This document appears to be a technical attachment related to a federal contract opportunity for hot aisle containment with server racks. The attachment provides a detailed layout and requirements for installing 16 seismic-compliant IT cabinet racks in two hot aisle containment (HAC) configurations, with each HAC consisting of two rows of four cabinets. Key requirements include brush grommet rail kits, copper bus bars, vertical cable bar kits, blanking/filler panels, remote power distribution units (rPDUs), temperature sensors, biometric door locks, LED strips, and thermal curtains. The contract also requires pre- and post-installation measurements of airflow and temperature within the facility. The related federal contract opportunity is for the Department of the Air Force Space Command, with a solicitation number of DCG. All questions are due by September 17, 2024, and there is currently no site visit scheduled.

View the file

Other files

File Type Posted
Attachment A - Mod Build-Out Parts List_v3_for RFQ.pdf PDF
Question Answered.docx DOCX document
DCG_Combo.pdf PDF
Attachment 2 Statement of Work .pdf PDF
Attachment 5 SSFB IFS .pdf PDF
Attachment 8 Drawing.pdf PDF
Attachment 4 Parts List.pdf PDF
Attachment 6 HVAC Study.pdf PDF
Attachment 1 Clauses and Provisions.pdf PDF
Attachment 3-Quote Worksheet.xlsx XLSX spreadsheet

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

7-Tile Pitch - Definition https://its.uark.edu/about/policies/data-center/racks-rows-guidelines.php https://www.akcp.com/articles/airflow-management-plan-for-data-center/

AKCP

Scope of Mod-Build-Out Demo with 7-Tile Pitch https://www.akcp.com/articles/airflow-management-plan-for-data-center/

AKCPAKCP

C ol d Ai sl e

48”

Hot Aisle

C ol d Ai sl e

42” 36” 48”42”

Cabinet Rack (x16)

Hot Aisle

2’x2’ Tiles

Directional Floor Vent (x12)

Cabinet Front

Cold Aisle

Hot Aisle Containment Door (x4)Cabinet Rear

No. of tiles: 132 = (16x9) - 12

This image is a snippet of the larger schematic from Mr. Bloodgood. See the “Demo Drawing.pdf” file [FINAL SOW Docs folder] for the full-view layout.

This is the area in Mod 3 (Bldg 400) where the 16 racks will be placed.