6-
W2.9XW2.9 WWR ON
VAPOR RETARDER ON
COMPACTED FILL
#3 X 2'-0" AT 24"OC
DRILL AND ADHESIVE
INTO EXISTING SLAB
WITH 6" EMBED
EXISTING CONCRETE
SLAB ON GRADE
VAPOR RETARDER, 6" LAP
SCALE AA121
1 LEVEL 1 PARTITION PLAN
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:3
A
M MB
MB
03/14/2024
A121JMO
PARTITION PLANS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
A121
SCALE AA121
2 MEZZANINE PARTITION PLAN
SCALE EA121
3 CONCRETE SLAB PATCH DETAIL
SCALE A 8 0 8 16
1/8" = 1'-0"
SCALE E 1 0 1
1 1/2" = 1'-0"
CEILING PLAN SHEET NOTES
1. CEILING ELEMENTS (LIGHTS, GRILLS, ETC...) SHOWN FOR LOCATION AND
COORDINATION.
2. COORDINATE LOCATION, SIZE, AND REQUIREMENTS OF CEILING ELEMENTS WITH
M/E/P/F DOCUMENTS.
3. SUSPENDED TILE CEILING GRIDS SHALL BE SET WITH EITHER A FULL TILE OR A
GRID INTERSECTION OCCURRING AT THE CENTER OF THE CEILING EXPANSE SO
AS TO ACHIEVE TILES OF EQUAL WIDTH AT OPPOSING SIDES OF THE CEILING. NO
CEILING GRID CONFIGURATION SHALL RESULT IN A TILE AT ANY PERIMETER
EDGE OF LESS THAN 4 INCHES IN WIDTH.
4. IMMEDIATELY BRING DISCREPANCIES TO THE ARCHITECT'S ATTENTION.
5. IN ACOUSTICAL PANEL CEILINGS, CENTER CEILING ELEMENTS IN PANELS.
6. IN GYPSUM WALL BOARD CEILINGS ALIGN CEILING ELEMENTS WITH ADJACENT
CEILING ELEMENTS.
7. PROVIDE ACCESS PANELS IN NON-ACCESSIBLE CEILINGS (SUCH AS GYPSUM
BOARD) WHERE REQUIRED FOR ACCESS TO SERVICEABLE MECHANICAL,
ELECTRICAL, OR PLUMBING DEVICES. PROVIDE COORDINATED ACCESS PANEL
LOCATION SHOP DRAWING FOR REVIEW AND APPROVAL BY ARCHITECT PRIOR
TO INSTALLATION.
CEILING TAG HEIGHT AFF
2'x4' & 2'x2'
RECESSED
LIGHT FIXTURE
CEILING LEGEND
2'x2' CEILING GRID
GWB CEILING
RECESSED
DOWNLIGHTS
HVAC
TERMINALS
SUPPLY RETURN EXHAUST
CEILING FINISHAPC-1
9'-0"
A210
A210
NO WORK THIS AREA
APC1
7'-6"
APC1
7'-6"
GWB
7'-11 3/8"
APC1
7'-6"
APC1
7'-6" APC1
10'-4"
APC1
11'-8"
A210
A210
E Q
E Q
2'-6"
PROVIDE GWB CEILING ACCESS
PANEL TO SERVICE DAMPER
PAINT EXTERIOR SOFFIT
SCALE AA131
1 LEVEL 1 CEILING PLAN
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:3
A
M MB
MB
03/14/2024
A131JMO
CEILING PLAN
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
A131
ROOF PLAN SHEET NOTES
1. COORDINATE ALL EQUIPMENT SHOWN ON THE ROOF PLAN WITH
CONSTRUCTION DOCUMENTS ASSOCIATED WITH THEIR RESPECTIVE
DISCIPLINES.
