This document package includes a technical specification sheet and federal contract opportunity notice. The technical specification sheet provides product details for Hoffman sealed environmental network cabinets, including dimensions, material specifications, finish options, load ratings, and accessories. Air conditioner models G28 and G52 are also specified, with performance data, electrical characteristics, and dimensions.
The related federal contract opportunity is a renovation project to provide a new mail room and reprographics area within Building 297 at the VA Greater Los Angeles Healthcare System campus. The scope of work involves construction of the mail room and reprographics spaces, bathroom and break room remodeling, electrical room updates, exterior painting, and ADA parking improvements. The projected contract completion time is 290 calendar days.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Free-Stand CabinetS PROLINE NEtwORk SEaLEd ENvIRONmENtaL PackagES nVent.com/HOFFMANSUBJECT TO CHANGE WITHOUT NOTICEnetworking1 Spec-00125 P
ProLine VoiCe/data and SerVer Cabinet, tyPe 12 indUStry StandardS
EIA RS-310-D
UL 508A Listed; Type 12; File Number E61997 cUL Listed per CSA C22.2 No 94; Type 12; File Number E61997
NEMA/EEMAC, Type 12 aPPLiCation Robustly built and sealed for use in wet, dusty or hot environments, ProLine Type 12 Cabinets have optional cutouts to air condition voice/data equipment and servers.
FeatUreS
• Three-point locking handles on all doors provide easy but controlled access; two keys included
| • | Fully welded frame safely supports sensitive equipment |
| • | Fully gasketed to keep contaminants away from equipment, |
reducing maintenance costs
• Two sets of 19-in. rack angles support both front and rear of equipment
• Rack angles are infinitely adjustable from front to rear for
| positioning | flexibility | |||||||||
| • | Mobile base provides easy placement of cabinet | |||||||||
| • | Levelers | and | anti-tip | bracket | secure | cabinet | to | the | floor |
SPeCiFiCationS
| • | Welded 12 gauge steel frame with integral struts |
| • | Front window door made of 16 or 14 gauge steel with safety glass |
window
| • | Solid 16 or 14 gauge steel back door | |||||||||||
| • | Standard package has solid 16 or 14 gauge steel sides | |||||||||||
| • | AC | package | has | cutout | for | easy | in-the-field | installation | of | any | G28 |
| or | G52 | Series | air | conditioner | (ordered | and | shipped | separately) |
| • | Models available with EIA Universal standard 3/8-in. square or |
10-32 tapped holes
| • | Mobile base includes casters, levelers and gland plate | |||||||
| • | Gland | plate | allows | easy | routing | of | cable |
FiniSH Pretreated steel coated with RAL 9005 black or RAL 7035 light-gray textured, low-gloss polyester powder paint. Other finishes available—contact nVent HOFFMAN Customer Service.
Load rating Static Load rating: 2500 lb. (1134 kg) A cabinet has a static load when:
| • | it | is | in | its | final, | permanent, | fully | secured | location | |
| • | its | levelers | are | fully | extended | |||||
| • | the anti-tip bracket is installed | |||||||||
| • | its load is uniformly applied to the two sets of rack-mounting |
angles, and
• the casters are not supporting any load (use the casters only to move the cabinet to its final location before loading) never move a cabinet with its maximum static load applied.
Contact Hoffman if further information is needed.
Casters Maximum Load: 1000 lb. (453 kg)
| Exercise | care | when | using | casters | to | move | the | cabinet. | Do | not | use | |
| casters | to | move | a | cabinet | with | more | than | 1000 | lb. | (453 | kg) | load. |
Avoid tipping and damage to the cabinet and its contents by slowly moving the cabinet on its casters across smooth, flat flooring. Avoid obstructions such as:
| • | large cracks | ||
| • | floor | displacement | |
| • | seams | ||
| • | gravel |
never use casters while transporting a cabinet by truck on roadways.
Contact nVent HOFFMAN if further information is needed.
aCCeSSorieS See the Package Components table. For AC-Ready Cabinet, see
| G28 | or | G52 | air | conditioner | specifications | following | the | Package |
| Compenents | table. | Full | AC | specifications | available | in | the | Thermal |
chapter. Air conditioner must be ordered and shipped separately; it cannot be factory installed.
noteS The cabinet must be fully secured in its final position before the AC unit (ordered separately) is mounted to the cabinet. never move the cabinet with the aC mounted.
Bulletin: DPC, DPSR
Standard Product
Catalog Number AxBxC mm AxBxC in. Cabinet, Package Type Finish Rack Units
Hole Type Rack Angle
PDCP2078B12 2085 x 708 x 799 82.10 x 27.87 x 31.46 Voice Data, Standard DataCom Black 42 Tapped PRA1920TPL1 PDCP2078G12 2085 x 708 x 799 82.10 x 27.87 x 31.46 Voice Data, Standard ProLine Gray 42 Tapped PRA1920TPL1 PSC20610B12 2085 x 608 x 999 82.10 x 23.94 x 39.34 Server, Standard DataCom Black 42 Square PRA1920THL1 PSC20610G12 2085 x 608 x 999 82.10 x 23.94 x 39.34 Server, Standard ProLine Gray 42 Square PRA1920THL1
AC-Ready Cabinets
Catalog Number AxBxC mm AxBxC in.
Cabinet Package Type Finish AC Rack Units Hole Type Rack Angle
PDCP2078BAC 2085 x 708 x 799 82.10 x 27.87 x 31.46 Voice/Data, AC-Ready DataCom Black G28 42 Tapped PRA1920TPL1 PDCP2078GAC 2085 x 708 x 799 82.10 x 27.87 x 31.46 Voice/Data, AC-Ready ProLine Gray G28 42 Tapped PRA1920TPL1 PSC20610BAC 2085 x 608 x 999 82.10 x 23.94 x 39.34 Server, AC-Ready DataCom Black G28 42 Square PRA1920THL1 PSC20610GAC 2085 x 608 x 999 82.10 x 23.94 x 39.34 Server, AC-Ready ProLine Gray G28 42 Square PRA1920THL1 PDCP2078BAC2 2082 x 708 x 799 81.98 x 27.87 x 31.47 Voice/Data, AC-Ready DataCom Black G52 42 Tapped PRA1920TPL1 PDCP2078GAC2 2082 x 708 x 799 81.98 x 27.87 x 31.47 Voice/Data, AC-Ready ProLine Gray G52 42 Tapped PRA1920TPL1 PSC20610BAC2 2082 x 609 x 999 81.98 x 23.96 x 39.32 Server, AC-Ready DataCom Black G52 42 Square PRA1920THL1 PSC20610GAC2 2082 x 609 x 999 81.98 x 23.96 x 39.32 Server, AC-Ready ProLine Gray G52 42 Square PRA1920THL1
17x001.07 VA Mail Room BID Question #29 RECV'D VIA EMAIL 04/01/21
05/04/2021 15:03 Page 1 of 6 http://hoffman.nvent.com/en/hoffman/PDCP2078B12 http://hoffman.nvent.com/en/hoffman/PDCP2078G12 http://hoffman.nvent.com/en/hoffman/PSC20610B12 http://hoffman.nvent.com/en/hoffman/PSC20610G12 http://hoffman.nvent.com/en/hoffman/PDCP2078BAC http://hoffman.nvent.com/en/hoffman/PDCP2078GAC http://hoffman.nvent.com/en/hoffman/PSC20610BAC http://hoffman.nvent.com/en/hoffman/PSC20610GAC http://hoffman.nvent.com/en/hoffman/PDCP2078BAC2 http://hoffman.nvent.com/en/hoffman/PDCP2078GAC2 http://hoffman.nvent.com/en/hoffman/PSC20610BAC2 http://hoffman.nvent.com/en/hoffman/PSC20610GAC2
PH 763.422.2661nVent.com/HOFFMAN networking 2Spec-00125 P
Package Components and Replacement Parts Catalog Number AxBxC mm AxBxC in. Description Finish PFD2078B 2000 x 700 x 800 78.70 x 27.60 x 31.50 Frame Black PFD2078G 2000 x 700 x 800 78.70 x 27.60 x 31.50 Frame Gray PFD20610B 2000 x 600 x 1000 78.70 x 23.60 x 39.40 Frame Black PFD20610G 2000 x 600 x 1000 78.70 x 23.60 x 39.40 Frame Gray PDWG206B 2000 x 600 78.70 x 23.60 Window Doors Black PDWG206G 2000 x 600 78.70 x 23.60 Window Doors Gray PDWG207B 2000 x 700 78.70 x 27.60 Window Doors Black PDWG207G 2000 x 700 78.70 x 27.60 Window Doors Gray PDS206B 2000 x 600 78.70 x 23.60 Solid Doors Black PDS206G 2000 x 600 78.70 x 23.60 Solid Doors Gray PDS207B 2000 x 700 78.70 x 27.60 Solid Doors Black PDS207G 2000 x 700 78.70 x 27.60 Solid Doors Gray PSS208B 2000 x 800 78.74 x 31.50 Solid Sides Black PSS208G 2000 x 800 78.74 x 31.50 Solid Sides Gray PSS2010B 2000 x 1000 78.74 x 39.37 Solid Sides Black PSS2010G 2000 x 1000 78.74 x 39.37 Solid Sides Gray PSS208ACB 2000 x 800 78.74 x 31.50 Sides with AC Cutout Black PSS208ACG 2000 x 800 78.74 x 31.50 Sides with AC Cutout Gray PSS2010ACB 2000 x 1000 78.74 x 39.37 Sides with AC Cutout Black PSS2010ACG 2000 x 1000 78.74 x 39.37 Sides with AC Cutout Gray PSS208AC2B 1939 x 753 x 25 76.34 x 29.66 x 0.99 Sides with AC Cutout Black PSS208AC2G 1939 x 753 x 25 76.34 x 29.66 x 0.99 Sides with AC Cutout Gray PSS2010AC2B 1939 x 953 x 25 76.34 x 37.54 x 0.99 Sides with AC Cutout Black PSS2010AC2G 1939 x 953 x 25 76.34 x 37.54 x 0.99 Sides with AC Cutout Gray Pt78B 700 x 800 27.56 x 31.50 Top Black Pt78G 700 x 800 27.56 x 31.50 Top Gray Pt610B 600 x 1000 23.62 x 39.37 Top Black Pt610G 600 x 1000 23.62 x 39.37 Top Gray PBMG78B 700 x 800 27.60 x 31.50 Mobile Base Black PBMG610B 600 x 1000 23.60 x 39.37 Mobile Base Gray
17x001.07 VA Mail Room BID Question #29 RECV'D VIA EMAIL 04/01/21
05/04/2021 15:03 Page 2 of 6 http://hoffman.nvent.com/en/hoffman/PFD2078B http://hoffman.nvent.com/en/hoffman/PFD2078G http://hoffman.nvent.com/en/hoffman/PFD20610B http://hoffman.nvent.com/en/hoffman/PFD20610G http://hoffman.nvent.com/en/hoffman/PDWG206B http://hoffman.nvent.com/en/hoffman/PDWG206G http://hoffman.nvent.com/en/hoffman/PDWG207B http://hoffman.nvent.com/en/hoffman/PDWG207G http://hoffman.nvent.com/en/hoffman/PDS206B http://hoffman.nvent.com/en/hoffman/PDS206G http://hoffman.nvent.com/en/hoffman/PDS207B http://hoffman.nvent.com/en/hoffman/PDS207G http://hoffman.nvent.com/en/hoffman/PSS208B http://hoffman.nvent.com/en/hoffman/PSS208G http://hoffman.nvent.com/en/hoffman/PSS2010B http://hoffman.nvent.com/en/hoffman/PSS2010G http://hoffman.nvent.com/en/hoffman/PSS208ACB http://hoffman.nvent.com/en/hoffman/PSS208ACG http://hoffman.nvent.com/en/hoffman/PSS2010ACB http://hoffman.nvent.com/en/hoffman/PSS2010ACG http://hoffman.nvent.com/en/hoffman/PSS208AC2B http://hoffman.nvent.com/en/hoffman/PSS208AC2G http://hoffman.nvent.com/en/hoffman/PSS2010AC2B http://hoffman.nvent.com/en/hoffman/PSS2010AC2G http://hoffman.nvent.com/en/hoffman/PT78B http://hoffman.nvent.com/en/hoffman/PT78G http://hoffman.nvent.com/en/hoffman/PT610B http://hoffman.nvent.com/en/hoffman/PT610G http://hoffman.nvent.com/en/hoffman/PBMG78B http://hoffman.nvent.com/en/hoffman/PBMG610B nVent.com/HOFFMANSUBJECT TO CHANGE WITHOUT NOTICEnetworking3 Spec-00125 P air Conditioner Sizing
Air conditioners are appropriate for applications in which:
| • | The temperature inside the enclosure must be maintained at or below ambient temperature. |
| • | Humidity must be removed from the enclosure. |
| • | Ambient air contaminants must be kept out of the enclosure. |
The following air conditioner sizing procedure applies to uninsulated, sealed and gasketed enclosures in indoor locations.
Step 1. determine the internal heat load in watts (w) Add the maximum heat output specifications for all equipment to be installed in cabinet.
Conversion: 1 W = 3.413 BTU/hr.
Step 2. Determine the desired temperature difference (ΔT) between the ambient temperature and the temperature inside the cabinet
| Subtract | the | desired | maximum | temperature | inside | the | cabinet | (Ti) | from | the | maximum | expected | temperature | (To) | outside | the | cabinet. |
| To - Ti | = | ΔT |
Conversion: 1 K or C ΔT = 1.8 F ΔT
Step 3. determine the exposed surface area of the cabinet in square feet.
Use the following formula to determine area when H, W and D are the cabinet dimensions in inches.
2[(H x W) + (H x D) + (W x D)] ÷144 = Area (ft.2) Conversion: If dimensions are in millimeters, substitute 1,000,000 for 144. Then multiply the result by 10.76 to convert from m2 to ft.2
Step 4. determine the air conditioner capacity required Use the following formula:
(Watts x 3.413) + [(1.25 x Area in ft.2) x ΔT in F] = BTU/hr.
Required air conditioner capacity in BTU/hr.
Use this formula to determine the required cooling capacity needed to maintain the desired operating temperature for your enclosure. This selection procedure applies to uninsulated, sealed, gasketed enclosures in indoor locations.
All industrial air conditioners are rated at their maximum operating point. Operating an air conditioner at temperatures below maximum conditions will result in reduced cooling capacity. In other words, operating 95 F ambient and 95 F enclosure temperature results in a 10 percent to 20 percent reduction in the rated capacity.
Full cooling capacity is probably not necessary at lower ambient temperatures.
17x001.07 VA Mail Room BID Question #29 RECV'D VIA EMAIL 04/01/21
05/04/2021 15:03 Page 3 of 6
PH 763.422.2661nVent.com/HOFFMAN networking 4Spec-00125 P g28 air Conditioner SPeCiFiCationS
Sealed encloSure cooling Air Conditioners nVent.com/HoFFmAnSUBJect to cHAnGe WItHoUt notIceThermal managemenT1 Spec-01257 A g28 air condiTioner SPeciFicaTionS
Performance Data G28 Models 4000/6000 BTU/Hr. (1172/1758 Watt)
CATALOG NUMBER
Indoor Model G280416G050 G280426G050 G280446G050 G280616G050 G280626G050 G280646G050 Indoor Model Stainless Steel Type 4X G280416G051 G280426G051 G280446G051 G280616G051 G280626G051 G280646G051 Indoor Model with Remote Access Control* G280416G060 G280426G060 G280446G060 G280616G060 G280626G060 G280646G060 Outdoor Model without Heat Pkg. G280416G100 G280426G100 G280446G100 G280616G100 G280626G100 G280646G100 Outdoor Model Partial Recessed Mount** G280416G101 G280426G101 G280446G101 G280616G101 G280626G101 G280646G101 Outdoor Model with Heat Pkg. G280416G150 G280426G150 — G280616G150 G280626G150 — Outdoor Model with Heat Pkg. Stainless Steel Type 4X G280416G151 G280426G151 — G280616G151 G280626G151 — cooling PerFormance Nominal:
BTU/Hr. 4000 4600/4900 4600/4900 6000/6400 6000/6400 5400/6000 Watts 1172 1347/1435 1347/1435 1757/1874 1757/1874 1581/1757
At 131 F/131 F (55 C/55 C):
BTU/Hr. (50/60 Hz) 3700 4600/4900 4600/4900 6000/6400 6000/6400 5400/6000 W (50/60 Hz) 1084 1347/1435 1347/1435 1757/1874 1757/1874 1581/1757
At 95 F/95 F (35 C/35 C):
BTU/Hr. (50/60 Hz) 3300/3410 4300/4600 4324/4655 5600/6000 5600/6000 5054/5685 W (50/60 Hz) 967/1000 1260/1364 1267/1364 1641/1758 1641/1758 1481/1666
Refrigerant R134A R407C R134A R407C R407C R134A Refrigerant Charge (ounces/grams) 12/340 20/567 16/454 20/567 20/567 16/454 Operating Temperature Range:
Maximum (°F/°C) 131 F/55 C 131 F/55 C 131 F/55 C 131 F/55 C 131 F/55 C 131 F/55 C Minimum (°F/°C) -40 F/-40 C -40 F/-40 C -40 F/-40 C -40 F/-40 C -40 F/-40 C -40 F/-40 C
Air Flow at 0 Static Pressure:
Internal loop 50 Hz (CFM / m3/hr.) 151/256 189/321 189/321 189/321 189/321 189/321
External loop 50 Hz (CFM / m3/hr.) 284/482 291/494 291/494 291/494 291/494 291/494
Internal loop 60 Hz (CFM / m3/hr.) 183/310 221/375 221/375 221/375 221/375 221/375
External loop 60 Hz (CFM / m3/hr.) 290/492 300/509 300/509 300/509 300/509 300/509 Max. Heater W (Outdoor Models) 2000 2000 NA 2000 2000 NA elecTrical daTa Rated Voltage 115 230 400/460 3~ 115 230 400/460 3~ Frequency (Hz) 50/60 50/60 50/60 50/60 50/60 50/60 Operating Range +/- 10% +/- 10% +/- 10% +/- 10% +/- 10% +/- 10% Max. Power Consumption (W at 50/60 Hz) 465/1055 1058/1334 680/874 1138.5/1311 1058/1334 680/874 Max. Nominal Current (A at 50/60 Hz) 10.4/10.1 4.6/5.8 1.7/1.9 9.9/11.4 4.6/5.8 1.7/1.9 Starting Current (A) 36.2 17.7 7.7 36.2 17.7 7.7 Agency Approvals UL/cUL Listed
CE
EAC
Power Input Description Terminal Block encloSure ProTecTion UL Type Type 12, 3R, 4 Standard**
Type 4X Stainless Steel Optional conTroller Description Basic Mechanical Thermostat Thermostat Location Enclosure Side on All Base Models Factory Thermostat Setting (°F/°C) 80/27 80/27 80/27 80/27 80/27 80/27
SOUND LEVEL
At 1.5 Meters 68 dB(A) uniT conSTrucTion Material Galvanized Sheet Metal Standard (Optional: Stainless Steel) Finish Powder Coat RAL 7035 Light Gray Standard acceSSorieS EASYSWAP Adaptor Plenum (GENESIS M28) Enables SPECTRACOOL to be mounted to GENESIS M28 air conditioner cutout
Catalog Number PLM28G28 EASYSWAP Adaptor Plenum (T-Series T29) Enables SPECTRACOOL to be mounted to T-Series T29 air conditioner cutout
Catalog Number PLT29G28 uniT dimenSionS Height (in./mm) 28.55/725.1 Width (in./mm) 16.97/431.1 Depth (in./mm) 10.10/256.6 Weight (lb./kg) 84/38 84/38 84/38 84/38 84/38 84/38 *Units with Remote Access Control utilize a digital controller and communicate via EtherNet/IP, Profinet, Modbus TCP/IP and SNMP over ethernet or modbus RTU over
USB.
