Drawings_Fire_Alarm_Sheet_65_-_69.pdf

PDF 326 KB Posted

Attached to
MODERNIZE NATCHEZ MAINTENANCE FACILITY
Solicitation number
140P5226R0002
Issued by

About this file

This is a Fire Alarm system design document for the Natchez Maintenance Facility Renovation project, prepared by Henry Adams LLC and Walker Architects. The document consists of a cover sheet with general fire alarm notes, floor plans for the first floor and mezzanine, installation details, and a fire alarm riser diagram.

The existing fire alarm system is a Simplex 4007ES Digital Addressable Control Panel with mass notification capability. The scope of work includes connecting new fire alarm devices to existing floor initiating and signaling circuits, with all modifications to be performed by a manufacturer's authorized service company. Key requirements include verifying the existing system is operational before making changes, obtaining written permission from the contracting officer before interrupting service, and ensuring all new devices are listed for compatibility with the existing control unit. The contractor must prepare comprehensive shop drawings including scaled floor plans with device locations and mounting heights, fire alarm device and cable legends, control panel and annunciator locations, power and battery calculations, voltage drop calculations, manufacturer technical data sheets, ceiling height and construction details, interface specifications for fire safety control functions, system riser diagrams, sequence of operations matrices, and loudness and candela settings for all notification appliances. Additionally, battery capacity must be increased to accommodate the additional load from new devices. All work must comply with NFPA 70, NFPA 72, NFPA 90A, NFPA 101, and IBC standards, with coordination required with the local fire marshal and fire department inspectors. The contractor is responsible for obtaining and paying for all required permits, performing re-acceptance testing per NFPA 72, and properly identifying all fire alarm circuits and devices with labeled nameplate and conduit markings throughout the facility.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL FIRE ALARM NOTES

1. VERIFY THAT EXISTING FIRE ALARM SYSTEM IS OPERATIONAL BEFORE MAKING CHANGES OR CONNECTIONS.

2. DO NOT INTERRUPT EXISTING FIRE ALARM SYSTEM WITHOUT [CONTRACTING OFFICER'S] [OWNER'S] [OWNER'S REPRESENTATIVE'S] [ENGINEER'S] [ARCHITECT'S] WRITTEN

PERMISSION.

3. ENGAGE A MANUFACTURER'S AUTHORIZED SERVICE COMPANY TO PERFORM MODIFICATIONS TO THE FIRE ALARM SYSTEM.

4. FOR NEW DEVICES THAT RECEIVE POWER FROM AN EXISTING CONTROL UNIT'S INITIATING DEVICE CIRCUIT OR SIGNALING LINE CIRCUIT, PROVDE DEVICES THAT ARE

LISTED FOR USE WITH THE EXISTING CONTROL UNIT.

5. DRAWINGS ARE CONCEPTUAL, INTENDED TO SHOW GENERAL SYSTEM CONFIGURATION AND PERFORMANCE. PREPARE SHOP DRAWINGS AND PROVIDE CONDUITS, WIRING, SYSTEM COMPONENTS AND EQUIPMENT FOR A COMPLETE AND OPERATIONAL SYSTEM IN COMPLIANCE WITH NFPA 70, NFPA 72, NFPA 90A, NFPA 101 IBC, THE

AUTHORITY HAVING JURISDICTION AND THE CONTRACT DOCUMENTS.

6. CONNECT NEW FIRE ALARM DEVICES TO RESPECTIVE EXISTING FLOOR INITIATING AND SIGNALING CIRCUITS.

7. EXISTING FIRE ALARM SYSTEM IS A SIMPLEX 4007ES DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL WITH MASS NOTIFICATION.

8. COORDINATE FIRE ALARM WORK WITH LOCAL FIRE MARSHAL, FIRE ALARM PLANS REVIEW, AND FIRE DEPARTMENT INSPECTORS.

9. OBTAIN AND PAY FOR PERMITS REQUIRED FOR INSTALLATION OF FIRE ALARM SYSTEM. PROVIDE SHOP DRAWING SUBMITTAL DOCUMENTS TO AUTHORITY HAVING JURISDICTION TO OBTAIN PERMIT. SUBMITTAL MUST INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING:

SCALED FLOOR PLANS WITH ROOM NAMES AND NUMBERS WHICH INDICATE USE OF ALL ROOMS.