A210
A210
A240
A240
A240
A240
A03
A03
A03 A04
A04
A210
A210
ALT. NO. 02
ALT. NO. 02
ALT. NO. 02
ALT. NO. 02
ALT. NO. 02
A240
A141
A141
A141
A141
A141
A240
A240
A240
A241
A241
1 x CEMENT FIBER TRIM
1 x 3 CEMENT FIBER TRIM
1 x 6 CEMENT FIBER TRIM
P.T. 2 x 8 WOOD SUBFASCIA
P.T. 1 x 4 WOOD SUBFASCIA
METAL CLEAT AND DRIP EDGE
FLASHING
ROOF SHINGLES ON SELF-
ADHERED SHEET
WATERPROOFING MEMBRANE ON
SHEATHING
SELF-ADHERED SHEET
WATERPROOFING MEMBRANE
STRIP FLASHING
METAL PANEL SOFFIT
5/4 x 8 CEMENT FIBER TRIM
SEALANT
CEMENT FIBER SIDING
AIR BARRIER
EXISTING SHEATHING
EXISTING GABLE END FRAMING
/4
ASPHALT SHINGLE ROOF W/ WOVEN
VALLEY SHINGLES
SELF-ADHERING UNDERLAYMENT
PREFORMED VALLEY FLASHING,
PER MANUFACTURER
BITUMINOUS SEALANT
FASTENER PER
MANUFACTURER
UNDERLAYMENT STRIPPING PLY
SET TOP SHINGLE TAB IN
BITUMINOUS SEALANT BED
MANUFACTURER
PER ROOFING
RIDGE VENT FASTENED TO ROOF
SHEATHING
CONTINUOUS RIDGE BLOCKING
FULLY ADHERED SHINGLE CAP
ASPHALT SHINGLE ROOFING ON
SELF-ADHERED UNDERLAYMENT
KEYNOTE LEGEND
A03 NEW ROOFING ON NEW UNDERLAYMENT.
A04 NEW ROOF EDGE TRIM, FASCIA AND SUBFASCIA, SOFFITS, BIRD BOXES,
GUTTERS AND DOWNSPOUTS.
SCALE AA141
1 ROOF PLAN
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:3
A
M MB
MB
03/14/2024
A141JMO
ROOF PLAN
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
A141
SCALE FA141
2 DETAIL - ROOF GABLE AT TRUSS (SHINGLES)
SCALE A 8 0 8 16
1/8" = 1'-0"
SCALE F 0 1
3" = 1'-0"
SCALE FA141
3 DETAIL - ROOF VALLEY
SCALE FA141
4 DETAIL - ROOF VENTED RIDGE
FINISH PLAN SHEET NOTES
1. AREAS SHOWN IN ROOM IDENTIFICATION TAGS ARE FOR ESTIMATING
PURPOSES ONLY. CONTRACTOR SHALL PERFORM THEIR OWN MATERIAL TAKE-
OFFS. DO NOT USE THESE AREAS FOR BIDDING.
2. REFER TO CUTTING AND PATCHING SPECIFICATION. MATCH, PATCH, AND
EXTEND EXISTING FINISHES TO PROVIDE SEAMLESS TRANSITION BETWEEN
NEW AND EXISTING.
3. PAINT ALL WALL SURFACES, DOOR FRAMES, SOFFITS, AND CEILINGS UNLESS
OTHERWISE INDICATED.
4. PAINT ALL MECHANICAL AND ELECTRICAL EQUIPMENT EXPOSED IN FINISHED
SPACES UNLESS OTHERWISE INDICATED.
5. PAINT AND COATING APPLICATION SUMMARY (MATCH SHEEN AND PAINT
PRODUCT TO SPEC)
A. INTERIOR GYPSUM BOARD WALLS, TYPICAL - I-OP (EGGSHELL LATEX)
B. INTERIOR GYPSUM BOARD CEILINGS, TYPICAL - I-OP (FLAT LATEX)
C. INTERIOR WOOD, OPAQUE - I-OP-MD-DT (SEMI-GLOSS ACRYLIC)
D. INTERIOR METALS - I-OP-MD-DT (SEMI-GLOSS ACRYLIC)
E. INTERIOR MEDIUM DUTY WALLS AND CEILINGS - I-OP-MD-WC (EGGSHELL
EPOXY). USE AT:
