This solicitation is for renovation services to convert space for a mail room and reprographics area in Building 297 at the VA Greater Los Angeles Healthcare System campus. The scope of work involves construction of the mail room and reprographics spaces, remodeling bathrooms, a break room and electrical room, as well as exterior painting and metal panel repairs. Site work will include new ADA parking stalls and paths of access. Relocation of a security gate is also included. The contractor must comply with all applicable codes and safety requirements described in the solicitation documentation. The performance period for contract completion is 290 calendar days. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
VA- GREATER LOS ANGELES MEDICAL CENTER
Department of Veteran's Affairs
11301 WILSHIRE BLVD , LOS ANGELES CA 90049
DESIGN TEAM
Architect Of Record John Silber IDS Group INC.
1 Peters Canyon Rd. Ste. 130 Irvine, CA 92606
CONTACT: MAXFIELD SINCLAIR
Project Manager Ph. (949) 387-8500 EXT 148
Mechanical Engineer Of Record
CAMPUS MAP
PROJECT DESCRIPTION
SYMBOL LEGEND
VICINITY MAPSHEET INDEX
RENOVATE SPACE FOR MAIL ROOM/REPROGRAPHICS IN BUILDING 297
Structural Engineer Of Record
CONSTRUCTION TYPE: III - FIRE SPRINKLERED
OCCUPANCY: B-S2
PROJECT AREA: PROPOSED MAIL ROOM AND REPROGRAPHICS: 2,986 S.F.
PROPOSED RESTROOMS AND BREAK AREA : 500 S.F.
EXISTING ELECTRICAL ROOM: 143 S.F.
TOTAL AREA OF WORK : 3,629 S.F.
TOTAL AREA OF EXISTING BUILDING 32,640 S.F.
PROJECT DATA
Rami Elhassan IDS Group INC.
1 Peters Canyon Rd. Ste. 130 Irvine, CA 92606
Walter Mclean IDS Group INC.
1 Peters Canyon Rd. Ste. 130 Irvine, CA 92606
LINE TYPES
EXISTING = SOLID
DEMO = DASHED
PLAN KEY NOTE
WALL TYPE
EDGE OF SLAB
SAW CUT
XX.##
GRID COLUMN CENTER LINE
CALLOUT TAG
DETAIL CUT
REMODEL KEY NOTE
(SEE SHEET)
DOOR TYPE
1 View Name ScaleR101
DETAIL VIEW TAG
SIM
REFERENCE SHEET
X
WINDOW TYPE
X
X
INTERIOR ELEVATION VIEW
EXISTING DOOR
EQUIPMENT DESIGNATION
WALL FINISH CALLOUT
D3
NEW DOOR
1 DEMOLITION KEY NOTE
X
AF-XXX
XX.##
ROOM NAME/
ROOM NUMBERA LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAMA AMERICAN ARCHITECTURAL
MANUFACTURERS ASSOCIATION
AB ANCHOR BOLT
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADC AUTOMATIC DOOR CLOSER
ADJ ADJACENT, ADJOINING, OR ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF ARCHITECTS
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ALT NO ALTERNATE NUMBER
ALUM ALUMINUM
AMP AMPERE
ANOD ANODIZE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE
ARCH ARCHITECT
ASSN ASSOCIATION
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AUTO AUTOMATIC
AUX AUXILIARY
AVG AVERAGE
B LABEL CLASS B DOOR
BB BULLETIN BOARD
BD BOARD
BD FT BOARD FEET (FOOT)
BLDG BUILDING
BLVD BOULEVARD
BM BEAM OR BENCHMARK
BOT BOTTOM
BRZ BRONZE
BTWN BETWEEN
C LABEL CLASS C DOOR
CAB CABINET
CB CATCH BASIN OR CORNER BEAD
CCTV CLOSED CIRCUIT TELEVISION
CD CONSTRUCTION DOCUMENTS OR CONTRACT DOCUMENTS
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CFCI CONTRACTOR FURNISHED AND INSTALLED.
CHEM CHEMICAL
CIP CAST-IN-PLACE
CIR CIRCLE
CJ CONSTRUCTION JOINT OR CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG HT CEILING HEIGHT
CLR CLEAR
cm² SQUARE CENTIMETER cm³ CUBIC CENTIMETER
CM CONSTRUCTION MANAGEMENT
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO₂ CARBON DIOXIDE
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONF CONFERENCE
CONN CONNECT
CONSTR CONSTRUCTION
CONT CONTINUE
COORD COORDINATE
CORR CORRIDOR
CPT CARPET
CRS COLD ROLLED STEEL
CSI CONSTRUCTION SPECIFICATIONS INSTITUTE
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTRL CONTROL
CTV CABLE TELEVISION
CU FT CUBIC FEET
CU IN CUBIC INCH
CU YD CUBIC YARD
CYL CYLINDER
CYL L CYLINDER LOCK
D DEPTH OR PENNY (NAIL)
D LABEL CLASS D DOOR
DAT DATUM
DBL DOUBLE
DBL GLZ DOUBLE GLAZE
DC DIRECT CURRENT
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFERENCE OR DIFFUSER
DIM DIMENSION
DL DEAD LOAD
DOC DOCUMENT
DOUG FIR DOUGLAS FIR
DR DOOR, DRAIN, DRESSING ROOM, OR DRIVE
DR CL DOOR CLOSER
DR FR DOOR FRAME
DR OPNG DOOR OPENING
DW DISHWASHER
DWG DRAWING
E EAST
E LABEL CLASS E DOOR
EA EACH
EJ EXPANSION JOINT
ELEC ELECTRIC
ELEC DR OP ELECTRIC DOOR OPENER
ELEV ELEVATION
ENGR ENGINEER
EPS EXPANDED POLYSTYRENE BOARD (INSULATION)
EQ EQUAL
EQUIP EQUIPMENT
ETC AND SO FORTH OR ET CETERA
EWS EYE WASH STATION
EXH EXHAUST
EXIST EXISTING
EXT EXTERIOR, EXTERNAL, OR EXTINGUISHER
F FAHRENHEIT OR FEMALE
FA FIRE ALARM
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FACE
FF&E FURNITURE, FIXTURE, AND EQUIPMENT
FHC FIRE HOSE CABINET
FIG FIGURE
FIN FINISH
FIN FLR FINISH FLOOR
FIXT FIXTURE
FL FLOORLINE
FLR FLOOR
FLR FIN FLOOR FINISH
FLR SK FLOOR SINK
FO FINISHED OPENING
FOC FACE OF CONCRETE OR FACE OF CURB
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF SLAB OR FACE OF STUD
FOW FACE OF WALL
FP FIRE PROTECTION OR FIREPROOF
FR FIRE RATING, FIRE RESISTANT, OR FRAME
FRP FIBER REINFORCED POLYESTER OR
FIBERGLASS REINFORCED PLASTIC
FT FEET OR FOOT
FTG FOOTING
FURN FURNISH OR FURNITURE
FUT FUTURE
GA GAGE OR GYPSUM ASSOCIATION
GAL GALLON
GALV GALVANIC OR GALVANIZED
GALV STL GALVANIZED STEEL
GC GENERAL CONTRACTOR
GEN GENERAL OR GENERATOR
GI GALVANIZED IRON
GR FL GROUND FLOOR
GYP GYPSUM
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H HIGH
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIBB
HDR HEADER
HDW HARDWARE
HM HOLLOW METAL
HNDRL HANDRAIL
HORIZ HORIZONTAL
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HW HOT WATER
IBC INTERNATIONAL BUILDING CODE
ID IDENTIFICATION, INSIDE DIAMETER, OR INTERIOR DESIGN
ID NO IDENTIFICATION NUMBER
INCL INCLUDED
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INTL INTERNATIONAL
JAN JANITOR
J-BOX JUNCTION BOX
KIT KITCHEN
KO KNOCKOUT
L ANGLE
LAM LAMINATE
LAM GL LAMINATED GLASS
LAV LAVATORY
LBS POUND
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LH LEFT HAND
LHR LEFT HAND REVERSE
LHR LEFT HAND REVERSE LATENT HEAT RATIO
LIN LINEAR
LIQ LIQUID
LS LUMP SUM
LT LIGHT
LT GA LIGHT GAGE
LTG LIGHTING
LVD LOUVERED
LVR LOUVER
LWC LIGHTWEIGHT CONCRETE
LYR LAYER
MAINT MAINTENANCE
MAN MANUAL
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MFR MANUFACTURER
MID MIDDLE
MIRR MIRROR
MISC MISCELLANEOUS
mm MILLIMETER
MO MASONRY OPENING OR MOTOR OPERATED
MTD MOUNTED
MTL METAL
MW MICROWAVE
N NORTH
NA NOT APPLICABLE
NAAMM NATIONAL ASSOCIATION OF
ARCHITECTURAL METAL MANUFACTURERS
NAT NATURAL
NATL NATIONAL
NC NOISE CRITERIA
NEG NEGATIVE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NUM NUMERAL
OC ON CENTER
OCC OCCUPY
OD OUTSIDE DIAMETER OUTSIDE DIMENSION
OD OUTSIDE DIMENSION OUTSIDE DIAMETER
OFCI OWNER FURNISHED/CONTRACTOR INSTALLED
OFD OVERFLOW DRAIN
OFF OFFICE
OH OVERHANG
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
ORIG ORIGINAL
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINSTRATION
OUT OUTLET
OZ OUNCE
PART PARTIAL
PED PEDESTAL
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PKG PACKAGE
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLYWD PLYWOOD
PMTL PAINTED METAL
PNL PANEL
POLY POLYETHYLENE (PLASTIC)
PR PAIR
PREFAB PREFABRICATE
PREFIN PREFINISH
PRELIM PRELIMINARY
PREP PREPARATION
PREV PREVIOUS
PROJ PROJECT
PROP PROPERTY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT, PNEUMATIC TUBE,
OR PRESSURE TREATED
PTN PARTITION
PVG PAVING
PWR POWER
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QTR QUARTER
QTY QUANTITY
QUAL QUALITY
R RADIUS OR RISER
RCP REFLECTED CEILING PLAN
RECD RECEIVED
REF REFERENCE OR REFRIGERATOR
REINF REINFORCE
REQDREQUIRED
RET RETURN
REV REVISION
RFI REQUEST FOR INFORMATION
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
SCHED SCHEDULE
SDG SIDING
SF SQUARE FOOT (FEET)
SHT SHEET
SIM SIMILAR
SPEC SPECIFICATION
SPKLR SPRINKLER
SPKR SPEAKER
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SS SANITARY SEWER OR SERVICE SINK
SST STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STOR STORAGE
STR STRINGERS
STRUCT STRUCTURAL
STRUCT STL STRUCTURAL STEEL
SV SHEET VINYL
T TREAD
T&G TONGUE AND GROOVE
T&M TIME AND MATERIALS
TECH TECHNICAL
TEL TELEPHONE
TEMP TEMPERATURE OR TEMPORARY
THK THICKNESS
THRU THROUGH
THRUOUT THROUGHOUT
TO TOP OF ___
TOB TOP OF BEAM
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOS TOP OF STEEL
TOW TOP OF WALL
TRTD TREATED
TV TELEVISION
TYP TYPICAL
U HEAT TRANSFER COEFFICIENT
UC UNDERCUT
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
UR URINAL
UTIL UTILITY
UV ULTRAVIOLET
V VOLT
VA [V.A.] VETERANS ADMINISTRATION
VAR VARIES
VCT VINYL COMPOSITION TILE VITRIFIED CLAY TILE
VENT VENTILATION
VERT VERTICAL
VIC VICINITY
VIF VERIFY IN FIELD
VOC VOLATILE ORGANIC COMPOUND
VOLT VOLTAGE
VP VENEER PLASTER
W WIDE OR WEST
W/ WITH
W/O WITHOUT
WBL WOOD BLOCKING
WC WALL COVERING OR WATER CLOSET
WD WOOD
WDW WINDOW
WF WIDE FLANGE
WH WATER HEATER
WHSE WAREHOUSE
WP WATERPROOFING
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
X BRACE CROSS BRACE
YD YARD
YR YEAR
Plumbing Engineer Of Record Walter Mclean IDS Group INC.
