241011 CDC Wireless CD Set - MECH~1.pdf
PDF 1 MB Posted
- Solicitation number
- S-29100-00012927
- Issued by
- Marion County, Oregon
About this file
This is a mechanical engineering drawing set for a CDC Wireless Building restroom remodel project located at 3601 State Street, Building 3 in Salem, Oregon. The drawings, dated September 12, 2024 with a permit set date of October 11, 2024, detail mechanical specifications and plans for remodeling restrooms, including exhaust fan installations and associated ductwork. The project requires compliance with Oregon state building codes including the Oregon Structural Specialty Code, Mechanical Specialty Code, Plumbing Specialty Code, Energy Efficiency Specialty Code, and Fire Code.
The plans specify installation of two Panasonic FV-0511VK3 exhaust fans (EF-1 and EF-2) rated at 80 CFM each to serve restrooms 102 and 103, with ECM motors and backdraft dampers. The scope includes removal of existing unit heaters, ductwork, and associated controls, with detailed specifications for new ductwork installation according to SMACNA standards. The drawings are prepared by Cole Design Engineering with offices in multiple locations including Bend, Eugene, Medford, Monterey, Napa and Santa Cruz, and are signed by Professional Engineer Laura Jane Breit (PE #79874) with a license expiration date of December 31, 2025.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NUMBER
REVISION SCHEDULE
JOB NUMBER:
TH
E
US
E
OF
T
HE
SE
P
LA
NS
A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L B E
RE
ST
RI
CT
ED
T
O
TH
E
OR
IG
IN
AL
SI
TE
FO
R W
HI
CH
T
HE
Y W
ER
E
PR
EP
AR
ED
A
ND
P
UB
LIC
AT
IO
N
TH
ER
EO
F I
S E
XP
RE
SS
LY
LI
M
IT
ED
T
O
SU
CH
U
SE
. R
E-
US
E, R
EP
RO
DU
CT
IO
N, O R
PU
BL
IC
AT
IO
N
BY
A
NY
M
ET
HO
D, IN
W
HO
LE
O
R
IN
P
AR
T, IS
P
RO
HI
BI
TE
D.
T
IT
LE
T
O
TH
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
R
EM
AI
NS
W
IT
H
TH
E
EN
GI
NE
ER
W
IT
HO
UT
P
RE
JU
DI
CE
. V
IS
UA
L C
ON
TA
CT
W
IT
H
TH
ES
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L C
ON
ST
IT
UT
E
PR
IM
A
FA
CI
E
EV
ID
EN
CE
O F T
HE
A
CC
EP
TA
NC
E
OF
T
HE
SE
R
ES
TR
IC
TI
ON
S.
C
OL
EB
RE
IT
E
NG
IN
EE
RI
NG
, L
LC
D
BA
A
XI
OM
E
NG
IN
EE
RS
CD
C
W
IR
EL
ES
S B
LD
G
DATE: 09/12/2024
20240427
RE
ST
RO
OM
S R
EM
OD
EL
ST
AT
E
ST
BU
ILD
IN
G
SA
LE
M
OR
PERMIT SET 10/11/2024
BEND | EUGENE | MEDFORD
MONTEREY | NAPA | SANTA CRUZ
E N G I N E E R I N G
MECHANICAL
LEGENDS, SCHEDULES,
NOTES, AND ABBREVIATIONS
M001
M
LONG SWEEP 90° ELBOW -
RECTANGULAR, ROUND OR OVAL
90° TAKEOFF WITH 45° ELONGATED TEE -
ROUND TO ROUND
45° LATERAL - ROUND TO ROUND OR
OVAL TO OVAL
90° ELBOW - RECTANGULAR DUCT
(NO DUCT TURNING VANES)
SHORT SWEEP 90° ELBOW -
RECTANGULAR, ROUND OR OVAL
90° CONICAL TEE - ROUND TO ROUND OR
OVAL TO OVAL
Y BRANCH -
ROUND OR OVAL DUCT
90° ELBOW -RECTANGULAR DUCT
WITH TURNING VANES
REGISTER SIZE
MARK
(DESIGN CFM)
90° TAKEOFF WITH 45° TAPER -
RECTANGULAR TO RECTANGULAR
(FOR BRANCH TAKEOFF LONGER THAN
50'-0", USE 15°)
90° RECTANGULAR SPLIT -
RECTANGULAR DUCT, PROVIDE SPLITTER
DAMPER, X/Y PROPORTIONAL SPLIT
90° RADIUS SPLIT -
RECTANGULAR DUCT, PROVIDE SPLITTER
DAMPER, X/Y PROPORTIONAL SPLIT
SPIN-IN WITH BALANCE DAMPER -
RECTANGULAR TO ROUND OR
RECTANGULAR TO OVAL
A. ALL SYMBOLS MAY NOT BE USED IN THIS PROJECT.
B. SYMBOLS DO NOT ALWAYS REPRESENT REAL LIFE DIMENSIONS.
C. SEE BOOK SPECIFICATIONS FOR ADDITIONAL INFORMATION.
D. SEE PLANS FOR DUCT AND PIPE SIZES.
(OR) GENERAL MECHANICAL NOTES
LEGEND NOTES
INCHIN
ID INSIDE DIAMETER
HERTZHZ
HTG HEATING
HEATING SEASONAL PERFORMANCE
FACTORHSPF
HR HOUR
HORSEPOWERHP
GAS PRESSURE REGULATORGPR
GPM GALLONS PER MINUTE
GAUGE
GAS
GA
G
FTR FLUE THRU ROOF
FEET HEADFT HD
FT FEET
FEET PER MINUTE
FLEXIBLE
FULL LOAD AMPS
FIRE/SMOKE DAMPER
FIRE DAMPER
ENTERING WATER TEMPERATURE
ENTERING WET BULB
EXTERNAL STATIC PRESSURE
EQUIPMENT
ELECTRICALELEC
EQUIP
ESP
EWB
EWT
FD
FSD
FLA
FLEX
FPM
EFF
EF
EER
EAT
EA
(E)
DWGS
DSD
DN
DB
dBA
CV
CONST
COP
COORD COORDINATE
COEFFICIENT OF PERFORMANCE
CONSTRUCTION
COEFFICIENT OF FLOW
A-WEIGHTED DECIBELS
DRY BULB
DOWN
DUCT SMOKE DETECTOR
DRAWINGS
EXISTING TO REMAIN
EXHAUST AIR
ENTERING AIR TEMPERATURE
ENERGY EFFICIENCY RATIO
EXHAUST FAN
EFFICIENCY
COOLING
CONTINUED, CONTINUATION
CONNECTION
CEILING
CIRCULATING
CUBIC FEET PER MINUTE
COMBUSTION AIR
BRITISH THERMAL UNITS PER HOUR
BUILDING
BRAKE HORSEPOWER
BACKDRAFT DAMPER
ARCHITECT/ARCHITECTURAL
AMPERE
ANNUAL FUEL UTILIZATION EFFICIENCY
ABOVE FINISH FLOOR
AIR CHANGES PER HOUR
AIR CONDITIONERAC
AC/H
AFF
AFUE
AMP
ARCH
BDD
BHP
BLDG
BTUH
CA
CFM
CIRC
CLG
CONN
CONT
COOL
°F DEGREES FAHRENHEIT
AT
AND
DIAMETER
ø
ABBRV. IDENTIFICATION ABBRV. IDENTIFICATION
KW
LAT
LBS
LRA
LVG
LWT
LWB
MAX
MBH
MCA
MCC
MECH
MFR
MIN
MOCP MAXIMUM OVERCURRENT PROTECTION
MINIMUM
MANUFACTURER
MECHANICAL
MOTOR CONTROL CENTER
MINIMUM CIRCUIT AMPS
1000 BTU PER HOUR
MAXIMUM
LEAVING WET BULB
LEAVING WATER TEMPERATURE
LEAVING
LOCKED ROTOR AMPS
POUNDS
LEAVING AIR TEMPERATURE
KILOWATTS
(N)
NC
NIC
NTS
OA
OBD
OC
OD
PD
PH
P/N
POC
PSI
P/T PRESSURE/TEMPERATURE
POUNDS PER SQUARE INCH
POINT OF CONNECTION
PART NUMBER
PHASE
PRESSURE DROP
OUTSIDE DIAMETER
ON CENTER
OPPOSED BLADE DAMPER
OUTSIDE AIR
NOT TO SCALE
NOT IN CONTRACT
NORMALLY CLOSED
NEW
QTY
(R)
RA
REQD
RLA
RPM
SA
SC
SEER
SF
SOV
SOO
SP
SPEC SPECIFICATION
STATIC PRESSURE
SEQUENCE OF OPERATION
SHUT-OFF VALVE
SUPPLY FAN OR SQUARE FEET
SEASONAL ENERGY EFFICIENCY RATIO
SENSIBLE COOLING
SUPPLY AIR
REVOLUTIONS PER MINUTE
RATED/RUNNING LOAD AMPS
REQUIRED
RETURN AIR
RELOCATE EXISTING
QUANTITY
TOTAL (COOLING) CAPACITY
TEMPERATURE
TOTAL STATIC PRESSURE
THERMOSTAT
TYPICAL
UNDERCUT DOOR
UNDERWRITER'S LABORATORIES
UNLESS OTHERWISE NOTED
VOLT
WITH
WATTS
WET BULB
WATER COLUMN
WEIGHT
EXISTING TO BE REMOVED(X)
WT
WC
WB
W
W/
V
UON
UL
UCD
TYP
TSTAT
TSP
TEMP
TC
ABBREVIATIONSHVAC SYMBOLS
IDENTIFICATIONSYMBOL
DUCT; SINGLE-LINE
DUCT; DOUBLE-LINE
45 DEGREE DUCT ELBOW; SINGLE-LINE
DUCT TRANSITION; SINGLE-LINE
DUCT TRANSITION; DOUBLE-LINE
DUCT TRANSITION RECTANGULAR TO ROUND;
DOUBLE-LINE
SUPPLY AIR DUCT IN CROSS-SECTION ROUTED UP OR
HORIZONTAL MOUNTED SUPPLY AIR DIFFUSER
RETURN AIR DUCT IN CROSS-SECTION ROUTED UP OR
HORIZONTAL MOUNTED RETURN AIR GRILLE
EXHAUST AIR DUCT IN CROSS-SECTION ROUTED UP OR
HORIZONTAL MOUNTED EXHAUST AIR GRILLE
SUPPLY AIR DUCT IN CROSS-SECTION ROUTED DOWN
RETURN AIR DUCT IN CROSS-SECTION ROUTED DOWN
EXHAUST AIR DUCT IN CROSS-SECTION ROUTED DOWN
ROUND DUCT UP - SUPPLY, RETURN OR EXHAUST
ROUND DUCT DOWN - SUPPLY, RETURN OR EXHAUST
VERTICAL MOUNTED SUPPLY AIR DEVICE
VERTICAL MOUNTED RETURN OR EXHAUST AIR DEVICE
POINT OF CONNECTION
TEMPERATURE SENSOR
THERMOSTAT MOUNT AT 48" AFF
FIRE AND SMOKE DAMPER - HORIZONTAL
FIRE DAMPER - HORIZONTAL
MOTORIZED DAMPER
BALANCE DAMPER
AIR TO DEVICE
AIR FROM DEVICE
SINGLE LINE DOUBLE LINE IDENTIFICATION
DUCT CONFIGURATIONS
12x12
CD
(300)
SHEET KEYNOTE TAG
CENTERLINE
FD
FSD
FIRE DAMPER - VERTICAL
FD
FIRE AND SMOKE DAMPER - VERTICAL
FSD
THIS WORK SHALL CONFORM TO ALL CURRENT AND ADOPTED LOCAL CODES
• OREGON STRUCTURAL SPECIALTY CODE (OSSC)
• OREGON MECHANICAL SPECIALTY CODE (OMSC)
• OREGON PLUMBING SPECIALTY CODE (OPSC)
• OREGON ENERGY EFFICIENCY SPECIALTY CODE (OEESC)
• OREGON FIRE CODE (OFC)
(OR) LIST OF GOVERNING CODES
MECHANICAL SPECIFICATIONS:
SCOPE: THIS PROJECT IS A REMODEL. THE PLANS AND SPECIFICATIONS INDICATE THE GENERAL EXTENT OF THE WORK BASED ON OWNER PROVIDED RECORD DRAWINGS AND LIMITED FIELD VERIFICATION. CONTRACTOR SHALL VISIT SITE, VERIFY EXISTING CONDITIONS, AND REPORT ANY DISCREPANCIES NOTED TO THE ARCHITECT PRIOR TO SUBMITTING A BID. CONTRACTOR SHALL BE RESPONSIBLE FOR THE DISCONNECTION AND RECONNECTION OF MECHANICAL, PLUMBING, AND ELECTRICAL SYSTEMS NECESSARY TO ACCOMPLISH THE WORK WHETHER OR NOT SPECIFIED AND/OR INDICATED. CUTTING OR CORING OF STRUCTURAL MEMBERS OR FOOTINGS IS PROHIBITED WITHOUT
THE PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER AND THE ARCHITECT.
COORDINATION: COOPERATE WITH GENERAL CONTRACTOR AND ALL OTHER TRADES.
DRAWINGS: DRAWINGS ARE DIAGRAMMATIC. ALL EQUIPMENT LOCATIONS & DUCTWORK ROUTING SHALL BE VERIFIED IN FIELD.
MAINTENANCE: ALL EQUIPMENT SHALL BE ACCESSIBLE FOR MAINTENANCE PER MANUFACTURER REQUIREMENTS.
O & M MANUALS: CONTRACTOR SHALL PROVIDE O & M MANUALS TO OWNER WITHIN 90 DAYS AFTER SYSTEM ACCEPTANCE.
RECORD DRAWINGS: CONTRACTOR SHALL PROVIDE RECORD DRAWINGS TO OWNER WITHIN 90 DAYS AFTER SYSTEM ACCEPTANCE.
DUCTWORK:
A. DUCT CONSTRUCTION: CONSTRUCTION OF DUCTWORK SHALL BE AS FOLLOWS:
1. GALVANIZED SHEETMETAL OF THICKNESS RECOMMENDED BY SMACNA.
B. FLEXIBLE DUCTS ARE PERMITTED ON THE LAST 5'-0" OF DUCT RUNS.
DAMPERS AND SHEETMETAL SPECIALTIES:
A. VOLUME DAMPERS SHALL BE PROVIDED FOR EACH SUPPLY DIFFUSER AND RETURN GRILLE AND SHALL BE SINGLE BLADE DAMPERS, JOB OR FACTORY FABRICATED OF GALVANIZED STEEL, TWO GAUGES HEAVIER THAN DUCT AND NO LONGER THAN 12" X 48" REINFORCED OR CRIMPED FOR RIGIDITY WITH PIVOT ROD EXTENDING THROUGH DUCT. POSITIONING DEVICE SHALL BE LOCKING
LEVER AND QUADRANT.
B. PROVIDE ACCESS DOORS OR CABLE ADJUSTORS FOR ALL BALANCING DAMPERS ABOVE HARD CEILINGS.
C. METAL GAUGES, JOINTS, BRACINGS, DUCT SUPPORTS AND TURNING VANES SHALL CONFORM TO SMACNA HVAC DUCT
CONSTRUCTION STANDARDS AS MINIMUM STANDARD, AND AS SPECIFIED AND/OR SHOWN.
DUCTWORK - INSTALLATION:
A. ALL DUCTWORK OF SHEETMETAL SHALL BE IN ACCORDANCE WITH THE APPLICABLE SMACNA MANUAL, UNLESS OTHERWISE SPECIFIED, AIRTIGHT AND SUPPORTED AS RECOMMENDED. DUCTWORK SHALL RUN CONCEALED UNLESS OTHERWISE NOTED.
B. ERECT ALL DUCTWORK TO DIMENSIONS INDICATED, STRAIGHT AND SMOOTH ON THE INSIDE WITH NEATLY FINISHED JOINTS LAPPED IN DIRECTION OF AIR TRAVEL. PROPERLY BRACE AND REINFORCE ALL DUCTS WITH STEEL ANGLES OR OTHER MEMBERS. ALL DUCTWORK SHALL BE OF GALVANIZED STEEL UNLESS OTHERWISE SPECIFIED OR INDICATED. FABRICATE CHANGES IN DIRECTION, BOTH HORIZONTAL AND VERTICAL, TO PERMIT EASY AIR FLOW.
C. INSTALL DUCTWORK TO CLEAR ALL OBSTRUCTIONS, PRESERVE HEADROOM, AND KEEP OPENINGS CLEAR.
D. SHOULD IT BE FOUND IMPRACTICAL TO INSTALL ANY DUCT OF THE EXACT SIZE GIVEN, A DUCT OF A DIFFERENT SHAPE BUT HAVING THE SAME AIR RESISTANCE SHALL BE INSTALLED. THESE ALTERNATE DUCT SIZES TO BE APPROVED BY THE ENGINEER PRIOR TO
INSTALLATION. DUCT SIZES GIVEN ARE INSIDE DIMENSIONS INSIDE THE LININGS.
E. ALL ELBOWS 45° OR GREATER SHALL BE FULL ELBOWS (CENTERLINE RADIUS EQUAL TO DUCT WIDTH) OR SHALL HAVE TURNING
VANES.
F. ALL DUCTS SHALL BE SUPPORTED PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS FOR SHEETMETAL DUCTS AND PER SMACNA
SEISMIC BRACE DUCTWORK AS INDICATED AND PER SMACNA MANUAL.
G. VERTICAL DUCTS SHALL BE SUPPORTED BY EXTENDING BRACING ANGLES TO REST FIRMLY ON FLOORS OR SHALL BE BOLTED TO
WALLS, COLUMNS, OR OTHER CONSTRUCTION.
H. FABRICATE COMPRESSION TYPE SUPPORTS FROM CROSS-BRACED METAL ANGLES NOT SMALLER THAN THAT REQUIRED FOR DUCT
BRACING.
DUCT SEALING:
A. DUCTS EXPOSED TO WEATHER SHALL BE COMPLETELY WEATHERPROOF WITH OUTDOOR VAPOR BARRIER MASTIC OVER TAPE AT ALL
JOINTS AND SEAMS.
B. SEAL JOINTS AND SEAMS OF INTERIOR DUCTWORK AIR TIGHT.
C. NO "GREY" DUCT TAPE SHALL BE USED. METAL DUCT SEALING SHALL BE "AEROBOL", "HARDCAST", OR SMACNA APPROVED FOIL-BACKED PRESSURE SENSITIVE TAPE, EXCEPT WHERE OTHERWISE INDICATED OR SPECIFIED.
D. ALL DUCT SEALING SHALL COMPLY WITH THE OREGON ENERGY EFFICIENCY SPECIALTY CODE.
REFRIGERANT PIPING:
A. CONTRACTOR IS RESPONSIBLE FOR REFRIGERANT PIPE SIZING AND ROUTING AND SHALL COMPLY WITH ALL MANUFACTURER'S
INSTRUCTIONS.
CONDENSATE PIPING:
A. REFER TO PLUMBING DRAWINGS.
EXHAUST FANS
MARK SERVING CFM ESP SONES
MOTOR WT
LBS MAKE & MODEL NOTES
V/PH WATTS
EF-1 RESTROOM 102 80 .25 0.3 120/1 10.6 10 PANSONIC FV-0511VK3 1,2
EF-2 RESTROOM 103 80 .25 0.3 120/1 10.6 10 PANSONIC FV-0511VK3 1,2
NOTES:
1. PROVIDE BACKDRAFT DAMPER, DISCONNECT SWITCH. FAN TO OFF OCCUPANCY SENSOR.
2. PROVIDE ECM MOTOR.
SPLIT SYSTEM HEAT PUMPS
MARK SERVING
COOL MBH HEAT
MBH TONS CFM ESP V/PH UNIT
MCA/MOCP
WT
LBS
SEER2
/(EER2)
HSPF2
/(COP)
MAKE & MODEL NOTES
TC SC
HP-1
RESTROOM 102 9 6 6
.5 - - 208/1 0.65 - 29 - - MITSUBISHI MUZ-FS06NA 1
FC-1 .5 380 - - 10.0 15 82 32.2 11.9 MITSUBISHI MSZ-FS06NA 2,3
HP-2
RESTROOM 103 9 6 6
.5 - - 208/1 0.65 - 29 - - MITSUBISHI MUZ-FS06NA 1
FC-2 .5 380 - - 10.0 15 82 32.2 11.9 MITSUBISHI MSZ-FS06NA 2,3
NOTES:
1. WALL MOUNTED OUTDOOR UNIT WITH FACTORY WALL KIT. SIZE AND INSTALL REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS.
2. HEATING SETPOINT SHALL BE NO GREATER THAN 60 DEG F AND COOLING SETPOINT SHALL BE NO LESS THAN 85 DEG F.
3. PROVIDE PROGRAMMABLE THERMOSTAT & OPTIONAL HIGH HEAD CONDENSATE PUMP. INDOOR UNIT POWERED THROUGH OUTDOOR UNIT.
SHEET INDEX
MOO1 MECHANICAL LEGENDS, SCHEDULES, NOTES, AND ABBREVIATIONS
M200 MECHANICAL ENLARGED FLOOR PLANS
R
EG
ISTERED PROFESSIONA
L
E N
G I N E E
R79874PE
OREGON
L A
U R A J A N E B R E I T
S E P . 0 9 , 2 0 0 8
EXPIRES 12/31/2025
EF-2
EF-16"ø
6"ø
FC-1
FC-2
TFC-2
TFC-1
HP-1
(E) HP BELOW
ON WALL
HP-2
(E) POST
INDICATOR
VALVE
(X) EF
NOT IN
SCOPE
SHEET NUMBER
REVISION SCHEDULE
JOB NUMBER:
TH
E
US
E
OF
T
HE
SE
P
LA
NS
A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L B E
RE
ST
RI
CT
ED
T
O
TH
E
OR
IG
IN
AL
SI
TE
FO
R W
HI
CH
T
HE
Y W
ER
E
PR
EP
AR
ED
A
ND
P
UB
LIC
AT
IO
N
TH
ER
EO
F I
S E
XP
RE
SS
LY
LI
M
IT
ED
T
O
SU
CH
U
SE
. R
E-
US
E, R
EP
RO
DU
CT
IO
N, O R
PU
BL
IC
AT
IO
N
BY
A
NY
M
ET
HO
D, IN
W
HO
LE
O
R
IN
P
AR
T, IS
P
RO
HI
BI
TE
D.
T
IT
LE
T
O
TH
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
R
EM
AI
NS
W
IT
H
TH
E
EN
GI
NE
ER
W
IT
HO
UT
P
RE
JU
DI
CE
. V
IS
UA
L C
ON
TA
CT
W
IT
H
TH
ES
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L C
ON
ST
IT
UT
E
PR
IM
A
FA
CI
E
EV
ID
EN
CE
O F T
HE
A
CC
EP
TA
NC
E
OF
T
HE
SE
R
ES
TR
IC
TI
ON
S.
C
OL
EB
RE
IT
E
NG
IN
EE
RI
NG
, L
LC
D
BA
A
XI
OM
E
NG
IN
EE
RS
CD
C
W
IR
EL
ES
S B
LD
G
DATE: 09/12/2024
20240427
RE
ST
RO
OM
S R
EM
OD
EL
ST
AT
E
ST
BU
ILD
IN
G
SA
LE
M
OR
PERMIT SET 10/11/2024
BEND | EUGENE | MEDFORD
MONTEREY | NAPA | SANTA CRUZ
E N G I N E E R I N G
MECHANICAL
ENLARGED FLOOR PLANS
M200
DEMO FLOOR PLAN - MECHANICAL
1/2" = 1'-0"M200
1NEW FLOOR PLAN - MECHANICAL
1/2" = 1'-0"M200
KEYED NOTES:
1. TERMINATE EXHAUST AIR DISCHARGE WITH WALL CAP AT EXTERIOR CONCRETE WALL.
COORDINATE EXHAUST WALL CAP LOCATION WITH EXISTING ELECTRICAL CONDUIT
THIS AREA. PROVIDE CONCRETE WALL PENETRATION. WALL PENETRATION TO BE 1/2"
INCH LARGER THAN ANNULAR DIAMETER OF DUCT. SEAL DUCT PENETRATION WATER
TIGHT.
2. ROUTE DUCT WITHIN JOIST BAY ABOVE CEILING, FIELD VERIFY.
3. MOUNT HEAT PUMP UNIT AT A SAME HEIGHT AS EXISTING ADJACENT UNITS.
NORTH NORTH
KEYED NOTES:
1. EXISTING UNIT HEATER AND ASSOCIATED CONTROLS TO BE REMOVED AND RETURN
TO BUILDING OWNER.
2. EXISTING EXHAUST FAN, DUCTWORK AND ASSOCIATED CONTROLS TO BE REMOVED.
PATCH AND SEAL EXISTING TERMINATION OPENING AS REQUIRED.
R
EG
ISTERED PROFESSIONA
L
E N
G I N E E
R79874PE
OREGON
L A
U R A J A N E B R E I T
S E P . 0 9 , 2 0 0 8
EXPIRES 12/31/2025
| Sheets and Views |
| M001 |
| 2024-10-11T16:48:59-0700 | |
| Laura Breit |
| 2024-10-11T16:48:59-0700 | |
| Laura Breit |