FIRE ALARM DEVICE AND CABLE SYMBOL LEGEND

FLOOR PLAN LAYOUT SHOWING LOCATIONS OF ALL DEVICES AND CONTROL EQUIPMENT, INCLUDING

MOUNTING HEIGHTS OF ALARM INITIATING DEVICES AND NOTIFICATION DEVICES.

FIRE ALARM CONTROL PANEL AND ANNUNCIATOR LOCATION.

POWER CONNECTION.

BATTERY CALCULATIONS.

VOLTAGE DROP CALCULATIONS FOR NOTIFICATION APPLIANCE CIRCUITS.

SIZE, TYPE, AND NUMBER OF CONDUCTORS.

MANUFACTURER'S TECHNICAL DATA SHEETS INCLUDING MODEL NUMBERS AND LISTING INFORMATION FOR EQUIPMENT, DEVICES, AND MATERIALS.

DETAILS OF CEILING HEIGHT AND CONSTRUCTION.

INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS.

FIRE ALARM SYSTEM RISER.

SEQUENCE OF OPERATIONS INPUT/OUTPUT MATRIX.

DEVICE TO DEVICE WIRING.

LOUDNESS AND CANDELA SETTINGS FOR EVERY NOTIFICATION APPLIANCE.

10. INCREASE BATTERY CAPACITY OF FIRE ALARM SYSTEM TO ACCOMMODATE ADDITIONAL LOAD.

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

(APPLICABLE TO ALL FIRE ALARM DRAWINGS)

11. FIRE ALARM BRANCH CIRCUIT IDENTIFICATION MUST COMPLY WITH NFPA 70 AND NFPA 72:

• PROVIDE APPROVED RED CIRCUIT BREAKER LOCKOUT DEVICE FOR EACH CIRCUIT BREAKER SERVING A FIRE ALARM CIRCUIT.

• IDENTIFY EACH FIRE ALARM CIRCUIT WITH A RED PHENOLIC NAMEPLATE WITH WHITE LETTERING. NAMEPLATE MUST READ "FIRE ALARM CIRCUIT". FASTEN NAMEPLATE

IN PANELBOARD ADJACENT TO CIRCUIT BREAKER.

12. IDENTIFY POWER SOURCE AND LOCATION OF BRANCH CIRCUIT DISCONNECTING SERVING FIRE ALARM EQUIPMENT. FASTEN PHENOLIC NAMEPLATE TO FIRE ALARM SYSTEM PANEL(S) INDICATING LOCATION OF DEDICATED BRANCH CIRCUIT DISCONNECTING MEANS. NAMEPLATE MUST READ "THIS PANEL FED FROM PANEL ____, CIRCUIT NO. ____, LOCATED IN _____."

13. IDENTIFY EACH FIRE ALARM DEVICE AND EQUIPMENT ENCLOSURE. DEVICE LABELS MUST INDICATE ADDRESS AND ZONE.

14. IDENTIFY FIRE ALARM CIRCUITS AT TERMINAL AND JUNCTION LOCATIONS WITH PERMANENT LABELS. PAINT FIRE ALARM CIRCUIT JUNCTION BOX COVERS RED AND LABEL COVER "FIRE ALARM". MARK CONDUITS CARYING FIRE ALARM SYSTEM CIRCUITS WITH RED STRIPE EVERY 10 FEET.

15. PERFORM RE-ACCEPTANCE TESTING IN ACCORDANCE WITH NFPA 72 TO VERIFY PROPER OPERATION OF ADDED OR REPLACED DEVICES INCLUDING BUT NOT LIMITED TO INITIATING DEVICES, NOTIFICATION APPLIANCES, EMERGENCY CONTROL FUNCTION DEVICES AND CONTROL EQUIPMENT.

FIRE ALARM LEGEND

DESCRIPTION

MOUNTING

HEIGHT

SYMBOL

FIRE ALARM SYSTEM - SMOKE DETECTOR, DUCT DETECTOR WITH

SAMPLING TUBE. SUBSCRIPT IDENTIFIES EQUIPMENT TO BE

CONTROLLED FOR SHUTDOWN.

FIRE ALARM SYSTEM - SMOKE DAMPER WITH DUCT SMOKE DETECTOR

WITH 120V POWER CONNECTION TO DAMPER

FIRE ALARM SYSTEM - FIRE/SMOKE DAMPER WITH DUCT SMOKE

DETECTOR. WITH 120V POWER CONNECTION TO DAMPER.