a. TOILET ROOMS
b. KITCHENS
F. INTERIOR LIGHT INDUSTRIAL COATINGS, WHERE INDICATED TO RECEIVE
EPOXY PAINT - SEE SPECIFICATION
G. EXTERIOR WOOD - E-OP (LATEX, SHEEN AS SPECIFIED)
H. EXTERIOR STEEL - ME-OP-3A (GLOSS ALKYD)
I. EXTERIOR GALVANIZED STEEL - MgE-OP-3A (GLOSS ALKYD)
6. REFER TO SHEET A300 FOR TYPICAL FINISH TRANSITION DETAILS.
7. THE TRANSITION OF DIFFERENT FLOORING MATERIALS AT A DOORWAY SHALL
OCCUR AT THE CENTERLINE OF DOOR UNLESS OTHERWISE INDICATED.
8. INSTALL FLOORING WALL TO WALL IN ROOMS INDICATED TO RECEIVE NEW
FLOORING. EXTEND BENEATH CASEWORK UNLESS OTHERWISE INDICATED.
CODE FINISH
APC ACOUSTIC PANEL CEILING
CG CORNER GUARD
CPT CARPET TILE
P PAINT
L HIGH PRESSURE LAMINATE
RB RESILIENT BASE
RF RESILIENT FLOORING
SCONC SEALED CONCRETE
SSM SOLID SURFACE MATERIAL
T TILE
WD WOOD
WS WINDOW SHADE
FINISH ABBREVIATIONS AND CODES
NO WORK THIS AREA
FLOOR:
BASE:
WALL:
1,071 SF
TRAINING
ROOM
CPT1
RB1
P1
FLOOR:
BASE:
WALL:
157 SF
OFFICE
CPT1
RB1
P1
FLOOR:
BASE:
WALL:
151 SF
OFFICE
CPT1
RB1
P1
FLOOR:
BASE:
WALL:
79 SF
LOCKERS
T1
T2
T2
FLOOR:
BASE:
WALL:
117 SF
UNISEX
TOILET
T1
T2
T2
FLOOR:
BASE:
WALL:
14 SF
WASHER
RF1
RB1
P1
FLOOR:
BASE:
WALL:
167 SF
KITCHEN
RF1
RB1
P1
FLOOR:
BASE:
WALL:
243 SF
CORRIDOR
C01
RF1
RB1
P1
FLOOR:
BASE:
WALL:
23 SF
TELECOM
TR01
RF1
RB1
P1
FLOOR:
BASE:
WALL:
109 SF
ELECTRICAL
ROOM
EXISTING
EXISTING
EXISTING
FLOOR:
BASE:
WALL:
16 SF
PANTRY
RF1
RB1
P1
T3 SHOWER FLOOR TILE
CPT2 WALK-OFF
CARPET TILE
CG1
CG1
SCALE AA161
1 LEVEL 1 FINISH PLAN
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:3
A
M MB
MB
03/14/2024
A161JMO
FINISH PLAN
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
A161
LEVEL 1
0"
MEZZANINE
9'-4"
ROOF
12'-0"
A210
A210
INSTALL OPAQUE FILM
AT EXISTING WINDOW
LEVEL 1
0"
MEZZANINE
9'-4"
ROOF
12'-0"
A210
A210
MECHANICAL
MEZZANINE
OFFICE
CORRIDOR
C01
KITCHEN
OFFICE
TRAINING
ROOM
CEILING
CEILING
NO WORK THIS AREA
NEW BATT INSULATION
AT BOTTOM OF
TRUSSES
PARTITION TO CLOSE
OFF FLOOR OF
MEZZANINE TO
BOTTOM OF TRUSSES
NEW GYPSUM BOARD
AT UNDERSIDE OF
TRUSS
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:3
A
M MB
MB
03/14/2024
A210JMO
BUILDING SECTIONS AND
PERSPECTIVES
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
A210
SCALE BA210
1 BUILDING SECTION
SCALE BA210
2 BUILDING SECTION
SCALE B 4 0 4 8
1/4" = 1'-0"
/4
ALT. NO. 02: REPLACE
DAMAGED SHEATHING IN KIND
5"
ALT. NO. 02: 1 x 4 CEMENT
FIBER TRIM
ALT. NO. 02: 1 x 2 CEMENT
FIBER TRIM
ALT. NO. 02: 1 x 6 CEMENT
FIBER TRIM
ALT. NO. 02: P.T. 2 x 8 WOOD
SUBFASCIA
ALT. NO. 02: P.T. 1 x 4 WOOD
SUBFASCIA
ALT. NO. 02: METAL DRIP CLEAT
AND EDGE FLASHING
ALT. NO. 02: ROOF SHINGLES ON
SELF-ADHERED SHEET
WATERPROOFING ON SHEATHING
ALT. NO. 02: SELF-ADHERED
SHEET WATERPROOFING STRIP
FLASHING
ALT. NO. 02: METAL GUTTER
ALT. NO. 02: METAL GUTTER
SUPPORT STRAPS
ALT. NO. 02: 1 x CEMENT FIBER TRIM
ALT. NO. 02: VENTED METAL PANEL SOFFIT
EXISTING FRAMING
EXISTING CMU WALL
SEE PARTITION PLAN FOR
FURRED WALL TYPE
BATT INSULATION
M
IN
.2
INSULATION BAFFLES
BETWEEN TRUSSES
CEILING
GWB LID
ALT. NO. 02: 1 x CEMENT FIBER TRIM
ALT. NO. 02: 1 x 3 CEMENT FIBER TRIM
ALT. NO. 02: 1 x 6 CEMENT FIBER TRIM
ALT. NO. 02: P.T. 2 x 8 WOOD SUBFASCIA
ALT. NO. 02: P.T. 1 x 4 WOOD SUBFASCIA
ALT. NO. 02: METAL DRIP
CLEAT AND EDGE FLASHING
ALT. NO. 02: ROOF SHINGLES ON
SELF-ADHERED SHEET
WATERPROOFING MEMBRANE ON
SHEATHING
ALT. NO. 02: SELF-ADHERED
SHEET WATERPROOFING
MEMBRANE STRIP FLASHING
ALT. NO. 02:
VENTED METAL
PANEL SOFFIT
/4
EXISTING CMU WALL
EXISTING FRAMING
ALT. NO. 02: ROOF SHINGLES ON
SELF-ADHERED SHEET
WATERPROOFING ON SHEATHING
ALT. NO. 02: SELF-ADHERED
SHEET UNDERLAYMENT
EXISTING FRAMING
STRIPPING PLY
4 POUND LEAD PIPE
FLASHING
LEAD FLANGE, PRIME AND
SET IN MASTIC
ROOFING SEALANT
M
IN
NON-COMBUSTIBLE
SPRAY-FOAM INSULATION
M
IN
SCALE FA240
1 DETAIL - ROOF EAVE
SCALE FA240
2 DETAIL - ROOF GABLE AT CMU
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:3
A
M MB
MB
03/14/2024
A240JMO
ROOF DETAILS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
A240
SCALE FA240
3 DETAIL - ROOF VTR
SCALE F 0 1
3" = 1'-0"
FASTEN CURB TO WOOD
BLOCKING BELOW DECK,
PER MANUF. INSTRUCTIONS
SHOP-FABRICATED 22 GAUGE
STAINLESS STEEL CURB CAP
ON VIBRATION ISOLATION
PADS (SLOPE TO DRAIN)
GALVANIZED, FULLY WELDED,
INSULATED EQUIPMENT CURB
WITH INNER LINER
ROOF UNDERLAYMENT
M
IN
IM
U
M
STRIPPING PLY
STAINLESS STEEL SHEET
METAL FLASHING W/ 3-BEAD
BITUMINOUS SEALANT AT
LAPS
GASKETED STAINLESS STEEL
SHIELD SCREW AT 12" O.C. &
AT 6" FROM EACH CORNER
P.T. 2x4 WOOD NAILER
VIBRATION ISOLATOR - SEE
MECHANICAL
DUCT OR FAN - SEE
MECHANICAL
PLYWOOD ROOF DECK
EXISTING FRAMING
NON-COMBUSTIBLE SPRAY
FOAM INSULATION
ROOFING SEALANT
ALT. NO. 02: ROOF SHINGLES ON
SELF-ADHERED SHEET
WATERPROOFING ON SHEATHING
SHOP FABRICATED STAINLESS
STEEL CRICKET BEYOND
ALT. NO. 02: ROOF SHINGLES ON
SELF-ADHERED SHEET
WATERPROOFING ON SHEATHING
ALT. NO. 02: SELF-ADHERED
SHEET UNDERLAYMENT
EXISTING FRAMING
STRIPPING PLY
FLUID APPLIED FLASHING
MEMBRANE
FLASHING FLANGE FULLY
ADHERED
ROOFING SEALANT
NON-COMBUSTIBLE
SPRAY-FOAM INSULATION
M
IN
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:3
A
M MB
MB
03/14/2024
A241JMO
ROOF DETAILS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
A241
SCALE F 0 1
3" = 1'-0"
SCALE FA241
1 DETAIL - ROOF FAN CURB
SCALE FA241
2 DETAIL - ROOF ROUND PENETRATION
INTERIOR ELEVATION SHEET NOTES
1. PROVIDE IN WALL BACKING FOR WALL MOUNTED ITEMS. SEE BACKING
DETAIL FOR TYPE.
