Attachment 4 Parts List.pdf

PDF 155 KB Posted

Attached to
Hot Aisle Containment with Server Rack
Solicitation number
Not on record
Issued by

About this file

This document is a detailed specification for a federal contract opportunity to purchase, deliver, and install sixteen (16) seismic compliant IT Cabinet Racks in two hot aisle containment (HAC) configurations at Schriever Air Force Base.

The key requirements include: 91" x 30" x 42" IT cabinet racks with 48 usable rack mount units, brush grommet rail kits, copper bus bars, vertical cable bar kits, blanking/filler panels, remote power distribution units (rPDUs), rPDU bracket sets, ganging kits, temperature sensors, hot aisle containment doors, LED lighting with motion sensors, thermal curtains, a main control server, new floor tiles and vents, and pre- and post-installation temperature, airflow, and power measurements. The contract also requires biometric door locks networked to the main control server. Responses are due by September 17, 2024, though no site visit is currently scheduled. This contract is being solicited by the Department of the Air Force Space Command.

View the file

Other files

File Type Posted
Attachment A - Mod Build-Out Parts List_v3_for RFQ.pdf PDF
Question Answered.docx DOCX document
Attachment 6 HVAC Study.pdf PDF
Attachment 7 Seven (7) Tile Pitch.pdf PDF
DCG_Combo.pdf PDF
Attachment 2 Statement of Work .pdf PDF
Attachment 5 SSFB IFS .pdf PDF
Attachment 8 Drawing.pdf PDF
Attachment 1 Clauses and Provisions.pdf PDF
Attachment 3-Quote Worksheet.xlsx XLSX spreadsheet

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Rack Hardware

16 IT Cabinet Rack

Dimensions: 91 inches (Height) x 30 inches (Width) x 42 inches (Depth) Rack Mount Units (RMU): 48 Usable Depth: 40 inches Maximum Rail Spacing: 35 inches Weight Capacity: 3300 lbs Color: Black

Includes Frame with levelers (2.5 inches Height; not installed unless specified at time of order) Two pairs of PDU (Power Distribution Unit) brackets Mesh Contour Front Door Mesh Contour Rear Door Solid Side Panels (2) Mounting Rails: 3/8-inch square (M6) with Rack Mount Hardware Solid Top Panel UL2416 certification

Rack Hardware

16 Brush Grommet Rail Kit Extends From Rail to Side Panel to Prevent Air Recirculation, Use with 91″H X 30″W Cabinets

Rack Hardware

16 Copper Bus Bar 76″L, Isolated, Use with 91 and 98″H Cabinets, Mounts along the ront Mounting Panel of cabinets and racks

Rack Hardware

16 Vertical Cable Bar Kit Includes 75″H X 4″W VCB (Qty 1), 29.5″H X 4″W HCB (Qty 2), 12″L Cinch Straps (Qty 6), Accepts Optional “D” Rings (CM-25 or CM-26), Use with 91″H Cabinets

Rack Hardware

160 Blanking/Filler Panels 19″ Mounting, 1 Rack Mount Unit, Black Panels, Pack of 10

Rack Hardware

80 Blanking/Filler Panels 19″ Mounting, 2 Rack Mount Unit, Black Panels, Pack of 5

Rack Hardware

16 PDU Bracket Sets Sets of Two Power Distribution Unit (PDU) Brackets with 2 Mounting Positions, Angled; Vertical Mounting of PDU, Installs in Rear Cabinet Corner, Use with 30/32″W X 42″D Cabinets

Rack Hardware

16 Ganging Kit Ganging Kit for Cabinets

Rack Hardware

16 rPDU (Power Distribution Unit)

Outlet-Level Switched rPDU with Environmental Monitoring Power Cord: A 10-foot (3-meter) power cord with an L5-20P plug Outlets: At least 24 NEMA 5-20R outlets Color: Black powder coat finish

Key Features:

- Has multiple addressable temperature probe ports

- Outlet-Level Control: Remotely switch outlets on/off for specific devices

- Power Monitoring: Monitor input and outlet power usage down to the device level

- Environmental Metrics: Optional sensors provide real-time data on temperature, humidity, and other environmental factors

- Daisy Chaining: Connect up to 40 rPDUs in a fault-tolerant daisy chain using RSTP (Rapid Spanning Tree Protocol)

Specifications:

- Power Configuration: Choose from 16A or 20A, 120V, 208V, or 230V

- Outlets: 12 combination C13/C19 outlets

- Monitoring:

- Input and outlet power monitoring

- Environmental monitoring via optional sensors

- Local LED display

Rack Hardware

32 Temperature Sensors Temperature sensor used to monitor temperature (degrees F) in data center airflows. Includes a 12ft (3.66m) cable Compatible with the rPDU

Rack Hardware

4 Hot Aisle Containment Doors

Number of Doors Needed: 4 (one for each end of the hot aisle)

Total Hot Aisle Width: 36-48" (91.44-121.92 cm).

Height: 91" (231.14 cm)

Material and Features:

Durable, high-quality materials suitable for data center environments.

Clear or opaque door panels (please specify options and costs).

Options for either sliding or swinging door mechanisms.

Efficient sealing to prevent air leakage and maintain effective containment.

Compatibility with existing cabinets and containment systems.

Optional integration with fire suppression systems.

Ease of access for personnel and equipment.

Can be integrated with biometrics security lock.

Additional Requirements:

Installation services (if available, please specify cost).

Lead time for manufacturing and delivery.

Warranty information.

M i t d t ti

Misc Hardware

1 Inline LEDs with Motion Sensor

White (5.7K) LEDs with inline motion sensor designed to detect movement and control the lighting system by switching the lights on or off based on occupancy. The LEDs and in-line sensor should plug into the rPDU, making it ideal for energy-saving and permit visibility inside the hot asile(s).

Key Specifications:

Detection Technology: Passive Infrared (PIR) Sensing Range:

Distance: Up to 20 feet (6 meters) adjustable range Angle: 120° to 180° field of view Response Time: < 1 second Power Supply:

Voltage: 120V AC Frequency: 50/60 Hz Current Consumption: Typically < 50 mA Output:

Type: Relay output, normally open (NO) Load Capacity: Up to 600W incandescent, 150W LED/CFL Connection Type: Inline with input and output terminals for integration into the existing circuit Operating Temperature: -20°C to 50°C (-4°F to 122°F) Humidity Range: 0% to 95% non-condensing Enclosure:

Material: High-impact ABS plastic Rating: IP54 (splash-proof and dust-resistant) Features:

Adjustable Sensitivity: Allows for customization of detection range and responsiveness.

Time Delay Adjustment: Configurable delay time (1 second to 10 minutes) for maintaining the light on after motion is no longer detected.

Ambient Light Sensor: Optional built-in sensor to prevent activation during daylight or well-lit conditions.

Compact Design: Small form factor for easy integration into existing lighting circuits.

Mounting Options: Surface mount with screws or adhesive, flush mount for seamless integration.

LED Indicator: Visual confirmation of motion detection and operational status.

Override Function: Manual override option to keep lights on or off regardless of motion detection.

Installation:

Wiring: Standard 3-prong plug for rPDU Setup: Adjust sensitivity and time delay settings using onboard controls Compliance and Certifications:

( l f )

Misc Hardware

$30/sq ft 150 Floor Tiles Purchase and install anti-static raised floor tiles. These tiles will be made from steel, with a load-bearing capacity of 250 lbs per square foot, and have anti-static properties to prevent electrostatic discharge. They create an underfloor plenum space for efficient cooling and organized cable management. Install new floor tiles directly inside, under, and surrounding the two new HACs (excluding where floor vents shall be placed). See reference floor diagram.

Misc Hardware

12 Floor Vents

Adjustability:

Vents should indicate specific air delivery volume in real-time so they can be set and adjusted based on unique rack load.

The vents must be adjustable to direct airflow in specific directions.

Provide a mechanism (e.g., louvers, dampers) for fine-tuning the vent angle.

Ensure smooth and reliable adjustment without compromising structural integrity.

Materials and Construction:

Construct vents from durable, non-corrosive materials (e.g., aluminum, stainless steel).

Consider fire-resistant coatings or materials to enhance safety.

Reinforce structural components to withstand foot traffic and equipment loads.

Mounting and Integration:

Vents should fit seamlessly into raised access floor tiles.

Ensure compatibility with standard floor tile dimensions (e.g., 24" x 24" or 60 cm x 60 cm).

Provide secure attachment mechanisms (e.g., locking clips) to prevent accidental displacement.

Airflow Control:

Design vents to allow variable airflow rates.

Include features for partial or full closure when needed.

Consider aerodynamic design to minimize turbulence and pressure drop.

Maintenance and Accessibility:

Ensure easy access for cleaning and maintenance.

Design vents to be removable without disrupting adjacent tiles.

Provide clear instructions for maintenance procedures.

Safety Features:

Include safety guards or grilles to prevent accidental contact with moving parts.

Consider tamper-resistant features to prevent unauthorized adjustments.

Testing and Validation:

Conduct airflow simulations to verify directional control.

Test adjustability and stability under load conditions

Misc Hardware

6 Ceiling Vents

Quality aluminum 24" x 24" fixed-bar air grille White powder coat finish Drop-ceiling compatible

Misc Hardware

16 Break Away Curtains

Curtain Material:

PVC-coated polyester or similar fire-resistant material.

Curtain Configuration:

Curtains to span the full height between racks.

Aluminum track system for installation.

Mounting and Attachment:

Hooks or clips for securing curtains to the track.

Ensure snug fit to prevent air leakage.

Overlap and Sealing:

Magnetic strips or Velcro for tight seal along edges.

Overlap adjacent curtains by at least 6 inches.

Breakaway Feature:

Breakaway design that detach without falling to the floor.

Utilize breakaway connectors or clips.

Access Points:

Include zippered openings for maintenance access.

Proper sealing for containment

Misc Hardware

1 Air Capture Hood

The hood should be suitable for measuring air volume at diffusers and grilles.

It’s essential for HVAC commissioning, troubleshooting, and testing and balancing in data centers.

Features:

Lightweight and ergonomic design for easy one-person operation.

Automatic flow sensing and display for efficiency.

Back pressure compensation ensures accurate readings.

Various hood sizes available for versatility.

Detachable digital micromanometer for flexibility.

Included Items:

Air capture hood/frame/base (size as needed for 24" tiles) Detachable micromanometer Flow conditioner Batteries AC adapter Pitot probe Static pressure probes Tubing Carrying case Calibration certification Downloading software and interface cable

Desktop 1 Computer

Operating System:

Windows 11 or later for desktop clients.

Modern web browsers for accessing the web-based interfaces (e.g., Chrome, Firefox, Edge).

Memory:

At least 4 GB RAM (more may be needed for intensive tasks).

Processor:

Modern multi-core processor (e.g., Intel i7 or AMD Ryzen).

Network:

Stable internet connection for accessing the software and any remote features.

Desktop 2 Monitors

34" curved monitor w/ stand Resolution: WQHD 3440 x 1440 Refresh rate: 60 Hz minimum Ports: 2x HDMI (HDCP 2.0); 1x Display Port

Network 6 Room Temperature Probes 6 realtime networked temperature probes (Need compatibility with Smart Power Strip)

Network 1 Network switch

Port Density and Type:

A managed switch with sufficient ports (e.g., 48 ports) to accommodate power meters and temperature probes.

A mix of Gigabit Ethernet (1 Gbps) and higher-speed ports (e.g., 10 Gbps or 40 Gbps) for scalability.

Power over Ethernet (PoE) Support:

PoE-enabled switch ports to power connected devices (such as power meters) via the Ethernet cable.

Verify compatibility with IEEE 802.3af/at standards for PoE delivery.

Quality of Service (QoS):

Prioritize traffic from temperature probes and power meters to ensure timely data collection.

Set Quality of Service policies based on device importance and criticality.

VLAN Configuration:

Can be configured to create separate VLANs for power meters and temperature probes.

Isolate monitoring traffic from regular data traffic.

Security Features:

Implement port security (MAC address filtering) to prevent unauthorized access.

Enable SNMP (Simple Network Management Protocol) for monitoring switch health and performance.

Redundancy and High Availability:

Use redundant power supplies and link aggregation (LACP) for resilience.

Stackable for seamless failover

Network 1 Server

Operating System:

64-bit Windows operating system is required for the server.

Ensure compatibility with Windows 2012 or later1.

Hardware Specifications:

Management Server: At least 60 GB of free disk space / 8 GB RAM / 4 CPUs Processor architecture recommended for the relevant Windows platforms.

Security Virtual Appliance: 35 GB free datastore space / 4 GB RAM / 4 CPUs Agent: 100 MB free disk space & 256 MB RAM / Compatible with various architectures (e.g., x86, SPARC, HP-UX, AMD 64).

Software Requirements: Windows Installer 2.0 or higher / Microsoft SQL Server 2008 or later for the production database.

If installing with SQL Server Express additional prerequisites include: NET Framework 4 0 or 4 5 1 / PowerShell 2 0 / Windo s 2008 or later

Network 1 Network Time Protocol Server

Primary Reference Source:

The server must synchronize to national standards via wire, radio, or calibrated atomic clocks.

It should deliver continuous local time based on Coordinated Universal Time (UTC), even during leap second adjustments.

Network Connectivity: The NTP server must communicate over UDP port 123.

Ensure proper firewall settings to allow incoming and outgoing traffic on this port.

Must keep within milliseconds of UTC maintaining accurate time across networks

Network 32 Biometric door locks

Authentication Methods:

Biometric data (e.g., fingerprint scans) for user identification.

Multifactor authentication (MFA) combining biometrics with other factors (e.g., PIN or RFID card).

Access Control Features:

Integration with a central server for user credential validation.

Remote unlocking capabilities for authorized users.

High-level monitoring and logging of access events.

Security Options:

Dual-factor authentication (2FA) using both biometrics and PIN/card.

Advanced biometric security options.

Encryption technology to ensure data protection

Software 100

Software Licenses, Helpdesk Support and Professional

Integration Services (for Software/Hardware Initial

Setup and Integration)

Phase 1 - 100 Racks Starter Licenses w/ Helpdesk Support and Professional Integration Services

Total Material cost for Rack Hardware, Misc Hardware, Desktop, Software, & Network