FIRE ALARM SYSTEM - HEAT DETECTOR (CEILING/WALL MOUNT)

SUBSCRIPTS:

F: FIXED TEMPERATURE (DEFAULT IF NO SUBSCRIPT INDICATED)

R: RATE OF RISE

R/C: RATE COMPENSATION

R/F: COMBINATION RATE OF RISE

SEE DETAIL

FIRE ALARM SYSTEM - SPRINKLER FLOW DETECTION SWITCH - -

FIRE ALARM SYSTEM - VALVE WITH TAMPER DETECTION SWITCH - -

FIRE ALARM SYSTEM - MAGNETIC DOOR HOLDER

COORDINATE

W/ DOOR

FIRE ALARM SYSTEM - MANUAL PULL STATION 46"

FIRE ALARM SYSTEM - ADDRESSABLE MODULE - -

FIRE ALARM SYSTEM - STROBE (CEILING/WALL MOUNT)

SUBSCRIPTS:

C: CO ALARM NOTIFICATION DEVICE

WP: WEATHERPROOF

WG: WIRE GUARD

EP: EXPLOSION PROOF

- - / 86"

FIRE ALARM SYSTEM - SPEAKER/HORN (CEILING/WALL MOUNT)

SUBSCRIPTS:

C: CO ALARM NOTIFICATION DEVICE

WP: WEATHERPROOF

WG: WIRE GUARD

EP: EXPLOSION PROOF

- - / 86"

FIRE ALARM SYSTEM - SPEAKER/HORN STROBE (CEILING/WALL MOUNT)

SUBSCRIPTS:

C: CO ALARM NOTIFICATION DEVICE

WP: WEATHERPROOF

WG: WIRE GUARD

EP: EXPLOSION PROOF

- - / 86"

FIRE ALARM SYSTEM - FIRE ALARM CONTROL PANEL 78" TO TOP

FIRE ALARM SYSTEM - FIRE ALARM SYSTEM ANNUNCIATOR PANEL 78" TO TOP

FIRE ALARM SYSTEM - SMOKE DETECTOR - AREA (CEILING/WALL MOUNT)

SUBSCRIPTS:

P: PHOTOELECTRIC TYPE (DEFAULT IF NO SUBSCRIPT INDICATED)

I: IONIZATION TYPE

BT: BEAM TRANSMITTER TYPE

BR: BEAM RECEIVER TYPE

IAF: IONIZATION TYPE (RATES FOR 0 - 1000 FPM AIR FLOW)

DH: DOOR HOLD RELEASE FUNCTION

E: ELEVATOR RECALL FUNCTION

SP: STAIR PRESSURIZATION FUNCTION

SEE DETAIL

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

FA0.1JST

FIRE ALARM COVER SHEET

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

323963

ELECTRICAL ROOM

KITCHEN

TELECOM

TR01

CORRIDOR

C01

WASHER

UNISEX TOILET

LOCKERS

OFFICE

OFFICE

TRAINING ROOM

15cd15cd

15cd15cd

15cd15cd

30cd30cd

75cd75cd

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

FA1.1JLW

FIRST FLOOR - FIRE ALARM NEW

WORK

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

DRAWING NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID

HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.

ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )

INDICATES EXISTING ITEMS TO REMAIN.

1.

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING

CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING

DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT

INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT

DIRECTION BEFORE PROCEEDING WITH THE WORK.

2.

TEXT.

TEXT.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

SCALE AFA1.1

1 FIRST FLOOR - FIRE ALARM - NEW WORK

SCALE OF FEET

4 0 4 8

SCALE A

MECHANICAL MEZZANINE

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

FA1.2JLW

MEZZANINE - FIRE ALARM NEW

WORK

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

DRAWING NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

UNLESS OTHERWISE NOTED, ELECTRICAL ITEMS SHOWN BY SOLID

HEAVY LINEWEIGHT ( ) INDICATES NEW WORK TO BE PROVIDED.

ELECTRICAL ITEMS SHOWN BY SOLID LIGHT LINEWEIGHT ( )

INDICATES EXISTING ITEMS TO REMAIN.

1.

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING

CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING

DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT

INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL

IMMEDIATELY NOTIFY THE ENGINEER IN WRITING AND AWAIT

DIRECTION BEFORE PROCEEDING WITH THE WORK.

2.

TEXT.

TEXT.

SPECIAL NOTES:

(APPLICABLE TO THIS DRAWING ONLY)

SCALE AFA1.2

1 MEZZANINE - FIRE ALARM - NEW WORK

SCALE OF FEET

4 0 4 8

SCALE A

INSTALL PER NATIONAL

ELECTRICAL CODE

AIR SUPPLY DIFFUSER OR

RETURN AIR OPENING

CONDUIT

JUNCTION BOX

TERMINAL

CABINET

FIRE ALARM CONTROL

PANEL OR EMERGENCY

VOICE PANEL

STROBE

MANUAL PULL

STATION

FINISHED

FLOOR

SMOKE

DETECTOR

AUDIBLE

DEVICE

CEILING

FLOOR-CEILING

ASSEMBLY

6'-0" MAX LENGTH FLEXIBLE RACEWAY TO DEVICE

MOUNTED ON SUSPENDED CEILING

MOUNT DETECTOR

ON APPROVED BOX

HEAT

DETECTOR

REMOTE LAMP

W/ TEST SWITCH

NOTE: MOUNT FIRE ALARM DEVICES ON APPROVED BOXES.

FROM EXIT OPENING

HEAT

DETECTOR

HEAT DETECTOR

HEAT DETECTOR MOUNTING

PLACEMENT REQUIREMENTS

DO NOT LOCATE

HEAT DETECTOR

WITHIN THIS AREA

SMOKE OR HEAT

DETECTOR

EXIT

0'-4" MIN.

0'-4" MIN.

0'-4" MIN 3'-0" MIN

5'-0" MAX

3'-10" FROM

OPERATING

HANDLE TO

FLOOR

5'-6"

6'-8" MIN TO 8'-0" MAX

FROM STROBE

LENS TO FLOOR

OR

WITHIN 0'-6" OF

FINISHED CEILING,

WHICHEVER IS

LOWER

7'-6" TO TOP

OF DEVICE

OR

0'-6" BELOW

FINISHED CEILING,

WHICHEVER IS

LOWER

5'-0" MIN TO

6'-6" MAX

1'-0" MAX

1'-0" MAX

AUDIBLE/STROBE

COMBINATION

CEILING

FINISHED

FLOOR

LISTED CEILING MOUNTED

NOTIFICATION APPLIANCE

ANNUNCIATOR

PANEL OR

SIDE WALL SIDE WALL

SIDE WALL

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

FA5.1JST

FIRE ALARM DETAILS

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

NO SCALE

FA5.1

1 FIRE ALARM DEVICE MOUNTING DETAIL

1.

2.

NOTES: (APPLICABLE TO FIRE ALARM RISER DIAGRAM ONLY)

FIRE ALARM SYSTEM RISER DIAGRAM IS DIAGRAMMATIC. PROVIDE CONDUITS, WIRING, AND SYSTEM COMPONENTS FOR A COMPLETE AND OPERATIONAL SYSTEM IN COMPLIANCE WITH NFPA 70, NFPA 72, NFPA 90A, NFPA 101, IBC, THE LOCAL AUTHORITY HAVING JURISDICTION

AND THE CONTRACT DOCUMENTS.

REFER TO FLOOR PLANS FOR QUANTITIES AND LOCATIONS OF FIRE ALARM DEVICES AND COMPONENTS. INSTALL PULL STATIONS SHOWN ADJACENT TO EXTERIOR DOORS WITHIN 5'-0" HORIZONTALLY OF DOOR OPENINGS. FIELD COORDINATE ACTUAL LOCATION AND SPACING OF INITIATING AND NOTIFICATION DEVICES AND CONDUIT RUNS WITH OTHER WORK INCLUDING BUT NOT LIMITED TO LUMINAIRES, DIFFUSERS, DUCT WORK, WALLS AND CEILINGS.

WOODSHOP

MECH MEZZ

ELEC

TRAINING ROOM

EX FACP

C01

CORRIDOR

KITCHEN

UNISEX TOILET

SS SSSS

FAAP

SSFF

VEHICLE

FACILITY

SS

DESIGNED:

CADD:

TECH REVIEW:

DATE:

SUB SHEET NO: TITLE OF SHEET: DRAWING NO.

PMIS/PKG NO.

OF

A/E FIRM:

PRIME:

SHEET

SUB:

HENRY

ADAMS, LLC.

BALTIMORE, MD

WALKER

ARCHITECTS,

GAINESVILLE, FL

/1

/2

:2

:3

A

M

JLW

JLW

03/14/2024

FA6.1JST

FIRE ALARM RISER DIAGRAM

NPS - NATCHEZ MAINTENANCE

FACILITY RENOVATION

NO SCALEFA6.1

2 FIRE ALARM RISER DIAGRAM

FA0-1 - FIRE ALARM COVER SHEET
Sheets
E0.1 - ELECTRICAL COVER SHEET
E0.2 - ELECTRICAL NOTES
E1.1 - FIRST FLOOR - POWER NEW WORK
E1.2 - MEZZANINE - POWER NEW WORK
E2.1 - FIRST FLOOR - LIGHTING NEW WORK
E2.2 - MEZZANINE - LIGHTING NEW WORK
E3.1 - FIRST FLOOR - SECURITY NEW WORK
E3.2 - MEZZANINE - SECURITY NEW WORK
E5.1 - ELECTRICAL DETAILS
E6.1 - ELECTRICAL ONE-LINE DIAGRAMS
E6.2 - TELECOMMUNICATIONS AND SECURITY RISER DIAGRAMS
E7.1 - LIGHTING CONTROL DIAGRAMS
E8.1 - LUMINAIRE SCHEDULE
E8.2 - ELECTRICAL EQUIPMENT SCHEDULES
E8.3 - PANELBOARD SCHEDULES
E8.4 - PANELBOARD SCHEDULES
ED1.1 - FIRST FLOOR - ELECTRICAL DEMOLITION
ED1.2 - MEZZANINE - ELECTRICAL DEMOLITION
FA0.1 - FIRE ALARM COVER SHEET
FA1.1 - FIRST FLOOR - FIRE ALARM NEW WORK
FA1.2 - MEZZANINE - FIRE ALARM NEW WORK
FA5.1 - FIRE ALARM DETAILS
FA6.1 - FIRE ALARM RISER DIAGRAM
FA1-1 - FIRST FLOOR - FIRE ALARM NEW WORK
Sheets
E0.1 - ELECTRICAL COVER SHEET
E0.2 - ELECTRICAL NOTES
E1.1 - FIRST FLOOR - POWER NEW WORK
E1.2 - MEZZANINE - POWER NEW WORK
E2.1 - FIRST FLOOR - LIGHTING NEW WORK
E2.2 - MEZZANINE - LIGHTING NEW WORK
E3.1 - FIRST FLOOR - SECURITY NEW WORK
E3.2 - MEZZANINE - SECURITY NEW WORK
E5.1 - ELECTRICAL DETAILS
E6.1 - ELECTRICAL ONE-LINE DIAGRAMS
E6.2 - TELECOMMUNICATIONS AND SECURITY RISER DIAGRAMS
E7.1 - LIGHTING CONTROL DIAGRAMS
E8.1 - LUMINAIRE SCHEDULE
E8.2 - ELECTRICAL EQUIPMENT SCHEDULES
E8.3 - PANELBOARD SCHEDULES
E8.4 - PANELBOARD SCHEDULES
ED1.1 - FIRST FLOOR - ELECTRICAL DEMOLITION
ED1.2 - MEZZANINE - ELECTRICAL DEMOLITION
FA0.1 - FIRE ALARM COVER SHEET
FA1.1 - FIRST FLOOR - FIRE ALARM NEW WORK
FA1.2 - MEZZANINE - FIRE ALARM NEW WORK
FA5.1 - FIRE ALARM DETAILS
FA6.1 - FIRE ALARM RISER DIAGRAM
FA1-2 - MEZZANINE - FIRE ALARM NEW WORK
Sheets
E0.1 - ELECTRICAL COVER SHEET
E0.2 - ELECTRICAL NOTES
E1.1 - FIRST FLOOR - POWER NEW WORK
E1.2 - MEZZANINE - POWER NEW WORK
E2.1 - FIRST FLOOR - LIGHTING NEW WORK
E2.2 - MEZZANINE - LIGHTING NEW WORK
E3.1 - FIRST FLOOR - SECURITY NEW WORK