2. CASEWORK IS PLASTIC LAMINATE CLAD, L1, UNLESS OTHERWISE
INDICATED.
3. WHERE CASEWORK EXTENDS FROM SIDEWALL TO SIDEWALL, CENTER
CASEWORK IN THE SPACE AND PROVIDE EQUAL WIDTH FILLER PANELS
AT EACH SIDE.
4. PROVIDE LOCKABLE CABINETS AND DRAWERS WHERE REQUIRED BY
OWNER.
5. COUNTERTOPS ARE QUARTZ, QZ1, UNLESS OTHERWISE INDICATED.
6. PROVIDE BACKSPLASHES AT COUNTERTOPS UNLESS OTHERWISE
INDICATED. WHERE COUNTERTOPS ABUT A SIDE WALL, PROVIDE SIDE
SPLASHES UNLESS OTHERWISE INDICATED.
7. PROVIDE WALL BASE AT CASEWORK.
8. FIELD VERIFY PARTITION DIMENSIONS PRIOR TO PREPARING SHOP
DRAWINGS.
9. COUNTERTOP HEIGHTS SHOWN ARE TO TOP OF COUNTER WHERE
THERE IS NO SINK OR AN UNDERMOUNT SINK. WHERE THE COUNTER
INCLUDES A DROP IN SINK, THE DIMENSION SHOWN IS TO THE TOP
SURFACE OF THE SINK RIM. COORDINATE ACTUAL HEIGHT OF
COUNTERTOP WITH PLUMBING FIXTURE SUBMITTAL.
ENLARGED PLAN SHEET NOTES
1. REFER TO G003 FOR TYPICAL TOILET ROOM FIXTURE AND ACCESSORIES
PLACEMENT AND MOUNTING HEIGHTS.
