DRAFT_Drawing 07 MABH-FireProtection.pdf
PDF 19 MB Posted
- Attached to
- Sources Sought - Hospital Modernization Misawa Air Base, Japan Federal contract opportunity
- Solicitation number
- FA5205-21-PKP-002
About this file
This document is a sources sought notice for a hospital modernization project at Misawa Air Base in Japan. The Department of the Air Force Pacific Air Forces is seeking industry input to develop an acquisition strategy for replacing and upgrading facilities at the base hospital. No contract will be awarded from this notice, as it is for market research purposes only. Interested parties are encouraged but not required to provide input to help determine technical requirements and availability of potential sources. All costs of responding should be paid by the interested party. Responses will be used within the Air Force for decision making and will not be disclosed outside the agency. The draft specification and drawings provided are for informational purposes only.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sources Sought - Misawa Hospital Modernization_3Feb2021.docx | DOCX document | |
| DRAFT_Drawing 05 MABH-Interiors.pdf | ||
| DRAFT_Drawing 09 MABH-Mechanical.pdf | ||
| Sources Sought - Misawa Hospital Modernization.docx | DOCX document | |
| DRAFT_Drawing 04 MABH-Architecture.pdf | ||
| DRAFT_Drawing 02 MABH-Civil.pdf | ||
| DRAFT_Specifications_Volume 2.pdf | ||
| DRAFT_Drawing 01 MABH-General.pdf | ||
| DRAFT_Drawing 08 MABH-Plumbing.pdf | ||
| DRAFT_Drawing 03 MABH-Structural.pdf | ||
| DRAFT_Drawing 06 MABH-Equipment.pdf | ||
| DRAFT_Drawing 10 MABH-Electrical.pdf | ||
| DRAFT_Specifications_Volume 1.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABCDEFGHJKL
MNPQRSTU
FD100-D
A1
FD100-E
A2
PHASE A2
PHASE B2
PHASE A1
PHASE B1
FD100-C
A2
FD100-E
A2
ZONE B1F-7
PRE-ACTION VALVE
ZONE B1F-6
PRE-ACTION VALVE
ZONE B1F-9
PRE-ACTION
VALVE
ZONE B1F-8
PRE-ACTION
VALVE
EXISTING FIRE
PUMP
BULK MAIN FROM
LOWER LEVEL TO
SUPPLY GROUND
LEVEL VALVES
FROM BELOW
ZONE B1F-2
PRE-ACTION VALVE
ZONE B1F-3
PRE-ACTION VALVE
ZONE B1F-4
PRE-ACTION VALVE
ZONE B1F-5
PRE-ACTION VALVE
ZONE B1F-1
PRE-ACTION VALVE
FIELD FDC ON
GROUND LEVEL,
FED FROM
BELOW
FIELD FDC ON
GROUND
LEVEL, FED
FROM BELOW
BF1-1
BF1-2
BF1-3
BF1-4
LOWER LEVEL ZONE LEGEND
BF1-5
BF1-6
BF1-7
BF1-8
BF1-9
1. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
2. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.
3. CONTRACTOR SHALL PATCH AND REPAIR CEILINGS AS REQUIRED FOR REMOVAL
OR INSTALLATION OF ALL UTILITY MODIFICATIONS.
4. DEMOLISH EXISTING FIRE ALARM SYSTEM DEVICES IN PHASE AREAS DURING
PHASE PORTION OF WORK UNLESS NOTED OTHERWISE.
5. COORDINATE CLOSELY WITH FACILITY AND CONTRACTING OFFICES DESIGNATED
REPRESENTATIVE FOR DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES
OUTSIDE OF PHASED AREAS.
6. REPLACE SPRINKLERS IN AREAS OF WORK AS NOTED, RELOCATE, AND ADD
SPRINKLERS IN PHASED AREAS OF WORK AS NEEDED TO PROVIDE ADEQUATE
COVERAGE.
7. ALL EXISTING SPRINKLERS, ARM OVERS, AND BRANCH LINE PIPING LOCATED IN
PHASED AREAS SERVING GROUND LEVEL AREA A SHALL BE REMOVED BACK TO
THE BULK MAIN AND REPLACED DURING THE COORDINATED PHASE.
8. HALF TONE NOTES ARE PROVIDED FOR INFORMATION ONLY.
9. BOLD FIRE ALARM DEVICES AND SPRINKLERS INDICATE ALARM DEVICES OR
SPRINKLERS TO BE DEMOLISHED.
10. ALL EXISTING HEAT DETECTION SHALL REMAIN THROUGHOUT THE BUILDING.
HEAT DETECTION IS PART OF THE EXISTING PRE-ACTION SPRINKLER SYSTEM,
AND SHALL REMAIN.
11. DECOMISSION AND REMOVE EXISTING FIRE ALARM CONTROL PANELS AND
ANNUNCIATORS ONLY AFTER NEW FIRE ALARM/MNS IS COMPLETE AND
OPERATIONAL.
12. ALL EXISTING PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR
INFORMATION ONLY.
13. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ELEMENTS, INCLUDING
STAFFING AND COORDINATION WITH SITE FIRE MARSHALL AND FIRE DEPARTMENT
FOR FIRE WATCHED NEEDED DURING CONSTRUCTION.
DEMOLITION NOTES FIRE PROTECTION
SCALE:1 : 250
A1
FIRE PROTECTION DEMOLITION PHASING PLAN LOWER LEVEL OVERALL
N
TRUE
NORTH
EPROJECT NO.:
CONSTR. CONTR. NO.
DRAWING NO.
SCALE:
SHEET
D E
P A
R T
M E
N T
O F
T H
E A
IR
F
O R
C E
A F
M S
A H
E A
L T
H F
A C
IL
IT
IE
S
D
IV
IS
IO
N
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
P A
C
IF
IC
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
DES
SUBMITTAL DATE
DRW CHK
ACTIVITY
FOR COMMANDER AFCEC
APPROVED
D D
C
B
A
54321
A
C
1 2 3 4 5
B
DRAWFORM
REVISION:
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
IF SHEET MEASURES LESS THAN 594 X 841 mm. IT IS A
REDUCED SIZE PRINT. REDUCE SCALE ACCORDINGLY
A/E INFO
SEAL
FA8903-15-D-0004 TO: 18-F-0072
APPROVED BY
23 DECEMBER 2019
KEY PLAN
A C
B D
E
L E
G A
C Y
P R
O J
E C
T
Q K
K A
O
P P
O R
T U
N
IT
Y
As indicated
/1
/2
:2 :1
P
M C
U se rs ew m cc ar th y\ D o cu m en ts
A u to d es k\ R ev it
P ro je ct s\
M A
B H
-F ir eP ro te ct io n ew m cc ar th y.
rv t
FD100
F
IR
E P
R O
T E
C T
IO
N
D E
M O
LI
T
IO
N
P
LA
N L
O W
E R
L E
V E
L O
V E
R A
LL
F Y
H
O S
P
IT
A L M
O D
E R
N
IZ
A T
IO
N
M
IS
A W
A A
IR
B
A S
E
J A
P A
N
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DLO EWM NSJ
8600 Indian Hills Drive
Omaha, NE 68114-4039
Tel 402.391.8111 Fax
402.391.8564
L A
D P ro je c t N o P ro je c t N u m b e r
2.5m
SCALE: 1:250
0 10m5m2.5m
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
ANN
LMNPQRSTU
EXISTING
ANNUNCIATOR PANEL
TO BE REMOVED
FD08
MECH
LN25A MECH
LN26
MECH
LN25
VEST
LN26A
MECH
LN17
STOR
LN14
READINESS
WAREHOUSE
LN13
MECH
LN10
MECH
LN11
GENERATOR
LN09
MECH
LN03
GAS STOR
LN24
MECH
LN16
LOUNGE
LN18
COMM
LN08
STOR
LN15 COMM
LN12
TLT
LN21
BREAK
LN19
OFFICE
LN22
ELEC
LN05
MECH
LN01
MECH
LN02
MECH
LN04
CORR
LN07
STAIR
LN07A
AMBUL. BAY
LN23
MECH
LN06
ZONE BIF-1
PRE-ACTION VALVE
ZONE BIF-2
PRE-ACTION VALVE
ZONE BIF-3
PRE-ACTION VALVE
ZONE BIF-4
PRE-ACTION VALVE
ZONE BIF-5
PRE-ACTION VALVE
FIELD FDC LOCATED
AT LEVEL ABOVE
FED FROM BELOW
EXISTING FIRE PUMP
TO REMAIN
EXISTING SMOKE DETECTOR TO BE REMOVED
DEMOLITION LEGEND FIRE
PROTECTION
EXISTING SMOKE DETECTOR TO REMAIN
EXISTING SPRINKLER TO BE REMOVED
EXISTING SPRINKLER TO REMAIN
FACP EXISTING FIRE ALARM CONTROL PANEL TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMAIN
1. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
2. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.
3. CONTRACTOR SHALL PATCH AND REPAIR CEILINGS AS REQUIRED FOR REMOVAL
OR INSTALLATION OF ALL UTILITY MODIFICATIONS.
4. DEMOLISH EXISTING FIRE ALARM SYSTEM DEVICES IN PHASE AREAS DURING
PHASE PORTION OF WORK UNLESS NOTED OTHERWISE.
5. COORDINATE CLOSELY WITH FACILITY AND CONTRACTING OFFICES DESIGNATED
REPRESENTATIVE FOR DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES
OUTSIDE OF PHASED AREAS.
6. REPLACE SPRINKLERS IN AREAS OF WORK AS NOTED, RELOCATE, AND ADD
SPRINKLERS IN PHASED AREAS OF WORK AS NEEDED TO PROVIDE ADEQUATE
COVERAGE.
7. ALL EXISTING SPRINKLERS, ARM OVERS, AND BRANCH LINE PIPING LOCATED IN
PHASED AREAS SERVING GROUND LEVEL AREA A SHALL BE REMOVED BACK TO
THE BULK MAIN AND REPLACED DURING THE COORDINATED PHASE.
8. HALF TONE NOTES ARE PROVIDED FOR INFORMATION ONLY.
9. BOLD FIRE ALARM DEVICES AND SPRINKLERS INDICATE ALARM DEVICES OR
SPRINKLERS TO BE DEMOLISHED.
10. ALL EXISTING HEAT DETECTION SHALL REMAIN THROUGHOUT THE BUILDING.
HEAT DETECTION IS PART OF THE EXISTING PRE-ACTION SPRINKLER SYSTEM,
AND SHALL REMAIN.
11. DECOMISSION AND REMOVE EXISTING FIRE ALARM CONTROL PANELS AND
ANNUNCIATORS ONLY AFTER NEW FIRE ALARM/MNS IS COMPLETE AND
OPERATIONAL.
12. ALL EXISTING PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR
INFORMATION ONLY.
13. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ELEMENTS, INCLUDING
STAFFING AND COORDINATION WITH SITE FIRE MARSHALL AND FIRE DEPARTMENT
FOR FIRE WATCHED NEEDED DURING CONSTRUCTION.
DEMOLITION NOTES FIRE PROTECTION
N
TRUE
NORTH
EPROJECT NO.:
CONSTR. CONTR. NO.
DRAWING NO.
SCALE:
SHEET
D E
P A
R T
M E
N T
O F
T H
E A
IR
F
O R
C E
A F
M S
A H
E A
L T
H F
A C
IL
IT
IE
S
D
IV
IS
IO
N
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
P A
C
IF
IC
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
DES
SUBMITTAL DATE
DRW CHK
ACTIVITY
FOR COMMANDER AFCEC
APPROVED
D D
C
B
A
54321
A
C
1 2 3 4 5
B
DRAWFORM
REVISION:
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
IF SHEET MEASURES LESS THAN 594 X 841 mm. IT IS A
REDUCED SIZE PRINT. REDUCE SCALE ACCORDINGLY
A/E INFO
SEAL
FA8903-15-D-0004 TO: 18-F-0072
APPROVED BY
23 DECEMBER 2019
KEY PLAN
A C
B D
E
L E
G A
C Y
P R
O J
E C
T
Q K
K A
O
P P
O R
T U
N
IT
Y
As indicated
/1
/2
:2 :2
P
M C
U se rs ew m cc ar th y\ D o cu m en ts
A u to d es k\ R ev it
P ro je ct s\
M A
B H
-F ir eP ro te ct io n ew m cc ar th y.
rv t
FD100-A
F
IR
E P
R O
T E
C T
IO
N
D E
M O
LI
T
IO
N
P
LA
N L
O W
E R
L E
V E
L
A R
E A
A
F Y
H
O S
P
IT
A L M
O D
E R
N
IZ
A T
IO
N
M
IS
A W
A A
IR
B
A S
E
J A
P A
N
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DLO EWM NSJ
8600 Indian Hills Drive
Omaha, NE 68114-4039
Tel 402.391.8111 Fax
402.391.8564
L A
D P ro je c t N o P ro je c t N u m b e r
KEYNOTE LEGEND
KEY DESCRIPTION
FD08 EXISTING FIRE ALARM CONTROL PANEL/REMOTE ANNUNCIATOR PANEL TO REMAIN
AS FUNCTIONAL AS POSSIBLE UNTIL THE ENTIRE NEW FIRE ALARM CONTROL
PANEL/REMOTE ANNUNCIATOR PANEL IN EACH AREA IS LOCATED AND IS READY TO
BE MADE ACTIVE. AT THIS POINT THE EXISTING PANELS SHALL BE DECOMMISSIONED
AND REMOVED.
SCALE:1 : 150
A1
FIRE PROTECTION DEMOLITION PLAN LOWER LEVEL - AREA A
NOTE:
ALL EXISTING CONDITIONS SHALL BE VERIFIED IN FIELD. REMOVE ALL SMOKE DETECTION
DEVICES. THIS AREA IS OUTSIDE OF PHASED WORK. TIMING OF WORK SHALL BE AT THE
GENERAL CONTRACTOR'S DISCRETION WITH COORDINATION WITH THE FACILITY AND
USERS. EXISTING FIRE ALARM CONTROL PANELS/REMOTE ANNUNCIATORS IN AREA TO
REMAIN AS FUNCTIONAL AS POSSIBLE UNTIL THE ENTIRE NEW FIRE ALARM CONTROL
PANELS/REMOTE ANNUNCIATORS IN EACH AREA IS LOCATED AND IS READY TO BE MADE
ACTIVE. AT THIS POINT THE EXISTING DEVICES MAY BE DECOMISSIONED AND REMOVED.
ALL EXISTING HEAT DETECTION DEVICES ARE TO REMAIN. HEAT DETECTION DEVICES ARE A
PART OF THE EXISTING PRE-ACTION FIRE SUPPRESSION SYSTEM AND SHALL REMAIN FULLY
FUNCTIONAL. ALL PRE-ACTION VALVES, FIRE DEPARTMENT CONNECTIONS (FDC), AND FIRE
PUMP ARE TO REMAIN AND ARE LABELED FOR INFORMATION ONLY.
EXISTING SUPPLY PIPING
TO ABOVE EXISTING
PRE-ACTION VALVES
1m
SCALE: 1:150
0 6m4m1m 2m
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
FGHJKL
OFFICE
LK14
OFFICE
LK16
OFFICE
LK17
OFFICE
LK18
HEARING
LK19
OFFICE
LK01
TLT
LK11
PHYSICAL
THERAPY
LK13
CLOS
LK07
JAN
LJ32
CAST
LJ31
DIRTY LIN
LJ28
TLT
LJ08A
BREAK
LJ08
OFFICE
LJ07
OFFICE
LJ06
EXAM
LJ05
OFFICE
LJ04
EXAM
LJ03
EXAM
LJ02
OFFICE
LJ01
OFFICE
LB08
PUBLIC HEALTH
LK15
STAIR
L-STAIR C
OFFICE
LK10
OFFICE
LK03
STOR
LJ33
STAIR
L-STAIR B
ELEC
LJ35
EXAM
LJ27
VEST
LJ37
ALCOVE
LJ36
OFFICE
LJ24
EXAM
LJ23
EXAM
LJ22
EXAM
LJ25
OFFICE
LJ26
OFFICE
LJ17
SURGICAL TRMT
LJ12
ENDOSCOPY
LJ13
ADMIN
LJ18
RECEPT
LJ19
TLT
LJ15
OFFICE
LJ10
VITALS
LJ20WAITING
LJ21
TLT
LC40
OFFICE
LC39
OFFICE
LC31
BREAK
LC32
OFFICE
LC33
ELEC
LC41
MICROBIO
LC34
SHIPPING
LC35 RECEPT
LC37
CORR
LCC3
WAITING
LC38
TLT
LC28
CORR
LJC4
CORR
LJC5
CORR
LJC3
CORR
LJC1
CORR
LJC2
CORR
LKC1
CORR
LKC2
CORR
LJC6
ELEC
LB10
STOR
LB32
ANESTH WKRM
LB31
BREAK RM
LB33
OFFICE
LB24
STOR
LC25
TLT
LC26
JAN
LC27
BLOOD BANK
LC21
OFFICE
LC04
TLT
LC29
LAB
LC24
LAB
LC20
CIRMCIS RM
LC05
VEST
LC36
CORR
LCC4
CORR
LBC3
EQPM STOR
LB28
ELEC
LB29
SOILED
LB26
LOUNGE
LB25
F/TLT
LB23
M/TLT
LB20
OR 2
LB04
CENT STERILE
LB02
SCRUB
LB03
TLT
LB06
F/LOCKER
LB21
M/LOCKER
LB18
OFFICE
LB15
NURSE STAT
LC02
NURSERY
LC03
SCRUB
LC06
JAN
LC12
CORR
LC10STOR
LC08
STOR
LC09 STOR
LC11
HAZ STOR
LC22
SPECIMAN
LC30
OFFICE
LC19
OFFICE
LC18
TLT
LC17
STOR
LC23
OFFICE
LC16 DAYROOM
LC15
OFFICE
LC14
BREAK
LC07
VEST
LC13
DICTATE
LB27
CORR
LBC4
ALCOVE
LB30
CORR
LBC1
CORR
LB17
JAN
LB14 ALCOVE
LB13
NURSE STAT
LB11
CORR
LB12
VEST
LB09
NURSE STAT
LB07
RECOVERY
LB05
CORR
LBC2FD04
FD04
EXISTING SMOKE DETECTOR TO BE REMOVED
DEMOLITION LEGEND FIRE
PROTECTION
EXISTING SMOKE DETECTOR TO REMAIN
EXISTING SPRINKLER TO BE REMOVED
EXISTING SPRINKLER TO REMAIN
FACP EXISTING FIRE ALARM CONTROL PANEL TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMAIN
1. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
2. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.
3. CONTRACTOR SHALL PATCH AND REPAIR CEILINGS AS REQUIRED FOR REMOVAL
OR INSTALLATION OF ALL UTILITY MODIFICATIONS.
4. DEMOLISH EXISTING FIRE ALARM SYSTEM DEVICES IN PHASE AREAS DURING
PHASE PORTION OF WORK UNLESS NOTED OTHERWISE.
5. COORDINATE CLOSELY WITH FACILITY AND CONTRACTING OFFICES DESIGNATED
REPRESENTATIVE FOR DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES
OUTSIDE OF PHASED AREAS.
6. REPLACE SPRINKLERS IN AREAS OF WORK AS NOTED, RELOCATE, AND ADD
SPRINKLERS IN PHASED AREAS OF WORK AS NEEDED TO PROVIDE ADEQUATE
COVERAGE.
7. ALL EXISTING SPRINKLERS, ARM OVERS, AND BRANCH LINE PIPING LOCATED IN
PHASED AREAS SERVING GROUND LEVEL AREA A SHALL BE REMOVED BACK TO
THE BULK MAIN AND REPLACED DURING THE COORDINATED PHASE.
8. HALF TONE NOTES ARE PROVIDED FOR INFORMATION ONLY.
9. BOLD FIRE ALARM DEVICES AND SPRINKLERS INDICATE ALARM DEVICES OR
SPRINKLERS TO BE DEMOLISHED.
10. ALL EXISTING HEAT DETECTION SHALL REMAIN THROUGHOUT THE BUILDING.
HEAT DETECTION IS PART OF THE EXISTING PRE-ACTION SPRINKLER SYSTEM,
AND SHALL REMAIN.
11. DECOMISSION AND REMOVE EXISTING FIRE ALARM CONTROL PANELS AND
ANNUNCIATORS ONLY AFTER NEW FIRE ALARM/MNS IS COMPLETE AND
OPERATIONAL.
12. ALL EXISTING PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR
INFORMATION ONLY.
13. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ELEMENTS, INCLUDING
STAFFING AND COORDINATION WITH SITE FIRE MARSHALL AND FIRE DEPARTMENT
FOR FIRE WATCHED NEEDED DURING CONSTRUCTION.
DEMOLITION NOTES FIRE PROTECTION
N
TRUE
NORTH
EPROJECT NO.:
CONSTR. CONTR. NO.
DRAWING NO.
SCALE:
SHEET
D E
P A
R T
M E
N T
O F
T H
E A
IR
F
O R
C E
A F
M S
A H
E A
L T
H F
A C
IL
IT
IE
S
D
IV
IS
IO
N
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
P A
C
IF
IC
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
DES
SUBMITTAL DATE
DRW CHK
ACTIVITY
FOR COMMANDER AFCEC
APPROVED
D D
C
B
A
54321
A
C
1 2 3 4 5
B
DRAWFORM
REVISION:
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
IF SHEET MEASURES LESS THAN 594 X 841 mm. IT IS A
REDUCED SIZE PRINT. REDUCE SCALE ACCORDINGLY
A/E INFO
SEAL
FA8903-15-D-0004 TO: 18-F-0072
APPROVED BY
23 DECEMBER 2019
KEY PLAN
A C
B D
E
L E
G A
C Y
P R
O J
E C
T
Q K
K A
O
P P
O R
T U
N
IT
Y
As indicated
/1
/2
:2 :2
P
M C
U se rs ew m cc ar th y\ D o cu m en ts
A u to d es k\ R ev it
P ro je ct s\
M A
B H
-F ir eP ro te ct io n ew m cc ar th y.
rv t
FD100-B
F
IR
E P
R O
T E
C T
IO
N
D E
M O
LI
T
IO
N
P
LA
N L
O W
E R
L E
V E
L
A R
E A
B
F Y
H
O S
P
IT
A L M
O D
E R
N
IZ
A T
IO
N
M
IS
A W
A A
IR
B
A S
E
J A
P A
N
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DLO EWM NSJ
8600 Indian Hills Drive
Omaha, NE 68114-4039
Tel 402.391.8111 Fax
402.391.8564
L A
D P ro je c t N o P ro je c t N u m b e r
SCALE: 1 : 100
A1
FIRE PROTECTION DEMOLITION PLAN LOWER LEVEL - AREA B
NOTE:
ALL EXISTING CONDITIONS SHALL BE VERIFIED IN FIELD. REMOVE ALL SMOKE DETECTION
DEVICES. THIS AREA IS OUTSIDE OF PHASED WORK. TIMING OF WORK SHALL BE AT THE
GENERAL CONTRACTOR'S DISCRETION WITH COORDINATION WITH THE FACILITY AND
USERS. EXISTING FIRE ALARM CONTROL PANELS/REMOTE ANNUNCIATORS IN AREA TO
REMAIN AS FUNCTIONAL AS POSSIBLE UNTIL THE ENTIRE NEW FIRE ALARM CONTROL
PANELS/REMOTE ANNUNCIATORS IN EACH AREA IS LOCATED AND IS READY TO BE MADE
ACTIVE. AT THIS POINT THE EXISTING DEVICES MAY BE DECOMISSIONED AND REMOVED.
ALL EXISTING HEAT DETECTION DEVICES ARE TO REMAIN. HEAT DETECTION DEVICES ARE A
PART OF THE EXISTING PRE-ACTION FIRE SUPPRESSION SYSTEM AND SHALL REMAIN FULLY
FUNCTIONAL.
KEYNOTE LEGEND
KEY DESCRIPTION
FD04 EXISTING BULK MAIN TO REMAIN.
1m
SCALE: 1:100
0 4m2m1m
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
FACP
EXISTING FIRE
ALARM CONTROL
PANEL TO BE
REMOVED
FD08
PHASE A1 AREA OF WORK:
DEMO SPRINKLERS, DROPS AND ARM
OVERS. DEMO BRANCH LINES AS
NEEDED.
OPTOMETRY
OFFICE
LM22
OPTOMETRY EXAM
LM21
OPTOMETRY
SUPPLY
LM19
FLT MED EXAM
LM18
FLT MED EXAM
LM17
FLT MED OFFICE
LM16
FLT MED EXAM
LM15
FLT MED EXAM
LM14
FLT MED EXAM
LM13
ELEC
LL15
FLT MED OFFICE
LL14
FLT MED OFFICE
LL13
FLT MED ROOM
LL12
PUBLIC HEALTH
LK15
TLT
LL11
OFFICE
LL10
STAIR
L-STAIR C
ELEV
L-ELEV 01
VEST
LL17
ELEC
LL05
F/TLT
LL03
OFFICE
LM01
OFFICE
LM03
SCREENING
LM02
STOR
LL16
OFFICE
LL06
JAN
LM05
TLT
LM04
OFFICE
LL07
NAVY MED/OPTM.
RECORDS
LM06
NAVY MED/OPTM.
LM07
ELEV
L-ELEV 02
VEST
LM27NAVY MED/OPTM.
RECORDS
LM08
OPTM. OFFICE
LM12
EYE LANE
LM24
OPTM. FITTING
ROOM
LM11
OPTOMETRY EXAM
LM10
EYE LANE
LM25
ELEC
LM23
STAIR
L-STAIR D
M/TLT
LL02
OFFICE
LL09
ALCOVE
LL08
WAITING
LC38
RADIOLOGY
WAITING
LF35
RADIOLOGY
RECORDS
LF37
RECEPTION
LF36
RAD. OFFICE
LF39
RAD. OFFICE
LF40
COMP.
TOMOGRAPHY
LF42
TLT
LF43
S. UTILITY
LG13
URGENT VITAL
LG14
COMM
LG15A
STOR
LG17A
URGENT WAITING
LG15
JAN
LG18
TLT
LG19
URGENT OFFICE
LG21
SUPPLY
LG22A
OFFICE
LG22B
URGENT TRIAGE
LG20
CORR
LGC5
URGENT MEDS
LG12
CORR
LMC2
CORR
LM26
URGENT
RECEPTION
LG17
TLT
LG16
CORR
LMC1
CORR
LF41
WORK SPACE
LF44
RADIOLOGY
READING
LF38
CORR
LLC2
CORR
LLC4
CORR
LLC1
CORR
LMC3
SPECIMAN
LC30
OFFICE
LC19
OFFICE
LC18 TLT
LC17
OFFICE
LC16
DAYROOM
LC15
OFFICE CONTROL
LF01
TLT
LF03COMM
LF17
COMM
LF18
RAD. MAMMO
LF19
TLT
LF22
CORR
LF20
ULTRASOUND
LF25
RAD. WORK AREA
LF26
RAD. X-RAY
LF21 L&D SUPPLY
LF08
TLT
LF06
CHAPEL
LF15
TLT
LF16 L&D LOUNGE
LF12
L&D SOILED UTL
LF14
RAD. X-RAY
LF30TLT
LF31
CORR
LF29
L&D SUPPLY
LF09
STOR
LF33
STOR
LF34
SUPPLY
LF32
URGENT EXAM
LG09
URGENT EXAM
LG10
URGENT EXAM
LG11
BIO. MED. EQ.
TECH SHOP
LG06
OFFICE
LG08
CORR
LGC4A LOUNGE
LG22C
LINEN
OFFICE/SUPPLY
LG05
LINEN S. LINEN
LG04
LINEN C. LINEN
LG03
VENDING
LG02
CORR
LGC4
CORR
LFC1
CORR
LFC3
CORR
LGC3
STOR
LG01
L&D NURSE
LF13
RAD. STORAGE
LF28
RAD. CONTROL
LF27
L&D MEDICATION
LF11
STOR
LF23
CORR
LCC2 CORR
LFC2
L&D PAT RM
LF05 L&D ANTE
LF04
CORR
LF10
MECH
LH31
OFFICE
LH30
STORAGE
LG26
VEST
LG25
STORAGE
LG27
ZONE BIF-1
PRE-ACTION VALVE
ZONE BIF-2
PRE-ACTION VALVE
ZONE BIF-3
PRE-ACTION VALVE
ZONE BIF-4
PRE-ACTION VALVE
ZONE BIF-5
PRE-ACTION VALVE
FD04
FD04
FD04
FD04
AREA OF WORK
HATCH LEGEND
STORAGE
SL001
EXISTING SMOKE DETECTOR TO BE REMOVED
DEMOLITION LEGEND FIRE
PROTECTION
EXISTING SMOKE DETECTOR TO REMAIN
EXISTING SPRINKLER TO BE REMOVED
EXISTING SPRINKLER TO REMAIN
FACP EXISTING FIRE ALARM CONTROL PANEL TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMAIN
1. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
2. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.
3. CONTRACTOR SHALL PATCH AND REPAIR CEILINGS AS REQUIRED FOR REMOVAL
OR INSTALLATION OF ALL UTILITY MODIFICATIONS.
4. DEMOLISH EXISTING FIRE ALARM SYSTEM DEVICES IN PHASE AREAS DURING
PHASE PORTION OF WORK UNLESS NOTED OTHERWISE.
5. COORDINATE CLOSELY WITH FACILITY AND CONTRACTING OFFICES DESIGNATED
REPRESENTATIVE FOR DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES
OUTSIDE OF PHASED AREAS.
6. REPLACE SPRINKLERS IN AREAS OF WORK AS NOTED, RELOCATE, AND ADD
SPRINKLERS IN PHASED AREAS OF WORK AS NEEDED TO PROVIDE ADEQUATE
COVERAGE.
7. ALL EXISTING SPRINKLERS, ARM OVERS, AND BRANCH LINE PIPING LOCATED IN
PHASED AREAS SERVING GROUND LEVEL AREA A SHALL BE REMOVED BACK TO
THE BULK MAIN AND REPLACED DURING THE COORDINATED PHASE.
8. HALF TONE NOTES ARE PROVIDED FOR INFORMATION ONLY.
9. BOLD FIRE ALARM DEVICES AND SPRINKLERS INDICATE ALARM DEVICES OR
SPRINKLERS TO BE DEMOLISHED.
10. ALL EXISTING HEAT DETECTION SHALL REMAIN THROUGHOUT THE BUILDING.
HEAT DETECTION IS PART OF THE EXISTING PRE-ACTION SPRINKLER SYSTEM,
AND SHALL REMAIN.
11. DECOMISSION AND REMOVE EXISTING FIRE ALARM CONTROL PANELS AND
ANNUNCIATORS ONLY AFTER NEW FIRE ALARM/MNS IS COMPLETE AND
OPERATIONAL.
12. ALL EXISTING PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR
INFORMATION ONLY.
13. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ELEMENTS, INCLUDING
STAFFING AND COORDINATION WITH SITE FIRE MARSHALL AND FIRE DEPARTMENT
FOR FIRE WATCHED NEEDED DURING CONSTRUCTION.
DEMOLITION NOTES FIRE PROTECTION
N
TRUE
NORTH
EPROJECT NO.:
CONSTR. CONTR. NO.
DRAWING NO.
SCALE:
SHEET
D E
P A
R T
M E
N T
O F
T H
E A
IR
F
O R
C E
A F
M S
A H
E A
L T
H F
A C
IL
IT
IE
S
D
IV
IS
IO
N
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
P A
C
IF
IC
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
DES
SUBMITTAL DATE
DRW CHK
ACTIVITY
FOR COMMANDER AFCEC
APPROVED
D D
C
B
A
54321
A
C
1 2 3 4 5
B
DRAWFORM
REVISION:
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
IF SHEET MEASURES LESS THAN 594 X 841 mm. IT IS A
REDUCED SIZE PRINT. REDUCE SCALE ACCORDINGLY
A/E INFO
SEAL
FA8903-15-D-0004 TO: 18-F-0072
APPROVED BY
23 DECEMBER 2019
KEY PLAN
A C
B D
E
L E
G A
C Y
P R
O J
E C
T
Q K
K A
O
P P
O R
T U
N
IT
Y
As indicated
/1
/2
:2 :3
P
M C
U se rs ew m cc ar th y\ D o cu m en ts
A u to d es k\ R ev it
P ro je ct s\
M A
B H
-F ir eP ro te ct io n ew m cc ar th y.
rv t
FD100-C
F
IR
E P
R O
T E
C T
IO
N
D E
M O
LI
T
IO
N
P
LA
N L
O W
E R
L E
V E
L
A R
E A
C
F Y
H
O S
P
IT
A L M
O D
E R
N
IZ
A T
IO
N
M
IS
A W
A A
IR
B
A S
E
J A
P A
N
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DLO EWM NSJ
8600 Indian Hills Drive
Omaha, NE 68114-4039
Tel 402.391.8111 Fax
402.391.8564
L A
D P ro je c t N o P ro je c t N u m b e r
KEYNOTE LEGEND
KEY DESCRIPTION
FD04 EXISTING BULK MAIN TO REMAIN.
