DRAWINGS

7 MB Posted

Attached to
MORNINGSIDE ELEMENTARY HVAC AND PLUMBING UPGRADES
Solicitation number
22-FAC-016
Issued by
Douglas County, Georgia

About this file

This is a comprehensive set of mechanical and plumbing design drawings for the Morningside Elementary School HVAC and Plumbing Upgrades project located at 120 Sunset Lane, Albany, Georgia 31705 (GA DOE ID #2058). The project scope encompasses the complete replacement and upgrade of heating, ventilation, air conditioning, and plumbing systems throughout the facility. The work includes removal and installation of wall-hung heat pumps (20 units), rooftop units (8 units), exhaust fans (12 units), ceiling heaters (10 units), ductless indoor units (8 units), heat recovery units, and associated ductwork, piping, and controls. The project is organized into five construction phases to minimize disruption to school operations, with provisions for relocating up to six classrooms per phase to temporary modular units. The design includes new equipment support platforms, concrete pads, roof curbs, and architectural modifications such as new ceiling chases and bulkheads to conceal ductwork. All existing R-22 refrigerant must be recovered by the mechanical contractor during demolition for owner processing.

The drawings specify equipment from Carrier as the basis of design, including variable refrigerant flow (VRF) systems, 100% outside air handling units with DX cooling coils, and ductless split-system heat pumps with R-410A refrigerant. The project requires installation of duct insulation, condensate drainage systems with traps and supports, fire and smoke dampers, motorized dampers, and building automation system integration. Specific details are provided for equipment installation, including wall-mounted units requiring integral bi-polar ionization units for indoor air quality, duct penetrations through walls and floors with sleeves and lintels, and roof-mounted equipment with curb adapters and concrete pads. The contractor must coordinate with existing building systems, field verify all dimensions and conditions, and provide protective measures for occupied areas during construction. The drawings indicate requirements for accessibility, maintenance clearances, and compliance with manufacturer specifications for refrigerant piping, condensate drainage, and electrical connections.

Text of this file

D A

D E

BLECKLEY LAURENS

CHATHAM

EFFINGHAM

IRWIN

BERRIEN

LOWNDESGRADY

SE

MI

NO

LE

DECATUR

EARLY

MILLER

BAKER

THOMAS

BROOKS

COLQUITT

MITCHELL

COOK

TIFT

SCHLEY

TERRELL

DOUGHERTY

WEBSTER

RANDOLPH

QUITMAN

CLAY

CALHOUN

CHATTAHOOCHEE

STEWART

MARION

WILCOX

CRISP

WORTH

LEE

TURNER

DOOLY

MACON

SUMTER

HOUSTON

PULASKI

McINTOSH

PIERCE

CHARLTON

LA

NIE

R

CLINCH

ECHOLS

ATKINSON

WARE

CAMDEN

BRANTLEY

GLYNN

TOOMBS

APPLING

COFFEE

BEN HILL

TELFAIR

DAVIS

JEFF

WHEELER

DODGE

TREUTLEN

M

ON

TG

OM

ER

Y

LONG

WAYNE

LIBERTY

BULLOCH

EVANS

CANDLER

TATTNALL

BRYAN

DAWSON FRANKLIN

CLARKE

OCONEE

PUTNAM

BALDWIN

TWIGGS

HENRY

FA

YE

TT

E

PIKE

UPSON

SPALDING

M

ER

IW

ET

HER

HARRIS

MUSCOGEE

TALBOT

COWETA

HEARD

TROUP

PEACH

CRAWFORD

TAYLOR

BIBB

MONROE

LAMAR

BUTTS

JASPER

JONES

CHEROKEE

FULTON

PAULDING

HARALSON

CARROLL

DOUGLAS

BARTOWFLOYD

POLK

COBB

NEWTON

DEKALB

CL

AY

TO

N

ROCKD

AL

E

WALTON

MORGAN

GWINNETT

FORSYTH

JACKSON

HALL BANKS

BARROW

M cD

U F

FI

E

JEFFERSON

EMANUEL

WASHINGTON

WILKINSON

JOHNSON

HANCOCK

WARREN

GLASCOCK

JENKINS

SCREVEN

RICHMOND

BURKE

COLUMBIA

OGLETHORPE

WILKES

TALIAFERROGREENE

LINCOLN

ELBERT

HART

MADISON

RABUN

STEPHENS

FANNIN

PICKENS

GILMER

WHITF

IELD

GORDON

C H

AT

TO

O G

A

WALKER M

U

R R

AY

CATOOSA

UNION

LUMPKIN

WHITE

HABERSHAM

TOWNS

BACON

DOUGHERTY

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

INDEX OF DRAWINGS GEORGIA/COUNTY MAP PROJECT LOCATION

GA DOE ID #: 2058

T100

TITLE SHEET

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

MORNINGSIDE ELEMENTARY SCHOOL - HVAC

& PLUMBING UPGRADES

120 SUNSET LN, ALBANY, GA 31705

T100 TITLE SHEET

C100 SITE PLAN

A100 CONSTRUCTION PHASING PLAN

A200 ARCHITECTURAL CEILING PLAN - OVERALL

A300 ARCHITECTURAL CHASE PLAN & DETAILS

MD100 MECHANICAL DUCT DEMO OVERALL PLAN

MD101 MECHANICAL DEMO PLAN - SECTOR A & C

MD102 MECHANICAL DEMO PLAN - SECTOR B

MD103 MECHANICAL DEMO PLAN - SECTOR D & E

M100 MECHANICAL NEW WORK OVERALL PLAN

M101 MECHANICAL NEW WORK PLAN - SECTOR A & C

M102 MECHANICAL NEW WORK PLAN - SECTOR B

M103 MECHANICAL NEW WORK PLAN - SECTOR D & E

M301 PIPING/WIRING DIAGRAMS

M501 MECHANICAL DETAILS

M502 MECHANICAL DETAILS

M503 MECHANICAL DETAILS

M601 MECHANICAL SCHEDULES

M602 MECHANICAL SCHEDULES, LEGEND & GENERAL NOTES

P101 PLUMBING FLOOR PLAN

P102 PLUMBING PLAN - SECTOR B & C

P103 PLUMBING FLOOR PLANS - SECTOR D & E

P104 PLUMBING ROOF PLAN

E001 ELECTRICAL OVERALL PLAN

ED101 ELECTRICAL DEMOLITION PLAN - SECTOR A & C

ED102 ELECTRICAL DEMOLITION PLAN - SECTORS B

ED103 ELECTRICAL DEMOLITION PLAN - SECTOR D & E

E101 ELECTRICAL NEW WORK PLAN - SECTOR A & C

E102 ELECTRICAL NEW WORK PLAN - SECTORS B

E103 ELECTRICAL DEMOLITION PLAN - SECTOR D & E

E801 ELECTRICAL SCHEDULES & LEGEND

No. Description Date

GA DOE ID #: 2058

TREE

TREE

TREE

TREE

TREE

TREE

TREE

VERIFY LOCATIONS OF OTHER TREES IN

THIS AREA

EXISTING PORTABLE

FENCE

FENCE FENCE

PARKING LOT

CONTRACTOR SHALL COORDINATE WITH OWNER FOR TEMPORARY

CONNECTION OF 2" DOMESTIC COLD WATER PIPING TO EXISTING IN

THIS APPROXIMATE LOCATION BELOW GRADE.

2" DCW

D C

W

2" DCW 1 1/2" DCW

1 1/2" DCW

1 1/2" DCW

1 1/2" DCW

GENERAL NOTE: LOCATIONS OF CLASSROOM TRAILERS IS APPROXIMATE.

CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF EXISTING STORM DRAINS, FENCING,

SIDEWALKS, PLAYGROUNDS, DRIVES, ETC. AND CAREFULLY COORDINATE PLACEMENT

OF CLASSROOMS TO AVOID CONFLICT AND MAINTAIN REQUIRED CLEARANCES.

TEMPORARY PORTABLE CLASSROOM

TEMPORARY PORTABLE CLASSROOM

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

D

E

GA DOE ID #: 2058

C101

SITE PLAN

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/16" = 1'-0"1 SITE PLAN

TREE

TREE

TREE

TREE

TREE

TREE

VERIFY LOCATIONS OF OTHER TREES IN

THIS AREA

EXISTING PORTABLE

(NOT IN SCOPE)

FENCE

FENCE FENCE

PARKING LOT

TEMPORARY PORTABLE CLASSROOM

TEMPORARY PORTABLE CLASSROOM

PHASE 2GYMNASIUM

CLASSROOM

COMPUTER LAB

CLASSROOM

COMPUTER LAB

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

MECHANICAL

99 GIRLS

BOYS

CORRIDOR

BOYS

GIRLS

CLASSROOM

60CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

ART CENTER

MUSIC ROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

88 CLASSROOM

CLASSROOM

COMPUTER LAB

COMPUTER LAB

STOR.

COACHES OFFICE

TOIL.

BOYS

49 GIRLS

JAN.

TOIL.

CORRIDOR

CORRIDOR

STOR.

STOR.

ELEC

TOIL.

STORAGE

STORAGE

CNSLR.

TOIL.

MEDIA PRODUCTION

MEDIA CENTER

VAULT

ASST. PRINC.

MECHANICAL

TOIL.

CORRIDOR

STAFF LOUNGE

TOIL.

PRINC.

MEDIA CTR. DIRECTOR

WORKROOM

TOIL.

TOIL.

FOOD STORAGE

LOCKERS

OFFICE

VEST.

JAN.

COOLER

FREEZER

KITCHEN

GIRLS

BOYS

BOOK STORAGE

WORK ROOM

30CORR.

CONFERENCE

CORRIDOR

CORR.

STOR.

STOR.

STOR.

BOYS

GIRLS

STAGE

CAFETERIA

CORRIDOR

RECEPTIONIST

AV STORAGE

CAN WASH

DISH WASH

JAN.

JAN.

ENTRY

WAITING

PHASE 1

PHASE 3

PHASE 4

PHASE 5

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

GA DOE ID #: 2058

A100

CONSTRUCTION PHASING

PLAN

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/16" = 1'-0"1 CONSTRUCTION PHASING PLAN

GENERAL NOTE: THERE WILL BE 3 MODULAR CLASSROOM BUILDINGS WITH (2) CLASSROOMS PER MODULAR UNIT ON THIS SITE PROVIDED BY THE CONTRACTOR. NO MORE THAN 6 CLASSROOMS MAY BE MOVED TO MODULAR UNITS FOR EACH PHASE. PHASES SHOWN HEREIN ARE SUGGESTED PHASES AND MAY BE CHANGED DUE TO CONSTRUCTION TIMELINES, CONSTRUCTION SCHEDULES, EQUIPMENT

LEAD TIMES, UNFORESEEN CIRCUMSTANCES ENCOUNTERED DURING THE CONSTRUCTION PROCESS

OR FURTHER COORDINATION WITH OWNER. VERIFY ALL PHASING, TEMPORARY WALL/PARTITION

INSTALLATION AND/OR SCHEDULING PRIOR TO COMMENCEMENT OF WORK.

NOTES: (THIS SHEET ONLY)

1 . ADJUST TEMPORARY WALLS AS REQUIRED TO MAINTAIN

SEPARATION FROM WORK AREAS AND OCCUPIED STUDENT

AREAS. ACCESS TO EXIT DOORS SHALL BE MAINTAINED AT

ALL TIMES.

2 . ADJUST TEPROVIDE TEMPORARY WALL (MIN 6' TALL) TO

SEPARATE WORK AREAS FROM OCCUPIED AREAS BASED ON

PHASING. PROVIDE DOORS AS REQUIRED FOR ACCESS TO

WORK AREA. PROVIDE PROTECTION FOR EXISTING

FLOORING, WALLS, ETC. TO PREVENT DAMAGE TO EXISTING

ITEMS DURING INSTALLATION / REMOVAL OF TEMPORARY

WALL.MPORARY WALLS AS REQUIRED TO ALLOW ACCESS TO

RESTROOMS WHILE MAINTAINING SEPARATION OF WORK

AREAS FROM OCCUPIED STUDENT AREAS.

3 . ADJUST TEMPORARY WALLS AS REQUIRED TO ALLOW

ACCESS TO RESTROOMS WHILE MAINTAINING SEPARATION

OF WORK AREAS FROM OCCUPIED STUDENT AREAS.

No. Description Date

GENERAL NOTE: PRIOR TO CONSTRUCTION, CONTRACTOR SHALL COORDINATE

WITH OWNER TO REMOVE ALL PERSONAL ITEMS FROM SPACES AFFECTED BY

DEMOLITION. CONTRACTOR SHALL PROTECT EXISTING CASEWORK, FURNITURE,

FLOORING, WALLS, CEILINGS, ETC. NOT ABLE TO BE REMOVED. AT THE END OF

CONSTRUCTION, CONTRACTOR SHALL REMOVE ALL PROTECTIVE COVERS AND

WIPE DOWN AND CLEAN ALL SURFACES AFFECTED BY DUST, DIRT,

CONSTRUCTION DEBRIS, ETC.

UP

KITCHEN

CAFETERIA

GENERAL NOTE: REMOVAL OF CEILINGS REQUIRED FOR

REMOVAL OF EXISTING EXHAUST FANS LOCATED ABOVE

RESTROOMS NOT SHOWN. SEE MECHANICAL DRAWINGS

FOR LOCATIONS OF ITEMS LOCATED ABOVE CEILINGS THAT

MAY REQUIRE REMOVAL OF CEILING TILES.

GYMNASIUM

CLASSROOM

COMPUTER LAB

CLASSROOM

COMPUTER LAB

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

MECHANICAL

GIRLS

BOYS

CORRIDOR

BOYS

GIRLS

CLASSROOM

60CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

ART CENTER

MUSIC ROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

88 CLASSROOM

CLASSROOM

COMPUTER LAB

COMPUTER LAB

STOR.

COACHES OFFICE

TOIL.

BOYS

49 GIRLS

JAN.

TOIL.

CORRIDOR

CORRIDOR

STOR.

STOR.

ELEC

TOIL.

STORAGE

STORAGE

CNSLR.

TOIL.

MEDIA PRODUCTION

MEDIA CENTER

VAULT

ASST. PRINC.

MECHANICAL

TOIL.

CORRIDOR

STAFF LOUNGE

TOIL.

PRINC.

MEDIA CTR. DIRECTOR

WORKROOM

TOIL.

TOIL.

FOOD STORAGE

LOCKERS

OFFICE

VEST.

JAN.

COOLER

FREEZER

GIRLS

BOYS

BOOK STORAGE

WORK ROOM

30CORR.

CONFERENCE

CORRIDOR

CORR.

STOR.

STOR.

STOR.

BOYS

GIRLS

STAGE

CORRIDOR

RECEPTIONIST

AV STORAGE

CAN WASH

DISH WASH

JAN.

JAN.

ENTRY

WAITING

CEILING IN STOR.

36 WILL NOT BE

REPLACED.

DEMO EXISTING CEILING TILE & GRID AS

REQUIREDAND REPLACE WITH NEW CEILING

TILE & GRID

DEMO EXISTING CEILING TILE &

REPLACE WITH NEW CEILING TILE

CEILING HATCH LEGEND

(NO HATCH) EXISTING CEILING TILE

& GRID TO REMAIN

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

D

E

GA DOE ID #: 2058

A200

ARCHITECTURAL CEILING

PLAN - OVERALL

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/16" = 1'-0"1 ARCHITECTURAL CEILING PLAN - OVERALL

1 1 1 1 1

1 1 1 1 1

1 1 1

1 LAYER ABUSE RESISTANT 5/8" GYPSUM BOARD (ONE SIDE).

ACOUSTICAL TILE T-BAR CEILING

EXTEND WALL 0'-6" (MAXIMUM) PAST CEILING - OR AS DICTATED BY

EXITING STRUCTURAL CONDITIONS, SUPPLY DUCT, ETC.

3" BATTS INSULATION BETWEEN STUDS FOR SOUND ATTENUATION.

CONTINUOUS SEALANT AT CEILING INTERFACE OF 5/8" GYP.

MTL. RUNNER - DO NOT FASTEN TO STUD.

HEAD

PLAN

BASE

OVERALL DIMENSION = 4-1/4"

'C' SHAPED MTL. STUD. DO NOT FASTEN TO RUNNER ABOVE.

FASTENERS @ 2'-0" O.C. MAX WITHIN 1" OF ENDS.

TOP OF STRUCTURAL SLAB.

CONTINUOUS SEALANT.

CONTINUOUS C'SHAPED METAL RUNNER.

BASEBOARD.

CLASSROOMCHASE

METAL STUD SIZE - 3-5/8"

WHHP

PROVIDE STEEL CORNER BEAD AT 90

DEG GYP. BOARD OUTSIDE CORNERS.

PROVIDE FRAMED OPENING FOR

SUPPLY DUCT AND RETURN GRILLE

AND DUCT. SEE MECHANICAL

DRAWINGS FOR EXACT SIZE.

SEE MECHANICAL DRAWINGS FOR

SUPPLY & RETURN DUCT SIZES.

EXTERIOR WALL

24" MAXIMUM

48" MAXIMUM

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

GA DOE ID #: 2058

A300

ARCHITECTURAL CHASE

PLAN & DETAILS

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/16" = 1'-0"1 ARCHITECTURAL CHASE PLAN

NOT TO SCALE

CHASE WALL DETAIL

1 . CONSTRUCT CHASE WALL FOR WALL HUNG UNIT DUCTWORK ACCORDING TO

CHASE WALL DETAIL, THIS SHEET.

2 . CONSTRUCT BULKHEAD/SOFFIT TO CONCEAL DUCTWORK RISE. SEE MECHANICAL

PLAN FOR DUCTWORK AND DETAILS.

3 . COORDINATE WITH OWNER FOR THE REMOVAL AND RELOCATION OF SHELVING

FOR NEW MECHANICAL EQUIPMENT IN THIS ROOM.

NOTES: (THIS SHEET ONLY)

NOT TO SCALE

WHHP CHASE WALL DETAIL

MD101

MD101

MD102

MD103

MD103

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

D

E

GA DOE ID #: 2058

MD100

MECHANICAL DUCT DEMO

OVERALL PLAN

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/16" = 1'-0"1 MECHANICAL OVERALL DEMO PLAN - OVERALL

1 1 1 1 1 1

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CORRIDOR

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

STOR.

CORR.

COMPUTER LAB

COMPUTER LAB

BOYS

GIRLS

1 1 1 1 1

11111

CLASSROOM

COMPUTER LAB

CLASSROOM

COMPUTER LAB

CLASSROOM

BOYS

GIRLS

CORRIDOR

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

D

E

GA DOE ID #: 2058

MD101

MECHANICAL DEMO PLAN -

SECTOR A & C

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR A

1/8" = 1'-0"2 MECHANICAL DEMO PLAN - SECTOR C

1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.

2 . REMOVE EXISTING CEILING HEATER FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR CEILING HEATER REPLACEMENT.

3 . REMOVE EXISTING PACKAGED ROOF TOP UNIT FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR RTU REPLACEMENT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW UNIT.

4 . REMOVE EXISTING ROOF EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN REPLACEMENT.

NOTES: (THIS SHEET ONLY)

No. Description Date

GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF

WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL

UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE

RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING

WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).

CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT

REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY

CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS

HAVE BEEN FILLED, CYLINDERS SHALL BE RETURNED TO OWNER FOR

PROCESSING.

COMPUTER LAB

CLASSROOM

CORRIDOR

CLASSROOM

CLASSROOM

CAFETERIA

STAGE

DISH WASH

FREEZER

COOLER

VEST.

FOOD STORAGE

CORRIDOR

8 8

91010

11 11

5 5(TYP) (TYP)

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

D

E

GA DOE ID #: 2058

MD102

MECHANICAL DEMO PLAN -

SECTOR B

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR B

NOTES: (THIS SHEET ONLY)

1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW WALL

HUNG HEAT PUMP SAME LOCATION.

2 . REMOVE EXISTING CEILING HEATER FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR CEILING HEATER REPLACEMENT.

3 . REMOVE EXISTING PACKAGED ROOF TOP UNIT FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR RTU REPLACEMENT. SALVAGE EXISTING GPS

BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW UNIT.

4 . REMOVE EXISTING ROOF EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN REPLACEMENT.

5 . (TYPICAL) EXISTING SUPPLY/RETURN/EXHAUST GRILLE AND ASSOCIATED FLEX DUCT (IF APPLICABLE) IN THIS APPROXIMATE LOCATION TO REMAIN FOR REUSE. SEE

NEW WORK DRAWING FOR AIRFLOW.

6 . REMOVE EXISTING CEILING EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN REPLACEMENT.

7 . REMOVE EXISTING KITCHEN HOOD EXHAUST FAN ON ROOF IN THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN REPLACEMENT.

8 . REMOVE EXISTING AIR HANDLER FROM THIS APPROXIMATE LOCATION. DUCTWORK TO REMAIN FOR REUSE WITH NEW UNIT. REMOVE ALL ASSOCIATED REFRIGEREANT PIPING FROM OUTDOOR UNIT TO INDOOR UNIT. CONDENSATE PIPE TO REMAIN FOR REUSE WITH NEW UNIT. REMOVE EXISTING BIPOLAR UNIT IN

EXISTING UNIT FOR REUSE IN NEW UNIT.

9 . REMOVE EXISTING HEAT PUMP FROM THIS APPROXIMATE LOCATION. CONCRETE EQUIPMENT PAD AND FENCE TO REMAIN FOR REUSE WITH NEW UNIT. REMOVE ALL

ASSOCIATED REFRIGEREANT PIPING FROM OUTDOOR UNIT TO INDOOR UNIT.

10 . EXISTING RETURN DUCT TO REMAIN IN THIS APPROXIMATE LOCATION. OPEN MANUAL VOLUME DAMPER ALL THE WAY TO ALLOW FULL AIRFLOW.

11 . EXISTING LOUVER, DUCTWORK, AND AUTOMATIC VOLUME DAMPER TO REMAIN FOR REUSE. REMOVE ACTUATOR. SEE NEW WORK DRAWINGS FOR INSTALLATION OF

NEW ACTUATOR AND MANUAL VOLUME DAMPER.

12 . EXISTING DISHWASHER EXHAUST FAN TO REMAIN.

13 . EXISTING DUCTWORK IN MECHANICAL ROOM AND ON ROOF TO REMAIN.

14 . EXISTING GRAVITY VENT ON ROOF. CAP AND SEAL VENT AIR TIGHT.

15 . REMOVE ALL EXISITNG DUCTWORK PAST THE SCOPE OF WORK SYMBOL. SEE NEW WORK DRAWINGS FOR NEW DUCTWORK. PROVIDE DUCT END CAP.

16 . REMOVE EXISTING CEILING DIFFUSER IN THIS APPROXIMATE LOCATION.

No. Description Date

GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF

WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL

UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE

RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING

WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).

CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT

REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY

CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS

HAVE BEEN FILLED, CYLINDERS SHALL BE RETURNED TO OWNER FOR

CLASSROOM

6 6

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

11 (TYP)

11 (TYP)

11 (TYP)

11 (TYP)11 (TYP)11 (TYP)

11 (TYP)

(TYP)12 12 12 12 12 12

121212121212

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

D

E

GA DOE ID #: 2058

MD103

MECHANICAL DEMO PLAN -

SECTOR D & E

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR D

1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR

INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.

2 . REMOVE EXISTING CEILING HEATER FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR CEILING HEATER REPLACEMENT.

3 . REMOVE EXISTING PACKAGED ROOF TOP UNIT FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR RTU REPLACEMENT.

SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW UNIT.

4 . REMOVE EXISTING ROOF EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN

REPLACEMENT.

5 . REMOVE EXISTING PACKAGED HEAT PUMP UNITS FROM THIS APPROXIMATE LOCATION. DEMO DUCTWORK AND DUCT COVERING UP TO CHASE TO ALLOW FOR NEW DUCTWORK CONNECTION. REMOVE EXISTING BIPOLAR IONIZATION UNIT FOR REUSE IN NEW PACKEGED UNIT.

6 . (TYPICAL) EXISTING DUCTWORK TO REMAIN.

7 . REMOVE EXISTING RETURN GRILLE FROM CEILING IN THIS APPROXIMATE LOCATION.

8 . REMOVE EXISTING ROOF VENTILATOR FROM THIS APPROXIMATE LOCATION. CAP EXISTING CURB.

9 . REMOVE EXISTING AIR HANDLER AND ALL ASSOCIATED PIPING, SUPPORTS, DUCTWORK, ETC. FROM THIS APPROXIMATE LOCATION.

10 . REMOVE ANY AND ALL HVAC RELATED ITEMS FROM MECHANICAL ROOM. THIS INLCUDES BUT IS NOT LIMITED TO, AIR COMPRESSOR, DUCTOWKR, PIPING, BOILER, CONTROLS, ETC.

11 . REMOVE EXISTING DUCTWORK.

12 . REMOVE EXISTING SIDE WALL GRILLE.

13 . REMOVE EXISTING CONDENSING UNIT ON ROOF. DEMO ANY ASSICIATED ELECTRICAL AND PIPING MATERIALS. SEAL ALL ROOF OPENINGS.

NOTES: (THIS SHEET ONLY)

No. Description Date

GENERAL NOTE: THIS PROJECT INVOLVES THE REMOVAL AND REPLACEMENT OF

WALL HUNG HEAT PUMPS (WHHP), ROOFTOP HEAT PUMPS (RTU), & FAN COIL

UNITS AND HEAT PUMPS (FCU AND HP). MECHANICAL CONTRACTOR SHALL BE

RESPONSIBLE FOR RECOVERING ALL R-22 REFRIGERANT FROM ALL EXISTING

WHHP, RTU, FCU/HP SYSTEMS REMOVED DURING DEMOLITION PHASE(S).

CONTRACTOR SHALL PROVIDE ALL LABOR AND TOOLS/RECOVERY EQUIPMENT

REQUIRED TO RECOVER R-22 REFRIGERANT. REFRIGERANT RECOVERY

CYLINDERS SHALL BE PROVIDED BY CONTRACTOR. ONCE RECOVERED CYLINDERS

HAVE BEEN FILLED, CYLINDERS SHALL BE RETURNED TO OWNER FOR

1/8" = 1'-0"2 MECHANICAL DEMO PLAN - SECTOR E

M101

M101

M102

M103

M103

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

D

E

GA DOE ID #: 2058

M100

MECHANICAL NEW WORK

OVERALL PLAN

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/16" = 1'-0"1 MECHANICAL NEW WORK PLAN OVERALL

WHHP-8 WHHP-9

WHHP-10

WHHP-6WHHP-5WHHP-4WHHP-3WHHP-2WHHP-1

RTU-4

RTU-3

EF-1

"x

"x

10"ø

10"ø10"ø

10"ø

A3

A3

A3

A3

30"x10" B1

"x

"x

10"ø

10"ø10"ø

10"ø

A3

A3

A3

A3

30"x10" B1

"x

"x

10"ø

10"ø10"ø

10"ø

A3

A3

A3

A3

30"x10" B1

"x

"x

" 10"ø

10"ø10"ø

10"ø A3

A3

A3

A3

30"x10"

B1

"x

"x

" 10"ø

10"ø10"ø

10"ø A3

A3

A3

A3

30"x10"

B1

"x

"x

" 10"ø

10"ø10"ø

10"ø A3

A3

A3

A3

30"x10"

B1

"x

"x

" 10"ø

10"ø10"ø

10"ø A3

A3

A3

A3

30"x10"

B1

"x

"x

" 10"ø

10"ø10"ø

10"ø A3

A3

A3

A3

30"x10"

B1

"x

"x

" 10"ø

10"ø10"ø

10"ø A3

A3

A3

A3

30"x10"

B1

1 1 1

1 1 1 1 1 1

CH-1

CC

WHHP-7

"x

"x

10"ø

10"ø10"ø

10"ø

A3

A3

A3

A3

30"x10" B1

MVD

A2

A2

A2

A2

A2

A2

150 A2

A2

COMPUTER LAB

CORR.

10"ø

12"ø 10"ø

12"ø12"x12"

12"ø

CLASSROOM

CLASSROOM

CORRIDOR

300 300

400 400

400400

COMPUTER LAB

CLASSROOM

STOR.

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

JAN.

ENTRY

CLASSROOM

6 6 6 6

6 6 6 6 6 6

TT TT TT TT TT TT

TTTTTTTT

TT

TT

CH-4

DFCU-4.1

DOU-4

DFCU-4.2

3/ 4"

D

/4

D

/2

D

3/4" D

10(TYP)

16"x10"

"x

M101

1 1/4" D

1 1/4" D

R R

A2

A2

8"ø 8"ø 8"ø 8"ø

8"ø8"ø8"ø8"ø

12 (TYP)

L-1

13 13 13 13

131313131313

OAU-1

DFCU-5

DOU-5

R

TT

TT

20"x30"

OAU-CU-1

R

1" D

16"x10"

F.D.

WHHP-16 WHHP-17 WHHP-18 WHHP-19 WHHP-20

WHHP-12WHHP-11

WHHP-13 WHHP-14

WHHP-15

EF-7 EF-8

"x

"x

" 10"ø

10"ø10"ø

10"ø A3

A3

A3

A3

30"x10"

B1

"x

"x

" 10"ø

10"ø10"ø

10"ø A3

A3

A3

A3

30"x10"

B1

"x

"x

" 10"ø

10"ø10"ø

10"ø A3

A3

A3

A3

30"x10"

B1

"x

"x

" 10"ø

10"ø10"ø

10"ø A3

A3

A3

A3

30"x10"

B1

"x

"x

10"ø

10"ø10"ø

10"ø

A3

A3

A3

A3

30"x10"

B1

"x

"x

10"ø

10"ø10"ø

10"ø

A3

A3

A3

A3

30"x10" B1

"x

"x

10"ø

10"ø10"ø

10"ø

A3

A3

A3

A3

30"x10" B1

"x

"x

10"ø

10"ø10"ø

10"ø

A3

A3

A3

A3

30"x10" B1

"x

"x

10"ø

10"ø10"ø

10"ø

A3

A3

A3

A3

30"x10" B1

"x

"x

30"x10"

B1

A3

A3

A3

A3

1 1 1 1

1 1 1 1 1

2 2

CCCC

A2

150A2

A2

A2

A2

A2

150 A2

A2

A2

CH-8

"x

MEDIA PRODUCTION

CORRIDOR

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CORRIDOR

CLASSROOM

BOYS

GIRLS

COMPUTER LAB

CLASSROOM

COMPUTER LAB

CLASSROOM

6 6 6 6 6

10 6 6 6

A2

TT TT TT TT TT

TT

TT TT TT TT

DFCU-2.2

DOU-2

DFCU-2.1

8"ø

10"ø12"ø14"x14"

12"ø 10"ø

8"ø

8"ø8"ø8"ø

8"ø 8"ø 8"ø

MVD

MVD

R

1 1/4" D

1 1/4" D

R

(TYP)

13 13 13

131313

8"ø 8"ø

8"ø

INSTALL ACOUSTICAL TILE CEILING BENEATH BULKHEAD/SOFFIT AT NO LOWER THAN 7' 6" A.F.F..

INSTALL 5/8" GYP BOARD ON BULKHEAD FACE (2 SIDES), ANCHORED TO KAM AND PAINTED

TO MATCH EXISTING WALLS.

PROVIDE KNURLED ANGLE MOLDING (KAM) ON BACK WALL FOR GRID MAIN SUPPORT.

FABRICATE SOFFIT FROM BENT DRYWALL ARMSTRONG (OR EQUAL) HD8906 MAIN

RUNNERS. NOTCH AT CORNERS AND SUPPORT WITH DW90 REINFORCEMENT. PROVIDE

LATERAL T-BAR GRID AT 16" ON CENTER.

TERMINATE EXISTING CEILING GRID AT NEW SOFFIT FACE.

PROVIDE BRACING TO WALL AS REQUIRED.

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

D

E

GA DOE ID #: 2058

M101

MECHANICAL NEW WORK

PLAN - SECTOR A & C

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

NOTES: (THIS SHEET ONLY)

1 . WALL HUNG HEAT PUMP. SEE WALL HUNG HEAT PUMP DETAIL - DUCTED SUPPLY.

2 . ROOF MOUNTED CENTRIFUGAL EXHAUST FAN. SEE ROOF MOUNTED CENTRIFUGAL EXHAUST

FAN DETAIL.

3 . CEILING HEATER.

4 . ROOFTOP AIR CONDITIONING UNIT MOUNTED ON ROOF CURB ADAPTER. SEE ROOF CURB

ADAPTER DETAIL.

5 . DUCT CURB. SEE DUCT CURB DETAIL.

6 . ATTACH NEW DUCT TO EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION. PROVIDE

NECESARY TRANSITIONS/OFFSET AS NEEDED TO MAKE CONNECTION.

7 . NEW DUCTLESS HEAT PUMP MOUNTED ON NEW EQUIPMENT SUPPORT PLATFORM. SEE ROOF

MOUNTED EQUIPMENT SUPPORT PLATFORM DETAIL. REFRIGERANT PIPING ROUTED THROUGH

NEW PIPE BOX ON ROOF. SEE PIPE BOX ASSEMBLY DETAIL.

8 . NEW DUCTLESS CEILING CASSETTE MOUNTED IN CEILING IN THIS APPROXIAMTE LOCATION.

FEILD VERIFY EXISTING CONDITIONS AND SHIFT UNIT AS NEEDED. UNIT'S SUPPLY GRILLE

FACING HOOD SHALL BE BLANKED OFF TO NOT INTERFERE WITH HOOD PERFORMANCE.

9 . PROVIDE FULL SIZE, SLOPED (1/4" PER FOOT), TRAPPED, SCHEDULE 40 PVC PIPING TO

DISCHARGE AS SHOWN ON DRAWINGS . DRAIN PIPING SHALL BE PROVIDED FROM EACH RTAC

AS SHOWN ON DRAWINGS. INSURE THAT DRAIN PIPING DOES NOT BLOCK RTAC ACCESS

PANELS. DO NOT ROUTE DRAIN PIPING IN FRONT OF ACCESS PANELS. SEE CONDENSATE

DRAIN TRAP DETAIL AND CONDENSATE ROOF SUPPORT DETAIL(S).

10 . CONDENSATE PIPE SUPPORT ON ROOF. SEE CONDENSATE PIPE SUPPORT ON ROOF DETAILS.

11 . NEW DUCTLESS CEILING CASSETTE MOUNTED IN CEILING IN THIS APPROXIAMTE LOCATION.

FEILD VERIFY EXISTING CONDITIONS AND SHIFT UNIT AS NEEDED. UNIT'S SUPPLY GRILLE

FACING HOOD SHALL BE BLANKED OFF TO NOT INTERFERE WITH HOOD PERFORMANCE.

12 . CONDENSATE SHALL BE PUMPED FROM UNIT UNIT THROUGH PIPE BOX AND DISCHARGE ONTO

ROOF.

13 . ALL REFRIGERANT PIPING AND CONDENSATE PIPING SHALL BE CONCEALED BEHIND

RECTORSEAL FORTRESS LINE HIDE KIT OR EQUAL ONCE IT PENETRATES CEILING.

14 . NEW DUCTLESS HEAT PUMP MOUNTED ON NEW EQUIPMENT SUPPORT PLATFORM. SEE ROOF

MOUNTED EQUIPMENT SUPPORT PLATFORM DETAIL. REFRIGERANT PIPING ROUTED THROUGH

NEW PIPE BOX ON ROOF. SEE PIPE BOX ASSEMBLY DETAIL.

15 . WALL MOUNTED DUCTLESS FAN COIL UNIT. MOUNT B.E. OF UNIT 6' 8" A.F.F.

16 . CONDENSATE SHALL BE PUMPED FROM UNIT UNIT THROUGH PIPE BOX AND DISCHARGE ONTO

ROOF.

17 . DDC TEMERATURE SENSOR TO MONITOR IDF SPACE TEMPERATURE. MOUNT B.E. 4' 6" A.F.F..

18 . FACTORY WALL MOUNTED DUCTLESS UNIT THERMOSTAT. MOUNT B.E. 4' 6" A.F.F..

19 . 100% OUTSIDE AIR HANDLING UNIT MOUNTED ATOP 4" INTERIOR CONCRETE PAD. SEE

CONCRETE EQUIPMENT PAD DETAIL. SEE INDOOR OA AIR HANDLER DETAIL.

20 . INSTALL LOUVER WITH BOTTOM ELEVATION AT 5'-0" A.F.F. UNLESS NOTED OTHERWISE. SEE

STATIONARY LOUVER DETAIL.

21 . OA DUCT TAPS OUT OF THE BOTTOM OF THE MAIN TRUNK DUCT AND PENETRATES THE

CLASSROOM WALL BELOW THE STRUCTURAL BEAM. DUCT ELBOWS UP AFTER BEAM AND IS

ROUTED ABOVE CEILING. SEE ARCHITECTURAL DRAWINGS FOR DUCT CHASE.

22 . EXISTING DATA PANEL.

23 . EXISTING PLUMBING CLEAN OUT.

24 . 100% OUTDOOR AIR CONDENSING UNIT MOUNTED ATOP CONCRETE EQUIPMENT PAD.

REFRIGERANT AND HOT GAS PIPING SHALL ROUTED INTO BUILDING AS SHOWN. SEE PIPE

SLEEVE DETAIL.

25 . DO NOT BLOCK ACCESS PANELS WITH PIPING.

26 . INSTALL 6' TALL CHAINLINK FENCE AROUND EQUIPMENT YARD IN ACCORDANCE TO

SPECIFICATIONS. INSTALL 3'GATE IN FENCE FOR SERVICE ACCESS.

27 . SOFFIT FOR DUCTWORK. SEE SOFFIT DETAIL.

1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR A

1/8" = 1'-0"2 MECHANICAL NEW WORK PLAN - SECTOR C

No. Description Date

GENERAL NOTE: PROVIDE LINTELS AT ALL NEW DUCT PENETRATIONS

THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.

1/4" = 1'-0"3 SOFFIT DETAIL

WHHP-15

RTU-2

RTU-1

EF-4

EF-5

EF-12

EF-3EF-2

EF-6

"x

"x

10"ø

10"ø10"ø

10"ø

A3

A3

30"x10"

A3

A3

"x

"x

30"x10"

B1

A3

A3

A3

A3

2 2

CH-5

CH-2

CH-3

CCCC

CC

CH-6

A2

545 545 545 545

A2

CH-7

CH-8

800 800

HP-1

HP-2

KEF-1

KSF-1

DFCU-1

DOU-1

CLASSROOM

CONFERENCE

31 BOOK STORAGE

WORK ROOM

MEDIA CENTER

GIRLS

BOYS

JAN.

RECEPTIONIST

WORKROOM

PRINC.

235.58 SF

TOIL.

ASST. PRINC.

STAFF LOUNGE

KITCHEN

FREEZER

COOLER

VEST.

FOOD STORAGE

CORRIDOR

MECHANICAL

MEDIA PRODUCTION

TOIL.

AV STORAGE

STORAGE

CNSLR.

STORAGE

TOIL.

ELEC

CORRIDOR

CORRIDOR

CAFETERIA

STAGE

STOR.

STOR.

DISH WASH

CAN WASH

JAN.

LOCKERS

10 OFFICE

CLASSROOM

CORRIDOR

R

DAC-1

TT

TT

TT

TT

TT

TT TT

AHU-2

AHU-1

7 7

7 7

1 1/4" D

R R

A1

RTU-2

CH-4

DFCU-2.1

DFCU-3

DOU-3

S

WAITING

MM

MM

R

8"ø

MVD

3/4" D

MM

A1

A1

6"ø 6"ø

8"ø

MVD

6"ø

F.D.

F.D.F.D.

F.D.

TT

TT

NOTES: (THIS SHEET ONLY)

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

D

E

GA DOE ID #: 2058

M102

MECHANICAL NEW WORK

PLAN - SECTOR B

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR B

No. Description Date

1 . WALL HUNG HEAT PUMP. SEE WALL HUNG HEAT PUMP DETAIL - DUCTED SUPPLY.

2 . ROOF MOUNTED CENTRIFUGAL EXHAUST FAN. SEE ROOF MOUNTED CENTRIFUGAL EXHAUST FAN DETAIL.

3 . CEILING HEATER.

4 . ROOFTOP AIR CONDITIONING UNIT MOUNTED ON ROOF CURB ADAPTER. SEE ROOF CURB ADAPTER DETAIL.

5 . 100% OUTSIDE AIR UNIT MOUNTED ON ROOF. UNIT WILL DISCHARGE HORIZONTALLY.

7 . ATTACH NEW DUCT TO EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION. PROVIDE NECESARY

TRANSITIONS/OFFSET AS NEEDED TO MAKE CONNECTION.

8 . EXISTING GOOSE NECK FOR COMBUSTION AIR.

9 . NEW DOOR AIR CURTAIN MOUNTED IN SAME LOCATION AS DOOR AIR CURTAIN REMOVED DURING DEMOLITION. FIELD VERIFY EXISTING DOOR DIMENSIONS TO ENSURE NEW DOOR AIR CURTAIN MATCHES.

10 . NEW HEAT PUMP MOUNTED ON EXSITING CONCRETE EQUIPMENT PAD. ROUTE NEW REFRIGERANT LINES

FROM NEW HEAT PUMP TO NEW FAN COIL UNIT USING THE EXISTING WALL PENETRATIONS.

11 . NEW VERTICAL FAN COIL UNIT MOUNTED IN PLACE OF EXISTING. CONNECT TO EXISTING SUPPLY DUCT AND CONDENSATE LINE. ROUTE NEW REFRIGERANT LINES ALONG THE EXISTING REFRIGERANT LINE'S PATH.

12 . NEW KITCHEN HOOD SUPPLY FAN MOUNTED ON EXISTING CURB. PROVIDE CURB ADAPTER AS NEED.

13 . NEW KITCHEN HOOD EXHAUST FAN MOUNTED ON EXISTING CURB. PROVIDE CURB ADAPTER AS NEED.

14 . NEW DUCTLESS HEAT PUMP MOUNTED ON NEW EQUIPMENT SUPPORT PLATFORM. SEE ROOF MOUNTED EQUIPMENT SUPPORT PLATFORM DETAIL. REFRIGERANT PIPING ROUTED THROUGH NEW PIPE BOX ON

ROOF. SEE PIPE BOX ASSEMBLY DETAIL.

15 . NEW DUCTLESS CEILING CASSETTE MOUNTED IN CEILING IN THIS APPROXIAMTE LOCATION. FEILD VERIFY EXISTING CONDITIONS AND SHIFT UNIT AS NEEDED. UNIT'S SUPPLY GRILLE FACING HOOD SHALL BE

BLANKED OFF TO NOT INTERFERE WITH HOOD PERFORMANCE.

16 . CAP AND SEAL EXISTING GRAVITY VENT ON ROOF AIR TIGHT.

17 . NEW DDC CONTROL PANEL MOUNTED ON WALL. V

18 . EXISTING DUCT MOUNTED SMOKE DETECTOR.

19 . ALL REFRIGERANT PIPING AND CONDENSATE PIPING SHALL BE CONCEALED BEHIND RECTORSEAL

FORTRESS LINE HIDE KIT OR EQUAL ONCE IT PENETRATES CEILING.

20 . CONDENSATE SHALL BE PUMPED FROM UNIT UNIT THROUGH PIPE BOX AND DISCHARGE ONTO ROOF.

21 . WALL MOUNTED DUCTLESS FAN COIL UNIT. MOUNT B.E. OF UNIT 6' 8" A.F.F.

22 . DDC TEMERATURE SENSOR TO MONITOR IDF SPACE TEMPERATURE. MOUNT B.E. 4' 6" A.F.F..

23 . FACTORY WALL MOUNTED DUCTLESS UNIT THERMOSTAT. MOUNT B.E. 4' 6" A.F.F..

GENERAL NOTE: PROVIDE LINTELS AT ALL NEW DUCT PENETRATIONS

WHHP-11

RTU-6

RTU-5

"x

"x

" 10"ø

10"ø10"ø

10"ø

A3

A3

30"x10"

B1

CC CC

EF-9EF-10

CH-9

CH-10

400400

400 400 300

875 875

875 875

875 875

875 875

OAU-2

"x

ART CENTER

STOR.

STOR.

MUSIC ROOM

CLASSROOM

CORRIDOR

GIRLS

TOIL.

46JAN.

STOR.

GYMNASIUM

COACHES OFFICE

TOIL.

BOYS

RTU-7 RTU-8

A2

TT

TT

TT

16 16

150 -

A1

6"ø

3/4" D

3/4" D

/2

D

18(TYP)

18(TYP)

22 22

TTTT

S

EF-11

CC

D1

D1

D1

D1

D1

D1

"x

8"ø 12"x6"

12"x6"

8"ø 8"ø 8"ø

12"x6"

12"x6"

8"ø

8"ø 12"x6"12"x6"8"ø

12"ø

IU-5

IU-2

IU-3

IU-1

IU-6 IU-7 IU-8

IU-4

MBC-1

HRU-1

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CORRIDOR

CLASSROOM

CLASSROOM

GIRLS

BOYS

JAN.

OAU-3

TT

TT

TT TT

TT TT

R R

R

R

RRR

R

R

R

TT

23 23

232323

1 1/2" D

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

A

B

C

D

E

GA DOE ID #: 2058

M103

MECHANICAL NEW WORK

PLAN - SECTOR D & E

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR D

1/8" = 1'-0"2 MECHANICAL NEW WORK PLAN - SECTOR E

1 . WALL HUNG HEAT PUMP. SEE WALL HUNG HEAT PUMP DETAIL - DUCTED SUPPLY.

2 . ROOF MOUNTED CENTRIFUGAL EXHAUST FAN. SEE ROOF MOUNTED CENTRIFUGAL EXHAUST FAN

DETAIL.

3 . CEILING HEATER.

4 . ROOFTOP AIR CONDITIONING UNIT MOUNTED ON ROOF CURB ADAPTER. SEE ROOF CURB ADAPTER

DETAIL.

5 . VRF CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED TO OVERHEAD

STRUCTURE WITH SUPPLEMENTAL 2"X2"X1/4" ANGLE IRON.

6 . MAIN/SUB VRF BRANCH CONTROLLER. BRANCH CONTROLLER SHALL BE MOUNTED ABOVE CEILING.

SUSPEND FROM DROP RODS (MIN 3/8") AND CONNECTED TO OVERHEAD STRUCTURE WITH 2"X2"X1/4" ANGLE IRON. PROVIDE DRAIN PAN BELOW MBC/SBC.SEE VRF DRAIN PAN DETAIL. PROVIDE AUXILIARY

DRAIN PAN UNDER BRANCH CONTROLLER. SEE CONDENSATE AUXILIARY DRAIN PAN DETAIL.

MOUNT RECTORSEAL AG9150 SENSOR IN PAN AND AUDIBLE ALARM. ALARM SHALL BE MOUNTED AT

CEILING LEVEL. PROVIDE 24V TRANSFORMER TO POWER SENSOR.

7 . VRF HEAT RECOVERY UNIT MOUNTED ON CONCRETE EQUIPMENT PAD.

8 . 100% OUTSIDE AIR DUCT PENETRATES BUILDING IN THIS APPROXIMATE LOCATION. SEE

RECTANGULAR DUCT THRU EXTERIOR WALL DETAIL.

9 . 100% OUTSIDE AIR UNIT MOUNTED ATOP CONCRETE EQUIPMENT PAD. SEE CONCRETE EQUIPMENT

PAD DETAIL.

10 . ATTACH NEW DUCT TO EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION.

11 . GENERAL: PIPE SLEEVES. SEE PIPE SLEEVE DETAIL.

12 . REFRIGERANT BRANCH LIQUID AND GAS REFRIGERANT PIPING TO INDOOR UNIT FROM BRANCH

CONTROLLER. SEE VRF SCHEMATIC FOR REFRIGERANT PIPE SIZES.

13 . REFRIGERANT HIGH PRESSURE AND LOW PRESSURE REFRIGERANT PIPING FROM OUTDOOR UNIT

TO MAIN BRANCH CONTROLLER. SEE VRF SCHEMATIC FOR REFRIGERANT PIPE SIZES. MOUNT

EXTERIOR REFRIGERANT PIPE ON ROOF ATOP B-LINE DURABLOCK (DB) SUPPORTS. SUPPORT

PIPING ON 6 FT. CENTERS.

14 . MAIN 1.5" CONDENSATE DRAIN PIPING SHALL BE LOCATED AS HIGH AS POSSIBLE. CONDENSATE

SHALL HAVE PROPER SLOPE (MIN 1/4" PER FOOT).

15 . PROVIDE 1.5" ELBOW UP AND MINIMUM 8" TALL VERTICAL OPEN STAND PIPE AT THIS APPROXIMATE

LOCATION.

16 . GROUND MOUNTED HORIZONTAL DISCHARGE PACKAGED HEAT PUMP MOUNTED ON EXISTING

CONCRETE EQUIPMENT PAD. VERIFY EXISTING PAD WILL SUFFICE. EXTEND AS NEEDED. SEE

CONCRETE EQUIPMENT PAD DETAIL.

17 . VRF CENTRALIZED CONTROLLER MOUNTED ON WALL WITH B.E. 4' 6" A.F.F.

18 . CONDENSATE PIPE SUPPORT ON ROOF. SEE CONDENSATE PIPE SUPPORT ON ROOF DETAILS.

19 . PROVIDE FULL SIZE, SLOPED (1/4" PER FOOT), TRAPPED, SCHEDULE 40 PVC PIPING TO DISCHARGE

AS SHOWN ON DRAWINGS . DRAIN PIPING SHALL BE PROVIDED FROM EACH RTAC AS SHOWN ON

DRAWINGS. INSURE THAT DRAIN PIPING DOES NOT BLOCK RTAC ACCESS PANELS. DO NOT ROUTE

DRAIN PIPING IN FRONT OF ACCESS PANELS. SEE CONDENSATE DRAIN TRAP DETAIL AND

CONDENSATE ROOF SUPPORT DETAIL(S).

20 . EXTEND CONCRETE EQUIPMENT PAD AND FENCING (ACCORDING TO SPEC) AS NEEDED TO FIT NEW UNIT. EXISITING FENCE MAY NEED EXTENSION AS WELL. FIELD VERIFY EXACT EXTENSIONS NEEDED.

SEE CONCRETE EQUIPMENT PAD DETAIL.

21 . WALL MOUNTED DDC SPACE TEMPERATURE/HUMIDITY SENSOR. MOUNT B.E. OF SENSOR 4' 6" A.F.F..

22 . WALL MOUNTED DDC SPACE TEMPERATURE/HUMIDITY SENSOR. MOUNT B.E. OF SENSOR 4' 6" A.F.F..

23 . FACTORY WALL MOUNTED VRF WIRED UNIT THERMOSTAT/CONTROLLER. MOUNT B.E. 4' 6" A.F.F..

24 . INSTALL 6' TALL CHAINLINK FENCE AROUND EQUIPMENT YARD IN ACCORDANCE TO SPECIFICATIONS.

INSTALL 3'GATE IN FENCE FOR SERVICE ACCESS.

NOTES: (THIS SHEET ONLY)

GENERAL: DRAWINGS SHOW GENERAL ARRANGEMENT, LAYOUT AND LOCATION OF PIPING, APPURTENANCES, ETC., BUT DO NOT SHOW ALL REQUIRED FITTINGS AND OFFSETS THAT MAY BE NECESSARY TO RUN PIPING AND CONNECT TO EQUIPMENT, ETC. OFFSET PIPING AROUND ALL OBSTRUCTIONS. FABRICATE AND INSTALL PIPING, FITTINGS, ETC. BASED ON FIELD MEASUREMENTS. PROVIDE ALL NECESSARY FITTINGS AND OFFSETS AT NO ADDITIONAL COST TO THE OWNER. PIPE ROUTING SHOWN ON DRAWINGS SHALL BE ALTERED BY CONTRACTOR WHERE REQUIRED TO AVOID INTERFERENCE AND CLEARANCE DIFFICULTIES. CAREFULLY COORDINATE PIPE ROUTING WITH ROOF MOUNTED GAS PIPING, CONDUITS AND EQUIPMENT TO AVOID

CONFLICTS .

No. Description Date

GENERAL NOTE: PROVIDE LINTELS AT ALL NEW DUCT PENETRATIONS

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

GA DOE ID #: 2058

M301

PIPING/WIRING DIAGRAMS

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

NOT TO SCALE

VRF PIPING DIAGRAM

NOT TO SCALE

VRF WIRING DIAGRAM

GENERAL NOTES:

1. EQUIPMENT MODEL NUMBERS INDICATED ARE FOR BASIS-OF-DESIGN

MANUFACTURER, CARRIER, UNLESS NOTED OTHERWISE.

2. REFRIGERANT PIPING SIZES INDICATED ARE APPROXIMATE AND SHALL BE

VERIFIED / COORDINATED WITH EQUIPMENT SUPPLIER BASED ON REQUIRED

LENGTHS, SYSTEM LAYOUT / INSTALLATION, SYSTEM CAPACITY, AND OTHER

FACTORS AS REQUIRED BY MANUFACTURER.

NOT TO SCALE

VRF CENTRALIZED CONTROLLER

No. Description Date

NOT TO SCALE

OAU-1 HOT GAS BYPASS PIPING DIAGRAM

NOT TO SCALE

OAU-1 HOT GAS REHEAT PIPING DIAGRAM

MAIN ROUND TRUNK DUCT

2 3/16" DUCT WRAP INSULATION FOR

SUPPLY AND RETURN DUCT

OPENING IN SIDE OF RECTANGULAR SHEET METAL

DUCT SHALL BE CUT WITH DRILL-CUTTER OR TIN

SNIPS. DIAMETER OF OPENING SHALL MATCH INNER

DIAMETER OF FOAM GASKET OR DIAMETER

RECOMMENDED BY TAKEOFF MANUFACTURER

DUCT

DUCT MASTICSHEET METAL SCREWS ON 6" CENTERS

FOAM GASKET

EXTERIOR VAPOR BARRIER (ONLY) SECURED

TO FITTING WITH NYLON "ZIP STRIP" BAND

SECURE INNER DUCT TO FITTING WITH NYLON

ZIP STRIP BAND IN ADDITION TO NYLON

STRIPBAND. SEAL INNER CORE TO DUCT.

FLEXIBLE DUCTWORK

90° SADDLE TAKEOFF COLLAR DAMPER AND THERMA-SEAL

GASKET FLANGE AND DAMPER HANDLE STANDOFF, SIMILAR TO

CROWN PRODUCT MODEL #314-DSO

FOR SUPPLY/RETURN DUCTS, INSULATE ENTIRE FITTING (EXCEPT OPERATOR

HANDLE) WITH 2 3/16" DUCT WRAP. SEAL WITH VAPOR PROOF MASTIC AND CLOTH

FABRIC OVERLAPPING ESCUTCHEON AND DUCT WRAP FSK JACKET TO PREVENT

PASSAGE OF SMOKE.

20 GAUGE GALVANIZED SHEET METAL COVER

SEAL AND CAULK ALL JOINTS WATERTIGHT

A S

R E

Q U

IR

E

D

AS REQUIRED

SHEET METAL COVER ATOP ANGLE IRON

CONTINUOUS INSULATION

LAG SCREWS TO CURB ON MAXIMUM 16" CENTERS

EXISTING ROOF CURB TO REMAIN FOR REUSE

EXISTING ROOF AND DECK

PLAN VIEW

ELEVATION VIEW

CONTRACTOR SHALL FIELD VERIFY

EXACT CURB DIMENSIONS PRIOR

TO FABRICATING CURB CAP.

3" X 3" X ¼" ANGLE IRON FULLY WELDED

(PROVIDE CENTER ANGLE AT MIDSPAN

FOR ALL CURBS LARGER THAN 8 SQ. FT.)

NOTE: ALL ITEMS IN THIS DETAIL ARE NEW UNLESS NOTED OTHERWISE.

CURB CAP IS TO BE CONSTRUCTED OF 3" X 3" X ¼" ANGLE IRON

MEMBERS, MITERED OR BUTTED AS SHOWN AND WELDED TOGETHER.

COVER ENTIRE FRAME WITH 20 GA. GALVANIZED SHEET METAL. SEAL

AND CAULK ALL SEAMS WATERTIGHT. LINE ENTIRE UNDERSIDE WITH 1 ½"

RIGID FIBERGLASS INSULATION. SECURE TO EXISTING CURB WITH

GALVANIZED LAG SCREWS ON 16" CENTERS.

PROVIDE 1" WIDE CLOSED CELL

ELASTOMERIC (ARMAFLEX) TAPE

AROUND FULL PERIMETER OF

CURB TO SEAL COVER TO CURB.

PROVIDE BACKERBOARD IN ANY GAPS

AND SEAL AIR TIGHT WITH SILICONE

CAULK AROUND FULL PERIMETER

AT POINT WHERE ANGLE IRON OVERLAPS

CURB.

CEILING, BY ARCHITECTURAL

SQUARE TO ROUND TRANSITION (WHERE ELBOW CONNECTS TO SQUARE

NECK DIFFUSERS). PROVIDE ROUND TO ROUND TRANSITION WHERE GRILLE

NECK SIZE DIFFERS FROM CONNECTING DUCT SIZE (EITHER LARGER OR

SMALLER). INSULATE ON SUPPLY DUCTS.

3 GORE ADJUSTABLE ELBOW. INSULATE

ON SUPPLY DUCTS.

NYLON ZIP STRIP ON OUTER VAPOR BARRIER.

ENSURE INSULATION IS PULLED DOWN WITH

VAPOR BARRIER SO NO DUCTWORK IS

UNINSULATED.

NOTE: DETAIL IS TYPICAL FOR ALL FLEX DUCT RUNOUTS TO DIFFUSERS

STAINLESS STEEL DRAWBAND

ON INNER DUCT

FLEX DUCT

INSULATION BLANKET ON TOP

OF SUPPLY DIFFUSERS

CEILING DIFFUSER

J

POWER WIRING AND CONDUIT BY ELECTRICAL

PROVIDE "KNOCK OUT" AND GROMMET

FOR POWER CABLE

ROOF CURB. SEE ROOF CURB DETAIL.

POWER CABLE BY ELECTRICAL

REMOVABLE ACCESS COVER FOR MOTOR

COMPARTMENT

INTERNAL FACTORY INSTALLED NEMA-1 DISCONNECT

SWITCH UNLESS SCHEDULED OTHERWISE

SEE SCHEDULE FOR DRIVE TYPE. (PROVIDE

ADJUSTABLE SHEAVE FOR ALL BELT DRIVE)

FACTORY WIRED FROM MOTOR TO

DISCONNECT SWITCH.

EXHAUST FAN

FACTORY FURNISHED DAMPER TRAY TO SUPPORT

BACK DRAFT DAMPER AND PROVIDE DUCT

ATTACHMENT.

FULL PERIMETER ANGLE IRON FRAMING BENEATH

CURB BY STRUCTURAL.

SECURE DUCT TO ROOF STRUCTURE WITH SHEET

METAL ON 4 SIDES. DUCT SHALL NOT BE

SUPPORTED BY DAMPER TRAY.

EXHAUST DUCT UP FROM BELOW

EXHAUST DUCT SHALL TRANSITION AS REQUIRED AT

UNDERSIDE OF ROOF DECK TO MATCH FANS DAMPER/

CURB SIZE.

MINIMUM 1 1/4" CLEARANCE FOR CONDUIT

FACTORY INSTALLED, MINIMUM 1/2"

DIA. CONDUIT CHASE

J

POWER WIRING AND CONDUIT BY ELECTRICAL

PROVIDE "KNOCK OUT" AND GROMMET

FOR POWER CABLE

ROOF CURB. SEE ROOF CURB DETAIL.

POWER CABLE BY ELECTRICAL

REMOVABLE ACCESS COVER FOR MOTOR

COMPARTMENT

INTERNAL FACTORY INSTALLED NEMA-1 DISCONNECT

SWITCH UNLESS SCHEDULED OTHERWISE

SEE SCHEDULE FOR DRIVE TYPE.

FACTORY WIRED FROM MOTOR TO

DISCONNECT SWITCH.

UPBLAST EXHAUST FAN

FACTORY FURNISHED DAMPER TRAY TO SUPPORT

BACK DRAFT DAMPER AND PROVIDE DUCT

ATTACHMENT.

FULL PERIMETER ANGLE IRON FRAMING BENEATH

CURB BY STRUCTURAL.

SECURE DUCT TO ROOF STRUCTURE WITH SHEET

METAL ON 4 SIDES. DUCT SHALL NOT BE

SUPPORTED BY DAMPER TRAY.

EXHAUST DUCT UP FROM BELOW

EXHAUST DUCT SHALL TRANSITION AS REQUIRED AT

UNDERSIDE OF ROOF DECK TO MATCH FANS DAMPER/

CURB SIZE.

MINIMUM 1 1/4" CLEARANCE FOR CONDUIT

FACTORY INSTALLED, MINIMUM 1/2"

DIA. CONDUIT CHASE GALVANIZED BIRD SCREEN

SECURE CURB CAP TO CURB WITH ANCHORS ON

MAXIMUM 12" CENTERS (MINIMUM 2 ANCHORS

EACH SIDE)

GRADE

WELDED WIRE MESH

AT MID DEPTH OF SLAB

6" X 6" 10/10 WWF

3000 PSI CONCRETE

1" CHAMFER

SEE SPECIFICATIONS FOR

PAD HEIGHT ABOVE

ADJACENT GRADE

2" MINIMUM

EXTERIOR CONCRETE PAD

FLOOR

1" CHAMFER

ANCHOR (TYPICAL OF 4)

INTERIOR CONCRETE PAD

WELDED WIRE MESH

AT MID DEPTH OF SLAB

6" X 6" 10/10 WWF

SEE SPECIFICATIONS FOR

PAD HEIGHT ABOVE

ADJACENT GRADE

2"

3000 PSI CONCRETE

1½"

3"

UNION

AC UNIT

DRAIN CONNECTION

DRAIN PIPE SHALL BE AT LEAST

THE SAME DIAMETER AS THE NIPPLE

ON THE DRAIN PAN CONNECTION

OPEN END NIPPLE

SEE DRAWINGS FOR

PIPE REQUIRED MATERIAL

SLOPE AS REQUIRED

IN SPECIFICATIONS

PIPE NIPPLE

6"

FRONT VIEW

4"

SIDE VIEW

V A

R

IE

S

CONDENSATE PIPE,

VERIFY SIZE (TYP)

UV - STABILIZED, EDPM ADJUSTABLE RUBBER PIPE

SUPPORT, VERIFY PIPE DIAMETER BEING SUPPORTED.

SPACED ON MAXIMUM 8 FT. CENTERS AND 24" OF

FITTINGS (ERICO CADDY PYRAMID RPSE - TYPICAL)

INSTALL CONDENSATE PIPE AT THE LOWEST

POSSIBLE ELEVATION TO REDUCE TOP

HEAVY PIPE AND TO REDUCE TIPPING OVER

BUT TO MAINTAIN SPECIFIED SLOPE.

GENERAL: THIS CONDENSATE SUPPORT SHALL BE USED WITH DRAIN ELEVATIONS ABOVE ROOF OF 7" OR LESS. CONDENSATE ELEVATIONS ABOVE 8" SHALL USE ERICO CADDY PYRAMID ST ADJUSTABLE

STRUT SUPPORT OR EQUAL BY MIRO.

OPENING IN SIDE OF RECTANGULAR

SHEET METAL DUCT SHALL BE CUT

WITH DRILL CUTTER (NOT TIN SNIPS).

DIAMETER OF OPENING SHALL MATCH

INNER DIAMTER OF FOAM GASKET.

DUCT

DUCT MASTIC

FOAM GASKET

SHEET METAL SCREWS

ON 4" CENTERSDUCT

2" DUCT WRAP INSULATION FOR SUPPLY DUCT

EXTERIOR VAPOR BARRIER (ONLY) SECURED TO

FITTING WITH NYLON "ZIP-STRIP" BAND

FLEXIBLE DUCTWORK

BELLMOUTH OR 45° FITTING WITH DAMPER

FOR SUPPLY DUCTS, INSULATE ENTIRE FITTING (EXCEPT OPERATOR HANDLE)

WITH 2" DUCTWRAP. SEAL WITH VAPOR PROOF MASTIC AND CLOTH FABRIC OVERLAPPING

ESCUTCHEON AND DUCT WRAP FSK JACKET TO PREVENT PASSAGE OF SMOKE.

PROVIDE OPTIONAL EXTENDED NECK SHAFT

FOR INSULATED DUCTS TO CLEAR INSULATION THICKNESS

SECURE INNER DUCT TO FITTING WITH 1/2" STAINLESS STEEL

DRAW BAND. CONTRACTOR SHALL NOT UTILIZE NYLON "ZIP-

STRIP" BAND TO SECURE INNER DUCT TO FITTING.

AIR

NOTE: SINGLE BI-POLAR IONIZATION UNIT SHOWN. INSTALLATION SIMILAR WHEN

MULTIPLE UNITS ARE INSTALLED IN ONE HVAC UNIT, EXCEPT 24V WIRING FROM

HVAC UNIT'S TERMINAL SIDE SHALL FEED CONTRACTOR FURNISHED TERMINAL

STRIP, WHICH SHALL THEN FEED POWER TO MULTIPLE UNITS. CONTRACTOR

FURNISHED TERMINAL STRIP SHALL BE ELECTRICALLY ISOLATED FROM THE HVAC

UNIT CASING AND ALL OTHER METAL COMPONENTS.

SECURE WITH SCREWS IN LOCATION THAT

WILL NOT DAMAGE HVAC EQUIPMENT OR

ASSOCIATED REFRIGERANT PIPE, WIRING

OR OTHER COMPONENTS

NEEDLEPOINT ELECTRODES. ENSURE UNIT IS

ORIENTED AND INSTALLED SO THAT AIR FLOW

PASSES BETWEEN ELECTRODES (INSTALL

PERPENDICULAR TO AIRFLOW). MAINTAIN

MANUFACTURER'S DISTANCE FROM NEEDLES

TO METAL SURFACE TO PREVENT ARCING.

FACTORY

FURNISHED

24VAC WIRING

BI-POLAR UNIT. SEE SCHEDULE FOR QUANTITY.

SEE ENLARGED DRAWING BELOW.

LED CONFIRMING IONIZATION OPERATION

B.A.S. CONTACTS TO ALLOW OWNER TO MONITOR STATUS.

MONITORING IS NOT INCLUDED IN THIS PROJECT.

BI-POLAR IONIZATION UNIT MOUNTED INSIDE UNIT DOWNSTREAM OF

FILTER IN SUPPLY AIRSTREAM IN LOCATION APPROVED BY HVAC

EQUIPMENT MANUFACTURER AND BI-POLAR MANUFACTURER

(FAN)

(24V POWER)

G

R

Y

W

C

O

CONNECT TO FAN AND 24V POWER TERMINALS ON 24 VAC

TERMINAL STRIP IN HVAC EQUIPMENT. ADDITIONAL GENERIC

TERMINALS ARE SHOWN FOR SYMBOLIC PURPOSES AND

ACTUAL TERMINALS WILL VARY BASED ON TYPE OF

EQUIPMENT.

PROVIDE ADDITIONAL WIRING (AS REQUIRED) IF FACTORY FURNISHED

WIRING WILL NOT REACH 24VAC TERMINAL STRIP. PROVIDE WIRE NUTS

AND ELECTRICAL TAPE AT JOINT. MATCH WIRE GAUGE OF

MANUFACTURER'S WIRING.

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

GA DOE ID #: 2058

M501

MECHANICAL DETAILS

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

NOT TO SCALE

90° SADDLE TAP TAKEOFF FITTING DETAIL

NOT TO SCALE

CAP AT EXISTING CURB

NOT TO SCALE

CEILING GRILLE DUCT CONNECTION DETAIL

NOT TO SCALE

CENTRIFUGAL DOWN BLAST EXHAUST FAN DETAIL

NOT TO SCALE

CENTRIFUGAL UPBLAST EXHAUST FAN DETAIL (CHECK)

NOT TO SCALE

CONCRETE EQUIPMENT PAD DETAIL

NOT TO SCALE

CONDENSATE DRAIN TRAP DETAIL

NOT TO SCALE

CONDENSATE PIPE SUPPORT ON ROOF DETAIL

NOT TO SCALE

BELLMOUTH AND 45° TAKEOFF FITTING DETAIL

NOT TO SCALE

COMPACT BI-POLAR IONIZATION UNIT DETAIL

PROVIDE INSULATED HOUSING WHERE SCHEDULED

DUCT

AIRFLOW

PARALLEL BLADE BACKDRAFT DAMPER

SQUARE ACCESS PANEL FOR DAMPER ACTUATOR ACCESS

ACCESS PANEL (BOTH SIDES)

MOUNTING BRACKETS (TYP)

HANGING VIBRATION ISOLATORS. SEE SPECS FOR TYPE.

THREADED ROD

SUPPLEMENTAL ANGLE IRON FRAMING

DOUBLE NUTS

DOUBLE NUTS

DUCT

MOTOR. SEE SPECS FOR TYPE.

NOTE: BELT DRIVE FAN SIMILAR, EXCEPT MOTOR

OUTISDE OF FAN CASING, AND WITH INSULATED

MOTOR COVER WHERE SPECIFIED.

DUCT MOUNTING COLLAR (TYP INLET AND OUTLET). PROVIDE

1/2" X 1/2" WELDED WIRE GALVANIZED INLET GUARD FOR

NON-DUCTED INLET APPLICATIONS AS SCHEDULED.

MAINTAIN MINIMUM 2.5 TIMES WHERE DIAMETER STRAIGHT

DUCT LENGTH AT INLET AND OUTLET OF FAN BEFORE

ELBOW, TRANSITION, DAMPER, ETC.

PROVIDE MOTORIZED DAMPER WITH INTERNAL ACTUATOR WHERE

SCHEDULED. DAMPER VOLTAGE SHALL MATCH FAN VOLTAGE.

FLEXIBLE DUCT

CONNECTION (TYP)

GALVANIZED MOTOR COVER

WHERE SCHEDULED

BACKWARD

INCLINED WHEEL

MAINTAIN MINIMUM 2.5 TIMES

WHEEL DIAMETER STRAIGHT

DUCT LENGTH AT INLET AND

OUTLET OF FAN BEFORE ELBOW,

TRANSITION, DAMPER, ETC.

FACTORY INSTALLED NEMA-1

DISCONNECT SWITCH

FACTORY WIRED FROM MOTOR

TO DISCONNECT SWITCH

WELD SIDE ANGLE CLIP TO PAN (TYP OF 4)

TO CORNERS. SUSPEND WITH 3/8"

THREADED ROD. DO NOT BLOCK ACCESS

TO CONTROLLER.

PAN SHALL BE MIN. 18 GAUGE

GALVANIZED STEEL

2"

3/4" NIPPLE WELDED

TO PAN

PIPE 3/4" PAN DRAIN TO LOCATION

SHOWN ON DRAWINGS. SLOPE

PAN TO THIS SIDE.

FABRICATE DRAIN PAN MINIMUM

12" LONGER AND WIDER THAN

MAIN/SUB CONTROLLER

FABRICATE DRAIN PAN MINIMUM

12" LONGER AND WIDER THAN

MAIN/SUB CONTROLLER

18 GAUGE GALVANIZED SHEET METAL COVER FACTORY

FABRICATED BY EQUIPMENT SUPPORT MANUFACTURER

SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.AS REQUIRED

RAISED CHANNEL SUPPORT FOR

MOUNTING OF HEAT PUMPS (TYP).

CHANNELS TO BE FACTORY

FABRICATED INTO COVER.

COORDINATE SPACING OF SUPPORT CHANNELS

WITH DIMENSIONS OF HEAT PUMPS BEING

INSTALLED ATOP PLATFORM. SEE PLANS

FOR UNIT LAYOUT.

ROOF CURB. SEE ROOF CURB DETAIL.COORDINATE LENGTH OF PLATFORM

REQUIRED WITH UNIT LAYOUT INDICATED

ON PLANS

ISOMETRIC VIEW

HEAT PUMP UNIT. SEE PLANS FOR SIZING AND LAYOUT.

SECURE HEAT PUMP

TO SUPPORT CHANNEL.

LAG SCREWS TO CURB ON

MAXIMUM 16" CENTERS.

ROOF CURB. SEE

ROOF CURB DETAIL.

PROVIDE FACTORY FURNISHED

INTERNAL SUPPORT CHANNELS

AS REQUIRED TO SUPPORT

WEIGHT OF HEAT PUMP UNITS.

ROOF DECK SHALL BE

CONTINUOUS UNDER CURB.

6" (MIN.)

FRONT VIEW

PRESSURE TREATED WOOD NAILER

SHEET METAL SCREW IN SIDE OF

COUNTER FLASHING (TYP)

18 GAUGE GALVANIZED STEEL

COUNTER FLASHING

SHEET METAL SCREW (TYP)

18 GAUGE STEEL BASE SECTION

FIELD INSTALLED INSULATION

INTEGRAL 18 GAUGE

GALVANIZED

STEEL BASE PLATE

FIELD INSTALLED CANT

ROOF DECK CONTINUOUS

BENEATH SUPPORT RAIL

SEE ARCHITECTURAL DRAWINGS FOR SPECIFIC

DETAILS CONCERNING ROOF CONSTRUCTION,

FLASHING, ANCHORS, BLOCKING,

ROOF DECK TYPE, ETC.

C U

R B

H E

IG

H

T

S T

Y

LE

A

S T

Y

LE

B

S T

Y

LE

C

2" MAX.

1" 1"

FOLDING BLADE STATIC RATED FIRE DAMPER

IN TYPE 'B' FRAME (EXCEPT TYPE 'A' SHALL BE

USED AT SIDEWALL REGISTERS AND NON-DUCTED

TRANSFER OPENING). DYNAMIC RATED DAMPERS

SHALL BE USED WHERE SPECIFICALLY SHOWN

ON DRAWINGS

ATTACH FIRE DAMPER TO SLEEVE IN

ACCORDANCE WITH MANUFACTUER'S

UL INSTALLATION INSTRUCTIONS

FACTORY FURNISHED ROUND OR OVAL

TRANSITION WITH BLADE STACK OUT

OF AIR STREAM

ROUND AND OVAL FIRE DAMPER

INSTALLATION SIMILAR

DUCT (WHERE APPLICABLE)

SLEEVE LENGTH SHALL BE DETERMINED BY CONTRACTOR TO

BE WITHIN MINIMUM AND MAXIMUM DISTANCE FROM

WALL/FLOOR AS REQUIRED BY MANUFACTUER

NOTE: INSTALLATION SHALL CONFORM TO THE FIRE

DAMPERS MANUFACTURER'S "UL" INSTALLATION

INSTRUCTIONS

WALL OR FLOOR. CONTRACTOR SHALL VERIFY

THICKNESS RATING, AND MATERIAL OF

CONSTRUCTION FROM ARCHITECTURAL DRAWINGS,

AND USE THIS INFORMATION TO SELECT FIRE

DAMPER AND FIRE DAMPER ACCESSORIES.

PROVIDE MINIMUM OVERLAP ALL AROUND AS REQUIRED BY

MANUFACTURER'S UL INSTALLATION INSTRUCTIONS

CLEARANCE (TYPICAL) AS REQUIRED BY MANUFACTURER'S

UL INSTALLATION INSTRUCTIONS

165° FUSIBLE LINK

DUCT TO SLEEVE CONNECTION SHALL BE AN APPROVED

TYPE AS LISTED IN THE MANUFACTURER'S UL INSTALLATION

INSTRUCTIONS. PROVIDE DUCT SEALANT APPROVED BY

FIRE DAMPER MANUFACTURER.

PROVIDE ACCESS PANEL FOR RECTANGULAR DUCTS. FOR ROUND DUCTS,

DOOR SIZE SHALL BE AS NOTED IN SPECIFICATIONS. FOR FLOOR

PENETRATIONS ACCESS PANEL SHALL BE ABOVE FLOOR.

FACTORY PROVIDED SLEEVE. SLEEVE LENGTH AND GAUGE SHALL

BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH

MANUFACTURER'S UL INSTALLATION INSTRUCTIONS.

FACTORY PROVIDED RETAINING ANGLES. ANGLE SIZE AND GAUGE

SHALL BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH

MANUFACTURER'S UL INSTALLATION INSTRUCTIONS.

GROUT

1" ABOVE FLOOR; FLUSH FOR WALLS

SCHEDULE 10 (MINIMUM)

STEEL PIPE

CONDUIT OR PIPING

PIPING INSULATION AS SPECIFIED.

PIPE INSULATION SHALL BE CONTINUOUS

THRU PENETRATION.

SEAL BETWEEN SLEEVE AND PIPING WITH FIRE RESISTANT

SEALANT OF SUFFICIENT THICKNESS TO MAINTAIN WALL'S

OR FLOOR FIRE RATING (1" MINIMUM THICKNESS). IF WALL

IS NOT FIRE RATED, PROVIDE CAULKING IN LIEU OF FIRE

RESISTANT SEALANT. SEALANT IS ONLY REQUIRED ON

ONE SIDE OF WALL, UNLESS REQUIRED BY MANUFACTURER

ON BOTH SIDES.

FIBERGLASS BATTS PACKED BETWEEN SLEEVE

AND PIPE (OR PIPE INSULATION ON INSULATED PIPE)

WALL OR FLOOR. CONTRACTOR SHALL VERIFY

CONSTRUCTION TYPE (MASONRY, CONCRETE,

BRICK AND CMU, ETC.) AND THICKNESS.

INSIDE

UNINSULATED REFRIGERANT LIQUID PIPE

REFRIGERANT PIPE DROPS

IN WALL AS REQUIRED

INSULATED REFRIGERANT

SUCTION PIPE

20 GAUGE GALVANIZED

STEEL SHEET METAL SLEEVE

TERMINATE SLEEVE

FLUSH WITH WALL

OUTSIDE

PIPE PENETRATES WALL

NEAR GRADE LEVEL

EXTERIOR PAINTABLE SILICON CAULK.

PAINT TO MATCH EXTERIOR. EXTERIOR WALL. SEE ARCHITECTURAL PLANS

FOR CONSTRUCTION

FIRE RESISTANT FOAM OF APPROPRIATE

THICKNESS TO MAINTAIN WALL'S FIRE RATING

(1" MINIMUM THICKNESS)

DIA. -",

(SEE PLANS)

3"

DIM. + ?"

DIM. + ?"

3"

PAINT INTERIOR OF BOX MATTE BLACK.1

2 MINIMUM 26 GAUGE GALV. SHEET METAL.

4 ADAPTER MAY BE FABRICATED BY CONTRACTOR OR PROVIDED BY CROWN

PRODUCTS MODEL #666 ADAPTER OR EQUAL.

PROVIDE 1/2" DUCT LINER ON RETURN DUCT

APPLICATIONS AND NO LINER ON EXHAUST APPLICATION.

NOTES: (THIS DETAIL ONLY)

CAULK AROUND FULL PERIMETER OF ANGLE

EACH SIDE OF WALL.

3" X 3", 22 GAUGE SHEET METAL ANGLE

AROUND PERIMETER OF DUCT EACH SIDE

OF WALL. ANCHOR TO WALL WITH

EXPANSION ANCHOR.

DUCT WRAP INSULATION WITH FSK JACKET.

INSULATION IS CONTINUOUS THROUGH WALL

OPENING.

ELEVATION SECTION

NOTE: DETAIL IS SIMILAR FOR

UNINSULATED DUCTS. SEE

SPECIFICATION FOR REQUIRED

INSULATION THICKNESS.

SEAL WITH VAPOR PROOF MASTIC AND CLOTH FABRIC

OVERLAPPING ANGLE AND DUCT WRAP FSK JACKET TO

PREVENT PASSAGE OF SMOKE.

CAULK AROUND FULL PERIMETER OF ANGLE

EACH SIDE OF WALL.

3" X 3", 22 GAUGE SHEET METAL ANGLE AROUND

PERIMETER OF DUCT EACH SIDE OF WALL.

ANCHOR TO WALL WITH EXPANSION ANCHOR.

DUCT WRAP INSULATION WITH FSK

JACKET.INSULATION IS CONTINUOUS

THROUGH WALL OPENING.

SEAL WITH VAPOR PROOF MASTIC AND CLOTH

FABRIC OVERLAPPING ANGLE AND DUCT WRAP

FSK JACKET TO PREVENT PASSAGE OF SMOKE.

PROJECT NUMBER:

DATE:

DRAWN BY:

CHECKED BY:

TITLE:

SUBJECT TO GENERAL

COPYRIGHT LAWS ©

REVISIONS

GA DOE ID #: 2058

M502

MECHANICAL DETAILS

2021201

M O

R N

IN

G

S

ID

E E

L E

M E

N T

A R

Y S

C H

O O

L

H V

A C

P

L U

M B

IN

G

U P

G R

A D

E S

05/20/2022

HHP

JA3

S U

N S

E T

L N

A

L B

A N

Y

G A

NOT TO SCALE

CENTRIFUGAL INLINE FAN DETAIL

NOT TO SCALE

CONDENSATE AUXILIARY DRAIN PAN DETAIL

NOT TO SCALE

EQUIPMENT SUPPORT PLATFORM DETAIL (HP)

NOT TO SCALE

EQUIPMENT SUPPORT RAIL DETAIL

NOT TO SCALE

FIRE DAMPER DETAIL

NOT TO SCALE

PIPE SLEEVE DETAIL

NOT TO SCALE

PIPE SLEEVE DETAIL - REFRIGERANT PIPE THRU EXTERIOR WALL

NOT TO SCALE

RECTANGULAR TO ROUND FLAT ADAPTER

NOT TO SCALE

DUCT PENETRATION THRU WALL DETAIL

INSIDEOUTSIDE

GRADE

EXTERIOR 22 GAUGE HOOD SHALL BE PAINT GRIP SHEET

METAL. ALL JOINTS AND SEAMS SHALL BE STANDARD

SMACNA CONSTRUCTION, AND SEALED NEATLY AND

WATERTIGHT. PAINT EXTERIOR DUCTWORK WITH 2 COATS

OF ENAMEL PAINT. VERIFY COLOR WITH ENGINEER.

HVAC

UNIT CAULK FULL WIDTH.

SEAL WEATHERTIGHT.

TURN CONNECTING DUCT UPWARD WITH 2"

FLANGE ON RTAC CONNECTION. CAULK FULL

PERIMETER OF DUCT.

1 LAYER OF EXTERIOR 2" THICK ARMACELL CLOSED

CELL ELASTOMERIC INSULATION OVER SUPPLY AND

RETURN DUCTWORK. FIBERGLASS INTERNAL DUCT

LINER OR EXTERNAL DUCT WRAP/BOARD IS NOT

ALLOWED ON THE DUCT. FINISH INSULATION WITH 2

COATS OF ARMACELL ARMAFLEX FINISH AND

EMBOSSED ALUMINUM COVER.

SEE PLANS FOR DUCT CONTINUATION.

NOTE: THE DUCT ROUTING SHOWN BETWEEN THE HVAC UNIT AND THE EXTERIOR WALL IS

SYMBOLIC IN THIS DETAIL AND DOES NOT INTEND TO INDICATE ALL ELBOWS, TRANSITIONS,

OFFSETS, ETC. SEE FLOOR PLANS FOR ACTUAL ROUTING.

CONCRETE EQUIPMENT PAD. SEE

CONCRETE EQUIPMENT PAD DETAIL.

22 GAUGE 3 SIDED METAL DUCT HOOD BETWEEN HVAC UNIT AND

EXTERIOR WALL. EXTEND BOTH SIDES OF SHEET METAL…

This is the start of the file's text. The full file is on GovTribe.

Other files

File Type Posted
Addendum 3 —
Addendum 2 —
Bid Invitation —
Addendum 1 —
Award Information —
Addendum 4 —

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .