This document is a pre-solicitation notice for a federal contract opportunity related to the Crater Lake National Park in Oregon. The primary work involves rehabilitation of the 1.1-mile Cleetwood Trail, including improvements to the trail tread and retaining walls, rockfall scaling and mitigation, removal and replacement of a failed marina bulkhead/dock, replacement of composting toilets, and construction of a permanent concessionaire booth. The estimated price range is between $30,000,000 and $40,000,000, with a tentative completion date of Fall 2027. This will be a negotiated, firm-fixed-price contract with a base period and four option periods. The solicitation is anticipated to be released in Winter 2024/2025 and will be offered for full and open competition on an unrestricted basis. Preliminary plans and additional project information are available as attachments.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NO SCALE
FOOTNOTE:
Place Soil Erosion control, fiber roll (coir roll) at or below bottom elecation of base rock.
[3]
Cover top and cut side of rockery with Geotextile filter, class 2, type A (nonwoven)[2]
See Sheet I.1-2 for information.[1]
TYPICAL SECTION
ROCKERY CUT SLOPE
[1] see Section C for details
Trail surface, CL rock
Cap
Base rock
Existing ground
5% min.
0.5'
0.5' min.
Leveling course base, grading D
Granular rock backdrain
Embankment
1'
TYPICAL SECTION
ROCKERY FILL SLOPE
[1] rock
Cap
Base rock
Existing ground
[2] type A (nonwoven)
Geotextile filter, class 2, 5% min.
0.5'
0.5' min.
Leveling course base, grading D
Granular rock backdrain
Embankment
1'
CL
[3] see section E for details fiber roll (coir roll), Soil erosion control, see Section C for details
Trail surface, V a ri e s t o
V a ri e s t o
:4 m a x
:4 m a x
Geotextile filter, class 2, :2 m a x
0.5'
NOTE:
1. Remove and dispose of existing walls.
Embankment
:1
W a ll h e ig h t, m a x
Base rock width, B
W a ll h e ig h t, m a x
Base rock width, B m in
:1
P
M
J u ly
R
O C
K E
R Y
D E
T A
IL
S
S
H E
E T
O
F c p w w o r k
\d
\c r la
P
L N
I .d g n
ROCKERY DETAILS (SHEET 1 OF 2)
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.3
NPS Drwg No. 186271 NPS PMIS No. 264912
NOT FOR CONSTRUCTION
CONSTRUCTION DETAIL
slope
Soil
5 5 5 5
55555
4 4 4 4
2 2 slope
Soil
ROCKERY TAPER DETAIL
FILL-SIDE
OR
CUT-SIDE
NOTE:
rockery information.
3. See Geotechnical Report Number GR05-24 for additional site and gaps and spaces to 3-inches maximum.
at least two stones beneath it. Cut or dress stones to reduce
2. After bottom row, bear each larger stone (size 4-5) firmly on to wall.
1. Place larger stones (size 4-5) with longest axis perpendicular
1 2 3
5 FT
10 FT
15 FT
0 FT
:3
J u n e
R
O C
K E
R Y
D E
T A
IL
S
S
H E
E T
O
F p w w o r k
\d
\c r la
P
L N
I .d g n
ROCKERY DETAILS (SHEET 2 OF 2)
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.4
Place Soil Erosion control, fiber roll (coir roll) at or below bottom elecation of base rock.
[3]
Cover top and cut side of gabion with Geotextile filter, class 2, type A (nonwoven).[2]
See Sheet I.1-2 for information.[1]
Granular rock backdrain
CL
see Section C for details
Trail surface, TYPICAL SECTION
GABION
[1]
Embankment
1:
m ax
[3] see section E for details fiber roll (coir roll), Soil erosion control, Embankment
Existing ground
Geotextile filter, class 2, NOTE:
1. Remove and dispose of existing walls.
and Gabion basket place on top of trail surface
Rock, 1:
:1 ty p
0.5'
3' (typ.)
W a ll h e ig h t, m a x
0.5'
1'
:1 u ly
G
A B
IO
N
D E
T A
IL
S p w w o r k
\d
\c r la
P
L N
I .d g n
GABION DETAILS
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.5
WESTERN FEDERAL LANDS HIGHWAY DIVISION
DETAIL APPROVED FOR USE --/----
DRAFT: 9/2011
REVISED:
W253-1
GABION BASKET
0.150" DIAMETER
(CUYD)
6 3.0
3.0
3.0
3.0
3.0
1.5
1.5
1.5
1.0
1.0
1.0
2.00
3.00
4.00
5.00
6.00
1.00
1.50
2.00
0.67
1.00
1.33
, 1 5', o r 1
8'
6', 9', 12'
1" overlap
0.118" wire diameter
0.118" wire diameter
Size in feet
0.087" diameter lacing wire
0.150" diameter
0.120" diameter mesh wires
Tie mesh with 0.150" diameter selvage hitch loops at 3" spacing
Tie mesh with 0.150" diameter
0.150" diameter
NO SCALE
TYPICAL INSTALLATION GABION BASKETS
SPIRAL BINDER
ALTERNATE TYING FASTENERS
GABION BASKET
TYPICAL ASSEMBLED
WALL GRADE TRANSITION AREAS
ASSEMBLED GABION BASKET IN
TYPICAL CULVERT INSTALLATION
ALL GABION CELLS
ALL END GABION CELLS ALL INTERIOR GABION CELLS
HALF HITCH LACING DETAIL
OVERLAPPING RING WIRE FASTENER
THROUGH GABION WALL
TYPICAL STIFFENERS
WELDED WIRE GABION BASKET
OPTIONAL STIFFENERS
Side
End
Base
Side
Stiffeners
WELDED WIRE MESH TWISTED WIRE MESH
back to outside diameter of culvert.
Cut wire basket mesh front and Culvert
CL
Cut wire basket mesh front and back. Lid
BEFORE CLOSURE AFTER CLOSURE
(Not allowed for basket to basket connection)
End
Side
Side
Base
Lid
Diaphragms
NOMINAL SIZES AND CAPACITY
GABION BASKET
Letter
Size Code
Length Height Partitions
Diaphragm Capacity
I
H
G
F
E
D
Y
X
C
B
A
(Twisted wire mesh)
(Welded wire mesh)
(Welded wire mesh)
SPIRAL BINDER TIE
HALF HITCH LACING DETAIL
INTERLOCKING WIRE FASTENER
BEFORE CLOSURE AFTER CLOSURE
are nominal
All dimensions
NOTE:
are nominal
All dimensions
NOTE:
selvage wires
Diaphragmswith stiffeners to prevent wall bulging wire and connect front and back mesh
Stiffeners each end of stiffener
Loop two meshes at
Diaphragms
Stiffeners
Stiffenershook closed
Crimp end of joint
Crimped joint end of
Crimped double half hitch wire to next
Continuous lacing
Single half hitch to next single half hitch
Continuous lacing wire
Le ng th
Crimp ends to lock
Spiral binder.
half hitches as shown
Alternate single and double
Double half hitch.
Lacing Details)
Lacing wire (see Lacing Details)
Lacing wire (see
Lacing wire. Tie with half stiffeners to prevent wall bulging.
connect front and back mesh with selvage wire around pipe, and intersection of wires stiffener hooked at
WESTERN FEDERAL LANDS HIGHWAY DIVISION
DETAIL APPROVED FOR USE --/----
DRAFT: 9/2011
REVISED:
W253-1
GABION BASKET3
:4
J u n e
G A
B
IO
N B
A S
K E
T p w w o r k
\d
\c r la
D e t.
W
.d g n
FEDERAL HIGHWAY ADMINISTRATION
U.S. DEPARTMENT OF TRANSPORTATION
DETAIL
U.S. CUSTOMARY DETAIL
"2
Le ng th
6', or 8'
3' (ty p.
)3'
3'
3' ( typ
H e ig h t
3' 3'
3'
H e ig h t
3' 3'
12"
12"
12"
.8
.9
.0
1.0"
.8
1.4"
0.45"
(min.)
4'
H e ig h t
3' 3'
12"
12"
12"
4"± nominal spacing
H e ig h t
H e ig h t
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.6
87°87°
Trail surface, see Section C for details
NO SCALE
Existing ground form (typ.)
Welded wire
WITH WELDED WIRE FORM FACE
MECHANICALLY-STABILIZED EARTH WALL
sheet drain, 50% coverage
Geocomposite
W a ll p a y m e n t li m it s
See Detail A
Underdrain system at mid height of panel at face 12" (min.)
Gabion rock
FACING DETAIL - ROCK FILL
Select granular backfill
Select granular backfill grid, 3 per panel (typ.)
on facing and
Tie transverse bars
Welded wire form facing
WELDED WIRE FORM
adjoining wire form for support, 4"
Place edge of wire inside of
4 x 4 W5 x W5
Inset end struts 6"
24" C to C or as needed.
Support struts spaced maximum
NOTE:
FOOTNOTE:
= 2.0% Min. gradient
UNDERDRAIN SYSTEM
PERFORATED PIPE
DETAIL A
Granular backfill
Leveling course
12"
Flow
24"
Geocomposite sheet drain beneath leveling course. Minimum gradient 0.5%
6" Ø Perforated pipe underdrain system pipe drain every 100 feet (max.)
6" Ø Rigid outlet
2%
See Facing Detail type A, non-woven class 2, Geotextile filter, type A, non-woven class 2, Geotextile filter, 18"
Elbows
(2) 45°
Friction angle = 34° for backfill material.
Unit weight of backfill material 125 pcf
4. Design assumptions:
3. The heights and quantities are subject to field adjustment.
for inextensible reinforcement.
reinforcement. Provide maximum vertical spacing of 24-inches
2. Provide maximum vertical spacing of 18-inches for geogrid
1. Remove and dispose existing retaining walls.
Top of wall (TW) (Layout line)
24" Embankment
Slope to drain
[3]Extend 6" (min.) beyond facing grading D.
Leveling course base, leveling pad (BLP)
Bottom of
Bottom of wall (BW)
[1]Rodent guard
See Sheet I.2 for reinforcement length.
[4] drain towards underdrain system.
Slope bottom of excavation at a minimum 2 percent grade to [3]
Section 208.03. Provide temporary shoring as needed.
Construct slopes at stable inclinations in accordance with [2] per manufacturer's recommendation
-inch. Install2
Opening in rodent guard not to exceed [1] geogrid, type III
Reinforcement geogrid type III
Reinforcement
NO SCALE
Unclassified borrow
H
Select granular backfill
Wall excavation
[2]V
1:3
12"
24"
2%
18"
Varies filter rock
Soil erosion control, H
[4]
Grid length, "L"
6" (min.)
(min.)
4' Set back m in
4' Return (min.)
m in
3" - 6"
H
H e ig h t v a r ie s m in
8'-0" ±
48"
0.5' 1'
:1 u ly
M
E C
H A
N
IC
A L
L Y
-S T
A B
IL
IZ
E D
E A
R T
H W
A L
L D
E T
A
H
E E
T o f p w w o r k
\d
\c r la
P
L N
I .d g n
(SHEET 1 OF 2)
EARTH WALL DETAILS
MECHANICALLY-STABILIZED
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.7
Underlying mats
Return mat
Welded wire form
(PLAN VIEWS)
GEOGRID BUTT DETAIL
Adjacent geogrids
TANGENT WALL FACE
backside without overlap
Butt adjacent geogrids at
Wall face
CURVE LEFT WALL FACE
Adjacent geogrids
Backside overlap acceptable
Wall face
CURVE RIGHT WALL FACE
Adjacent geogrids
Backside separation acceptable
Wall face wall face without overlap
Butt adjacent geogrids at wall face without overlap
Butt adjacent geogrids at wall face without overlap
Butt adjacent geogrids at recommended method.
with hog rings, wire ties, spiral binders, or the manufacturers
Connect adjacent welded wire reinforcement facing elements[1]
[1]Connect reinforcement
AND RETURN MAT DETAILS
MSE WALL FACING , CORNER
(roll direction) (roll direction)
Reinforcement length (L) perpendicular to front wall face type III with strongest axis
Reinforcement geogrid, NO SCALE
FOOTNOTE:
Underlying mats
Return mat
Welded wire form
(PLAN VIEWS)
GEOGRID BUTT DETAIL
Adjacent geogrids
TANGENT WALL FACE
backside without overlap
Butt adjacent geogrids at
Wall face
CURVE LEFT WALL FACE
Adjacent geogrids
Backside overlap acceptable
Wall face
CURVE RIGHT WALL FACE
Adjacent geogrids
Backside separation acceptable
Wall face wall face without overlap
Butt adjacent geogrids at wall face without overlap
Butt adjacent geogrids at wall face without overlap
Butt adjacent geogrids at recommended method.
with hog rings, wire ties, spiral binders, or the manufacturers
Connect adjacent welded wire reinforcement facing elements[1]
[1]Connect reinforcement
AND RETURN MAT DETAILS
MSE WALL FACING , CORNER
(roll direction) (roll direction)
Reinforcement length (L) perpendicular to front wall face type III with strongest axis
Reinforcement geogrid, Reinforcement length (L)
4' (min.)
Reinforcement geogrid length (L)
Machine Machine
Reinforcement length (L)
Reinforcement length (L)
4' (min.)
Reinforcement geogrid length (L)
Machine Machine
Reinforcement length (L)
:2
A
M a y
M
E C
H A
N
IC
A L
L Y
-S T
A B
IL
IZ
E D
E A
R T
H W
A L
L D
E T
A
(S
H E
E T o f p w w o r k
\d
\c r la
P
L N
I .d g n
(SHEET 2 OF 2)
EARTH WALL DETAILS
MECHANICALLY-STABILIZED
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.8
Soil Properties
See Geotechnical Report GR05-24 for additional information
Provide a minimum service life of 75 years for all components.
FHWA GEC 007, Soil Nail Walls Reference Manual 2015.
Design for soil nail walls shall conform to the requirements for
Oregon.
by a professional Geotechnical Engineer licensed by the State of
The design drawings and calculations shall be signed and sealed and external design (excluding seismic design).
Soil Nail Wall vendor shall perform all internal
Design:
SPECIFICATIONS
Description
Material
(psf)
Intercept
Cohesion
(Degrees)
Friction
Angle of Internal
(pcf)
Weight
Moist Unit
120 34 0 Retained Soils
Foundation &
NO SCALE
TAPER DETAIL
CUT SLOPE
NOTE:
TYPICAL SECTION
native material
Undisturbed
Soil nail wall
See Note 4
Weep drain
2%
2" PVC
Geocomposite drain
Granular rock backdrain
See Note 1
Soil nails (typ.)
See Note 2 construction facing.
4" (typ.) Shotcrete
See Note 3 permanent facing.
6" (min.) Shotcrete
Embankment
Top of wall profile
1:6 (m ax.
beyond face of wall extend 6-inch (min.)
Leveling course base, grading D, Collector pipe class 1 through 5 stones. See sheet I.4 for details.
11. Construct rockery facing in accordance with Section 252 using coupling bands or by other approved means.
Subsection 605.03. Hold the screen securely in place with standard
10. Cover the end of the drain outlet pipe with screen according
9. See geotechnical report for additional site information.
eliminate gaps over 3-inches minimum.
beneath it. Use smaller stones as needed to maintain spacing and
8. Bear each larger stone (size 4 and 5) firmly on at least two stones the CO for approval.
7. Provide collector pipe connection details and weep drain spacing to to wall.
6. Place larger stones (size 4 and 5) with longest axis perpendicular manufacturers recommendations.
5. Weep drain to be connected to the geocomposite per the from bottom up.
4. The permanent shotcrete facing can be applied in one lift or in lifts face prior to installing the next row of nails as per Section 259.05.
3. Install soil nails in lifts from the top down. Construct shotcrete details to the CO for approval.
illustrative. The contractor is responsible for providing final design
2. Soil nail wall layout, plan, details, facing and general notes are
1. Remove and dispose of existing retaining walls.
see Section C for details
Trail surface, CL
Rockery facing slope
Soil
10"
5' (min.)
H m in
0.5'
:3
J u n e
S
O
IL
N A
IL
R
E T
A
IN
IN
G
W A
L L
T Y
P
IC
A L
S E
C T
IO
N
D E
T A p w w o r k
\d
\c r la
P
L N
I .d g n
TYPICAL SECTION DETAILS
SOIL NAIL RETAINING WALL
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.9
L
BAR
GRADE
NOTE:
Verification soil nail location a
SOIL NAIL SCHEDULE
NOTE:
SOIL NAIL WALL LAYOUT
a
SOIL NAIL SCHEDULE
ROW L BAR GRADE PLATE A
D
NOTE:
Vertical Spacing (FT) = (max.)
Minimum Static FOS = 1.50
2.
1.
ELEVATION AT TOP OF WALL
- WALL STATIONING AND
- ELEVATION OF GROUND
SURFACE AT CONTROL LINE
LEGEND:
ROW
aROW L BAR GRADE PLATE A D
Minimum Static FOS = 1.501.
RESISTANCE (K/FT)
- ALLOWABLE DESIGN NAIL PULLOUT
- DECLINATION ANGLE OF SPECIFIC NAIL
SHOWN OTHERWISE ON PLANS
- NAIL DECLINATION (DEGREES) UNLESS
- NAIL BAR STEEL GRADE (Fy)
- NAIL BAR SIZE
- DRILLED NAIL LENGTH (FEET)
- SOIL NAIL / TIEBACK ROW NUMBER
- NAIL DECLINED AT
- SOIL NAIL / TIEBACK ROW
row of nails - ___ maximum and ___ minimum
15. Vertical distance from the bottom of the wall to the bottom nail - ___ maximum and ___ minimum
14. Distance from end of the soil nail wall to the nearest soil of soil nails - ___ maximum and ___ minimum
13. Vertical distance from the top of the wall to the first row
12. Vertical spacing - ___ maximum and ___ minimum
11. Horizontal spacing - ___ maximum and ___ minimum additional ___ inches of permanent facing.
10. Minimum facing thickness is __ inches construction face with an
_______ diameter headed studs.
9. Minimum connection plate size is ________with wall.
between the nails connected to weep holes at the base of the
8. Geocomposite drainage board, minimum 2-foot strips centered with FHWA guidelines.
7. Corrosion protection of nail tendons - Epoxy coating in accordance
6. Soil nail must not cross the project property line.
5. Minimum wall embedment below finished grade - ___
4. Minimum tendon size - __ grade __ rebar.
3. Minimum drill hole diameter - ___
2. Minimum soil nail length - ___ the CO for approval.
schedule and other details will be furnished by the contractor to vague and are meant to be illustrative. The final nailing pattern,
1. The details and tables on this sheet are purposely incomplete and
,0
.5
.0
,0
.9
:4
J u n e
S
O
IL
N A
IL
R
E T
A
IN
IN
G
W A
L L L
A Y
O U
T T
Y P
IC
L p w
-w o rk
\d \c rl a P
L N
I.
d g n
LAYOUT TYPICAL
SOIL NAIL RETAINING WALL
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.10
SECTIONAL VIEW ISOMETRIC VIEW
DRAIN GRATE DETAILS
FACING JOINT
TYPICAL SOIL NAIL
DRAINAGE STRIP DETAIL
GEOCOMPOSITE
2%
STUD DETAIL
CONNECTOR PLATE WITH
SHOTCRETE WALL JOINT DETAIL
with min. CIP cover of 2" soil face to provide bar end
Steel bar to protrude from
REINFORCEMENT DETAIL
CONSTRUCTION SHOTCRETE FACING
NOTE: Drain grate installation shall not disrupt geotextile design prior to shotcrete next lift the specifications in accordance with
Clean shotcrete joints angled joint as shown
45 degree angle to create
Backfill rebar lap at drain board strips (min.) 2' wide
Vert perm geocomposite
Temporary shotcrete joint
4" (typ.) Construction shotcrete facing
(size and # ) Rebars WWF (size)
(size) rebars
Continuous drain board (min.) 2' wide
Vertical geocomposite
See detail
Temporary shotcrete lift joint (typ.)
Weep hole
Shotcrete construction facingPermanent shotcrete facing
(plate should be wet set) centered about bar hole headed spaced - x -
- x - studs steel plate, with four
- x - thick mild with min. CIP cover of __" soil face to provide bar end
Steel bar to protrude from hex nut with beveled washer
Steel spherical seat nut or vertical and horizontal facing #__@ x" O.C.
at of permanent
Reinforcing placed
LC
LC
Centralizer
Nail grout
Shotcrete or nail grout corrosion protection and centralizers
Steel bar with double encapsulation
LC
Nail hole
(plate should be wet set) centered about bar hole studs spaced " x "
" x " welded steel plate, with four
" x " thick mild
(place at of tempoary shotcrete)
WWF (__ x __ - W __ x W __)
@ __" O.C. continuous behind plate
Waler bars (2) #__ - deformed steel bars
(placed at of temporary shotcrete)
Two __" x __" vertical rebars and full penetration buttweld
__" Dia. x __" heads
__" Dia. x __" with
Stud (typ. 4 places)
NOTE:
furnishing final design details for approval by the CO.
are meant to be representative. The contractor is responsibile for
1. The details on this sheet are purposely incomplete and vague and la p f o r
W W
F m in m in
L a p
(typ.)
x
(typ.)
4"
(min.)
6"
2" Clear
X
X
:4
J u n e
S
O
IL
N A
IL
R
E T
A
IN
IN
G
W A
L L
T Y
P
IC
A L
D E
T A
IL
S
S
H E
E T
O
F p w w o r k
\d
\c r la
P
L N
I .d g n
TYPICAL DETAILS (SHEET 1 OF 2)
SOIL NAIL RETAINING WALL
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.11
3. Proof test detail is same except performed on a production nail.
2. Bare bars may be used for sacrificial test nails.
furnishing final design details to the CO for approval.
meant to be representative.. The contractor is responsible for
1. The details on this sheet are purposely incomplete and vague and are
SOIL NAIL DETAIL
ENCAPSULATED PRODUCTION
VERIFICATION TEST SOIL NAIL DETAIL
Hex nut
Steel bar
Plate, with studs
Beveled washer
Shotcrete construction facing minimum 3" shotcrete or nail grout cover
Embed nail encapsulation to provide the top and bottom of drillhole provide centralizers within 2' from
Centralizer @ max. 6' o.c. and
Nail grout
Encapsulation
End cap assembly with architectural finish
CIP concrete wall supports independent of wall
Dial gauges attached to
Load cell
Reference plate
Bearing plates
To readout pressure gauge
To hydraulic pump and
Jack hydraulic ram
Verification test nail steel bearing plate
Wood cribbing and
2" (min.) cover
1" (min.)
Total nail bar length
3' (min.)
Unbonded length
10' (min.)
Bonded length
__" (min.)
L = Drilled nail length
:4
J u n e
S
O
IL
N A
IL
R
E T
A
IN
IN
G
W A
L L
T Y
P
IC
A L
D E
T A
IL
S
S
H E
E T
O
F p w w o r k
\d
\c r la
P
L N
I .d g n
TYPICAL DETAILS (SHEET 2 OF 2)
SOIL NAIL RETAINING WALL
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.12
Hard wood stakes
Conserved topsoil
Conserved topsoil
Roughened slope slope stabilization landscape log
Install mitigation
5" or greater (DBH)
Landscape logs
Hard wood stakes
2. Minimum length of landscape logs = 10-feet.
identified by the CO.
1. Selection, placement location, and orientation of logs will be
Embed stake to the midpoint of the log at embedment point.
[3]
Minimum depth of 4-foot, at refusal. Place at 4-foot maximum spacing.
[2]
Place conserved topsoil.
[1]
FOOTNOTE:
NOTE:
TYPICAL LANDSCAPE LOG
LOG STAKING DETAILSECTION A-A
Sl op e
[3
[1]
[1]
20°
2" Log embedment depth
(m in
[3
(m in
:5
J u n e
T
Y P
IC
A
L L
A N
D S
C A
P E
L O
G D
E T p w w o r k
\d
\c r la
P
L N
I .d g n
TYPICAL LANDSCAPE LOG DETAIL
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.13
3,000 psi.
2. Concrete backfill (min.) compressive strength shall be compressive resistance of 2 tons. Conform to ASTM A53 Grade A with hot-dip galvanization.
1. Steel pin piles shall be 2.375-inch O.D. with 0.218-inch Schedule 80 wall thickness with a nominal axial
WALL REPAIR ELEVATION
FOOTNOTE:
(min. 6'-0").
Drive piles to refusal criteria. Estimated length 15'-0"[1] around pile head
Concrete cap
12" x 12" x 6'
[1] driven pin piles
2-inch diameter rocks and debris
Remove loose
Contractor to verify width masonry facing in large gaps flowable grout. Add stone
Fill voids behind wall with top course stones of wall
Remove and reset stone masonry (top course), 16+23 to 16+78 RT face of wall
Repoint stone masonry, 16+23 to 16+78 RT
Equal spaces 1'-6" (max.)
Width estimated to be ~ 6'
:0
J u n e
S
T O
N E
M A
S O
N R
Y
U N
D E
R P
IN
N
IN
G
W
IT
H M
IC
R
O P
IL
E
S
(S H
E E
T
O F p w w o r k
\d
\c r la
P
L N
I .d g n
WITH MICROPILES) (SHEET 1 OF 2)
STONE MASONRY (UNDERPINNING
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.14
steel pin pile
2" diameter driven
Existing ground
Concrete cap around pile head
12" x 12" x 6'
WALL REPAIR SECTION
Existing wall
COUPLER DETAIL
TOP PLATE DETAIL
STEEL WEDGE CONNECTION DETAIL
SCREWJACK CONNECTION DETAIL
New steel pipe section strong steel ring " extra 4
Drive steel pipe section
Beveled end to aid insertion
Sleeve
Fillet weld
Pipe pile
" (typ.)2 jack and plates concrete around
Place 3,000 psi
Pin pile jack and plates concrete around
Place 3,000 psi by sledge hammer of varying size
(one or more)
Drive steel wedge
NO SCALE
See sheet I.15 for existing wall face image.
Add rubble mosonry in large gaps.
at the direction of the CO.
Replace and re-grout rubble masonry lean concrete backfill
Fill void with
E s ti m a te d m in t o
Pipe I.D. 2"
2" ty p
V a r ie s
V a r ie s
:3
J u n e
S
T O
N E
M A
S O
N R
Y
U N
D E
R P
IN
N
IN
G
W
IT
H M
IC
R
O P
IL
E
S
(S H
E E
T
O F p w w o r k
\d
\c r la
P
L N
I .d g n
WITH MICROPILES) (SHEET 2 OF 2)
STONE MASONRY (UNDERPINNING
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) I.15
0 1 2 3
SCALE IN MILES
N
Island
Wizard
CRATER LAKE
Lodge
Crater Lake Notch
Kerr
Little Cast le Creek
M u n so n
C re e k
M id d le F o r k
Rock
Mazama
Hill
Grouse
Rock
Liao
Peak
Hillman
House Lookout
Sun Creek
R I
M
Headquarters
Park
E a s t F o r k
RIM
R
IM
D R
IV
E
S k e ll C h a n n e l
Cove
Cleetwood
Point
Pumice
Point
Palisade Bay
Steel
Bay
Liao
Point Merriam
Point
Discovery
Point
Eagle
Ship
Phantom
Chaski Bay
Bay
Danger
Rock
Sentinel
Bay
Cloudcap
Cove
Grotto
W E S
T
R d
V a ll e y
Cas tle
Cre ek
T ra p p e r
C re e k
Campground
Mazama
EAST
E A
D R
IV
E
Parking Area
Trailhead
Cleetwood Cove
0 1 2 3
SCALE IN MILES
Island
Wizard
Lodge
Crater Lake Notch
Kerr
Little Cast le Creek
M u n so n
C re e k
M id d le F o r k
Cloudcap
Hill
Grouse
Rock
Liao
Peak
Hillman
House Lookout
Sun Creek
R I
M
PARK
NATIONAL
CRATER LAKE
Headquarters
Park
P in n a c le s R o a d
E a s t F o r k
PROJECT LOCATION
DRIVE
R
IM
D R
IV
E
S k e ll C h a n n e l
Bay
Liao
Point Merriam
Point
Discovery
Point
Eagle
Ship
Phantom
Chaski Bay
Bay
Danger
Rock
Sentinel
Bay
Cloudcap
Cove
Grotto
W E S
T
R d
V a ll e y
Cas tle
Cre ek
T ra p p e r
C re e k
Campground
Mazama
EAST
E A
R
IV
E
(D e a d E n d R o a d
OR NPS CRLA 2018(1)
portable changeable message sign (1)
Temporary traffic control, portable changeable message sign (1)
Temporary traffic control, m ile s
T o K la m a th Fa lls
~18 miles
To Union Creek m il e
T o N o r th E n tr a n c e
Overlook
Skell Head
:2 u ly
T
E M
P O
R A
R Y
T R
A F
F
IC
C O
N T
R O
L V
IC
IN
IT
Y
M p w w o r k
\d
\c r la
J
.d g n
VICINITY MAP
TEMPORARY TRAFFIC CONTROL
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) J.2
GPS
10008
G
DI
G
RP
RP
G
GPS
10008
CP
CP
CP
CP
TP
SG1901
SG19-01
see sheet J.4 for details trailhead parking lot, Cleetwood Cove
50 10002550
Scale in feet
N
RIM
Line to be constructed
G20-2
R8-3a
W20-7
R8-3a
W3-4
R8-3a
W20-1
R8-3a
G20-1
G20-2
ROAD WORK
NEXT 1 MILES
ROAD WORK
END
NO
PARKING
WORK
ROAD
AHEAD
NO
PARKING
NO
PARKING
NO
PARKING
BE
PREPARED
TO STOP
EAST DRIVE
ROAD WORK
END
BE
PREPARED
TO STOP
WORK
ROAD
AHEAD
ROAD WORK
NEXT 1 MILES
W20-7
W3-4
R8-3a
NO
PARKING
NO
PARKING
R8-3a
NO
PARKING
R8-3a
NO
PARKING
R8-3a
W20-1
G20-1
Temporary traffic control, flagger (traihead) Temporary traffic control, construction sign (SIGN A) (2 EACH), Temporary traffic control, barricade type 2 (2 EACH), Temporary traffic control, construction sign (R11-2) (3 EACH) Temporary traffic control, barricade type 3 (3 EACH), Temporary traffic control, drum (6 EACH) R8-3a
NO
PARKING
R8-3a
NO
PARKING
R8-3a
NO
PARKING
R8-3a
NO
PARKING
Temporary traffic control, construction sign (SIGN B, 4 EACH) Fence, chain link, 72-inch height (temporary), Temporary traffic control, construction sign (SIGN B, 4 EACH) Fence, chain link, 72-inch height (temporary), NOTE
1. Space "NO PARKING" R8-3a signs every 100 foot.
100'100'100'
:5 u ly
T
E M
P O
R A
R Y
T R
A F
F
IC
C O
N T
R O
L S
IG
N
L A
Y O
U p w
-w o rk
\d \c rl a J -0
.d g n
SIGN LAYOUT
TEMPORARY TRAFFIC CONTROL
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) J.3
NPS Drwg No. 186271 NPS PMIS No. 264912
TRAIL
CLOSEDNOT FOR CONSTRUCTION
G
I
G
R P
G
C P
C P
C P
S G
S G
50 10002550
Scale in feet
NOTE
1. Space barricade type 2 every 50 foot.
N from East Rim Drive to restroom
Maintain safe pesestrain public access
Temporary traffic control, construction sign (SIGN C, 12 EACH)
Temporary traffic control, barricade type 2 (12 EACH), Temporary traffic control, construction sign (SIGN C, 8 EACH)
Temporary traffic control, barricade type 2 (8 EACH), E A S
T R
IM
D
R
IV
E
:1 u ly
C
L E
E T
W O
O D
C O
V E
T R
A
IL
H E
A D
P A
R K
IN
G
L O
T S
T A
G
IN
G A
R E p w w o r k
\d
\c r la
J
.d g n
PARKING LOT STAGING AREA
CLEETWOOD COVE TRAILHEAD
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) J.4
NPS Drwg No. 186271 NPS PMIS No. 264912
NO
PARKING
ON
SIDEWALK
NO
PARKING
ON
SIDEWALK
ROAD WORK
END
WORK
ROAD
AHEAD
ROAD NAME
WORK
ROAD
AHEAD
ROAD WORK
END
WORK
ROAD
xxxxx
WORK
ROAD
xxxxxxx
ROAD WORK
NEXT xx MILES
WORK
ROAD
AHEAD
xx
MPH
ROAD NAME
ROAD WORK
END
WORK
ROAD
xxxxxxx
ROAD WORK
END
xx
MPH
WORK
ROAD
xxxxxxx
ROAD WORK
NEXT xx MILES
13.
12.
11.
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.
ROAD TYPE
DISTANCE BETWEEN
A B C
NOTE:
M in o r R o a d
M a jo r R o a d
See Note 8 W16-8P W20-1 over
W20-1
G20-2
See Note 9 W20-1
See Note 9 W20-1
(optional) W13-1P
See Note 10 G20-1
G20-2
See Note 8 W16-8P W20-1 over
G20-2
G20-2
See Note 9 W20-1
See Note 9 W20-1
(optional) W13-1P
See Note 10 G20-1 the distance to the work area in feet or in miles. Install an additional W20-1 The message on the W20-1 signs may be ROAD WORK AHEAD or may specify of the road on which the construction does occur (applies to major roads only).
construction work occurs, include a supplementary plaque indicating the name If W20-1 is placed on a roadway other than that on which the actual
Cover post-mounted signs when not applicable.
Do not store traffic control devices along the roadway when not in use.
the CO.
Maintain two-way traffic during all non-work hours except as approved by
NCHRP-350 or MASH for crashworthiness.
Ensure all sign supports exposed to impact by traffic meet the requirements of indicate a maximum recommended speed through the construction area.
Install advisory speed plates under the W20 series warning signs as needed to
Vary messages as required.
signs, locate the warning signs to fit field conditions as approved by the CO.
Where advance warning signs, placed as shown, interfere with permanent this traffic control plan as necessary to accommodate actual operations.
to this project. The Contractor may add or delete information and details in Not all details shown on the temporary traffic control sheets may be applicable
Erect all project advance warning signs before starting construction work.
retroreflective sheeting types.
Refer to Section 635 of the Special Contract Requirements for allowable
State standards may be used as an alternative if approved by the CO.
verify that an encroachment permit has been obtained.
If signing on a roadway under a jurisdiction other than the client agency, whole mile.
each end of the project. Show the distance on the G20-1 sign to the nearest
Ro ad N ame
SIGN SPACING TABLE
For work zones that are 2 miles or more in length, install G20-1 signs at signs "B" feet apart according to the Sign Spacing Table.
sign when approach speeds exceed 50 MPH. When used, place the two W20-1
C
B as de ter mi ne d b y t he C
O
Wor k z on e A re a o f I nfl ue nc e
(S ee S ign S pa cin g T ab le)
ADVANCE W
ARNI
NG
AREA
(S ee S ign S pa cin g T ab le)
ADVANCE W
ARNI
NG
AREA
A
B
C
A
A
A
A
Pr oje ct Lim its
Expressway / Freeway
SIGNS IN FEET
Rural greater than 50 MPH
Urban and Rural 35 MPH to 50 MPH
Urban and Rural 30 MPH and less
6/2005 STANDARD APPROVED FOR USE
7/2022 REVISED: 635-1
ADVANCE SIGNING
TEMPORARY TRAFFIC CONTROL
FLH STANDARD
STANDARD
OFFICE OF FEDERAL LANDS HIGHWAY
FEDERAL HIGHWAY ADMINISTRATION
U.S. DEPARTMENT OF TRANSPORTATION
:2
J u n e
S td
-1 p w
-w o rk
\d \c rl a J S td -1
.d g n
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) J.5
posted speed, not the advisory speed.
Approach speed based on the regulatory *
6.
5.
4.
3.
2.
1.
the buffer space.
Do not allow equipment, materials, or vehicles to be parked or stored in
For night time flagging operation, provide floodlighting at flagger stations.
WORK AHEAD (W20-1) and END ROAD WORK (G20-2) signs.
If closure is completely within the project limits, eliminate the ROAD name of the Contractor on the pilot car.
a conspicuous location on the rear of vehicle. Prominently display the
For pilot car operation, mount the PILOT CAR FOLLOW ME (G20-4) sign at as approved by the CO.
Final location and spacing of devices may be changed to fit field conditions those depicted for the opposite direction of travel.
Signs are shown for one direction of travel only. Place signs similar to
Flagger location
WORK
ROAD
AHEAD
See Note 4
W20-1
BE
PREPARED
TO STOP
W20-7
(optional)
W16-2Pxxx
FEET
Flagger location
ROAD WORK
END
See Note 4
G20-2
W3-4
Traffic flow
Traffic flow
NOTE:LENGTH AND SPACING TABLE SIGN SPACING TABLE
LENGTH
BUFFER SPACE
SPEED*
APPROACH
BUFFER SPACE
(optional)
Spacing Table)
(See Length and
ADVANCE WARNING AREA (See Sign Spacing Table)
TERMINATION AREAVARIABLEBUFFER SPACEABC
Spacing Table)
(See Length and WORK SPACE
A
ROAD TYPE
DISTANCE BETWEEN
A B C
Expressway / Freeway
SIGNS IN FEET
Rural greater than 50 MPH
Urban and Rural 35 MPH to 50 MPH
Urban and Rural 30 MPH and less
FEETMPH
7/2022 REVISED:
635-5
(WITH FLAGGERS)
ROAD CLOSURE LAYOUT
TEMPORARY TRAFFIC CONTROL
FLH STANDARD
STANDARD
OFFICE OF FEDERAL LANDS HIGHWAY
FEDERAL HIGHWAY ADMINISTRATION
U.S. DEPARTMENT OF TRANSPORTATION
:1 u ly
S td p w w o r k \d
\c r la
J S td .d g n
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) J.6
See post detail (typ.)
Break-away holes.
See table for hole size parallel to sign face.
Field drill holes through post
Bottom of sign panel
Post�
Local tangent
< 10
" dia. bolts 4 1Attach sign panels with a minimum of 2 -a minimum lateral distance of 1' behind the face of lateral offset of 2' may be used. In areas with curbs, 6" x 6" or larger.
Use 7' minimum spacing between posts for sign posts and 6' minimum mounting height for secondary sign.
use 7' minimum mounting height for main sign
NOTE:
WOOD POST SELECTION TABLE
7.
6.
5.
4.
3.
2.
1.
In areas where lateral distance is limited, a minimum
D = Post embedment depth for average soil conditions.
Select post lengths to fit field conditions.
H1 and H2 = Overall post length.
per post.
In pedestrian locations, or in areas with obstructed views, the curb may be used.
by the CO.
State standards may be used as an alternative if approved
SINGLE POST SIGN TWO POST SIGN
SIGN INSTALLATION ANGLE
POST DETAIL
E d g e o f p a v e d s h o u ld e r
E d g e o f tr a v e le d w a y
90°
93° "X"
WIDTH AREA
OF POSTS
NUMBER POST SIZE D HOLE SIZE
X X
0.75X
H
H
X
0.2X0.6X 0.2X
Y
H
D
H
D
H
D
Long side of post
D
(SQFT)
Other Shapes ≤ 48" Diamond ≤ 36"
Other Shapes ≤ 12' Diamond ≤ 48"
(INCH) (INCH) (INCH)
Diamond ≤ 48"
65 - 95
65 - 95
50 - 65
50 - 65
20 - 50
10 - 20
10 - 20
> 30'
> 17'
12' - 16'
> 13'
6 x 6
4 x 6
4 x 6
6 x 6
4 x 6
4 x 4
6 x 6
4 x 6
4 x 4
1.5
1.5
1.5
1.5
S e e N o te m in
S e e N o te m in
See Note 4
6' - 12'
On tangent alignment
200'
7/2022 REVISED: 635-14
WOOD POSTS
SIGN INSTALLATION
TEMPORARY TRAFFIC CONTROL
:2
J u n e
S td
-1 p w
-w o rk \d
\c rl a
J
S td
-1
.d g n
FLH STANDARD
STANDARD
OFFICE OF FEDERAL LANDS HIGHWAY
FEDERAL HIGHWAY ADMINISTRATION
U.S. DEPARTMENT OF TRANSPORTATION
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) J.7
See USDOT Pictograph spaced 0.5-inch apart
Three 0.5-inch stripes
See NPS Pictograph and Note 3 5 .2
.5
.2
.5
0.4510.2
0.675
2.25
0.675
0.4510.23.6
0.510.153.6
0.52 sqftArea:
Background - Blue (retroreflective)
Legend - White (retroreflective)Colors:
USDOT PICTOGRAPH
9.7652.489.76
22.52722.5
164016
3.7664.483.76
5.660.85.6
9.76 9.76
.3
.2
E
E
C
C
.3
BIL PROJECT FUNDING SOURCE SIGN
24 sqftArea:
Background - Green (retroreflective)
Legend, Border - White (retroreflective)Colors:
2.3" Radius, 1" BorderDimensions:
Ensure all pictographs are vector-based, vinyl-ready.
All incorporated pictographs are subject to approval. 3.
requirements.
Refer to Standard 635-14 for post and sign mounting 2.
Unless otherwise noted, dimensions are inches.1.
NOTES:
1.175
0.5C
0.7
0.5C
0.7
0.5C
1.175
14.25
Background - White (retroreflective)
Border - White (retroreflective)
Legend - PMS 1615, Brown (retroreflective)Colors:
NPS PICTOGRAPH
.2
:2 u ly
B
IP
A
R T
IS
A
N I
N F
R A
S T
R U
C T
U R
E L
A W
S
IG
N
N P p w w o r k
\d
\c r la
J b il s ig n .d g n
LAW SIGN (NPS)
BIPARTISAN INFRASTRUCTURE
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) J.8
STONE BENCH DETAIL
2. Grade around the becnh to be a 2% or less slope.
1. Dimensions are approximate and may be adjusted by CO.
FOOTNOTE:
Construct slope directing towards Crater Lake.
1.5%
TRAIL
3.5'
1.5'
:4
J u n e
S to n e b e n c h d e ta il p w w o r k
\d
\c r la
P
L N
N
.d g n
STONE BENCH DETAIL
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) N.1
BOULDER DETAIL
Boulder 3
Boulder3
NOTE:
Boulder
3. Dimensions are approximate and may be adjusted by CO.
2. Distance between log and boulders will vary. CO to field adjust.
1. Field adjust per direction of CO.
Existing ground typical section details
See Section C for
BOULDER TYPICAL SECTION
LC
:2 u ly
B
O U
L D
E R
D E
T p w w o r k
\d
\c r la
P
L N
N
.d g n
BOULDER DETAIL
STATE PROJECT
NUMBER
SHEET
OR NPS CRLA 2018(1) N.2
NPS CRLA 2018(1)
NPS PMIS No. 264912 NPS Drwg No. 186271
See Section C for details
NPS Drwg No. 186271NPS PMIS No. 264912
T.1
64605-0000
64603-0000
64603-0000 64603-0000
64603-0000
64603-0000
64603-0000
64605-0000
Fixture (Gangway)
Fixture (Floats, Type 1)
Fixture (Life Ring Station)
Fixture (Fire Extinguisher Station) Fixture (Safety Ladder) Fixture (Gangway Hoist Assembly)
Fixture (Floats, Type 2)
Fixture (Floats, Type 3)
55401-1000 Reinforcing Steel (Galvanized)
T.14.T.7
T.7
4716.
T.2T.11
T.6 T.11
T.8
T.4, T.11
T.19, T.16
T.16
T.16
T.15
T.18
T.18
T.15
T.3
T.7
T.5, T.6
T.4
T.4
T.19, T.15
T.9
T.10
T.11
T.9
T.4
T.5
See final Geotechnical report GR05-24.
T.5
T.6 T.11
T.4)
T.12, T.12.
T.6sheet T.8
T.8
T.8
T.5 T.8
T.8, T.8
T.8, T.7
T.8
T.9.
T.8
T.9.
T.9
T.10
T.1 646.
T.8
T.6
T.6
T.9
T.10
T.11.
T.10
T.15
T.11
T.12 T.12
T.4
T.12.
T.4 T.5
T.12
T.12NOT FOR CONSTRUCTION
T.12
T.13
T.13
T.5
T.13
T.13
T.14
T.10.
T.1
T.1.
646.
T.15T.17
T.18T.18
T.19, T.19, T.10
T.14
T.16
T.14
T.17
T.17
T.17
T.19, T.17NOT FOR CONSTRUCTION
T.17
T.18
T.2
T.2.
T.19
CONCESSION BUILDING PLAN
NPS PMIS No. 000000 NPS Drwg No. XXX/XXXX
STATE PROJECT SHEET
NUMBER
C X
D X
C X
B X
TICKET BOOTH BUILDING PLAN
D
NOT TO SCALE
NOT TO SCALE
NOTES:
1.
2.
3.
THIS PLAN IS PROVIDED FOR REFERENCE ONLY AND IS NOT TO SCALE
THIS PLAN IS INTENDED TO SHOW THE GENERALIZED BUILDING COMPONENTS, LAYOUT, AND
DIMENSIONS REQUIRED.
THE BASIS OF THIS DESIGN IS A CXT SCHWEITZER (10.5'x12') UNIT.
STEEL DOUBLE DOORS
WITH STAINLESS LOCKSET
ROLL UP SHUTTER
CONCESSION WINDOW
NOTES:
REFERENCE CIVIL DRAWINGS FOR SITE LOCATION.
CONSTRUCT PRECAST TICKET
BOOTH BUILDING
PRECAST CONCRETE
BOARD AND BATTEN
PATTERN SIDING
PRECAST CONCRETE
BOARD AND BATTEN
PATTERN SIDING
OR NPS CRLA 2018(1) P.2
TOILET DEMOLITION
STATE PROJECT SHEET
NUMBER
264912
OR NPS CRLA 2018(1) Y.2
186271
-2.0%
-2.0%
TOILET PLAN
NPS PMIS No. 000000 NPS Drwg No. XXX/XXXX
STATE PROJECT SHEET
NUMBER
A X
B X
A X
B X
264912
OR NPS CRLA 2018(1) Y.3
PRECAST BUILDING PLAN
STATE PROJECT SHEET
NUMBER
264912
OR NPS CRLA 2018(1) Y.4