1 Peters Canyon Rd. Ste. 130 Irvine, CA 92606
Electrical Engineer Of Record Rob O' Neil IDS Group INC.
1 Peters Canyon Rd. Ste. 130 Irvine, CA 92606
PROJECT LOCATION
DETAIL INDICATOR
NORTH
CODE REFERENCES
2018 INTERNATIONAL BUILDING CODE (IBC)
2018 INTERNATIONAL ELECTRICAL CODE (IEC)
2018 INTERNATIONAL MECHANICAL CODE (IMC)
2018 INTERNATIONAL PLUMBING CODE (IPC)
2018 INTERNATIONAL FIRE CODE (IFC)
2018 NFPA 1 - FIRE CODE
2018 NFPA 70E - STANDARD FOR ELECTRICAL SAFETY IN WORKPLACE
2019 NFPA 72 - NATIONAL FIRE ALARM CODE
2019 NFPA 80 - STANDARD FOR FIRE DOORS, AND OTHER
OPENING PROTECTIVES
2018 NFPA 101 - LIFE SAFETY CODE
UNDERWRITERS LABORATORY (UL),
SHEET METAL AND AIR CONDITIONING CONTRACTOR'S NATIONAL
ASSOCIATION (SMACNA),
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM),
AMERICAN SOCIETY FOR MECHANICAL ENGINEERS (ASME)
1. BUILDING 297 - PROJECT LOCATION
2. EXISTING ADJACENT BUILDING
NORTH
PROJECT LOCATION
AREA OF WORK
KEY PLAN
THE PROJECT CONSISTS OF REMODEL AND REPAIR WORK IN BUILDING 297 AT THE
VA GREATER LOS ANGELES (GLA) HEALTHCARE SYSTEM - WEST LOS ANGELES (WLA)
CAMPUS AS FOLLOWS:
1. REMODEL OF EXISTING ADMINISTRATIVE AND WAREHOUSE SPACES IN THE
BUILDING FOR MAILROOM, REPROGRAPHIC SERVICES, AND ANCILLARY SPACES.
2. REMODEL OF THE EXISTING MALE & FEMALE BATHROOMS/ LOCKERS AND
BREAKROOM, TO BE SHARED BY MAIL ROOM STAFF & WAREHOUSE STAFF AT
THE SAME LOCATION.
3. REPLACE & RELOCATE IT RACKS, CLOSET & PROVIDE A UPS BACK-UP POWER W/
REMOTE MONITORING & CONDITIONED SPACE.
4. REPLACE DAMAGED SIDING PANELS, GUTTERS, & DOWNSPOUTS.
5. REPAIR DAMAGED CONCRETE SIDEWALK @ LOADING DOCK AREAS.
6. REPLACE THE EXISTING TRANSFORMER TO AN OUTDOOR LOCATION
7. REPLACE/UPGRADE THE BUILDING'S ELECTRICAL PANELS & BREAKERS AS
NEEDED, & RENOVATE THE EXISTING ELECTRICAL ROOM AS NEEDED.
8. REPLACE EXISTING STEAM RADIATORS BY GAS RADIATORS IN THE BUILDING &
BRING GAS LINE FROM THE ADJOINING BUILDING.
9. ADD SPRINKLERS IN NEW CONSTRUCTION AS DESIGN-BUILD WITH QRS
PRINKLERHEADS PER VA DESIGN DESIGN GUIDE AND CODE.
10. PROVIDE SPRINKLERS IN NEW MAIL ROOM BUILDING AS DESIGN BUILD WITH
QRS SPRINKLER HEADS.
OWNER
VA GREATER LOS ANGELES
MEDICAL CENTER
11301 Wilshire Blvd Los Angeles, California 90049
INCL:
3.
4.
EXISTING ADJACENT BUILDING
EXISTING ADJACENT BUILDING
BUILDING KEY PLAN
XX
BUILDING
SHT.NO SHEET DESCRIPTION
GENERAL
GI.01 COVER DRAWING
GI.02 GENERAL NOTES
GI.03 ADA NOTES
GI.04 ADA NOTES
GI.05 ADA NOTES
GI.06 ADA NOTES
ARCHITECTURAL
AS.07 ARCHITECTURAL SITE PLAN
AD.10 DEMOLITION FLOOR PLAN
AD.11 DEMOLITION ELEVATIONS
AD.12 DEMOLITION ELEVATIONS
AE.20 OVERALL FLOOR PLAN/FIRE LIFE SAFETY PLAN
AE.21 MAILROOM & REPROGRAPHICS - ENLARGED FLOOR PLAN
AC.22 MAILROOM & REPROGRAPHICS - REFLECTED CEILING PLAN
QJ.23 MAILROOM & REPROGRAPHICS - MECHANICAL LAYOUT
AF.24 MAILROOM & REPROGRAPHICS - ROOM SECTIONS
AF.25 MAILROOM & REPROGRAPHICS - SHELL ELEVATIONS
AF.25A MAILROOM & REPROGRAPHICS - ELEVATION CMU PATTERNS
AF.26 MAILROOM & REPROGRAPHICS - INTERIOR ELEVATIONS
AF.30 RESTROOMS - ENLARGED PLAN, RCP, & INTERIOR ELEVATIONS
AF.31 RESTROOMS - BREAKROOMS SECTIONS
AE.40 EXTERIOR BUILDING ELEVATIONS
AE.41 EXTERIOR BUILDING ELEVATIONS
AE.42 EXTERIOR DETAILS
IN.50 DOOR, WINDOW, & WALL DETAILS
IN.51 SUSPENDED CEILING DETAILS
IN.60 SCHEDULES
IN.61 FINISH & INTERIOR DETAILS
QK.70 EQUIPMENT CONFIGURATION PLAN
STRUCTURAL
S-001 GENERAL NOTES
S-002 GENERAL NOTES
S-101 TYPICAL DETAILS
S-102 TYPICAL MASONRY DETAILS
S-201 FOUNDATION PLAN
S-202 ROOF FRAMING PLAN
S-301 TYPICAL DETAILS
S-302 SEISMIC UPGRADE DETAILS
MECHANICAL
MH-001 MECHANICAL NOTES, LEGEND, AND ABBREVIATIONS
MD-101 MECHANICAL DEMOLITION FLOOR PLAN
MH-101 MECHANICAL FLOOR PLANS
MH-401 MECHANICAL ENLARGED PLAN
MH-402 MECHANICAL ENLARGED PLAN
MH-403 MECHANICAL ENLARGED PLAN
MH-404 MECHANICAL SECTION
MH-501 MECHANICAL SCHEDULES
MH-601 MECHANICAL DETAILS
MH-602 MECHANICAL DETAILS
MH-701 TITLE 24 DOCUMENTATION
ELECTRICAL
E001 GENERAL NOTE ABBREVIATIONS, SYMBOL LIST AND SHEET INDEX
E002 PARTIAL SINGLE LINE DIAGRAM
E003 PANEL SCHEDULES
E101 ELECTRICAL SITE PLAN - DEMO
E102 ELECTRICAL SITE PLAN - NEW
E103 EXISTING FLOOR PLAN - BLD 297
E201 FLOOR PLAN - BLD 297
E203 ENLARGED PLAN
PLUMBING
PK-001 PLUMBING NOTES, LEGEND AND ABBREVIATIONS
PS-101 PLUMBING SITE PLAN
PD-101.1 PLUMBING DEMOLITION FLOOR PLAN
PP-102.1 PLUMBING FLOOR PLAN
PP-102.2 PLUMBING
PK-501 EXISTING FLOOR PLAN - BLD 297
PL-601 FLOOR PLAN - BLD 297
E203 ENLARGED PLAN
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
OFFICE
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GREATER LOS ANGELES, VA MEDICAL CENTER
11301 WILSHIRE BLVD
WEST LOS ANGELES, CA 90073
Project Director
10/02/2020Revisions: Date:
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS
IDS GROUP
Project # 17X001.07
SHEET OF 26
PROJECT NO.