CODE FINISH
APC ACOUSTIC PANEL CEILING
CG CORNER GUARD
CPT CARPET TILE
P PAINT
L HIGH PRESSURE LAMINATE
RB RESILIENT BASE
RF RESILIENT FLOORING
SCONC SEALED CONCRETE
SSM SOLID SURFACE MATERIAL
T TILE
WD WOOD
WS WINDOW SHADE
FINISH ABBREVIATIONS AND CODES
A210
A210
OFFICE
TELECOM
TR01
PANTRY
KITCHEN
LOCKERS
UNISEX
TOILET
WASHER
A
3 / A300
4 / A300
CORRIDOR
C01
ELECTRICAL
ROOM
C2D
A3C
C2D
C2D
C2D
C2C
A3C
A3D
A6D
C2D
C2D
C3D
A3D
A3C
C2D
.1
.1
.1
T R
.1
S1
WC1
S1 U1
8'-0" 3'-11"
/8
4'-8"
5'-9 3/8"9'-11"
/8
/2
4'-4"
A210
A210
108.2
101.1
110.1
A3C
C2D
5 3/16"
1'-1" 4" 1'-9" 3'-0" 1'-0" 2'-0" 3'-0" 2'-6"
6 1/8" ±
1'-1"
16'-3 1/8" ±
2'-0" 2" 1'-0" 3'-0" 1'-0" 2'-0" 3'-0" 1'-9"
4 1/8" ±
2'-0"
L1, TYP. AT UPPER AND
LOWER CABINETS
QZ1 COUNTER
TOP, BACK AND
SIDE SPLASHES
P1
A430
A430
A430
A430
TYP. DETAIL FOR ALL
UPPER CABINETS
UNDERMOUNT SINK -
SEE PLUMBING
1 1/8" ± 3'-0" 2'-6" 1'-0" 2'-6" 1'-0"
11'-3 1/8"
2'-0"2"2'-6"1'-0"2'-6"3'-0"1 1/8" ±
EXTEND QZ1 UP TO
HOOD BEHIND
RANGE
A430
TYP. DETAIL FOR ALL
UPPER CABINETS
A430
A430
1'-1" 1" 1'-0" 2'-6" 1'-3"
1 1/8" ±
6'-0 1/8"
2'-0" 2" 2'-6" 1'-3"
1 1/8" ±
A430
TYP. DETAIL FOR ALL
UPPER CABINETS
A430
A430
RESILIENT FLOORING CARPET TILE
RESILIENT TRANSITION DOOR WHERE
OCCURS
TILE FLOORING
CONCRETE FLOOR SLAB
TILE EDGE STRIP
RESILIENT FLOORING
DOOR
CONTINUOUS SEALANT,
MATCH COLOR TO
RESILIENT FLOORING
WALL
BASE
FLOOR
AS INDICATED
RB (COVED)
CPT
AS INDICATED
RB (COVED)
RF
WALL
BASE
FLOOR
MILLWORK
RB (COVED)
SEE SCHEDULE
COVED
TRIM AS
SPECIFIED 4
RESILIENT BASE
CARPET
RESILIENT BASE
RESILIENT
FLOORING
TILE
TILE
TILE
SCALE BA300
1 PARTIAL ENLARGED LEVEL 1 FLOOR PLAN
SCALE CA300
2 INTERIOR ELEVATION
SCALE CA300
3 INTERIOR ELEVATION
SCALE CA300
4 INTERIOR ELEVATION
DESIGNED:
CADD:
TECH REVIEW:
DATE:
SUB SHEET NO: TITLE OF SHEET: DRAWING NO.
PMIS/PKG NO.
OF
A/E FIRM:
PRIME:
SHEET
SUB:
HENRY
ADAMS, LLC.
BALTIMORE, MD
JOE WALKER
AIA ARCHITECT
GAINESVILLE, FL
323963
/2
/2
:3
:3
A
M MB
MB
03/14/2024
A300JMO
ENLARGED INTERIOR VIEWS
NPS - NATCHEZ MAINTENANCE
FACILITY RENOVATION
A300
SCALE GA300
5 FLOOR TRANSITION - CARPET TO RESILIENT
SCALE GA300
6 FLOOR TRANSITION - TILE TO CARPET OR RESILIENT
SCALE FA300
7 WALL BASE DETAILS
SCALE B 4 0 4 8
1/4" = 1'-0"
SCALE C 2 0 2 4
3/8" = 1'-0"
SCALE F 0 1
3" = 1'-0"
SCALE G 0 6"
6" = 1'-0"
1 LAYER OF 5/8" GWB
METAL FRAMING
PER SCHEDULE
BELOW
INSULATION PER
SCHEDULE BELOW
2 1/4" 3 1/8" 4 1/4" 4 5/8" 6 5/8"
STUD + GWB
ONE LAYER OF 5/8" GWB ON ONE SIDE OF STUD FRAMING.
TYPICAL UNLESS NOTED OTHERWISE BY MODIFIER/S.
7/8"
1 1/2"
C
1-HR RATED TO STRUCTURE
ABOVE WITH INSULATION.
R A
T E
D
1-HR RATED TO STRUCTURE
ABOVE.
N O
N -R
A T
PARTIAL HEIGHT WALL.
REFER TO SECTION OR
ELEVATION…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .