5-B297 - Record drawings and HAZMAT report.pdf

PDF 11 MB Posted

Attached to
Y1AZ--691-20-151- Renovate Space for Mail room in b297
Solicitation number
36C25821B0011
Issued by

About this file

This federal solicitation is for renovation services to convert space for a mail room and reprographics area in Building 297 at the VA Greater Los Angeles Healthcare System campus. The scope of work involves construction of the mail room and reprographics spaces, remodeling bathrooms, a break room and electrical room, as well as exterior painting and metal panel repairs. Additional requirements include ADA parking stalls and path of travel improvements in the existing parking lot. The contractor must verify all as-built site conditions and complete work in compliance with applicable codes, standards and VA program guides. The performance period is 290 calendar days. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22.

View the file

Other files

File Type Posted
Updated TOC Div 27 spec section-r.pdf PDF
36C25821B0011 0004.docx DOCX document
3- 08 71 13 Automatic door operator.pdf PDF
23-IMG_0991.jpg JPG image
FileCab A B297 - Pocket 13 Folder 4 1 thru 5 B297 1948.pdf PDF
4-IT Data Rack.pdf PDF
19-Ceiling-IMG_0956.jpg JPG image
6-Jamb-clarification.pdf PDF
6-Panels D and F- IMG_0972.jpg JPG image
16-Ceiling-IMG_0954.jpg JPG image
8-drawings with clouds-IN60-AF26-AF30.pdf PDF
2-VA.1- No change.pdf PDF
4-Panels A-B and C-IMG_0973.jpg JPG image
17- Ceiling-IMG_0953.jpg JPG image
9-Construction Barrier as noted on SOW.pdf PDF
3-West wall-IMG_0937.jpg JPG image
7-Panels D and F-close-up_0978.jpg JPG image
10-Panel E-IMG_0974.jpg JPG image
8-Panels G and H-IMG_0957.jpg JPG image
18-Ceiling-IMG_0968.jpg JPG image
5-Panels A-B and C-closeup_0979.jpg JPG image
12-Disconnect 1-IMG_0975.jpg JPG image
9-Panels G and H-close-up_0977.jpg JPG image
AF.26 - MAILROOM & REPROGRAPHICS - INTERIOR ELEVATION.pdf PDF
7- 08 71 00 revised-4-15-21.pdf PDF
AF.30- RESTROOM - ENLARGED ELEV.pdf PDF
22-Ceiling-IMG_0955.jpg JPG image
14-Transformer-IMG_0990.jpg JPG image
20-Ceiling.jpeg JPEG file
IN.60 - SCHEDULES_04132021.pdf PDF
1-South wall-IMG_0981.jpg JPG image
2-North and East wall-IMG_0982.jpg JPG image
21-Ceiling-IMG_0967.jpg JPG image
11-Panel E-close-up_0980.jpg JPG image
13-Disconnect 2-IMG_0976.jpg JPG image
15-Pull box-IMG_0965.jpg JPG image
691-20-151-B297 SOW REVISED.docx DOCX document
36C25821B0011 0003.docx DOCX document
S05 Request for Information Log Mail Reprographics Room v1.docx DOCX document
36C25821B0011 0002.docx DOCX document
36C25821B0011 0001.docx DOCX document
Sign-in sheets-691-20-151 29 March Site Walk.pdf PDF
VA Mailroom and Reprographics_Specifications_10-17-2020.pdf PDF
Wage Determination 03192021.pdf PDF
36C25821B0011.docx DOCX document
Self Performance Calculations.pdf PDF
DRAWINGS- FULL SET- 10-15-20- final.pdf PDF
GLA Construction Safety Requirements and permits forms.pdf PDF
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1.) ALL WIRING, INITIATING DEVICES, AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION (F/A PANEL TO SUPERVISE THE ANNUNCIATOR PANEL ALL CIRCUITS AND INITIATING DEVICES), 2.) WIRING SHALL NOT BE LOOPED THROUGH DEVICES; WIRE MUST BE CUT FOR IN AND OUT.

3.) POINT AND COMMON ANNUNCIATION PROHIBITED. NON-ADDRESSABLE CIRCUITS T-TAPPING IS PROHIBITED.

4.) ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED TO MANUFACTURERS SPECIFICATIONS.

5.) AUDIBILITY OF ALARM SHALL BE NOT LESS THAN 15dBA ABOVE AMBIENT SOUND, BUT NOT LESS THAN 75 dBA, THROUGHOUT AREA OF ALARM.

6.) AREAS HAVING MORE THAN 2 STROBES IN THE FIELD OF VIEW SHALL BE SYNCHRONIZED.

7.) SMOKE DETECTORS AND HEAT DETECTOR LOCATIONS ARE BASED ON SMOOTH CEILING WITH MAXIMUM HEIGHT OF 10 FEET

UNLESS OTHERWISE NOTED.

8.) STROBE LOCATION ARE BASED ON NFPA 72 REQUIREMENTS UNLESS OTHERWISE NOTED.

9.) WALL-MOUNTED STROBES SHALL HAVE THEIR BOTTOMS NOT LESS THAN 80 INCHES ABOVE FINISHED FLOOR AND NO GREATER

THAN 96 INCHES ABOVE FINISHED FLOOR.

10.) FIRE ALARM SIGNAL SHALL MEET ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL (TEMPORAL PATTERN).

11.) ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH N.E.C. ARTICLE 760, POWER LIMITED FIRE PROTECTIVE SIGNALING

CIRCUITS.

12.) UPON COMPLETION OF THE INSTALLATION OF THE FIRE ALARM SYSTEM, A SATISFACTORY TEST OF THE ENTIRE SYSTEM SHALL BE

MADE IN THE PRESENCE OF THE FIRE MARSHAL.

13.) A STAMPED SET OF APPROVED FIRE ALARM PLANS SHALL BE ON THE JOB SITE AND USED FOR INSTALLATION. ANY DEVIATION FROM APPROVED PLANS, INCLUDING THE SUBSTITUTION OF DEVICES, SHALL BE APPROVED BY THE FIRE MARSHAL.

14.) ANY DISCREPANCIES BETWEEN THE DRAWINGS AND THE CODE OR RECOGNIZED STANDARDS SHALL BE BROUGHT TO THE

ATTENTION OF THE INSPECTOR OF RECORD.

15.) ALL DEVICES OF THE FIRE ALARM SYSTEM SHALL BE APPROVED AND LISTED BY THE CALIFORNIA STATE FIRE MARSHAL.

16.) FIRE ALARM DEVICES SHALL BE INSTALLED PER N.F.P.A. 72.

17.) ALL WIRING SHALL BE INSTALLED IN CONDUIT. CONDUIT SIZE SHALL BE 3/4" MINIMUM UNLESS OTHERWISE NOTED.

18.) ALL CONDUCTORS ARE COPPER.

19.) SYSTEM IS POWER LIMITED.

20.) ALL CONDUIT AND J-BOXES SERVING FIRE ALARM CIRCUITS SHALL BE PAINTED RED AND LABELED FA.

21.) POWER FOR THE FIRE ALARM CONTROL PANEL IS TO BE PROVIDED BY A DEDICATED CIRCUIT BREAKER, AHEAD OF THE MAIN CIRCUIT BREAKER. INDICATE LOCATION OF THIS BREAKER AT THE FACP. BREAKER TO BE RED AND LABELED "FIRE ALARM

CONTROL DISCONNECT".

22.) ELECTRICAL POWER SERVICE SHALL BE ON A DEDICATED CIRCUIT(S). THE CIRCUIT(S) AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED (CIRCUIT BREAKERS SHALL BE LOCKED IN THE ON POSITION WITH AN APPROVED MECHANICAL CLIP.) CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT". THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE

PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.

23.) ALL OUTSIDE CONTROL VALVES, FLOW SWITCHES AND ELECTRICAL JUNCTION BOXES SHALL HAVE ELECTRICALLY SUPERVISED COVERS. ELECTRICAL JUNCTION BOXES MAY TAMPER PROOF SCREWS IN PLACE OF ELECTRICAL SUPERVISION. THIS PROVISION IS SPECIFICALLY DIRECTED TO EQUIPMENT USED OUTSIDE A BUILDING WHERE TAMPERING WITH THE FIRE ALARM SYSTEMS IS

POSSIBLE.

24.) PROVIDE ELECTRICAL MONITORING FOR ALL EXTERIOR CONTROL VALVES CONTROLLING THE WATER SUPPLY FOR THE SPRINKLER SYSTEMS. THIS INCLUDES, PIV'S, DOUBLE CHECK DETECTOR ASSEMBLY, ETC. 2007 CFC 903.4 ALL SECTIONAL CONTROL VALVES FEEDING THE ON-SITE WATER SUPPLIES ARE ELECTRONICALLY MONITORED. ALL CONTROL VALVES SHALL BE LOCKED IN THE POSITION WITH A NON-CASE-HARDENED LOCK. THE EXISTING BELOW GRADE SECTIONAL VALVES SHALL BE ELECTRONICALLY MONITORED. THE SECTIONAL VALVES SHALL BE WIRED TO THE CLOSEST RESPECTIVE BUILDING PER EXISTING CONDITIONS. WHERE A SECTIONAL AFFECTS THE WATER DISTRIBUTION TO MULTIPLE BUILDINGS, EACH BUILDING AFFECTED SHALL INDICATE A

SUPERVISORY CONDITION WHEN A VALVE IS IN THE OFF-NORMAL POSITION.