691-20-151WLOF
CONSTRUCTION
AND
FACILITIES
MANAGEMENT
RENOVATE SPACE FOR MAIL
ROOM/REPROGRAPHICS
IN BUILDING 297
100% CONSTRUCTION DOCUMENTS
MAX JS/RC
DATE SIGNED: 07-10-2020
L
IC
ENSED ARCH I TECT
JO
HN
JOSEPH S I LBER
S
TAT E OF CA L I FORN
I A
No. C15573
EXP. 07-31-21
GI.01
COVER SHEET
VA.1 Exterior Rolling Gate and fence, and Notes
A. THE CONTRACTOR SHALL PROCURE ALL PERMITS AND LICENSES REQUIRED FOR THE
COMPLETION OF THE WORK. THE COST OF THESE NOTICES, PERMITS, AND LICENSES
IS INCIDENTAL TO OTHER ITEMS OF WORK AND NO ADDITIONAL PAYMENT WILL BE
MADE FOR COSTS INCURRED IN OBTAINING NOTICES, PERMITS, AND LICENSES OR IN
CONFORMING TO THE REQUIREMENTS THEREOF.
A. OVERALL DIMENSIONS ARE TO FACE OF METAL STUDS, AND/OR NOMINAL FACE OF
MASONRY UNLESS NOTED OTHERWISE.
B. ELEVATIONS AND VERTICAL DIMENSIONS ARE TO TOP OF FINISH MATERIAL.
THICKNESS OF ALL DECKING FINISH MATERIAL MUST BE FULLY COORDINATED.
C. GRID LINES REPRESENT THE EXISTING STRUCTURE AND MAY VARY IN THE FIELD.
NOTIFY THE ARCHITECT IN WRITING PRIOR TO THE COMMENCEMENT OF WORK OF ANY
DISCREPANCIES IN THE DIMENSIONS.
D. DO NOT SCALE DRAWINGS.
A. THE CONTRACTOR SHALL PROVIDE PORTABLE FIRE EXTINGUISHERS AS REQUIRED BY
CODE, AND AUTHORITY HAVING JURISDICTION, AT ALL PORTIONS OF THE BUILDING ON
EACH FLOOR. THESE EXTINGUISHERS SHALL BE INSTALLED IN THE LOCATIONS
APPROVED BY THE FIRE DEPARTMENT AND THE ARCHITECT.
B. WHERE TESTING LABORATORY DESIGN NUMBERS ARE LISTED FOR FIRE RATED
CONSTRUCTION, THE COMPONENTS AND INSTALLATION DETAILS MUST CONFORM WITH
THE DESIGN NUMBER SPECIFIED.
A. EXIT DOORS SHALL BE OF THE PIVOTED OR SIDE-HINGED SWINGING TYPE. EXIT DOORS
SHALL SWING IN THE DIRECTION OF EXIT TRAVEL WHEN THE AREA SERVED HAS AN
OCCUPANT LOAD OF 50 OR MORE.
B. EVERY EXIT DOOR SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY
OR ANY SPECIAL KNOWLEDGE OR EFFORT. NOTE ALSO THAT FLUSH BOLTS OR
SURFACE BOLTS ARE PROHIBITED.
C. PANIC HARDWARE SHALL BE PROVIDED ON EXIT DOORS OF ROOMS, CORRIDORS,
STAIRWAYS, HANDLING AN OCCUPANT CAPACITY OF 50 OR MORE PERSONS.
D. EXIT SIGNS SHALL BE INSTALLED AT REQUIRED EXIT DOORWAYS AND WHERE
OTHERWISE NECESSARY TO CLEARLY INDICATE THE DIRECTION OF EGRESS IN
COMPLIANCE WITH THE CODE OF JURISDICTION.
E. STAIRWAYS SHALL NOT BE LESS THAN 44 INCHES WIDE WITH RISERS NOT TO EXCEED 7
INCHES AND TREADS NOT LESS THAN 11 INCHES.
F. EGRESS DOORS SHALL BE SET IN MOTION WHEN SUBJECTED TO A 30LB. FORCE. THE
DOOR SHALL SWING TO THE FULLY OPEN POSITION WHEN AN OPENING FORCE NOT
EXCEEDING 15 LBS IS APPLIED TO THE LATCH SIDE.
G. EACH DOOR IN A MEANS OF EGRESS FROM A GROUP 'A' OCCUPANCY SHALL NOT BE
PROVIDED WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
HARDWARE (CBC 1010.1.9).
H. DOOR HANDLES, LOCK AND OTHER OPERATING DEVICES SHALL BE INSTALLED AT A MIN.
34" AND A MAX. 48" A.F.F.
I. EXIT SIGNS SHALL BE CONNECTED TO AN EMERGENCY POWER SYSTEM THAT WILL
PROVIDE AN ILLUMINATION OF NOT LESS THAT 90MIN. IN CASE OF PRIMARY POWER
LOSS (CBC 1013.6.3)
J. THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE, SHALL BE ILLUMINATED AT
ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF EGRESS IS OCCUPIED.
A. FIRE PROTECTION OF STRUCTURAL MEMBERS SHALL BE IN COMPLIANCE WITH STATE
REGULATIONS.
B. STEEL FIREPROOFING THICKNESS SHALL BE IN COMPLIANCE WITH THE CURRENT
EDITION OF THE CBC .
C. PERIODIC INSPECTIONS SHALL BE PROVIDED FOR ALL REQUIRED SPRAYED-ON
FIREPROOFING TO THE REQUIREMENTS OF CBC CHAPTER 17A SPECIAL INSPECTIONS
AND TESTS. THE INSPECTOR SHALL SUBMIT A SIGNED AFFIDAVIT THAT ALL SPRAYED-ON
FIREPROOFING, WHERE REQUIRED, IS APPLIED ACCORDING TO CODE AND
MANUFACTURER'S SPECIFICATIONS.
A. MECHANICAL DUCTS, ETC. PENETRATING FIRE-RATED CEILINGS AND FIRE WALLS
SHALL BE CORRESPONDINGLY RATED OR DAMPERED. CABINETS, ELECTRICAL PANELS,
LIGHTS, ETC. RECESSED INTO FIRE RATED WALLS OR CEILINGS SHALL BE BACKED
WITH CORRESPONDING FIRE-RESISTIVE CONSTRUCTION AS REQUIRED TO MAINTAIN
THE INTEGRITY OF THE FIRE PROTECTION.
B. FIRE RESISTIVE ASSEMBLIES FOR PROTECTION OF OPENINGS SHALL COMPLY WITH
CBC. PENETRATION OF FIRE RATED ASSEMBLIES WHICH REQUIRE OPENING
PROTECTION SHALL BE FIRE STOPPED. FIRE STOPPING SHALL BE IDENTICAL TO AN
APPROVED UNDERWRITERS LABORATORIES (UL) LISTED ASSEMBLY WITH AN "F" OF "T"
RATING. PENETRATIONS MUST ALSO CONSIST OF APPROVED MATERIALS FOR
THROUGH WALL PENETRATIONS FIRE STOP SYSTEMS AS PRESCRIBED IN CBC
STANDARD 7-5 FIRE RATING FOR FIRE STOP SYSTEMS SHALL BE EQUAL TO THE
ASSEMBLY PENETRATED.
C. SHAFT ENCLOSURES: OPENINGS EXTENDING VERTICALLY THROUGH FLOORS SHALL BE
ENCLOSED IN A SHAFT OF 1-HOUR FIRE-RESISTIVE CONSTRUCTION. SHAFTS SHALL
INCLUDE A GYPSUM BOARD HORIZONTAL TERMINATION AT BOTTOM, ENGINEERED BY
GENERAL CONTRACTOR. PROTECTION FOR STAIRWAYS SHALL BE AS SPECIFIED IN
CODE OF JURISDICTION.
A. All dissimilar metals shall be effectively isolated.
A. REFER TO ELECTRICAL, TELEPHONE/DATA, AND SECURITY ELECTRONICS DRAWINGS
FOR LOCATION OF AND SPECIFICATIONS FOR THE INSTALLATION OF FIRE RETARDANT
TREATED PLYWOOD BACKBOARDS REQUIRED IN ELECTRICAL AND COMMUNICATION
ROOMS. THESE REQUIRED PLYWOOD BACKBOARDS HAVE NOT BEEN SHOWN ON THE
ARCHITECTURAL DRAWINGS, BUT MUST BE FURNISHED AND INSTALLED AS A PART OF
THE OVERALL CONTRACT. BACKBOARDS SHALL BE PAINTED WHITE.
A. FURNISH AND INSTALL SUPPORTS AND OTHER NECESSARY FINISH MATERIALS FOR A
COMPLETE SIGNAGE INSTALLATION.
B. ACCESSIBLE SIGNAGE / IDENTIFICATION
1. THE INTERNATIONAL SYMBOL OF ACCESSIBILITY SHALL BE THE STANDARD USED TO
IDENTIFY FACILITIES THAT ARE ACCESSIBLE TO AND USEABLE BY PHYSICALLY
DISABLED PERSONS.
2. LETTERS AND NUMBERS ON SIGNS HAVE A WIDTH TO HEIGHT RATIO OF BETWEEN
3:5 AND 1:1 AND STROKE WIDTH TO HEIGHT RATIO OF BETWEEN 1:5 AND 1:10.
3. CHARACTERS AND SYMBOLS SHALL CONTRAST WITH THEIR BACKGROUND, EITHER
LIGHT CHARACTERS ON A DARK BACKGROUND OR DARK CHARACTERS ON A LIGHT
BACKGROUND.
4. ALL BUILDING ENTRANCES THAT ARE ACCESSIBLE TO AND USABLE BY PHYSICALLY
HANDICAPPED PERSONS SHALL BE IDENTIFIED WITH AT LEAST ONE STANDARD SIGN
AND WITH ADDITIONAL DIRECTIONAL SIGNS AS REQUIRED TO BE VISIBLE TO PERSONS
ALONG APPROACHING PEDESTRIAN WAYS.
5. ALL SANITARY FACILITIES WILL BE PROVIDED WITH APPROPRIATE IDENTIFICATION
SYMBOLS.
