241011 CDC Wireless CD Set - ELEC~1.pdf
PDF 6 MB Posted
- Solicitation number
- S-29100-00012927
- Issued by
- Marion County, Oregon
About this file
This is an electrical drawing set for a restroom remodeling project at the CDC Wireless Building located at 3601 State Street, Building 3 in Salem, Oregon. The permit set, dated October 11, 2024, includes electrical symbols and legends, schedules, specifications, overall floor plans, and enlarged lighting and power plans for the renovation of restrooms. The project involves updating electrical systems including lighting, power distribution, and mechanical equipment connections in the restroom areas.
The drawings detail the demolition and new installation of electrical components including receptacles, lighting fixtures, exhaust fans, water heaters, and associated circuitry. Specific equipment includes LED lighting fixtures by Lithonia, new heat pumps rated at 1.7 KW, exhaust fans rated at 0.01 KW, and a 4.0 KW electric water heater. The work must comply with the 2023 Oregon Electrical Specialty Code, 2021 Oregon Energy Efficiency Specialty Code, and ASHRAE 90.1-2019 standards. The plans show modifications to existing electrical panels including Panel L, Panel M, and Panel Sub-M, with detailed load calculations showing the total new loads will remain within existing panel capacities.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NUMBER
REVISION SCHEDULE
JOB NUMBER:
TH
E
US
E
OF
T
HE
SE
P
LA
NS
A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L B E
RE
ST
RI
CT
ED
T
O
TH
E
OR
IG
IN
AL
SI
TE
FO
R W
HI
CH
T
HE
Y W
ER
E
PR
EP
AR
ED
A
ND
P
UB
LIC
AT
IO
N
TH
ER
EO
F I
S E
XP
RE
SS
LY
LI
M
IT
ED
T
O
SU
CH
U
SE
. R
E-
US
E, R
EP
RO
DU
CT
IO
N, O R
PU
BL
IC
AT
IO
N
BY
A
NY
M
ET
HO
D, IN
W
HO
LE
O
R
IN
P
AR
T, IS
P
RO
HI
BI
TE
D.
T
IT
LE
T
O
TH
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
R
EM
AI
NS
W
IT
H
TH
E
EN
GI
NE
ER
W
IT
HO
UT
P
RE
JU
DI
CE
. V
IS
UA
L C
ON
TA
CT
W
IT
H
TH
ES
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L C
ON
ST
IT
UT
E
PR
IM
A
FA
CI
E
EV
ID
EN
CE
O F T
HE
A
CC
EP
TA
NC
E
OF
T
HE
SE
R
ES
TR
IC
TI
ON
S.
C
OL
EB
RE
IT
E
NG
IN
EE
RI
NG
, L
LC
D
BA
A
XI
OM
E
NG
IN
EE
RS
CD
C
W
IR
EL
ES
S B
LD
G
DATE: 10/11/2024
20240427
RE
ST
RO
OM
S R
EM
OD
EL
ST
AT
E
ST
BU
ILD
IN
G
SA
LE
M
OR
PERMIT SET 10/11/2024
BEND | EUGENE | MEDFORD
MONTEREY | NAPA | SANTA CRUZ
E N G I N E E R I N G
ELECTRICAL SYMBOLS AND
LEGEND
E001
ABBREVIATIONS
ABBRV.
POWER SYMBOLS
SYMBOL IDENTIFICATION IDENTIFICATION
AC ALTERNATING CURRENT
AFF ABOVE FINISH FLOOR
AT TRIP RATING IN AMPERES
FRAME RATING IN AMPERES
AS SWITCH RATING IN AMPERES
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO VISUAL
C CONDUIT
CL CENTERLINE
DC DIRECT CURRENT
(E) EXISTING TO REMAIN
ELEV ELEVATOR
EMT ELECTRO METALLIC TUBING
G GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
IG ISOLATED GROUND
LCP LIGHTING CONTROL PANEL
NC NORMALLY CLOSED
NEMA NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NO NORMALLY OPEN
NTS NOT TO SCALE
PVC POLYVINYL CHLORIDE CONDUIT
RSC RIGID STEEL CONDUIT
TTB TERMINAL BACKBOARD
TC TERMINAL CABINET
TEL TELEPHONE
UON UNLESS OTHERWISE NOTED
VFD VARIABLE FREQUENCY DRIVE
W WEATHERPROOF
WAP WIRELESS ACCESS POINT
W/ WITH
XFMR TRANSFORMER
XP EXPLOSION PROOF
NEC NATIONAL ELECTRIC CODE
(X) REMOVE EXISTING
(R) RELOCATE EXISTING
20A, 125V, DUPLEX RECEPTACLE OUTLET +18" AFF TO CENTERLINE
OF BOX UNLESS OTHERWISE NOTED
20A, 125V, DOUBLE DUPLEX RECEPTACLE OUTLET +18" AFF TO
CENTERLINE OF BOX UNLESS OTHERWISE NOTED
CONN CONNECTED
SPECIAL PURPOSE RECEPTACLE OUTLET; NEMA
CONFIGURATIONS AS SHOWN ON DRAWINGS; 18" AFF TO
CENTERLINE OF BOX UNLESS OTHERWISE NOTED
20A, 125V, SINGLE RECEPTACLE OUTLET; +18" AFF TO
CENTERLINE OF BOX UNLESS OTHERWISE NOTED
A = ABOVE COUNTER
C = CEILING MOUNTED
G = GFCI
S = SWITCHED RECEPTACLE
U = WITH (2) USB PORTS
W = WEATHERPROOF COVER AND GFCI
X
20A, 125V, DUPLEX RECEPTACLE OUTLET;
FLOOR RECESSED
20A, 125V, DOUBLE DUPLEX RECEPTACLE OUTLET;
FLOOR RECESSED
2-COMPARTMENT FLOOR BOX W/ (2) GANG POWER / (2)
GANG DATA; PROVIDE 1"C. FROM EACH DATA OUTLET TO
ACCESSIBLE CEILING SPACE.
SINGLE POLE SWITCH
3 = THREE WAY SWITCH
4 = FOUR-WAY SWITCH
D = DIMMER SWITCH
K = KEY OPERATED SWITCH
M = MOTOR RATED SWITCH
T = INTERVAL TIMER
V = VACANCY SENSOR SWITCH
W = WEATHERPROOF SWITCH
X
PUSH BUTTON
OCCUPANCY LIGHT CONTROL SWITCH; CEILING MOUNTED
OCCUPANCY LIGHT CONTROL SWITCH; WALL MOUNTED
PHOTOSENSOR; CEILING MOUNTED
C = CORRIDOR PATTERN
X
DIMMING PHOTOSENSOR
D
ELECTRIC VEHICLE CHARGING STATION
LUMINAIRE; CEILING OR SURFACE MOUNTED
LUMINAIRE; WALL MOUNTED
AREA POLE WITH MOUNTED LUMINAIRE
LUMINAIRE ON EMERGENCY POWER
EXIT SIGN; CEILING MOUNTED; ARROWS AND FACES AS
SHOWN ON PLANS
EXIT SIGN; WALL MOUNTED; ARROWS AND FACES AS
SHOWN ON PLANS
SPD SURGE PROTECTION DEVICE
PH PHASE
GND GROUND
CONTRACTOR FURNISHED,
CONTRACTOR INSTALLEDCFCI
CONTRACTOR FURNISHED, OWNER
INSTALLEDCFOI
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
MOTOR CONNECTION
FUSED DISCONNECT
SWITCH XX/XX/XX = AMP SWITCH/POLES/AMP FUSE
NON-FUSED DISCONNECT
SWITCH XX/XX = AMP SWITCH/POLES
JUNCTION BOX
JUNCTION BOX; CEILING MOUNTEDC
JUNCTION BOX WITH WHIP-STYLE CONNECTION TO
POWERED FURNITURE; POWER AND/OR DATA
JUNCTION BOX; WALL MOUNTED
GENERATOR CONNECTION
TRANSFORMER; BOTTOM OF T DESIGNATES FRONT SIDE
PANELBOARD OR TERMINAL CABINET; SURFACE MOUNTED
PANELBOARD OR TERMINAL CABINET; FLUSH MOUNTED
AUTOMATIC TRANSFER SWITCH
DRAWOUT CIRCUIT BREAKER; RATING AS SHOWN ON PLANS
STATIONARY - CIRCUIT BREAKER; RATING AS SHOWN ON PLANS
FUSED DISCONNECT; RATING AS SHOWN ON PLANS
NON-FUSED DISCONNECT; RATING AS SHOWN ON PLANS
TRANSFORMER
INVERTER
GROUNDING POINT
UTILITY METER
GROUND BUS BAR
M
G
F
J
J
J
OS
O S
OS
PS
S = OCCUPANCY SENSOR SWITCH
T = TAMPER PROOF
+#" = INCHES ABOVE FINISH FLOOR TO CENTERLINE OF BOX
COMMERCIAL CORD REEL RECEPTACLE; CEILING MOUNTED
H = HIGH BAY SENSOR
V = VACANCY SENSOR MODE
EV
J
EMERGENCY FIXTURE; DUAL LAMP HEAD
J C
M
PB
LIGHTING SYMBOLS
SYMBOL IDENTIFICATION
WIRING DEVICE SYMBOLS
SYMBOL IDENTIFICATION
CONDUIT INSTALLED BELOW FINISHED FLOOR OR BELOW
GRADE
CONDUIT INSTALLED ABOVE FINISHED FLOOR OR GRADE
INDICATES CONDUIT TURNING UP
CONDUIT HOMERUN; ROUTE TO PANELBOARD, CABINET, OR
TERMINAL BOARD INDICATED, AND TERMINATE CONDUCTORS TO
CIRCUIT OVER CURRENT PROTECTIVE DEVICE
CONDUIT SYMBOLS
SYMBOL IDENTIFICATION
FEEDER DESIGNATION TAG
SHEET KEYNOTE TAG
MECHANICAL EQUIPMENT TAG
CONTRACTOR EQUIPMENT TAG
LETTER INDICATES FIXTURES CONTROL (WHERE SHOWN)
NUMBER INDICATES CIRCUIT NUMBER (WHERE SHOWN)
REVISION DELTA WITH REVISION NUMBER#
a.$
XX-#
XX-#
DESIGNATION SYMBOLS
SYMBOL IDENTIFICATION
MANUAL TRANSFER SWITCH
CUSTOMER METERCM
T
INDICATES CONDUIT TURNING DOWN
CONDUIT STUBBED AND CAPPED
CONDUIT AND WIRE. HATCH LINES INDICATE QUANTITY OF
UNGROUNDED #12 CONDUCTORS, OR CONDUCTOR SIZE AS NOTED
ADJACENT TO HATCH LINES. GROUND CONDUCTOR TO BE PROVIDED
SIZED IN ACCORDANCE WITH NEC TABLE 250-122. IF NO HATCH LINES
ARE SHOWN, 2#12 & 1#12G CONDUCTORS ARE ASSUMED.
TERMINAL CABINET OR CONTROL PANEL; FLUSH MOUNTED
TERMINAL CABINET OR CONTROL PANEL; FLUSH MOUNTED
EXIT SIGN WITH DUAL LAMP HEAD
STRIP LIGHT
EPO PUSH BUTTON
OS
PS COMBINATION OCCUPANCY SENSOR/PHOTOSENSOR
PS
AIC AMPS INTERRUPTING CURRENT
A AMPERES
AWG AMERICAN WIRE GAUGE
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFG ABOVE FINISHED GRADE
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CU COPPER
EM EMERGENCY / STANDBY POWER
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
HP HORSEPOWER
HZ HERTZ
IDF INTERMEDIATE DISTRIBUTION FRAME
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
LED LIGHT EMITTING DIODE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDF MAIN DISTRIBUTION FRAME
MTS MANUAL TRANSFER SWITCH
NIC NOT INCLUDED IN CONTRACT
PV PHOTOVOLTAIC
TYP TYPICAL
(RR) REMOVE AND REPLACE WITH NEW
EV ELECTRICAL VEHICLE
MLO MAIN LUGS ONLY
CONDUIT ONLYCO
CURRENT TRANSFORMERCT
UL UNDERWRITER LABORATORIES
V VOLTAGE
W/O WITHOUT
AF
LEGEND NOTES
A.
B.
C.
D.
ALL SYMBOLS MAY NOT BE USED IN THIS PROJECT
SYMBOLS DO NOT ALWAYS REPRESENT REAL LIFE DIMENSIONS
SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION
MOUNTING HEIGHTS OF DEVICES SHALL BE AS NOTED IN THE LEGEND FOR THE RESPECTIVE
SYMBOL, UON ON FLOOR PLANS OR AS REQUIRED PER ADA REQUIREMENTS.
ABBRV. IDENTIFICATION
PRI PRIMARY
SEC SECONDARY
P POLE
(RR) RECEPTACLE
LGT LIGHTING
A. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF FIRE RATED WALLS, FLOORS, CEILINGS, ETC. PROVIDE FIRE RATED PENETRATIONS AT THESE LOCATIONS.
B. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR EXACT LOCATIONS OF EQUIPMENT
AND ADDITIONAL CONTROL REQUIREMENTS. CONNECTION REQUIREMENTS TO ALL
EQUIPMENT TO BE VERIFIED WITH APPROVED SUBMITTALS / SHOP DRAWINGS.
C. FLOOR MOUNTED ELECTRICAL EQUIPMENT SHALL BE INSTALLED ON A 3" HIGH CONCRETE
HOUSEKEEPING PAD.
D. VERIFY DEVICE MOUNTING HEIGHT AND ORIENTATION (VERTICAL OR HORIZONTAL) WITH
ARCHITECTURAL AND INTERIOR DESIGN DRAWINGS AND ELEVATIONS.
E. DISCONNECT SWITCHES TO BE SIZED AT MINIMUM TO MATCH THE BREAKER SIZE OF THE
RESPECTIVE BRANCH CIRCUIT BEING FED.
F. RACEWAY SYSTEMS AND CONDUIT ROUTING SHOWN ON ELECTRICAL DRAWINGS IS
DIAGRAMMATIC IN NATURE AND TOR SHOW THE DESIGN INTENT OF CONDUIT
INFRASTRUCTURE REQUIREMENTS. ACTUAL LOCATION AND ROUTING OF ALL CONDUIT
RACEWAYS SHALL BE DETERMINED BY CONTRACTOR TO SUIT FIELD CONDITIONS.
G. CONTRACTOR TO PROVIDE PULL STRINGS IN ALL LOW VOLTAGE SYSTEM CONDUITS AND ALL
SPARE CONDUITS.
H. PROVIDE DEDICATED NEUTRAL FOR EACH NEW CIRCUIT PER NEC 210.4. HOME RUN
CONDUCTORS MAY BE COMBINED INTO ONE CONDUIT. NO RACEWAY OR CABLE SHALL
CONTAIN MORE THAN NINE (9) CURRENT CARRYING CONDUCTORS.
I. BRANCH CIRCUITS TO BE SIZED FOR MAXIMUM 3% VOLTAGE DROP. PROVIDE #10 AWG
CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS LONGER THAN 75' AND #8 AWG
CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS LONGER THAN 120'. PROVIDE #10
AWG CONDUCTORS FOR 20 AMPERE, 277V BRANCH CIRCUITS LONGER THAN 200'.
THIS WORK SHALL CONFORM TO ALL CURRENT AND ADOPTED LOCAL CODES
2021 OREGON ENERGY EFFICIENCY SPECIALTY CODE (OEESC)
ASHRAE 90.1-2019
2023 OREGON ELECTRICAL SPECIALTY CODE (OESC) - BASED ON THE 2023 NATIONAL ELECTIRCAL CODE
(OR) LIST OF GOVERNING CODES
GENERAL ELECTRICAL NOTES:
SHEET INDEX
E001 ELECTRICAL SYMBOLS AND LEGEND
E002 ELECTRICAL SCHEDULES
E003 ELECTRICAL SPECIFICATIONS
E100 ELECTRICAL OVERALL FLOOR PLAN
E200 ELECTRICAL ENLARGED LIGHTING
PLAN
E300 ELECTRICAL ENLARGED POWER
PLANS
A. REFER TO DEMOLITION DRAWINGS FOR EXTENT OF DEMOLITION THROUGHOUT THE BUILDING. REFER TO TECHNOLOGY DRAWINGS FOR DEMOLITION SCOPE OF DATA/IT, TELEPHONE, SECURITY, AND CATV SYSTEMS.
B. DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELD INVESTIGATION PRIOR TO DEMOLITION.
NOTES AND GRAPHIC REPRESENTATIONS SHALL NOT LIMIT THE EXTENT OF DEMOLITION REQUIRED.
CONTRACTOR SHALL VISIT THE SITE TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND IN ORDER TO AVOID CONFLICTS. CONTRACTOR SHALL PERFORM ALL DEMOLITION REQUIRED TO ACHIEVE THE FINAL
DESIGN INTENT AS REQUIRED BY THE CONTRACT DOCUMENTS.
C. DE-ENERGIZE AND SAFE-OFF ALL EQUIPMENT AND ANY WIRING AND/OR EQUIPMENT TO BE REMOVED PRIOR TO ANY DEMOLITION WORK. CONTRACTOR RESPONSIBLE FOR SAFE-OFF DEMO AS NECESSARY FOR CONSTRUCTION EFFORTS. PROVIDE LOCK-OUT/TAG-OUT PROCEDURES TO PROVIDE SAFE WORKING
ENVIRONMENT.
D. UNLESS OTHERWISE NOTED, DISCONNECT AND REMOVE ALL FIXTURES, RECEPTACLES, OUTLETS AND OTHER ELECTRICAL DEVICES ALONG WITH ASSOCIATED WIRING, CONDUIT RACEWAYS, BOXES AND SUPPORTS IN AREAS OF DEMOLITION. EXISTING ELECTRICAL DEVICES SHALL INCLUDE, BUT NOT LIMITED TO, LIGHTING
SWITCHES, RECEPTACLES, ETC.
E. REMOVE ALL ELECTRICAL APPURTENANCES (DISCONNECTS, STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED
WITH EQUIPMENT TO BE REMOVED BY OTHERS.
F. UNLESS OTHERWISE INDICATED, EXISTING SERVICES, SYSTEMS AND WIRING SERVICE EXISTING AREAS OUTSIDE OF DEMOLITION AREA SHALL REMAIN OR BE RELOCATED AS REQUIRED TO MAINTAIN OPERATION
OF EXISTING SYSTEMS AND AVOID CONFLICT WITH NEW CONSTRUCTION.
G. EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT NO ADDITIONAL COST TO OWNER, ANY
DAMAGE CAUSED TO EXISTING CONSTRUCTION AND/OR EQUIPMENT TO REMAIN.
H. ALL CONDUIT REMOVED SHALL BE REMOVED IN IT'S ENTIRETY, INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE, ETC. PROVIDE CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS CREATED BY THE REMOVAL OF CONDUIT. PROVIDE BLANK COVER PLATES FOR ALL OPENED OUTLET BOXES CREATED BY THE
REMOVAL OF EQUIPMENT AND / OR DEVICES.
I. FEEDERS AND BRANCH CIRCUITS TO BE REMOVED - WIRING, CONDUIT AND SUPPORTS SHALL BE REMOVED
TO THE PANEL OF ORIGIN.
J. EXISTING CIRCUITING TO REMAIN SHALL BE REROUTED OR RECONNECTED, AS REQUIRED, WHERE AFFECTED
BY NEW WORK IN ORDER TO MAINTAIN CONTINUITY OF THE CIRCUIT.
K. PROVIDE TEMPORARY SUPPORTS FOR ALL CONDUITS, DEVICES, EQUIPMENT AND CABLING THAT ARE TO REMAIN. COORDINATE ALL WORK WITH BUILDING OPERATING PERSONNEL AND BUILDING'S FIRE ALARM, SECURITY AND TELECOM CONTRACTORS.
L. PROVIDE BLANK PLATES AT ALL OPEN BOXES WHERE DEVICES ARE REMOVED AND SURFACE IS NOT
SCHEDULED TO BE PATCHED AND RE-FINISHED.
M. EQUIPMENT INDICATED TO BE REMOVED SHALL BE TAKEN FROM THE SITE AND DISPOSED OF IN
ACCORDANCE WITH APPLICABLE LAWS AND ENVIRONMENTAL REGULATIONS.
N. EQUIPMENT NOTED TO BE SALVAGED SHALL BE REMOVED WITH CARE TO PREVENT DAMAGE, AND SHALL BE
TURNED OVER TO THE OWNER.
O. ALL WORK AND ALL POWER OUTAGES IN THE EXISTING BUILDING SHALL BE COORDINATED WITH AND
SCHEDULED AT TIMES CONVENIENT TO THE OWNER.
P. CONTRACTOR RESPONSIBLE FOR ALL ELECTRICAL DEMO AND DISPOSAL FEES. ASSUME T8 AND T12
FLUORESCENT FIXTURES AND TUBES.
GENERAL DEMOLITION NOTES
JOB NUMBER:
TH
E
US
E
OF
T
HE
SE
P
LA
NS
A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L B E
RE
ST
RI
CT
ED
T
O
TH
E
OR
IG
IN
AL
SI
TE
FO
R W
HI
CH
T
HE
Y W
ER
E
PR
EP
AR
ED
A
ND
P
UB
LIC
AT
IO
N
TH
ER
EO
F I
S E
XP
RE
SS
LY
LI
M
IT
ED
T
O
SU
CH
U
SE
. R
E-
US
E, R
EP
RO
DU
CT
IO
N, O R
PU
BL
IC
AT
IO
N
BY
A
NY
M
ET
HO
D, IN
W
HO
LE
O
R
IN
P
AR
T, IS
P
RO
HI
BI
TE
D.
T
IT
LE
T
O
TH
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
R
EM
AI
NS
W
IT
H
TH
E
EN
GI
NE
ER
W
IT
HO
UT
P
RE
JU
DI
CE
. V
IS
UA
L C
ON
TA
CT
W
IT
H
TH
ES
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L C
ON
ST
IT
UT
E
PR
IM
A
FA
CI
E
EV
ID
EN
CE
O F T
HE
A
CC
EP
TA
NC
E
OF
T
HE
SE
R
ES
TR
IC
TI
ON
S.
C
OL
EB
RE
IT
E
NG
IN
EE
RI
NG
, L
LC
D
BA
A
XI
OM
E
NG
IN
EE
RS
CD
C
W
IR
EL
ES
S B
LD
G
DATE: 10/11/2024
20240427
RE
ST
RO
OM
S R
EM
OD
EL
ST
AT
E
ST
BU
ILD
IN
G
SA
LE
M
OR
PERMIT SET 10/11/2024
BEND | EUGENE | MEDFORD
MONTEREY | NAPA | SANTA CRUZ
E N G I N E E R I N G
ELECTRICAL SCHEDULES
E002
LUMINAIRE SCHEDULE
TYPE DESCRIPTION / MOUNTING FINISH DRIVER/POWER SUPPLY LAMP(S)
INPUT POWER
MFG/CATALOG # NOTES
WATTS UNIT
S1 4' LINEAR DOWNLIGHT WHITE MVOLT, 0-10V DIMMING TO 10% 3500K, 3000LM, FLAT DIFFUSE LENS 23 W LITHONIA:
MODEL# CLX-L36-3000LM-SEF-FDL-MVOLT-GZ10-35K-80CRI VERIFY FINISH WITH CLIENT.
S2 2' LOW PROFILE LED WRAPAROUND STANDARD WHITE MVOLT, 0-10V DIMMING TO 10% 3500K, 800LM, CURVED SMOOTH LENS 8 W LITHONIA:
MODEL# BLWP2-8L-ADP-MVOLT-GZ10-LP835 VERIFY FINISH AND TRIM WITH CLIENT.
W1 2' RESTROOM VANITY FIXTURE BRONZE MVOLT, NON-DIMMING 3000K, 3500K, 4000K SELECTABLE
(3500K), 1725LM, ACRYLIC DIFFUSE LENS
17.5 W LITHONIA:
MODEL# FMVCSLS-12IN-MVOLT-30K35K40K-90CRI-BZ VERIFY FINISH WITH CLIENT.
NOTES:
1 THIS LUMINAIRE SCHEDULE IS NOT COMPLETE WITHOUT A COPY OF THE PROJECT MANUAL CONTAINING THE ELECTRICAL SPECIFICATIONS.
2 DIMMING CONTROL PROTOCOL (0-10VDC, LINE VOLTAGE, DALI, ETC.) COMPATIBLE WITH LIGHTING CONTROL SYSTEM AS SPECIFIED AND SHOWN ON DRAWINGS.
3 PROVIDE +/- 12 INCH ADJUSTABILITY IN AIRCRAFT CABLE LENGTH WHERE USED.
4 COORDINATE ALL CEILING TYPES WITH LUMINAIRE LOCATIONS PRIOR TO ORDERING LUMINAIRES. COORDINATE INSTALLATION WITH REFLECTED CEILING PLAN.
5 SPECIFIED MANUFACTURERS ARE APPROVED TO SUBMIT BID. INCLUSION DOES NOT RELIEVE MANUFACTURER FROM SUPPLYING PRODUCT AS DESCRIBED.
6 PROVIDE SUBMITTALS THAT INCLUDE THE LUMINAIRE, LAMP AND BALLAST INFORMATION OF EACH LUMINAIRE, WITH APPLICABLE OPTIONS CLEARLY CHECKED OR HIGHLIGHTED. SUBMITTALS NOT INCLUDING THIS INFORMATION WILL BE RETURNED AS REJECTED BY THE ENGINEER OF RECORD.
7 REMOTE BALLASTS/DRIVERS: UL LISTED FOR THEIR APPLICATION. BALLASTS/DRIVERS MARKED AS UL RECOGNIZED COMPONENT BUT NOT UL LISTED ARE SUBJECT TO REMOVAL AND REPLACEMENT AT NO COST TO OWNER.
8 PROVIDE COMMISSIONING OF THE LIGHTING AND LIGHTING CONTROLS IN ACCORDANCE WITH OREGON STATE LIGHTING COMMISSIONING REQUIREMENTS.
LOAD ANALYSIS:
(E) PANEL MDP
(250A, 480/277V, 3P, 4W)
LOAD REMOVED: 60VA+3.18KVA+11KVA
LOAD ADDED:
.11KVA+2.18KVA(L)+4KVA(SUB-M)+1.7KVA(M)
TOTAL NEW LOAD: -6.25KVA (-7.5A@480V/3P)
(E)PANEL L
(250A, 208/120V, 3P, 4W)
LOAD REMOVED: 3.18KVA+11KVA(SUB-M)
LOAD ADDED: 2.18KVA+1.7KVA(M)+4KVA(SUB-M)
TOTAL NEW LOAD: -6.3KVA(-17.5A@208V/3P)
(E)PANEL M
(250A, 208/120V, 3P, 4W)
LOAD REMOVED 11KVA(SUB-M)
LOAD ADDED: 4KVA(SUB-M)+1.7KVA
TOTAL NEW LOAD: -5.3KVA (-14.72A@208V/3P)
(E)PANEL SUB-M
(60A, 208/120V, 3P, 4W)
LOAD REMOVED: 11KVA
LOAD ADDED: 4KVA
TOTAL NEW LOAD: -7KVA (-19.4A@208V/3P)
NOTE: LOADS BEING REMOVED ARE BASED ON
NAMEPLATE DATA OF EQUIPMENT.
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
ITEM DESCRIPTION LOCATION VOLTS /
PHASE LOAD MCA DISCONNECT WIRE /
CONDUIT NOTES
EF-1 EXHAUST FAN RESTROOM 102 120/1 0.01 KW 202 2
EF-2 EXHAUST FAN RESTROOM 103 120/1 0.01 KW 202 2
HP-1 HEAT PUMP EXTERIOR WALL 208/1 1.7 KW 10 30A/2P 202
FC-1 FAN COIL RR 102 - - 1
HP-2 HEAT PUMP EXTERIOR WALL 208/1 1.7 KW 10 30A/2P 202
FC-2 FAN COIL RR 103 - 1
EWH-1 ELECTRIC WATER HEATER HALL 101 208/1 4.0 KW 30A/2P 302
GENERAL MECHANICAL EQUIPMENT CONNECTION SCHEDULE NOTES:
A. THE ABOVE INFORMATION IS FOR A SPECIFIC MANUFACTURER. ACTUAL MANUFACTURER FOR EQUIPMENT MAY BE DIFFERENT. COORDINATE WITH MECHANICAL EQUIPMENT SUBMITTALS FOR LOADS AND OVER CURRENT PROTECTION REQUIREMENTS PRIOR TO INSTALLATION OF WIRING.
B. MOCP = MAXIMUM OVER CURRENT PROTECTION
MCA = MINIMUM CIRCUIT AMPACITY
C. PROVIDE DISCONNECTING MEANS FOR EACH ITEM OF EQUIPMENT LISTED IN THE SCHEDULE ABOVE, EXCEPT AS SPECIFICALLY NOTED OTHERWISE IN
SCHEDULE NOTES, BELOW.
MECHANICAL EQUIPMENT CONNECTION SCHEDULE NOTES:
1 INDOOR UNIT TO BE PROWERED BY THE OUTDOOR UNIT; PROVIDE 1" CONDUIT FOR CONNECTION BETWEEN INDOOR AND OUTDOOR UNIT. CONTRACTOR
TO PROVIDE ALL WIRING PER MANUFACTURER'S RECOMMENDATIONS.
2 PROVIDE MOTOR RATED TOGGLE SWITCH TO SERVE AS DISCONNECT.
WIRE / CONDUIT SCHEDULE
202 2 #12 CU, 1 #12 CU GND., IN 3/4" C.
302 2 #10 CU, 1 #10 CU GND., IN 3/4" C.
(E) PANEL 'L'
LOCATION: ELECTRICAL ROOM VOLTAGE: 208/120V 3PH 4W
SUPPLY FROM: (E) MDP TRANSFORMER MAINS RATING: 250A MCB
MOUNTING: SURFACE BUSSING RATING: 250 A
ENCLOSURE: NEMA 1 K.A.I.C. RATING: 22 KAIC
FEED-THRU LUGS: NO
NOTE: ALL BREAKERS, CIRCUITS AND LOADS ARE EXISTING UNLESS OTHERWISE NOTED
CKT CIRCUIT DESCRIPTION LC NOTE
TRIP
(A) POLE
CONNECTED LOAD (VA)
POLE
TRIP
(A) NOTE LC CIRCUIT DESCRIPTION CKTA B C
1 PANEL 'M' 100 3 2 30 2ND FLOOR WATER HEATER 2
3 - - - - - - 4
5 - - - 1 20 EXISTING LOAD 6
7 RECEPT - SOUTH WALL RADIO ROOM 20 1 1 20 EXISTING LOAD 8
9 RECEPT - BAY 3 20 1 1 20 EXISTING LOAD 10
11 RECEPT - WIRELESS CAGE 20 1 1 20 EXISTING LOAD 12
13 RECEPT - SMOKE SHACK 20 1 1 20 EXISTING LOAD 14
15 RECEPT - WIRELESS CAGE AREA BENCH 20 1 1 20 EXISTING LOAD 16
17 (N)RECEPT - HALL 1 20 1 180 1 20 EXISTING LOAD 18
19 LTG - BATHROOM 20 1 2 20 WIRELESS ARGUS-1 20
21 LTG - BATHROOM 20 1 - - - 22
23 LTG - BATHROOM 20 1 2 20 WIRELESS ARGUS-2 24
25 (N)HP-1, FC-2 1 20 2 915 - - - 26
27 - - - - 915 2 20 WIRELESS ARGUS-3 28
29 BATHROOM HEATER 40 2 - - - 30
31 - - - 2 20 WIRELESS ARGUS-4 32
33 BATHROOM HEATER 40 2 - - - 34
35 - - - 2 50 PANEL 'B' 36
37 BATHROOM HEATER 30 2 - - - 38
39 - - - 2 60 PANEL 'T' 40
41 LTG CONTROL - EXTERIOR 20 1 - - - 42
TOTAL LOAD (VA): 915 915 180
TOTAL AMPS: 3 3 1
NOTES:
1. DISCONNECT EXISTING CIRCUIT AND CONNECT NEW CIRCUIT TO EXISTING BREAKER.
2.
3.
(E) PANEL 'SUB-M'
LOCATION: ELECTRICAL ROOM VOLTAGE: 208/120V 1PH 3W
SUPPLY FROM: (E) PANEL 'M' MAINS RATING: 60A MCB
MOUNTING: SURFACE BUSSING RATING: 60 A
ENCLOSURE: NEMA 1 K.A.I.C. RATING: 10 KAIC
FEED-THRU LUGS: NO
NOTE: ALL BREAKERS, CIRCUITS AND LOADS ARE EXISTING UNLESS OTHERWISE NOTED
CKT CIRCUIT DESCRIPTION LC NOTE
TRIP
(A) POLE
CONNECTED LOAD (VA)
POLE
TRIP
(A) NOTE LC CIRCUIT DESCRIPTION CKTA C
1 MAIN BREAKER 60 2 -- -- BUSSED PROVISIONS FOR MCB 2
3 - - - -- -- BUSSED PROVISIONS FOR MCB 4
5 BAY 5 RACK 20 1 1 20 EXISTING LOAD 6
7 BAY 4 RACK 20 1 1 15 EXISTING LOAD/EXISTING LOAD TANDEM BRKR 8
9 BAY 3 RACK 20 1 1 15 EXISTING LOAD/EXISTING LOAD TANDEM BRKR10
11 BAY 2 RACK 20 1 1 20 RECEPT - CEILING OVER WORKBENCH 12
13 RECEPT - INVERTER 20 1 1 20 RECEPT - CEILING OVER WORKBENCH 14
15 PORTABLE LAB 20 1 1 15 EXISTING LOAD/EXISTING LOAD TANDEM BRKR16
17 EXISTING LOAD 30 1 1 20 RECEPT - CEILING OVER WORKBENCH 18
19 EXISTING LOAD 20 1 2,000 2 30 1 (N)ELECTRIC WATER HEATER EWH-1 20
21 EXISTING LOAD 20 1 2,000 - - - - 22
23 BUSSED PROVISIONS -- -- -- -- BUSSED PROVISIONS 24
TOTAL LOAD (VA): 2,000 2,000
TOTAL AMPS: 10 10
NOTES:
1. EXISTING 60A/2P BREAKER TO BE REPLACED WITH NEW 30A/2P BREAKER.
2.
3.
(E) PANEL 'M'
LOCATION: ELECTRICAL ROOM VOLTAGE: 208/120V 3PH 4W
SUPPLY FROM: (E) PANEL 'M' MAINS RATING: 100 MCB
MOUNTING: SURFACE BUSSING RATING: 250 A
ENCLOSURE: NEMA 1 K.A.I.C. RATING: 22 KAIC
FEED-THRU LUGS: NO
NOTE: ALL BREAKERS, CIRCUITS AND LOADS ARE EXISTING UNLESS OTHERWISE NOTED
CKT CIRCUIT DESCRIPTION LC NOTE
TRIP
(A) POLE
CONNECTED LOAD (VA)
POLE
TRIP
(A) NOTE LC CIRCUIT DESCRIPTION CKTA B C
1 SPLIT UNIT 25 2 2 60 FURNACE 2
3 - - - -- -- - 4
5 SPLIT UNIT 25 2 1 20 GEN RECEPT. 6
7 - - - 1 20 GEN RECEPT. 8
9 SPLIT UNIT 25 2 1 20 GEN RECEPT. 10
11 - - - 1 20 GEN RECEPT. 12
13 PANEL 'SUB-M' 60 2 1 20 GEN RECEPT. 14
15 - - - 1 20 GEN RECEPT. 16
17 HP-2, FC-2 1 20 2 832 1 20 GEN RECEPT. 18
19 - - - - 832 1 20 GEN RECEPT. 20
21 BUSSED PROVISIONS -- -- 1 20 RECEPT - MDF ROOM 22
23 RECEPT - ADJACENT WALL 20 1 1 20 MAV LENS 24
25 MICROWAVE - RADIO ROOM 20 1 1 20 RECEPT - RESTROOM 26
27 SPARE 20 1 1 20 GEN RECEPT. 28
29 SPARE 20 1 1 20 RECEPT - SOUTH WORKBENCH 30
TOTAL LOAD (VA): 2,832 0 832
TOTAL AMPS: 8 0 2
NOTES:
1. PROVIDE AND INSTALL NEW BREAKER.
2.
3.
JOB NUMBER:
TH
E
US
E
OF
T
HE
SE
P
LA
NS
A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L B E
RE
ST
RI
CT
ED
T
O
TH
E
OR
IG
IN
AL
SI
TE
FO
R W
HI
CH
T
HE
Y W
ER
E
PR
EP
AR
ED
A
ND
P
UB
LIC
AT
IO
N
TH
ER
EO
F I
S E
XP
RE
SS
LY
LI
M
IT
ED
T
O
SU
CH
U
SE
. R
E-
US
E, R
EP
RO
DU
CT
IO
N, O R
PU
BL
IC
AT
IO
N
BY
A
NY
M
ET
HO
D, IN
W
HO
LE
O
R
IN
P
AR
T, IS
P
RO
HI
BI
TE
D.
T
IT
LE
T
O
TH
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
R
EM
AI
NS
W
IT
H
TH
E
EN
GI
NE
ER
W
IT
HO
UT
P
RE
JU
DI
CE
. V
IS
UA
L C
ON
TA
CT
W
IT
H
TH
ES
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L C
ON
ST
IT
UT
E
PR
IM
A
FA
CI
E
EV
ID
EN
CE
O F T
HE
A
CC
EP
TA
NC
E
OF
T
HE
SE
R
ES
TR
IC
TI
ON
S.
C
OL
EB
RE
IT
E
NG
IN
EE
RI
NG
, L
LC
D
BA
A
XI
OM
E
NG
IN
EE
RS
CD
C
W
IR
EL
ES
S B
LD
G
DATE: 10/11/2024
20240427
RE
ST
RO
OM
S R
EM
OD
EL
ST
AT
E
ST
BU
ILD
IN
G
SA
LE
M
OR
PERMIT SET 10/11/2024
BEND | EUGENE | MEDFORD
MONTEREY | NAPA | SANTA CRUZ
E N G I N E E R I N G
ELECTRICAL SPECIFICATIONS
E003
E200
E200
E300
E300
SCOPE OF WORK
SHEET NUMBER
REVISION SCHEDULE
JOB NUMBER:
TH
E
US
E
OF
T
HE
SE
P
LA
NS
A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L B E
RE
ST
RI
CT
ED
T
O
TH
E
OR
IG
IN
AL
SI
TE
FO
R W
HI
CH
T
HE
Y W
ER
E
PR
EP
AR
ED
A
ND
P
UB
LIC
AT
IO
N
TH
ER
EO
F I
S E
XP
RE
SS
LY
LI
M
IT
ED
T
O
SU
CH
U
SE
. R
E-
US
E, R
EP
RO
DU
CT
IO
N, O R
PU
BL
IC
AT
IO
N
BY
A
NY
M
ET
HO
D, IN
W
HO
LE
O
R
IN
P
AR
T, IS
P
RO
HI
BI
TE
D.
T
IT
LE
T
O
TH
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
R
EM
AI
NS
W
IT
H
TH
E
EN
GI
NE
ER
W
IT
HO
UT
P
RE
JU
DI
CE
. V
IS
UA
L C
ON
TA
CT
W
IT
H
TH
ES
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L C
ON
ST
IT
UT
E
PR
IM
A
FA
CI
E
EV
ID
EN
CE
O F T
HE
A
CC
EP
TA
NC
E
OF
T
HE
SE
R
ES
TR
IC
TI
ON
S.
C
OL
EB
RE
IT
E
NG
IN
EE
RI
NG
, L
LC
D
BA
A
XI
OM
E
NG
IN
EE
RS
CD
C
W
IR
EL
ES
S B
LD
G
DATE: 10/11/2024
20240427
RE
ST
RO
OM
S R
EM
OD
EL
ST
AT
E
ST
BU
ILD
IN
G
SA
LE
M
OR
PERMIT SET 10/11/2024
BEND | EUGENE | MEDFORD
MONTEREY | NAPA | SANTA CRUZ
E N G I N E E R I N G
ELECTRICAL
OVERALL FLOOR PLAN
E100
NORTH
SCALE:
OVERALL FLOOR PLAN - ELECTRICAL
3/16" = 1'-0"
(E) DIST
PANEL 'MDP'
(E) ATS
(E) PANEL 'L-10'
(E) XFMR
(E) PANEL 'SUB-M'
(E) PANEL 'L'
(E) PANEL 'M'
S2
S2
W1
W1
S
SS
S S1
S1
(E) DIST
PANEL 'MDP'
(E) ATS
(E) PANEL 'L-10'
(E) XFMR
(E) PANEL 'SUB-M'
(E) PANEL 'L'
(E) PANEL 'M'
SHEET NUMBER
REVISION SCHEDULE
JOB NUMBER:
TH
E
US
E
OF
T
HE
SE
P
LA
NS
A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L B E
RE
ST
RI
CT
ED
T
O
TH
E
OR
IG
IN
AL
SI
TE
FO
R W
HI
CH
T
HE
Y W
ER
E
PR
EP
AR
ED
A
ND
P
UB
LIC
AT
IO
N
TH
ER
EO
F I
S E
XP
RE
SS
LY
LI
M
IT
ED
T
O
SU
CH
U
SE
. R
E-
US
E, R
EP
RO
DU
CT
IO
N, O R
PU
BL
IC
AT
IO
N
BY
A
NY
M
ET
HO
D, IN
W
HO
LE
O
R
IN
P
AR
T, IS
P
RO
HI
BI
TE
D.
T
IT
LE
T
O
TH
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
R
EM
AI
NS
W
IT
H
TH
E
EN
GI
NE
ER
W
IT
HO
UT
P
RE
JU
DI
CE
. V
IS
UA
L C
ON
TA
CT
W
IT
H
TH
ES
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L C
ON
ST
IT
UT
E
PR
IM
A
FA
CI
E
EV
ID
EN
CE
O F T
HE
A
CC
EP
TA
NC
E
OF
T
HE
SE
R
ES
TR
IC
TI
ON
S.
C
OL
EB
RE
IT
E
NG
IN
EE
RI
NG
, L
LC
D
BA
A
XI
OM
E
NG
IN
EE
RS
CD
C
W
IR
EL
ES
S B
LD
G
DATE: 10/11/2024
20240427
RE
ST
RO
OM
S R
EM
OD
EL
ST
AT
E
ST
BU
ILD
IN
G
SA
LE
M
OR
PERMIT SET 10/11/2024
BEND | EUGENE | MEDFORD
MONTEREY | NAPA | SANTA CRUZ
E N G I N E E R I N G
ELECTRICAL
ENLARGED LIGHTING PLANS
E200
DEMO LIGHTING PLAN - ELECTRICAL
1/4" = 1'-0"E200
1NEW LIGHTING PLAN - ELECTRICAL
1/4" = 1'-0"E200
1. EXISTING LIGHTING AND CONTROLS IN THIS SPACE TO REMAIN.
2. NEW LIGHTING TO CONNECT TO EXISTING CIRCUIT MADE AVAILABLE FROM DEMOLITION.
EXTEND AND CONNECT TO NEW LIGHTING FIXTURES. FIXTURE TO CONNECT TO NEW
CONTROLS IN SPACE.
3. NEW LIGHTING TO CONNECT TO EXISTING CIRCUIT MADE AVAILABLE FROM DEMOLITION.
EXTEND AND CONNECT TO NEW LIGHTING FIXTURES. FIXTURE TO CONNECT TO EXISTING
CONTROLS IN SPACE.
PLAN KEYNOTE - NEW WORK
1. EXISTING LIGHTING AND CONTROLS IN THIS SPACE TO REMAIN.
2. EXISTING LIGHTING AND CONTROLS IN THIS SPACE TO BE REMOVED. EXISTING CIRCUIT TO BE
REUSED FOR NEW WORK. EXTEND AND CONNECT TO NEW LIGHTING FIXTURES.
3. EXISTING LIGHTING IN THIS SPACE TO BE REMOVED. CONTROLS TO BE REUSED FOR NEW
FIXTURES. EXISTING CIRCUIT TO BE REUSED FOR NEW WORK. EXTEND AND CONNECT TO NEW
LIGHTING FIXTURES.
PLAN KEYNOTE - DEMOLITION
(E) DIST
PANEL 'MDP'
(E) ATS
(E) PANEL 'L-10'
(E) XFMR
(E) PANEL 'SUB-M'
(E) PANEL 'L'
(E) PANEL 'M'
AG
L-17.
AG
L-17.
G �
#10
L-25,27.
HP-2
HP-1
SM
S
M
EF-1
FC-1
EF-2
EWH-1
FC-2
SUB-M-20,22
L-17.
M-17,19.
(E) DIST
PANEL 'MDP'
(E) ATS
(E) PANEL 'L-10'
(E) XFMR
(E) PANEL 'SUB-M'
(E) PANEL 'L'
(E) PANEL 'M'
(X)
(X)
(X)
SHEET NUMBER
REVISION SCHEDULE
JOB NUMBER:
TH
E
US
E
OF
T
HE
SE
P
LA
NS
A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L B E
RE
ST
RI
CT
ED
T
O
TH
E
OR
IG
IN
AL
SI
TE
FO
R W
HI
CH
T
HE
Y W
ER
E
PR
EP
AR
ED
A
ND
P
UB
LIC
AT
IO
N
TH
ER
EO
F I
S E
XP
RE
SS
LY
LI
M
IT
ED
T
O
SU
CH
U
SE
. R
E-
US
E, R
EP
RO
DU
CT
IO
N, O R
PU
BL
IC
AT
IO
N
BY
A
NY
M
ET
HO
D, IN
W
HO
LE
O
R
IN
P
AR
T, IS
P
RO
HI
BI
TE
D.
T
IT
LE
T
O
TH
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
R
EM
AI
NS
W
IT
H
TH
E
EN
GI
NE
ER
W
IT
HO
UT
P
RE
JU
DI
CE
. V
IS
UA
L C
ON
TA
CT
W
IT
H
TH
ES
E
PL
AN
S A
ND
SP
EC
IF
IC
AT
IO
NS
SH
AL
L C
ON
ST
IT
UT
E
PR
IM
A
FA
CI
E
EV
ID
EN
CE
O F T
HE
A
CC
EP
TA
NC
E
OF
T
HE
SE
R
ES
TR
IC
TI
ON
S.
C
OL
EB
RE
IT
E
NG
IN
EE
RI
NG
, L
LC
D
BA
A
XI
OM
E
NG
IN
EE
RS
CD
C
W
IR
EL
ES
S B
LD
G
DATE: 10/11/2024
20240427
RE
ST
RO
OM
S R
EM
OD
EL
ST
AT
E
ST
BU
ILD
IN
G
SA
LE
M
OR
PERMIT SET 10/11/2024
BEND | EUGENE | MEDFORD
MONTEREY | NAPA | SANTA CRUZ
E N G I N E E R I N G
ELECTRICAL
ENLARGED POWER PLANS
E300
DEMO POWER PLAN - ELECTRICAL
1/4" = 1'-0"E300
1NEW POWER PLAN - ELECTRICAL
1/4" = 1'-0"E300
1. ALL EXISTING WIRING DEVICES IN THIS SPACE TO REMAIN UNLESS OTHERWISE
NOTED.
2. NEW EXHAUST FANS TO BE CONNECTED TO EXISTING CIRCUIT MADE AVAILABLE
FROM DEMOLITION. EXTEND AND CONNECT ALL ASSOCIATED WIRING TO NEW
EXHAUST FANS.
3. INDOOR FAN COIL UNIT POWERED BY OUTDOOR HEAT PUMP.
PLAN KEYNOTE - NEW WORK
1. ALL EXISTING WIRING DEVICES IN THIS SPACE TO REMAIN UNLESS OTHERWISE
NOTED.
2. EXISTING WIRING DEVICES ALONG THIS WALL TO BE DISCONNECTED AND RELOCATED
IN SAME LOCATION ON NEW WALL. EXTEND ALL ASSOCIATED WIRING TO NEW
LOCATION.
3. ALL EXISTING WIRING DEVICES IN THIS SPACE TO BE REMOVED. EXISTING CIRCUITS
TO BE REUSED FOR NEW WORK. SEE NEW WORK PLAN FOR ADDITIONAL
INFORMATION.
4. EXISTING UNIT HEATER TO BE DISCONNECTED AND REMOVED. EXISTING CIRCUIT TO
BE REUSED FOR NEW MECHANICAL EQUIPMENT. SEE NEW WORK PLAN FOR
ADDITIONAL INFORMATION.
5. EXISTING EXHAUST FAN TO BE DISCONNECTED AND REMOVED. CIRCUIT TO BE
REUSED FOR NEW EXHAUST FANS. EXTEND AND RECONNECT TO NEW EXHAUST FAN
LOCATIONS.
6. EXISTING INSTANT WATER HEATER TO BE DISCONNECTED AND REMOVED. EXISTING
CIRCUIT TO BE REUSED FOR NEW WATER HEATER. SEE NEW WORK PLAN FOR
ADDITIONAL INFORMATION.
PLAN KEYNOTE - DEMOLITION
| Sheets and Views |
| ELEC-E001-E001 - LEGEND AND NOTES |
| ELEC-E002-E001 - LEGEND AND NOTES |
| ELEC-E003-E001 - LEGEND AND NOTES |
| ELEC-E100-E001 - LEGEND AND NOTES |
| ELEC-E200-E001 - LEGEND AND NOTES |
| ELEC-E300-E001 - LEGEND AND NOTES |
| 2024-10-11T08:59:01-0700 | |
| John Pride |
| 2024-10-11T08:59:01-0700 | |
| John Pride |
| 2024-10-11T08:59:02-0700 | |
| John Pride |
| 2024-10-11T08:59:02-0700 | |
| John Pride |
| 2024-10-11T08:59:02-0700 | |
| John Pride |
| 2024-10-11T08:59:03-0700 | |
| John Pride |
File details come from the government source that posted it. Updated .