25.) FIRE ALARM CONDUCTORS USED IN WET OR UNDERGROUND LOCATIONS SHALL BE OF TYPE THWN.

26.) FIRE ALARM SYSTEM "RECORD OF COMPLETION" DOCUMENT SHALL BE PROVIDED TO THE CLIENT ALONG WITH THE OTHER REQUIRED CLOSE-OUT DOCUMENTATION AT THE TIME OF SYSTEM ACCEPTANCE AND APPROVAL PER NFPA 72.

27.) ELECTRICAL EQUIPMENT SHALL BE LISTED BY A CITY OF LOS ANGELES RECOGNIZED ELECTRICAL TESTING LABORATORY OR

APPROVED BY THE DEPARTMENT.

APPLICABLE CODES & REGULATIONS

2010 BUILDING CODES WITH AMENDMENTS

2010 CALIFORNIA ELECTRICAL CODE

2010 MECHANICAL CODE

2010 PLUMBING CODE

2010 FIRE CODE (CFC) WITH JANUARY 1, 2009 SUPPLEMENT

2010 NFPA 72 WITH CALIFORNIA AMENDMENTS

TITLE 19, C.C.R., PUBLIC SAFETY

STATE FIRE MARSHALL REGULATIONS

CAMPUS INDEX

GENERAL NOTES

ABBREVIATIONS

BP BACKFLOW PREVENTER

CSFD COMBINATION SMOKE / FIRE DAMPER

EOL END-OF-LINE RESISTOR

EX EXISTING DEVICE TO REMAIN

FACP FIRE ALARM CONTROL PANEL

FATC FIRE ALARM TERMINAL CABINET

LRM LOCAL RAIL MODULE

N NEW DEVICE

PIV POST INDICATOR VALVE

FPL FIRE-POWER LIMITED

FPLP FIRE-POWER LIMITED PLENUM

FPLR FIRE-POWER LIMITED RISER

TP TWISTED PAIR

TSP TWISTED SHIELDED PAIR

THHN "T" THERMOPLASTIC INSULATED CABLE

"HH" MEANS THAT THE WIRE IS HEAT RESISTANT AND CAN WITHSTAND

A HIGHER TEMPERATURE (UP TO 194° F)

"N" NYLON COATING THAT COVERS WIRE INSULATION

THWN "T" THERMOPLASTIC INSULATED CABLE

"H" MEANS WIRE IS HEAT RESISTANT

"W" MEANS WIRE IS APPROVED FOR DAMP/WET LOCATIONS

"N" NYLON COATING THAT COVERS WIRE INSULATION

WP WEATHERPROOF DEVICE

SCOPE OF WORK

1.) INSTALLATION OF (1) NEW FIRE ALARM CONTROL PANEL ON THE GROUND FLOOR AS SHOWN ON FLOOR PLANS. CONNECT TO THE EXISTING MONITOR MODULES FOR ALARM, SUPERVISORY AND TROUBLE SIGNALS TO THE EXISTING SEIMENS APOGEE

(EST3) NETWORK PANEL.

2.) ALL INITIATING DEVICES ARE ADDRESSABLE.

3.) ALL NECESSARY WIRINGS SHOULD BE INSTALLED IN CONDUITS AND BOXES PROVIDED BY THE ELECTRICAL CONTRACTOR.

4.) INSTALLATION OF NEW NOTIFICATION & ADDRESSABLE DEVICE/S THROUGHOUT THE ENTIRE BUILDING AS SHOWN ON THE

PLANS.

5.) DEMOLITION OF ALL EXISTING FARADAY AND ISC FIRE ALARM PANELS AND DEVICES CONNECTED TO THESE PANELS.

SHEET INDEX

DRAWING TITLEDRAWING NUMBER

KEY MAP, SCOPE OF WORK, GENERAL NOTES, ABBREVIATION,

APPLICABLE CODES AND SHEET INDEX

WIRE/DEVICE/SYMBOL LEGENDS AND SEQUENCE OF OPERATIONS

FOR BUILDING 212, 218, 226 & 297

FIRE ALARM PANEL DETAILS AND DIMENSIONS

BUILDING 212: CALCULATIONS AND RISER DIAGRAM

DWG 1 OF 23

DWG 2 OF 23

DWG 3 OF 23

DWG 4 OF 23

DWG 5 OF 23

DWG 6 OF 23

DWG 7 OF 23

DWG 8 OF 23

FA-101

FA-102

FA-201

FA-202

FA-301

FA-302

FA-303

FA-304

3-WALL PENETRATION, MOUNTING HEIGHTS, WIRING/MOUNTING

DETAILS

BUILDING 212 - SALVATION ARMY

BUILDING 218 - ADMINISTRATION BUILDING

1.) INSTALLATION OF (1) NEW FIRE ALARM CONTROL PANEL ON THE GROUND FLOOR AS SHOWN ON FLOOR PLANS.

CONNECT TO THE EXISTING MONITOR MODULES FOR ALARM, SUPERVISORY AND TROUBLE SIGNALS TO THE EXISTING

SIEMENS APOGEE (EST3) NETWORK PANEL.

2.) ALL INITIATING DEVICES ARE ADDRESSABLE.

3.) WIRE CONDUCTORS SHALL BE INSTALLED IN CONDUIT AND BOXES PROVIDED BY THE ELECTRICAL CONTRACTOR.

4.) INSTALLATION OF NEW NOTIFICATION & ADDRESSABLE DEVICE/S THROUGHOUT THE BUILDING AS SHOWN ON THE PLANS.

BUILDING 226 - WADSWORTH THEATER

1.) INSTALLATION OF (1) NEW FIRE ALARM CONTROL PANEL ON THE BASEMENT FLOOR AS SHOWN ON FLOOR PLANS AND CONNECT TO THE EXISTING MONITOR MODULES FOR ALARM, SUPERVISORY AND TROUBLE SIGNALS TO THE EXISTING SIEMENS APOGEE (EST3)

NETWORK PANEL.

2.) ALL NECESSARY WIRING SHALL BE INSTALLED IN CONDUIT AND BOXES PROVIDED BY THE ELECTRICAL CONTRACTOR.

3.) INSTALLATION OF NEW NOTIFICATION & ADDRESSABLE DEVICE/S THROUGHOUT THE ENTIRE BUILDING AS SHOWN ON THE PLANS.

4.) AFTER ACCEPTANCE, REMOVE OLD FIRE ALARM PANEL AND ASSOCIATED DEVICES.

BUILDING 297 - SUPPLY WAREHOUSE

1.) INSTALLATION OF (1) NEW FIRE ALARM CONTROL PANEL IN THE WAITING AREA AS SHOWN ON FLOOR PLANS AND CONNECT TO THE EXISTING MONITOR MODULES FOR ALARM, SUPERVISORY AND TROUBLE SIGNALS TO THE EXISTING SIEMENS APOGEE (EST3)

NETWORK PANEL.

2.) INSTALLATION OF NEW FIRE ALARM ADDRESSABLE AND NOTIFICATION DEVICES THROUGHOUT THE WAREHOUSE BUILDING, AS

SHOWN ON FLOOR PLANS, TO MEET MINIMUM CODE COMPLIANT REQUIREMENTS PER NFPA 72.

3.) ALL INITIATING DEVICES ARE ADDRESSABLE.

4.) WIRE CONDUCTORS SHALL BE INSTALLED IN CONDUIT AND BOXES PROVIDED BY THE ELECTRICAL CONTRACTOR.

DEPARTMENT OF VETERANS AFFAIRS

11301 WILSHIRE BOULEVARD, LOS ANGELES, CA 90073

FIRE ALARM RETROFIT FOR:

BUILDING 212 - SALVATION ARMY

BUILDING 218 - ADMINISTRATION BUILDING

BUILDING 226 - WADSWORTH THEATRE

BUILDING 297 - SUPPLY WAREHOUSE

BUILDING 218: CALCULATIONS AND RISER DIAGRAM

BUILDING 226: CALCULATIONS AND RISER DIAGRAM

BUILDING 297: CALCULATIONS AND RISER DIAGRAM

BUILDING 212: GROUND FLOOR PLAN

BUILDING 212: FIRST FLOOR PLAN

DWG 9 OF 23

DWG 10 OF 23

FA-401

FA-402

FA-403

FA-404

FA-501

BUILDING 212: SECOND FLOOR PLAN

BUILDING 212: THIRD FLOOR PLAN

BUILDING 218: BASEMENT & GROUND FLOOR PLAN

BUILDING 218: FIRST FLOOR PLAN

BUILDING 218: SECOND FLOOR PLAN

FA-502

FA-503

FA-504

FA-505

FA-601

BUILDING 218: THIRD FLOOR PLAN

BUILDING 218: ROOF FLOOR PLAN

BUILDING 226: BASEMENT FLOOR PLAN

BUILDING 226: FIRST FLOOR PLAN

BUILDING 226: BALCONY FLOOR PLAN

FA-602

FA-603

FA-604

FA-701

FA-702

BUILDING 226: ATTIC FLOOR PLAN

BUILDING 297: AREA A FLOOR PLAN

BUILDING 297: AREA B FLOOR PLAN

DWG 11 OF 23

DWG 12 OF 23

DWG 13 OF 23

DWG 14 OF 23

DWG 15 OF 23

DWG 16 OF 23

DWG 17 OF 23

DWG 18 OF 23

DWG 19 OF 23

DWG 20 OF 23

DWG 21 OF 23

DWG 22 OF 23

DWG 23 OF 23

ARCHITECT/ENGINEERS/CONSULTANTS:

FP

12-28-11

691-11-107

218-1-3308-C

Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net

Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 FA-

Retrofit Fire Alarm System Buildings 212, 218, 226 & 297

212, 218, 226 & 297 KR

FOR CONSTRUCTION

vhaglasubhan Text Box Record for reference and information only.

Pages 1-7-As-built fire alarm drawings.

Pages 8-12- Existing break room door drawing (not as-built) Pages 13-14- Site Utilities (to be verified in field) Pages 15 18- Building original drawings (not as-built) pages 19-29- HAZMAT report for b297

15CD WALL-MOUNTED * STROBE, RED 7125-1657:0220

30CD WALL-MOUNTED * STROBE, RED

75CD WALL-MOUNTED * STROBE, RED

YES

ACTION

DEVICE

YES

YES

NO

NO

YES

YES

YES

YES

NO NONO

YES

YES

YES

NO

YES

YES

YES

YES

YES

YES

YES

YES

YESYES YESYES YES NO

YES

YES

YES

NO

YES

YES YESYESYES YESYESYES

YES

NO

YES

NO

NO

YES

YES

YES

YES

NO

YES

YES

(SUPERVISORY)

YES

YES

YES

YES

YES

YES

NO

YES

SIGA-270 MANUAL PULL STATION 2-1/4" BOX w/ SINGLE GANG RING

2-1/4" BOX 4" SQUARE w/ DOUBLE GANG RING

7150-1657:0129

G1RF-CVM (CHIME STROBE) 7125-1657:0220

7125-1657:0220

WALL-MOUNTED CHIME, REDG1RF-C 7125-1657:0220

DEVICE LEGEND

WIRE LEGEND SEQUENCE OF OPERATION: BUILDING 212

* RECOMMENDATION FOR CONDUIT SIZE BY N.E.C

MAXIMUM CONDUCTORS

1 1/2" 1 1/4"

INCHES

CONDUIT SIZE

2"

1" 3/4" 1/2"

#18 AWG

#16 AWG #14 AWG

MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METALLIC TUBING

TYPE

LETTERS

CONDUCTOR

SIZE

AWG/KCMIL

3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4

22 35 61 84 138 241 364 476 608 16 26 45 61 101 176 266 347 443 10 16 28 38 63 111 167 219 279 6 9 16 16 36 64 96 126 161

THHN

THWN

PERCENT AREA OF CONDUIT PERCENT REDUCTION PER - NUMBER

18AWG TWISTED SHIELDED PAIRS

TRADE SIZE

INCHES

INTERNAL

DIAMETER

INCHES

TOTAL

AREA 100%

SQ. IN.

OVER 2

WIRES 40%

SQ. IN.

1 2 3 4 5 6 7 8

3/4 0.824 0.533 0.213 19% 38% 57% 76% 95% X X X

1 1.049 0.864 0.346 12% 24% 36% 48% 6% 72% 84% 96%

1 1/4 1.380 1.496 0.598 7% 14% 21% 28% 35% 42% 49% 56%

1 1/2 1.610 2.036 0.814 5% 10% 15% 20% 25% 30% 35% 40%

2 2.067 3.356 1.342 3% 3% 9% 12% 15% 18% 21% 24%

BOX SIZE VS. NUMBER OF WIRES PER N.E.C.

J-BOXES

3-1/4X1-1/2 OCTAGON

3-1/2X1-1/2 OCTAGON

4X1-1/2 OCTAGON

4X1-1/8 OCTAGON

4X4X1-1/2 4X4X2-1/8 4X2-1/8X1-1/2 4X2-1/8X1-7/8 4X2-1/2X2-1/2

#14

#12

CONDUIT WIRE FILL CHART

SYMBOL DESCRIPTION C.S.F.M.MOUNTING INFORMATION

SYMBOL LEGEND

CATALOG #

MANUFACTURER

FIRE ALARM CONTROL PANEL FLUSH MOUNT ENCLOSURE

7165-1657:0244GE SECURITY

iO500G2

INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR 7272-1657:0299MOUNTS TO DETECTOR BASE

7270-1657:0288MOUNTS TO DETECTOR BASEINTELLIGENT HEAT DETECTOR

7300-1657:01204" SQUARE BOX STANDARD DETECTOR BASE

7300-1657:01204" SQUARE BOX STANDARD DETECTOR BASE

GE SECURITY

SIGA2-PS

GE SECURITY

SIGA2-HRS

GE SECURITY

SIGA-SB4

GE SECURITY

SIGA-SB4

7300-1657:0121DUAL MONITOR MODULE

SINGLE MONITOR MODULE 7300-1657:0121

GE SECURITY

SIGA-CT2

GE SECURITY

SIGA-CT1 2-1/4" BOX w/ SINGLE GANG RING

2-1/4" BOX w/ SINGLE GANG RING

CONTROL RELAY MODULE 7300-1657:0121GE SECURITY

SIGA-CR 2-1/4" BOX w/ SINGLE GANG RING

7320-1657:021815CD WALL-MOUNTED STROBE, REDGE SECURITY

---FIRE ALARM TERMINAL CABINET BACKBOX SUPPLIED & INSTALLED BY E.C.

---WATER FLOW SWITCH MONITORED BY HCI; SUPPLIED & INSTALLED BY

OTHERS

---VALVE TAMPER SWITCH MONITORED BY HCI; SUPPLIED & INSTALLED BY

---RISER DOWN ---

---RISER UP ---

EOL END-OF-LINE RESISTOR ---

FACP-2

M2

R

GE SECURITY

G1RF-VM

7320-1657:0218

7320-1657:0218

30CD WALL-MOUNTED STROBE, REDGE SECURITY

GE SECURITY

G1RF-VM

110CD WALL-MOUNTED STROBE, REDGE SECURITY

GE SECURITY

G1RF-VM

GE SECURITY

CS405-7AT 15/75 CD WALL-MOUNTED STROBE, RED MOUNTS TO 449-SERIES WEATHERPROOF BOX

WEATHERPROOF BOXGE SECURITY

7125-1657:0814

18 AMP HOUR SEALED LEAD ACID BATTERY MOUNTS INSIDE BC-1INTERSTATE

SLA1116

BATTERY CABINET TO BE DETERMINED IN THE FIELD.GE SECURITY

BC-1

7.2 AMP HOUR SEALED LEAD ACID BATTERY MOUNTS INSIDE POWER SUPPLY ENCLOSUREINTERSTATE

SLA1079

10 AMP BOOSTER POWER SUPPLY

7300-1657:0229

GE SECURITY

BPS10A

SURFACE MOUNT, BACKBOX PROVIDED BY HCI

& INSTALLED BY E.C.11

PS-?

SYNCHRONIZATION OUTPUT MODULE 7300-1657:0121GE SECURITY

SIGA-CC1SS

S

GE SECURITY31

56 GE SECURITY

BP

OTHERS

---BACKFLOW PREVENTER MONITORED BY HCI; SUPPLIED & INSTALLED BY---

---- OTHERS

A ADDRESSABLE CIRCUIT

CALLOUT USAGE

2#18 FPLR (UNSHIELDED)

TYPE

AUXILIARY CIRCUITC 2#14 THHN (UNSHIELDED)

(CONSTANT POWER)

TWISTED-PAIR, SOLID

STRANDED

ANNUNCIATOR CIRCUITP

2#16 FPLR (SHIELDED)

TWISTED-PAIR, SOLID

2#14 THHN

STRANDED (UNSHIELDED)

V SIGNAL CIRCUIT 2#14 THHN (UNSHIELDED)

ANN REMOTE ANNUNCIATOR 4" SQUARE BOXGE SECURITY

RLCD 7120-1657:0254

110CD WALL-MOUNTED * STROBE, RED 7125-1657:0220GE SECURITY

U UNDERGROUND CIRCUIT 2#14 THWN (UNSHIELDED)

---DOOR HOLDER CONTROLLED BY HCI; SUPPLIED & INSTALLED BY

OTHERS

V1-22

DENOTES NOTIFICATION

DEVICE NUMBER

DENOTES NOTIFICATION

CIRCUIT NUMBER

DENOTES DEVICE TYPE

DENOTES AUDIO/VISUAL

(CEILING-MOUNTED) DEVICE SYMBOL

15CD DENOTES CANDELA RATING

V1

EOL

END-OF-LINE RESISTOR

DENOTES END-OF-LINE FOR

CIRCUIT #V1

V1-22

DENOTES NOTIFICATION

DEVICE NUMBER

DENOTES NOTIFICATION

CIRCUIT NUMBER

DENOTES DEVICE TYPE

DENOTES VISUAL (CEILING-MOUNTED)

DEVICE SYMBOL

15CD DENOTES CANDELA RATING

V1

EOL

END-OF-LINE RESISTOR

DENOTES END-OF-LINE FOR

CIRCUIT #V1

C

ADDRESSABLE DEVICES:

NOTIFICATION APPLIANCES:

SURFACE MOUNT, BACKBOX SUPPLIED BY HCI

INSTALLED BY E.C.

CABINET SUPPLIED BY HCI, INSTALLED BY E.C.

WP

2 TRIM KIT GE SECURITY

SA-TRIM2 FLUSH MOUNT

CABINET SUPPLIED BY HCI, INSTALLED BY E.C.

010022

DENOTES DEVICE'S POINT ADDRESS

(DETECTOR DEVICES - 0001 THROUGH 0125

0251 THROUGH 0375)

DENOTES PANEL'S CABINET NUMBER

DEVICE'S SYMBOL (DETECTORS)

M

DENOTES DEVICE'S POINT ADDRESS

(MODULE DEVICES - 0126 THROUGH 0250

0376 THROUGH 0500)

DENOTES PANEL'S CABINET NUMBER

DEVICE'S SYMBOL (MODULES)

010126

YES

NO

YES

MANUAL

PULL

STATION

AREA

HEAT

DETECTOR

AREA

SMOKE

DETECTOR

ELEVATOR

LOBBY SMOKE

DETECTOR

ELEVATOR

MACHINE RM

SMOKE

DETECTORS

DUCT

SMOKE

DETECTOR

(SUPERVISORY)

SPRINKLER

WATER FLOW

SWITCH

SPRINKLER

VALVE TAMPER

SWITCH

SUPERVISORY

BACKFLOW

PREVENTER

SPECIAL

EXTINGUISHING

SYSTEM

BUILDING

POWER

FAILURE

SHUNTRIP

CIRCUIT

SUPERVISORY

ANNUNCIATE AT THE THE FIRE COMMAND

CENTER AND AT ALL REMOTE

ANNUNCIATORS

ANNUNCIATE AT 24-HOUR ATTENDED

CENTRAL MONITORING STATION

ACTIVATE AUDIBLE/VISUAL

ALARM SIGNAL ON

THROUGHOUT THE BUILDING

SHUT DOWN ALL AIR HANDLING UNIT (AC)

THROUGHOUT THE BUILDING

RELEASE ALL DOOR HOLDERS

RECALL ALL ELEVATORS

SERVING FLOOR OF ALARM

TO ALTERNATE FLOOR RECALL

NO

NO

NO NO

NO

NONO

2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER

2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER

2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER

2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER

2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER

2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER

2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER

2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER

GE SECURITY

757-1A-T WALL-MOUNTED WEATHERPROOF HORN , RED

7300-1657:0191BACKBOX PROVIDED BY HCI; INSTALLED BY E.C.GE SECURITY

757A-WB WEATHERPROOF BOX, RED, SURFACE

MOUNTS TO 757A-WB WEATHERPROOF BOX 7125-1657:0188

1 SIGNATURE LOOP EXPANSION MODULEGE SECURITY

XAL250 CONNECTS TO iO500G CIRCUIT BOARD 7165-1657:0244

WP

B BEAM SMOKE CIRCUIT 2#14 THHN (UNSHIELDED)

STRANDED

T 2#14 THHN (UNSHIELDED)

STRANDEDTEST STATION CIRCUIT

STRANDED

STRANDED

BLDG.

BLDG.

GCFR-HDVM 15CD CEILING-MOUNTED HORN STROBE, RED 7125-1657:0202

30CD CEILING-MOUNTED HORN STROBE, RED

75CD CEILING-MOUNTED HORN STROBE, RED

GCFR-HDVM

GCFR-HDVM

GE SECURITY

GE SECURITY

95CD CEILING-MOUNTED HORN STROBE, REDGCFR-HDVM

GE SECURITY12

2-1/4" BOX 4" SQUARE ELECTRICAL BOX-

GE SECURITY

C

7320-1657:021915CD CEILING-MOUNTED STROBE, REDGE SECURITY

GCFR-VM45 2-1/4" BOX 4" SQUARE ELECTRICAL BOX- 42

7125-1657:02022-1/4" BOX 4" SQUARE ELECTRICAL BOX

7125-1657:02022-1/4" BOX 4" SQUARE ELECTRICAL BOX

7125-1657:02022-1/4" BOX 4" SQUARE ELECTRICAL BOX

7320-1657:021930CD CEILING-MOUNTED STROBE, REDGE SECURITY

GCFR-VM17 2-1/4" BOX 4" SQUARE ELECTRICAL BOX- 16

7320-1657:021975CD CEILING-MOUNTED STROBE, REDGE SECURITY

GCFR-VM8 2-1/4" BOX 4" SQUARE ELECTRICAL BOX- 4

7320-1657:021995CD CEILING-MOUNTED STROBE, REDGE SECURITY

GCFR-VM10 2-1/4" BOX 4" SQUARE ELECTRICAL BOX- 1

---NETWORK PANEL ---- ---

---- -FACP-1

PIV ---POST INDICATOR VALVE MONITORED BY HCI; SUPPLIED & INSTALLED BY---

---- OTHERS- -

(USED FOR BLDG. 212 & 218)

BLDG.

FIRE ALARM CONTROL PANEL FLUSH MOUNT ENCLOSURE

7165-1657:0244GE SECURITY

iO64G2 CABINET SUPPLIED BY HCI, INSTALLED BY E.C.- - (USED FOR BLDG. 226 & 297)1

1 TRIM KITGE SECURITY

SA-TRIM1 FLUSH MOUNT- - 1

(USED FOR iO500G PANEL IN BLDG. 212 & 218)

(USED FOR iO64G PANEL IN BLDG. 226)

4 12 AMP HOUR SEALED LEAD ACID BATTERY MOUNTS INSIDE PANEL ENCLOSUREINTERSTATE

SLA1105- - 2

7270-1582:0101MOUNTS TO AR5 (ADAPTER PLATE)WEATHERPROOF HEAT DETECTOR

---ADAPTER PLATE

CHEMTRONICS

WPB/MPB-501

CHEMTRONICS

AR5

WP

(*CHIME IN BLDG. 212; HORN IN BLDG. 226)

(*CHIME IN BLDG. 212; HORN IN BLDG. 226)

(*CHIME IN BLDG. 212; HORN IN BLDG. 226)

(*CHIME IN BLDG. 212; HORN IN BLDG. 226)

G1RF-HDVM (HORN STROBE)

G1RF-CVM (CHIME STROBE)

G1RF-HDVM (HORN STROBE)

G1RF-CVM (CHIME STROBE)

G1RF-HDVM (HORN STROBE)

G1RF-CVM (CHIME STROBE)

G1RF-HDVM (HORN STROBE)

7320-1657:021875CD WALL-MOUNTED STROBE, REDGE SECURITY

G1RF-VM3 2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER- - 3

BD

BD

T

R 4- -

4 GE SECURITY

EC-50R- -

GE SECURITY

EC-50R

BEAM SMOKE DETECTOR - TRANSMITTER

CONVENTIONAL

BEAM SMOKE DETECTOR - REFLECTOR

CONVENTIONAL SURFACE MOUNT

SURFACE MOUNT 7260-1657:0233

7260-1657:0233

T 4- - 4 GE SECURITY

EC-LLT SURFACE MOUNT 7300-1657:0234TEST STATION

OS&Y ---OUTSIDE SCREW & YOKE VALVE MONITORED BY HCI; SUPPLIED & INSTALLED BY---

---- OTHERS- - -

---JUNCTION BOX---

----- - - SUPPLIED & INSTALLED BY OTHERS

2-1/4" BOX 4" SQUARE ELECTRICAL BOX

SINGLE MONITOR MODULE 7300-1657:0121GE SECURITY

SIGA-CT1 2-1/4" BOX w/ SINGLE GANG RING1- - 1

BLDG.

OVERALL

QTY.

H

SEQUENCE OF OPERATION: BUILDING 218

SEQUENCE OF OPERATION: BUILDING 226

SEQUENCE OF OPERATION: BUILDING 297

VALVE TAMPER

ACTIVATE AUDIBLE/VISUAL

THROUGHOUT

ALARM SIGNAL ON YES

ATTENDED REMOTE

ANNUNCIATE AT 24 HR.

FIRE CONTROL ROOM

ANNUNCIATE AT

LOCATION

ACTION

DEVICE

DETECTORS

YES

YES

SMOKE

AREA

NONO

FAILURE

YES

YES

POWER

BUILDING

YES

SWITCH

YES

STANDPIPE

SUPERVISORY

YES

DETECTOR

YES

YES

ROOM SMOKE

MACHINE

ELEVATOR

YES

DETECTOR

YES

YES

ROOM HEAT

MACHINE

ELEVATOR

SUPERVISORY

CIRCUIT

SHUNTRIP

YES

DETECTORS

YES

YES

SMOKE

LOBBY

ELEVATOR

NO

YES

YES

SERVING FLOOR OF ALARM

RECALL ALL ELEVATORS

ELEVATOR SHUNT TRIP

YES

STATIONS

YES

YES

PULL

MANUAL

NO

NO

NO

NO

YES

NO NO

YES YES

YES

NO

NO

YES NO

NONO

WATERFLOW

YES

YES

SWITCH

YES

STANDPIPE

NO

NO

NO

NO

VALVE

INDICATOR

YES

YES

POST

NO

NO

NO

PREVENTER

BACKFLOW

YES

YES

NO

SUPERVISORY SUPERVISORY

VALVE TAMPER

ACTIVATE AUDIBLE

THROUGHOUT

ALARM SIGNAL ON

FIRE CONTROL ROOM

ANNUNCIATE AT

ACTION

DEVICE

DETECTOR

SMOKE/HEAT

SWITCH

WATER FLOW

SPRINKLER

SWITCH

SPRINKLER

SUPERVISORY

RELEASE OF FIRE CURTAINS

ANNUNCIATE AT

24 HOUR CENTRAL STATION

YES

YES

YES

YES

NO

YES

YES YES YES

YES YES NO

SYSTEM

DELUGE

YES

YES

SHUTDOWN OF ALL

THROUGHOUT THE BUILDING

AIR HANDLING UNITS YES YES NO

YES

NO

YES

DETECTOR

BEAM

YES

YES

YES

YES

YES

SMOKE

PREVENTER

BACKFLOW

YES

YES

NO

NO

NO

PREVENTER

YES YES

ACTION

DEVICE

DETECTOR

YES

YES

SMOKE

AREA

SWITCH

WATER FLOW

YES

YES

SPRINKLER

NONO

FAILURE

YES

YES

POWER

BUILDING

YES

TAMPER

YES

BACKFLOW

SUPERVISORY

YES

PULL STATION

YES

YES

MANUAL

ACTIVATE AUDIBLE/VISUAL

ALARM SIGNAL THROUGHOUT

THE BUILDING

ANNUNCIATE AT 24 HOUR

ATTENDED REMOTE

LOCATION

ANNUNCIATE AT FIRE ALARM

CONTROL PANEL IN WAITING

AREA

ARCHITECT/ENGINEERS/CONSULTANTS:

FP

12-28-11

691-11-107

218-1-3308-C

Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net

Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 FA-

Retrofit Fire Alarm System Buildings 212, 218, 226 & 297

212, 218, 226 & 297 KR

FOR CONSTRUCTION

A

SECTION A-A

SYSTEM No. C-AJ-1063 (Formerly System No. 368)

L rating at Ambient- Less than 1 cfm/ sq ft (see item 4)

L rating at 400f- Less than 1 cfm/ sq ft (see item 4)

A 2

T RATING - 1/2 Hr

F RATING - 3 Hr

1B

1A

1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 INCHES THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100 - 150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED BLOCKS. MAX DIAMETER OF OPENING IS 4 INCHES. SEE CONCRETE BLOCK (CAZT) CATEGORY IN

THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.

2. STEEL PIPE - NOM 2 INCHES DIAMETER (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL SPACE OF 13/16 INCH IS REQUIRED WITHIN THE FIRESTOP SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH

SIDES OF FLOOR OR WALL ASSEMBLY.

3. PACKING MATERIAL - MINIMUM 3 INCHES THICKNESS OF MINIMUM 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM, PACKING MATERIAL TO BE

RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO

ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.

4. FILL, VOID OR CAVITY MATERIAL - SEALANT - MINIMUM 1/2 INCH THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF

WALL. WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.

MINNESOTA MINNING & MANUFACTURING CORPORATION - TYPES FB-2000, FB-2000+, FB-2003

(FLOORS ONLY) (NOTE: L RATINGS APPLY WHEN FB-2000+ IS USED.)

* BEARING THE UL CLASSIFICATION MARKING

FLOOR PENETRATION DETAIL WALL PENETRATION DETAIL

T RATING - 0 Hr

F RATING - 2 Hr

SYSTEM No. W-L-1082

3 1B

1A

1A

3 1B

1. WALL ASSEMBLY - THE FIRE RATED GYPSUM WALL BOARD/STUD WALL ASSEMBLY SHALL BE

CONSTRUCTED OF MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U4000

SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL

INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNELS STUDS.

WOOD STUDS TO CONSIST OF NUM 2 BY 4 INCHES LUMBER SPACED 16 INCHES O.C. STEEL

STUDS TO BE MIN 3-1/2 INCHES WIDE AND SPACES MAX 24 INCHES O.C.

B. WALL BOARD GYPSUM - TWO LAYERS OF NOM 5/8 INCH THICK GYPSUM WALL BOARD, AS

SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN DIAMETER OF OPENING IS 1-1/2

INCHES LARGER THAN THE OUTSIDE DIAMETER OF PIPE.

2. THROUGH-PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE OF 3/4 INCH IS REQUIRED WITHIN THE FIRESTOP SYSTEM.

PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE

FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 12 INCHES DIAMETER (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. CONDUIT - NOM 6 INCHES DIAMETER (OR SMALLER) STEEL CONDUIT.

C. CONDUIT - NOM 4 INCHES DIAMETER (OR SMALLER) STEEL ELECTRIC METALLIC TUBING.

D. COPPER TUBING - NOM 6 INCHES DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER

TUBING.

E. COPPER PIPE - NOM 6 INCHES DIAMETER (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

3. FORMING MATERIAL - NOM 1 INCH DIAMETER POLYETHYLENE BACKER ROD FRICTION FITTED INTO

OPENING AS A PERMANENT FORM. FORMING MATERIAL TO BE RECESSED FROM BOTH

SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL

MATERIAL.

4. FILL, VOID OR CAVITY MATERIAL - SEALANT - MINIMUM 5/8 INCH THICKNESS OF FILL MATERIAL

APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL ASSEMBLY.

MINNESOTA MINNING & MANUFACTURING CORPORATION - FB-2000+

*BEARING THE UL CLASSIFICATION MARKING

SECTION A-A

A

A

A

A

1. WALL ASSEMBLY - THE FIRE RATED GYPSUM WALL BOARD/STUD WALL ASSEMBLY SHALL BE

CONSTRUCTED OF MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U4000

SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL

INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNELS STUDS.

WOOD STUDS TO CONSIST OF NUM 2 BY 4 INCHES LUMBER SPACED 16 INCHES O.C. STEEL STUDS

TO BE MIN 3-5/8 INCHES WIDE AND SPACES MAX 24 INCHES O.C.

B. WALL BOARD GYPSUM - NOM 5/8 INCH THICK GYPSUM WALL BOARD, AS SPECIFIED IN THE

INDIVIDUAL WALL AND PARTITION DESIGN DIAMETER OF OPENING IS 1-1/2 INCHES LARGER

THAN THE OUTSIDE DIAMETER OF PIPE.

2. THROUGH-PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE OF 3/4 INCH IS REQUIRED WITHIN THE FIRESTOP SYSTEM.

PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE

FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 12 INCHES DIAMETER (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. CONDUIT - NOM 6 INCHES DIAMETER (OR SMALLER) ELECTRIC METALLIC TUBING OR STEEL

CONDUIT.

C. COPPER TUBING - NOM 6 INCHES DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER

TUBING.

D. COPPER PIPE - NOM 6 INCHES DIAMETER (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

3. FILL, VOID OR CAVITY MATERIAL - SEALANT - MINIMUM 5/8 INCH THICKNESS OF FILL MATERIAL

APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL ASSEMBLY.

MINNESOTA MINNING & MANUFACTURING CORPORATION - FB-2000+

*BEARING THE UL CLASSIFICATION MARKING

SECTION A-AA

A

SYSTEM No. W-L-1084

T RATING - 0 Hr

F RATING - 1 Hr

WALL PENETRATION DETAIL

3-WALL PENETRATIONS

SECTION A-A

DETAILS

SIGA-CT2 DUAL INPUT MODULE

NOT TO SCALE

CONTACT

STATUS/ALARM

EOLR

47K

STATUS/ALARM

CONTACT

EOLR

47K

0.8" (20 mm)

4.4" (112 mm)

2.0" (51 mm)

SIGA-SB4 DETECTOR BASE

NOT TO SCALE

4" SQUARE 1-1/2" DEEP

ELECTRICAL BOX BY E.C.

SIGA-SB4 DETECTOR BASE

NOT TO SCALE

WIRING DETAIL:

NOTE:

1.) A 4" BOX TRIM SKIRT/RING MUST

BE INSTALLED TO GIVE A

"FINISHED" APPEARANCE TO THE

4" BASE.

MOUNTING DIAGRAM:

ACCESS SLOT FOR TAMPER

RESIST MECHANISM

TAMPER-RESIST LEVER ARM

BREAK OFF TO DISABLE

(LOCATED ON BASE)

SIGA-TS

4" BOX TRIM SKIRT/RING

SIGA-CT1 SINGLE INPUT MODULE

NOT TO SCALE

CONTACT

STATUS/ALARM

EOLR

47K

FIRE

BETWEEN 80" A.F.F.

TO BOTTOM OF LENS

AND NO GREATER

THAN 96" A.F.F.

WALL MOUNTED

AUDIO/VISUAL

NOTIFICATION

APPLIANCE

CEILING MOUNTED

SMOKE DETECTOR

FIRE

ALARM

PULL

OF

FIRE 42" MIN. & 48" MAX.

FROM FLOOR LEVEL

TO THE HIGHEST

POINT OF THE

ACTIVATING

HANDLE OR LEVER

OF THE BOX

MANUAL PULL

STATION

CEILING LINE

ABOVE FINISHED FLOOR

FACTORY

CONNECTIONS:

DO NOT ALTER

GREEN LED

(NORMAL)

RED LED

(ALARM/ACTIVE)

4 3 2 1

TB1

SIGA-270 MANUAL PULL STATION

WIRING DETAIL: SINGLE-ACTION

DATA IN (+) DATA OUT (+)

FROM SIGNATURE

CONTROLLER OR

PREVIOUS DEVICE TO NEXT DEVICE

2-1/4" BOX w/

SINGLE GANG RING

(BY E.C.)

BACK

MOUNTING

PLATE (BY HCI)

TOGGLE

SWITCH

COVER

RELEASE

SCREW

NFPA 72, 2010 EDITION NOTES:

17.14.6 MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN 60" OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR.

17.14.7 MANUAL FIRE ALARM BOXES SHALL BE MOUNTED ON BOTH SIDES OF GROUPED OPENINGS OVER 40 FT IN WIDTH, AND WITHIN 60" OF

EACH SIDE OF THE OPENING.

17.14.8 ADDITIONAL MANUAL FIRE ALARM BOXES SHALL BE PROVIDED SO THAT THE TRAVEL DISTANCE TO THE NEAREST FIRE ALARM BOX WILL

NOT BE IN EXCESS OF 200 FT, MEASURED HORIZONTALLY ON THE SAME FLOOR.

SIGA-270 MANUAL PULL STATION

NOT TO SCALE

MOUNTING

SCREWS (BY HCI)

GLASS ROD

RELEASE LEVER

NOT TO SCALE

72" MAX

60" MIN.

& BOOSTER

POWER SUPPLY

60"

REMOTE

ANNUNCIATOR

BETWEEN 80" A.F.F.

TO BOTTOM OF LENS

AND NO GREATER

THAN 96" A.F.F.

WALL MOUNTED

AUDIBLE

NOTIFICATION

APPLIANCE

SIGA-CR: AHU SHUTDOWN

NOT TO SCALE

SIGA-CR: DOOR HOLDER CIRCUIT (24V)

NOT TO SCALE

SIGA-CC1S SIGNAL MODULE

NOT TO SCALE

DATA IN (-)

DATA IN (+)

DATA OUT (-)

DATA OUT (+)

(-) N N

H

(+) C

WHT

BLK

RED

BLU

YEL

ORG

C

N.C.

N.O.

120V CIRCUIT BREAKER

WHT

BLK

RED

BLU

YEL

ORG

C

N.C.

N.O.

SINGLE INPUT MODULE

CAT. NO. SIGA-CT1

REFER TO 387021 REV.2.0

FOR RATING AND

INSTALLATION INFO.

DATA IN (-)

DATA IN (+)

DATA OUT (-)

DATA OUT (+)

ELEVATOR

MAIN

C N .C

N .O

AUXILIARY

POWER

PAM1

RELAY

PR-1

RELAY

SIGA-CR: ELEVATOR SHUNT TRIP AND SUPERVISORY RECALL

CONTROL RELAY MODULE

CAT. NO. SIGA-CR

REFER TO 387023 REV.2.0

FOR RATING AND

INSTALLATION INFO.

NOT TO SCALE

TYPICAL STROBE CIRCUIT

NOT TO SCALE

TYPICAL HORN/STROBE CIRCUIT

NOT TO SCALE

TYPICAL CHIME/STROBE CIRCUIT

NOT TO SCALE

SIGA-DH DUCT DETECTOR HOUSING

NOT TO SCALE

AIR DUCT

MOUNTING DIAGRAM:

6 DUCT WIDTHS

(MINIMUM)

BEND OR OTHER

OBSTRUCTION

DUCT WIDTH

DUCT DETECTOR

LOCATION

THE DUCT DETECTOR HOUSING ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE

WITH NFPA 72 AND THE AUTHORITIES HAVING JURISDICTION. THE PREFERRED

LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT

WIDTHS FROM ANY BENDS OR OTHER OBSTRUCTION AS SHOWN ABOVE.

MOUNTING HEIGHTS DETAIL

NOT TO SCALE

USUALLY INSTALLED

BETWEEN 19" AND 24"

BELOW CEILING

BEAM

DETECTOR

FIRE ALARM

CONTROL PANEL

ARCHITECT/ENGINEERS/CONSULTANTS:

FP

12-28-11

691-11-107

218-1-3308-C

Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net

Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 FA-

Retrofit Fire Alarm System Buildings 212, 218, 226 & 297

212, 218, 226 & 297 KR

LINE

EARTH

GROUND

NEUTRAL

L

N

120VAC, 60Hz, 1.3A

DEDICATED BRANCH CIRCUIT

(PROVIDED BY E.C.)

TRANSFORMER

3.85"

29.5"

18.75"

BATTERY6.6"

7.2"

BATTERY

3/4" CONDUIT

SLA1116

12 VDC BATTERY, 18 A.H.

SLA1116

12 VDC BATTERY, 18 A.H.

3/4" CONDUIT

iO500 FIRE ALARM CONTROL PANEL (FOR BUILDING 212 & 218)

LINE

EARTH

GROUND

NEUTRAL

L

N

120VAC, 60Hz, 1.3A

DEDICATED BRANCH CIRCUIT

(PROVIDED BY E.C.)

TRANSFORMER

SLA1105

12 VDC BATTERY, 12 A.H.

SLA1105

12 VDC BATTERY, 12 A.H.

iO64 FIRE ALARM CONTROL PANEL (FOR BUILDING 226 & 297)

BPS10A BOOSTER POWER SUPPLY MAIN BOARD

iO SERIES CONTROL PANEL DIMENSION RLCD REMOTE ANNUNCIATOR

3.375 IN.

3.5 IN.

17 IN.

6.5 IN.

12 IN.

13 IN.

ALL KNOCKOUTS

FOR 3/4 IN. CONDUIT

FRONT VIEW

TOP VIEW

SI

D

E V

IE

W

SI

D

E V

IE

W

BPS10A POWER SUPPLY DIMENSION

ARCHITECT/ENGINEERS/CONSULTANTS:

FP

12-28-11

691-11-107

218-1-3308-C

Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net

Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 FA-

Retrofit Fire Alarm System Buildings 212, 218, 226 & 297

212, 218, 226 & 297 KR

SCALE:

N.T.S.

C

15CD15CD15CD

WP

N

C C C

95CD 95CD 95CD

V1-8 V1-7 V1-6 N N N

V1-4 N

V1-5

30CD

V1-3 N

V1-2

NEOL

V1

15CD

V1-1 N

CC

95CD95CD95CD95CD

J V2-1V2-2V2-5V2-6

NNNN

95CD

V2-3

NEOL

V2

PS-1

S S

FATC

P M2

95CD 95CD

C C

95CD 95CD

V3-4 V3-3 V3-2 V3-1

N N N NEOL

V3 J

CC

95CD 95CD

V4-4 V4-3 N N

95CD

V4-2 N

95CD

V4-1

NEOL

V4

1V1V1V2V

1V

1V1V1V

1V 1V 1V 1A,3V1A,3V 1V

1V 1V 1V 1V 1V

2V 1V1V1V1V

1A 1A

1A,1C 1A,1C

EXISTING FACP-1 BATTERY CALCULATIONS

POWER SUPPLY (PS-1) BATTERY & VOLTAGE DROP CALCULATIONS

COATED (OHM/kFT)

WIRE SIZE (AWG)

3.26

2.01

5.08

8.08

FEET = One way distance in feet measured

VOLTAGE DROP FOR A GIVEN

AMP = Amperes per terminal of load

WHERE:

= AMP x FEET x 3.26 x 2

OPERATING VOLTAGE

VOLTAGE DROP PERCENTAGE

= SYSTEM VOLTAGE (24)

LENGTH OF CONDUCTOR

= VOLTS x 100 from source of supply to load

FORMULA:

- VOLTS

0101 0103

1A

4V 1A,1C

RISER DIAGRAM

15CD

V2-4 N

1V

WP

V5 -1 N

1V

EOL

V5 P

1A,1C

120VAC DEDICATED

CIRCUIT PROVIDED

BY E.C.

TO MONITOR ALARM

TO MONITOR SUPERVISORY

TO MONITOR TROUBLE

H

120VAC DEDICATED

CIRCUIT PROVIDED

BY E.C.

ARCHITECT/ENGINEERS/CONSULTANTS:

FP

12-28-11

691-11-107

218-1-3308-C

FA-

Retrofit Fire Alarm System Buildings 212, 218, 226 & 297

297 KR

Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net

Corporate Office:1354 S. Parkside PlaceOntario, CA 91761

M

TC

HL

IN

E

SE

E

FA

-7

F

O R

C O

N

TIN

UA

TIO

N

15CDWP

N

M2

95CD 95CD

C

C

C

C

C

95CD 95CD

95CD 95CD

95CD 95CD

J

J

V3-4 V3-3

V1-8 V1-7

V3-2 V3-1

V1-6 V2-1

N N

N N

N N

N N

V1-4 N

V1-5

30CD

EOL

V3

EOL

V1

1A,1V 1A,1V 1A,1V 1A,1V 1V

1V1A,3V

1A,2V

1V 1V 1V

1V

1V

1V

2V

1A,3V

1 1 1 1

1V

1V

15CD

V1-2

N

1A

1A

1A,1V

VERIFY

LOCATION

AT FIELD

15CD

V1-3 N

C

P S

-1

15CD

S S

FA

TC

P

V1-1 N

1A,1C,1V

1A,1C

1A,1V

0103 N

N

P

1V 1A,1V

EXISTING NETWORK

PANEL

120VAC DEDICATED

CIRCUIT PROVIDED

BY E.C.

TO MONITOR ALARM

TO MONITOR SUPERVISORY

TO MONITOR TROUBLE

1A,1C

1V

WP

H

120VAC DEDICATED

CIRCUIT PROVIDED

BY E.C.

EOL

V5

V5-1 N

KEY PLAN : NTS

SCALE: 1/8" = 1'- 0"

ARCHITECT/ENGINEERS/CONSULTANTS:

FP

12-28-11

691-11-107

218-1-3308-C

FA-

Retrofit Fire Alarm System Buildings 212, 218, 226 & 297

297 KR

Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net

Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 701

SYMBOL DESCRIPTION

PS-1

INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR

M2 DUAL MONITOR MODULE

S SYNCHRONIZATION OUTPUT MODULE

10 AMP BOOSTER POWER SUPPLY

S

CEILING-MOUNTED HORN STROBE, RED

WP

WATERFLOW SWITCH

BP BACKFLOW PREVENTER

C

P

EOL END-OF-LINE RESISTOR

CEILING-MOUNTED STROBE, RED

CEILING-MOUNTED WEATHERPROOF STROBE, RED

* RECOMMENDATION FOR CONDUIT SIZE BY N.E.C

MAXIMUM CONDUCTORS

1 1/2" 1 1/4"

INCHES

CONDUIT SIZE

2"

1" 3/4" 1/2"

#18 AWG

#16 AWG #14 AWG

MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METALLIC TUBING

TYPE

LETTERS

CONDUCTOR

SIZE

AWG/KCMIL

3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4

22 35 61 84 138 241 364 476 608 16 26 45 61 101 176 266 347 443 10 16 28 38 63 111 167 219 279 6 9 16 16 36 64 96 126 161

THHN

THWN

PERCENT AREA OF CONDUIT PERCENT REDUCTION PER - NUMBER

18AWG TWISTED SHIELDED PAIRS

TRADE SIZE

INCHES

INTERNAL

DIAMETER

INCHES

TOTAL

AREA 100%

SQ. IN.

OVER 2

WIRES 40%

SQ. IN.

1 2 3 4 5 6 7 8

3/4 0.824 0.533 0.213 19% 38% 57% 76% 95% X X X

1 1.049 0.864 0.346 12% 24% 36% 48% 6% 72% 84% 96%

1 1/4 1.380 1.496 0.598 7% 14% 21% 28% 35% 42% 49% 56%

1 1/2 1.610 2.036 0.814 5% 10% 15% 20% 25% 30% 35% 40%

2 2.067 3.356 1.342 3% 3% 9% 12% 15% 18% 21% 24%

BOX SIZE VS. NUMBER OF WIRES PER N.E.C.

J-BOXES

3-1/4X1-1/2 OCTAGON

3-1/2X1-1/2 OCTAGON

4X1-1/2 OCTAGON

4X1-1/8 OCTAGON

4X4X1-1/2 4X4X2-1/8 4X2-1/8X1-1/2 4X2-1/8X1-7/8 4X2-1/2X2-1/2

#14

#12

CONDUIT WIRE FILL CHART

WIRE LEGEND

SYMBOL LEGEND

NOTES

J JUNCTION BOX

NETWORK PANEL

NOTIFICATION APPLIANCES TO BE INSTALLED UNDER SUSPENDED LIGHTS OR BEAMS

20 FEET ABOVE FINISHED FLOOR, PENDANT MOUNTING.

WALL-MOUNTED WEATHERPROOF HORN , RED

WP

H

A ADDRESSABLE CIRCUIT

CALLOUT USAGE

2#18 FPLR (UNSHIELDED)

TYPE

AUXILIARY CIRCUITC 2#14 THHN (UNSHIELDED)

(CONSTANT POWER)

TWISTED-PAIR, SOLID

STRANDED

V SIGNAL CIRCUIT 2#14 THHN (UNSHIELDED)

STRANDED

FIRE ALARM CONTROL PANEL

M

TC

HL

IN

E

SE

E

FA

-7

F

O R

C O

N

TIN

UA

TIO

N

C

C

C

C

95CD 95CD 95CD

95CD95CD

J

J

V2-2 V2-5 V2-6

V4-4V4-3

N N N

NN

95CD

V4-2 N

95CD

V4-1 N

95CD

V2-3 N

EOL

V2

EOL

V4

1V 1V 1V 1V

1V1V1V1V

1A,2V

1 1 1 1

1V

1V

15CD

V2-4 N

1V

KEY PLAN : NTS

SCALE: 1/8" = 1'- 0"

ARCHITECT/ENGINEERS/CONSULTANTS:

FP

12-28-11

691-11-107

218-1-3308-C

FA-

Retrofit Fire Alarm System Buildings 212, 218, 226 & 297

297 KR

Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net

Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 702

SYMBOL DESCRIPTION

PS-1

INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR

M2 DUAL MONITOR MODULE

S SYNCHRONIZATION OUTPUT MODULE

10 AMP BOOSTER POWER SUPPLY

S

CEILING-MOUNTED HORN STROBE, RED

WP

WATERFLOW SWITCH

BP BACKFLOW PREVENTER

C

P

EOL END-OF-LINE RESISTOR

CEILING-MOUNTED STROBE, RED

CEILING-MOUNTED WEATHERPROOF STROBE, RED

* RECOMMENDATION FOR CONDUIT SIZE BY N.E.C

MAXIMUM CONDUCTORS

1 1/2" 1 1/4"

INCHES

CONDUIT SIZE

2"

1" 3/4" 1/2"

#18 AWG

#16 AWG #14 AWG

MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METALLIC TUBING

TYPE

LETTERS

CONDUCTOR

SIZE

AWG/KCMIL

3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4

22 35 61 84 138 241 364 476 608 16 26 45 61 101 176 266 347 443 10 16 28 38 63 111 167 219 279 6 9 16 16 36 64 96 126 161

THHN

THWN

PERCENT AREA OF CONDUIT PERCENT REDUCTION PER - NUMBER

18AWG TWISTED SHIELDED PAIRS

TRADE SIZE

INCHES

INTERNAL

DIAMETER

INCHES

TOTAL

AREA 100%

SQ. IN.

OVER 2

WIRES 40%

SQ. IN.

1 2 3 4 5 6 7 8

3/4 0.824 0.533 0.213 19% 38% 57% 76% 95% X X X

1 1.049 0.864 0.346 12% 24% 36% 48% 6% 72% 84% 96%

1 1/4 1.380 1.496 0.598 7% 14% 21% 28% 35% 42% 49% 56%

1 1/2 1.610 2.036 0.814 5% 10% 15% 20% 25% 30% 35% 40%

2 2.067 3.356 1.342 3% 3% 9% 12% 15% 18% 21% 24%

BOX SIZE VS. NUMBER OF WIRES PER N.E.C.

J-BOXES

3-1/4X1-1/2 OCTAGON

3-1/2X1-1/2 OCTAGON

4X1-1/2 OCTAGON

4X1-1/8 OCTAGON

4X4X1-1/2 4X4X2-1/8 4X2-1/8X1-1/2 4X2-1/8X1-7/8 4X2-1/2X2-1/2

#14

#12

CONDUIT WIRE FILL CHART

WIRE LEGEND

SYMBOL LEGEND

NOTES

J JUNCTION BOX

NETWORK PANEL

NOTIFICATION APPLIANCES TO BE INSTALLED UNDER SUSPENDED LIGHTS OR BEAMS

20 FEET ABOVE FINISHED FLOOR, PENDANT MOUNTING.

WALL-MOUNTED WEATHERPROOF HORN , RED

WP

H

A ADDRESSABLE CIRCUIT

CALLOUT USAGE

2#18 FPLR (UNSHIELDED)

TYPE

AUXILIARY CIRCUITC 2#14 THHN (UNSHIELDED)

(CONSTANT POWER)

TWISTED-PAIR, SOLID

STRANDED

V SIGNAL CIRCUIT 2#14 THHN (UNSHIELDED)

STRANDED

FIRE ALARM CONTROL PANEL

vhaglasubhan Rectangle

HI LO S

HI LO S HI LO S HI LO S

NO

Oval vhaglasubhan Oval vhaglasubhan Oval vhaglasubhan Line vhaglasubhan Line vhaglasubhan Text Box The three circled manholes have been verified to be part of sanitary line to which the B297 bathrooms sewer line is connected. There is no manhole at the junction of the line from the bathrooms to the sanitary sewer line. Exact location of the connecting line is not available. Contractor to verify. Dotted red line is only an approximate guess to be confirmed by the contractor.

vhaglasubhan Typewritten Text vhaglasubhan Text Box 15" vhaglasubhan Text Box Sanitary Sewer Line vhaglasubhan Text Box B297 main gas distribution vhaglasubhan Text Box Gas Line

Rectangle

Original drawings of Warehouse- 1948- Not As-built

Project No. 22015.2030 869 rev2 August 2015

BUILDING 297 – SUPPLY WAREHOUSE BUILDING

Building No. 297 is the Supply Warehouse building and was built in 1948. The building has one floor and is 32,700 ft2 in size. The interior includes a mix of drywall and metal walls with metal and drop-in ceiling panels. The interior flooring finishes include 12”x12” vinyl floor tiles, carpet and bare concrete. The exterior is composed of both a raised and slab-on grade foundation with metal walls, metal windows and a sheet paper roof. The HVAC system is comprised of a forced air system with one air handling units located on the ground adjacent to the building and has 15 heating ceiling units.

Historical Data:

An asbestos survey was conducted by others. The data from this survey is listed below. The findings of this survey noted the following materials as being ACM:

• Transite wall panels;

• Mastic material (sealant);

• 9”x9” RFT & mastic; and

• Sink undercoating.

No documents were provided on any materials removed from the building.

Historical Data on LBP – LBP has been discovered in previous surveys on the structural trusses, beams, columns, and braces. Also, lead paint was discovered on the exterior dock plate.

Millennium’s Data:

No ACM was detected in the survey. No lead-based paint was detected in the survey.

The details of location, condition, color, substrate analytical results are provided in the appendix of this report.

Prior to making inferences and interpretations of these data, please refer to the Limitations section of this report.

The total ACM/Lead removal costs for building 297 are $9,600. The total asbestos removal cost is $9,600 and lead-based paint removal costs for building 297 are $0. Please refer to Tables 1-3 included herein.

West Los Angeles Building 297

Reading No Units Building name/# Location/Room Component Substrate Side Color Results PbC PbC Error 438 mg / cm ^2 calib calib calib CALIB calib Positive 1 0.1 439 mg / cm ^2 calib calib calib CALIB calib Positive 1 0.1 440 mg / cm ^2 VALA BLDG,297 Bathroom Baseboard Wood A Beige Negative 0.17 0.05 441 mg / cm ^2 VALA BLDG,297 lounge Window Wood D White Negative 0.1 0.04 442 mg / cm ^2 VALA BLDG,297 lounge Window Wood D White Negative 0.13 0.06 443 mg / cm ^2 VALA BLDG,297 lounge Window Wood D White Negative 0.13 0.04 444 mg / cm ^2 VALA BLDG,297 warehouse Door Metal C Green Negative 0.26 0.03 445 mg / cm ^2 VALA BLDG,297 Office Wall Metal A Beige Negative < LOD 0.03 446 mg / cm ^2 VALA BLDG,297 Office Wall Drywall A Beige Negative < LOD 0.03 447 mg / cm ^2 VALA BLDG,297 lounge Ceiling Drywall A White Negative 0.13 0.04 448 mg / cm ^2 VALA BLDG,297 Kitchen Wall Metal C Yellow Negative 0.24 0.03 449 mg / cm ^2 VALA BLDG,297 Bathroom Door Wood D White Negative 0.07 0.02 450 mg / cm ^2 VALA BLDG,297 Bathroom Door Frame Wood D Beige Negative 0.06 0.02 451 mg / cm ^2 VALA BLDG,297 warehouse Chair Rail Metal D Yellow Negative < LOD 0.03 452 mg / cm ^2 VALA BLDG,297 warehouse Chair Rail Metal D Yellow Negative < LOD 0.03 453 mg / cm ^2 VALA BLDG,297 warehouse Baseboard Wood C Brown Negative < LOD 0.03 454 mg / cm ^2 calib calib calib calib calib Positive 1 0.1 455 mg / cm ^2 calib calib calib calib calib Positive 1 0.1 456 mg / cm ^2 calib calib calib calib calib Positive 1 0.1

: Lead‐Based Paint : Lead‐Containing Paint

VA West Los Angeles Finish Schedule

Building 297

1st Floor - B297 - 1

Building 297 Room Surface Primary Material

Description Primary Color ACM Quantity

ACM

Condition

ACM LBP Quantity

LBP

Condition Lead Notes/Comments

First Floor 1, 2 & 3 Floor 12x12 Resilient Floor Tiles Beige No 0 N/A No 0 N/A First Floor 1, 2 & 3 Ceiling 2'x4' Lay-in Ceiling Panels White No 0 N/A No 0 N/A First Floor 1, 2 & 3 Wall(s) Drywall Walls Yellow No 0 N/A No 0 N/A First Floor 1, 2 & 3 Misc Rubber Cove Base W/ Mastic Tan No 0 N/A No 0 N/A First Floor 1, 2 & 3 Door/Door Frame Wood Door/Metal Frame Burgundy No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor 4 Floor 12x12 Resilient Floor Tiles Beige No 0 N/A No 0 N/A First Floor 4 Ceiling 2'x4' Lay-in Ceiling Panels White No 0 N/A No 0 N/A First Floor 4 Wall(s) Drywall Walls Yellow No 0 N/A No 0 N/A First Floor 4 Misc Rubber Cove Base W/ Mastic Tan No 0 N/A No 0 N/A First Floor 4 Door/Door Frame Wood Door/Metal Frame Burgundy No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor 4 Misc Wood Windows Yellow No 0 N/A No 0 N/A First Floor Bathroom Floor 12x12 Resilient Floor Tiles Beige No 0 N/A No 0 N/A First Floor Bathroom Wall(s) Drywall Walls Beige No 0 N/A No 0 N/A First Floor Bathroom Ceiling Solid Drywall Ceiling White No 0 N/A No 0 N/A First Floor Bathroom Door/Door Frame Wood Door/Wood Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Bathroom Misc Wood Windows White No 0 N/A No 0 N/A First Floor Bathroom Misc Wooden Baseboard Beige No 0 N/A No 0 N/A First Floor Kitchen Floor 12x12 Resilient Floor Tiles Beige No 0 N/A No 0 N/A First Floor Kitchen Wall(s) Drywall Walls White No 0 N/A No 0 N/A First Floor Kitchen Ceiling Solid Drywall Ceiling White No 0 N/A No 0 N/A First Floor Kitchen Door/Door Frame Wood Door/Wood Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Kitchen Misc Wood Windows White No 0 N/A No 0 N/A First Floor Kitchen Misc Wooden Baseboard White No 0 N/A No 0 N/A First Floor Men's Locker Ceiling 2'x4' Lay-in Ceiling Panels White No 0 N/A No 0 N/A First Floor Men's Locker Floor Carpeting over 12x12 Floor Tile Gray No 0 N/A No 0 N/A First Floor Men's Locker Wall(s) Drywall Walls White No 0 N/A No 0 N/A First Floor Men's Locker Door/Door Frame Wood Door/Metal Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Men's RR Floor 12x12 Resilient Floor Tiles White No 0 N/A No 0 N/A First Floor Men's RR Wall(s) Drywall Walls White No 0 N/A No 0 N/A

First Floor Men's RR Misc Metal Windows White No 0 N/A No 0 N/A

First Floor Men's RR Ceiling Solid Drywall Ceiling White No 0 N/A No 0 N/A First Floor Men's RR Door/Door Frame Wood Door/Wood Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Men's Shower Floor 12x12 Resilient Floor Tiles White/Beige No 0 N/A No 0 N/A First Floor Men's Shower Floor Ceramic Flooring - 4x4 White/Beige No 0 N/A No 0 N/A First Floor Men's Shower Wall(s) Ceramic Tile Walls - 4x4 White/Beige No 0 N/A No 0 N/A First Floor Men's Shower Wall(s) Drywall Walls White/Beige No 0 N/A No 0 N/A First Floor Men's Shower Misc Metal Windows Bare No 0 N/A No 0 N/A First Floor Men's Shower Ceiling Solid Drywall Ceiling White No 0 N/A No 0 N/A First Floor Men's Shower Door/Door Frame Wood Door/Metal Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Sink Room Floor Concrete - Bare No 0 N/A No 0 N/A First Floor Sink Room Wall(s) Drywall Walls Beige No 0 N/A No 0 N/A First Floor Sink Room Ceiling Solid Drywall Ceiling Beige No 0 N/A No 0 N/A First Floor Sink Room Misc Wooden Baseboard Green No 0 N/A No 0 N/A First Floor Sink Room Door/Door Frame Wooden Frame only White No 0 N/A No 0 N/A First Floor Storage Floor Concrete - Bare No 0 N/A No 0 N/A First Floor Storage Wall(s) Drywall Walls White No 0 N/A No 0 N/A First Floor Storage Ceiling Solid Drywall Ceiling White No 0 N/A No 0 N/A First Floor Storage Door/Door Frame Wood Door/Metal Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Training Room Ceiling 2'x4' Lay-in Ceiling Panels White No 0 N/A No 0 N/A First Floor Training Room Wall(s) Drywall Walls Yellow No 0 N/A No 0 N/A First Floor Training Room Misc Metal Baseboard Bare No 0 N/A No 0 N/A

First Floor Training Room Door/Door Frame Wood Door/Metal Frame Natural Wood/Bare Metal No* 0 N/A No 0 N/A * Possible asbestos core fire door

First Floor Training Room Wall(s) Wood Paneling Walls No 0 N/A No 0 N/A First Floor Warehouses 1,2, 3, 4 Floor Concrete - Bare No 0 N/A No 0 N/A vhaglasubhan Line

Line

VA West Los Angeles Finish Schedule

Building 297

1st Floor - B297 - 2

Building 297 Room Surface Primary Material

Description Primary Color ACM Quantity

ACM

Condition

ACM LBP Quantity

LBP

Condition Lead Notes/Comments

First Floor Warehouses 1,2, 3, 4 Door/Door Frame Metal Door Green No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Warehouses 1,2, 3, 4 Door/Door Frame Metal Roll-up Door Bare No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Warehouses 1,2, 3, 4 Ceiling Metal Roof/Ceiling Bare No 0 N/A No 0 N/A First Floor Warehouses 1,2, 3, 4 Wall(s) Metal Walls Bare No 0 N/A No 0 N/A First Floor Warehouses 1,2, 3, 4 Misc Metal Windows Bare No 0 N/A No 0 N/A First Floor Water Heater Room Floor Concrete - Bare No 0 N/A No 0 N/A First Floor Water Heater Room Wall(s) Drywall Walls Beige No 0 N/A No 0 N/A First Floor Water Heater Room Ceiling Solid Drywall Ceiling Beige No 0 N/A No 0 N/A First Floor Water Heater Room Misc Wood Baseboard Green No 0 N/A No 0 N/A First Floor Water Heater Room Door/Door Frame Wood Door/Wood Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door vhaglasubhan Line

Line

As-built fire alarm drawings

File details come from the government source that posted it. Updated .