C. AREA AND OCCUPANCY SIGNAGE REQUIREMENTS OCCUPANT LOAD SIGN SHALL BE
POSTED IN EACH CLASSROOM, ASSEMBLY ROOM OR SIMILAR PURPOSE ROOM HAVING
AN OCCUPANT LOAD OF 50 OR MORE.
A. EXACT LOCATIONS AND HEIGHTS OF ELECTRICAL, LOW VOLTAGE, MECHANICAL AND
PLUMBING DEVICES, INCLUDING BUT NOT LIMITED TO SMOKE DETECTORS, PULL
STATIONS, SWITCHES, OUTLETS, PHONE JACKS, AND THERMOSTATS, SHALL BE
COORDINATED BY THE CONTRACTOR PER THE APPLICABLE CODE FOR ALIGNMENT
AND COORDINATION WITH EACH OTHER AND OTHER BUILDING FEATURES PRIOR TO
INSTALLATION.
A. THE DRAWINGS ARE DIVIDED INTO SEPARATE SHEETS AND THE PROJECT MANUAL
INTO SEPARATE SECTIONS FOR GENERAL CONVENIENCE ONLY. SHEET DESIGNATION
OR NUMBERS SHALL NOT BE CONSIDERED TO LIMIT AREAS OF THE WORK OR
RESPONSIBILITY OF TRADES. COORDINATE THE WORK SHOWN ON THE DRAWINGS
AND IN THE PROJECT MANUAL IN ORDER TO COMPLETE THE PROJECT TO SATISFY
INTENT.
B. VERIFY ALL SIZES OF, AND PREPARE WORK FOR, EQUIPMENT OF OTHERS. G.C. SHALL
COORDINATE WORK ON THIS CONTRACT WITH ITEMS OF WORK NOT IN CONTRACT
(N.I.C.) OR WORK FURNISHED BY OTHERS.
C. LOCATIONS AND SIZES OF EQUIPMENT ARE BASED ON AVAILABLE INFORMATION.
PROVIDE AND COORDINATE THE EXACT DIMENSIONS, SIZES, AND POSITIONS.
D. PROVIDE AND COORDINATE THE EXACT DIMENSIONS, SIZES, AND POSITIONS OF
OPENINGS IN SLABS AND WALLS NECESSARY FOR THE INSTALLATION OF THE WORK.
E. PROVIDE REINFORCING STEEL, MESH, AND DOWELS REQUIRED BY THE STRUCTURAL
GENERAL NOTES AND STRUCTURAL DRAWINGS FOR ARCHITECTURAL DETAILS
INDICATED ON THE ARCHITECTURAL DRAWINGS.
F. QUANTITIES INDICATED ON THE DRAWINGS ARE APPROXIMATE. CONTRACTOR SHALL
VERIFY QUANTITIES AND INCLUDE ACCURATE QUANTITIES AS PART OF THE WORK.
G. NOTES AND DETAILS: SPECIFIC NOTES OR KEYNOTES ON DETAILS APPLY TO SIMILAR
CONDITIONS ON OTHER DETAILS ON ALL DRAWINGS UNLESS SPECIFICALLY NOTED
OTHERWISE.
1. ALL WORK SHALL CONFORM TO CONTRACT DOCUMENTS. NO CHANGES TO THE CONTRACT DOCUMENTS SHALL
BE MADE WITHOUT WRITTEN APPROVAL OF THE ARCHITECT. WHERE MORE INFORMATION IS NEEDED TO DO THE
WORK, OR WHEN AN INTERPRETATION OF THE CONTRACT DOCUMENTS REQUIRES CLARIFICATION, THE
CONTRACTOR SHALL, BEFORE PROCEEDING WITH WORK, REFER THE MATTER, IN WRITING TO THE ARCHITECT
THROUGH AN R.F.I. THE ARCHITECT WILL FURNISH THE INFORMATION OR INTERPRETATION IN THE FORM OF
SUPPLEMENTAL INFORMATION, OTHER WRITTEN FORM, OR BY DRAWING.
2. WHERE ONLY PART OF THE WORK IS INDICATED, SIMILAR PARTS SHALL BE CONSIDERED REPETITIONS. WHERE
ANY DETAIL IS SHOWN AND THE COMPONENTS ARE DESCRIBED ELSEWHERE, SIMILAR DETAILS SHALL BE
CONSTRUCTED AS DESCRIBED IN THE ORIGINAL DETAILS.
3. DRAWINGS ARE GENERIC IN NATURE. CONTRACTOR SHALL FULLY COORDINATE ALL ASPECTS OF THE WORK TO
BE PERFORMED. DETAILS ARE NOT INTENDED TO SHOW METHOD AND MANNER OF ACCOMPLISHING THE WORK.
4. ALL DIMENSIONS ORIGINATING AT, CONNECTED TO, OR CONTINUING THROUGH EXISTING CONDITIONS, INCLUDING PREVIOUS PHASES, MUST BE COORDINATED AND FIELD VERIFIED BY THE CONTRACTOR PRIOR TO
FABRICATION INSTALLATION, AND CONSTRUCTION OF BUILDING ELEMENTS OR SYSTEMS.
5. CONTRACTORS SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, AND ALL EXISTING CONDITIONS AT THE SITE
BEFORE COMMENCING WORK AND REPORT ANY DISCREPANCIES IN WRITING TO THE ARCHITECT AND OWNER.
6. SHOULD A CONFLICT BE DISCOVERED WITHIN THE CONTRACT DOCUMENTS, THE CONTRACTOR SHALL BE
DEEMED TO HAVE INCLUDED IN HIS WORK THE HIGHEST QUALITY WAY OF DOING THE WORK UNLESS HE HAS, IN
WRITING, REQUESTED AND OBTAINED A DECISION FROM THE ARCHITECT AND OWNER.
A. THE DRAWINGS SHOW DIAGRAMMATICALLY THE APPROXIMATE LOCATION OF
UNDERGROUND UTILITIES WHERE INFORMATION IS AVAILABLE, BUT THE
DRAWINGS ARE NOT EXACT AS TO THE QUANTITY, EXTENT OR LOCATION.
B. PREPARE SURFACES OF FLOOR AREAS WHICH HAVE FINISHES DEMOLISHED TO
RECEIVE NEW FINISH MATERIAL AS SPECIFIED.
C. FOR ADDITIONAL DEMOLITION REQUIREMENTS, SEE SPECIFICATIONS.
A. ALL CONSTRUCTION, ALSO REFERRED TO AS 'THE WORK' AND/OR 'WORK',
SHALL COMPLY WITH THE APPLICABLE CODES AS ADOPTED BY THE REGIONAL,
STATE, AND NATIONAL AUTHORITIES HAVING JURISDICTION.
B. FOR ADDITIONAL APPLICATION, THE LIST OF CODES APPLICABLE TO THIS
PROJECT, SEE 'APPLICABLE CODES' ON COVER SHEET.
A. THE REMOVAL OF HAZARDOUS MATERIALS IS NOT INTENDED TO BE INCLUDED AS PART
OF THIS PROJECT UNLESS SPECIFICALLY NOTED OTHERWISE.
B. IF HAZARDOUS MATERIALS ARE DISCOVERED DURING THE COURSE OF
CONSTRUCTION, THE CONTRACTOR SHALL STOP ALL AFFECTED WORK AND NOTIFY
THE OWNER AND ARCHITECT IMMEDIATELY.
C. OWNER ACKNOWLEDGES THAT IDS GROUP SHALL HAVE NO RESPONSIBILITY FOR THE
DISCOVERY, PRESENCE, HANDLING, REMOVAL, DISPOSAL OR EXPOSURE OF PERSONS
TO HAZARDOUS SUBSTANCES, MATERIALS, AND WASTES IN ANY FORM AT PROJECT
SITE, INCLUDING BUT NOT LIMITED TO: ASBESTOS, ASBESTOS PRODUCTS, PCB MOLD,
OR OTHER TOXIC SUBSTANCES.
D. THE OWNER ACKNOWLEDGES THAT IT ACCEPTS RESPONSIBILITY FOR NOTIFYING THE
APPROPRIATE FEDERAL, STATE, AND AUTHORITIES HAVING JURISDICTION FOR ANY
DEMOLITION, CONSTRUCTION, OR REPAIR WORK.
E. ANY QUESTIONS THAT ARISE FROM RELATED TO ASBESTOS SHALL BE REFERRED TO
OWNER FOR RESOLUTION. IDS GROUP SHALL NOT BE REQUIRED TO DO ANY WORK NOR
RENDER ANY OPINIONS RELATED TO ASBESTOS.
F. THE OWNER SHALL RETAIN AN INDEPENDENT CONSULTANT WHO IS TRAINED AND
EXPERIENCED IN IDENTIFICATION AND SURVEY OF EXISTING SITES PRIOR TO
DEMOLITION CONSTRUCTION.
G. ALL CONTRACTORS AND SUBCONTRACTORS SHALL REPORT THE PRESENCE OF ANY
MATERIAL OR ASSEMBLY SUSPECTED TO CONTAIN ASBESTOS UPON DISCOVERY. THE
WORK SHALL BE CARRIED OUT PER THE CONSULTANTS RECOMMENDATIONS.
CONSTRUCTION ACTIVITIES INCLUDING ADDITIONS, ALTERATIONS, AND DEMOLITIONS SHALL
PROVIDE PEDESTRIAN PROTECTION PURSUANT TO SECTION 3306 OF THE CALIFORNIA
BUILDING CODE. TO DETERMINE THE TYPE OF PROTECTION REQUIRED FOR PEDESTRIANS,
MEASURE THE ULTIMATE HEIGHT OF CONSTRUCTION WITH CONSIDERATION FOR BUILDING
SETBACKS AND PROJECTIONS FROM THE BUILDING. FOR SLOPING SITES, MEASURE THE
HEIGHT OF THE BUILDING FROM CONSTRUCTION EDGE OF THE WALKWAY AND THE SETBACK
DISTANCE BETWEEN THE WALKWAY AND THE BUILDING LINE.
BELOW ARE REQUIREMENTS TO BE ADDRESSED IN THE DESIGN OF PEDESTRIAN
PROTECTIONS:
A. WALKWAYS SHALL PROVIDE SUFFICIENT WIDTH WITH THE MINIMUM OF 4 FT. CLEAR.
B. DIRECTIONAL BARRICADES SHELL BE PROVIDED AS NEEDED WHERE THE WALKWAY
EXTENDS INTO THE STREET.
C. CONSTRUCTION RAILINGS SHALL BE AT LEAST 42 INCHES IN HEIGHT.
D. BARRIERS SHALL BE A MINIMUM OF 8 FT. IN HEIGHT AND BE DESIGNED TO RESIST
LOADS REQUIRED.
E. SUCH PROTECTION SHALL BE MAINTAINED IN PLACE AND KEPT IN GOOD ORDER.
UNTIL WORK IS COMPLETED.
F. WHENEVER A WALKWAY MUST EXTEND INTO THE ROADWAY, A RAILING IS REQUIRED
ON THE STREET SIDE.
A. THE INSTRUMENTS OF SERVICES ARE ANY EXPRESSION, WHETHER TANGIBLE OR
INTANGIBLE, OF CREATIVE WORKED PERFORMED BY A DESIGN PROFESSIONAL FOR A
PROJECT, SUCH AS:
· MODELS
· SKETCHES AND DRAWINGS
· SPECIFICATIONS
THE INSTRUMENTS OF SERVICE ARE ALSO KNOWN AS DESIGN DOCUMENTS AND
CONSTRUCTION DOCUMENTS.
ACCORDING TO THE ARCHITECT'S PRACTICE ACT, BUSINESS AND PROFESSIONS CODE
SECTION 5536.4, NO PERSON MAY USE AN ARCHITECT'S INSTRUMENTS OF SERVICES,
AS THOSE PROFESSIONAL SERVICES ARE DESCRIBED IN PARAGRAPH (2) OF
SUBDIVISION (B) OF SECTION 5500.1, WITHOUT THE CONSENT OF THE ARCHITECT IN A
WRITTEN CONTRACT, WRITTEN AGREEMENT, OR WRITTEN LICENSE SPECIFICALLY
AUTHORIZING THAT USE.
THE PLANS AND SPECIFICATIONS ARE COMPLIMENTARY AND INTENDED TO CONVEY
THE DESIGN INTENT OF THE PROJECT. THEY ARE NOT INTENDED TO SUPPLANT THE
GENERAL CONTRACTOR'S CONSTRUCTION EXPERTISE, AND, IN FACT, RELY ON THE
CONTRACTOR TO CLARIFY AND/OR OBTAIN ANY ELEMENTS OF NEEDED INFORMATION
PRIOR TO THE SUBMISSION OF A BID. THE CONTRACTOR'S BID SHALL BE ASSUMED TO
INCLUDE THE SUFFICIENT COSTS TO CONSTRUCT ALL WORK SHOWN ON THE
DOCUMENTS, WHETHER OR NOT ADEQUATELY DESCRIBED IN THE DOCUMENTS, IN
ORDER TO PROVIDE THE OWNER A SAFE, COMPLETE AND FULLY FUNCTIONAL
PROJECT.
B. THE SCOPE OF THIS PROJECT IS AS GENERALLY DEPICTED IN THESE INSTRUMENTS OF
SERVICE AS PART OF THE CONTRACT DOCUMENTS. WORK INCLUDING: POINTS OF
CONNECTION, NOT SPECIFICALLY DEPICTED, THAT NEED TO BE MADE ARE THE
RESPONSIBILITY OF THE GENERAL CONTRACTOR. ALL WORK PERFORMED EVEN IN
REMOTE AREAS OF THE BUILDING OR SITE, PERTAINING TO THIS PROJECT SHALL
COMPLY WITH THE INTENT OF CONTRACT DOCUMENTS.
C. THESE CONTRACT DOCUMENTS COVER THE FURNISHING AND INSTALLATION OF
MATERIALS AND WORK AS CALLED FOR ON THE DRAWINGS OR IN THE SPECIFICATIONS
(OR IN BOTH) WHICH ARE BOUND SEPARATELY AND ARE A PART OF THE CONTRACT. IT
SHALL BE THE RESPONSIBILITY OF EACH CONTRACTOR TO CHECK WITH THE
ARCHITECTURAL DRAWINGS BEFORE FINALIZING THEIR BID AND BEFORE THE
INSTALLATION OF THEIR WORK. ANY DISCREPANCY BETWEEN THE ARCHITECTURAL
AND THE CONSULTING ENGINEER(S) DRAWINGS SHALL BE BROUGHT TO THE
ARCHITECTS ATTENTION BY WRITTEN REQUEST FOR CLARIFICATION. ANY WORK
INSTALLED IN CONFLICT WITH THE ARCHITECTURAL DRAWINGS SHALL BE CORRECTED
BY THE CONTRACTOR AT HIS OWN EXPENSE AND AT NO EXPENSE TO THE OWNER OR
ARCHITECT.
D. GENERAL REQUIREMENTS, DESCRIBING THE PROJECT'S ADMINISTRATIVE
REQUIREMENTS AND THE PHYSICAL ASPECTS OF CONSTRUCTION, ARE PROVIDED
WITHIN EACH PROFESSIONAL DISCIPLINE'S PROJECT SPECIFICATION AND GENERAL
NOTATION. GENERAL REQUIREMENTS ARE NOT LIMITED TO THE INSTRUMENT OF
SERVICES AND MAY EXTEND TO THE CONTRACT DOCUMENTS AND OWNER
REQUIREMENTS.
E. THE PROJECT SPECIFICATIONS CONSISTING OF THE WRITTEN REQUIREMENTS FOR
MATERIAL, EQUIPMENT, SYSTEMS, STANDARDS, AND WORKMANSHIP FOR THE WORK,
AND PERFORMANCE OF RELATED SERVICES ARE CONTAINED WITHIN EACH OF THE
ARCHITECT AND THE ARCHITECT'S INSTRUMENT OF SERVICES. REFER TO GENERAL
NOTES FOR ADDITIONAL PROJECT STANDARDS INFORMATION. DOCUMENTS INDICATED
AS 'REFERENCE DOCUMENT' ARE NOT CONSIDERED INSTRUMENTS OF SERVICES AND
ARE BEING ISSUED TO PROVIDE ASSISTANCE DURING THE REGULATORY AGENCY
CONTRACT DOCUMENT REVIEW.
F. REFER TO LIFE SAFETY AND ACCESSIBILITY DIAGRAMS THAT INDICATE PROVISIONS
WITHIN EXISTING CONDITIONS.
G. THESE DRAWINGS ARE BASED ON FIELD OBSERVATION AND/OR DOCUMENTS
FURNISHED BY THE OWNER. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY BY THE
CONTRACTOR OF ANY DISCREPANCIES OR OTHER QUESTIONS PERTAINING TO THE
CONTRACT DOCUMENTS. IF OBVIOUS OMISSIONS OR CONTRADICTORY SITUATIONS IN
THE CONTRACT DOCUMENTS ARE DISCOVERED TO EXIST, THEY SHOULD BE
IMMEDIATELY CALLED TO THE ATTENTION OF ARCHITECT FOR CLARIFICATION.
H. ALL DIMENSIONS TAKE PRECEDENCE OVER SCALE UNLESS OTHERWISE NOTED BY A
PLUS/MINUS DIMENSION. CONTRACTOR SHALL CHECK ACCURACY OF DIMENSIONS ON
PLANS WITH ACTUAL FIELD DIMENSIONS. THE CONTRACTOR SHALL REPORT TO THE
ARCHITECT ALL CONDITIONS WHICH PREVENT THE PROPER EXECUTION OF ITS WORK.
CONTRACTOR SHALL NOT START ANY CONSTRUCTION OR ANY OFF-SITE FABRICATION
OF MATERIALS UNTIL THE DRAWINGS DIMENSIONS ARE VERIFIED WITH ACTUAL FIELD
CONDITIONS. DO NOT SCALE DRAWINGS.
I. THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE RESULTS OF ANY ERRORS,
DISCREPANCIES OR OMISSIONS THAT THE CONTRACTOR FAILED TO NOTIFY THE
ARCHITECT OF BEFORE CONSTRUCTION AND/OR FABRICATION OF THE WORK.
J. WORK INCLUDES DEMOLITION, REMOVAL, AND REINSTALLATION WHERE REQUIRED.
REMOVE, REVISE, RELOCATE AND REINSTALL AS REQUIRED.
K. IT IS NOT THE RESPONSIBILITY OF THE ARCHITECT OR GENERAL CONTRACTOR TO
ENSURE THAT AREAS OF THE BUILDING, NOT DESCRIBED WITHIN THE SCOPE OF THIS
PROJECT, COMPLY WITH CURRENT BUILDING CODES. IT IS THE RESPONSIBILITY OF
THE OWNER TO MAINTAIN THE BUILDING, SO AS TO PROVIDE FOR THE SAFETY AND
COMFORT OF THE OCCUPANTS. THIS INCLUDES ALL LIFE SAFETY FEATURES SUCH AS
FIRE ALARM, FIRE-SPRINKLERS, NURSE CALL, EXIT ENCLOSURE, ACCESSIBILITY, ETC..
THIS ALSO INCLUDES MAINTAINING THE BUILDING FREE OF HAZARDOUS MATERIALS I.E.,
CHEMICALS AS DESCRIBED BY STATE OR FEDERAL AGENCIES AS 'HAZARDOUS'
INCLUDING ASBESTOS.
A. CONTRACTOR FOR THE PROJECT SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED
BUILDING PERMITS PRIOR TO COMMENCING WORK. SEE 15. PERMITS AS APPLIES.
B. CONTRACTOR IS RESPONSIBLE TO MAINTAIN AND SUPPORT SUSTAINABLE PRACTICES.
C. THE CONTRACTOR SHALL INSURE THAT ALL WORK IS DONE IN A PROFESSIONAL
WORK-MAN-LIKE MANNER BY SKILLED MECHANICS AND SHALL REPLACE ANY NEW AND/OR
EXISTING MATERIALS OR ITEMS INDICATED TO REMAIN DAMAGED BY ANY CAUSE DURING
CONSTRUCTION.
D. THE CONTRACTOR AND/OR SUBCONTRACTOR SHALL, PRIOR TO THE SUBMISSION OF THEIR
BID OR PERFORMANCE OF WORK, NOTIFY THE OWNER OF ANY WORK CALLED OUT ON THE
DRAWINGS OR IN THE SPECIFICATIONS IN THEIR TRADE THAT CANNOT BE FULLY
GUARANTEED OR WARRANTED FROM DEFECTIVE WORKMANSHIP OR MATERIAL DEFECTS.
E. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IF DETAILS ARE CONSIDERED UNSOUND,
UNSAFE, NOT WATERPROOF, OR NOT WITHIN CUSTOMARY TRADE PRACTICE. IF WORK IS
PERFORMED, IT WILL BE ASSUMED THAT THERE IS NO OBJECTIONS TO THE DETAIL. DETAILS
ARE INTENDED TO SHOW END RESULT OF DESIGN, MINOR MODIFICATIONS MAY BE
REQUIRED TO SUIT JOB CONDITIONS AND CURRENT TRADE PRACTICE AND SHALL BE
INCLUDED AS PART OF THIS PROJECT.
F. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL FINISHES AT POINT OF CONNECTIONS FOR
ALL WORK (ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL) FINISHES WILL
MATCH THOSE SPECIFIED OR EXISTING IN LINE, TEXTURE AND FINISH. SPOT PAINTING IS
NOT ACCEPTABLE. NEW FINISHES SHALL BE FROM CORNER TO CORNER, FLOOR TO CEILING,
ETC.
G. UNLESS OTHERWISE NOTED, ALL MATERIALS SHALL BE NEW AND OF GOOD QUALITY.
WHERE EXISTING MATERIALS ARE INDICATED TO BE SALVAGED, CONTRACTOR SHALL
INVENTORY, CLEAN,BOX PROTECT, AND STORE ITEMS FOR REUSE ON THE PROJECT. ITEMS
NOT REUSED SHALL BE RETURNED TO OWNER.
H. COORDINATION: THE GENERAL AND EACH SUB-CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFICATION AND COORDINATION WITH OTHER SUB-CONTRACTORS TO ASSURE
COMPLIANCE WITH DRAWINGS AND SPECIFICATIONS, AND THE ACCURATE LOCATION OF
ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL BUILDING ELEMENTS.
THEIR REQUIRED OPENINGS CLEARANCES SUPPORT SYSTEMS ARE ALL INTERCONNECTED
AND COORDINATED.
I. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK OF ALL TRADES AND
FOR BEING AWARE OF ALL CONDITIONS THAT AFFECT THEIR WORK. NOTIFY OWNER, IN
WRITING, WITHIN 3 WORKING DAYS OF AWARD OF CONTRACT, OF THE PROPOSED DELIVERY
SCHEDULE, OF ANY EQUIPMENT, FINISHES OR MATERIAL, FOR WHICH THAT SCHEDULE WILL
PREVENT THE INSTALLATION FROM BEING COMPLETED AT THE TIME OF THE SCHEDULED
PROJECT COMPLETION.
J. COORDINATION OF WORK:
· THE CONTRACTOR SHALL PROVIDE AND COORDINATE THE EXACT DIMENSIONS
SIZES AND POSITIONS OF ALL SYSTEMS, EQUIPMENT, MOUNTING, AND
ATTACHMENTS RELATING TO THE WORK.
· THE CONTRACTOR SHALL PROVIDE AND COORDINATE ALL DIMENSIONS SIZES AND
POSITIONS OF OPENINGS IN SLABS AND WALLS NECESSARY TO THE INSTALLATION
OF THE WORK.
· ALL EQUIPMENT, CONTROLS AND TERMINATIONS SHALL BE POSITIONED FOR SAFE,
DIRECT AND EASY ACCESS.
K. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS OF EXISTING SITE. THE
CONTRACTOR SHALL REPORT TO THE ARCHITECT ALL CONDITIONS WHICH PREVENT THE
PROPER EXECUTION OF ITS WORK. THE DRAWINGS SHALL NOT BE SCALED.
L. CONSTRUCTION SHALL COMPLY WITH APPLICABLE EDITION OF CALIFORNIA BUILDING CODE, ALL APPLICABLE LOCAL, STATE AND FEDERAL CODES, ORDINANCES, LAWS, REGULATIONS
AND PROTECTIVE COVENANTS GOVERNING THE WORK. IN CASE OF CONFLICTS, THE MORE
STRINGENT REQUIREMENT SHALL GOVERN.
M. GENERAL CONTRACTOR TO ARRANGE INSPECTIONS AS NECESSARY OR REQUIRED.
N. ALL CONTRACTOR'S WORK SHALL BE OF THE QUALITY TO PASS INSPECTIONS BY LOCAL
AND STATE AUTHORITIES, LENDING INSTITUTIONS, THE ARCHITECT AND HIS ENGINEERS,
INSPECTOR OF RECORD, AND OWNER. ANY ONE OR ALL OF THE ABOVE MENTIONED
INSPECTORS MAY INSPECT TRADE(S) AT ANY TIME, AND ANY CORRECTIONS NEEDED TO
MEET THE REQUIRED QUALITY OF CONSTRUCTION SHALL BE DONE IMMEDIATELY AFTER
NOTIFYING THE ARCHITECT AND THE OWNER FOR APPROVAL.
O. THE CONTRACTOR/SUB CONTRACTORS SHALL INSPECT THE SITE PRIOR TO START OF
CONSTRUCTION AND NOTIFY OWNER AND THE ARCHITECT OF ANY EXISTING CONDITIONS
THAT MAY AFFECT THE WORK INCLUDING ELEMENTS THAT MAY BE SUBJECT TO DAMAGE
DURING DEMOLITION AND RENOVATION. THE CONTRACTOR SHALL FIELD VERIFY EXISTING
DIMENSIONS, PRIOR TO START OF CONSTRUCTION AND NOTIFY OWNER AND ARCHITECT OF
ANY DISCREPANCIES BETWEEN THE EXISTING DIMENSIONS AND THE DRAWING DIMENSIONS
THAT MAY AFFECT THE WORK. THE CONTRACTOR SHALL OBTAIN DIRECTION FROM OWNER
ON RESOLUTION OF THE DISCREPANCIES BETWEEN THE EXISTING CONDITIONS AND
DIMENSIONS AND DRAWINGS PRIOR TO STARTING ANY WORK THAT MAY BE AFFECTED BY
SUCH DISCREPANCIES.
P. CLEANUP: TYPICALLY EACH SUBCONTRACTOR IS HELD RESPONSIBLE FOR CLEANUP OF
THE WORK OF THEIR TRADE BY THE GENERAL CONTRACTOR. HOWEVER, THE GENERAL
CONTRACTOR SHALL BE HELD SOLELY RESPONSIBLE FOR CONTINUOUS CLEANUP AS THE
JOB PROGRESSES, AND FINAL CLEANUP UPON SUBSTANTIAL COMPLETION. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR CLEANING UP AND REMOVING FROM THE JOB
SITE ALL TRASH AND DEBRIS, IMMEDIATELY UPON COMPLETION OF HIS DAILY WORK.
CONTINUOUS CLEANUP SHALL KEEP THE JOB FREE AT ALL TIMES FROM UNREASONABLE
BUILDUP OF DEBRIS, WRAPPERS, CONTAINERS, WASTE MATERIALS, ETC., WHICH MAY
CAUSE ACCIDENTS, UNDUE HARDSHIP ON THE TRADESMAN, AND WORK PROGRESS. FINAL
CLEANUP INCLUDES CLEANING OF ALL SURFACES TO A 'LIKE NEW' CONDITION AND
PREPARING THE BUILDING FOR ITS INTENDED USE.
Q. THE CONTRACTOR SHALL AT ALL TIMES MAINTAIN THE SITE AND ADJACENT AREAS IN A
CLEAN, NEAT, AND ORDERLY MANNER. THE CONTRACTOR SHALL BE RESPONSIBLE ONLY
FOR DEBRIS THAT IS A RESULT OF THE WORK, INCLUDING ANY THAT MAY RESULT FROM
THE WORKERS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING HIS OWN
REFUSE CONTAINERS AND SHALL AT NO TIME USE THE BUILDING REFUSE CONTAINERS.
R. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE SECURITY OF THE SITE
WHILE THE JOB IS IN PROGRESS AND UNTIL THE JOB IS COMPLETED.
S. CONTRACTOR SHALL PROVIDE A PORTABLE FIRE EXTINGUISHER WITH A RATING OF NOT
LESS THAN 2-A OR 2-10BC WITHIN 75 FEET OF TRAVEL DISTANCE TO ALL PORTIONS OF THE
BUILD OUT AREA DURING CONSTRUCTION.
T. OBTAIN ALL CAL / OSHA CONSTRUCTION ACTIVITY PERMITS, PRIOR TO OBTAINING THE
BUILDING PERMIT, AS REQUIRED BY AND IN ACCORDANCE WITH APPLICABLE CODES.
U. DEMARCATE AND NOTIFY THE REGIONAL NOTIFICATION CENTER (DIG ALERT, 811) AT LEAST
TWO WORKING DAYS PRIOR TO MAKING ANY EXCAVATIONS.
13. FIELD APPLICATION OF PEDESTRIAN PROTECTION
12. HAZARDOUS MATERIALS
3. CONTRACTOR OBLIGATIONS
10. COORDINATION OF DEVICES
9. SIGNAGE
8. ELECTRICAL BACKBOARDS
7. DISSIMILAR METALS
6. RATED ASSEMBLY PENETRATIONS
11. INSTRUMENTS OF SERVICE
1. GENERAL CONSTRUCTION NOTES
14. CODES
15. PERMITS
16. COORDINATION & VERIFICATION
17. UTILITIES AND DEMOLITION
18. DIMENSIONS
19. FIRE PROTECTION
4. EXITS
5. FIREPROOFING
1. DRAWINGS AND SPECIFICATIONS ARE PROPERTY OF IDS GROUP, INC. USE BY OWNER, CONTRACTOR, AND ALL
OTHER ENTITIES ARE LIMITED FOR SINGLE USE AS APPLICABLE TO THIS SPECIFIC PROJECT SOLELY. DUPLICATION
BY ANY MEANS FOR USE ON ANY OTHER PROJECT OR SITE IS PROHIBITED UNDER COPYRIGHT LAWS WITHOUT
THE EXPRESS WRITTEN CONSENT OF IDS GROUP.
2. ALL REQUIRED NOTIFICATIONS AND/OR WORK INFORMATION BY THE CONTRACTOR TO THE OWNER AND/OR
ARCHITECT ARE TO BE IN WRITING WITH ISSUE DATE.
3. NO CHANGES ARE TO BE MADE TO THE CONTRACT DOCUMENTS WITHOUT THE WRITTEN CONSENT OF THE
ARCHITECT/ ENGINEER OF RECORD WHOSE SIGNATURE APPEARS HEREON.
4. DIMENSIONS AS INDICATED ON THE DRAWINGS ARE THE DIMENSIONS TO BE USED FOR
CONSTRUCTION. DO NOT SCALE THE DRAWINGS.
5. CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES PROCEDURES, AND FOR COORDINATING ALL PORTIONS OF THE WORK UNDER THE
CONTRACT.
6. CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL ASPECTS OF JOBSITE SAFETY. ALL CONSTRUCTION
SHALL BE PERFORMED IN ACCORDANCE WITH THE STATE CONSTRUCTION SAFETY ORDERS ENFORCED
BY THE STATE OF CALIFORNIA, DIVISION OF INDUSTRIAL SAFETY.
7. CONTRACTOR IS RESPONSIBLE FOR ALL PHASING OF THE WORK, CREATING TEMPORARY
BARRICADES, AND SEPARATE PROTECTED ACCESS POINTS FOR SAFE PASSAGE BY CONSTRUCTION
TEAM, PUBLIC, AND/ OR SPECIFIC TENANTS.
8. CONTRACTOR TO PROVIDE USE OF TEMPORARY UTILITIES REQUIRED BY THE OWNER TO BE
OPERATIONAL DURING CONSTRUCTION. CONTRACTOR SHALL COORDINATE SCHEDULING OF SHUT OFF
SERVICES WITH LOCAL UTILITY COMPANIES AND FACILITY MANAGEMENT/ ENGINEERING SERVICES.
9. NO FRAMING OF ANY TYPE IS TO BE CONCEALED PRIOR TO INSPECTION BY GOVERNING AGENCIES.
10. CONTRACTOR TO COMPLY WITH CODES, ORDINANCES, RULES, AND REGULATIONS OF PUBLIC
AUTHORITIES GOVERNING THE WORK.
11. CONTRACTOR SHALL PROVIDE STRICT DISCIPLINE AND GOOD ORDER AMONG THE CONTRACTOR'S
EMPLOYEES AND OTHER PERSONS CARRYING OUT THE WORK. CONTRACTOR SHALL NOT PERMIT
EMPLOYMENT OF UNFIT PERSONS OR PERSONS NOT PROPERLY SKILLED IN TASKS ASSIGNED TO THEM.
12. CONTRACTOR SHALL KEEP PROJECT SITE AND SURROUNDING AREAS FREE FROM ACCUMULATION
OF WASTE MATERIAL AND RUBBISH CAUSES BY OPERATIONS UNDER THE CONTRACT.
13. CONTRACTOR TO DEVELOP AND ENFORCE COVID-19 PROTOCOLS FOR ALL PERSONAL ENTERING
THE JOB SITE OR ASSOCIATED AREAS. GUIDELINES SHALL BE MADE AVAILABLE TO OWNER AND
ARCHITECT/ ENGINEER OF RECORD. STANDARDS DEVELOPED BY STATE AND LOCAL JURISDICTIONS
SHALL BE BENCHMARK OF MINIMUM STANDARDS.
14. PERSONS WHO SHOW SIGNS OF RESPIRATORY SYMPTOMS ASSOCIATED WITH COVID-19 OR OTHER
HIGHLY CONTAGIOUS DISEASES SHALL BE SENT HOME OR TO HOSPITAL IMMEDIATELY. CONTRACTOR TO NOTIFY
ARCHITECT AND OWNER WITHIN 48 HOURS.
15. CONTRACTOR TO OBTAIN AND PAY FOR ALL WORK RELATED PERMITS, FEES, LICENSES, AND INSPECTIONS
REQUIRED BY PUBLIC AUTHORITIES GOVERNING THE WORK.
16. CONTRACTOR TO REVIEW DOCUMENTS, VERIFY DIMENSIONS, RECORD EXISTING FIELD CONDITIONS, AND
CONFIRM THAT THE WORK IS CONSTRUCTIBLE AS SHOWN. REPORT IN WRITING ANY CONFLICTS OR OMISSIONS
TO THE ARCHITECT FOR CLARIFICATION PRIOR TO PERFORMING ANY WORK IN QUESTION.
17. CONTRACTOR SHALL CONFIRM AND CONDUCT ANY OWNER OR LOCAL JURISDICTIONAL REQUIREMENTS
REGULATING CONSTRUCTION OPERATIONS. THIS CAN INCLUDE DEFINED WORKDAYS/ HOURS, DELIVERY HOURS, NOISE LEVELS, STAGING AREA, VISUAL SCREENING REQUIREMENTS, AND/OR USE OF PLACEMENT OF
TEMPORARY BARRICADES.
18. CONSTRUCTION DOCUMENTS INCLUDE DRAWINGS AND SPECIFICATIONS. ONE DOES NOT
OVERRULE THE OTHER. IF DISCREPANCIES ARE FOUND, CONTRACTOR SHALL NOTIFY THE ARCHITECT
OF RECORD IN WRITING THROUGH THE R.F.I. PROCESS. ARCHITECT IS SOLELY RESPONSIBLE FOR
COORDINATING WITH ENGINEERS TO RESOLVE THE DISCREPANCIES AND WILL ISSUE WRITTEN
RESPONSE. DRAWINGS AND SPECIFICATIONS ARE SUBJECT TO CHANGE THROUGHOUT THE
CONSTRUCTION PHASE WITHOUT NOTICE. CONTRACTOR IS RESPONSIBLE TO KEEP ON SITE AT LEAST
ONE CURRENT HARD COPY SET OF EACH DOCUMENT.
19. FOR SUBSTITUTIONS PROCEDURES, REFER TO SPECIFICATIONS.
20. SHOP DRAWINGS, PRODUCT DATA, SAMPLES, AND SIMILAR SUBMITTALS ARE NOT CONTRACT
DOCUMENTS. THEIR PURPOSE IS TO DEMONSTRATE HOW THE CONTRACTOR PROPOSES TO CONFORM
TO THE DESIGN INTENT EXPRESSED IN THE CONSTRUCTION DOCUMENTS. REVIEW BY THE ARCHITECT/
ENGINEER OF RECORD IS SUBJECT TO LIMITATIONS.
21. ARCHITECT'S REVIEW AND APPROVAL OF SHOP DRAWINGS, PRODUCT DATA, SAMPLES AND
SUBMITTALS DOES NOT RELIEVE CONTRACTOR FROM THEIR RESPONSIBILITY OF MEETING THE
REQUIREMENTS CONTAINED WITHIN THE CONTRACT DOCUMENTS, MANUFACTURER'S INSTRUCTIONS, AND/OR
INDUSTRY-SPECIFIC BEST PRACTICES.
22. CONTRACTOR SHALL NOT COMMENCE, NOR PERFORM, ANY PORTION OF THE WORK THAT REQUIRES SUBMITTAL
AND REVIEW BY ARCHITECT OF SHOP DRAWINGS, PRODUCT DATA, SAMPLES, AND SIMILAR SUBMITTALS UNTIL
RESPECTIVE WRITTEN SUBMITTAL HAS BEEN APPROVED BY THE ARCHITECT AND SUBMITTED BACK TO THE
GENERAL CONTRACTOR.
23. ARCHITECT/ ENGINEER REVIEW OF SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES ARE FOR THE
LIMITED PURPOSE OF CHECKING FOR CONFORMANCE WITH THE DESIGN INTENT EXPRESSED IN THE
CONSTRUCTION DOCUMENTS. THE REVIEW OF SUCH SUBMITTALS IS NOT CONDUCTED FOR THE
PURPOSE OF DETERMINING ACCURACY OR COMPLETENESS OF THE DRAWINGS OR DETAILS. A/E REVIEW DOES
NOT INCLUDE CONFIRMING DIMENSIONS, QUANTITIES, OR SUBSTANTIATING INSTALLATION INSTRUCTIONS OR
PERFORMANCE OF EQUIPMENT OR SYSTEM(S). ALL AFOREMENTIONED ITEMS REMAIN THE RESPONSIBILITY OF
THE CONTRACTOR TO COORDINATE WITH THE DRAWING SET AND TO BRING ANY INCONSISTENCIES TO THE
ATTENTION OF THE ARCHITECT.
24. ARCHITECT HAS THE AUTHORITY TO REJECT WORK THAT DOES NOT CONFORM TO THE CONTRACT
DOCUMENTS AND HAS THE AUTHORITY TO REQUIRE INSPECTION OR TESTING OF THE WORK WHETHER
OR NOT THE WORK IS FABRICATED, INSTALLED, OR COMPLETED.
25. IT IS RECOGNIZED THAT THE A/E PROFESSIONAL(S) DO NOT HAVE THE AUTHORITY TO STOP WORK
NOR CONTINUE OPERATIONS AT A JOB SITE. THIS DIRECTIVE IS ONLY AVAILABLE TO OWNER, CONTRACTOR, AND BUILDING INSPECTOR. IF A/E PROFESSIONAL(S) BECOMES AWARE OF
NON-CONFORMING WORK OR UNSAFE CONDITIONS, THEY WILL NOTIFY CONTRACTOR AND OWNER AS QUICKLY
AS DEEMED NECESSSARY.
26. CONTRACTOR SHALL MAKE AVAILABLE AND MAINTAIN IN GOOD ORDER, AT THE PROJECT SITE, THE CONTRACT
DOCUMENTS, INCLUDING CHANGE ORDERS, CONSTRUCTION CHANGE DIRECTIVES, AND OTHER MODIFICATIONS
AND MARKED CURRENT TO INDICATE PROGRESS AND PROVIDE A "AS-BUILT" RECORD OF COMPLETED WORK.
27. CONTRACTOR TO COORDINATE WITH OWNER ON SCHEDULING TIME AND LOCATIONS FOR DELIVERIES, BUILDING ACCESS, USE OF BUILDING SERVICES, ALL ASSOCIATED FACILITIES, AND USE OF ELEVATORS, WHERE
THEY OCCUR. CONTRACTOR SHALL COORDINATE WORK WITH OTHER CONTRACTS. MINIMIZE DISTURBANCE OF
BUILDING FUNCTIONS AND OCCUPANTS, INCLUDING TRASH REMOVAL ACCESS.
28. OWNER SHALL PROVIDE WORK NOTED "BY OTHERS" OR "NIC" UNDER A SEPARATE CONTRACT.
CONTRACTOR TO INCLUDE "BY OTHER" AND "NIC" INTO SCHEDULE REQUIREMENTS FOR CONSTRUCTION
PROGRESS SCHEDULE AND COORDINATE TO ASSURE ORDERLY SEQUENCE OF INSTALLATION.
29. THE CONTRACTOR IS RESPONSIBLE FOR CUTTING, FITTING, OR PATCHING REQUIRED TO COMPLETE
THE WORK AND/OR TO MAKE ITS PARTS FIT TOGETHER PROPERLY. ALL AREAS REQUIRING CUTTING, FITTING, OR PATCHING SHALL BE RESTORED TO THE ORIGINAL CONDITION OR MADE TO MATCH NEW.
2. EXISTING CONDITIONS NOTES
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
OFFICE
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GREATER LOS ANGELES, VA MEDICAL CENTER
11301 WILSHIRE BLVD
WEST LOS ANGELES, CA 90073
Project Director
10/02/2020
Revisions: Date:
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS
IDS GROUP
Project # 17X001.07
SHEET OF 26
PROJECT NO.
691-20-151WL
OF
CONSTRUCTION
AND
FACILITIES
MANAGEMENT
RENOVATE SPACE FOR MAIL
ROOM/REPROGRAPHICS
IN BUILDING 297
100% CONSTRUCTION DOCUMENTS
MAX JS/RC
DATE SIGNED: 07-10-2020
L
I
C
E
N
S
E
D
AR
C
H
I
T
E
C
T
J
O
H
N
J
O
S
E P
S
I
L
B
E
R
S
T
A
T
E
F
CA
L
I
F
O
R
N
I
A
No. C15573
EXP. 07-31-21
GENERAL NOTES
GI.02
7.
8.
8.
7.
6.
5.
9.
9.
MAXIMUM EFFORT TO OPERATE INTERIOR AND EXTERIOR DOORS SHALL NOT
EXCEED 5 POUNDS, WITH SUCH PULL OR PUSH EFFORT BEING APPLIED AT
RIGHT ANGLES TO HINGED DOORS AND AT THE CENTER PLANE OF SLIDING OR
FOLDING DOORS. COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS
MAY BE UTILIZED TO MEET THE ABOVE STANDARDS. WHEN FIRE DOORS ARE
REQUIRED, THE MAXIMUM EFFORT TO OPERATE THE DOOR MAY BE INCREASED
TO THE MINIMUM ALLOWABLE BY THE APPROPRIATE ADMINISTRATIVE
AUTHORITY, NOT TO EXCEED 15 POUNDS.
FOR HINGED DOORS, THE OPENING WIDTH SHALL BE MEASURED WITH THE
DOOR POSITION AT AN ANGLE OF 90 DEGREES FROM THE CLOSED POSITION.
MINIMUM MANEUVERING CLEARANCES AT DOORS SHALL BE AS SHOWN IN
FIGURE 11B-26. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
CLEARANCES SHALL BE LEVEL AND CLEAR.
THERE SHALL BE A LEVEL AND CLEAR FLOOR OR LANDING ON EACH SIDE OF A
DOOR. THE LEVEL AREA SHALL HAVE A LENGTH IN THE DIRECTION OF DOOR
SWING OF AT LEAST 60" AND THE LENGTH OPPOSITE THE DIRECTION OF DOOR
SWING OF 48" AS MEASURED AT RIGHT ANGLES TO THE PLANE OF THE DOOR IN
THE CLOSED POSITION. WHERE THE PLANE OF THE DOORWAY IS OFFSET OR
LOCATED IN AN ALCOVE A DISTANCE MORE THAN 8" MEASURED FROM THE
PLANE OF THE DOORWAY TO THE FACE OF THE WALL, THE DOOR SHALL BE
PROVIDED WITH 60" MANEUVERING CLEARANCE FOR FRONT APPROACH.
PROVIDE CLEAR SPACE OF 12" PAST STRIKE EDGE OF THE DOOR ON THE
OPPOSITE SIDE TO WHICH THE DOOR SWINGS IF THE DOOR IS EQUIPPED WITH
BOTH A LATCH AND A CLOSER.
WHERE THE DOOR OPENS INTO A STAIR OF A SMOKE PROOF ENCLOSURE, THE
LANDING NEED NOT HAVE A LENGTH OF 60".
WHEN THE DOOR HAS A CLOSER, THEN THE SWEEP PERIOD OF THE CLOSER
SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 70 DEGREES, THE
DOOR WILL TAKE AT LEAST 3 SECONDS TO MOVE TO A POINT 3" FROM THE
LATCH, MEASURED TO THE LANDING EDGE OF THE DOOR.
10.
11.
14.
15.
16.
17.
STROBE SIGNALING DEVICES REQUIRED FOR THE HEARING IMPAIRED SHALL BE
STATE FIRE MARSHALL, NFPA 72: PER CHAPTER 6, SECTION 6-4, VISIBLE
CHARACTERISTICS, PUBLIC MODE.
2.
MANEUVERING CLEARANCES AT DOORS SHALL BE LEVEL (1:50 MAX. SLOPE)
AND CLEAR IF DOORS ARE NOT AUTOMATIC OR POWER ASSISTED.
21.
EVERY CORRIDOR SHALL BE AS SHOWN ON THE PLANS AND SHALL BE
DETERMINED AS PER IBC CHAPTER 10, BUT SHALL NOT BE LESS THAN 44" IN
WIDTH.
EVERY PORTION OF EVERY BUILDING IN WHICH ARE INSTALLED SEATS, TABLES,
MAILING, EQUIPMENT, STORAGE RACKS OR SIMILAR MATERIALS SHALL BE
PROVIDED WITH AISLES LEADING TO AN EXIT.
APPROVED NOTIFICATION APPLIANCES FOR THE HEARING IMPAIRED SHALL BE
INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF NFPA 72 AND CBC,
CHAPTER 9, SECTION 907.9.1 AND 907.9.2.
1.
2.
1.
ALL ACCESSIBLE ENTRANCES SHALL BE IDENTIFIED WITH AT LEAST ONE
STANDARD SIGN AND WITH ADDITIONAL DIRECTIONAL SIGNS, AS REQUIRED,
VISIBLE FROM APPROACHING PEDESTRIAN WAYS.
EVERY REQUIRED EXIT DOORWAY WHICH IS LOCATED WITHIN AN ACCESSIBLE
PATH OF TRAVEL SHALL BE CAPABLE OF OPENING AT LEAST 90 DEGREES,
SHALL HAVE A MINIMUM CLEAR OPENING OF 32", AND SHALL BE OF A SIZE AS TO
PERMIT THE INSTALLATION OF A DOOR NOT LESS THAN 3' IN WIDTH AND NOT
LESS THEN 6'-8" IN HEIGHT.
LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED AND WHICH ARE
IN A PATH OF TRAVEL SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER
TYPE HARDWARE, BY PANIC BARS, PUSH-PULL ACTIVATING BARS, OR OTHER
HARDWARE DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE
ABILITY TO GRASP THE OPENING HARDWARE.
HAND-ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED BETWEEN
30" AND 44" ABOVE THE FLOOR.
THE FLOOR AND LANDING ON EACH SIDE OF AN ENTRANCE OR PASSAGE DOOR
SHALL BE LEVEL AND CLEAR. THE LEVEL AND CLEAR AREA SHALL HAVE A
LENGTH IN THE DIRECTION OF DOOR SWING OF AT LEAST 60" AND THE LENGTH
OPPOSITE THE DIRECTION OF DOOR SWING OF 44" AS MEASURED AT RIGHT
ANGLES TO THE PLANE OF THE DOOR IN ITS CLOSED POSITION.
THE FLOOR OR LANDING SHALL BE NOT MORE THAN 1/2" LOWER THAN THE
THRESHOLD OF THE DOORWAY. CHANGE IN LEVEL BETWEEN 1/4" AND 1/2"
SHALL BE BEVELED WITH A SLOPE NO GREATER THAN 1:2.
THE BOTTOM 10" OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING SHALL HAVE
A SMOOTH UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY
A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS
CONDITION. WHERE NARROW FRAME DOORS ARE USED, A 10" HIGH SMOOTH
PANEL SHALL BE INSTALLED ON THE PUSH SIDE OF THE DOOR, WHICH WILL
ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT
CREATING A TRAP OR HAZARDOUS CONDITION.
12.
WHERE A PAIR OF DOORS IS UTILIZED, AT LEAST ONE OF THE DOORS SHALL
PROVIDE A CLEAR, UNOBSTRUCTED OPENING WIDTH OF 32" WITH THE LEAF
POSITIONED AT AN ANGLE OF 90 DEGREES FROM ITS CLOSED POSITION.
13.
WHEN AN AUTOMATIC DOOR OPERATOR IS UTILIZED TO OPERATE A PAIR OF
DOORS, AT LEAST ONE OF THE DOORS SHALL PROVIDE A CLEAR
UNOBSTRUCTED OPENING WIDTH OF 32" WITH THE DOOR POSITIONED AT AN
ANGLE OF 90 DEGREES FROM ITS CLOSED POSITION.
ACCESSIBLE ENTRANCES TO AND FROM EXITS FROM A BUILDING MUST BE
PROVIDED,…