Corrections Distribution Warehouse Bldg 3 Restrooms Specs~1.pdf

PDF 1 MB Posted

Attached to
Central Distribution Center Building 3 Bathroom Remodel Rebid
Solicitation number
S-29100-00012927
Issued by
Marion County, Oregon

About this file

This is a technical specification file detailing the requirements for plumbing systems and restroom renovations at Building 3 of a Corrections Distribution Warehouse. The specifications outline comprehensive requirements for plumbing materials and installation including piping, valves, hangers, supports, insulation, and identification systems. The work involves installing new restroom facilities with associated plumbing infrastructure including hot and cold water supply lines, waste lines, fixtures, and accessories. The specifications require coordination with other trades and compliance with all applicable building codes and standards including seismic requirements.

The specifications emphasize quality assurance requirements, with materials needing to be new, UL listed where applicable, and installed according to manufacturer specifications. Special attention is given to proper identification of piping systems, thermal insulation requirements, and seismic bracing. The document includes detailed execution requirements for installation, testing, and commissioning of the plumbing systems. While specific pricing information is not included, the specifications require comprehensive submittals including product data, shop drawings, and warranties for all components. The contractor must also provide complete operations and maintenance documentation upon completion.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS S3A

2022-199

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

TABLE OF CONTENTS

00 0110

SECTION 00 0110

TABLE OF CONTENTS

SPECIFICATIONS

1.01 DIVISION 06 -- WOOD, PLASTICS, AND COMPOSITES

A. 06 1000 - Rough Carpentry

1.02 DIVISION 08 -- OPENINGS

A. 08 1213 - Hollow Metal Frames B. 08 1416 - Flush Wood Doors C. 08 7100 - Door Hardware D. 08 7113 - Power Door Operators

1.03 DIVISION 09 -- FINISHES

A. 09 2116 - Gypsum Board Assemblies B. 09 6500 - Resilient Flooring C. 09 9123 - Interior Painting

1.04 DIVISION 22 -- PLUMBING

A. 22 0000 - General Requirements for Plumbing B. 22 0516 - Expansion Fittings and Loops for Plumbing Piping C. 22 0517 - Sleeves and Sleeve Seals for Plumbing Piping D. 22 0523 - General-Duty Valves for Plumbing Piping E. 22 0529 - Hangers and Supports for Plumbing Piping and Equipment F. 22 0553 - Identification for Plumbing Piping and Equipment G. 22 0719 - Plumbing Piping Insulation H. 22 1005 - Plumbing Piping I. 22 1006 - Plumbing Piping Specialties J. 22 3000 - Plumbing Equipment K. 22 4000 - Plumbing Fixtures

1.05 DIVISION 23 -- HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)

A. 23 0000 - General Reqiurements for HVAC B. 23 0529 - Hangers and Supports for HVAC Piping and Equipment C. 23 0553 - Identification for HVAC Piping and Equipment D. 23 3100 - HVAC Ducts and Casings E. 23 3423 - HVAC Power Ventilators F. 23 8126.13 - Small-Capacity Split-System Air Conditioners

1.06 DIVISION 26 -- ELECTRICAL

A. 26 0000 - General Requirements for Electrical B. 26 0505 - Selective Demolition for Electrical C. 26 0519 - Low-Voltage Electrical Power Conductors and Cables D. 26 0526 - Grounding and Bonding for Electrical Systems E. 26 0529 - Hangers and Supports for Electrical Systems

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS S3A

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

TABLE OF CONTENTS

00 0110

F. 26 0533.13 - Conduit for Electrical Systems G. 26 0533.16 - Boxes for Electrical Systems H. 26 0553 - Identification for Electrical Systems I. 26 0583 - Wiring Connections J. 26 0923 - Lighting Control Devices K. 26 2816.16 - Enclosed Switches L. 26 5100 - Interior Lighting

END OF SECTION 00 0110

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES S3A

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

ROUGH CARPENTRY

06 1000

SECTION 06 1000

ROUGH CARPENTRY

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Nonstructural dimension lumber framing.

1.02 REFERENCE STANDARDS

A. ASTM A153/A153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware; 2023.

B. PS 20 - American Softwood Lumber Standard; 2021.

1.03 DELIVERY, STORAGE, AND HANDLING

A. General: Cover wood products to protect against moisture. Support stacked products to prevent deformation and to allow air circulation.

PART 2 PRODUCTS

2.01 GENERAL REQUIREMENTS

A. Dimension Lumber: Comply with PS 20 and requirements of specified grading agencies.

1. If no species is specified, provide species graded by the agency specified; if no grading agency is specified, provide lumber graded by grading agency meeting the specified requirements.

2. Grading Agency: Grading agency whose rules are approved by the Board of Review, American Lumber Standard Committee at www.alsc.org, and who provides grading service for the species and grade specified; provide lumber stamped with grade mark unless otherwise indicated.

2.02 DIMENSION LUMBER

A. Sizes: Nominal sizes as indicated on drawings, S4S.

B. Stud Framing (2 by 2 through 2 by 6 (50 by 50 mm through 50 by 150 mm) ):

1. Grade: No. 2.

C. Miscellaneous Framing, Blocking, Nailers, Grounds, and Furring:

1. Lumber: S4S, No. 2 or Standard Grade.

2. Boards: Standard or No. 3.

2.03 ACCESSORIES

A. Fasteners and Anchors:

1. Metal and Finish: Hot-dipped galvanized steel complying with ASTM A153/A153M for high humidity and preservative-treated wood locations, unfinished steel elsewhere.

PART 3 EXECUTION

3.01 INSTALLATION - GENERAL

A. Select material sizes to minimize waste.

B. Reuse scrap to the greatest extent possible; clearly separate scrap for use on site as accessory components, including: shims, bracing, and blocking.

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES S3A

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

ROUGH CARPENTRY

06 1000

3.02 FRAMING INSTALLATION

A. Set structural members level, plumb, and true to line. Discard pieces with defects that would lower required strength.

B. Make provisions for temporary construction loads, and provide temporary bracing sufficient to maintain structure in true alignment and safe condition until completion of erection and installation of permanent bracing.

C. Install structural members full length without splices unless otherwise specifically detailed.

D. Comply with member sizes, spacing, and configurations indicated, and fastener size and spacing indicated, but not less than required by applicable codes.

E. Construct double joist headers at floor and ceiling openings and under wall stud partitions that are parallel to floor joists; use metal joist hangers unless otherwise detailed.

F. Frame wall openings with two or more studs at each jamb; support headers on cripple studs.

3.03 BLOCKING, NAILERS, AND SUPPORTS

A. Provide framing and blocking members as indicated or as required to support finishes, fixtures, specialty items, and trim.

B. In framed assemblies that have concealed spaces, provide solid wood fireblocking as required by applicable local code, to close concealed draft openings between floors and between top story and roof/attic space; other material acceptable to authorities having jurisdiction may be used in lieu of solid wood blocking.

C. In walls, provide blocking attached to studs as backing and support for wall-mounted items, unless item can be securely fastened to two or more studs or other method of support is explicitly indicated.

3.04 TOLERANCES

A. Framing Members: 1/4 inch (6 mm) from true position, maximum.

B. Variation from Plane, Other than Floors: 1/4 inch in 10 feet (2 mm/m) maximum, and

1/4 inch in 30 feet (7 mm in 10 m) maximum.

END OF SECTION 06 1000

DIVISION 08 - OPENINGS S3A

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

HOLLOW METAL FRAMES

08 1213

SECTION 08 1213

HOLLOW METAL FRAMES

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Non-fire-rated hollow metal frames for non-hollow metal doors.

1.02 REFERENCE STANDARDS

A. ADA Standards - 2010 ADA Standards for Accessible Design; 2010.

B. ANSI/SDI A250.8 - Specifications for Standard Steel Doors and Frames (SDI-100); 2023.

C. ANSI/SDI A250.10 - Test Procedure and Acceptance Criteria for Prime Painted Steel

Surfaces for Steel Doors and Frames; 2020.

D. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process; 2023.

E. ASTM A1008/A1008M - Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Required Hardness, Solution Hardened, and Bake Hardenable; 2023, with Editorial Revision.

F. ASTM A1011/A1011M - Standard Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, and Ultra-High Strength; 2023.

G. ASTM C143/C143M - Standard Test Method for Slump of Hydraulic-Cement Concrete;

2020.

H. ASTM C476 - Standard Specification for Grout for Masonry; 2023.

I. BHMA A156.115 - Hardware Preparation in Steel Doors and Frames; 2016.

J. ICC A117.1 - Accessible and Usable Buildings and Facilities; 2017.

K. NAAMM HMMA 830 - Hardware Selection for Hollow Metal Doors and Frames; 2002.

L. NAAMM HMMA 831 - Hardware Locations for Hollow Metal Doors and Frames; 2011.

M. NAAMM HMMA 840 - Guide Specifications for Receipt, Storage and Installation of

Hollow Metal Doors and Frames; 2024.

N. NAAMM HMMA 861 - Guide Specifications for Commercial Hollow Metal Doors and

Frames; 2014.

O. SDI 117 - Manufacturing Tolerances for Standard Steel Doors and Frames; 2023.

1.03 SUBMITTALS

A. Product Data: Materials and details of design and construction, hardware locations, reinforcement type and locations, anchorage and fastening methods, and finishes; and one copy of referenced grade standard.

B. Shop Drawings: Details of each opening, showing elevations, glazing, frame profiles, and identifying location of different finishes, if any.

1.04 DELIVERY, STORAGE, AND HANDLING

A. Store in accordance with applicable requirements and in compliance with standards and/or custom guidelines as indicated.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

HOLLOW METAL FRAMES

08 1213

B. Protect with resilient packaging; avoid humidity build-up under coverings; prevent corrosion.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Hollow Metal Frames:

1. Ceco Door, an Assa Abloy Group company: www.assaabloydss.com/#sle.

2. Curries, an Assa Abloy Group company: www.assaabloydss.com/#sle.

3. Republic Doors, an Allegion brand: www.republicdoor.com/#sle.

4. Steelcraft, an Allegion brand: www.allegion.com/#sle.

5. Or approved equivalent.

2.02 PERFORMANCE REQUIREMENTS

A. Door Frame Type: Provide hollow metal door frames with integral casings.

1. Interior Doors: Use frames with integral casings.

B. Steel Sheet: Comply with one or more of the following requirements; galvannealed steel complying with ASTM A653/A653M, cold-rolled steel complying with ASTM A1008/A1008M, or hot-rolled pickled and oiled (HRPO) steel complying with ASTM A1011/A1011M, commercial steel (CS) Type B, for each.

C. Accessibility: Comply with ICC A117.1 and ADA Standards.

D. Combined Requirements: If a particular door and frame unit is indicated to comply with more than one type of requirement, comply with the specified requirements for each type; for instance, an exterior frame that is also indicated as being sound-rated must comply with the requirements specified for exterior frames and for sound-rated frames; where two requirements conflict, comply with the most stringent.

E. Hardware Preparations, Selections and Locations: Comply with BHMA A156.115, NAAMM HMMA 830, NAAMM HMMA 831 or ANSI/SDI A250.8 (SDI-100) in accordance with specified requirements.

2.03 HOLLOW METAL DOOR FRAMES WITH INTEGRAL CASINGS

A. Frame Finish: Factory primed and field finished.

B. Interior Door Frames, Non-Fire Rated: Full profile/continuously welded type.

2.04 FINISHES

A. Primer: Rust-inhibiting, complying with ANSI/SDI A250.10, door manufacturer's standard.

2.05 ACCESSORIES

A. Silencers: Resilient rubber, fitted into drilled hole; provide three on strike side of single door, three on center mullion of pairs, and two on head of pairs without center mullions.

B. Grout for Frames: Mortar grout complying with ASTM C476 with maximum slump of 4 inches (102 mm) as measured in accordance with ASTM C143/C143M for hand troweling in place; plaster grout and thinner pumpable grout are prohibited.

C. Temporary Frame Spreaders: Provide for factory- or shop-assembled frames.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

HOLLOW METAL FRAMES

08 1213

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify existing conditions before starting work.

B. Verify that opening sizes and tolerances are acceptable.

C. Verify that finished walls are in plane to ensure proper door alignment.

3.02 PREPARATION

A. Coat inside of frames to be installed in masonry or to be grouted, with bituminous coating, prior to installation.

3.03 INSTALLATION

A. Install frames in accordance with manufacturer's instructions and related requirements of specified frame standards or custom guidelines indicated.

B. Coordinate frame anchor placement with wall construction.

C. Grout frames using hand trowel methods; brace frames so that pressure of grout before setting will not deform frames.

D. Install door hardware as specified in Section 08 7100.

3.04 TOLERANCES

A. Clearances Between Door and Frame: Comply with related requirements of specified frame standards or custom guidelines indicated in accordance with SDI 117 or NAAMM

HMMA 861.

B. Maximum Diagonal Distortion: 1/16 inch (1.5 mm) measured with straight edges, crossed corner to corner.

END OF SECTION 08 1213

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

HOLLOW METAL FRAMES

08 1213

This page intentionally left blank

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

FLUSH WOOD DOORS

08 1416

SECTION 08 1416

FLUSH WOOD DOORS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Flush wood doors; flush configuration; non-rated.

1.02 REFERENCE STANDARDS

A. AWI/AWMAC/WI (AWS) - Architectural Woodwork Standards, 2nd Edition; 2014, with Errata (2016).

B. AWMAC/WI (NAAWS) - North American Architectural Woodwork Standards; 2021, with Errata.

1.03 SUBMITTALS

A. Product Data: Indicate door core materials and construction; veneer species, type and characteristics.

B. Shop Drawings: Show doors and frames, elevations, sizes, types, swings, undercuts, beveling, blocking for hardware, factory machining, factory finishing, cutouts for glazing and other details.

1.04 DELIVERY, STORAGE, AND HANDLING

A. Package, deliver and store doors in accordance with specified quality standard.

B. Accept doors on site in manufacturer's packaging, and inspect for damage.

C. Protect doors with resilient packaging sealed with heat shrunk plastic; do not store in damp or wet areas or areas where sunlight might bleach veneer; seal top and bottom edges with tinted sealer if stored more than one week, and break seal on site to permit ventilation.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Wood Veneer Faced Doors:

1. Lynden Door or approved equivalent.

2.02 DOORS

A. Doors:

1. Quality Standard: Custom Grade, Heavy Duty performance, in accordance with AWI/AWMAC/WI (AWS) or AWMAC/WI (NAAWS), unless noted otherwise.

2. Wood Veneer Faced Doors: 5-ply unless otherwise indicated.

B. Interior Doors: 1-3/4 inches (44 mm) thick unless otherwise indicated; flush construction.

1. Provide solid core doors at each location.

2.03 DOOR AND PANEL CORES

A. Non-Rated Solid Core and 20 Minute Rated Doors: Type particleboard core (PC), plies and faces as indicated.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

FLUSH WOOD DOORS

08 1416

2.04 DOOR FACINGS

A. Veneer Facing for Transparent Finish: Birch, Maple, or similar, veneer grade in accordance with quality standard indicated, plain sliced (flat cut), with book match between leaves of veneer, running match of spliced veneer leaves assembled on door or panel face.

2.05 DOOR CONSTRUCTION

A. Fabricate doors in accordance with door quality standard specified.

B. Cores Constructed with stiles and rails:

1. Provide solid blocks at lock edge for hardware reinforcement.

C. Factory machine doors for hardware other than surface-mounted hardware, in accordance with hardware requirements and dimensions.

D. Factory fit doors for frame opening dimensions identified on shop drawings, with edge clearances in accordance with specified quality standard.

E. Provide edge clearances in accordance with the quality standard specified.

2.06 FINISHES - WOOD VENEER DOORS

A. Finish work in accordance with AWI/AWMAC/WI (AWS) or AWMAC/WI (NAAWS), Section 5 - Finishing for grade specified.

2.07 ACCESSORIES

A. Hollow Metal Door Frames: See Section 08 1213.

B. Door Hardware: See Section 08 7100.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify existing conditions before starting work.

B. Verify that opening sizes and tolerances are acceptable.

C. Do not install doors in frame openings that are not plumb or are out-of-tolerance for size or alignment.

3.02 INSTALLATION

A. Install doors in accordance with manufacturer's instructions and specified quality standard.

B. Factory-Finished Doors: Do not field cut or trim; if fit or clearance is not correct, replace door.

C. Use machine tools to cut or drill for hardware.

D. Coordinate installation of doors with installation of frames and hardware.

3.03 TOLERANCES

A. Comply with specified quality standard for fit and clearance tolerances.

B. Comply with specified quality standard for telegraphing, warp, and squareness.

3.04 ADJUSTING

A. Adjust doors for smooth and balanced door movement.

B. Adjust closers for full closure.

END OF SECTION 08 1416

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

DOOR HARDWARE

08 7100

SECTION 08 7100

DOOR HARDWARE

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Hardware for wood doors.

B. Weatherstripping and gasketing.

1.02 REFERENCE STANDARDS

A. ADA Standards - 2010 ADA Standards for Accessible Design; 2010.

B. BHMA A156.1 - Standard for Butts and Hinges; 2021.

C. BHMA A156.6 - Standard for Architectural Door Trim; 2021.

D. BHMA A156.16 - Standard for Auxiliary Hardware; 2023.

E. BHMA A156.18 - Standard for Materials and Finishes; 2020.

F. BHMA A156.22 - Standard for Gasketing; 2021.

G. BHMA A156.36 - Auxiliary Locks; 2020.

H. DHI (LOCS) - Recommended Locations for Architectural Hardware for Standard Steel

Doors and Frames; 2004.

I. ICC A117.1 - Accessible and Usable Buildings and Facilities; 2017.

1.03 ADMINISTRATIVE REQUIREMENTS

A. Coordinate the manufacture, fabrication, and installation of products that door hardware is installed on.

B. Furnish templates for door and frame preparation to manufacturers and fabricators of products requiring internal reinforcement for door hardware.

1.04 SUBMITTALS

A. Product Data: Manufacturer's catalog literature for each type of hardware, marked to clearly show products to be furnished for this project, and includes construction details, material descriptions, finishes, and dimensions and profiles of individual components.

B. Manufacturer's Installation Instructions: Indicate special procedures and perimeter conditions requiring special attention.

C. Maintenance Data: Include data on operating hardware, lubrication requirements, and inspection procedures related to preventative maintenance.

1.05 DELIVERY, STORAGE, AND HANDLING

A. Package hardware items individually; label and identify each package with door opening code to match door hardware schedule.

PART 2 PRODUCTS

2.01 DESIGN AND PERFORMANCE CRITERIA

A. Provide specified door hardware as required to make doors fully functional, compliant with applicable codes, and secure to extent indicated.

B. Provide individual items of single type, of same model, and by same manufacturer.

C. Provide door hardware products that comply with the following requirements:

1. Applicable provisions of federal, state, and local codes.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

DOOR HARDWARE

08 7100

2. Accessibility: ADA Standards and ICC A117.1.

D. Fasteners:

1. Provide fasteners of proper type, size, quantity, and finish that comply with commercially recognized standards for proposed applications.

a. Aluminum fasteners are not permitted.

b. Provide phillips flat-head screws with heads finished to match door surface hardware unless otherwise indicated.

2.02 HINGES

A. Manufacturers:

1. McKinney; an Assa Abloy Group company; T4A3786: www.assaabloydss.com/#sle.

2. Ives; an Allegion brand; 5BB1HW: us.allegion.com/#sle.

3. Or approved equivalent.

B. Hinges: Comply with BHMA A156.1, Grade 1.

1. Provide hinges on every swinging door.

2. Provide five-knuckle full mortise butt hinges unless otherwise indicated.

3. Provide ball-bearing hinges at each door.

4. Provide non-removable pins on interior outswinging doors at locations as indicated in Door Hardware Schedule.

5. Provide power transfer hinges where electrified hardware is mounted in door leaf.

6. Provide following quantity of butt hinges for each door:

a. Doors From 60 inches (1.5 m) High up to 90 inches (2.3 m) High: Three hinges.

2.03 AUXILIARY LOCKS (DEADLOCKS)

A. Manufacturers:

1. Falcon, an Allegion brand; MA941: www.allegion.com/us/#sle.

2. Or approved equivalent.

B. Auxiliary Locks (Deadlocks): Comply with BHMA A156.36, Grade 1.

1. Type: Mortise.

2. Provide indicator trim.

3. Provide monitor strike to disable operator when door is locked.

2.04 DOOR PULLS AND PUSH PLATES

A. Manufacturers:

1. Rockwood; an Assa Abloy Group company: www.assaabloydss.com/#sle.

2. Ives; an Allegion Brand: www.allegion.com/#sle.

3. Or approved equivalent.

B. Door Pulls and Push Plates: Comply with BHMA A156.6.

1. Pull Type: Straight, unless otherwise indicated.

2. Push Plate Type: Flat, with square corners, unless otherwise indicated.

a. Edges: Square, unless otherwise indicated.

3. Material: Stainless steel, unless otherwise indicated.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

DOOR HARDWARE

08 7100

2.05 POWER DOOR OPERATORS

A. See Section 08 7113.

2.06 PROTECTION PLATES

A. Manufacturers:

1. Rockwood; an Assa Abloy Group company: www.assaabloydss.com/#sle.

2. Ives, an Allegion brand: www.allegion.com/us/#sle.

3. Or approved equivalent.

B. Protection Plates: Comply with BHMA A156.6.

C. Kick Plates: Provide along bottom edge of push side of door.

1. Size: 12 inch (305 mm) high by 2 inch (51 mm) less door width (LDW) on push side of door.

D. Metal Properties: Stainless steel material.

E. Edges: Square, on four sides unless otherwise indicated.

F. Fasteners: Countersunk screw fasteners.

2.07 WALL STOPS

A. Wall Stops: Comply with BHMA A156.16, Grade 1 and Resilient Material Retention Test as described in this standard.

1. Type: Bumper, concave, wall stop.

2. Material: Steel housing with rubber insert.

2.08 WEATHERSTRIPPING AND GASKETING

A. Weatherstripping and Gasketing: Comply with BHMA A156.22.

2.09 FINISHES

A. Finishes: Provide door hardware of same finish, unless otherwise indicated.

1. Finish: 630; satin stainless steel, with stainless steel 300 series base material (former US equivalent US32D); BHMA A156.18.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that doors and frames are ready to receive this work; labeled, fire-rated doors and frames are properly installed, and dimensions are as indicated on shop drawings.

3.02 INSTALLATION

A. Install hardware in accordance with manufacturer's instructions and applicable codes.

B. Use templates provided by hardware item manufacturer.

C. Door Hardware Mounting Heights: Distance from finished floor to center line of hardware item.

1. For Steel Doors and Frames: Install in compliance with DHI (LOCS) recommendations.

3.03 ADJUSTING

A. Adjust hardware for smooth operation.

B. Adjust gasketing for complete, continuous seal; replace if unable to make complete seal.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

DOOR HARDWARE

08 7100

3.04 CLEANING

A. Clean finished hardware in accordance with manufacturer's written instructions after final adjustments have been made.

B. Clean adjacent surfaces soiled by hardware installation.

C. Replace items that cannot be cleaned to manufacturer's level of finish quality at no additional cost.

END OF SECTION 08 7100

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

POWER DOOR OPERATORS

08 7113

SECTION 08 7113

POWER DOOR OPERATORS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Operators for swinging doors.

B. Controllers, actuators, and safety devices.

1.02 REFERENCE STANDARDS

A. AAMA 611 - Specification for Anodized Architectural Aluminum; 2024.

B. ADA Standards - 2010 ADA Standards for Accessible Design; 2010.

C. BHMA A156.19 - Power Assist and Low Energy Power Operated Swinging Doors; 2019.

D. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having

Jurisdiction, Including All Applicable Amendments and Supplements.

E. NFPA 101 - Life Safety Code; Most Recent Edition Adopted by Authority Having

Jurisdiction, Including All Applicable Amendments and Supplements.

1.03 SUBMITTALS

A. Shop Drawings:

1. Indicate layout and dimensions; head, jamb, and sill conditions; elevations;

components, anchorage, recesses, materials, and finishes, electrical characteristics and connection requirements.

2. Identify installation tolerances required, assembly conditions, routing of service lines and conduit, and locations of operating components and boxes.

B. Product Data: Provide data on system components, sizes, features, and finishes.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Operators for Swinging Doors:

1. ASSA ABLOY Entrance Solutions; Besam SW200i: www.besam-usa.com/#sle.

2. LCN, an Allegion brand; 9130 Series: www.allegion.com/us/#sle.

3. Horton Automatics; 7100 Series: www.hortondoors.com/#sle.

4. record-usa; SimpleSwing HD: www.recorddoors.com/#sle.

5. Or approved equivalent.

2.02 POWER DOOR OPERATORS - GENERAL

A. Electrically Operated or Controlled Hardware: Provide necessary power supplies, relays, and interfaces as required for proper operation; provide wiring between control components and to building power connection in compliance with NFPA 70.

B. Comply with ADA Standards for egress requirements.

C. Comply with NFPA 101 and requirements of authorities having jurisdiction; provide units selected for actual door weight and for light pedestrian traffic unless otherwise indicated.

2.03 OPERATORS FOR SWINGING DOORS

A. Door Operator: Electromechanical.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

POWER DOOR OPERATORS

08 7113

1. Applications: Include operators for single doors.

2. Speed Control: Variable, field-adjustable opening and closing cycles.

3. Functionality: Low-energy power open, spring close operation.

a. Low-Energy Power Operators: Comply with BHMA A156.19; operator activated by pushing or pulling the door or by manual actuator, not a sensor;

safeties not required.

4. Mounting: Surface mounted overhead.

5. Power Supply Units: Self-contained, electrically operated, and independent of door operator.

6. Actuators: Manufacturer's standard.

2.04 CONTROLLERS, ACTUATORS, AND SAFETY DEVICES

A. Actuators: Manufacturer's standard for products specified.

1. Push Plate Actuator: Standard, wall mounted, surface mounted, momentary contact type; satin stainless steel plate; 4-inch diameter; labeled PUSH TO OPEN.

2.05 FINISHES

A. Aluminum Finishes: Manufacturer's standard.

1. Class I Natural Anodized Finish: Clear anodic coating; AAMA 611 AA-M12C22A41, minimum dry film thickness (DFT) of 0.7 mil, 0.0007 inch (0.018 mm).

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify installation conditions including, but not limited to the following: opening sizes, floor conditions, plumb and level mounting surfaces.

B. Verify that surfaces are ready to receive work and dimensions are as indicated on shop drawings.

C. Verify that electric power is available, in the correct location, and of the correct characteristics.

3.02 INSTALLATION

A. Coordinate installation of components with related and adjacent work.

B. Install equipment in accordance with manufacturer's instructions.

3.03 ADJUSTING

A. Adjust door equipment for correct function and smooth operation.

3.04 CLEANING

A. Remove temporary protection, clean exposed surfaces.

END OF SECTION 08 7113

DIVISION 09 - FINISHES S3A

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

GYPSUM BOARD ASSEMBLIES

09 2116

SECTION 09 2116

GYPSUM BOARD ASSEMBLIES

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Acoustic insulation.

B. Gypsum wallboard.

C. Joint treatment and accessories.

1.02 REFERENCE STANDARDS

A. ASTM C475/C475M - Standard Specification for Joint Compound and Joint Tape for

Finishing Gypsum Board; 2017 (Reapproved 2022).

B. ASTM C840 - Standard Specification for Application and Finishing of Gypsum Board;

2023.

C. ASTM C954 - Standard Specification for Steel Drill Screws for the Application of

Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness; 2022.

D. ASTM C1047 - Standard Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base; 2019.

E. ASTM C1396/C1396M - Standard Specification for Gypsum Board; 2017.

F. GA-216 - Application and Finishing of Gypsum Panel Products; 2024.

1.03 DELIVERY, STORAGE, AND HANDLING

A. Store gypsum products and accessories indoors and keep above freezing. Elevate boards above floor, on nonwicking supports, in accordance with manufacturer's recommendations.

B. Store metal products to prevent corrosion.

PART 2 PRODUCTS

2.01 BOARD MATERIALS

A. Manufacturers - Gypsum-Based Board:

1. American Gypsum Company: www.americangypsum.com/#sle.

2. CertainTeed Corporation: www.certainteed.com/#sle.

3. Georgia-Pacific Gypsum: www.gpgypsum.com/#sle.

4. Gold Bond Building Products, LLC provided by National Gypsum Company:

www.goldbondbuilding.com/#sle.

5. PABCO Gypsum: www.pabcogypsum.com/#sle.

6. USG Corporation: www.usg.com/#sle.

7. Or approved equivalent.

B. Gypsum Wallboard: Paper-faced gypsum panels as defined in ASTM C1396/C1396M;

sizes to minimize joints in place; ends square cut.

1. Application: Use for vertical surfaces and ceilings, unless otherwise indicated.

2. Thickness:

a. Vertical Surfaces: 5/8 inch (16 mm).

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

GYPSUM BOARD ASSEMBLIES

09 2116

b. Ceilings: 5/8 inch (16 mm).

2.02 GYPSUM BOARD ACCESSORIES

A. Acoustic Insulation: ASTM C665; preformed mineral-fiber, friction fit type, unfaced;

thickness as required for stud depth.

B. Finishing Accessories: ASTM C1047, galvanized steel sheet ASTM A924/A924M G90, unless noted otherwise.

1. Types: As detailed or required for finished appearance.

C. Joint Materials: ASTM C475/C475M and as recommended by gypsum board manufacturer for project conditions.

D. Screws for Fastening of Gypsum Panel Products to Steel Members from 0.033 to 0.112 inch (0.84 to 2.84 mm) in Thickness: ASTM C954; steel drill screws, corrosion-resistant.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that project conditions are appropriate for work of this section to commence.

3.02 ACOUSTIC ACCESSORIES INSTALLATION

A. Acoustic Insulation: Place tightly within spaces, around cut openings, behind and around electrical and mechanical items within partitions, and tight to items passing through partitions.

B. Acoustic Sealant: Install in accordance with manufacturer's instructions.

3.03 BOARD INSTALLATION

A. Comply with ASTM C840, GA-216, and manufacturer's instructions. Install to minimize butt end joints, especially in highly visible locations.

3.04 INSTALLATION OF TRIM AND ACCESSORIES

A. Control Joints: Place control joints consistent with lines of building spaces and as indicated.

B. Corner Beads: Install at external corners, using longest practical lengths.

3.05 JOINT TREATMENT

A. Finish gypsum board in accordance with levels defined in ASTM C840, as follows:

1. Level 4: Walls and ceilings to receive paint finish or wall coverings, unless otherwise indicated.

B. Tape, fill, and sand exposed joints, edges, and corners to produce smooth surface ready to receive finishes.

1. Feather coats of joint compound so that camber is maximum 1/32 inch (0.8 mm).

3.06 TOLERANCES

A. Maximum Variation of Finished Gypsum Board Surface from True Flatness: 1/8 inch in

10 feet (3 mm in 3 m) in any direction.

3.07 PROTECTION

A. Protect installed gypsum board assemblies from subsequent construction operations.

END OF SECTION 09 2116

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

RESILIENT FLOORING

09 6500

SECTION 09 6500

RESILIENT FLOORING

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Resilient base.

1.02 REFERENCE STANDARDS

A. ASTM F1861 - Standard Specification for Resilient Wall Base; 2021.

1.03 SUBMITTALS

A. See Section 01 3000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide data on specified products, describing physical and performance characteristics; including sizes, patterns and colors available; and installation instructions.

1.04 DELIVERY, STORAGE, AND HANDLING

A. Upon receipt, immediately remove any shrink-wrap and check materials for damage and the correct style, color, quantity and run numbers.

B. Store all materials off of the floor in an acclimatized, weather-tight space.

PART 2 PRODUCTS

2.01 RESILIENT BASE

A. Resilient Base: ASTM F1861, Type TS, rubber, vulcanized thermoset.

1. Manufacturers:

a. Flexco Corporation: www.flexcofloors.com/#sle.

b. Johnsonite, a Tarkett Company: www.johnsonite.com/#sle.

c. Mannington Commercial: www.manningtoncommercial.com#sle.

d. Roppe Corporation: www.roppe.com/#sle.

e. Or approved equivalent.

2. Height: 4 inches (100 mm).

3. Thickness: 0.125 inch (3.2 mm).

4. Finish: Satin.

5. Color: Black.

PART 3 EXECUTION

3.01 INSTALLATION - RESILIENT BASE

A. Fit joints tightly and make vertical. Maintain minimum dimension of 18 inches (45 mm) between joints.

B. Install base on solid backing. Bond tightly to wall and floor surfaces.

END OF SECTION 09 6500

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

RESILIENT FLOORING

09 6500

This page intentionally left blank

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

INTERIOR PAINTING

09 9123

SECTION 09 9123

INTERIOR PAINTING

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Surface preparation.

B. Field application of paints.

C. Scope: Finish interior surfaces exposed to view, unless fully factory-finished and unless otherwise indicated.

D. Do Not Paint or Finish the Following Items:

1. Items factory-finished unless otherwise indicated; materials and products having factory-applied primers are not considered factory finished.

2. Items indicated to receive other finishes.

3. Items indicated to remain unfinished.

4. Fire rating labels, equipment serial number and capacity labels, bar code labels, and operating parts of equipment.

5. Floors, unless specifically indicated.

6. Glass.

7. Concealed pipes, ducts, and conduits.

1.02 REFERENCE STANDARDS

A. ASTM D4442 - Standard Test Methods for Direct Moisture Content Measurement of

Wood and Wood-Based Materials; 2020.

B. MPI (APSM) - Master Painters Institute Architectural Painting Specification Manual;

Current Edition.

C. SSPC-SP 1 - Solvent Cleaning; 2015, with Editorial Revision (2016).

D. SSPC-SP 2 - Hand Tool Cleaning; 2018.

E. SSPC-SP 6/NACE No.3 - Commercial Blast Cleaning; 2006.

1.03 SUBMITTALS

A. Product Data: Provide complete list of products to be used, with the following information for each:

1. Manufacturer's name, product name and/or catalog number, and general product category (e.g., "alkyd enamel").

2. MPI product number (e.g., MPI #47).

3. Cross-reference to specified paint system products to be used in project; include description of each system.

4. Manufacturer's installation instructions.

B. Samples: Submit three paper "draw down" samples, 8-1/2 by 11 inches (216 by 279

mm) in size, illustrating range of colors available for each finishing product specified.

1.04 DELIVERY, STORAGE, AND HANDLING

A. Deliver products to site in sealed and labeled containers; inspect to verify acceptability.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

INTERIOR PAINTING

09 9123

B. Container Label: Include manufacturer's name, type of paint, brand name, lot number, brand code, coverage, surface preparation, drying time, cleanup requirements, color designation, and instructions for mixing and reducing.

C. Paint Materials: Store at minimum ambient temperature of 45 degrees F (7 degrees C) and a maximum of 90 degrees F (32 degrees C), in ventilated area, and as required by manufacturer's instructions.

1.05 FIELD CONDITIONS

A. Do not apply materials when surface and ambient temperatures are outside the temperature ranges required by the paint product manufacturer.

B. Follow manufacturer's recommended procedures for producing best results, including testing of substrates, moisture in substrates, and humidity and temperature limitations.

C. Do not apply materials when relative humidity exceeds 85 percent, at temperatures less than 5 degrees F (3 degrees C) above the dew point, or to damp or wet surfaces.

D. Minimum Application Temperatures for Paints: 50 degrees F (10 degrees C) for interiors unless required otherwise by manufacturer's instructions.

E. Provide lighting level of 80 fc (860 lux) measured mid-height at substrate surface.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Provide paints and finishes from the same manufacturer to the greatest extent possible.

B. Paints:

1. Basis of Design: Sherwin-Williams Company; Duration Interior Acrylic Latex:

www.sherwin-williams.com/#sle.

2. Behr Paint Company: www.behr.com/#sle.

3. Benjamin Moore: www.benjaminmoore.com.

4. PPG Paints: www.ppgpaints.com/#sle.

5. Rodda Paint Co: www.roddapaint.com/#sle.

6. Or approved equivalent..

C. Primer Sealers: Same manufacturer as top coats.

2.02 PAINTS AND FINISHES - GENERAL

A. Paints and Finishes: Ready-mixed, unless intended to be a field-catalyzed paint.

1. Provide paints and finishes of a soft paste consistency, capable of being readily and uniformly dispersed to a homogeneous coating, with good flow and brushing properties, and capable of drying or curing free of streaks or sags.

2. Supply each paint material in quantity required to complete entire project's work from a single production run.

3. Do not reduce, thin, or dilute paint or finishes or add materials unless such procedure is specifically described in manufacturer's product instructions.

B. Colors: To be selected from manufacturer's full range of available colors.

1. Selection to be made by Owner's Representative after award of contract.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

INTERIOR PAINTING

09 9123

2.03 PAINT SYSTEMS - INTERIOR

A. Interior Surfaces to be Painted, Unless Otherwise Indicated: Including gypsum board, wood, uncoated steel, shop primed steel, and galvanized steel.

1. Two top coats and one coat primer.

2. Top Coat(s): Interior Latex; MPI #43, 44, 52, 53, 54, or 114.

3. Top Coat Sheen:

a. Flat: MPI gloss level 1; use this sheen for ceilings and other overhead surfaces.

b. Velvet: MPI gloss level 2; use this sheen at all locations unless otherwise indicated.

c. Satin: MPI gloss level 4; use this sheen for items subject to frequent touching by occupants, including door frames and railings.

4. Primer: As recommended by top coat manufacturer for specific substrate.

2.04 ACCESSORY MATERIALS

A. Accessory Materials: Provide primers, sealers, cleaning agents, cleaning cloths, sanding materials, and clean-up materials as required for final completion of painted surfaces.

B. Patching Material: Latex filler.

C. Fastener Head Cover Material: Latex filler.

PART 3 EXECUTION

3.01 INSTALLERS

3.02 EXAMINATION

A. Do not begin application of paints and finishes until substrates have been adequately prepared.

B. Verify that surfaces are ready to receive work as instructed by the product manufacturer.

C. Examine surfaces scheduled to be finished prior to commencement of work. Report any condition that may potentially affect proper application.

D. Test shop-applied primer for compatibility with subsequent cover materials.

E. Measure moisture content of surfaces using an electronic moisture meter. Do not apply finishes unless moisture content of surfaces is below the following maximums:

1. Gypsum Wallboard: 12 percent.

2. Interior Wood: 15 percent, measured in accordance with ASTM D4442.

3.03 PREPARATION

A. Clean surfaces thoroughly and correct defects prior to application.

B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

C. Remove or mask surface appurtenances, including electrical plates, hardware, light fixture trim, escutcheons, and fittings, prior to preparing surfaces or finishing.

D. Seal surfaces that might cause bleed through or staining of topcoat.

E. Gypsum Board: Fill minor defects with filler compound. Spot prime defects after repair.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

INTERIOR PAINTING

09 9123

F. Galvanized Surfaces:

1. Remove surface contamination and oils and wash with solvent according to SSPC-

SP 1.

2. Prepare surface according to SSPC-SP 2.

G. Ferrous Metal:

1. Solvent clean according to SSPC-SP 1.

2. Shop-Primed Surfaces: Sand and scrape to remove loose primer and rust. Feather edges to make touch-up patches inconspicuous. Clean surfaces with solvent.

Prime bare steel surfaces. Re-prime entire shop-primed item.

3. Remove rust, loose mill scale, and other foreign substances using methods recommended in writing by paint manufacturer and blast cleaning in accordance with SSPC-SP 6/NACE No.3. Protect from corrosion until coated.

H. Wood Surfaces to Receive Opaque Finish: Wipe off dust and grit prior to priming. Seal knots, pitch streaks, and sappy sections with sealer. Fill nail holes and cracks after primer has dried; sand between coats. Back prime concealed surfaces before installation.

3.04 APPLICATION

A. Apply products in accordance with manufacturer's written instructions and recommendations in "MPI Architectural Painting Specification Manual".

B. Do not apply finishes to surfaces that are not dry. Allow applied coats to dry before next coat is applied.

C. Apply each coat to uniform appearance in thicknesses specified by manufacturer.

D. Sand wood and metal surfaces lightly between coats to achieve required finish.

E. Vacuum clean surfaces of loose particles. Use tack cloth to remove dust and particles just prior to applying next coat.

F. Reinstall electrical cover plates, hardware, light fixture trim, escutcheons, and fittings removed prior to finishing.

3.05 CLEANING

A. Collect waste material that could constitute a fire hazard, place in closed metal containers, and remove daily from site.

3.06 PROTECTION

A. Protect finishes until completion of project.

B. Touch-up damaged finishes after Substantial Completion.

END OF SECTION 09 9123

DIVISION 10 - SPECIALTIES S3A

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

TOILET, BATH, AND LAUNDRY ACCESSORIES

10 2800

SECTION 10 2800

TOILET, BATH, AND LAUNDRY ACCESSORIES

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Commercial toilet accessories.

1.02 REFERENCE STANDARDS

A. ASTM A269/A269M - Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service; 2022.

B. ASTM A666 - Standard Specification for Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate, and Flat Bar; 2023.

C. ASTM C1036 - Standard Specification for Flat Glass; 2021.

D. ASTM C1048 - Standard Specification for Heat-Strengthened and Fully Tempered Flat

Glass; 2018.

1.03 SUBMITTALS

A. Product Data: Submit data on accessories describing size, finish, details of function, and attachment methods.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Commercial Toilet, Shower, and Bath Accessories:

1. Basis of Design: Bobrick: www.bobrick.com.

B. Other manufacturers:

1. American Specialties, Inc: www.americanspecialties.com/#sle.

2. Bradley Corporation: www.bradleycorp.com/#sle.

3. Georgia-Pacific Professional: www.gppro.com/#sle.

4. Or approved equivalent.

2.02 MATERIALS

A. Accessories - General: Shop assembled, free of dents and scratches and packaged complete with anchors and fittings, steel anchor plates, adapters, and anchor components for installation.

B. Stainless Steel Sheet: ASTM A666, Type 304.

C. Stainless Steel Tubing: ASTM A269/A269M, Grade TP304 or TP316.

D. Mirror Glass: Tempered safety glass, ASTM C1048; and ASTM C1036 Type I, Class 1, Quality Q2, with silvering as required.

E. Fasteners, Screws, and Bolts: Hot dip galvanized; tamper-proof; security type.

2.03 FINISHES

A. Stainless Steel: Satin finish, unless otherwise noted.

2.04 COMMERCIAL TOILET ACCESSORIES

A. Toilet Paper Dispenser: Double roll, semi-recessed, stainless steel unit with pivot hinge.

B. Paper Towel Dispenser: Electric, roll paper type.

1. Paper Discharge: Touchless automatic.

DIVISION 10 - SPECIALTIES S3A

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

TOILET, BATH, AND LAUNDRY ACCESSORIES

10 2800

2. Power: Battery operated.

C. Soap Dispenser: Liquid soap dispenser, wall-mounted, surface, with stainless steel cover and horizontal stainless steel tank and working parts; push type soap valve, check valve, and window gauge refill indicator.

D. Mirrors: Stainless steel framed, 1/4 inch (6 mm) thick tempered safety glass; ASTM C1048.

1. Size: As scheduled.

E. Seat Cover Dispenser: Stainless steel, recessed, reloading by hinged front panel.

F. Grab Bars: Stainless steel, smooth surface.

1. Heavy Duty Grab Bars: Floor supports are not acceptable.

a. Push/Pull Point Load: Minimum 1000 pound-force (4448.2 N), minimum.

b. Dimensions: 1-1/2 inch (38 mm) outside diameter, minimum 0.125 inch (3.17

mm) wall thickness, exposed flange mounting, 1-1/2 inch (38 mm) clearance between wall and inside of grab bar.

c. Length and Configuration: As indicated on drawings.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify existing conditions before starting work.

B. Verify exact location of accessories for installation.

C. Verify that field measurements are as indicated on drawings.

3.02 PREPARATION

A. Deliver inserts and rough-in frames to site for timely installation.

B. Provide templates and rough-in measurements as required.

3.03 INSTALLATION

A. Install accessories in accordance with manufacturers' instructions in locations indicated on drawings.

B. Install plumb and level, securely and rigidly anchored to substrate.

C. Mounting Heights: As required by accessibility regulations, unless otherwise indicated.

1. Grab Bars: As indicated on drawings.

3.04 PROTECTION

A. Protect installed accessories from damage due to subsequent construction operations.

END OF SECTION 10 2800

DIVISION 22 - PLUMBING S3A

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

GENERAL REQUIREMENTS FOR PLUMBING

22 0000

SECTION 22 0000

GENERAL REQUIREMENTS FOR PLUMBING

PART 1 – GENERAL

1.01 APPLICABLE REQUIREMENTS

A. All work to be furnished and installed under this section shall comply with Division 01 – General Requirements when available. If not available, the Contractor shall meet the requirements of these specifications.

B. Where the Owner-Contractor Agreement contradicts this division, the more stringent shall apply.

1.02 RELATED REQUIREMENTS

A. Codes to include latest adopted editions, including current amendments, supplements, and local jurisdiction requirements in effect as of the date of the Contract Documents, including state/local building code, mechanical code, plumbing code, electrical code, fire code, and energy code.

1.03 GENERAL SCOPE

A. Work included in 22 00 00 applies to Division 22 work to provide materials, labor, tools, permits, incidentals, and other services to provide and make ready for Owner's use of mechanical systems for proposed project.

B. Contract Documents include, but are not limited to, Specifications, Drawings, Addenda, Owner/ Engineer Agreement, and Owner/Contractor Agreement. Confirm requirements before commencement of work.

C. In the event there is a discrepancy between the drawings, specifications and current code, the more stringent shall apply.

D. Examine the Drawings, specifications and other Contract Documents relating to the Work and the work of all trades and become fully informed as to the extent and character of work required. Coordinate all work with that of others to ensure proper and complete installation of all materials, equipment and supports.

E. Intent:

1. The intent of the Contract Documents is for the Contractor to include all work necessary for the complete systems, tested and ready for operation (hereinafter “Design Intent”).

2. Provide all items not specifically shown on the drawings, called for in the specifications or related Contract Documents, but required to conform to the labor, material and equipment to achieve the Design Intent.

3. Provide all scaffolding, access provisions, tools, appliances, consumables, debris removal/disposal, supervision and labor, including required start-up, check-out and training to provide complete and fully operable systems in full compliance with the Contract Documents.

4. Before submitting a bid and prior to the start of work, Contractor shall examine all conditions relating to the Work, including that associated with the work of other

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

GENERAL REQUIREMENTS FOR PLUMBING

22 0000 trades upon which Contractor’s work may rely or otherwise depend, to achieve the Design Intent, in accordance with the best trade practices, workmanship and highest quality product installation, taking into account the sequence of the work, delivery, storage and hoisting requirements, requirements for access, testing and temporary services and all other site limitations and project complexities. Report to the Owner's Representative any conditions which might prevent installation of materials and/or equipment in the manner intended by the Contract Documents or contrary to applicable codes, standards or regulations.

5. By submitting a bid, the Contractor represents that it has made a thorough examination of the site, of the work, including that associated with the work of other trades, all existing conditions and limitations, and that it has examined the Contract Documents in complete detail and has determined beyond doubt that the drawings, specifications, and existing conditions are sufficient, adequate and satisfactory for the construction of the work under the Contract.

6. No consideration or allowance will be granted for any alleged misunderstanding of materials, equipment or components to be furnished or work to be done; it being agreed that tender of proposal carries with it agreement to items, terms and conditions required by the Contract Documents.

7. Where minor adjustments of the work are necessary for purposes of fabrication or installation of items, or resolution of conflicts between items within the intent of the Contract Documents, the Contractor shall make such adjustments with no added compensation. Where such adjustments affect functional or aesthetic design of the work, they shall first be submitted to the Owner's Representative for review and approval.

F. Site Visit:

1. Contractor shall visit the site and verify the exact conditions relating to the work and obtain such information as may be necessary to present a complete and comprehensive bid. No allowance will be made for any extra expense due to Contractor’s failure to make such a visit and reasonably verify all actual/existing conditions. In the event of a conflict between existing conditions and the requirements of the Contract Documents, perform the necessary work to conform to Design Intent. The Owner or his representative will be the sole individual to interpret the intent of the Drawings in the event of a conflict between (1) existing conditions and those shown on the drawings, or (2) quality of existing material and quality of material indicated on the drawings or in the specifications.

Wherever a conflict such as this occurs, the higher standard shall prevail.

G. Conditions:

1. Conform to all Bidding Requirements and General Conditions

2. The Contractor is obligated to comply with the above in addition to the requirements of this Section.

CORRECTIONS DISTRIBUTION WAREHOUSE

BLDG 3 RESTROOMS

GENERAL REQUIREMENTS FOR PLUMBING

22 0000

3. Modifications by this Section do not…