**Outdoor Model Partial Recessed Mount units are UL Type 12, 3R only.
05/04/2021 15:03 Page 4 of 6 nVent.com/HOFFMANSUBJECT TO CHANGE WITHOUT NOTICEnetworking5 Spec-00125 P g52 air Conditioner SPeCiFiCationS
Sealed encloSure cooling Air Conditioners nVent.com/HoFFmAnSUBJect to cHAnGe WItHoUt notIceThermal managemenT1 Spec-01258 A g52 air condiTioner SPeciFicaTionS
Performance Data G52 Models 8000/12000 BTU/Hr. (2300/3500 Watt)
CATALOG NUMBER
Indoor Model G520816G050 G520826G050 G520846G050 G521216G050 G521226G050 G521246G050 Indoor Model Stainless Steel Type 4X G520816G051 G520826G051 G520846G051 G521216G051 G521226G051 G521246G051 Indoor Model with Remote Access Control* G520816G060 G520826G060 G520846G060 G521216G060 G521226G060 G521246G060 Outdoor Model without Heat Pkg. G520816G100 G520826G100 G520846G100 G521216G100 G521226G100 G521246G100 Outdoor Model Partial Recessed Mount** G520816G101 G520826G101 G520846G101 G521216G101 G521226G101 G521246G101 Outdoor Model with Heat Pkg. G520816G150 G520826G150 G520846G150 G521216G150 G521226G150 G521246G150 Outdoor Model with Heat Pkg. Stainless Steel Type 4X G520816G151 G520826G151 G520846G151 G521216G151 G521226G151 G521246G151 cooling PerFormance Nominal:
BTU/Hr. 8000 8000 8000 12000 12000 12000 Watts 2300 2300 2300 3500 3500 3500
At 131 F/131 F (55 C/55 C):
BTU/Hr. 7300/8200 7300/8200 8800/9800 12000/12500 12000/12500 11100/12000 Watts 2139/2403 2139/2403 2578/2871 3516/3662 3516/3662 3252/3516
At 95 F/95 F (35 C/35 C):
BTU/Hr. 6000/6800 6000/6800 7400/8200 9900/10700 9900/10700 9900/10700 Watts 1758/1992 1758/1992 2168/2402 2900/3135 2900/3135 2900/3135
Refrigerant R134a R134a R134a R134a R134a R134a Refrigerant Charge (ounces/grams) 24/680 24/680 24/680 38/1077 38/1077 38/1077 Operating Temperature Range:
Maximum (ºF/ºC) 131/55 131/55 131/55 131/55 131/55 131/55 Indoor Minimum (ºF/ºC) 50/10 50/10 50/10 50/10 50/10 50/10 Outdoor Minimum (ºF/ºC) -40/-40 -40/-40 -40/-40 -40/-40 -40/-40 -40/-40
Airflow at 0 Static Pressure:
Internal loop 50 Hz (CFM / m3/hr.) 285/484 285/484 285/484 287/487 287/487 287/487
External loop 50 Hz (CFM / m3/hr.) 650/1104 650/1104 650/1104 635/1078 635/1078 635/1078
Internal loop 60 Hz (CFM / m3/hr.) 310/527 310/527 310/527 305/518 305/518 305/518
External loop 60 Hz (CFM / m3/hr.) 700/1189 700/1189 700/1189 650/1104 650/1104 650/1104 Max. Heater W (Outdoor Models): 2000 2000 2000 2000 2000 2000 elecTrical daTa Rated Voltage 115 230/208-230 400/460 3~ 115 230/208-230 400/460 3~ Frequency (Hz) 50/60 50/60 50/60 50/60 50/60 50/60 Operating Range +/- 10% +/- 10% +/- 10% +/- 10% +/- 10% +/- 10% Max. Power Consumption (W) 1250/1415 1250/1415 806/957*** 2100/2427 1830/2130 910/1106*** Max. Nominal Current (A at 50/60 Hz) 11.2/12.3 5.6/7.0-6.2 3.1/3.2 16.1/21.0 9.1/10.6-9.5 3.6/3.5 Starting Current (A) 48 27 16 57 38 16 Agency Approvals UL/cUL Listed
CE
EAC
Others available upon request Power Input Description Terminal Block encloSure ProTecTion UL Type Type 12, 3R, 4 standard**
Type 4X Stainless steel optional International Rating IP56 internal loop
IP34 external loop conTroller Description Basic mechanical thermostat with digital display Thermostat Location Enclosure side on all base models Digital Display Location:
Indoor Models Ambient side Outdoor Models Enclosure side Factory Thermostat Setting (F/C) 80/27
SOUND LEVEL
At 1.5 Meters 68 dB(A) uniT conSTrucTion Material Galvanized sheet metal standard
Stainless steel optional Finish RAL 7035 light-gray, semi-textured powder-coat paint standard
Other colors available acceSSorieS EASYSWAP Adaptor Plenum (GENESIS M52) Enables SPECTRACOOL to be mounted to a GENESIS M52 air conditioner cutout
Catalog Number PLM52G52 uniT dimenSionS Height (in./mm) 52.69/1338 Width (in./mm) 17.12/435 Depth (in./mm) 11.66/296 Weight (lb./kg) 128/58.1 128/58.1 138/62.6 131/59.4 131/59.4 141/64.0 *Units with Remote Access Control utilize a digital controller and communicate via EtherNet/IP, Profinet, Modbus TCP/IP and SNMP over ethernet or modbus RTU over
USB.
**Outdoor Model Partial Recessed Mount units are UL Type 12, 3R only.
***Watts based on .65 power factor.
Spec-01258.indd 1 2/22/2019 1:06:42 PM
05/04/2021 15:03 Page 5 of 6
File details come from the government source that posted it. Updated .