Addendum 3
2 MB Posted
- Solicitation number
- 22-FAC-016
- Issued by
- Douglas County, Georgia
About this file
Addendum 3 Summary
Addendum 3, dated June 15, 2022, is a contract modification for the Morningside Elementary School HVAC and Plumbing Upgrades project located in Albany, Georgia under the Dougherty County Board of Education. This addendum modifies specifications and drawings originally dated May 20, 2022, and must be acknowledged by all bidders of record to avoid disqualification. The primary changes include revisions to Section 015000 regarding temporary modular classrooms, which must accommodate two standard-size classrooms (600-700 square feet each) and two ADA-accessible restrooms within a minimum 68-foot by 28-foot structure. The modular classrooms require comprehensive furnishing including fire alarm systems connected to the main building panel, intercom speakers (Bogen model MB8TSL(VR) or approved equal), wireless internet connectivity, ADA-accessible restrooms, above-ground septic tanks with weekly pumping service, lighting capable of maintaining 50 foot-candles at desk height, heating and cooling equipment to maintain 70-75 degrees Fahrenheit, and exterior lighting. Contact information for modular classroom distributors includes Wilscot (Tallahassee, FL) and Mobile Modular (Arcade, GA). The addendum also replaces Section 095113 (Acoustical Panel Ceilings) in its entirety with a revised June 15, 2022 version and updates Section 234100 to specify that bi-polar ionization units shall be manufactured by Global Plasma Solutions or an approved equal. Additionally, nine mechanical and electrical drawing sheets are deleted and replaced with revised versions dated 06/15/2022, including mechanical demo plans, new work plans, mechanical details, schedules, and electrical overall plans and schedules.
The revised specifications detail acoustical panel requirements distinguishing between wet and non-wet areas, with non-wet areas requiring Type XII mineral fiber panels from manufacturers such as Armstrong World Industries, CertainTeed Corp., or USG Interiors, and wet areas requiring high-density ceramic and mineral base panels with scrubbable finishes. Metal suspension systems must comply with ASTM standards and include 15/16-inch capped, double-web steel systems with intermediate-duty structural classification. Equipment schedules contained within the addendum document specify 20 wall-hung heat pumps (model T36S1D with 33.3 MBH cooling capacity, with one unit model T60S1D at 55.5 MBH), eight rooftop units with varying capacities, twelve exhaust fans, ten ceiling heaters (CDF 3 model with 10.2 KW output), door air curtains, ductless indoor and outdoor units, and various grille and register specifications. Mechanical schedules include detailed performance parameters such as cooling capacity in MBH, sensible cooling capacity, supply CFM, outdoor air CFM, heating output, and minimum ambient temperature requirements. The contract documents require coordination with the fire marshal prior to ceiling installation and an above-ceiling observation by the architect, with contractors obligated to notify the architect seven days in advance of readiness for inspection in areas receiving ceilings.
Text of this file
Morningside Elementary School May 20, 2022 HVAC & Plumbing Upgrades Dougherty County Board of Education Albany, Georgia
Addendum No. 3- Page 1 of 3
ANDREWS, HAMMOCK & POWELL, INC. 250 CHARTER LANE, SUITE 100, MACON, GA 31210
ADDENDUM NUMBER: THREE DATED: June 15, 2022
To: All contract bidders of record.
This addendum forms a part of the Contract Documents and modifies the original Specifications and Drawings dated May 20, 2022, as noted below. Acknowledge receipt of this Addendum in the space provided on the Bid Price Form; failure to do so may subject bidder to disqualification.
CHANGES TO SPECIFICATIONS
1. SECTION 015000 - TEMPORARY FACILITIES AND CONTROLS
A. On page 015000-3, delete paragraph 2.2.C. in its entirety and replace with the following:
“C. Modular Classrooms: Of sufficient size (68’ x 28’ minimum) to accommodate two
(2) standard size classrooms (600-700 s.f.) and two (2) restrooms with ADA access. Furnish and equip modular classrooms as follows:
1. Fire Alarm Pull Station at door (one in each classroom). Connect pull station to the main building Fire Alarm Panel.
2. Fire Alarm Horn/Strobe (one in each classroom). Connect fire alarm to the main building Fire Alarm Panel.
3. Exit Light/Emergency Light (one in each classroom at egress).
4. Computer Hub/Switch. Connect to nearest IDF in the main building.
5. Wireless internet access, associated with main building. Connect portable classroom hub/switch to nearest IDF in the main building.
6. Wireless Access Point (one in each classroom). Connect to hub/switch.
7. Intercom Speaker (one in each classroom). Bogen model number
MB8TSL(VR) or approved equal.
8. Relay Board/s and Analog Card to Main Intercom Head End to support the additional temporary classroom intercom speakers.
9. Intrusion Alarm on Exterior Doors. Connect to main building alarm panel.
10. ADA Accessible Rest Room (one in each classroom).
11. Cooling and heating equipment necessary to maintain a uniform indoor temperature of 70-75 deg. F.
12. Lighting fixtures capable of maintaining average illumination of 50fc at desk height
13. One Set of Steps and One ADA Ramp.
14. Above ground septic tank, which will include weekly pumping service.
15. Exterior Light (Hubbell Model # LMC-30LU-4K-3-1-BZ or equal (one each portable).
16. Above ground septic tank, which will include weekly pumping service.
Addendum No. 3- Page 2 of 3
17. Modular Classroom Distributers:
a. Wilscot, 4742 Blountstown Hwy., Tallahassee, FL 3204;
(850) 574-9222, Contact Person; Rusty Young (850) 228-6575.
b. Mobile Modular, 530 Etheridge Rd., Arcade GA 30549,
(770) 366-3356, wendy.grenske@mobilemodular.com”
2. SECTION 095113 - ACOUSTICAL PANEL CEILINGS
A. Delete Section 095113 - Acoustical Panel Ceilings dated May 20, 2022, in its entirety and replace with Section 095113 - Acoustical Panel Ceilings, revised June 15, 2022, included herewith.
3. SECTION 234100 - PARTICULATE AIR FILTRATION AND BI-POLAR IONIZATION
UNITS
A. On page 234100-3, paragraph 2.3.A, delete the last sentence of this paragraph in its entirety and replace with the following:
“Bi-polar ionization unit shall be manufactured by Global Plasma Solutions or prior approved equal.”
CHANGES TO DRAWINGS
1. SHEET MD101 - MECHANICAL DEMO PLAN - SECTOR A & C
A. Delete Sheet MD101 in its entirety and replace with Sheet MD101, revised 06/15/2022, included herewith.
2. SHEET MD102 - MECHANICAL DEMO PLAN - SECTOR B
A. Delete Sheet MD102 in its entirety and replace with Sheet MD102, revised 06/15/2022, included herewith.
3. SHEET MD103 - MECHANICAL DEMO PLAN - SECTOR D & E
A. Delete Sheet MD103 in its entirety and replace with Sheet MD103, revised 06/15/2022, included herewith.
4. SHEET M102 - MECHANICAL NEW WORK PLAN - SECTOR B
A. Delete Sheet M102 in its entirety and replace with Sheet M102, revised 06/15/2022, included herewith.
5. SHEET M103 - MECHANICAL NEW WORK PLAN - SECTOR D & E
A. Delete Sheet M103 in its entirety and replace with Sheet M103, revised 06/15/2022, included herewith.
Addendum No. 3- Page 3 of 3
6. SHEET M502 - MECHANICAL DETAILS
A. Delete Sheet M502 in its entirety and replace with Sheet M502, revised 06/15/2022, included herewith.
7. SHEET M601 - MECHANICAL SCHEDULES
A. Delete Sheet M601 in its entirety and replace with Sheet M601, revised 06/15/2022, included herewith.
8. SHEET E001- ELECTRICAL OVERALL PLAN
A. Delete Sheet E001 in its entirety and replace with Sheet E001, revised 06/15/2022, included herewith.
9. SHEET E801- ELECTRICAL SCHEDULES AND LEGEND
A. Delete Sheet E801 in its entirety and replace with Sheet E801, revised 06/15/2022, included herewith.
END OF ADDENDUM #3
Morningside Elementary School Revised June 15, 2022
ACOUSTICAL PANEL CEILINGS 095113 - 1
SECTION 095113 - ACOUSTICAL PANEL CEILINGS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes acoustical panels and exposed suspension systems for ceilings.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.4 CLOSEOUT SUBMITTALS
A. Maintenance Data: For finishes to include in maintenance manuals.
1.5 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Acoustical Ceiling Panels: Furnish 100 full-size panels of APC #1 and 25 full-size panels of APC #2.