FD08 EXISTING FIRE ALARM CONTROL PANEL/REMOTE ANNUNCIATOR PANEL TO REMAIN
AS FUNCTIONAL AS POSSIBLE UNTIL THE ENTIRE NEW FIRE ALARM CONTROL
PANEL/REMOTE ANNUNCIATOR PANEL IN EACH AREA IS LOCATED AND IS READY TO
BE MADE ACTIVE. AT THIS POINT THE EXISTING PANELS SHALL BE DECOMMISSIONED
AND REMOVED.
SCALE:1 : 150
A2
FIRE PROTECTION DEMOLITION PLAN LOWER LEVEL - AREA C
NOTE:
ALL EXISTING CONDITIONS SHALL BE VERIFIED IN FIELD. REMOVE ALL SMOKE DETECTION
DEVICES. WHERE AREAS OF WORK HAVE ASSIGNED PHASING, ALL WORK SHALL BE DURING
THE PHASE NOTED. SEE ARCHITECTURAL SHEETS FOR PHASING DETAILS. TIMING OF WORK
OUTSIDE OF ASSIGNED PHASED AREAS SHALL BE AT THE GENERAL CONTRACTOR'S
DISCRETION WITH COORDINATION WITH THE FACILITY AND USERS. EXISTING FIRE ALARM
CONTROL PANELS/REMOTE ANNUNCIATORS IN AREA TO REMAIN AS FUNCTIONAL AS
POSSIBLE UNTIL THE ENTIRE NEW FIRE ALARM CONTROL PANELS/REMOTE ANNUNCIATORS
IN EACH AREA IS LOCATED AND IS READY TO BE MADE ACTIVE. AT THIS POINT THE EXISTING
DEVICES MAY BE DECOMISSIONED AND REMOVED. ALL EXISTING HEAT DETECTION DEVICES
IN THIS AREA IN ITS ENTIRETY ARE TO REMAIN. HEAT DETECTION DEVICES EXIST AS PART
OF THE PRE-ACTION FIRE SUPPRESSION SYSTEM AND SHALL REMAIN FULLY FUNCTIONAL.
ALL PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR INFORMATION ONLY.
1m
SCALE: 1:100
0 4m2m1m
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
ABCDE
FD01
PHASE B2 AREA OF WORK:
DEMO SPRINKLERS, DROPS AND ARM
OVERS. DEMO BRANCH LINES AS
NEEDED.
FD05
FD04
FD04
FD04
AREA OF WORK
HATCH LEGEND
CENT STERILE
ORSR1
SCRUB
ORSA1
BREAK
LC07
VEST
LC13
CORR
NTG02
CORR
NTG02
OR 1
ORGS1
STERILE STOR
ORSS1
STAIR
NTG14
VEST
NTG10
STERILE STOR
ORSS1
VEST
NTG10
EQUIP WASH &
DRY
CSIA2
STERILE STOR
ORSS1
EQPM STOR
SRE01
OFFICE
OFA01
ALCOVE
CLSC1
ALCOVE
CLSC1
CORR
NTG02
OFFICE
OFA01
DELIVERY RM
LDRP1
CENT STERILE
CSSS1
TLT
TLTU1
MEDS
LA14
STOR
PHBS1
JAN
JANC1
LABOR DELIVERY
LDRP2
SCRUB
ORSA1
NURSE STAT
NSTA1
LOUNGE
SL001
STOR
SRSE1
NON-STERILE
ASSEMBLY
CSIA2
STERILE WASHER
SCWS3
F/TLT
TLTF1 M/TLT
TLTM1
CORR
NTG02
VEST
NTG10
F/LOCKER
LR002
M/LOCKER
LR002
ALCOVE
LA28
CORR
NTG02
LABOR DELIVERY
LDRP2
TLT/SHWR
LA18
LABOR DELIVERY
LDRP2
TLT/SHWR
LA22
CORR
NTG02
CORR
NTG02
F/SHWR
SHWR1
M/SHWR
SHWR1
STOR
LD05
STORAGE
LD01
CORR
NTG02
JAN
LD04
GYM
LD02TLT
LD08
EQPM STOR
SRE01
TLT
TLTU1
STAFF SLEEP RM
SL001
STAIR
NTG14
CORR
NTG02
CORR
NTG10
CORR
NTG10
SHOWER
SHWR1
M/TLT
TLTM1
F/TLT
TLTF1
MECHANICAL
NTG05
ANTE
LD06
TLT
LD10
PATIENT RM
LD07
DBL PAT RM
BRLC2
DBL PAT RM
BRLC2
TLT
TLTS1
SOILED
USCL1ALCOVE
CLSC1
MED
PHOD1
TLT
TLTS1
DBL PAT RM
BRLC2
DBL PAT RM
BRLC2
ALCOVE
CLSC1
TLT
TLTS1
TLT
TLTS1
DBL PAT RM
BRLC2
CORR
NTG02
WAREHOUSE
SRS01
COURT YARD
COURT
EXISTING SMOKE DETECTOR TO BE REMOVED
DEMOLITION LEGEND FIRE
PROTECTION
EXISTING SMOKE DETECTOR TO REMAIN
EXISTING SPRINKLER TO BE REMOVED
EXISTING SPRINKLER TO REMAIN
FACP EXISTING FIRE ALARM CONTROL PANEL TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMAIN
1. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
2. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.
3. CONTRACTOR SHALL PATCH AND REPAIR CEILINGS AS REQUIRED FOR REMOVAL
OR INSTALLATION OF ALL UTILITY MODIFICATIONS.
4. DEMOLISH EXISTING FIRE ALARM SYSTEM DEVICES IN PHASE AREAS DURING
PHASE PORTION OF WORK UNLESS NOTED OTHERWISE.
5. COORDINATE CLOSELY WITH FACILITY AND CONTRACTING OFFICES DESIGNATED
REPRESENTATIVE FOR DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES
OUTSIDE OF PHASED AREAS.
6. REPLACE SPRINKLERS IN AREAS OF WORK AS NOTED, RELOCATE, AND ADD
SPRINKLERS IN PHASED AREAS OF WORK AS NEEDED TO PROVIDE ADEQUATE
COVERAGE.
7. ALL EXISTING SPRINKLERS, ARM OVERS, AND BRANCH LINE PIPING LOCATED IN
PHASED AREAS SERVING GROUND LEVEL AREA A SHALL BE REMOVED BACK TO
THE BULK MAIN AND REPLACED DURING THE COORDINATED PHASE.
8. HALF TONE NOTES ARE PROVIDED FOR INFORMATION ONLY.
9. BOLD FIRE ALARM DEVICES AND SPRINKLERS INDICATE ALARM DEVICES OR
SPRINKLERS TO BE DEMOLISHED.
10. ALL EXISTING HEAT DETECTION SHALL REMAIN THROUGHOUT THE BUILDING.
HEAT DETECTION IS PART OF THE EXISTING PRE-ACTION SPRINKLER SYSTEM,
AND SHALL REMAIN.
11. DECOMISSION AND REMOVE EXISTING FIRE ALARM CONTROL PANELS AND
ANNUNCIATORS ONLY AFTER NEW FIRE ALARM/MNS IS COMPLETE AND
OPERATIONAL.
12. ALL EXISTING PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR
INFORMATION ONLY.
13. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ELEMENTS, INCLUDING
STAFFING AND COORDINATION WITH SITE FIRE MARSHALL AND FIRE DEPARTMENT
FOR FIRE WATCHED NEEDED DURING CONSTRUCTION.
DEMOLITION NOTES FIRE PROTECTION
N
TRUE
NORTH
EPROJECT NO.:
CONSTR. CONTR. NO.
DRAWING NO.
SCALE:
SHEET
D E
P A
R T
M E
N T
O F
T H
E A
IR
F
O R
C E
A F
M S
A H
E A
L T
H F
A C
IL
IT
IE
S
D
IV
IS
IO
N
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
P A
C
IF
IC
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
DES
SUBMITTAL DATE
DRW CHK
ACTIVITY
FOR COMMANDER AFCEC
APPROVED
D D
C
B
A
54321
A
C
1 2 3 4 5
B
DRAWFORM
REVISION:
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
IF SHEET MEASURES LESS THAN 594 X 841 mm. IT IS A
REDUCED SIZE PRINT. REDUCE SCALE ACCORDINGLY
A/E INFO
SEAL
FA8903-15-D-0004 TO: 18-F-0072
APPROVED BY
23 DECEMBER 2019
KEY PLAN
A C
B D
E
L E
G A
C Y
P R
O J
E C
T
Q K
K A
O
P P
O R
T U
N
IT
Y
As indicated
/1
/2
:2 :4
P
M C
U se rs ew m cc ar th y\ D o cu m en ts
A u to d es k\ R ev it
P ro je ct s\
M A
B H
-F ir eP ro te ct io n ew m cc ar th y.
rv t
FD100-D
F
IR
E P
R O
T E
C T
IO
N
D E
M O
LI
T
IO
N
P
LA
N L
O W
E R
L E
V E
L
A R
E A
D
F Y
H
O S
P
IT
A L M
O D
E R
N
IZ
A T
IO
N
M
IS
A W
A A
IR
B
A S
E
J A
P A
N
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DLO EWM NSJ
8600 Indian Hills Drive
Omaha, NE 68114-4039
Tel 402.391.8111 Fax
402.391.8564
L A
D P ro je c t N o P ro je c t N u m b e r
KEYNOTE LEGEND
KEY DESCRIPTION
FD01 EXISTING SMOKE DETECTION TO BE DEMOLISHED IN THIS AREA DURING THE
CORRESPONDING DEMOLITION PHASE NOTED.
FD04 EXISTING BULK MAIN TO REMAIN.
FD05 REMOVE EXISTING SPRINKLERS DROPS, ARM OVERS, AND BRANCH LINES BACK TO
EXISTING MAIN IN THIS AREA OF WORK DURING THE CORRESPONDING PHASE.
SCALE: 1 : 100
A1
FIRE PROTECTION DEMOLITION PLAN LOWER LEVEL - AREA D
NOTE:
ALL EXISTING CONDITIONS SHALL BE VERIFIED IN FIELD. REMOVE ALL SMOKE DETECTION
DEVICES. WHERE AREAS OF WORK HAVE ASSIGNED PHASING, ALL WORK SHALL BE DURING
THE PHASE NOTED. SEE ARCHITECTURAL SHEETS FOR PHASING DETAILS. TIMING OF
WORK OUTSIDE OF ASSIGNED PHASED AREAS SHALL BE AT THE GENERAL CONTRACTOR'S
DISCRETION WITH COORDINATION WITH THE FACILITY AND USERS. EXISTING FIRE ALARM
CONTROL PANELS/REMOTE ANNUNCIATORS IN AREA TO REMAIN AS FUNCTIONAL AS
POSSIBLE UNTIL THE ENTIRE NEW FIRE ALARM CONTROL PANELS/REMOTE ANNUNCIATORS
IN EACH AREA IS LOCATED AND IS READY TO BE MADE ACTIVE. AT THIS POINT THE
EXISTING DEVICES MAY BE DECOMISSIONED AND REMOVED. ALL EXISTING HEAT
DETECTION DEVICES IN THIS AREA IN ITS ENTIRETY ARE TO REMAIN. HEAT DETECTION
DEVICES EXIST AS PART OF THE PRE-ACTION FIRE SUPPRESSION SYSTEM AND SHALL
REMAIN FULLY FUNCTIONAL.
1m
SCALE: 1:100
0 4m2m1m
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
ABCDEF
KITCHEN SPACE
IPK01
OFFICE, CONSULT
OFA04
DAYROOM
LC15
OFFICE
LC14
TLT
LF06
TLT
LE06
LINEN S. LINEN
LG04
LINEN C. LINEN
LG03
VENDING
LG02
STOR
LG01
L&D NURSE
LF13
BREAK
LC07
VEST
LC13
CORR
LFC2
L&D ANTE
LF04
CORR
LF10
MECH
LH31
FACILITIES OFFICE
LH30
STAIR
L-STAIR E
OFFICE
LH14
HOUSEKEEPING
LH28
STOR
LG23
OFFICE
LH26
ELEC
LH25
TLT
LH27
VEST
LG24
L&D CL LINEN
LE26
ELEC
LE25
OFFICE
LH16
OFFICE
LH15
FACILITIES OFFICE
LH29
FACILITIES OFFICE
LH29A
JAN
LD04
GYM
LD02
TLT
LD08
STAFF SLEEP RM
LA26
STAIR
L-STAIR F
CORR
LDC1
CORR
LA48
CORR
LA47
SHOWER
LD24
M/TLT
LD27
F/TLT
LD22
MECHANICAL
LD25
WAREHOUSE
LD23
COURT YARD
COURT
PATIENT RM
LD07
MED
LD14
TLT
LD16
DBL PAT RM
LD15
DBL PAT RM
LD17
ALCOVE
LD19
TLT
LD18
TLT
LD21
DBL PAT RM
LD20
CORR
LD26
L&D PATIENT RM
LE05
L&D ANTE
LE04
TLT
LE09 L&D PATIENT RM
LE08
ANTE
LE07
L&D PATIENT RM
LE10
L&D PATIENT RM
LE12
TLT
LE11
TLT
LE13
CORR
LEC1
SYSTEMS OFFICE
LE14
TLT
LE15
OFFICE
LE16
TLT
LE22
TLT
LE21
F/LCKR
LE20
M/LCKR
LE23
LOCKER
LE19TLT
LE17
JAN
LE18
CORR
LHC1
CORR
LHC2
CORR
LH13
LOADING DOCK
LH11
TRASH
LH10
MORGUE
LH09
GAS STOR
LH01
GAS STOR
LH02
GAS STOR
LH02A
LOG. VAULT
LE02
LOUNGE
LH06
F/TLT
LH08
M/TLT
LH07
STOR
LH05
ELEC
LH04
STORAGE
LG27 STORM WATER
PUMP ROOM
LG30
CORR
LG28
STOR
LG29
MECH
LG31
CORR
LH12
PHASE A2 AREA OF WORK:
DEMO SPRINKLERS, DROPS AND
ARM OVERS. DEMO BRANCH
LINES AS NEEDED.
FD09
ZONE BIF-6
PRE-ACTION VALVE
ZONE BIF-7
PRE-ACTION VALVE
PIPING TO FIELD
FDC ABOVE
FD04
FD04
FD04
FD04
FD04
FD10
AREA OF WORK
HATCH LEGEND
PHASE B1 AREA OF WORK:
DEMO SPRINKLERS, DROPS AND ARM
OVERS BACK TO BRANCH LINE IN
AREA OF WORK ONLY. BRANCH
LINES ARE TO REMAIN.
ZONE BIF-8
PRE-ACTION VALVE
ZONE BIF-9
PRE-ACTION VALVE
EXISTING SMOKE DETECTOR TO BE REMOVED
DEMOLITION LEGEND FIRE
PROTECTION
EXISTING SMOKE DETECTOR TO REMAIN
EXISTING SPRINKLER TO BE REMOVED
EXISTING SPRINKLER TO REMAIN
FACP EXISTING FIRE ALARM CONTROL PANEL TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMAIN
1. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
2. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.
3. CONTRACTOR SHALL PATCH AND REPAIR CEILINGS AS REQUIRED FOR REMOVAL
OR INSTALLATION OF ALL UTILITY MODIFICATIONS.
4. DEMOLISH EXISTING FIRE ALARM SYSTEM DEVICES IN PHASE AREAS DURING
PHASE PORTION OF WORK UNLESS NOTED OTHERWISE.
5. COORDINATE CLOSELY WITH FACILITY AND CONTRACTING OFFICES DESIGNATED
REPRESENTATIVE FOR DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES
OUTSIDE OF PHASED AREAS.
6. REPLACE SPRINKLERS IN AREAS OF WORK AS NOTED, RELOCATE, AND ADD
SPRINKLERS IN PHASED AREAS OF WORK AS NEEDED TO PROVIDE ADEQUATE
COVERAGE.
7. ALL EXISTING SPRINKLERS, ARM OVERS, AND BRANCH LINE PIPING LOCATED IN
PHASED AREAS SERVING GROUND LEVEL AREA A SHALL BE REMOVED BACK TO
THE BULK MAIN AND REPLACED DURING THE COORDINATED PHASE.
8. HALF TONE NOTES ARE PROVIDED FOR INFORMATION ONLY.
9. BOLD FIRE ALARM DEVICES AND SPRINKLERS INDICATE ALARM DEVICES OR
SPRINKLERS TO BE DEMOLISHED.
10. ALL EXISTING HEAT DETECTION SHALL REMAIN THROUGHOUT THE BUILDING.
HEAT DETECTION IS PART OF THE EXISTING PRE-ACTION SPRINKLER SYSTEM,
AND SHALL REMAIN.
11. DECOMISSION AND REMOVE EXISTING FIRE ALARM CONTROL PANELS AND
ANNUNCIATORS ONLY AFTER NEW FIRE ALARM/MNS IS COMPLETE AND
OPERATIONAL.
12. ALL EXISTING PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR
INFORMATION ONLY.
13. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ELEMENTS, INCLUDING
STAFFING AND COORDINATION WITH SITE FIRE MARSHALL AND FIRE DEPARTMENT
FOR FIRE WATCHED NEEDED DURING CONSTRUCTION.
DEMOLITION NOTES FIRE PROTECTION
N
TRUE
NORTH
EPROJECT NO.:
CONSTR. CONTR. NO.
DRAWING NO.
SCALE:
SHEET
D E
P A
R T
M E
N T
O F
T H
E A
IR
F
O R
C E
A F
M S
A H
E A
L T
H F
A C
IL
IT
IE
S
D
IV
IS
IO
N
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
P A
C
IF
IC
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
DES
SUBMITTAL DATE
DRW CHK
ACTIVITY
FOR COMMANDER AFCEC
APPROVED
D D
C
B
A
54321
A
C
1 2 3 4 5
B
DRAWFORM
REVISION:
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
IF SHEET MEASURES LESS THAN 594 X 841 mm. IT IS A
REDUCED SIZE PRINT. REDUCE SCALE ACCORDINGLY
A/E INFO
SEAL
FA8903-15-D-0004 TO: 18-F-0072
APPROVED BY
23 DECEMBER 2019
KEY PLAN
A C
B D
E
L E
G A
C Y
P R
O J
E C
T
Q K
K A
O
P P
O R
T U
N
IT
Y
As indicated
/1
/2
:2 :5
P
M C
U se rs ew m cc ar th y\ D o cu m en ts
A u to d es k\ R ev it
P ro je ct s\
M A
B H
-F ir eP ro te ct io n ew m cc ar th y.
rv t
FD100-E
F
IR
E P
R O
T E
C T
IO
N
D E
M O
LI
T
IO
N
P
LA
N L
O W
E R
L E
V E
L
A R
E A
E
F Y
H
O S
P
IT
A L M
O D
E R
N
IZ
A T
IO
N
M
IS
A W
A A
IR
B
A S
E
J A
P A
N
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DLO EWM NSJ
8600 Indian Hills Drive
Omaha, NE 68114-4039
Tel 402.391.8111 Fax
402.391.8564
L A
D P ro je c t N o P ro je c t N u m b e r
SCALE:1 : 150
A2
FIRE PROTECTION DEMOLITION PLAN LOWER LEVEL - AREA E
KEYNOTE LEGEND
KEY DESCRIPTION
FD04 EXISTING BULK MAIN TO REMAIN.
FD09 CEILING TO BE DEMOLISHED IN THIS AREA AS PART OF PHASE 1 TO ACCOMMODATE
CONSTRUCTION OF A NEW MECHANICAL ROOM. REMOVE SPRINKLERS, DROPS, ARM
OVERS, AND BRANCH LINES BACK TO THE EXISTING BULK MAIN IN THIS AREA OF
WORK AS NECESSARY.
FD10 DEMOLISH EXISTING PIPE AS FAR BACK AS NECESSARY FOR INSTALLATION OF NEW
SPRINKLERS. TRY TO KEEP DEMOLITION WITHIN THE AREA OF WORK.
NOTE:
ALL EXISTING CONDITIONS SHALL BE VERIFIED IN FIELD. REMOVE ALL SMOKE DETECTION
DEVICES. WHERE AREAS OF WORK HAVE ASSIGNED PHASING, ALL WORK SHALL BE DURING
THE PHASE NOTED. SEE ARCHITECTURAL SHEETS FOR PHASING DETAILS. TIMING OF WORK
OUTSIDE OF ASSIGNED PHASED AREAS SHALL BE AT THE GENERAL CONTRACTOR'S
DISCRETION WITH COORDINATION WITH THE FACILITY AND USERS. EXISTING FIRE ALARM
CONTROL PANELS/REMOTE ANNUNCIATORS IN AREA TO REMAIN AS FUNCTIONAL AS
POSSIBLE UNTIL THE ENTIRE NEW FIRE ALARM CONTROL PANELS/REMOTE ANNUNCIATORS
IN EACH AREA IS LOCATED AND IS READY TO BE MADE ACTIVE. AT THIS POINT THE EXISTING
DEVICES MAY BE DECOMISSIONED AND REMOVED. ALL EXISTING HEAT DETECTION DEVICES
ARE TO REMAIN. HEAT DETECTION DEVICES EXIST AS PART OF THE PRE-ACTION FIRE
SUPPRESSION SYSTEM AND SHALL REMAIN FULLY FUNCTIONAL. ALL VALVES ARE TO
REMAIN AND ARE LABELED FOR INFORMATION ONLY.
