5-B297 - Record drawings and HAZMAT report.pdf
PDF 11 MB Posted
- Solicitation number
- 36C25821B0011
About this file
This federal solicitation is for renovation services to convert space for a mail room and reprographics area in Building 297 at the VA Greater Los Angeles Healthcare System campus. The scope of work involves construction of the mail room and reprographics spaces, remodeling bathrooms, a break room and electrical room, as well as exterior painting and metal panel repairs. Additional requirements include ADA parking stalls and path of travel improvements in the existing parking lot. The contractor must verify all as-built site conditions and complete work in compliance with applicable codes, standards and VA program guides. The performance period is 290 calendar days. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1.) ALL WIRING, INITIATING DEVICES, AND ANNUNCIATOR PANEL SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION (F/A PANEL TO SUPERVISE THE ANNUNCIATOR PANEL ALL CIRCUITS AND INITIATING DEVICES), 2.) WIRING SHALL NOT BE LOOPED THROUGH DEVICES; WIRE MUST BE CUT FOR IN AND OUT.
3.) POINT AND COMMON ANNUNCIATION PROHIBITED. NON-ADDRESSABLE CIRCUITS T-TAPPING IS PROHIBITED.
4.) ALL DEVICES IN THE ALARM SYSTEM SHALL BE COMPATIBLE AND INSTALLED TO MANUFACTURERS SPECIFICATIONS.
5.) AUDIBILITY OF ALARM SHALL BE NOT LESS THAN 15dBA ABOVE AMBIENT SOUND, BUT NOT LESS THAN 75 dBA, THROUGHOUT AREA OF ALARM.
6.) AREAS HAVING MORE THAN 2 STROBES IN THE FIELD OF VIEW SHALL BE SYNCHRONIZED.
7.) SMOKE DETECTORS AND HEAT DETECTOR LOCATIONS ARE BASED ON SMOOTH CEILING WITH MAXIMUM HEIGHT OF 10 FEET
UNLESS OTHERWISE NOTED.
8.) STROBE LOCATION ARE BASED ON NFPA 72 REQUIREMENTS UNLESS OTHERWISE NOTED.
9.) WALL-MOUNTED STROBES SHALL HAVE THEIR BOTTOMS NOT LESS THAN 80 INCHES ABOVE FINISHED FLOOR AND NO GREATER
THAN 96 INCHES ABOVE FINISHED FLOOR.
10.) FIRE ALARM SIGNAL SHALL MEET ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL (TEMPORAL PATTERN).
11.) ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH N.E.C. ARTICLE 760, POWER LIMITED FIRE PROTECTIVE SIGNALING
CIRCUITS.
12.) UPON COMPLETION OF THE INSTALLATION OF THE FIRE ALARM SYSTEM, A SATISFACTORY TEST OF THE ENTIRE SYSTEM SHALL BE
MADE IN THE PRESENCE OF THE FIRE MARSHAL.
13.) A STAMPED SET OF APPROVED FIRE ALARM PLANS SHALL BE ON THE JOB SITE AND USED FOR INSTALLATION. ANY DEVIATION FROM APPROVED PLANS, INCLUDING THE SUBSTITUTION OF DEVICES, SHALL BE APPROVED BY THE FIRE MARSHAL.
14.) ANY DISCREPANCIES BETWEEN THE DRAWINGS AND THE CODE OR RECOGNIZED STANDARDS SHALL BE BROUGHT TO THE
ATTENTION OF THE INSPECTOR OF RECORD.
15.) ALL DEVICES OF THE FIRE ALARM SYSTEM SHALL BE APPROVED AND LISTED BY THE CALIFORNIA STATE FIRE MARSHAL.
16.) FIRE ALARM DEVICES SHALL BE INSTALLED PER N.F.P.A. 72.
17.) ALL WIRING SHALL BE INSTALLED IN CONDUIT. CONDUIT SIZE SHALL BE 3/4" MINIMUM UNLESS OTHERWISE NOTED.
18.) ALL CONDUCTORS ARE COPPER.
19.) SYSTEM IS POWER LIMITED.
20.) ALL CONDUIT AND J-BOXES SERVING FIRE ALARM CIRCUITS SHALL BE PAINTED RED AND LABELED FA.
21.) POWER FOR THE FIRE ALARM CONTROL PANEL IS TO BE PROVIDED BY A DEDICATED CIRCUIT BREAKER, AHEAD OF THE MAIN CIRCUIT BREAKER. INDICATE LOCATION OF THIS BREAKER AT THE FACP. BREAKER TO BE RED AND LABELED "FIRE ALARM
CONTROL DISCONNECT".
22.) ELECTRICAL POWER SERVICE SHALL BE ON A DEDICATED CIRCUIT(S). THE CIRCUIT(S) AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED (CIRCUIT BREAKERS SHALL BE LOCKED IN THE ON POSITION WITH AN APPROVED MECHANICAL CLIP.) CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT". THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL BE
PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT.
23.) ALL OUTSIDE CONTROL VALVES, FLOW SWITCHES AND ELECTRICAL JUNCTION BOXES SHALL HAVE ELECTRICALLY SUPERVISED COVERS. ELECTRICAL JUNCTION BOXES MAY TAMPER PROOF SCREWS IN PLACE OF ELECTRICAL SUPERVISION. THIS PROVISION IS SPECIFICALLY DIRECTED TO EQUIPMENT USED OUTSIDE A BUILDING WHERE TAMPERING WITH THE FIRE ALARM SYSTEMS IS
POSSIBLE.
24.) PROVIDE ELECTRICAL MONITORING FOR ALL EXTERIOR CONTROL VALVES CONTROLLING THE WATER SUPPLY FOR THE SPRINKLER SYSTEMS. THIS INCLUDES, PIV'S, DOUBLE CHECK DETECTOR ASSEMBLY, ETC. 2007 CFC 903.4 ALL SECTIONAL CONTROL VALVES FEEDING THE ON-SITE WATER SUPPLIES ARE ELECTRONICALLY MONITORED. ALL CONTROL VALVES SHALL BE LOCKED IN THE POSITION WITH A NON-CASE-HARDENED LOCK. THE EXISTING BELOW GRADE SECTIONAL VALVES SHALL BE ELECTRONICALLY MONITORED. THE SECTIONAL VALVES SHALL BE WIRED TO THE CLOSEST RESPECTIVE BUILDING PER EXISTING CONDITIONS. WHERE A SECTIONAL AFFECTS THE WATER DISTRIBUTION TO MULTIPLE BUILDINGS, EACH BUILDING AFFECTED SHALL INDICATE A
SUPERVISORY CONDITION WHEN A VALVE IS IN THE OFF-NORMAL POSITION.
25.) FIRE ALARM CONDUCTORS USED IN WET OR UNDERGROUND LOCATIONS SHALL BE OF TYPE THWN.
26.) FIRE ALARM SYSTEM "RECORD OF COMPLETION" DOCUMENT SHALL BE PROVIDED TO THE CLIENT ALONG WITH THE OTHER REQUIRED CLOSE-OUT DOCUMENTATION AT THE TIME OF SYSTEM ACCEPTANCE AND APPROVAL PER NFPA 72.
27.) ELECTRICAL EQUIPMENT SHALL BE LISTED BY A CITY OF LOS ANGELES RECOGNIZED ELECTRICAL TESTING LABORATORY OR
APPROVED BY THE DEPARTMENT.
APPLICABLE CODES & REGULATIONS
2010 BUILDING CODES WITH AMENDMENTS
2010 CALIFORNIA ELECTRICAL CODE
2010 MECHANICAL CODE
2010 PLUMBING CODE
2010 FIRE CODE (CFC) WITH JANUARY 1, 2009 SUPPLEMENT
2010 NFPA 72 WITH CALIFORNIA AMENDMENTS
TITLE 19, C.C.R., PUBLIC SAFETY
STATE FIRE MARSHALL REGULATIONS
CAMPUS INDEX
GENERAL NOTES
ABBREVIATIONS
BP BACKFLOW PREVENTER
CSFD COMBINATION SMOKE / FIRE DAMPER
EOL END-OF-LINE RESISTOR
EX EXISTING DEVICE TO REMAIN
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
LRM LOCAL RAIL MODULE
N NEW DEVICE
PIV POST INDICATOR VALVE
FPL FIRE-POWER LIMITED
FPLP FIRE-POWER LIMITED PLENUM
FPLR FIRE-POWER LIMITED RISER
TP TWISTED PAIR
TSP TWISTED SHIELDED PAIR
THHN "T" THERMOPLASTIC INSULATED CABLE
"HH" MEANS THAT THE WIRE IS HEAT RESISTANT AND CAN WITHSTAND
A HIGHER TEMPERATURE (UP TO 194° F)
"N" NYLON COATING THAT COVERS WIRE INSULATION
THWN "T" THERMOPLASTIC INSULATED CABLE
"H" MEANS WIRE IS HEAT RESISTANT
"W" MEANS WIRE IS APPROVED FOR DAMP/WET LOCATIONS
"N" NYLON COATING THAT COVERS WIRE INSULATION
WP WEATHERPROOF DEVICE
SCOPE OF WORK
1.) INSTALLATION OF (1) NEW FIRE ALARM CONTROL PANEL ON THE GROUND FLOOR AS SHOWN ON FLOOR PLANS. CONNECT TO THE EXISTING MONITOR MODULES FOR ALARM, SUPERVISORY AND TROUBLE SIGNALS TO THE EXISTING SEIMENS APOGEE
(EST3) NETWORK PANEL.
2.) ALL INITIATING DEVICES ARE ADDRESSABLE.
3.) ALL NECESSARY WIRINGS SHOULD BE INSTALLED IN CONDUITS AND BOXES PROVIDED BY THE ELECTRICAL CONTRACTOR.
4.) INSTALLATION OF NEW NOTIFICATION & ADDRESSABLE DEVICE/S THROUGHOUT THE ENTIRE BUILDING AS SHOWN ON THE
PLANS.
5.) DEMOLITION OF ALL EXISTING FARADAY AND ISC FIRE ALARM PANELS AND DEVICES CONNECTED TO THESE PANELS.
SHEET INDEX
DRAWING TITLEDRAWING NUMBER
KEY MAP, SCOPE OF WORK, GENERAL NOTES, ABBREVIATION,
APPLICABLE CODES AND SHEET INDEX
WIRE/DEVICE/SYMBOL LEGENDS AND SEQUENCE OF OPERATIONS
FOR BUILDING 212, 218, 226 & 297
FIRE ALARM PANEL DETAILS AND DIMENSIONS
BUILDING 212: CALCULATIONS AND RISER DIAGRAM
DWG 1 OF 23
DWG 2 OF 23
DWG 3 OF 23
DWG 4 OF 23
DWG 5 OF 23
DWG 6 OF 23
DWG 7 OF 23
DWG 8 OF 23
FA-101
FA-102
FA-201
FA-202
FA-301
FA-302
FA-303
FA-304
3-WALL PENETRATION, MOUNTING HEIGHTS, WIRING/MOUNTING
DETAILS
BUILDING 212 - SALVATION ARMY
BUILDING 218 - ADMINISTRATION BUILDING
1.) INSTALLATION OF (1) NEW FIRE ALARM CONTROL PANEL ON THE GROUND FLOOR AS SHOWN ON FLOOR PLANS.
CONNECT TO THE EXISTING MONITOR MODULES FOR ALARM, SUPERVISORY AND TROUBLE SIGNALS TO THE EXISTING
SIEMENS APOGEE (EST3) NETWORK PANEL.
2.) ALL INITIATING DEVICES ARE ADDRESSABLE.
3.) WIRE CONDUCTORS SHALL BE INSTALLED IN CONDUIT AND BOXES PROVIDED BY THE ELECTRICAL CONTRACTOR.
4.) INSTALLATION OF NEW NOTIFICATION & ADDRESSABLE DEVICE/S THROUGHOUT THE BUILDING AS SHOWN ON THE PLANS.
BUILDING 226 - WADSWORTH THEATER
1.) INSTALLATION OF (1) NEW FIRE ALARM CONTROL PANEL ON THE BASEMENT FLOOR AS SHOWN ON FLOOR PLANS AND CONNECT TO THE EXISTING MONITOR MODULES FOR ALARM, SUPERVISORY AND TROUBLE SIGNALS TO THE EXISTING SIEMENS APOGEE (EST3)
NETWORK PANEL.
2.) ALL NECESSARY WIRING SHALL BE INSTALLED IN CONDUIT AND BOXES PROVIDED BY THE ELECTRICAL CONTRACTOR.
3.) INSTALLATION OF NEW NOTIFICATION & ADDRESSABLE DEVICE/S THROUGHOUT THE ENTIRE BUILDING AS SHOWN ON THE PLANS.
4.) AFTER ACCEPTANCE, REMOVE OLD FIRE ALARM PANEL AND ASSOCIATED DEVICES.
BUILDING 297 - SUPPLY WAREHOUSE
1.) INSTALLATION OF (1) NEW FIRE ALARM CONTROL PANEL IN THE WAITING AREA AS SHOWN ON FLOOR PLANS AND CONNECT TO THE EXISTING MONITOR MODULES FOR ALARM, SUPERVISORY AND TROUBLE SIGNALS TO THE EXISTING SIEMENS APOGEE (EST3)
NETWORK PANEL.
2.) INSTALLATION OF NEW FIRE ALARM ADDRESSABLE AND NOTIFICATION DEVICES THROUGHOUT THE WAREHOUSE BUILDING, AS
SHOWN ON FLOOR PLANS, TO MEET MINIMUM CODE COMPLIANT REQUIREMENTS PER NFPA 72.
3.) ALL INITIATING DEVICES ARE ADDRESSABLE.
4.) WIRE CONDUCTORS SHALL BE INSTALLED IN CONDUIT AND BOXES PROVIDED BY THE ELECTRICAL CONTRACTOR.
DEPARTMENT OF VETERANS AFFAIRS
11301 WILSHIRE BOULEVARD, LOS ANGELES, CA 90073
FIRE ALARM RETROFIT FOR:
BUILDING 212 - SALVATION ARMY
BUILDING 218 - ADMINISTRATION BUILDING
BUILDING 226 - WADSWORTH THEATRE
BUILDING 297 - SUPPLY WAREHOUSE
BUILDING 218: CALCULATIONS AND RISER DIAGRAM
BUILDING 226: CALCULATIONS AND RISER DIAGRAM
BUILDING 297: CALCULATIONS AND RISER DIAGRAM
BUILDING 212: GROUND FLOOR PLAN
BUILDING 212: FIRST FLOOR PLAN
DWG 9 OF 23
DWG 10 OF 23
FA-401
FA-402
FA-403
FA-404
FA-501
BUILDING 212: SECOND FLOOR PLAN
BUILDING 212: THIRD FLOOR PLAN
BUILDING 218: BASEMENT & GROUND FLOOR PLAN
BUILDING 218: FIRST FLOOR PLAN
BUILDING 218: SECOND FLOOR PLAN
FA-502
FA-503
FA-504
FA-505
FA-601
BUILDING 218: THIRD FLOOR PLAN
BUILDING 218: ROOF FLOOR PLAN
BUILDING 226: BASEMENT FLOOR PLAN
BUILDING 226: FIRST FLOOR PLAN
BUILDING 226: BALCONY FLOOR PLAN
FA-602
FA-603
FA-604
FA-701
FA-702
BUILDING 226: ATTIC FLOOR PLAN
BUILDING 297: AREA A FLOOR PLAN
BUILDING 297: AREA B FLOOR PLAN
DWG 11 OF 23
DWG 12 OF 23
DWG 13 OF 23
DWG 14 OF 23
DWG 15 OF 23
DWG 16 OF 23
DWG 17 OF 23
DWG 18 OF 23
DWG 19 OF 23
DWG 20 OF 23
DWG 21 OF 23
DWG 22 OF 23
DWG 23 OF 23
ARCHITECT/ENGINEERS/CONSULTANTS:
FP
12-28-11
691-11-107
218-1-3308-C
Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net
Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 FA-
Retrofit Fire Alarm System Buildings 212, 218, 226 & 297
212, 218, 226 & 297 KR
FOR CONSTRUCTION
vhaglasubhan Text Box Record for reference and information only.
Pages 1-7-As-built fire alarm drawings.
Pages 8-12- Existing break room door drawing (not as-built) Pages 13-14- Site Utilities (to be verified in field) Pages 15 18- Building original drawings (not as-built) pages 19-29- HAZMAT report for b297
15CD WALL-MOUNTED * STROBE, RED 7125-1657:0220
30CD WALL-MOUNTED * STROBE, RED
75CD WALL-MOUNTED * STROBE, RED
YES
ACTION
DEVICE
YES
YES
NO
NO
YES
YES
YES
YES
NO NONO
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
YES
YES
YESYES YESYES YES NO
YES
YES
YES
NO
YES
YES YESYESYES YESYESYES
YES
NO
YES
NO
NO
YES
YES
YES
YES
NO
YES
YES
(SUPERVISORY)
YES
YES
YES
YES
YES
YES
NO
YES
SIGA-270 MANUAL PULL STATION 2-1/4" BOX w/ SINGLE GANG RING
2-1/4" BOX 4" SQUARE w/ DOUBLE GANG RING
7150-1657:0129
G1RF-CVM (CHIME STROBE) 7125-1657:0220
7125-1657:0220
WALL-MOUNTED CHIME, REDG1RF-C 7125-1657:0220
DEVICE LEGEND
WIRE LEGEND SEQUENCE OF OPERATION: BUILDING 212
* RECOMMENDATION FOR CONDUIT SIZE BY N.E.C
MAXIMUM CONDUCTORS
1 1/2" 1 1/4"
INCHES
CONDUIT SIZE
2"
1" 3/4" 1/2"
#18 AWG
#16 AWG #14 AWG
MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METALLIC TUBING
TYPE
LETTERS
CONDUCTOR
SIZE
AWG/KCMIL
3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
22 35 61 84 138 241 364 476 608 16 26 45 61 101 176 266 347 443 10 16 28 38 63 111 167 219 279 6 9 16 16 36 64 96 126 161
THHN
THWN
PERCENT AREA OF CONDUIT PERCENT REDUCTION PER - NUMBER
18AWG TWISTED SHIELDED PAIRS
TRADE SIZE
INCHES
INTERNAL
DIAMETER
INCHES
TOTAL
AREA 100%
SQ. IN.
OVER 2
WIRES 40%
SQ. IN.
1 2 3 4 5 6 7 8
3/4 0.824 0.533 0.213 19% 38% 57% 76% 95% X X X
1 1.049 0.864 0.346 12% 24% 36% 48% 6% 72% 84% 96%
1 1/4 1.380 1.496 0.598 7% 14% 21% 28% 35% 42% 49% 56%
1 1/2 1.610 2.036 0.814 5% 10% 15% 20% 25% 30% 35% 40%
2 2.067 3.356 1.342 3% 3% 9% 12% 15% 18% 21% 24%
BOX SIZE VS. NUMBER OF WIRES PER N.E.C.
J-BOXES
3-1/4X1-1/2 OCTAGON
3-1/2X1-1/2 OCTAGON
4X1-1/2 OCTAGON
4X1-1/8 OCTAGON
4X4X1-1/2 4X4X2-1/8 4X2-1/8X1-1/2 4X2-1/8X1-7/8 4X2-1/2X2-1/2
#14
#12
CONDUIT WIRE FILL CHART
SYMBOL DESCRIPTION C.S.F.M.MOUNTING INFORMATION
SYMBOL LEGEND
CATALOG #
MANUFACTURER
FIRE ALARM CONTROL PANEL FLUSH MOUNT ENCLOSURE
7165-1657:0244GE SECURITY
iO500G2
INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR 7272-1657:0299MOUNTS TO DETECTOR BASE
7270-1657:0288MOUNTS TO DETECTOR BASEINTELLIGENT HEAT DETECTOR
7300-1657:01204" SQUARE BOX STANDARD DETECTOR BASE
7300-1657:01204" SQUARE BOX STANDARD DETECTOR BASE
GE SECURITY
SIGA2-PS
GE SECURITY
SIGA2-HRS
GE SECURITY
SIGA-SB4
GE SECURITY
SIGA-SB4
7300-1657:0121DUAL MONITOR MODULE
SINGLE MONITOR MODULE 7300-1657:0121
GE SECURITY
SIGA-CT2
GE SECURITY
SIGA-CT1 2-1/4" BOX w/ SINGLE GANG RING
2-1/4" BOX w/ SINGLE GANG RING
CONTROL RELAY MODULE 7300-1657:0121GE SECURITY
SIGA-CR 2-1/4" BOX w/ SINGLE GANG RING
7320-1657:021815CD WALL-MOUNTED STROBE, REDGE SECURITY
---FIRE ALARM TERMINAL CABINET BACKBOX SUPPLIED & INSTALLED BY E.C.
---WATER FLOW SWITCH MONITORED BY HCI; SUPPLIED & INSTALLED BY
OTHERS
---VALVE TAMPER SWITCH MONITORED BY HCI; SUPPLIED & INSTALLED BY
---RISER DOWN ---
---RISER UP ---
EOL END-OF-LINE RESISTOR ---
FACP-2
M2
R
GE SECURITY
G1RF-VM
7320-1657:0218
7320-1657:0218
30CD WALL-MOUNTED STROBE, REDGE SECURITY
GE SECURITY
G1RF-VM
110CD WALL-MOUNTED STROBE, REDGE SECURITY
GE SECURITY
G1RF-VM
GE SECURITY
CS405-7AT 15/75 CD WALL-MOUNTED STROBE, RED MOUNTS TO 449-SERIES WEATHERPROOF BOX
WEATHERPROOF BOXGE SECURITY
7125-1657:0814
18 AMP HOUR SEALED LEAD ACID BATTERY MOUNTS INSIDE BC-1INTERSTATE
SLA1116
BATTERY CABINET TO BE DETERMINED IN THE FIELD.GE SECURITY
BC-1
7.2 AMP HOUR SEALED LEAD ACID BATTERY MOUNTS INSIDE POWER SUPPLY ENCLOSUREINTERSTATE
SLA1079
10 AMP BOOSTER POWER SUPPLY
7300-1657:0229
GE SECURITY
BPS10A
SURFACE MOUNT, BACKBOX PROVIDED BY HCI
& INSTALLED BY E.C.11
PS-?
SYNCHRONIZATION OUTPUT MODULE 7300-1657:0121GE SECURITY
SIGA-CC1SS
S
GE SECURITY31
56 GE SECURITY
BP
OTHERS
---BACKFLOW PREVENTER MONITORED BY HCI; SUPPLIED & INSTALLED BY---
---- OTHERS
A ADDRESSABLE CIRCUIT
CALLOUT USAGE
2#18 FPLR (UNSHIELDED)
TYPE
AUXILIARY CIRCUITC 2#14 THHN (UNSHIELDED)
(CONSTANT POWER)
TWISTED-PAIR, SOLID
STRANDED
ANNUNCIATOR CIRCUITP
2#16 FPLR (SHIELDED)
TWISTED-PAIR, SOLID
2#14 THHN
STRANDED (UNSHIELDED)
V SIGNAL CIRCUIT 2#14 THHN (UNSHIELDED)
ANN REMOTE ANNUNCIATOR 4" SQUARE BOXGE SECURITY
RLCD 7120-1657:0254
110CD WALL-MOUNTED * STROBE, RED 7125-1657:0220GE SECURITY
U UNDERGROUND CIRCUIT 2#14 THWN (UNSHIELDED)
---DOOR HOLDER CONTROLLED BY HCI; SUPPLIED & INSTALLED BY
OTHERS
V1-22
DENOTES NOTIFICATION
DEVICE NUMBER
DENOTES NOTIFICATION
CIRCUIT NUMBER
DENOTES DEVICE TYPE
DENOTES AUDIO/VISUAL
(CEILING-MOUNTED) DEVICE SYMBOL
15CD DENOTES CANDELA RATING
V1
EOL
END-OF-LINE RESISTOR
DENOTES END-OF-LINE FOR
CIRCUIT #V1
V1-22
DENOTES NOTIFICATION
DEVICE NUMBER
DENOTES NOTIFICATION
CIRCUIT NUMBER
DENOTES DEVICE TYPE
DENOTES VISUAL (CEILING-MOUNTED)
DEVICE SYMBOL
15CD DENOTES CANDELA RATING
V1
EOL
END-OF-LINE RESISTOR
DENOTES END-OF-LINE FOR
CIRCUIT #V1
C
ADDRESSABLE DEVICES:
NOTIFICATION APPLIANCES:
SURFACE MOUNT, BACKBOX SUPPLIED BY HCI
INSTALLED BY E.C.
CABINET SUPPLIED BY HCI, INSTALLED BY E.C.
WP
2 TRIM KIT GE SECURITY
SA-TRIM2 FLUSH MOUNT
CABINET SUPPLIED BY HCI, INSTALLED BY E.C.
010022
DENOTES DEVICE'S POINT ADDRESS
(DETECTOR DEVICES - 0001 THROUGH 0125
0251 THROUGH 0375)
DENOTES PANEL'S CABINET NUMBER
DEVICE'S SYMBOL (DETECTORS)
M
DENOTES DEVICE'S POINT ADDRESS
(MODULE DEVICES - 0126 THROUGH 0250
0376 THROUGH 0500)
DENOTES PANEL'S CABINET NUMBER
DEVICE'S SYMBOL (MODULES)
010126
YES
NO
YES
MANUAL
PULL
STATION
AREA
HEAT
DETECTOR
AREA
SMOKE
DETECTOR
ELEVATOR
LOBBY SMOKE
DETECTOR
ELEVATOR
MACHINE RM
SMOKE
DETECTORS
DUCT
SMOKE
DETECTOR
(SUPERVISORY)
SPRINKLER
WATER FLOW
SWITCH
SPRINKLER
VALVE TAMPER
SWITCH
SUPERVISORY
BACKFLOW
PREVENTER
SPECIAL
EXTINGUISHING
SYSTEM
BUILDING
POWER
FAILURE
SHUNTRIP
CIRCUIT
SUPERVISORY
ANNUNCIATE AT THE THE FIRE COMMAND
CENTER AND AT ALL REMOTE
ANNUNCIATORS
ANNUNCIATE AT 24-HOUR ATTENDED
CENTRAL MONITORING STATION
ACTIVATE AUDIBLE/VISUAL
ALARM SIGNAL ON
THROUGHOUT THE BUILDING
SHUT DOWN ALL AIR HANDLING UNIT (AC)
THROUGHOUT THE BUILDING
RELEASE ALL DOOR HOLDERS
RECALL ALL ELEVATORS
SERVING FLOOR OF ALARM
TO ALTERNATE FLOOR RECALL
NO
NO
NO NO
NO
NONO
2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER
2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER
2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER
2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER
2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER
2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER
2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER
2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER
GE SECURITY
757-1A-T WALL-MOUNTED WEATHERPROOF HORN , RED
7300-1657:0191BACKBOX PROVIDED BY HCI; INSTALLED BY E.C.GE SECURITY
757A-WB WEATHERPROOF BOX, RED, SURFACE
MOUNTS TO 757A-WB WEATHERPROOF BOX 7125-1657:0188
1 SIGNATURE LOOP EXPANSION MODULEGE SECURITY
XAL250 CONNECTS TO iO500G CIRCUIT BOARD 7165-1657:0244
WP
B BEAM SMOKE CIRCUIT 2#14 THHN (UNSHIELDED)
STRANDED
T 2#14 THHN (UNSHIELDED)
STRANDEDTEST STATION CIRCUIT
STRANDED
STRANDED
BLDG.
BLDG.
GCFR-HDVM 15CD CEILING-MOUNTED HORN STROBE, RED 7125-1657:0202
30CD CEILING-MOUNTED HORN STROBE, RED
75CD CEILING-MOUNTED HORN STROBE, RED
GCFR-HDVM
GCFR-HDVM
GE SECURITY
GE SECURITY
95CD CEILING-MOUNTED HORN STROBE, REDGCFR-HDVM
GE SECURITY12
2-1/4" BOX 4" SQUARE ELECTRICAL BOX-
GE SECURITY
C
7320-1657:021915CD CEILING-MOUNTED STROBE, REDGE SECURITY
GCFR-VM45 2-1/4" BOX 4" SQUARE ELECTRICAL BOX- 42
7125-1657:02022-1/4" BOX 4" SQUARE ELECTRICAL BOX
7125-1657:02022-1/4" BOX 4" SQUARE ELECTRICAL BOX
7125-1657:02022-1/4" BOX 4" SQUARE ELECTRICAL BOX
7320-1657:021930CD CEILING-MOUNTED STROBE, REDGE SECURITY
GCFR-VM17 2-1/4" BOX 4" SQUARE ELECTRICAL BOX- 16
7320-1657:021975CD CEILING-MOUNTED STROBE, REDGE SECURITY
GCFR-VM8 2-1/4" BOX 4" SQUARE ELECTRICAL BOX- 4
7320-1657:021995CD CEILING-MOUNTED STROBE, REDGE SECURITY
GCFR-VM10 2-1/4" BOX 4" SQUARE ELECTRICAL BOX- 1
---NETWORK PANEL ---- ---
---- -FACP-1
PIV ---POST INDICATOR VALVE MONITORED BY HCI; SUPPLIED & INSTALLED BY---
---- OTHERS- -
(USED FOR BLDG. 212 & 218)
BLDG.
FIRE ALARM CONTROL PANEL FLUSH MOUNT ENCLOSURE
7165-1657:0244GE SECURITY
iO64G2 CABINET SUPPLIED BY HCI, INSTALLED BY E.C.- - (USED FOR BLDG. 226 & 297)1
1 TRIM KITGE SECURITY
SA-TRIM1 FLUSH MOUNT- - 1
(USED FOR iO500G PANEL IN BLDG. 212 & 218)
(USED FOR iO64G PANEL IN BLDG. 226)
4 12 AMP HOUR SEALED LEAD ACID BATTERY MOUNTS INSIDE PANEL ENCLOSUREINTERSTATE
SLA1105- - 2
7270-1582:0101MOUNTS TO AR5 (ADAPTER PLATE)WEATHERPROOF HEAT DETECTOR
---ADAPTER PLATE
CHEMTRONICS
WPB/MPB-501
CHEMTRONICS
AR5
WP
(*CHIME IN BLDG. 212; HORN IN BLDG. 226)
(*CHIME IN BLDG. 212; HORN IN BLDG. 226)
(*CHIME IN BLDG. 212; HORN IN BLDG. 226)
(*CHIME IN BLDG. 212; HORN IN BLDG. 226)
G1RF-HDVM (HORN STROBE)
G1RF-CVM (CHIME STROBE)
G1RF-HDVM (HORN STROBE)
G1RF-CVM (CHIME STROBE)
G1RF-HDVM (HORN STROBE)
G1RF-CVM (CHIME STROBE)
G1RF-HDVM (HORN STROBE)
7320-1657:021875CD WALL-MOUNTED STROBE, REDGE SECURITY
G1RF-VM3 2-1/4" BOX 4" SQUARE w/ SINGLE GANG COVER- - 3
BD
BD
T
R 4- -
4 GE SECURITY
EC-50R- -
GE SECURITY
EC-50R
BEAM SMOKE DETECTOR - TRANSMITTER
CONVENTIONAL
BEAM SMOKE DETECTOR - REFLECTOR
CONVENTIONAL SURFACE MOUNT
SURFACE MOUNT 7260-1657:0233
7260-1657:0233
T 4- - 4 GE SECURITY
EC-LLT SURFACE MOUNT 7300-1657:0234TEST STATION
OS&Y ---OUTSIDE SCREW & YOKE VALVE MONITORED BY HCI; SUPPLIED & INSTALLED BY---
---- OTHERS- - -
---JUNCTION BOX---
----- - - SUPPLIED & INSTALLED BY OTHERS
2-1/4" BOX 4" SQUARE ELECTRICAL BOX
SINGLE MONITOR MODULE 7300-1657:0121GE SECURITY
SIGA-CT1 2-1/4" BOX w/ SINGLE GANG RING1- - 1
BLDG.
OVERALL
QTY.
H
SEQUENCE OF OPERATION: BUILDING 218
SEQUENCE OF OPERATION: BUILDING 226
SEQUENCE OF OPERATION: BUILDING 297
VALVE TAMPER
ACTIVATE AUDIBLE/VISUAL
THROUGHOUT
ALARM SIGNAL ON YES
ATTENDED REMOTE
ANNUNCIATE AT 24 HR.
FIRE CONTROL ROOM
ANNUNCIATE AT
LOCATION
ACTION
DEVICE
DETECTORS
YES
YES
SMOKE
AREA
NONO
FAILURE
YES
YES
POWER
BUILDING
YES
SWITCH
YES
STANDPIPE
SUPERVISORY
YES
DETECTOR
YES
YES
ROOM SMOKE
MACHINE
ELEVATOR
YES
DETECTOR
YES
YES
ROOM HEAT
MACHINE
ELEVATOR
SUPERVISORY
CIRCUIT
SHUNTRIP
YES
DETECTORS
YES
YES
SMOKE
LOBBY
ELEVATOR
NO
YES
YES
SERVING FLOOR OF ALARM
RECALL ALL ELEVATORS
ELEVATOR SHUNT TRIP
YES
STATIONS
YES
YES
PULL
MANUAL
NO
NO
NO
NO
YES
NO NO
YES YES
YES
NO
NO
YES NO
NONO
WATERFLOW
YES
YES
SWITCH
YES
STANDPIPE
NO
NO
NO
NO
VALVE
INDICATOR
YES
YES
POST
NO
NO
NO
PREVENTER
BACKFLOW
YES
YES
NO
SUPERVISORY SUPERVISORY
VALVE TAMPER
ACTIVATE AUDIBLE
THROUGHOUT
ALARM SIGNAL ON
FIRE CONTROL ROOM
ANNUNCIATE AT
ACTION
DEVICE
DETECTOR
SMOKE/HEAT
SWITCH
WATER FLOW
SPRINKLER
SWITCH
SPRINKLER
SUPERVISORY
RELEASE OF FIRE CURTAINS
ANNUNCIATE AT
24 HOUR CENTRAL STATION
YES
YES
YES
YES
NO
YES
YES YES YES
YES YES NO
SYSTEM
DELUGE
YES
YES
SHUTDOWN OF ALL
THROUGHOUT THE BUILDING
AIR HANDLING UNITS YES YES NO
YES
NO
YES
DETECTOR
BEAM
YES
YES
YES
YES
YES
SMOKE
PREVENTER
BACKFLOW
YES
YES
NO
NO
NO
PREVENTER
YES YES
ACTION
DEVICE
DETECTOR
YES
YES
SMOKE
AREA
SWITCH
WATER FLOW
YES
YES
SPRINKLER
NONO
FAILURE
YES
YES
POWER
BUILDING
YES
TAMPER
YES
BACKFLOW
SUPERVISORY
YES
PULL STATION
YES
YES
MANUAL
ACTIVATE AUDIBLE/VISUAL
ALARM SIGNAL THROUGHOUT
THE BUILDING
ANNUNCIATE AT 24 HOUR
ATTENDED REMOTE
LOCATION
ANNUNCIATE AT FIRE ALARM
CONTROL PANEL IN WAITING
AREA
ARCHITECT/ENGINEERS/CONSULTANTS:
FP
12-28-11
691-11-107
218-1-3308-C
Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net
Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 FA-
Retrofit Fire Alarm System Buildings 212, 218, 226 & 297
212, 218, 226 & 297 KR
FOR CONSTRUCTION
A
SECTION A-A
SYSTEM No. C-AJ-1063 (Formerly System No. 368)
L rating at Ambient- Less than 1 cfm/ sq ft (see item 4)
L rating at 400f- Less than 1 cfm/ sq ft (see item 4)
A 2
T RATING - 1/2 Hr
F RATING - 3 Hr
1B
1A
1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 INCHES THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100 - 150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED BLOCKS. MAX DIAMETER OF OPENING IS 4 INCHES. SEE CONCRETE BLOCK (CAZT) CATEGORY IN
THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. STEEL PIPE - NOM 2 INCHES DIAMETER (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL SPACE OF 13/16 INCH IS REQUIRED WITHIN THE FIRESTOP SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH
SIDES OF FLOOR OR WALL ASSEMBLY.
3. PACKING MATERIAL - MINIMUM 3 INCHES THICKNESS OF MINIMUM 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM, PACKING MATERIAL TO BE
RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO
ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
4. FILL, VOID OR CAVITY MATERIAL - SEALANT - MINIMUM 1/2 INCH THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF
WALL. WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
MINNESOTA MINNING & MANUFACTURING CORPORATION - TYPES FB-2000, FB-2000+, FB-2003
(FLOORS ONLY) (NOTE: L RATINGS APPLY WHEN FB-2000+ IS USED.)
* BEARING THE UL CLASSIFICATION MARKING
FLOOR PENETRATION DETAIL WALL PENETRATION DETAIL
T RATING - 0 Hr
F RATING - 2 Hr
SYSTEM No. W-L-1082
3 1B
1A
1A
3 1B
1. WALL ASSEMBLY - THE FIRE RATED GYPSUM WALL BOARD/STUD WALL ASSEMBLY SHALL BE
CONSTRUCTED OF MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U4000
SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL
INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNELS STUDS.
WOOD STUDS TO CONSIST OF NUM 2 BY 4 INCHES LUMBER SPACED 16 INCHES O.C. STEEL
STUDS TO BE MIN 3-1/2 INCHES WIDE AND SPACES MAX 24 INCHES O.C.
B. WALL BOARD GYPSUM - TWO LAYERS OF NOM 5/8 INCH THICK GYPSUM WALL BOARD, AS
SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN DIAMETER OF OPENING IS 1-1/2
INCHES LARGER THAN THE OUTSIDE DIAMETER OF PIPE.
2. THROUGH-PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE OF 3/4 INCH IS REQUIRED WITHIN THE FIRESTOP SYSTEM.
PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE
FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 12 INCHES DIAMETER (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. CONDUIT - NOM 6 INCHES DIAMETER (OR SMALLER) STEEL CONDUIT.
C. CONDUIT - NOM 4 INCHES DIAMETER (OR SMALLER) STEEL ELECTRIC METALLIC TUBING.
D. COPPER TUBING - NOM 6 INCHES DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER
TUBING.
E. COPPER PIPE - NOM 6 INCHES DIAMETER (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
3. FORMING MATERIAL - NOM 1 INCH DIAMETER POLYETHYLENE BACKER ROD FRICTION FITTED INTO
OPENING AS A PERMANENT FORM. FORMING MATERIAL TO BE RECESSED FROM BOTH
SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL
MATERIAL.
4. FILL, VOID OR CAVITY MATERIAL - SEALANT - MINIMUM 5/8 INCH THICKNESS OF FILL MATERIAL
APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL ASSEMBLY.
MINNESOTA MINNING & MANUFACTURING CORPORATION - FB-2000+
*BEARING THE UL CLASSIFICATION MARKING
SECTION A-A
A
A
A
A
1. WALL ASSEMBLY - THE FIRE RATED GYPSUM WALL BOARD/STUD WALL ASSEMBLY SHALL BE
CONSTRUCTED OF MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U4000
SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL
INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNELS STUDS.
WOOD STUDS TO CONSIST OF NUM 2 BY 4 INCHES LUMBER SPACED 16 INCHES O.C. STEEL STUDS
TO BE MIN 3-5/8 INCHES WIDE AND SPACES MAX 24 INCHES O.C.
B. WALL BOARD GYPSUM - NOM 5/8 INCH THICK GYPSUM WALL BOARD, AS SPECIFIED IN THE
INDIVIDUAL WALL AND PARTITION DESIGN DIAMETER OF OPENING IS 1-1/2 INCHES LARGER
THAN THE OUTSIDE DIAMETER OF PIPE.
2. THROUGH-PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE CENTERED WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE OF 3/4 INCH IS REQUIRED WITHIN THE FIRESTOP SYSTEM.
PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE
FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 12 INCHES DIAMETER (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. CONDUIT - NOM 6 INCHES DIAMETER (OR SMALLER) ELECTRIC METALLIC TUBING OR STEEL
CONDUIT.
C. COPPER TUBING - NOM 6 INCHES DIAMETER (OR SMALLER) TYPE L (OR HEAVIER) COPPER
TUBING.
D. COPPER PIPE - NOM 6 INCHES DIAMETER (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
3. FILL, VOID OR CAVITY MATERIAL - SEALANT - MINIMUM 5/8 INCH THICKNESS OF FILL MATERIAL
APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL ASSEMBLY.
MINNESOTA MINNING & MANUFACTURING CORPORATION - FB-2000+
*BEARING THE UL CLASSIFICATION MARKING
SECTION A-AA
A
SYSTEM No. W-L-1084
T RATING - 0 Hr
F RATING - 1 Hr
WALL PENETRATION DETAIL
3-WALL PENETRATIONS
SECTION A-A
DETAILS
SIGA-CT2 DUAL INPUT MODULE
NOT TO SCALE
CONTACT
STATUS/ALARM
EOLR
47K
STATUS/ALARM
CONTACT
EOLR
47K
0.8" (20 mm)
4.4" (112 mm)
2.0" (51 mm)
SIGA-SB4 DETECTOR BASE
NOT TO SCALE
4" SQUARE 1-1/2" DEEP
ELECTRICAL BOX BY E.C.
SIGA-SB4 DETECTOR BASE
NOT TO SCALE
WIRING DETAIL:
NOTE:
1.) A 4" BOX TRIM SKIRT/RING MUST
BE INSTALLED TO GIVE A
"FINISHED" APPEARANCE TO THE
4" BASE.
MOUNTING DIAGRAM:
ACCESS SLOT FOR TAMPER
RESIST MECHANISM
TAMPER-RESIST LEVER ARM
BREAK OFF TO DISABLE
(LOCATED ON BASE)
SIGA-TS
4" BOX TRIM SKIRT/RING
SIGA-CT1 SINGLE INPUT MODULE
NOT TO SCALE
CONTACT
STATUS/ALARM
EOLR
47K
FIRE
BETWEEN 80" A.F.F.
TO BOTTOM OF LENS
AND NO GREATER
THAN 96" A.F.F.
WALL MOUNTED
AUDIO/VISUAL
NOTIFICATION
APPLIANCE
CEILING MOUNTED
SMOKE DETECTOR
FIRE
ALARM
PULL
OF
FIRE 42" MIN. & 48" MAX.
FROM FLOOR LEVEL
TO THE HIGHEST
POINT OF THE
ACTIVATING
HANDLE OR LEVER
OF THE BOX
MANUAL PULL
STATION
CEILING LINE
ABOVE FINISHED FLOOR
FACTORY
CONNECTIONS:
DO NOT ALTER
GREEN LED
(NORMAL)
RED LED
(ALARM/ACTIVE)
4 3 2 1
TB1
SIGA-270 MANUAL PULL STATION
WIRING DETAIL: SINGLE-ACTION
DATA IN (+) DATA OUT (+)
FROM SIGNATURE
CONTROLLER OR
PREVIOUS DEVICE TO NEXT DEVICE
2-1/4" BOX w/
SINGLE GANG RING
(BY E.C.)
BACK
MOUNTING
PLATE (BY HCI)
TOGGLE
SWITCH
COVER
RELEASE
SCREW
NFPA 72, 2010 EDITION NOTES:
17.14.6 MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN 60" OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR.
17.14.7 MANUAL FIRE ALARM BOXES SHALL BE MOUNTED ON BOTH SIDES OF GROUPED OPENINGS OVER 40 FT IN WIDTH, AND WITHIN 60" OF
EACH SIDE OF THE OPENING.
17.14.8 ADDITIONAL MANUAL FIRE ALARM BOXES SHALL BE PROVIDED SO THAT THE TRAVEL DISTANCE TO THE NEAREST FIRE ALARM BOX WILL
NOT BE IN EXCESS OF 200 FT, MEASURED HORIZONTALLY ON THE SAME FLOOR.
SIGA-270 MANUAL PULL STATION
NOT TO SCALE
MOUNTING
SCREWS (BY HCI)
GLASS ROD
RELEASE LEVER
NOT TO SCALE
72" MAX
60" MIN.
& BOOSTER
POWER SUPPLY
60"
REMOTE
ANNUNCIATOR
BETWEEN 80" A.F.F.
TO BOTTOM OF LENS
AND NO GREATER
THAN 96" A.F.F.
WALL MOUNTED
AUDIBLE
NOTIFICATION
APPLIANCE
SIGA-CR: AHU SHUTDOWN
NOT TO SCALE
SIGA-CR: DOOR HOLDER CIRCUIT (24V)
NOT TO SCALE
SIGA-CC1S SIGNAL MODULE
NOT TO SCALE
DATA IN (-)
DATA IN (+)
DATA OUT (-)
DATA OUT (+)
(-) N N
H
(+) C
WHT
BLK
RED
BLU
YEL
ORG
C
N.C.
N.O.
120V CIRCUIT BREAKER
WHT
BLK
RED
BLU
YEL
ORG
C
N.C.
N.O.
SINGLE INPUT MODULE
CAT. NO. SIGA-CT1
REFER TO 387021 REV.2.0
FOR RATING AND
INSTALLATION INFO.
DATA IN (-)
DATA IN (+)
DATA OUT (-)
DATA OUT (+)
ELEVATOR
MAIN
C N .C
N .O
AUXILIARY
POWER
PAM1
RELAY
PR-1
RELAY
SIGA-CR: ELEVATOR SHUNT TRIP AND SUPERVISORY RECALL
CONTROL RELAY MODULE
CAT. NO. SIGA-CR
REFER TO 387023 REV.2.0
FOR RATING AND
INSTALLATION INFO.
NOT TO SCALE
TYPICAL STROBE CIRCUIT
NOT TO SCALE
TYPICAL HORN/STROBE CIRCUIT
NOT TO SCALE
TYPICAL CHIME/STROBE CIRCUIT
NOT TO SCALE
SIGA-DH DUCT DETECTOR HOUSING
NOT TO SCALE
AIR DUCT
MOUNTING DIAGRAM:
6 DUCT WIDTHS
(MINIMUM)
BEND OR OTHER
OBSTRUCTION
DUCT WIDTH
DUCT DETECTOR
LOCATION
THE DUCT DETECTOR HOUSING ASSEMBLY SHOULD BE INSTALLED IN ACCORDANCE
WITH NFPA 72 AND THE AUTHORITIES HAVING JURISDICTION. THE PREFERRED
LOCATION OF THE HOUSING IS IN A LENGTH OF STRAIGHT DUCT AT LEAST SIX DUCT
WIDTHS FROM ANY BENDS OR OTHER OBSTRUCTION AS SHOWN ABOVE.
MOUNTING HEIGHTS DETAIL
NOT TO SCALE
USUALLY INSTALLED
BETWEEN 19" AND 24"
BELOW CEILING
BEAM
DETECTOR
FIRE ALARM
CONTROL PANEL
ARCHITECT/ENGINEERS/CONSULTANTS:
FP
12-28-11
691-11-107
218-1-3308-C
Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net
Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 FA-
Retrofit Fire Alarm System Buildings 212, 218, 226 & 297
212, 218, 226 & 297 KR
LINE
EARTH
GROUND
NEUTRAL
L
N
120VAC, 60Hz, 1.3A
DEDICATED BRANCH CIRCUIT
(PROVIDED BY E.C.)
TRANSFORMER
3.85"
29.5"
18.75"
BATTERY6.6"
7.2"
BATTERY
3/4" CONDUIT
SLA1116
12 VDC BATTERY, 18 A.H.
SLA1116
12 VDC BATTERY, 18 A.H.
3/4" CONDUIT
iO500 FIRE ALARM CONTROL PANEL (FOR BUILDING 212 & 218)
LINE
EARTH
GROUND
NEUTRAL
L
N
120VAC, 60Hz, 1.3A
DEDICATED BRANCH CIRCUIT
(PROVIDED BY E.C.)
TRANSFORMER
SLA1105
12 VDC BATTERY, 12 A.H.
SLA1105
12 VDC BATTERY, 12 A.H.
iO64 FIRE ALARM CONTROL PANEL (FOR BUILDING 226 & 297)
BPS10A BOOSTER POWER SUPPLY MAIN BOARD
iO SERIES CONTROL PANEL DIMENSION RLCD REMOTE ANNUNCIATOR
3.375 IN.
3.5 IN.
17 IN.
6.5 IN.
12 IN.
13 IN.
ALL KNOCKOUTS
FOR 3/4 IN. CONDUIT
FRONT VIEW
TOP VIEW
SI
D
E V
IE
W
SI
D
E V
IE
W
BPS10A POWER SUPPLY DIMENSION
ARCHITECT/ENGINEERS/CONSULTANTS:
FP
12-28-11
691-11-107
218-1-3308-C
Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net
Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 FA-
Retrofit Fire Alarm System Buildings 212, 218, 226 & 297
212, 218, 226 & 297 KR
SCALE:
N.T.S.
C
15CD15CD15CD
WP
N
C C C
95CD 95CD 95CD
V1-8 V1-7 V1-6 N N N
V1-4 N
V1-5
30CD
V1-3 N
V1-2
NEOL
V1
15CD
V1-1 N
CC
95CD95CD95CD95CD
J V2-1V2-2V2-5V2-6
NNNN
95CD
V2-3
NEOL
V2
PS-1
S S
FATC
P M2
95CD 95CD
C C
95CD 95CD
V3-4 V3-3 V3-2 V3-1
N N N NEOL
V3 J
CC
95CD 95CD
V4-4 V4-3 N N
95CD
V4-2 N
95CD
V4-1
NEOL
V4
1V1V1V2V
1V
1V1V1V
1V 1V 1V 1A,3V1A,3V 1V
1V 1V 1V 1V 1V
2V 1V1V1V1V
1A 1A
1A,1C 1A,1C
EXISTING FACP-1 BATTERY CALCULATIONS
POWER SUPPLY (PS-1) BATTERY & VOLTAGE DROP CALCULATIONS
COATED (OHM/kFT)
WIRE SIZE (AWG)
3.26
2.01
5.08
8.08
FEET = One way distance in feet measured
VOLTAGE DROP FOR A GIVEN
AMP = Amperes per terminal of load
WHERE:
= AMP x FEET x 3.26 x 2
OPERATING VOLTAGE
VOLTAGE DROP PERCENTAGE
= SYSTEM VOLTAGE (24)
LENGTH OF CONDUCTOR
= VOLTS x 100 from source of supply to load
FORMULA:
- VOLTS
0101 0103
1A
4V 1A,1C
RISER DIAGRAM
15CD
V2-4 N
1V
WP
V5 -1 N
1V
EOL
V5 P
1A,1C
120VAC DEDICATED
CIRCUIT PROVIDED
BY E.C.
TO MONITOR ALARM
TO MONITOR SUPERVISORY
TO MONITOR TROUBLE
H
120VAC DEDICATED
CIRCUIT PROVIDED
BY E.C.
ARCHITECT/ENGINEERS/CONSULTANTS:
FP
12-28-11
691-11-107
218-1-3308-C
FA-
Retrofit Fire Alarm System Buildings 212, 218, 226 & 297
297 KR
Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net
Corporate Office:1354 S. Parkside PlaceOntario, CA 91761
M
TC
HL
IN
E
SE
E
FA
-7
F
O R
C O
N
TIN
UA
TIO
N
15CDWP
N
M2
95CD 95CD
C
C
C
C
C
95CD 95CD
95CD 95CD
95CD 95CD
J
J
V3-4 V3-3
V1-8 V1-7
V3-2 V3-1
V1-6 V2-1
N N
N N
N N
N N
V1-4 N
V1-5
30CD
EOL
V3
EOL
V1
1A,1V 1A,1V 1A,1V 1A,1V 1V
1V1A,3V
1A,2V
1V 1V 1V
1V
1V
1V
2V
1A,3V
1 1 1 1
1V
1V
15CD
V1-2
N
1A
1A
1A,1V
VERIFY
LOCATION
AT FIELD
15CD
V1-3 N
C
P S
-1
15CD
S S
FA
TC
P
V1-1 N
1A,1C,1V
1A,1C
1A,1V
0103 N
N
P
1V 1A,1V
EXISTING NETWORK
PANEL
120VAC DEDICATED
CIRCUIT PROVIDED
BY E.C.
TO MONITOR ALARM
TO MONITOR SUPERVISORY
TO MONITOR TROUBLE
1A,1C
1V
WP
H
120VAC DEDICATED
CIRCUIT PROVIDED
BY E.C.
EOL
V5
V5-1 N
KEY PLAN : NTS
SCALE: 1/8" = 1'- 0"
ARCHITECT/ENGINEERS/CONSULTANTS:
FP
12-28-11
691-11-107
218-1-3308-C
FA-
Retrofit Fire Alarm System Buildings 212, 218, 226 & 297
297 KR
Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net
Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 701
SYMBOL DESCRIPTION
PS-1
INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR
M2 DUAL MONITOR MODULE
S SYNCHRONIZATION OUTPUT MODULE
10 AMP BOOSTER POWER SUPPLY
S
CEILING-MOUNTED HORN STROBE, RED
WP
WATERFLOW SWITCH
BP BACKFLOW PREVENTER
C
P
EOL END-OF-LINE RESISTOR
CEILING-MOUNTED STROBE, RED
CEILING-MOUNTED WEATHERPROOF STROBE, RED
* RECOMMENDATION FOR CONDUIT SIZE BY N.E.C
MAXIMUM CONDUCTORS
1 1/2" 1 1/4"
INCHES
CONDUIT SIZE
2"
1" 3/4" 1/2"
#18 AWG
#16 AWG #14 AWG
MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METALLIC TUBING
TYPE
LETTERS
CONDUCTOR
SIZE
AWG/KCMIL
3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
22 35 61 84 138 241 364 476 608 16 26 45 61 101 176 266 347 443 10 16 28 38 63 111 167 219 279 6 9 16 16 36 64 96 126 161
THHN
THWN
PERCENT AREA OF CONDUIT PERCENT REDUCTION PER - NUMBER
18AWG TWISTED SHIELDED PAIRS
TRADE SIZE
INCHES
INTERNAL
DIAMETER
INCHES
TOTAL
AREA 100%
SQ. IN.
OVER 2
WIRES 40%
SQ. IN.
1 2 3 4 5 6 7 8
3/4 0.824 0.533 0.213 19% 38% 57% 76% 95% X X X
1 1.049 0.864 0.346 12% 24% 36% 48% 6% 72% 84% 96%
1 1/4 1.380 1.496 0.598 7% 14% 21% 28% 35% 42% 49% 56%
1 1/2 1.610 2.036 0.814 5% 10% 15% 20% 25% 30% 35% 40%
2 2.067 3.356 1.342 3% 3% 9% 12% 15% 18% 21% 24%
BOX SIZE VS. NUMBER OF WIRES PER N.E.C.
J-BOXES
3-1/4X1-1/2 OCTAGON
3-1/2X1-1/2 OCTAGON
4X1-1/2 OCTAGON
4X1-1/8 OCTAGON
4X4X1-1/2 4X4X2-1/8 4X2-1/8X1-1/2 4X2-1/8X1-7/8 4X2-1/2X2-1/2
#14
#12
CONDUIT WIRE FILL CHART
WIRE LEGEND
SYMBOL LEGEND
NOTES
J JUNCTION BOX
NETWORK PANEL
NOTIFICATION APPLIANCES TO BE INSTALLED UNDER SUSPENDED LIGHTS OR BEAMS
20 FEET ABOVE FINISHED FLOOR, PENDANT MOUNTING.
WALL-MOUNTED WEATHERPROOF HORN , RED
WP
H
A ADDRESSABLE CIRCUIT
CALLOUT USAGE
2#18 FPLR (UNSHIELDED)
TYPE
AUXILIARY CIRCUITC 2#14 THHN (UNSHIELDED)
(CONSTANT POWER)
TWISTED-PAIR, SOLID
STRANDED
V SIGNAL CIRCUIT 2#14 THHN (UNSHIELDED)
STRANDED
FIRE ALARM CONTROL PANEL
M
TC
HL
IN
E
SE
E
FA
-7
F
O R
C O
N
TIN
UA
TIO
N
C
C
C
C
95CD 95CD 95CD
95CD95CD
J
J
V2-2 V2-5 V2-6
V4-4V4-3
N N N
NN
95CD
V4-2 N
95CD
V4-1 N
95CD
V2-3 N
EOL
V2
EOL
V4
1V 1V 1V 1V
1V1V1V1V
1A,2V
1 1 1 1
1V
1V
15CD
V2-4 N
1V
KEY PLAN : NTS
SCALE: 1/8" = 1'- 0"
ARCHITECT/ENGINEERS/CONSULTANTS:
FP
12-28-11
691-11-107
218-1-3308-C
FA-
Retrofit Fire Alarm System Buildings 212, 218, 226 & 297
297 KR
Phone: (877) 331-2084Fax: (909) 628-777424-Hour Service: (909) 628-8886Website: www.hcisystems.net
Corporate Office:1354 S. Parkside PlaceOntario, CA 91761 702
SYMBOL DESCRIPTION
PS-1
INTELLIGENT PHOTOELECTRIC SMOKE DETECTOR
M2 DUAL MONITOR MODULE
S SYNCHRONIZATION OUTPUT MODULE
10 AMP BOOSTER POWER SUPPLY
S
CEILING-MOUNTED HORN STROBE, RED
WP
WATERFLOW SWITCH
BP BACKFLOW PREVENTER
C
P
EOL END-OF-LINE RESISTOR
CEILING-MOUNTED STROBE, RED
CEILING-MOUNTED WEATHERPROOF STROBE, RED
* RECOMMENDATION FOR CONDUIT SIZE BY N.E.C
MAXIMUM CONDUCTORS
1 1/2" 1 1/4"
INCHES
CONDUIT SIZE
2"
1" 3/4" 1/2"
#18 AWG
#16 AWG #14 AWG
MAXIMUM NUMBER OF CONDUCTORS IN ELECTRICAL METALLIC TUBING
TYPE
LETTERS
CONDUCTOR
SIZE
AWG/KCMIL
3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
22 35 61 84 138 241 364 476 608 16 26 45 61 101 176 266 347 443 10 16 28 38 63 111 167 219 279 6 9 16 16 36 64 96 126 161
THHN
THWN
PERCENT AREA OF CONDUIT PERCENT REDUCTION PER - NUMBER
18AWG TWISTED SHIELDED PAIRS
TRADE SIZE
INCHES
INTERNAL
DIAMETER
INCHES
TOTAL
AREA 100%
SQ. IN.
OVER 2
WIRES 40%
SQ. IN.
1 2 3 4 5 6 7 8
3/4 0.824 0.533 0.213 19% 38% 57% 76% 95% X X X
1 1.049 0.864 0.346 12% 24% 36% 48% 6% 72% 84% 96%
1 1/4 1.380 1.496 0.598 7% 14% 21% 28% 35% 42% 49% 56%
1 1/2 1.610 2.036 0.814 5% 10% 15% 20% 25% 30% 35% 40%
2 2.067 3.356 1.342 3% 3% 9% 12% 15% 18% 21% 24%
BOX SIZE VS. NUMBER OF WIRES PER N.E.C.
J-BOXES
3-1/4X1-1/2 OCTAGON
3-1/2X1-1/2 OCTAGON
4X1-1/2 OCTAGON
4X1-1/8 OCTAGON
4X4X1-1/2 4X4X2-1/8 4X2-1/8X1-1/2 4X2-1/8X1-7/8 4X2-1/2X2-1/2
#14
#12
CONDUIT WIRE FILL CHART
WIRE LEGEND
SYMBOL LEGEND
NOTES
J JUNCTION BOX
NETWORK PANEL
NOTIFICATION APPLIANCES TO BE INSTALLED UNDER SUSPENDED LIGHTS OR BEAMS
20 FEET ABOVE FINISHED FLOOR, PENDANT MOUNTING.
WALL-MOUNTED WEATHERPROOF HORN , RED
WP
H
A ADDRESSABLE CIRCUIT
CALLOUT USAGE
2#18 FPLR (UNSHIELDED)
TYPE
AUXILIARY CIRCUITC 2#14 THHN (UNSHIELDED)
(CONSTANT POWER)
TWISTED-PAIR, SOLID
STRANDED
V SIGNAL CIRCUIT 2#14 THHN (UNSHIELDED)
STRANDED
FIRE ALARM CONTROL PANEL
vhaglasubhan Rectangle
HI LO S
HI LO S HI LO S HI LO S
NO
Oval vhaglasubhan Oval vhaglasubhan Oval vhaglasubhan Line vhaglasubhan Line vhaglasubhan Text Box The three circled manholes have been verified to be part of sanitary line to which the B297 bathrooms sewer line is connected. There is no manhole at the junction of the line from the bathrooms to the sanitary sewer line. Exact location of the connecting line is not available. Contractor to verify. Dotted red line is only an approximate guess to be confirmed by the contractor.
vhaglasubhan Typewritten Text vhaglasubhan Text Box 15" vhaglasubhan Text Box Sanitary Sewer Line vhaglasubhan Text Box B297 main gas distribution vhaglasubhan Text Box Gas Line
Rectangle
Original drawings of Warehouse- 1948- Not As-built
Project No. 22015.2030 869 rev2 August 2015
BUILDING 297 – SUPPLY WAREHOUSE BUILDING
Building No. 297 is the Supply Warehouse building and was built in 1948. The building has one floor and is 32,700 ft2 in size. The interior includes a mix of drywall and metal walls with metal and drop-in ceiling panels. The interior flooring finishes include 12”x12” vinyl floor tiles, carpet and bare concrete. The exterior is composed of both a raised and slab-on grade foundation with metal walls, metal windows and a sheet paper roof. The HVAC system is comprised of a forced air system with one air handling units located on the ground adjacent to the building and has 15 heating ceiling units.
Historical Data:
An asbestos survey was conducted by others. The data from this survey is listed below. The findings of this survey noted the following materials as being ACM:
• Transite wall panels;
• Mastic material (sealant);
• 9”x9” RFT & mastic; and
• Sink undercoating.
No documents were provided on any materials removed from the building.
Historical Data on LBP – LBP has been discovered in previous surveys on the structural trusses, beams, columns, and braces. Also, lead paint was discovered on the exterior dock plate.
Millennium’s Data:
No ACM was detected in the survey. No lead-based paint was detected in the survey.
The details of location, condition, color, substrate analytical results are provided in the appendix of this report.
Prior to making inferences and interpretations of these data, please refer to the Limitations section of this report.
The total ACM/Lead removal costs for building 297 are $9,600. The total asbestos removal cost is $9,600 and lead-based paint removal costs for building 297 are $0. Please refer to Tables 1-3 included herein.
West Los Angeles Building 297
Reading No Units Building name/# Location/Room Component Substrate Side Color Results PbC PbC Error 438 mg / cm ^2 calib calib calib CALIB calib Positive 1 0.1 439 mg / cm ^2 calib calib calib CALIB calib Positive 1 0.1 440 mg / cm ^2 VALA BLDG,297 Bathroom Baseboard Wood A Beige Negative 0.17 0.05 441 mg / cm ^2 VALA BLDG,297 lounge Window Wood D White Negative 0.1 0.04 442 mg / cm ^2 VALA BLDG,297 lounge Window Wood D White Negative 0.13 0.06 443 mg / cm ^2 VALA BLDG,297 lounge Window Wood D White Negative 0.13 0.04 444 mg / cm ^2 VALA BLDG,297 warehouse Door Metal C Green Negative 0.26 0.03 445 mg / cm ^2 VALA BLDG,297 Office Wall Metal A Beige Negative < LOD 0.03 446 mg / cm ^2 VALA BLDG,297 Office Wall Drywall A Beige Negative < LOD 0.03 447 mg / cm ^2 VALA BLDG,297 lounge Ceiling Drywall A White Negative 0.13 0.04 448 mg / cm ^2 VALA BLDG,297 Kitchen Wall Metal C Yellow Negative 0.24 0.03 449 mg / cm ^2 VALA BLDG,297 Bathroom Door Wood D White Negative 0.07 0.02 450 mg / cm ^2 VALA BLDG,297 Bathroom Door Frame Wood D Beige Negative 0.06 0.02 451 mg / cm ^2 VALA BLDG,297 warehouse Chair Rail Metal D Yellow Negative < LOD 0.03 452 mg / cm ^2 VALA BLDG,297 warehouse Chair Rail Metal D Yellow Negative < LOD 0.03 453 mg / cm ^2 VALA BLDG,297 warehouse Baseboard Wood C Brown Negative < LOD 0.03 454 mg / cm ^2 calib calib calib calib calib Positive 1 0.1 455 mg / cm ^2 calib calib calib calib calib Positive 1 0.1 456 mg / cm ^2 calib calib calib calib calib Positive 1 0.1
: Lead‐Based Paint : Lead‐Containing Paint
VA West Los Angeles Finish Schedule
Building 297
1st Floor - B297 - 1
Building 297 Room Surface Primary Material
Description Primary Color ACM Quantity
ACM
Condition
ACM LBP Quantity
LBP
Condition Lead Notes/Comments
First Floor 1, 2 & 3 Floor 12x12 Resilient Floor Tiles Beige No 0 N/A No 0 N/A First Floor 1, 2 & 3 Ceiling 2'x4' Lay-in Ceiling Panels White No 0 N/A No 0 N/A First Floor 1, 2 & 3 Wall(s) Drywall Walls Yellow No 0 N/A No 0 N/A First Floor 1, 2 & 3 Misc Rubber Cove Base W/ Mastic Tan No 0 N/A No 0 N/A First Floor 1, 2 & 3 Door/Door Frame Wood Door/Metal Frame Burgundy No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor 4 Floor 12x12 Resilient Floor Tiles Beige No 0 N/A No 0 N/A First Floor 4 Ceiling 2'x4' Lay-in Ceiling Panels White No 0 N/A No 0 N/A First Floor 4 Wall(s) Drywall Walls Yellow No 0 N/A No 0 N/A First Floor 4 Misc Rubber Cove Base W/ Mastic Tan No 0 N/A No 0 N/A First Floor 4 Door/Door Frame Wood Door/Metal Frame Burgundy No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor 4 Misc Wood Windows Yellow No 0 N/A No 0 N/A First Floor Bathroom Floor 12x12 Resilient Floor Tiles Beige No 0 N/A No 0 N/A First Floor Bathroom Wall(s) Drywall Walls Beige No 0 N/A No 0 N/A First Floor Bathroom Ceiling Solid Drywall Ceiling White No 0 N/A No 0 N/A First Floor Bathroom Door/Door Frame Wood Door/Wood Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Bathroom Misc Wood Windows White No 0 N/A No 0 N/A First Floor Bathroom Misc Wooden Baseboard Beige No 0 N/A No 0 N/A First Floor Kitchen Floor 12x12 Resilient Floor Tiles Beige No 0 N/A No 0 N/A First Floor Kitchen Wall(s) Drywall Walls White No 0 N/A No 0 N/A First Floor Kitchen Ceiling Solid Drywall Ceiling White No 0 N/A No 0 N/A First Floor Kitchen Door/Door Frame Wood Door/Wood Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Kitchen Misc Wood Windows White No 0 N/A No 0 N/A First Floor Kitchen Misc Wooden Baseboard White No 0 N/A No 0 N/A First Floor Men's Locker Ceiling 2'x4' Lay-in Ceiling Panels White No 0 N/A No 0 N/A First Floor Men's Locker Floor Carpeting over 12x12 Floor Tile Gray No 0 N/A No 0 N/A First Floor Men's Locker Wall(s) Drywall Walls White No 0 N/A No 0 N/A First Floor Men's Locker Door/Door Frame Wood Door/Metal Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Men's RR Floor 12x12 Resilient Floor Tiles White No 0 N/A No 0 N/A First Floor Men's RR Wall(s) Drywall Walls White No 0 N/A No 0 N/A
First Floor Men's RR Misc Metal Windows White No 0 N/A No 0 N/A
First Floor Men's RR Ceiling Solid Drywall Ceiling White No 0 N/A No 0 N/A First Floor Men's RR Door/Door Frame Wood Door/Wood Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Men's Shower Floor 12x12 Resilient Floor Tiles White/Beige No 0 N/A No 0 N/A First Floor Men's Shower Floor Ceramic Flooring - 4x4 White/Beige No 0 N/A No 0 N/A First Floor Men's Shower Wall(s) Ceramic Tile Walls - 4x4 White/Beige No 0 N/A No 0 N/A First Floor Men's Shower Wall(s) Drywall Walls White/Beige No 0 N/A No 0 N/A First Floor Men's Shower Misc Metal Windows Bare No 0 N/A No 0 N/A First Floor Men's Shower Ceiling Solid Drywall Ceiling White No 0 N/A No 0 N/A First Floor Men's Shower Door/Door Frame Wood Door/Metal Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Sink Room Floor Concrete - Bare No 0 N/A No 0 N/A First Floor Sink Room Wall(s) Drywall Walls Beige No 0 N/A No 0 N/A First Floor Sink Room Ceiling Solid Drywall Ceiling Beige No 0 N/A No 0 N/A First Floor Sink Room Misc Wooden Baseboard Green No 0 N/A No 0 N/A First Floor Sink Room Door/Door Frame Wooden Frame only White No 0 N/A No 0 N/A First Floor Storage Floor Concrete - Bare No 0 N/A No 0 N/A First Floor Storage Wall(s) Drywall Walls White No 0 N/A No 0 N/A First Floor Storage Ceiling Solid Drywall Ceiling White No 0 N/A No 0 N/A First Floor Storage Door/Door Frame Wood Door/Metal Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Training Room Ceiling 2'x4' Lay-in Ceiling Panels White No 0 N/A No 0 N/A First Floor Training Room Wall(s) Drywall Walls Yellow No 0 N/A No 0 N/A First Floor Training Room Misc Metal Baseboard Bare No 0 N/A No 0 N/A
First Floor Training Room Door/Door Frame Wood Door/Metal Frame Natural Wood/Bare Metal No* 0 N/A No 0 N/A * Possible asbestos core fire door
First Floor Training Room Wall(s) Wood Paneling Walls No 0 N/A No 0 N/A First Floor Warehouses 1,2, 3, 4 Floor Concrete - Bare No 0 N/A No 0 N/A vhaglasubhan Line
Line
VA West Los Angeles Finish Schedule
Building 297
1st Floor - B297 - 2
Building 297 Room Surface Primary Material
Description Primary Color ACM Quantity
ACM
Condition
ACM LBP Quantity
LBP
Condition Lead Notes/Comments
First Floor Warehouses 1,2, 3, 4 Door/Door Frame Metal Door Green No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Warehouses 1,2, 3, 4 Door/Door Frame Metal Roll-up Door Bare No* 0 N/A No 0 N/A * Possible asbestos core fire door First Floor Warehouses 1,2, 3, 4 Ceiling Metal Roof/Ceiling Bare No 0 N/A No 0 N/A First Floor Warehouses 1,2, 3, 4 Wall(s) Metal Walls Bare No 0 N/A No 0 N/A First Floor Warehouses 1,2, 3, 4 Misc Metal Windows Bare No 0 N/A No 0 N/A First Floor Water Heater Room Floor Concrete - Bare No 0 N/A No 0 N/A First Floor Water Heater Room Wall(s) Drywall Walls Beige No 0 N/A No 0 N/A First Floor Water Heater Room Ceiling Solid Drywall Ceiling Beige No 0 N/A No 0 N/A First Floor Water Heater Room Misc Wood Baseboard Green No 0 N/A No 0 N/A First Floor Water Heater Room Door/Door Frame Wood Door/Wood Frame White No* 0 N/A No 0 N/A * Possible asbestos core fire door vhaglasubhan Line
Line
As-built fire alarm drawings