2. Suspension-System Components: Furnish 100 lineal feet of each exposed component for suspension system for APC #1.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.
B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.
C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.
1.7 FIELD CONDITIONS
A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.
ACOUSTICAL PANEL CEILINGS 095113 - 2
B. Above-Ceiling Observation: Before Contractor installs acoustical panel ceilings, Architect will conduct an above-ceiling observation and report deficiencies in the Work observed.
Do not proceed with installation of ceilings until deficiencies have been corrected.
1. Notify Architect seven days in advance of date and time when Project, or part of Project, will be ready for above-ceiling observation.
2. Before notifying Architect, complete the following in areas to receive ceilings:
a. Installation of lighting fixtures, powered for operation.
b. Installation, insulation, and leak and pressure testing of water piping systems.
c. Installation of air-duct systems.
d. Installation of air devices.
e. Installation of mechanical system control-air tubing.
f. Installation of ceiling support framing.
C. Coordinate with fire marshal prior to installing ceilings. Most jurisdictions require above-ceiling inspections prior to installing ceilings.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials.
2. Smoke-Developed Index: 450 or less.
2.2 ACOUSTICAL PANELS, GENERAL
A. Source Limitations: Obtain acoustical ceiling panels and supporting suspension system from single source from single manufacturer.
B. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated.
C. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type.
2.3 ACOUSTICAL PANELS <APC #1> (NON WET AREAS)
A. Acoustical tile ceiling in non-wet areas shall be provided by one of the following:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.
ACOUSTICAL PANEL CEILINGS 095113 - 3
B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type XII, mineral fiber with transparent membrane, non-directional fissured design; Form 2, water felted.
2. Pattern: E.
C. Color: White.
D. LR: Not less than 0.90.
E. NRC: Not less than 0.95.
F. Humidity/Sag Resistance: Humiguard Plus.
G. Edge/Joint Detail: Square edge.
H. Thickness: 5/8 inch.
I. Modular Size: 24 by 24 inches.
2.4 ACOUSTICAL PANELS <APC #2> (WET AREAS)
A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:
1. Armstrong World Industries, Inc.; Clean Room VL
2. CertainTeed Corp.; Performa, Vinyrock
3. USG Interiors, Inc.; Subsidiary of USG Corporation.; Gypsum Lay-in Clima Plus
B. Classification: Provide panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type IV or Type XX other types; described as high-density, ceramic- and mineral base panels with scrubbable finish, resistant to heat, moisture, and corrosive fumes. Provide gypsum core and stippled pattern tile.
2. Pattern: As indicated by manufacturer’s designation.
C. Color: White.
D. LR: Not less than 0.78.
E. CAC: Not less than 38.
F. Edge/Joint Detail: Square.
G. Thickness: 1/2 inch.
H. Modular Size: 24 by 24 inches.
ACOUSTICAL PANEL CEILINGS 095113 - 4
2.5 METAL SUSPENSION SYSTEMS, GENERAL
A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M.
1. High-Humidity Finish: Comply with ASTM C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated.
B. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:
1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.
2. Size: Select wire diameter so its stress at three times hanger design load (ASTM C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.106-inch-diameter wire.
2.6 METAL SUSPENSION SYSTEM <For APC #1 Ceilings>
A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries; Suprafine ML or a comparable product by another manufacturer:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.; Subsidiary of USG Corporation
B. 15/16-Inch Capped, Double-Web, Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized according to ASTM A 653/A 653M, not less than G30 coating designation; with prefinished 15/16-inch-wide metal caps on flanges.
1. Structural Classification: Intermediate-duty system.
2. End Condition of Cross Runners: Override (stepped) type.
3. Face Design: Flat, flush.
4. Cap Material: Steel cold-rolled sheet.
5. Cap Finish: Painted white.
2.7 METAL SUSPENSION SYSTEM <For APC #2 Ceilings>
A. Manufacturers/Products: Subject to compliance with requirements, provide one of the following:
1. Armstrong World Industries, Inc.; Prelude Plus XL Fireguard
2. CertainTeed Corp.; Classic Environmental Stab
3. USG Interiors, Inc.; Subsidiary of USG Corporation; Don ZXLA
ACOUSTICAL PANEL CEILINGS 095113 - 5
B. 15/16-Inch Capped, Double-Web, Hot-Dip Galvanized, G60, Steel Suspension System:
Main and cross runners roll formed from cold-rolled steel sheet; hot-dip galvanized according to ASTM A 653/A 653M, G60 coating designation; with prefinished, cold-rolled, 15/16-inch-wide aluminum caps on flanges.
1. Structural Classification: Intermediate-duty system.
2. Face Design: Flat, flush.
3. Face Finish: Painted white.
2.8 METAL EDGE MOLDINGS AND TRIM
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Armstrong World Industries, Inc.
2. CertainTeed Corp.
3. USG Interiors, Inc.; Subsidiary of USG Corporation.
B. Roll-Formed, Sheet-Metal Edge Moldings and Trim: Type and profile indicated or, if not indicated, manufacturer's standard moldings for edges and penetrations that comply with seismic design requirements; formed from sheet metal of same material, finish, and color as that used for exposed flanges of suspension-system runners.
1. Provide manufacturer's standard edge moldings that fit acoustical panel edge details and suspension systems indicated and that match width and configuration of exposed runners unless otherwise indicated.
2. For lay-in panels in corridors, provide stepped edge molding that forms reveal of same depth and width as that formed between edge of panel and flange at exposed suspension member.
3. For circular penetrations of ceiling, provide edge moldings fabricated to diameter required to fit penetration exactly.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical panel ceilings.
B. Examine acoustical panels before installation. Reject acoustical panels that are wet, moisture damaged, or mold damaged.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
ACOUSTICAL PANEL CEILINGS 095113 - 6
3.2 PREPARATION
A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans.
3.3 INSTALLATION
A. General: Install acoustical panel ceilings to comply with ASTM C 636/C 636M and seismic design requirements indicated, according to manufacturer's written instructions and CISCA's "Ceiling Systems Handbook."
B. Suspend ceiling hangers from building's structural members and as follows:
1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.
2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.
3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension-system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.
4. Secure wire hangers to ceiling-suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.
5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both the structure to which hangers are attached and the type of hanger involved. Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.
6. Do not support ceilings directly from permanent metal forms or floor deck. Fasten hangers to cast-in-place hanger inserts, postinstalled mechanical or adhesive anchors, or power-actuated fasteners that extend through forms into concrete.
7. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires.
8. Do not attach hangers to steel deck tabs.
9. Do not attach hangers to steel roof deck. Attach hangers to structural members.
10. Space hangers not more than 48 inches o.c. along each member supported directly from hangers unless otherwise indicated; provide hangers not more than 8 inches from ends of each member.
11. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.
ACOUSTICAL PANEL CEILINGS 095113 - 7
C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs. Fasten bracing wires into concrete with cast-in-place or post installed anchors.
D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels.
1. Screw attach moldings to substrate at intervals not more than 16 inches o.c. and not more than 3 inches from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet. Miter corners accurately and connect securely.
2. Do not use exposed fasteners, including pop rivets, on moldings and trim.
E. Install suspension-system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members.
F. Install acoustical panels with undamaged edges and fit accurately into suspension-system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit.
1. Arrange directionally patterned acoustical panels as follows:
a. Install panels in a basket-weave pattern.
2. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension-system runners and moldings.
3. Paint cut edges of panel remaining exposed after installation; match color of exposed panel surfaces using coating recommended in writing for this purpose by acoustical panel manufacturer.
3.4 CLEANING
A. Clean exposed surfaces of acoustical panel ceilings, including trim, edge moldings, and suspension-system members. Comply with manufacturer's written instructions for cleaning and touchup of minor finish damage. Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.
END OF SECTION 095113
ACOUSTICAL PANEL CEILINGS 095113 - 8
THIS PAGE INTENTIONALLY LEFT BLANK
1 1 1 1 1 1
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
STOR.
CORR.
COMPUTER LAB
COMPUTER LAB
BOYS
GIRLS
1 1 1 1 1
11111
CLASSROOM
COMPUTER LAB
CLASSROOM
COMPUTER LAB
CLASSROOM
BOYS
GIRLS
CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
D
E
GA DOE ID #: 2058
MD101
MECHANICAL DEMO PLAN -
SECTOR A & C
2021201
M O
R N
IN
G
S
ID
E E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
05/20/2022
HHP
JA3
S U
N S
E T
L N
A
L B
A N
Y
G A
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR A
1/8" = 1'-0"2 MECHANICAL DEMO PLAN - SECTOR C
1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.
2 . REMOVE EXISTING CEILING HEATER FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR CEILING HEATER REPLACEMENT.
3 . REMOVE EXISTING PACKAGED ROOF TOP UNIT FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR RTU REPLACEMENT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW UNIT.
4 . REMOVE EXISTING ROOF EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN REPLACEMENT.
NOTES: (THIS SHEET ONLY)
GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY
THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE
WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.
GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL
BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.
NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND
REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM
HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE
OWNER.
No. Description Date
1 ADDENDUM #2 06/06/22
2 ADDENDUM #3 06/15/22
COMPUTER LAB
CLASSROOM
CORRIDOR
CLASSROOM
CLASSROOM
CAFETERIA
STAGE
DISH WASH
FREEZER
COOLER
VEST.
FOOD STORAGE
CORRIDOR
8 8
91010
11 11
5 5(TYP) (TYP)
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
D
E
GA DOE ID #: 2058
MD102
MECHANICAL DEMO PLAN -
SECTOR B
2021201
M O
R N
IN
G
S
ID
E E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
05/20/2022
HHP
JA3
S U
N S
E T
L N
A
L B
A N
Y
G A
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR B
NOTES: (THIS SHEET ONLY)
1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW WALL
HUNG HEAT PUMP SAME LOCATION.
2 . REMOVE EXISTING CEILING HEATER FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR CEILING HEATER REPLACEMENT.
3 . REMOVE EXISTING PACKAGED ROOF TOP UNIT FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR RTU REPLACEMENT. SALVAGE EXISTING GPS
BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW UNIT.
4 . REMOVE EXISTING ROOF EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN REPLACEMENT.
5 . (TYPICAL) EXISTING SUPPLY/RETURN/EXHAUST GRILLE AND ASSOCIATED FLEX DUCT (IF APPLICABLE) IN THIS APPROXIMATE LOCATION TO REMAIN FOR REUSE. SEE
NEW WORK DRAWING FOR AIRFLOW.
6 . REMOVE EXISTING CEILING EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN REPLACEMENT.
7 . REMOVE EXISTING KITCHEN HOOD EXHAUST FAN ON ROOF IN THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN REPLACEMENT.
8 . REMOVE EXISTING AIR HANDLER FROM THIS APPROXIMATE LOCATION. DUCTWORK TO REMAIN FOR REUSE WITH NEW UNIT. REMOVE ALL ASSOCIATED REFRIGEREANT PIPING FROM OUTDOOR UNIT TO INDOOR UNIT. CONDENSATE PIPE TO REMAIN FOR REUSE WITH NEW UNIT. REMOVE EXISTING BIPOLAR UNIT IN
EXISTING UNIT FOR REUSE IN NEW UNIT.
9 . REMOVE EXISTING HEAT PUMP FROM THIS APPROXIMATE LOCATION. CONCRETE EQUIPMENT PAD AND FENCE TO REMAIN FOR REUSE WITH NEW UNIT. REMOVE ALL
ASSOCIATED REFRIGEREANT PIPING FROM OUTDOOR UNIT TO INDOOR UNIT.
10 . EXISTING RETURN DUCT TO REMAIN IN THIS APPROXIMATE LOCATION. OPEN MANUAL VOLUME DAMPER ALL THE WAY TO ALLOW FULL AIRFLOW.
11 . EXISTING LOUVER, DUCTWORK, AND AUTOMATIC VOLUME DAMPER TO REMAIN FOR REUSE. REMOVE ACTUATOR. SEE NEW WORK DRAWINGS FOR INSTALLATION OF
NEW ACTUATOR AND MANUAL VOLUME DAMPER.
12 . EXISTING DISHWASHER EXHAUST FAN TO REMAIN.
13 . EXISTING DUCTWORK IN MECHANICAL ROOM AND ON ROOF TO REMAIN.
14 . EXISTING GRAVITY VENT ON ROOF. CAP AND SEAL VENT AIR TIGHT.
15 . REMOVE ALL EXISITNG DUCTWORK PAST THE SCOPE OF WORK SYMBOL. SEE NEW WORK DRAWINGS FOR NEW DUCTWORK. PROVIDE DUCT END CAP.
16 . REMOVE EXISTING CEILING DIFFUSER IN THIS APPROXIMATE LOCATION.
GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY
THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE
WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.
GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL
BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.
NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND
REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM
HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE
OWNER.
No. Description Date
1 ADDENDUM #2 06/06/22
2 ADDENDUM #3 06/15/22
CLASSROOM
6 6
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
11 (TYP)
11 (TYP)
11 (TYP)
11 (TYP)11 (TYP)11 (TYP)
11 (TYP)
(TYP)12 12 12 12 12 12
121212121212
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
D
E
GA DOE ID #: 2058
MD103
MECHANICAL DEMO PLAN -
SECTOR D & E
2021201
M O
R N
IN
G
S
ID
E E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
05/20/2022
HHP
JA3
S U
N S
E T
L N
A
L B
A N
Y
G A
1/8" = 1'-0"1 MECHANICAL DEMO PLAN - SECTOR D
1 . REMOVE EXISTING WALL HUNG HEAT PUMP AND ASSOCIATED DISCONNECT. SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR
INSTALLATION IN NEW WALL HUNG HEAT PUMP SAME LOCATION.
2 . REMOVE EXISTING CEILING HEATER FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR CEILING HEATER REPLACEMENT.
3 . REMOVE EXISTING PACKAGED ROOF TOP UNIT FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR RTU REPLACEMENT.
SALVAGE EXISTING GPS BIPOLAR IONIZATION UNIT FOR INSTALLATION IN NEW UNIT.
4 . REMOVE EXISTING ROOF EXHAUST FAN FROM THIS APPROXIMATE LOCATION. SEE NEW WORK DRAWING FOR EXHAUST FAN
REPLACEMENT.
5 . REMOVE EXISTING PACKAGED HEAT PUMP UNITS FROM THIS APPROXIMATE LOCATION. DEMO DUCTWORK AND DUCT COVERING UP TO CHASE TO ALLOW FOR NEW DUCTWORK CONNECTION. REMOVE EXISTING BIPOLAR IONIZATION UNIT FOR REUSE IN NEW PACKEGED UNIT.
6 . (TYPICAL) EXISTING DUCTWORK TO REMAIN.
7 . REMOVE EXISTING RETURN GRILLE FROM CEILING IN THIS APPROXIMATE LOCATION.
8 . REMOVE EXISTING ROOF VENTILATOR FROM THIS APPROXIMATE LOCATION. CAP EXISTING CURB.
9 . REMOVE EXISTING AIR HANDLER AND ALL ASSOCIATED PIPING, SUPPORTS, DUCTWORK, ETC. FROM THIS APPROXIMATE LOCATION.
10 . REMOVE ANY AND ALL HVAC RELATED ITEMS FROM MECHANICAL ROOM. THIS INLCUDES BUT IS NOT LIMITED TO, AIR COMPRESSOR, DUCTOWKR, PIPING, BOILER, CONTROLS, ETC.
11 . REMOVE EXISTING DUCTWORK.
12 . REMOVE EXISTING SIDE WALL GRILLE.
13 . REMOVE EXISTING CONDENSING UNIT ON ROOF. DEMO ANY ASSICIATED ELECTRICAL AND PIPING MATERIALS. SEAL ALL ROOF OPENINGS.
NOTES: (THIS SHEET ONLY)
GENERAL NOTE: OWNERSHIP OF ALL REMOVED EQUIPMENT NOT RETAINED BY
THE OWNER SHALL BECOME PROPERTY OF THE CONTRACTOR. COORDINATE
WITH OWNER FOR SALVAGE OF ANY EQUIPMENT TO BE RETAINED BY THE OWNER.
GENERAL NOTE: GPS NEEDLEPOINT BIPOLAR IONIZATION DEVICES (NPBI) SHALL
BE REMOVED FROM THE EXISTING HVAC UNITS BY THE CONTROLS CONTRACTOR.
NPBI DEVICE(S) SHALL BE LABELED, PROPERLY AND SAFELY STORED, AND
REINSTALLED IN THE NEW UNIT IN THE SAME LOCATION. NPBI DEVICE(S) FROM
HVAC UNITS REMOVED AND NOT REPLACED SHALL BE TURNED OVER TO THE
OWNER.
1/8" = 1'-0"2 MECHANICAL DEMO PLAN - SECTOR E
No. Description Date
1 ADDENDUM #2 06/06/22
2 ADDENDUM #3 06/15/22
WHHP-15
RTU-2
RTU-1
EF-4
EF-5
EF-12
EF-3EF-2
EF-6
"x
"x
10"ø
10"ø10"ø
10"ø
A3
A3
30"x10"
A3
A3
"x
"x
30"x10"
B1
A3
A3
A3
A3
2 2
CH-5
CH-2
CH-3
CCCC
CC
CH-6
A2
545 545 545 545
A2
CH-7
CH-8
800 800
HP-1
HP-2
KEF-1
KSF-1
DFCU-1
DOU-1
CLASSROOM
CONFERENCE
31 BOOK STORAGE
WORK ROOM
MEDIA CENTER
GIRLS
BOYS
JAN.
RECEPTIONIST
WORKROOM
PRINC.
235.58 SF
TOIL.
ASST. PRINC.
STAFF LOUNGE
KITCHEN
FREEZER
COOLER
VEST.
FOOD STORAGE
CORRIDOR
MECHANICAL
MEDIA PRODUCTION
TOIL.
AV STORAGE
STORAGE
CNSLR.
STORAGE
TOIL.
ELEC
CORRIDOR
CORRIDOR
CAFETERIA
STAGE
STOR.
STOR.
DISH WASH
CAN WASH
JAN.
LOCKERS
10 OFFICE
CLASSROOM
CORRIDOR
R
DAC-1
TT
TT
TT
TT
TT
TT TT
AHU-2
AHU-1
7 7
7 7
1 1/4" D
R R
A1
RTU-2
CH-4
DFCU-2.1
DFCU-3
DOU-3
S
WAITING
MM
MM
R
8"ø
MVD
3/4" D
MM
A1
A1
6"ø 6"ø
8"ø
MVD
6"ø
F.D.
F.D.F.D.
F.D.
TT
TT
NOTES: (THIS SHEET ONLY)
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
D
E
GA DOE ID #: 2058
M102
MECHANICAL NEW WORK
PLAN - SECTOR B
2021201
M O
R N
IN
G
S
ID
E E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
05/20/2022
HHP
JA3
S U
N S
E T
L N
A
L B
A N
Y
G A
1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR B
1 . WALL HUNG HEAT PUMP. SEE WALL HUNG HEAT PUMP DETAIL - DUCTED SUPPLY.
2 . ROOF MOUNTED CENTRIFUGAL EXHAUST FAN. SEE ROOF MOUNTED CENTRIFUGAL EXHAUST FAN DETAIL.
3 . CEILING HEATER.
4 . ROOFTOP AIR CONDITIONING UNIT MOUNTED ON ROOF CURB ADAPTER. SEE ROOF CURB ADAPTER DETAIL.
5 . DDC TEMERATURE SENSOR TO MONITOR IDF SPACE TEMPERATURE. MOUNT B.E. 4' 6" A.F.F..
6 . FACTORY WALL MOUNTED DUCTLESS UNIT THERMOSTAT. MOUNT B.E. 4' 6" A.F.F..
7 . ATTACH NEW DUCT TO EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION. PROVIDE NECESARY
TRANSITIONS/OFFSET AS NEEDED TO MAKE CONNECTION.
8 . EXISTING GOOSE NECK FOR COMBUSTION AIR.
9 . NEW DOOR AIR CURTAIN MOUNTED IN SAME LOCATION AS DOOR AIR CURTAIN REMOVED DURING DEMOLITION. FIELD VERIFY EXISTING DOOR DIMENSIONS TO ENSURE NEW DOOR AIR CURTAIN MATCHES.
10 . NEW HEAT PUMP MOUNTED ON EXSITING CONCRETE EQUIPMENT PAD. ROUTE NEW REFRIGERANT LINES
FROM NEW HEAT PUMP TO NEW FAN COIL UNIT USING THE EXISTING WALL PENETRATIONS.
11 . NEW VERTICAL FAN COIL UNIT MOUNTED IN PLACE OF EXISTING. CONNECT TO EXISTING SUPPLY DUCT AND CONDENSATE LINE. ROUTE NEW REFRIGERANT LINES ALONG THE EXISTING REFRIGERANT LINE'S PATH.
12 . NEW KITCHEN HOOD SUPPLY FAN MOUNTED ON EXISTING CURB. PROVIDE CURB ADAPTER AS NEED.
13 . NEW KITCHEN HOOD EXHAUST FAN MOUNTED ON EXISTING CURB. PROVIDE CURB ADAPTER AS NEED.
14 . NEW DUCTLESS HEAT PUMP MOUNTED ON NEW EQUIPMENT SUPPORT PLATFORM. SEE ROOF MOUNTED EQUIPMENT SUPPORT PLATFORM DETAIL. REFRIGERANT PIPING ROUTED THROUGH NEW PIPE BOX ON
ROOF. SEE PIPE BOX ASSEMBLY DETAIL.
15 . NEW DUCTLESS CEILING CASSETTE MOUNTED IN CEILING IN THIS APPROXIAMTE LOCATION. FEILD VERIFY EXISTING CONDITIONS AND SHIFT UNIT AS NEEDED. UNIT'S SUPPLY GRILLE FACING HOOD SHALL BE
BLANKED OFF TO NOT INTERFERE WITH HOOD PERFORMANCE.
16 . CAP AND SEAL EXISTING GRAVITY VENT ON ROOF AIR TIGHT.
17 . NEW DDC CONTROL PANEL MOUNTED ON WALL. V
18 . EXISTING DUCT MOUNTED SMOKE DETECTOR.
19 . ALL REFRIGERANT PIPING AND CONDENSATE PIPING SHALL BE CONCEALED BEHIND RECTORSEAL
FORTRESS LINE HIDE KIT OR EQUAL ONCE IT PENETRATES CEILING.
20 . CONDENSATE SHALL BE PUMPED FROM UNIT UNIT THROUGH PIPE BOX AND DISCHARGE ONTO ROOF.
21 . WALL MOUNTED DUCTLESS FAN COIL UNIT. MOUNT B.E. OF UNIT 6' 8" A.F.F.
GENERAL NOTE: PROVIDE LINTELS AT ALL NEW DUCT PENETRATIONS
THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.
No. Description Date
2 ADDENDUM #3 06/15/22
WHHP-11
RTU-6
RTU-5
"x
"x
" 10"ø
10"ø10"ø
10"ø
A3
A3
30"x10"
B1
CC CC
EF-9EF-10
CH-9
CH-10
400400
400 400 300
875 875
875 875
875 875
875 875
OAU-2
"x
ART CENTER
STOR.
STOR.
MUSIC ROOM
CLASSROOM
CORRIDOR
GIRLS
TOIL.
46JAN.
STOR.
GYMNASIUM
COACHES OFFICE
TOIL.
BOYS
RTU-7 RTU-8
A2
TT
TT
TT
16 16
150 -
A1
6"ø
3/4" D
3/4" D
/2
D
18(TYP)
18(TYP)
22 22
TTTT
S
EF-11
CC
D1
D1
D1
D1
D1
D1
"x
8"ø 12"x6"
12"x6"
8"ø 8"ø 8"ø
12"x6"
12"x6"
8"ø
8"ø 12"x6"12"x6"8"ø
12"ø
IU-5
IU-2
IU-3
IU-1
IU-6 IU-7 IU-8
IU-4
MBC-1
HRU-1
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CORRIDOR
CLASSROOM
CLASSROOM
GIRLS
BOYS
JAN.
OAU-3
TT
TT
TT TT
TT TT
R R
R
R
RRR
R
R
R
TT
23 23
232323
1 1/2" D
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
A
B
C
D
E
GA DOE ID #: 2058
M103
MECHANICAL NEW WORK
PLAN - SECTOR D & E
2021201
M O
R N
IN
G
S
ID
E E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
05/20/2022
HHP
JA3
S U
N S
E T
L N
A
L B
A N
Y
G A
1/8" = 1'-0"1 MECHANICAL NEW WORK PLAN - SECTOR D
1/8" = 1'-0"2 MECHANICAL NEW WORK PLAN - SECTOR E
1 . WALL HUNG HEAT PUMP. SEE WALL HUNG HEAT PUMP DETAIL - DUCTED SUPPLY.
2 . ROOF MOUNTED CENTRIFUGAL EXHAUST FAN. SEE ROOF MOUNTED CENTRIFUGAL EXHAUST FAN
DETAIL.
3 . CEILING HEATER.
4 . ROOFTOP AIR CONDITIONING UNIT MOUNTED ON ROOF CURB ADAPTER. SEE ROOF CURB ADAPTER
DETAIL.
5 . VRF CEILING CASSETTE. SUSPENDED FROM DROP RODS (MIN 3/8") CONNECTED TO OVERHEAD
STRUCTURE WITH SUPPLEMENTAL 2"X2"X1/4" ANGLE IRON.
6 . MAIN/SUB VRF BRANCH CONTROLLER. BRANCH CONTROLLER SHALL BE MOUNTED ABOVE CEILING.
SUSPEND FROM DROP RODS (MIN 3/8") AND CONNECTED TO OVERHEAD STRUCTURE WITH 2"X2"X1/4" ANGLE IRON. PROVIDE DRAIN PAN BELOW MBC/SBC.SEE VRF DRAIN PAN DETAIL. PROVIDE AUXILIARY
DRAIN PAN UNDER BRANCH CONTROLLER. SEE CONDENSATE AUXILIARY DRAIN PAN DETAIL.
MOUNT RECTORSEAL AG9150 SENSOR IN PAN AND AUDIBLE ALARM. ALARM SHALL BE MOUNTED AT
CEILING LEVEL. PROVIDE 24V TRANSFORMER TO POWER SENSOR.
7 . VRF HEAT RECOVERY UNIT MOUNTED ON CONCRETE EQUIPMENT PAD.
8 . 100% OUTSIDE AIR DUCT PENETRATES BUILDING IN THIS APPROXIMATE LOCATION. SEE
RECTANGULAR DUCT THRU EXTERIOR WALL DETAIL.
9 . 100% OUTSIDE AIR UNIT MOUNTED ATOP CONCRETE EQUIPMENT PAD. SEE CONCRETE EQUIPMENT
PAD DETAIL.
10 . ATTACH NEW DUCT TO EXISTING DUCTWORK AT THIS APPROXIMATE LOCATION.
11 . GENERAL: PIPE SLEEVES. SEE PIPE SLEEVE DETAIL.
12 . REFRIGERANT BRANCH LIQUID AND GAS REFRIGERANT PIPING TO INDOOR UNIT FROM BRANCH
CONTROLLER. SEE VRF SCHEMATIC FOR REFRIGERANT PIPE SIZES.
13 . REFRIGERANT HIGH PRESSURE AND LOW PRESSURE REFRIGERANT PIPING FROM OUTDOOR UNIT
TO MAIN BRANCH CONTROLLER. SEE VRF SCHEMATIC FOR REFRIGERANT PIPE SIZES. MOUNT
EXTERIOR REFRIGERANT PIPE ON ROOF ATOP B-LINE DURABLOCK (DB) SUPPORTS. SUPPORT
PIPING ON 6 FT. CENTERS.
14 . MAIN 1.5" CONDENSATE DRAIN PIPING SHALL BE LOCATED AS HIGH AS POSSIBLE. CONDENSATE
SHALL HAVE PROPER SLOPE (MIN 1/4" PER FOOT).
15 . PROVIDE 1.5" ELBOW UP AND MINIMUM 8" TALL VERTICAL OPEN STAND PIPE AT THIS APPROXIMATE
LOCATION.
16 . GROUND MOUNTED HORIZONTAL DISCHARGE PACKAGED HEAT PUMP MOUNTED ON EXISTING
CONCRETE EQUIPMENT PAD. VERIFY EXISTING PAD WILL SUFFICE. EXTEND AS NEEDED. SEE
CONCRETE EQUIPMENT PAD DETAIL.
17 . VRF CENTRALIZED CONTROLLER MOUNTED ON WALL WITH B.E. 4' 6" A.F.F.
18 . CONDENSATE PIPE SUPPORT ON ROOF. SEE CONDENSATE PIPE SUPPORT ON ROOF DETAILS.
19 . PROVIDE FULL SIZE, SLOPED (1/4" PER FOOT), TRAPPED, SCHEDULE 40 PVC PIPING TO DISCHARGE
AS SHOWN ON DRAWINGS . DRAIN PIPING SHALL BE PROVIDED FROM EACH RTAC AS SHOWN ON
DRAWINGS. INSURE THAT DRAIN PIPING DOES NOT BLOCK RTAC ACCESS PANELS. DO NOT ROUTE
DRAIN PIPING IN FRONT OF ACCESS PANELS. SEE CONDENSATE DRAIN TRAP DETAIL AND
CONDENSATE ROOF SUPPORT DETAIL(S).
20 . EXTEND CONCRETE EQUIPMENT PAD AND FENCING (ACCORDING TO SPEC) AS NEEDED TO FIT NEW UNIT. EXISITING FENCE MAY NEED EXTENSION AS WELL. FIELD VERIFY EXACT EXTENSIONS NEEDED.
SEE CONCRETE EQUIPMENT PAD DETAIL.
21 . WALL MOUNTED DDC SPACE TEMPERATURE/HUMIDITY SENSOR. MOUNT B.E. OF SENSOR 4' 6" A.F.F..
22 . WALL MOUNTED DDC SPACE TEMPERATURE/HUMIDITY SENSOR. MOUNT B.E. OF SENSOR 4' 6" A.F.F..
23 . FACTORY WALL MOUNTED VRF WIRED UNIT THERMOSTAT/CONTROLLER. MOUNT B.E. 4' 6" A.F.F..
24 . INSTALL 6' TALL CHAINLINK FENCE AROUND EQUIPMENT YARD IN ACCORDANCE TO SPECIFICATIONS.
INSTALL 3'GATE IN FENCE FOR SERVICE ACCESS.
25 . 100% OUTSIDE AIR UNIT MOUNTED ON ROOF. UNIT WILL DISCHARGE HORIZONTALLY. UNIT SHALL
SHALL BE PLACED ON TWO JOISTS IN THIS APPROXIMATE LOCATION AND JOIST SHALL BE
REINFORCED. SEE JOIST REINFORCEMENT DETAIL. ALL EXTERIOR DUCTWORK SHALL BE HAVE AN
EXTERIOR SHEILD. SEE PAD MOUNTED EXTERIOR METAL DUCT HOOD DETAIL FOR DUCT
HOOD/SHEILD DETAILS.
NOTES: (THIS SHEET ONLY)
GENERAL: DRAWINGS SHOW GENERAL ARRANGEMENT, LAYOUT AND LOCATION OF PIPING, APPURTENANCES, ETC., BUT DO NOT SHOW ALL REQUIRED FITTINGS AND OFFSETS THAT MAY BE NECESSARY TO RUN PIPING AND CONNECT TO EQUIPMENT, ETC. OFFSET PIPING AROUND ALL OBSTRUCTIONS. FABRICATE AND INSTALL PIPING, FITTINGS, ETC. BASED ON FIELD MEASUREMENTS. PROVIDE ALL NECESSARY FITTINGS AND OFFSETS AT NO ADDITIONAL COST TO THE OWNER. PIPE ROUTING SHOWN ON DRAWINGS SHALL BE ALTERED BY CONTRACTOR WHERE REQUIRED TO AVOID INTERFERENCE AND CLEARANCE DIFFICULTIES. CAREFULLY COORDINATE PIPE ROUTING WITH ROOF MOUNTED GAS PIPING, CONDUITS AND EQUIPMENT TO AVOID
CONFLICTS .
GENERAL NOTE: PROVIDE LINTELS AT ALL NEW DUCT PENETRATIONS
THRU EXISTING WALLS. SEE LINTEL DETAIL AT EXISTING WALL.
No. Description Date
2 ADDENDUM #3 06/15/22
PROVIDE INSULATED HOUSING WHERE SCHEDULED
DUCT
AIRFLOW
PARALLEL BLADE BACKDRAFT DAMPER
SQUARE ACCESS PANEL FOR DAMPER ACTUATOR ACCESS
ACCESS PANEL (BOTH SIDES)
MOUNTING BRACKETS (TYP)
HANGING VIBRATION ISOLATORS. SEE SPECS FOR TYPE.
THREADED ROD
SUPPLEMENTAL ANGLE IRON FRAMING
DOUBLE NUTS
DOUBLE NUTS
DUCT
MOTOR. SEE SPECS FOR TYPE.
NOTE: BELT DRIVE FAN SIMILAR, EXCEPT MOTOR
OUTISDE OF FAN CASING, AND WITH INSULATED
MOTOR COVER WHERE SPECIFIED.
DUCT MOUNTING COLLAR (TYP INLET AND OUTLET). PROVIDE
1/2" X 1/2" WELDED WIRE GALVANIZED INLET GUARD FOR
NON-DUCTED INLET APPLICATIONS AS SCHEDULED.
MAINTAIN MINIMUM 2.5 TIMES WHERE DIAMETER STRAIGHT
DUCT LENGTH AT INLET AND OUTLET OF FAN BEFORE
ELBOW, TRANSITION, DAMPER, ETC.
PROVIDE MOTORIZED DAMPER WITH INTERNAL ACTUATOR WHERE
SCHEDULED. DAMPER VOLTAGE SHALL MATCH FAN VOLTAGE.
FLEXIBLE DUCT
CONNECTION (TYP)
GALVANIZED MOTOR COVER
WHERE SCHEDULED
BACKWARD
INCLINED WHEEL
MAINTAIN MINIMUM 2.5 TIMES
WHEEL DIAMETER STRAIGHT
DUCT LENGTH AT INLET AND
OUTLET OF FAN BEFORE ELBOW,
TRANSITION, DAMPER, ETC.
FACTORY INSTALLED NEMA-1
DISCONNECT SWITCH
FACTORY WIRED FROM MOTOR
TO DISCONNECT SWITCH
WELD SIDE ANGLE CLIP TO PAN (TYP OF 4)
TO CORNERS. SUSPEND WITH 3/8"
THREADED ROD. DO NOT BLOCK ACCESS
TO CONTROLLER.
PAN SHALL BE MIN. 18 GAUGE
GALVANIZED STEEL
2"
3/4" NIPPLE WELDED
TO PAN
PIPE 3/4" PAN DRAIN TO LOCATION
SHOWN ON DRAWINGS. SLOPE
PAN TO THIS SIDE.
FABRICATE DRAIN PAN MINIMUM
12" LONGER AND WIDER THAN
MAIN/SUB CONTROLLER
FABRICATE DRAIN PAN MINIMUM
12" LONGER AND WIDER THAN
MAIN/SUB CONTROLLER
18 GAUGE GALVANIZED SHEET METAL COVER FACTORY
FABRICATED BY EQUIPMENT SUPPORT MANUFACTURER
SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.AS REQUIRED
RAISED CHANNEL SUPPORT FOR
MOUNTING OF HEAT PUMPS (TYP).
CHANNELS TO BE FACTORY
FABRICATED INTO COVER.
COORDINATE SPACING OF SUPPORT CHANNELS
WITH DIMENSIONS OF HEAT PUMPS BEING
INSTALLED ATOP PLATFORM. SEE PLANS
FOR UNIT LAYOUT.
ROOF CURB. SEE ROOF CURB DETAIL.COORDINATE LENGTH OF PLATFORM
REQUIRED WITH UNIT LAYOUT INDICATED
ON PLANS
ISOMETRIC VIEW
HEAT PUMP UNIT. SEE PLANS FOR SIZING AND LAYOUT.
SECURE HEAT PUMP
TO SUPPORT CHANNEL.
LAG SCREWS TO CURB ON
MAXIMUM 16" CENTERS.
ROOF CURB. SEE
ROOF CURB DETAIL.
PROVIDE FACTORY FURNISHED
INTERNAL SUPPORT CHANNELS
AS REQUIRED TO SUPPORT
WEIGHT OF HEAT PUMP UNITS.
ROOF DECK SHALL BE
CONTINUOUS UNDER CURB.
6" (MIN.)
FRONT VIEW
PRESSURE TREATED WOOD NAILER
SHEET METAL SCREW IN SIDE OF
COUNTER FLASHING (TYP)
18 GAUGE GALVANIZED STEEL
COUNTER FLASHING
SHEET METAL SCREW (TYP)
18 GAUGE STEEL BASE SECTION
FIELD INSTALLED INSULATION
INTEGRAL 18 GAUGE
GALVANIZED
STEEL BASE PLATE
FIELD INSTALLED CANT
ROOF DECK CONTINUOUS
BENEATH SUPPORT RAIL
SEE ARCHITECTURAL DRAWINGS FOR SPECIFIC
DETAILS CONCERNING ROOF CONSTRUCTION,
FLASHING, ANCHORS, BLOCKING,
ROOF DECK TYPE, ETC.
C U
R B
H E
IG
H
T
S T
Y
LE
A
S T
Y
LE
B
S T
Y
LE
C
2" MAX.
1" 1"
FOLDING BLADE STATIC RATED FIRE DAMPER
IN TYPE 'B' FRAME (EXCEPT TYPE 'A' SHALL BE
USED AT SIDEWALL REGISTERS AND NON-DUCTED
TRANSFER OPENING). DYNAMIC RATED DAMPERS
SHALL BE USED WHERE SPECIFICALLY SHOWN
ON DRAWINGS
ATTACH FIRE DAMPER TO SLEEVE IN
ACCORDANCE WITH MANUFACTUER'S
UL INSTALLATION INSTRUCTIONS
FACTORY FURNISHED ROUND OR OVAL
TRANSITION WITH BLADE STACK OUT
OF AIR STREAM
ROUND AND OVAL FIRE DAMPER
INSTALLATION SIMILAR
DUCT (WHERE APPLICABLE)
SLEEVE LENGTH SHALL BE DETERMINED BY CONTRACTOR TO
BE WITHIN MINIMUM AND MAXIMUM DISTANCE FROM
WALL/FLOOR AS REQUIRED BY MANUFACTUER
NOTE: INSTALLATION SHALL CONFORM TO THE FIRE
DAMPERS MANUFACTURER'S "UL" INSTALLATION
INSTRUCTIONS
WALL OR FLOOR. CONTRACTOR SHALL VERIFY
THICKNESS RATING, AND MATERIAL OF
CONSTRUCTION FROM ARCHITECTURAL DRAWINGS,
AND USE THIS INFORMATION TO SELECT FIRE
DAMPER AND FIRE DAMPER ACCESSORIES.
PROVIDE MINIMUM OVERLAP ALL AROUND AS REQUIRED BY
MANUFACTURER'S UL INSTALLATION INSTRUCTIONS
CLEARANCE (TYPICAL) AS REQUIRED BY MANUFACTURER'S
UL INSTALLATION INSTRUCTIONS
165° FUSIBLE LINK
DUCT TO SLEEVE CONNECTION SHALL BE AN APPROVED
TYPE AS LISTED IN THE MANUFACTURER'S UL INSTALLATION
INSTRUCTIONS. PROVIDE DUCT SEALANT APPROVED BY
FIRE DAMPER MANUFACTURER.
PROVIDE ACCESS PANEL FOR RECTANGULAR DUCTS. FOR ROUND DUCTS,
DOOR SIZE SHALL BE AS NOTED IN SPECIFICATIONS. FOR FLOOR
PENETRATIONS ACCESS PANEL SHALL BE ABOVE FLOOR.
FACTORY PROVIDED SLEEVE. SLEEVE LENGTH AND GAUGE SHALL
BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH
MANUFACTURER'S UL INSTALLATION INSTRUCTIONS.
FACTORY PROVIDED RETAINING ANGLES. ANGLE SIZE AND GAUGE
SHALL BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH
MANUFACTURER'S UL INSTALLATION INSTRUCTIONS.
GROUT
1" ABOVE FLOOR; FLUSH FOR WALLS
SCHEDULE 10 (MINIMUM)
STEEL PIPE
CONDUIT OR PIPING
PIPING INSULATION AS SPECIFIED.
PIPE INSULATION SHALL BE CONTINUOUS
THRU PENETRATION.
SEAL BETWEEN SLEEVE AND PIPING WITH FIRE RESISTANT
SEALANT OF SUFFICIENT THICKNESS TO MAINTAIN WALL'S
OR FLOOR FIRE RATING (1" MINIMUM THICKNESS). IF WALL
IS NOT FIRE RATED, PROVIDE CAULKING IN LIEU OF FIRE
RESISTANT SEALANT. SEALANT IS ONLY REQUIRED ON
ONE SIDE OF WALL, UNLESS REQUIRED BY MANUFACTURER
ON BOTH SIDES.
FIBERGLASS BATTS PACKED BETWEEN SLEEVE
AND PIPE (OR PIPE INSULATION ON INSULATED PIPE)
WALL OR FLOOR. CONTRACTOR SHALL VERIFY
CONSTRUCTION TYPE (MASONRY, CONCRETE,
BRICK AND CMU, ETC.) AND THICKNESS.
INSIDE
UNINSULATED REFRIGERANT LIQUID PIPE
REFRIGERANT PIPE DROPS
IN WALL AS REQUIRED
INSULATED REFRIGERANT
SUCTION PIPE
20 GAUGE GALVANIZED
STEEL SHEET METAL SLEEVE
TERMINATE SLEEVE
FLUSH WITH WALL
OUTSIDE
PIPE PENETRATES WALL
NEAR GRADE LEVEL
EXTERIOR PAINTABLE SILICON CAULK.
PAINT TO MATCH EXTERIOR. EXTERIOR WALL. SEE ARCHITECTURAL PLANS
FOR CONSTRUCTION
FIRE RESISTANT FOAM OF APPROPRIATE
THICKNESS TO MAINTAIN WALL'S FIRE RATING
(1" MINIMUM THICKNESS)
DIA. -",
(SEE PLANS)
3"
DIM. + ?"
DIM. + ?"
3"
PAINT INTERIOR OF BOX MATTE BLACK.1
2 MINIMUM 26 GAUGE GALV. SHEET METAL.
4 ADAPTER MAY BE FABRICATED BY CONTRACTOR OR PROVIDED BY CROWN
PRODUCTS MODEL #666 ADAPTER OR EQUAL.
PROVIDE 1/2" DUCT LINER ON RETURN DUCT
APPLICATIONS AND NO LINER ON EXHAUST APPLICATION.
NOTES: (THIS DETAIL ONLY)
CAULK AROUND FULL PERIMETER OF ANGLE
EACH SIDE OF WALL.
3" X 3", 22 GAUGE SHEET METAL ANGLE
AROUND PERIMETER OF DUCT EACH SIDE
OF WALL. ANCHOR TO WALL WITH
EXPANSION ANCHOR.
DUCT WRAP INSULATION WITH FSK JACKET.
INSULATION IS CONTINUOUS THROUGH WALL
OPENING.
ELEVATION SECTION
NOTE: DETAIL IS SIMILAR FOR
UNINSULATED DUCTS. SEE
SPECIFICATION FOR REQUIRED
INSULATION THICKNESS.
SEAL WITH VAPOR PROOF MASTIC AND CLOTH FABRIC
OVERLAPPING ANGLE AND DUCT WRAP FSK JACKET TO
PREVENT PASSAGE OF SMOKE.
CAULK AROUND FULL PERIMETER OF ANGLE
EACH SIDE OF WALL.
3" X 3", 22 GAUGE SHEET METAL ANGLE AROUND
PERIMETER OF DUCT EACH SIDE OF WALL.
ANCHOR TO WALL WITH EXPANSION ANCHOR.
DUCT WRAP INSULATION WITH FSK
JACKET.INSULATION IS CONTINUOUS
THROUGH WALL OPENING.
SEAL WITH VAPOR PROOF MASTIC AND CLOTH
FABRIC OVERLAPPING ANGLE AND DUCT WRAP
FSK JACKET TO PREVENT PASSAGE OF SMOKE.
REINF. OF JOISTS FOR LOADS 100 LBS
OR MORE BETWEEN PANEL POINTS
LOAD
LOAD
1" M
IN
2 X 2 X 3__
ANGLE EACH
SIDE OF JOIST
TOP CHORD
BOTTOM CHORD
JOIST
PANEL POINT
EACH
END3__
PANEL POINT
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 2058
M502
MECHANICAL DETAILS
2021201
M O
R N
IN
G
S
ID
E E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
05/20/2022
HHP
JA3
S U
N S
E T
L N
A
L B
A N
Y
G A
NOT TO SCALE
CENTRIFUGAL INLINE FAN DETAIL
NOT TO SCALE
CONDENSATE AUXILIARY DRAIN PAN DETAIL
NOT TO SCALE
EQUIPMENT SUPPORT PLATFORM DETAIL (HP)
NOT TO SCALE
EQUIPMENT SUPPORT RAIL DETAIL
NOT TO SCALE
FIRE DAMPER DETAIL
NOT TO SCALE
PIPE SLEEVE DETAIL
NOT TO SCALE
PIPE SLEEVE DETAIL - REFRIGERANT PIPE THRU EXTERIOR WALL
NOT TO SCALE
RECTANGULAR TO ROUND FLAT ADAPTER
NOT TO SCALE
DUCT PENETRATION THRU WALL DETAIL
No. Description Date
2 ADDENDUM #3 06/15/22
NOT TO SCALE
JOIST REINFORCEMENT DETAIL
PROJECT NUMBER:
DATE:
DRAWN BY:
CHECKED BY:
TITLE:
SUBJECT TO GENERAL
COPYRIGHT LAWS ©
REVISIONS
GA DOE ID #: 2058
M601
MECHANICAL SCHEDULES
2021201
M O
R N
IN
G
S
ID
E E
L E
M E
N T
A R
Y S
C H
O O
L
H V
A C
P
L U
M B
IN
G
U P
G R
A D
E S
05/20/2022
HHP
JA3
S U
N S
E T
L N
A
L B
A N
Y
G A
WALL HUNG HEAT PUMPS
TAG MODEL NO.
TOTAL
COOLING MBH
TOTAL
SENSIBLE MBH
TOTAL
SUPPLY CFM
O.A. CFM
INTEGRAL HEATING
CAPACITY (MBH)
RESIST HEAT
(KW)
NOTES
WHHP-1 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-2 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-3 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-4 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-5 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-6 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-7 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-8 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-9 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-10 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-11 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-12 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-13 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-14 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-15 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-16 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-17 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-18 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
WHHP-19 T60S1D 55.5 40.0 1650 - 34.6 9 1 THRU 15
WHHP-20 T36S1D 33.3 26.0 1100 - 22.7 6 1 THRU 15
ROOFTOP UNITS
TAG
MODEL
NUMBER
TOTAL
COOLING MBH
SENSIBLE
COOLING MBH
TOTAL
SUPPLY CFM
O.A. CFM
HEATING
INPUT MBH
(LOW/HIGH)
HEATING
OUTPUT MBH
(LOW/HIGH)
APPROX.
E.S.P.
(IN.W.G.)
SUPPLY FAN
HP
MINUMUM STAGES
COOLING ENTERING
CONDITIONS
MINIMUM
AMBIENT
COOLING TEMP
NOTES
COOLING HEATING E.A.T. D.B. °F E.A.T. W.B. °F
RTU-1 48HC14 153.2 120.6 5,815 400 192/240 156/195 0.85 3.49 BHP 2 2 78.1 65.4 40 1:3:5:6:7:8:9:10:11:12:13:14:15:16
RTU-2 48HC04 32.5 25.1 1,300 150 50/67 40/54 0.85 0.49 BHP 2 2 76.6 63.3 40 1:3:5:6:7:8:9:10:11:12:13:14:15:16
RTU-3 48GC05 45.8 36.1 1,600 150 50/67 40/54 0.5 1.0 BHP 2 2 76.6 63.3 40 1:3:5:6:7:8:9:10:11:12:13:14:15:16
RTU-4 48GC05 45.8 36.1 1,600 150 50/67 40/54 0.5 1.0 BHP 2 2 76.6 63.3 40 1:3:5:6:7:8:9:10:11:12:13:14:15:16
RTU-5 48GC05 45.8 36.1 1,600 150 50/67 40/54 0.5 1.0 BHP 2 2 76.6 63.3 40 1:3:5:6:7:8:9:10:11:12:13:14:15:16
RTU-6 48GC06 59.6 43.4 2,000 150 82/110 65/88 0.85 1.2 BHP 2 2 76.6 63.3 40 1:3:5:6:7:8:9:10:11:12:13:14:15:16
RTU-7 50HCQ12 115.6 92.3 4,000 250 30.8 KW 64.8 MBH 0.75 1.35 BHP 2 2 77.4 63.9 40 1:2:3:4:5:6:7:8:9:10:11:12:13:14
RTU-8 50HCQ12 115.6 92.3 4,000 250 30.8 KW 64.8 MBH 0.75 1.35 BHP 2 2 77.4 63.9 40 1:2:3:4:5:6:7:8:9:10:11:12:13:14
EXHAUST FANS
TAG
MODEL
NUMBER
CFM APPROX. E.S.P. (IN.W.G.) FAN RPM MOTOR HP SONES NOTES
EF-1 G-070-VG 150 0.3 1,365 1/15 3.2 1:3:4:5:6
EF-2 G-090-VG 300 0.3 1,136 1/10 4.7 1:3:4:5:6
EF-3 G-090-VG 375 0.3 1,216 1/10 5.0 1:3:4:5:6
EF-4 SP-B110 75 0.3 768 80W 1.0 2:3:4:5
EF-5 SP-B110 75 0.3 768 80W 1.0 2:3:4:5
EF-6 SP-B110 75 0.3 768 80W 1.0 2:3:4:5
EF-7 G-090-VG 300 0.3 1,136 1/10 4.7 1:3:4:5:6
EF-8 G-090-VG 375 0.5 1,614 1/6 10.8 1:3:4:5:6
EF-9 G-090-VG 375 0.5 1,641 1/6 10.8 1:3:4:5:6
EF-10 G-090-VG 225 0.5 1,599 1/6 12.4 1:3:4:5:6
EF-11 G-090-VG 575 0.3 1,506 1/10 7.0 1:3:4:5:6
EF-12 G-095-VG 225 0.75 0.75 1/6 12.4 1:3:4:5:6
KEF-1 CUE-240-VG 8,200 0.8 1,055 5 28 3:4:5:8
KSF-1 SAF-118 6,600 0.85 763 5 - 4:7
CEILING HEATERS
TAG MODEL NUMBER KW BTU/HR OUTPUT CFM NOTES
CH-1 CDF 3 10.2 300 1:2:3:4:5
CH-2 CDF 3 10.2 300 1:2:3:4:5
CH-3 CDF 3 10.2 300 1:2:3:4:5
CH-4 CDF 3 10.2 300 1:2:3:4:5
CH-5 CDF 3 10.2 300 1:2:3:4:5
CH-6 CDF 3 10.2 300 1:2:3:4:5
CH-7 CDF 3 10.2 300 1:2:3:4:5
CH-8 CDF 3 10.2 300 1:2:3:4:5
CH-9 CDF 3 10.2 300 1:2:3:4:5
CH-10 CDF 3 10.2 300 1:2:3:4:5
1 COMMERCIAL DOWN FLOW FAN FORCED CEILING MOUNTED ELECTRIC HEATER WITH WHITE
LOUVERED FACE PLATE.