E3.2 - MEZZANINE - SECURITY NEW WORK
E5.1 - ELECTRICAL DETAILS
E6.1 - ELECTRICAL ONE-LINE DIAGRAMS
E6.2 - TELECOMMUNICATIONS AND SECURITY RISER DIAGRAMS
E7.1 - LIGHTING CONTROL DIAGRAMS
E8.1 - LUMINAIRE SCHEDULE
E8.2 - ELECTRICAL EQUIPMENT SCHEDULES
E8.3 - PANELBOARD SCHEDULES
E8.4 - PANELBOARD SCHEDULES
ED1.1 - FIRST FLOOR - ELECTRICAL DEMOLITION
ED1.2 - MEZZANINE - ELECTRICAL DEMOLITION
FA0.1 - FIRE ALARM COVER SHEET
FA1.1 - FIRST FLOOR - FIRE ALARM NEW WORK
FA1.2 - MEZZANINE - FIRE ALARM NEW WORK
FA5.1 - FIRE ALARM DETAILS
FA6.1 - FIRE ALARM RISER DIAGRAM
FA5-1 - FIRE ALARM DETAILS
Sheets
E0.1 - ELECTRICAL COVER SHEET
E0.2 - ELECTRICAL NOTES
E1.1 - FIRST FLOOR - POWER NEW WORK
E1.2 - MEZZANINE - POWER NEW WORK
E2.1 - FIRST FLOOR - LIGHTING NEW WORK
E2.2 - MEZZANINE - LIGHTING NEW WORK
E3.1 - FIRST FLOOR - SECURITY NEW WORK
E3.2 - MEZZANINE - SECURITY NEW WORK
E5.1 - ELECTRICAL DETAILS
E6.1 - ELECTRICAL ONE-LINE DIAGRAMS
E6.2 - TELECOMMUNICATIONS AND SECURITY RISER DIAGRAMS
E7.1 - LIGHTING CONTROL DIAGRAMS
E8.1 - LUMINAIRE SCHEDULE
E8.2 - ELECTRICAL EQUIPMENT SCHEDULES
E8.3 - PANELBOARD SCHEDULES
E8.4 - PANELBOARD SCHEDULES
ED1.1 - FIRST FLOOR - ELECTRICAL DEMOLITION
ED1.2 - MEZZANINE - ELECTRICAL DEMOLITION
FA0.1 - FIRE ALARM COVER SHEET
FA1.1 - FIRST FLOOR - FIRE ALARM NEW WORK
FA1.2 - MEZZANINE - FIRE ALARM NEW WORK
FA5.1 - FIRE ALARM DETAILS
FA6.1 - FIRE ALARM RISER DIAGRAM
FA6-1 - FIRE ALARM RISER DIAGRAM
Sheets
E0.1 - ELECTRICAL COVER SHEET
E0.2 - ELECTRICAL NOTES
E1.1 - FIRST FLOOR - POWER NEW WORK
E1.2 - MEZZANINE - POWER NEW WORK
E2.1 - FIRST FLOOR - LIGHTING NEW WORK
E2.2 - MEZZANINE - LIGHTING NEW WORK
E3.1 - FIRST FLOOR - SECURITY NEW WORK
E3.2 - MEZZANINE - SECURITY NEW WORK
E5.1 - ELECTRICAL DETAILS
E6.1 - ELECTRICAL ONE-LINE DIAGRAMS
E6.2 - TELECOMMUNICATIONS AND SECURITY RISER DIAGRAMS
E7.1 - LIGHTING CONTROL DIAGRAMS
E8.1 - LUMINAIRE SCHEDULE
E8.2 - ELECTRICAL EQUIPMENT SCHEDULES
E8.3 - PANELBOARD SCHEDULES
E8.4 - PANELBOARD SCHEDULES
ED1.1 - FIRST FLOOR - ELECTRICAL DEMOLITION
ED1.2 - MEZZANINE - ELECTRICAL DEMOLITION
FA0.1 - FIRE ALARM COVER SHEET
FA1.1 - FIRST FLOOR - FIRE ALARM NEW WORK
FA1.2 - MEZZANINE - FIRE ALARM NEW WORK
FA5.1 - FIRE ALARM DETAILS
FA6.1 - FIRE ALARM RISER DIAGRAM