1m
SCALE: 1:100
0 4m2m1m
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
DEFGHJKL
MNPQ
FD101-A
A1
FD101-A
B4
FD101-A
A1
FD101-C
A1
PHASE C3
PHASE D2
PHASE C4PHASE C2
FD101-A
A1
PHASE C5
ZONE 1F-1
INSPECTOR
TEST AND DRAIN
VALVE
ZONE 1F-4
INSPECTOR
TEST AND
DRAIN VALVE
ZONE 1F-3
INSPECTOR
TEST AND DRAIN
VALVE
ZONE 1F-2
INSPECTOR
TEST AND DRAIN
VALVE
ZONE 1F-4
PRE-ACTION VALVE
ZONE 1F-3
PRE-ACTION VALVE
ZONE 1F-2
PRE-ACTION VALVE
ZONE 1F-1
PRE-ACTION VALVE
FIELD FDC'S
FED FROM
BELOW
1F-1
1F-2
1F-3
1F-4
GROUND LEVEL
SUPPRESSION
ZONES
1. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
2. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.
3. CONTRACTOR SHALL PATCH AND REPAIR CEILINGS AS REQUIRED FOR REMOVAL
OR INSTALLATION OF ALL UTILITY MODIFICATIONS.
4. DEMOLISH EXISTING FIRE ALARM SYSTEM DEVICES IN PHASE AREAS DURING
PHASE PORTION OF WORK UNLESS NOTED OTHERWISE.
5. COORDINATE CLOSELY WITH FACILITY AND CONTRACTING OFFICES DESIGNATED
REPRESENTATIVE FOR DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES
OUTSIDE OF PHASED AREAS.
6. REPLACE SPRINKLERS IN AREAS OF WORK AS NOTED, RELOCATE, AND ADD
SPRINKLERS IN PHASED AREAS OF WORK AS NEEDED TO PROVIDE ADEQUATE
COVERAGE.
7. ALL EXISTING SPRINKLERS, ARM OVERS, AND BRANCH LINE PIPING LOCATED IN
PHASED AREAS SERVING GROUND LEVEL AREA A SHALL BE REMOVED BACK TO
THE BULK MAIN AND REPLACED DURING THE COORDINATED PHASE.
8. HALF TONE NOTES ARE PROVIDED FOR INFORMATION ONLY.
9. BOLD FIRE ALARM DEVICES AND SPRINKLERS INDICATE ALARM DEVICES OR
SPRINKLERS TO BE DEMOLISHED.
10. ALL EXISTING HEAT DETECTION SHALL REMAIN THROUGHOUT THE BUILDING.
HEAT DETECTION IS PART OF THE EXISTING PRE-ACTION SPRINKLER SYSTEM,
AND SHALL REMAIN.
11. DECOMISSION AND REMOVE EXISTING FIRE ALARM CONTROL PANELS AND
ANNUNCIATORS ONLY AFTER NEW FIRE ALARM/MNS IS COMPLETE AND
OPERATIONAL.
12. ALL EXISTING PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR
INFORMATION ONLY.
13. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ELEMENTS, INCLUDING
STAFFING AND COORDINATION WITH SITE FIRE MARSHALL AND FIRE DEPARTMENT
FOR FIRE WATCHED NEEDED DURING CONSTRUCTION.
DEMOLITION NOTES FIRE PROTECTION
N
TRUE
NORTH
EPROJECT NO.:
CONSTR. CONTR. NO.
DRAWING NO.
SCALE:
SHEET
D E
P A
R T
M E
N T
O F
T H
E A
IR
F
O R
C E
A F
M S
A H
E A
L T
H F
A C
IL
IT
IE
S
D
IV
IS
IO
N
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
P A
C
IF
IC
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
DES
SUBMITTAL DATE
DRW CHK
ACTIVITY
FOR COMMANDER AFCEC
APPROVED
D D
C
B
A
54321
A
C
1 2 3 4 5
B
DRAWFORM
REVISION:
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
IF SHEET MEASURES LESS THAN 594 X 841 mm. IT IS A
REDUCED SIZE PRINT. REDUCE SCALE ACCORDINGLY
A/E INFO
SEAL
FA8903-15-D-0004 TO: 18-F-0072
APPROVED BY
23 DECEMBER 2019
A C
KEY PLAN
B
L E
G A
C Y
P R
O J
E C
T
Q K
K A
O
P P
O R
T U
N
IT
Y
As indicated
/1
/2
:2 :1
P
M C
U se rs ew m cc ar th y\ D o cu m en ts
A u to d es k\ R ev it
P ro je ct s\
M A
B H
-F ir eP ro te ct io n ew m cc ar th y.
rv t
FD101
F
IR
E P
R O
T E
C T
IO
N
D E
M O
LI
T
IO
N
P
LA
N G
R O
U N
D L
E V
E L
O V
E R
A
LL
F Y
H
O S
P
IT
A L M
O D
E R
N
IZ
A T
IO
N
M
IS
A W
A A
IR
B
A S
E
J A
P A
N
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DLO EWM NSJ
8600 Indian Hills Drive
Omaha, NE 68114-4039
Tel 402.391.8111 Fax
402.391.8564
L A
D P ro je c t N o P ro je c t N u m b e r
SCALE:1 : 250
A2
FIRE PROTECTION DEMOLITION PLAN GROUND LEVEL OVERALL
2.5m
SCALE: 1:250
0 10m5m2.5m
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
ZONE 1F-4
PRE-ACTION VALVE
ZONE 1F-3
PRE-ACTION VALVE
ZONE 1F-2
PRE-ACTION VALVE
ZONE 1F-1
PRE-ACTION VALVE
FD04 FD04
FD04
FD04
LM
FD04
LMNPQ
PROSTHO LAB
UF29
CERAMICS LAB
UF30
LOUNGE
UF33
JANITOR
UF32
SUPPLY
UF31
M/LOCKER
UF34
F/LOCKER
UF38
VEST
NTG10
OFFICE
OFA01
LAB
DNPB1
DTR
DNTE1
DTR
DNTG1
PROSTHO
DNPL1
OFFICE
OFA01
CORR
NTG02
DTR
DNTG1
DTR
DNTG1
DTR
DNTG1
DTR
DNTG1
DTR
DNTG1
DTR
DNTG1
DTR
DNTG1
DTR
DNTG1
STOR
DNSC6
DTR
DNTS1
DTR
DNTS1
OFFICE
OFA01
ELEC
NTG05
S-TLT
TLTU1
OFFICE
OFA01
CORR
NTG02CORR
NTG02
EQIP
DNSS1
CORR
NTG02
JAN
UF37
OFFICE
OFA01
DTR
DNTG1
DTR
DNTG1
DTR
DNTG1
DTR
DNTE1
STOR
SRS01
ELEC
NTG05
DIPC
DNSC2
SUPPLY
DNSC3
CORR
NTG02
DENTAL
CONFERENCE
DNTC1
VEST
UE12
OFFICE
UE07
OFFICE
UE06
OFFICE
UE05
OFFICE
UE08
M/TLT
TLTM1
F/TLT
TLTF1
RECEPT RECORDS
RECP2
CORR
NTG02
WAITING
WRC01
WAITING
WRC01
OFFICE
OFA01
DTR
DNTG1
DTR
DNTG1
DTR
DNTG1
DTR
DNTG1
WORKROOM
NTG10
X-RAY
DNXD1
X-RAY
DNXD1
DTR
DNTG1
DTR
DNTG1
CORR
NTG02
CORR
NTG02DTR
DNTG1
STOR
DNTG1
STOR
SRGC2
STOR
SRHM1
COMM
COMC1
OFFICE
OFA01
DTR
DNTG1
SUPPLY
SRS02 OFFICE
OFA01
OFFICE
OFA01
SUPPLY
LCCL1
ELEC
NTG05
MECH
UF41
PHASE C2
PHASE LEGEND
PHASE C3
PHASE C4
PHASE C5
TEMPORARY
MENS LOCKER
TEMPORARY
STAFF LOUNGE
TEMPORARY TEAM
WORKROOM
TEMPORARY
CENTRAL SUPPLY
EXISTING SMOKE DETECTOR TO BE REMOVED
DEMOLITION LEGEND FIRE
PROTECTION
EXISTING SMOKE DETECTOR TO REMAIN
EXISTING SPRINKLER TO BE REMOVED
EXISTING SPRINKLER TO REMAIN
FACP EXISTING FIRE ALARM CONTROL PANEL TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMAIN
1. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
2. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.
3. CONTRACTOR SHALL PATCH AND REPAIR CEILINGS AS REQUIRED FOR REMOVAL
OR INSTALLATION OF ALL UTILITY MODIFICATIONS.
4. DEMOLISH EXISTING FIRE ALARM SYSTEM DEVICES IN PHASE AREAS DURING
PHASE PORTION OF WORK UNLESS NOTED OTHERWISE.
5. COORDINATE CLOSELY WITH FACILITY AND CONTRACTING OFFICES DESIGNATED
REPRESENTATIVE FOR DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES
OUTSIDE OF PHASED AREAS.
6. REPLACE SPRINKLERS IN AREAS OF WORK AS NOTED, RELOCATE, AND ADD
SPRINKLERS IN PHASED AREAS OF WORK AS NEEDED TO PROVIDE ADEQUATE
COVERAGE.
7. ALL EXISTING SPRINKLERS, ARM OVERS, AND BRANCH LINE PIPING LOCATED IN
PHASED AREAS SERVING GROUND LEVEL AREA A SHALL BE REMOVED BACK TO
THE BULK MAIN AND REPLACED DURING THE COORDINATED PHASE.
8. HALF TONE NOTES ARE PROVIDED FOR INFORMATION ONLY.
9. BOLD FIRE ALARM DEVICES AND SPRINKLERS INDICATE ALARM DEVICES OR
SPRINKLERS TO BE DEMOLISHED.
10. ALL EXISTING HEAT DETECTION SHALL REMAIN THROUGHOUT THE BUILDING.
HEAT DETECTION IS PART OF THE EXISTING PRE-ACTION SPRINKLER SYSTEM,
AND SHALL REMAIN.
11. DECOMISSION AND REMOVE EXISTING FIRE ALARM CONTROL PANELS AND
ANNUNCIATORS ONLY AFTER NEW FIRE ALARM/MNS IS COMPLETE AND
OPERATIONAL.
12. ALL EXISTING PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR
INFORMATION ONLY.
13. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ELEMENTS, INCLUDING
STAFFING AND COORDINATION WITH SITE FIRE MARSHALL AND FIRE DEPARTMENT
FOR FIRE WATCHED NEEDED DURING CONSTRUCTION.
DEMOLITION NOTES FIRE PROTECTION
N
TRUE
NORTH
EPROJECT NO.:
CONSTR. CONTR. NO.
DRAWING NO.
SCALE:
SHEET
D E
P A
R T
M E
N T
O F
T H
E A
IR
F
O R
C E
A F
M S
A H
E A
L T
H F
A C
IL
IT
IE
S
D
IV
IS
IO
N
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
P A
C
IF
IC
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
DES
SUBMITTAL DATE
DRW CHK
ACTIVITY
FOR COMMANDER AFCEC
APPROVED
D D
C
B
A
54321
A
C
1 2 3 4 5
B
DRAWFORM
REVISION:
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
IF SHEET MEASURES LESS THAN 594 X 841 mm. IT IS A
REDUCED SIZE PRINT. REDUCE SCALE ACCORDINGLY
A/E INFO
SEAL
FA8903-15-D-0004 TO: 18-F-0072
APPROVED BY
23 DECEMBER 2019
A C
KEY PLAN
B
L E
G A
C Y
P R
O J
E C
T
Q K
K A
O
P P
O R
T U
N
IT
Y
As indicated
/1
/2
:2 :3
P
M C
U se rs ew m cc ar th y\ D o cu m en ts
A u to d es k\ R ev it
P ro je ct s\
M A
B H
-F ir eP ro te ct io n ew m cc ar th y.
rv t
FD101-A
F
IR
E P
R O
T E
C T
IO
N
D E
M O
LI
T
IO
N
P
LA
N G
R O
U N
D L
E V
E L
A
R E
A A
F Y
H
O S
P
IT
A L M
O D
E R
N
IZ
A T
IO
N
M
IS
A W
A A
IR
B
A S
E
J A
P A
N
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DLO EWM NSJ
8600 Indian Hills Drive
Omaha, NE 68114-4039
Tel 402.391.8111 Fax
402.391.8564
L A
D P ro je c t N o P ro je c t N u m b e r
SCALE: 1 : 100
B4
FIRE PROTECTION DEMOLITION PLAN GROUND LEVEL - AREA A - PHASE C5
KEYNOTE LEGEND
KEY DESCRIPTION
FD04 EXISTING BULK MAIN TO REMAIN.
NOTE:
REMOVE ALL SMOKE DETECTION DEVICES. REMOVE EXISTING SPRINKLERS DROPS, ARM
OVERS AND BRANCH LINES BACK TO EXISTING MAIN DURING THE CORRESPONDING PHASE.
TIMING OF WORK SHALL BE AT THE GENERAL CONTRACTOR'S DISCRETION WITH
COORDINATION WITH THE FACILITY AND USERS. EXISTING FIRE ALARM CONTROL
PANELS/REMOTE ANNUNCIATORS IN AREA TO REMAIN AS FUNCTIONAL AS POSSIBLE UNTIL
THE ENTIRE NEW FIRE ALARM CONTROL PANELS/REMOTE ANNUNCIATORS IN EACH AREA IS
LOCATED AND IS READY TO BE MADE ACTIVE. AT THIS POINT THE EXISTING DEVICES MAY
BE DECOMISSIONED AND REMOVED. ALL EXISTING HEAT DETECTION DEVICES ARE TO
REMAIN. HEAT DETECTION DEVICES EXIST AS PART OF THE PRE-ACTION FIRE
SUPPRESSION SYSTEM AND SHALL REMAIN FULLY FUNCTIONAL. ALL PRE-ACTION VALVES
ARE TO REMAIN AND ARE LABELED FOR INFORMATION ONLY.
SCALE: 1 : 100
A1
FIRE PROTECTION DEMOLITION PLAN GROUND LEVEL - AREA A
DEMOLITION WITHIN THE BOUNDARY
DURING PHASE C5. SEE B4/FD101-A
1m
SCALE: 1:100
0 4m2m1m
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
EFGHJKL
VEST
UCC4
STAIR
STAIR B
VEST
UBC2
ULTRA SND
UB33
EXAM
UB36
ELEC
UB35
OFFICE
UB37
OFFICE
UB38
EXAM
UB39
STAIR
STAIR C OFFICE
UB41
TLT
UB42
WAITING
UB21
OFFICE
UB23 OFFICE
UB15
OFFICE
UB14
OFFICE
UB24
RECEPT
UB18
EXAM
UB13
EXAM
UB25
OFFICE
UB28
PROCEDURE
UB32
EXAM
UB26
OFFICE
UB09
EXAM
UB27
STORAGE
UB31
STORAGE
UB30
JAN
UB29
SUPPLY
UB07
S. UTILITY
UB08
CORR
UBC5
CORR
UBC5
CORR
UBC6
CORR
UBC4
TLT
UB06
OFFICE
UB05
OFFICE
UB04
OFFICE
UB03
OFFICE
UB02
CORR
UBC1
EXAM
UB11
EXAM
UB12
EXAM
UA46
ELEC
UA47
ELEC
UB10
EXAM
UA45
EXAM
UA44
EXAM
UA43
BREAST FEEDING
UA42
CORR
UBC3
OFFICE
UB01
TREATMENT
UA32
OFFICE
UA31
LOUNGE
UA04
ALCOVE
UA33
EXAM
UA34
EXAM
UA35
EXAM
UA36
EXAM
UA37
PUB HEALTH
ASSESMENT OFF
UA38
OFFICE
UA28
EXAM
UA27
EXAM
UA26
EXAM
UA25
EXAM
UA24
JAN
UA23
JAN
UA22
CORR
UAC4
SUPPLY
UA20
OFFICE
UA19
OFFICE
UA18
EXAM
UA17
OFFICE
UA16
EXAM
UA09
EXAM
UA08
EXAM
UA07
OFFICE
UA06
OFFICE
UA10
CORR
UAC3
CORR
UAC1
CORR
UAC2
ALCOVE
UA21
TREATMENT
UA02 S/UTIL
UA04
STAIR
STAIR A
C/UTL
UA03
VEST
UCC4
WAITING
UB21
OFFICE
UA28
VEST
UCC4A
VEST
UD35
ELEV
LOBB
UB43
WAIT
UB45
ELEC
UB44
COFFEE
UB46
TLT
UB20
TLT
UB19
SCREENING
UB16A
IMMUNIZATION
UB16
CORR
UBC3
WAITING
UA41
WAITING
UB17
FAMILY PRACTICE
CHK-IN
UA29
CORR
UAC4
TLT
UA15
WAITING
UA14
OFFICE
UA13
EXAM
UA12
EXAM
UA11
CORR
UAC3
CORR
UDC1
CORR
UBC3
CORR
UAC4
CORR
UAC3
EXISTING SMOKE DETECTOR TO BE REMOVED
DEMOLITION LEGEND FIRE
PROTECTION
EXISTING SMOKE DETECTOR TO REMAIN
EXISTING SPRINKLER TO BE REMOVED
EXISTING SPRINKLER TO REMAIN
FACP EXISTING FIRE ALARM CONTROL PANEL TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMAIN
1. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
2. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.
3. CONTRACTOR SHALL PATCH AND REPAIR CEILINGS AS REQUIRED FOR REMOVAL
OR INSTALLATION OF ALL UTILITY MODIFICATIONS.
4. DEMOLISH EXISTING FIRE ALARM SYSTEM DEVICES IN PHASE AREAS DURING
PHASE PORTION OF WORK UNLESS NOTED OTHERWISE.
5. COORDINATE CLOSELY WITH FACILITY AND CONTRACTING OFFICES DESIGNATED
REPRESENTATIVE FOR DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES
OUTSIDE OF PHASED AREAS.
6. REPLACE SPRINKLERS IN AREAS OF WORK AS NOTED, RELOCATE, AND ADD
SPRINKLERS IN PHASED AREAS OF WORK AS NEEDED TO PROVIDE ADEQUATE
COVERAGE.
7. ALL EXISTING SPRINKLERS, ARM OVERS, AND BRANCH LINE PIPING LOCATED IN
PHASED AREAS SERVING GROUND LEVEL AREA A SHALL BE REMOVED BACK TO
THE BULK MAIN AND REPLACED DURING THE COORDINATED PHASE.
8. HALF TONE NOTES ARE PROVIDED FOR INFORMATION ONLY.
9. BOLD FIRE ALARM DEVICES AND SPRINKLERS INDICATE ALARM DEVICES OR
SPRINKLERS TO BE DEMOLISHED.
10. ALL EXISTING HEAT DETECTION SHALL REMAIN THROUGHOUT THE BUILDING.
HEAT DETECTION IS PART OF THE EXISTING PRE-ACTION SPRINKLER SYSTEM,
AND SHALL REMAIN.
11. DECOMISSION AND REMOVE EXISTING FIRE ALARM CONTROL PANELS AND
ANNUNCIATORS ONLY AFTER NEW FIRE ALARM/MNS IS COMPLETE AND
OPERATIONAL.
12. ALL EXISTING PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR
INFORMATION ONLY.
13. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ELEMENTS, INCLUDING
STAFFING AND COORDINATION WITH SITE FIRE MARSHALL AND FIRE DEPARTMENT
FOR FIRE WATCHED NEEDED DURING CONSTRUCTION.
DEMOLITION NOTES FIRE PROTECTION
N
TRUE
NORTH
EPROJECT NO.:
CONSTR. CONTR. NO.
DRAWING NO.
SCALE:
SHEET
D E
P A
R T
M E
N T
O F
T H
E A
IR
F
O R
C E
A F
M S
A H
E A
L T
H F
A C
IL
IT
IE
S
D
IV
IS
IO
N
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
P A
C
IF
IC
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
DES
SUBMITTAL DATE
DRW CHK
ACTIVITY
FOR COMMANDER AFCEC
APPROVED
D D
C
B
A
54321
A
C
1 2 3 4 5
B
DRAWFORM
REVISION:
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
IF SHEET MEASURES LESS THAN 594 X 841 mm. IT IS A
REDUCED SIZE PRINT. REDUCE SCALE ACCORDINGLY
A/E INFO
SEAL
FA8903-15-D-0004 TO: 18-F-0072
APPROVED BY
23 DECEMBER 2019
A C
KEY PLAN
B
L E
G A
C Y
P R
O J
E C
T
Q K
K A
O
P P
O R
T U
N
IT
Y
As indicated
/1
/2
:2 :4
P
M C
U se rs ew m cc ar th y\ D o cu m en ts
A u to d es k\ R ev it
P ro je ct s\
M A
B H
-F ir eP ro te ct io n ew m cc ar th y.
rv t
FD101-B
F
IR
E P
R O
T E
C T
IO
N
D E
M O
LI
T
IO
N
P
LA
N G
R O
U N
D L
E V
E L
A
R E
A B
F Y
H
O S
P
IT
A L M
O D
E R
N
IZ
A T
IO
N
M
IS
A W
A A
IR
B
A S
E
J A
P A
N
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DLO EWM NSJ
8600 Indian Hills Drive
Omaha, NE 68114-4039
Tel 402.391.8111 Fax
402.391.8564
L A
D P ro je c t N o P ro je c t N u m b e r
SCALE: 1 : 100
A1
FIRE PROTECTION DEMOLITION PLAN GROUND LEVEL - AREA B
NOTE:
ALL EXISTING CONDITIONS SHALL BE VERIFIED IN FIELD. REMOVE ALL SMOKE DETECTION
DEVICES. THIS AREA IS OUTSIDE OF PHASED WORK. TIMING OF WORK SHALL BE AT THE
GENERAL CONTRACTOR'S DISCRETION WITH COORDINATION WITH THE FACILITY AND
USERS. EXISTING FIRE ALARM CONTROL PANELS/REMOTE ANNUNCIATORS IN AREA TO
REMAIN AS FUNCTIONAL AS POSSIBLE UNTIL THE ENTIRE NEW FIRE ALARM CONTROL
PANELS/REMOTE ANNUNCIATORS IN EACH AREA IS LOCATED AND IS READY TO BE MADE
ACTIVE. AT THIS POINT THE EXISTING DEVICES MAY BE DECOMISSIONED AND REMOVED.
ALL EXISTING HEAT DETECTION DEVICES ARE TO REMAIN. HEAT DETECTION DEVICES ARE A
PART OF THE EXISTING PRE-ACTION FIRE SUPPRESSION SYSTEM AND SHALL REMAIN FULLY
FUNCTIONAL.
1m
SCALE: 1:100
0 4m2m1m
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
EFGHJKL
OFF FLT CC
OFA04
CORR
EXISTING
ANNUNCIATOR PANEL
DENTAL OFF,
SHARED
OFA05
COMPUTER
UC22
CONFERENCE
UC16
STORAGE
UC18A
CLASSROOM
UC18
DISTRO
UC19
OFFICE
UC20
OFFICE
UC24
M/TLT
UC21
F/TLT
UC12
SUPPLY
UC13
OFFICE
UC14
OFFICE
UC15
M/TLT
UC03
OFFICE
UC23
ELEV
CORR
UC34
CORR
UCC3
STORAGE
UC11
OFFICE
UC31
OFFICE
UC32
OFFICE
UC30
OFFICE
UC29
OFFICE
UC25
OFFICE
UC28
OFFICE
UC27
OFFICE
UC26
ELEC
UC33
TLT
UD32
CLOS
UD33
CONFERENCE
UD34
OFFICE
UD31
OFFICE
UD29
OFFICE
UD30
OFFICE
UC10
PHARMACY
UC07
OFFICE
UC09
VAULT
UC08
STAIR
STAIR D
OFFICE
UD25
OFFICE
UD24
OFFICE
UD23
OFFICE
UD27
OFFICE
UD26
OFFICE
UD28
F/TLT
UC02
CORR
UCC2
CORR
UDC4
ELEC
UD16
JAN
UD11
TLT
UD10
OFFICE
UD06
OFFICE
UD05
RECORDS
UE09
OFFICE
UD15
STAIR
STAIR E
OFFICE
UD04
OFFICE
UD03
OFFICE
UD08
CONFERENCE
UD07
CORR
UDC2
OFFICE
UD14
OFFICE
UD13
CORR
UDC3
ELEV
CORR
UDC5
WAITING
UC06
JAN
UC05
JAN
UC04
OFFICE
UD18
CORR
OFFICE
UD12
RECEPTION
UD02
WAITING
UD01
VEST
UC03A
VEST
UC02A
VEST
UD35
WAIT
UB45COFFEE
UB46
TLT
UB19
OFFICE
UA13
CORR
UDC1
OFFICE
UD22
OFFICE
OFA01
FD08
FD04
VEST
UCC4
RECORDS
UD21
AREA OF WORK
HATCH LEGEND
EXISTING SMOKE DETECTOR TO BE REMOVED
DEMOLITION LEGEND FIRE
PROTECTION
EXISTING SMOKE DETECTOR TO REMAIN
EXISTING SPRINKLER TO BE REMOVED
EXISTING SPRINKLER TO REMAIN
FACP EXISTING FIRE ALARM CONTROL PANEL TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMOVED
EXISTING UPRIGHT SPRINKLER TO BE REMAIN
1. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
2. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO STARTING WORK.
3. CONTRACTOR SHALL PATCH AND REPAIR CEILINGS AS REQUIRED FOR REMOVAL
OR INSTALLATION OF ALL UTILITY MODIFICATIONS.
4. DEMOLISH EXISTING FIRE ALARM SYSTEM DEVICES IN PHASE AREAS DURING
PHASE PORTION OF WORK UNLESS NOTED OTHERWISE.
5. COORDINATE CLOSELY WITH FACILITY AND CONTRACTING OFFICES DESIGNATED
REPRESENTATIVE FOR DEMOLITION OF EXISTING FIRE ALARM SYSTEM DEVICES
OUTSIDE OF PHASED AREAS.
6. REPLACE SPRINKLERS IN AREAS OF WORK AS NOTED, RELOCATE, AND ADD
SPRINKLERS IN PHASED AREAS OF WORK AS NEEDED TO PROVIDE ADEQUATE
COVERAGE.
7. ALL EXISTING SPRINKLERS, ARM OVERS, AND BRANCH LINE PIPING LOCATED IN
PHASED AREAS SERVING GROUND LEVEL AREA A SHALL BE REMOVED BACK TO
THE BULK MAIN AND REPLACED DURING THE COORDINATED PHASE.
8. HALF TONE NOTES ARE PROVIDED FOR INFORMATION ONLY.
9. BOLD FIRE ALARM DEVICES AND SPRINKLERS INDICATE ALARM DEVICES OR
SPRINKLERS TO BE DEMOLISHED.
10. ALL EXISTING HEAT DETECTION SHALL REMAIN THROUGHOUT THE BUILDING.
HEAT DETECTION IS PART OF THE EXISTING PRE-ACTION SPRINKLER SYSTEM,
AND SHALL REMAIN.
11. DECOMISSION AND REMOVE EXISTING FIRE ALARM CONTROL PANELS AND
ANNUNCIATORS ONLY AFTER NEW FIRE ALARM/MNS IS COMPLETE AND
OPERATIONAL.
12. ALL EXISTING PRE-ACTION VALVES ARE TO REMAIN AND ARE LABELED FOR
INFORMATION ONLY.
13. GENERAL CONTRACTOR SHALL PROVIDE ALL NECESSARY ELEMENTS, INCLUDING
STAFFING AND COORDINATION WITH SITE FIRE MARSHALL AND FIRE DEPARTMENT
FOR FIRE WATCHED NEEDED DURING CONSTRUCTION.
DEMOLITION NOTES FIRE PROTECTION
N
TRUE
NORTH
EPROJECT NO.:
CONSTR. CONTR. NO.
DRAWING NO.
SCALE:
SHEET
D E
P A
R T
M E
N T
O F
T H
E A
IR
F
O R
C E
A F
M S
A H
E A
L T
H F
A C
IL
IT
IE
S
D
IV
IS
IO
N
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
P A
C
IF
IC
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R C
E N
T E
R
DES
SUBMITTAL DATE
DRW CHK
ACTIVITY
FOR COMMANDER AFCEC
APPROVED
D D
C
B
A
54321
A
C
1 2 3 4 5
B
DRAWFORM
REVISION:
P L A N N I N G
A R C H I T E C T U R E
E N G I N E E R I N G
I N T E R I O R S
EST. 1915
IF SHEET MEASURES LESS THAN 594 X 841 mm. IT IS A
REDUCED SIZE PRINT. REDUCE SCALE ACCORDINGLY
A/E INFO
SEAL
FA8903-15-D-0004 TO: 18-F-0072
APPROVED BY
23 DECEMBER 2019
A C
KEY PLAN
B
L E
G A
C Y
P R
O J
E C
T
Q K
K A
O
P P
O R
T U
N
IT
Y
As indicated
/1
/2
:2 :4
P
M C
U se rs ew m cc ar th y\ D o cu m en ts
A u to d es k\ R ev it
P ro je ct s\
M A
B H
-F ir eP ro te ct io n ew m cc ar th y.
rv t
FD101-C
F
IR
E P
R O
T E
C T
IO
N
D E
M O
LI
T
IO
N
P
LA
N G
R O
U N
D L
E V
E L
A
R E
A C
F Y
H
O S
P
IT
A L M
O D
E R
N
IZ
A T
IO
N
M
IS
A W
A A
IR
B
A S
E
J A
P A
N
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
DLO EWM NSJ
8600 Indian Hills Drive
Omaha, NE 68114-4039
Tel 402.391.8111 Fax
402.391.8564
L A
D P ro je c t N o P ro je c t N u m b e r
SCALE: 1 : 100
A1
FIRE PROTECTION DEMOLITION PLAN GROUND LEVEL - AREA C
KEYNOTE LEGEND
KEY DESCRIPTION
FD04 EXISTING BULK MAIN TO REMAIN.
FD08 EXISTING FIRE ALARM CONTROL PANEL/REMOTE ANNUNCIATOR PANEL TO REMAIN
AS FUNCTIONAL AS POSSIBLE UNTIL THE ENTIRE NEW FIRE ALARM CONTROL
PANEL/REMOTE ANNUNCIATOR PANEL IN EACH AREA IS LOCATED AND IS READY TO
BE MADE ACTIVE. AT THIS POINT THE EXISTING PANELS SHALL BE DECOMMISSIONED
AND REMOVED.
NOTE:
ALL EXISTING CONDITIONS SHALL BE VERIFIED IN FIELD. REMOVE ALL SMOKE
DETECTION DEVICES. TIMING OF WORK SHALL BE AT THE GENERAL
CONTRACTOR'S DISCRETION WITH COORDINATION WITH THE FACILITY AND USERS.
ALL EXISTING HEAT DETECTION DEVICES IN THIS AREA IN ITS ENTIRETY ARE TO
REMAIN. HEAT DETECTION DEVICES EXIST AS PART OF THE PRE-ACTION FIRE
SUPPRESSION SYSTEM AND SHALL REMAIN FULLY FUNCTIONAL.
PHASE D2 AREA OF WORK:
DEMO SPRINKLERS, DROPS AND
ARM OVERS. DEMO BRANCH LINES
AS NEEDED.
1m
SCALE: 1:100
0 4m2m1m
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
FIRE ALARM/MNS SYMBOLS
SYMBOL DESCRIPTION
NEW WALL MOUNTED SPEAKER/STROBE
NEW WALL MOUNTED STROBE
EXISTING FIRE ALARM CONTROL PANEL
EXISTING FIRE ALARM ANNUNCIATOR
EXISTING SMOKE DETECTOR
FACP
ANN
NEW FIRE ALARM/MNS ANNUNCIATOR PANEL
NEW WALL MOUNTED SPEAKER
NEW CEILING MOUNTED SPEAKER
NEW CEILING MOUNTED STROBE
NEW CEILING MOUNTED SPEAKER/STROBE
S
NEW FIRE ALARM CONTROL PANELFACP
ANN
S
NEW WALL MOUNTED SPEAKER/STROBE INSTALLED DURING A PREVIOUS PHASE
NEW WALL MOUNTED SPEAKER INSTALLED DURING A PREVIOUS PHASE
NEW CEILING MOUNTED SPEAKER INSTALLED DURING A PREVIOUS PHASE
NEW CEILING MOUNTED STROBE INSTALLED DURING A PREVIOUS PHASE
NEW CEILING MOUNTED SPEAKER/STROBE INSTALLED DURING A PREVIOUS PHASE
EXISTING PRESSURE SWITCH
NEW DUCT SMOKE DETECTOR
EXISTING IN-LINE HEAT DETECTORC°
F D
PS
1. PROVIDE AND INSTALL A NEW, REPLACEMENT FIRE ALARM SYSTEM THROUGHOUT
THE BUILDING PER THE UFC AND NFPA 72. REFER TO SPEC SECTION 28 31 76
INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM. REPLACEMENT FIRE
ALARM SYSTEM WILL BE ZONED TO MATCH EXISTING ZONES.
2. FIRE ALARM SYSTEM SHALL…