This document is a federal contract opportunity (RFQ) for the purchase, delivery, and installation of sixteen seismic-compliant IT cabinet racks in two hot aisle containment (HAC) configurations. Each HAC will have two rows of four cabinets. The racks must be fitted with various hardware components, including brush grommet rail kits, copper bus bars, vertical cable bar kits, blanking/filler panels, remote power distribution units (rPDUs), rPDU bracket sets, ganging kits, and temperature sensors. The requirement also includes hot aisle containment doors, biometric door locks, LED lighting strips, thermal breakaway curtains, a main control server, new floor tiles, and adjustable floor vents. Pre- and post-installation airflow, temperature, and power measurements are required. The contract is being issued by the Department of the Air Force Space Command, and all questions are due by September 17, 2024.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Question Answered.docx | DOCX document | |
| DCG_Combo.pdf | ||
| Attachment 2 Statement of Work .pdf | ||
| Attachment 5 SSFB IFS .pdf | ||
| Attachment 8 Drawing.pdf | ||
| Attachment 4 Parts List.pdf | ||
| Attachment 6 HVAC Study.pdf | ||
| Attachment 7 Seven (7) Tile Pitch.pdf | ||
| Attachment 1 Clauses and Provisions.pdf | ||
| Attachment 3-Quote Worksheet.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Line Item Type Quantity Item Description
Rack
Hardware 16 IT Cabinet Rack
Dimensions: 91 inches (Height) x 30 inches (Width) x 42 inches (Depth) Rack Mount Units (RMU): 48 Usable Depth: 40 inches Maximum Rail Spacing: 35 inches Weight Capacity: 3300 lbs Color: Black
Includes Frame with levelers (2.5 inches Height; not installed unless specified at time of order) Two pairs of PDU (Power Distribution Unit) brackets Mesh Contour Front Door Mesh Contour Rear Door Solid Side Panels (2) Mounting Rails: 3/8-inch square (M6) with Rack Mount Hardware Solid Top Panel UL2416 certification
Rack
Hardware 16 Brush Grommet Rail Kit Extends From Rail to Side Panel to Prevent Air Recirculation, Use with 91″H X 30″W Cabinets
Rack
Hardware 16 Copper Bus Bar 76″L, Isolated, Use with 91 and 98″H Cabinets, Mounts along the ront Mounting Panel of cabinets and racks
Rack
Hardware 16 Vertical Cable Bar Kit Includes 75″H X 4″W VCB (Qty 1), 29.5″H X 4″W HCB (Qty 2), 12″L Cinch Straps (Qty 6), Accepts Optional “D” Rings (CM-25 or CM-26), Use with 91″H Cabinets
Rack
Hardware 160 Blanking/Filler Panels 19″ Mounting, 1 Rack Mount Unit, Black Panels
Rack
Hardware 80 Blanking/Filler Panels 19″ Mounting, 2 Rack Mount Unit, Black Panels
Rack
Hardware 16 PDU Bracket Sets Sets of Two Power Distribution Unit (PDU) Brackets with 2 Mounting Positions, Angled; Vertical Mounting of PDU, Installs in Rear Cabinet Corner, Use with 30/32″W X 42″D Cabinets
Rack
Hardware 16 Ganging Kit Ganging Kit for Cabinets
Rack
Hardware 16 rPDU (Power Distribution Unit)
Outlet-Level Switched rPDU with Environmental Monitoring Power Cord: A 10-foot (3-meter) power cord with an L5-20P plug Outlets: At least 24 NEMA 5-20R outlets Color: Black powder coat finish
Key Features:
- Has multiple addressable temperature probe ports
- Outlet-Level Control: Remotely switch outlets on/off for specific devices
- Power Monitoring: Monitor input and outlet power usage down to the device level
- Environmental Metrics: Optional sensors provide real-time data on temperature, humidity, and other environmental factors
- Daisy Chaining: Connect up to 40 rPDUs in a fault-tolerant daisy chain using RSTP (Rapid Spanning Tree Protocol)
Specifications:
- Power Configuration: Choose from 16A or 20A, 120V, 208V, or 230V
- Outlets: 12 combination C13/C19 outlets
- Monitoring:
- Input and outlet power monitoring
- Environmental monitoring via optional sensors
- Local LED display
- Receptacle: Combination C13/C19
Rack
Hardware 32 Temperature Sensors Temperature sensor used to monitor temperature (degrees F) in data center airflows. Includes a 12ft (3.66m) cable. Is compatible with the rPDUs
Rack
Hardware 4 Hot Aisle Containment Doors
Number of Doors Needed: 4 (one on each end of a hot aisle)
Total Hot Aisle Width: 36"
Height: 91" (231.14 cm)
Material and Features:
Durable, high-quality materials suitable for data center environments.
Clear or opaque door panels (please specify options and costs).
Options for either sliding or swinging door mechanisms.
Efficient sealing to prevent air leakage and maintain effective containment.
Compatibility with existing cabinets and containment systems.
Optional integration with fire suppression systems.
Ease of access for personnel and equipment.
Can be integrated with biometrics security lock.
Additional Requirements:
Installation services (if available, please specify cost).
Lead time for manufacturing and delivery.
Warranty information.
Maintenance and support options.
Misc
Hardware 1 Inline LEDs with Motion Sensor
White (5.7K) LEDs with motion sensor designed to detect movement and control the lighting system by switching the lights on or off based on occupancy. The LEDs and in-line sensor should plug into the rPDU, making it ideal for energy-saving and permit visibility inside the hot asile(s).
Key Specifications:
Detection Technology: Passive Infrared (PIR) Sensing Range:
Distance: Up to 20 feet (6 meters) adjustable range Angle: 120° to 180° field of view Response Time: < 1 second Power Supply:
Voltage: 120V AC Frequency: 50/60 Hz Current Consumption: Typically < 50 mA Output:
Type: Relay output, normally open (NO) Operating Temperature: -20°C to 50°C (-4°F to 122°F) Humidity Range: 0% to 95% non-condensing Features:
Adjustable Sensitivity: Allows for customization of detection range and responsiveness.
Time Delay Adjustment: Configurable delay time (1 second to 10 minutes) for maintaining the light on after motion is no longer detected.
Compact Design: Small form factor for easy integration into existing lighting circuits.
Mounting Options: Surface mount with screws or adhesive, flush mount for seamless integration.
Override Function: Manual override option to keep lights on or off regardless of motion detection.
Installation:
Wiring: Standard 3-prong plug for rPDU Setup: Adjust sensitivity and time delay settings using onboard controls Compliance and Certifications:
Standards: UL, CE, RoHS, FCC (depending on the model and manufacturer) Warranty: Minimum 1-year manufacturer warranty
Misc
Hardware 140 Floor Tiles
Purchase and install anti-static raised floor tiles. These tiles will be made from steel, with a load-bearing capacity of 250 lbs per square foot, and have anti-static properties to prevent electrostatic discharge. They create an underfloor plenum space for efficient cooling and organized cable management. Install new floor tiles directly inside, under, and surrounding the two new HACs (excluding where floor vents shall be placed). See reference floor diagram.
Misc
Hardware 12 Floor Vents
Adjustability:
Vents should indicate specific air delivery volume so they can be set and adjusted based on unique rack load.
The vents must be adjustable to direct airflow in specific directions.
Provide a mechanism (e.g., louvers, dampers) for fine-tuning the vent angle.
Ensure smooth and reliable adjustment without compromising structural integrity.
Materials and Construction:
Construct vents from durable, non-corrosive materials (e.g., aluminum, stainless steel).
Consider fire-resistant coatings or materials to enhance safety.
Reinforce structural components to withstand foot traffic and equipment loads.
Mounting and Integration:
Vents should fit seamlessly into raised access floor tiles.
Ensure compatibility with standard floor tile dimensions (e.g., 24" x 24" or 60 cm x 60 cm).
Provide secure attachment mechanisms (e.g., locking clips) to prevent accidental displacement.
Airflow Control:
Design vents to allow variable airflow rates.
Include features for partial or full closure when needed.
Consider aerodynamic design to minimize turbulence and pressure drop.
Maintenance and Accessibility:
Ensure easy access for cleaning and maintenance.
Design vents to be removable without disrupting adjacent tiles.
Provide clear instructions for maintenance procedures.
Safety Features:
Include safety guards or grilles to prevent accidental contact with moving parts.
Consider tamper-resistant features to prevent unauthorized adjustments.
Testing and Validation:
Conduct airflow simulations to verify directional control.
Test adjustability and stability under load conditions.
Validate compatibility with existing floor systems.
Misc
Hardware 6 Ceiling Vents
Quality aluminum 24" x 24" fixed-bar air grille White powder coat finish Drop-ceiling compatible
Misc
Hardware 16 Break Away Curtains
Curtain Material:
PVC-coated polyester or similar fire-resistant material.
Curtain Configuration:
Curtains to span the full height between racks.
Aluminum track system for installation.
Mounting and Attachment:
Hooks or clips for securing curtains to the track.
Ensure snug fit to prevent air leakage.
Overlap and Sealing:
Magnetic strips or Velcro for tight seal along edges.
Overlap adjacent curtains by at least 6 inches.
Breakaway Feature:
Breakaway design that detach without falling to the floor.
Utilize breakaway connectors or clips.
Access Points:
Include zippered openings for maintenance access.
Proper sealing for containment.
Misc
Hardware 1 Air Capture Hood
The hood should be suitable for measuring air volume at diffusers and grilles.
It’s essential for HVAC commissioning, troubleshooting, and testing and balancing in data centers.
Features:
Lightweight and ergonomic design for easy one-person operation.
Automatic flow sensing and display for efficiency.
Back pressure compensation ensures accurate readings.
Various hood sizes available for versatility.
Detachable digital micromanometer for flexibility.
Included Items:
Air capture hood/frame/base (size as needed for 24" tiles) Detachable micromanometer Flow conditioner Batteries AC adapter Pitot probe Static pressure probes Tubing Carrying case Calibration certification Downloading software and interface cable
18 Desktop 1 Computer
Operating System:
Windows 11 or later for desktop clients.
Modern web browsers for accessing the web-based interfaces (e.g., Chrome, Firefox, Edge).
Memory:
At least 4 GB RAM (more may be needed for intensive tasks).
Processor:
Modern multi-core processor (e.g., Intel i7 or AMD Ryzen).
Network:
Stable internet connection for accessing the software and any remote features.
19 Desktop 2 Monitors
34" curved monitor w/ stand Resolution: WQHD 3440 x 1440 Refresh rate: 60 Hz minimum Ports: 2x HDMI (HDCP 2.0); 1x Display Port
20 Network 6 Room Temperature Probes 6 realtime networked temperature probes (Need compatibility with Smart Power Strip)
21 Network 1 Network switch
Port Density and Type:
A managed switch with sufficient ports (e.g., 48 ports) to accommodate power meters and temperature probes.
A mix of Gigabit Ethernet (1 Gbps) and higher-speed ports (e.g., 10 Gbps or 40 Gbps) for scalability.
Power over Ethernet (PoE) Support:
PoE-enabled switch ports to power connected devices (such as power meters) via the Ethernet cable.
Verify compatibility with IEEE 802.3af/at standards for PoE delivery.
Quality of Service (QoS):
Prioritize traffic from temperature probes and power meters to ensure timely data collection.
Set Quality of Service policies based on device importance and criticality.
VLAN Configuration:
Can be configured to create separate VLANs for power meters and temperature probes.
Isolate monitoring traffic from regular data traffic.
Security Features:
Implement port security (MAC address filtering) to prevent unauthorized access.
Enable SNMP (Simple Network Management Protocol) for monitoring switch health and performance.
Redundancy and High Availability:
Use redundant power supplies and link aggregation (LACP) for resilience.
Stackable for seamless failover.
22 Network 1 Server
Operating System:
64-bit Windows operating system is required for the server.
Ensure compatibility with Windows 2012 or later1.
Hardware Specifications:
Management Server: At least 60 GB of free disk space / 8 GB RAM / 4 CPUs Processor architecture recommended for the relevant Windows platforms.
Security Virtual Appliance: 35 GB free datastore space / 4 GB RAM / 4 CPUs Agent: 100 MB free disk space & 256 MB RAM / Compatible with various architectures (e.g., x86, SPARC, HP-UX, AMD 64).
Software Requirements: Windows Installer 2.0 or higher / Microsoft SQL Server 2008 or later for the production database.
If installing with SQL Server Express, additional prerequisites include: .NET Framework 4.0 or 4.5.1. / PowerShell 2.0. / Windows 2008 or later
23 Network 1 Network Time Protocol Server
Primary Reference Source:
The server must synchronize to national standards via wire, radio, or calibrated atomic clocks.
It should deliver continuous local time based on Coordinated Universal Time (UTC), even during leap second adjustments.
Network Connectivity: The NTP server must communicate over UDP port 123.
Ensure proper firewall settings to allow incoming and outgoing traffic on this port.
Must keep within milliseconds of UTC, maintaining accurate time across networks
24 Network 32 Biometric door locks
Authentication Methods:
Biometric data (e.g., fingerprint scans) for user identification.
Multifactor authentication (MFA) combining biometrics with other factors (e.g., PIN or RFID card).
Access Control Features:
Integration with a central server for user credential validation.
Remote unlocking capabilities for authorized users.
High-level monitoring and logging of access events.
Security Options:
Dual-factor authentication (2FA) using both biometrics and PIN/card.
Advanced biometric security options.
Encryption technology to ensure data protection.