2 PROVIDE FAN DELAY SWITCH AN DHIGH TEMPERATURE CUT-OUT.
3 PROVIDE RECESS ENCLOSURE TO ALLOW FOR RECESS MOUNTING IN CEILING. SEE
ARCHITECTURAL DRAWINGS FOR CEILING TYPE (ACOUSTICAL T-BAR OR RIGID GYP. BOARD).
4 PROVIDE POWER DISCONNECT SWITCH (OPTION CFD-DS).
5 PROVIDE REMOTE MOUNTED 24V SNAP ACTION HEAT ONLY THERMOSTAT. PROVIDE
INTEGRAL CONTROL POWER TRANSFORMER AND 24V RELAY.
6 PROVIDE INTEGRAL LINE VOLTAGE THERMOSTAT.
GENERAL NOTE: NOMINAL TONNAGEIS MINIMUM SIZE UNIT ALLOWED. DESIGN AIRFLOWS ARE MINIMUM ALOOWED. LOWER AIRFLOWS WILL NOT BE ALLOWED.
* PEAK SUPPLY INDICATES UNIT MAX AIRFLOWS ON HIGH SPEED SETTING
1. DUCTLESS CEILING CASSATE FAN COIL UNIT. SEE SCHEDULE FOR FULL OR COMPACT SIZE. SEE SPECIFICATION FOR ADDITIONAL INFORMATION. MOUNT PER MANUFACTURER'S INSTRUCTIONS.UNIT SHALL BE
DESIGNED FOR T-BAR GRID INSTALLATION
2. NOMINAL COOLING CAPACITIES BASED ON AIR ENTERING EVAPORATOR AT 80ºFdb, 67ºFwb AND MATCHED WITH INDICATED HEAT RECOVERY SYSTEM.
3. NOMINAL HEATING CAPACITY BASED ON AIR ENTERING EVAPORATOR AT 70ºFdb, AND OUTDOOR AIR OF 43ºFdb AND MATCHED WITH INDICATED HEAT RECOVERY UNIT(S).
4. PROVIDE FACTORY BUILT-IN CONDENSATE PUMP.
5. PROVIDE FACTORY AUXILIARY CONDENSATE OVERFLOW SENSOR KIT.
6. PROVIDE WIRED REMOTE CONTROLLER, WIRELESS TYPE WILL NOT BE ALLOWED.
7. PROVIDE BI-POLAR UNIT. NOT SHOWN ON PLANS. SEE VRF BI POLAR UNIT SCHEDULE AND DETAILS FOR MORE INFORMATION.
1. COOLING CAPACTITY BASED COOLING OUTDOOR DB TEMPERATURE OF 95°F AMBIENT AIR TEMPERATURE AND 80/67°F EAT INDOOR UNITS AND MATCHED WITH INDICATED INDOOR FAN COIL UNITS.
2. HEATING CAPACITY BASED ON REVERSE CYCLE (HEAT PUMP) OPERATION WITH DEFROST ALLOWANCE 43°F wb AMBIENT AIR TEMPERATURE AND 70°F EAT FOR INDOORS UNITS.
3. PROVIDE REFRIGERANT PIPING SIZED AND DESIGNED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. INSULATE REFRIGERANT LINES PER MANUFACTURERS INSTRUCTIONS.
4. SCHEDULED CAPACITIES ARE OVERALL CAPACITIES REQUIRED FOR MATCHED INDOOR UNITS, TEMPERATURE, PIPE LENGTH EFFECT, ETC. INDOOR UNIT CAPACITY SHALL NOT EXCEED 101% OF OUTDOOR UNIT
CAPACITY.
5. PROVIDE INTEGRAL CONTROLS INCLUDING CONTACTORS, CONTROL TRANSFORMER, DEFROST CONTROL BOARD, MAIN AND SUB BC CONTROLLER, ETC.
6. UNIT SHALL UTILIZE R-410a REFRIGERANT. PROVIDE 410a REFRIGERANT TO CHARGE ENTIRE SYSTEM.
7. MANUFACTURER SHALL PROVIDE SCHEMATIC LAYOUT OF DISTRIBUTION BOXES/BRANCH CONTROLLERS AT TIME OF SUBMITTAL FOR COORDINATION PURPOSES.
8. PROVIDE HAIL GUARD SCREEN OVER CONDENSER COILS. DO NOT PROVIDE FACTORY HAIL GUARD KIT THAT INCREASES WIND LOAD ON OUTDOOR UNIT AND REQUIRES TIE DOWN POINTS. SEE CONDENSER COIL
GUARD DETAIL.
9. PROVIDE TWINNING KIT FOR JOINING MODULES.
10. PROVIDE AND MOUNT ATOP ROOF EQUIPMENT PLATFORM. SEE ROOF EQUIPMENT PLATFORM DETAIL. ALSO PROVIDE PIPE BOX ASSEMBLY. SEE PIPE BOX ASSEMBLY DETAIL.
11. BMS INTERFACE CARD. TRANSLATOR SHALL INTEGRATE VRF DATA INTO BMS SEAMLESSLY. VRF MANUFACTURER SHALL PROVIDE FACTORY ON-SITE ASSISTANCE TO INTEGRATE INTO BUILDING MANAGEMENT
SYSTEM.
1. PROVIDE ISOLATION BALL VALVES (DIAMONDBACK BALL VALVE BV-SERIES) AT EACH PORT RATED FOR R-410A, FULL PORT, 700PSIG.
2. CONNECTED CAPACITY TO SUB CONTROLLER SHALL NOT EXCEED 126,000 BTU/HR FOR DOUBLE SUB CONTROLLERS ,168,000 BTU/HR .
3. PROVIDE GALVANIZED DRAIN PAN TO EXTEND 12" BEYOND FOOTPRINT OF CONTROLLER. SEE DRAIN PAN DETAIL.
4. PROVIDE FACTORY PROVIDED CONDENSATE PUMP.
VRF BRANCH CONTROLLERS
TAG MODEL NUMBER TYPE (MAIN/SUB) NO.
This is the start of the file's text. The full file is on GovTribe.
Other files
| File | Type | Posted |
|---|---|---|
| DRAWINGS | — | |
| Addendum 2 | — | |
| Bid Invitation | — | |
| Addendum 1 | — | |
| Award Information | — | |
| Addendum 4 | — |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .